1 UNIVERSITI TEKNIKAL MALAYSIA MELAKA DESIGNING AIR FILTRATION TEST RIG (PROTOTYPE) IN EVALUATE EFFICIENCY OF HVAC FILTER This report submitted in accordance with requirement of the Universiti Teknikal Malaysia Melaka (UTeM) for the Bachelor Degree of Mechanical Engineering Technology (Refrigeration and Air Conditioning System) with Honours by AHMAD SHAFIQ BIN ABDUL GANI B FACULTY OF ENGINEERING TECHNOLOGY 2016

2 DECLRATTION I hereby, declared this report entitled Designing air filtration test rig (prototype) in evaluate efficiency of HVAC filter is the results of my own research except as cited in references Signature : Author s name : AHMAD SHAFIQ BIN ABDUL GANI Date :

3 APPROVAL This report is submitted to the Faculty of Engineering Technology of UTeM as a partial fulfillment of the requirements for the degree of Bachelor of Mechanical Engineering Technology (Refrigeration and air conditioning system) with Honours. The member of the supervisory is as follow.. (Amir Abdullah bin Muhamad Damanhuri)

4 ABSTRAK Kawalan pencemaran telah menjadi isu semasa dalam menyediakan kualiti udara yang bersih. Penapis udara bertindak sebagai pertahanan utama terhadap pencemaran melindungi komponen pemanasan, pengudaraan dan penghawa dingin (HVAC) dari kotoran dan seterusnya membekalkan udara bersih kepada pengguna. Kecekapan penapis udara ditakrifkan bagaimana penapis itu membersihkan udara dengan menapis habuk-habuk (PM). Kejatuhan tekanan adalah prestasi utama yang menjadi penunjuk kepada penapis HVAC. Oleh itu, ia boleh mengukur penggunaan tenaga dengan meramalkan rintangan aliran udara penapis. Rintangan aliran udara yang rendah adalah salah satu kaedah yang paling mudah untuk mengurangkan kos tenaga dimana system motor HVAC tidak perlu bekerja keras untuk mengalirkan aliran udara. Dalam erti kata lain, ujian penapis adalah salah satu kaedah yang terbaik untuk mengukur prestasi penapis udara. Objektif kajian ini adalah untuk mereka bentuk prototaip pelantar ujian penapis udara HVAC di mana ia boleh mengukur prestasi penapis udara berdasarkan parameter utama. Kajian ini terbahagi kepada beberapa peringkat iaitu persediaan dan penyiasatan pengiraan parameter kecekapan penapis, proses rekaan dan proses pembuatan pelantar ujian. Rekabentuk pelantar ujian penapis udara adalah bentuk U dengan ukuran 20 inci x 20 inci dan untuk bahagian penapis adalah 24 inci x 24 inci. Spesifikasi ujian pelantar adalah reka bentuk untuk memenuhi standard ASHARE52.2 dan EN779 yang pelbagai kadar aliran udara adalah dalam lingkungan 600 m³/h sehingga 6000 m³/h. Pada akhir projek, prototaip ini seperti yang di jangka di mana ia boleh digunakan seperti pelantar ujian penapis udara yang sebenar untuk membuat ujian individu terutamanya bagi kontraktor bangunan. i

5 ABSTRACT Contaminant control have become current issue in providing safe air quality. Air filter perform as the primary defense against pollutants to protect heating ventilation air conditioning (HVAC) components from dust thus supply clean air to the occupants. The efficiency of air filter defines how well the filter clean the air by removing the particulate matter (PM). Pressure drop are the primary performance indicator for HVAC filter, hence could measure energy consumption by predicting air flow resistance of the filter. Low air flow resistance is one of the easiest method to reduce energy cost, as HVAC system motor does not have to work hard to deliver air flow. In other words, filter testing is one of the best method to measure performance of air filter. The objective of this study is to design the HVAC air filter test rig in evaluate efficiency of air filter based on set key parameter. This study divide into several stage that are preparation and investigation of filter efficiency parameter, calculation, designing process and development of the test rig. Design of filter test rig is U shape with dimension 20 inch x 20 inch and for filter section is 24 inch x 24 inch. The test rig specification are design to meet ASHARE52.2 and EN779 standard which range of air flow rate is 600 m³/h to 6000 m³/h. For the end of this project, this prototype as expected can be used as an actual air filter test rig to make individual test especially for the contractor. ii

6 DEDICATION I dedicate this project to Allah Almighty my creator, my strong pillar, my source of inspiration, wisdom, knowledge and understanding. He has been the source of my strength throughout this program and on His wings only have I soared. I also dedicate this work to my family who has encouraged me all the way and whose encouragement has made sure that I give it all it takes to finish that which I have started. This project also is especially dedicated to my supervisor, for his willingness to guide me to the success of this project for my degree. iii

7 ACKNOWLEDGEMENT First of all, I would like to express my gratitude to my supervisor Mr. Amir Abdullah bin Muhamad Damanhuri for his mindful supervision and guidance that have guided me in accomplishing this project. His wide knowledge in this studied area has contributed in making this project succeed. For my Co-supervisor Mrs. Siti Nor Ain Binti Mokhtar, no words that I can say other than thank you because a lot of experienced that I have during through this project. Besides that, I am grateful for having my housemates and beloved friend as my companion along the way while working on this project. They have given me the greatest support right from the beginning and it has given me the courage to move on when not capable to through more further while developing this project. Finally, thanks a lot to my family who have been supporting and giving me endless encouragement. Without the spirit and support that I received throughout this path, possibility these projects will not be successfully completed. iv

8 TABLE OF CONTENT Abstrak Abstract Dedication Acknowledgement Table of contents List of Tables List of Figures List Abbreviations, Symbols and Nomenclatures i ii iii iv v viii ix xii CHAPTER 1: INTRODUCTION 1.1 Project Background Problem Statement Objective Scope 3 CHAPTER 2: LITERATURE REVIEW 2.0 Introduction Air filter Type of Air filter Air Filter Classification Indoor Air Quality The important of air filtration to Indoor Air Quality and human Health Filter Test Rig Fans Fans Selection Acrylic 12 v

9 2.5.1 Acrylic characteristic Global Standard for air filter testing Filter Test Rig Standard ISO/TS-21220: ASHRAE Standard Europe standard Comparison between ASHRAE and Europe Standard Test procedure Filter classification Final pressure drop 23 CHAPTER 3: METHODOLOGY 3.0 Introduction Preparation and investigation Calculation Designing filter test rig Product specification (Material and Equipment) Concept scoring Detailed design Design development using SolidWorks Data Taken Procedure 45 CHAPTER 4: RESULT & DISCUSSION 4.0 Introduction Design result Fabrication (prototype development) Scribing and marking Cutting Drilling Finishing Create and installation damper 51 vi

10 4.2.6 Making a table trolley Installation wire to fan Joining and installation Closing gap Filter installation Development result Data validation and energy demand calculation Energy demand calculation Comparison between HVAC Filter test rig, ASHRAE 52.2 and EN 779 Standard 63 CHAPTER 5: CONCLUSION AND RECOMMENDATION 5.0 Introduction Summary of the project Achievement of project activities Future Development 66 REFERENCE 68 APPENDICES 71 vii

11 LIST OF TABLES 2.1 MERV categories The type of contaminant that will growth in their size their applications The classification of air filters according to EN 779: The Comparison of ASHRAE52.1, ASHRAE 52.2 and EN 779: The result and the limit of the each standard Dimensions and parts drawing before assembly using Solidworks Average data for air velocity and air flow rate when fan at 800 CFM Average data of amount of dust and pressure when fan at 800 CFM Average data of temperature and humidity when fan at 800 CFM Air flow rate data with different speed Comparison between HVAC Filter Test Rig, ASHRAE52.2 and EN viii

12 LIST OF FIGURES 2.1 AHU compartment Type of Air filter The typical minimum efficiency curve Filter test rig based on EN 779 and ASHRAE 52.2 standard The schematic diagram of test rig based on EN 779 standard The dimensions of the test rig based on EN 779 standard Acrylic sheet Air filter Aluminium sheet Axial fan Jig saw Acrylic glue Sandpaper was used File Table at the lab Hand drill Screw and screw driver square hollow iron bar Regulator pin plug Pitot tube 36 ix

13 3.16 Anemometer Tachometer LEV monitoring device Concept scoring of this project Schematic diagram of filter test rig design Filter test rig drawing design in 2D after assembly Each side view of 2D drawing Flow chart process HVAC filter test rig prototype full 3D drawing Marking process Cutting acrylic using jigsaw Making a hole using hand drill Finishing process Acrylic done attached with holder Making a table trolley process Wire installation process Assembly process Closing gap Air filter after installation HVAC filter test rig prototype Point of data taken Relationship between velocity and air flow rate graph Relationship between amount of dust and pressure graph Relationship between temperature and humidity graph 60 x

14 4.17 Relationship between fan speed and air flow rate graph 61 xi

15 LIST OF ABBREVIATIONS, SYMBOLS AND NOMENCLATURE A - Ampere ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning AHU - Air Handling Unit CAD - Computer Assisted Design CCWS - Central Chiller Water System CEN - European Committee for Standardization CFM - Cubic Feet Per Minute DEHS - Debian External Health Status EN - European Standard EUROVENT - Europe s Industry Association for Indoor Climate HEPA - High Efficiency Particulate Arrestance HVAC - Heating, Ventilation and Air-Conditioning IAQ - Indoor Air Quality ISO - International Standard Organization In.w.g - Inch Water Gauge MERV - Minimum Efficiency Reporting Value mm - milimetre m³/h - Meter cube per hour m/s - Meter per second PM - Particulate Matter Pa - Pascal SARS - Severe Acute Respiratory Syndrome TES - Thermal Energy Storage F - Degree Fahrenheit xii

16 µm - micrometre - Less Than - More Than xiii

17 CHAPTER 1 INTRODUCTION 1.1 Project Background Air-Conditioning is a system where it supply cool air, fresh air and provide thermal comfort required to the conditioned space (Viswambharan, Patidar, & Saxena, 2014). There are four main components of air-conditioning system which are compressor, condenser, evaporator and expansion valve. For large air-conditioning system usually use air handling unit (AHU) as a device to contribute the cool air to the conditioned space. To provide thermal comfort in required spaced AHU system also have their main components such as cooling and heating equipment, humidifier, air filter and fan. Each components has their importance function for the system. For example is air filter. The function of air filter is to avoid contaminant and provide clean to the occupants or the conditioned space (Lyngby et al., 2015). Besides that, the air filter is also important in air conditioning systems where it can improve the quality of indoor air in the condition space. Besides that, air filter also can prevent occupants from suffering health diseases affected from breathing air currently polluted. Pollution control has become an issue of great concern. Therefore, the air filter is a very important agent for the distribution of clean air. Air filter perform as the primary defences against pollutants to protect heating ventilation air conditioning (HVAC) components from dust thus supply clean air to the occupants (Berbari, Shakkour, & Hashem, 2007). To supply clean air, the air filter must be kept in pristine condition and free from microorganisms that can cause illness to the residents of the surrounding area. Each filter will have its own life expectancy and user must to know how long air filter can be used. 1

18 Many air filter test rig which has been produced nowadays according to the standards appropriate to the size of the air filter and the pressure drop required. The lower the pressure drop the less energy required for running the system. The standard used is ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers) standard and Europe standard. For ASHRAE, Standard 52.2 is a standard that makes reference while Europe Standard is used EN779 as the reference. The both standard take ISO as their guidelines to develop a filter test rig and each parameters are taken from that ISO. Besides that, this standard also constantly updated for several years. The content of this standard will be a signpost to complete this air filtration test. Therefore, the existence of this standard is extremely important to the industry as well as universities in researching the substances or equipment that want to be tested, simulation or as the project research. 1.2 Problem Statement Nowadays, we always have a problem with life expectancy of the HVAC air filter, ways to enhance the efficiency and performance of typical control contaminant filter classes (Bennett, 2012). The user must be difficult to predict the usability of an air filter used. Therefore, the importance of the organization designing the air filtration test rig to evaluate the effectiveness of an air filter especially HVAC filter to predict the duration of its use. We often forget that each air filter should be checked with the periodic time. Therefore, long dirt suspended on the air filter should be cleaned to produce good air quality. With a filter of this rig, it can monitor the life expectancy of the air filter. Besides that, the building owner or contractor can estimate lifecycles air filter where it can still be use either to replace at the same time it still can be used. It will lead to saving the cost. Before making a test rig some things need to be addressed such as the size of the ducting, the size of the air filter and the air flow required in the test rig system. The design will be a small scale prototype, means that is for test individual filter. From there we can save the space to place it. Besides that, it also can saving the energy demand. 2

19 1.3 Objective In this study, there are a number of targets to be given full attention in order to achieve the objectives. Therefore, the following below are objectives of this project. 1. To design HVAC filter test rig prototype that can measured performance of air filter refer to ASHRAE52.2 and EN779 standard. 2. To fabricate and develop HVAC filter test rig prototype to meet design scale of single air filter used in common market which is 24 inch x 24 inch. 1.4 Scope This research will focus on designing and develop prototype of the air filtration test rig in evaluate efficiency of HVAC filters. Several scope have been selected to this project and only equipment that will be aim which the type of air filter only washable furnace filter (primary and secondary filter). The design required for two air filters which are pre pleated and pocket bag filter. The size of that air filter only 24 inch x 24 inch where the standard size for commonly used in AHU. For the parameters that will measured in this project which are the particle size where it just 0.3 μm until 10.0 μm and the actual air flow rate for the fan is 800 CFM. Besides that, for standard static pressure 0.2 to 0.4 inch per water gauge per 100 feet where it for the usually standard industry using. 3

20 CHAPTER 2 LITERATURE REVIEW 2.0 Introduction This chapter will focus on the theory and terms mainly related to this research, which is about how to designing air filtration test rig, evaluate its efficiency and its relationship with indoor air quality. The sources of theory are from previous research, related articles and from the global standard. This chapter aim to give a better understanding about this research and to give strong evidence, support and reasons why this research should be done. Lately, there is numerous studies have been related to the level of indoor air quality (IAQ) and its effect on human health, therefore this study focusing on the air filter test rig design and evaluate its efficiency. Thus, this research will aim to the HVAC filter at the air handling unit (AHU). Air cooling is a system where it cools the refrigerant and cooling medium of water and sent away to be cooled. There are a lot of cooling system used at present, especially in industries that busy which are a central chiller water system (CCWS), Thermal energy storage (TES) and hybrid evaporative cooling system. Central chiller system cooling process water in the chilled water plant to be sent to the conditioned space. Thermal energy storage is a process in which the cooling water to be frozen during the off peak and would send the cold water at peak time on the conditioned space. Hybrid evaporative cooling system, it is same as the CCWS where it cooled refrigerant and water but differ in medium that cools the condenser. CCWS system cools the condenser using cooling tower which hybrid system cools the condenser use water from the reservoir tank and the air supply from the fan. All the three 4

21 system using AHU as a device to supply air to the conditioned space. Because of that AHU become a most important part in HVAC system. AHU is device used to condition and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. Usually it exists with a large metal box and inside it containing a heating or cooling elements, blower, sound attenuators, dampers and air filter racks or chambers. Ductwork ventilation system are connected with the air handlers to distributes the conditioned air through the building and it returns back to the AHU (Edward G. Pita, 2013) as shown in figure 2.1. There are two types of AHU which are draw through type and blow through type. Draw through type is when the fan located downstream of the cooling coil and blow through type is when fan located upstream located upstream of the coils. Figure 2.1: AHU compartment (Source: 5

22 2.1 Air filter Air filter is the component that must have in HVAC system to provide a good indoor air quality because of that air filter cannot be separated with indoor air quality. When talking about the air filter indirectly indoor air quality also being considered because the air filter is an important role in providing good indoor air quality (T J. Robinson & A. E. Ouellet, 1992). The higher the efficiency of an air filter that improved indoor air quality provided. The good indoor air quality given the good performance of equipment. Problems that always occur in HVAC systems especially odour pollution and air quality that is the air filter one of the causes (Bluyssen et al., 2003) Type of Air filter There are many types of air filters are always used in HVAC system. For the pre- filter commonly uses a pleated filters, filter pad, metal panels, media rolls, fan coils filters and primary bag filters. Each type has a difference of size. The air filters are difference design such as washable furnace filter, rigid filter and HEPA filter. The air filter plays significant role in HVAC system.. Every place with ventilation system will needs an air filter. For example, occupants need the air filters because of many environments that have been affected by airborne particle that cannot be seen by the naked eye. Because of that each places have their interest type of air that want to use.(william C. Hinds, 1999). The following places have their own interests to require good air quality is why we need to choose the type of air filter. The examples filter for every needs is comfort, power systems, oral solid dosage, clean process, air pollution control and industrial (Camfil Product Catalogue, 2015). Figure 2.2 shows the type of air filter commonly used in industry nowadays. 6

23 (i) Metal panels filter (ii) Pre-pleated filter (iii) Primary bag filter Figure 2.2: Type of Air filter (Camfil Product Catalogue, 2015) Air Filter Classification HVAC filters made of semi porous, the fibrous material which prevents the passage of particles. Manufacture of particle filters will depend on the size of the filter, the filter material, depth and any related to pore size and fibre. The characteristics of a filter with a MERV (minimum efficiency reporting value) size it depends where it is between MERV size of 1 to 20 (Hitchcock et al., 2006). To review the performance of the air filter, several test procedure must be carried out to prove the theory is the same as the experiment or test performed.(vaughn & Ramachandran, 2002) The test also being carried out according to standard guidelines. American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) introduce filters with MERV with standard testing method ASHRAE From this testing, it is measured in 12 particle size ranging from 0.30 to 10.0 micrometres. Some procedure will be followed in this test to determine the MERV which is from MERV 1 to MERV 12. If higher the rating of the MERV is higher the efficient of the filter and capture more particles with small of size particles. In addition to efficiency, filter attributes also include a reasonable holding capacity and adequate airflow for ventilation. Another factor must to be consider media filter become more efficient as they load, whereas electronic cleaning devices that need to be washed or wiped rapidly lose efficiency as the plates that generate the electrostatic charge become coated with particles. There are no 7

24 certification for the testing in the United States for the testing standards (Sublett et al., 2010). Figure 2.3 shows the typical minimum efficiency curves ASHRAE Figure 2.3: The curve on the table above shows to the following applications (Camfil Farr, 2013): 95% or MERV 14 - typically applied as the final filter in hospital HVAC systems. 85% or MERV 13- typically applied in above average commercial applications. 65% or MERV 11- applied in standard commercial buildings, such as office space. 25% or MERV 6 and 7- pleated panel filters, applied in office environments, and pre filters. <20% or MERV 1 through 5- typical polyester or fiberglass throwaway panels and metal washable filters (Camfil Farr, 2013). 8

EFFECT OF FINE AGGREGATE ANGULARITY ON RUTTING RESISTANCE OF ASPHALT CONCRETE AC10

EFFECT OF FINE AGGREGATE ANGULARITY ON RUTTING RESISTANCE OF ASPHALT CONCRETE AC10 EFFECT OF FINE AGGREGATE ANGULARITY ON RUTTING RESISTANCE OF ASPHALT CONCRETE AC10 IZZUL BIN RAMLI A project report submitted in partial fulfillment of the requirements for the award of the degree of Master

More information

IMPROVEMENT OF BUS ROOF SECTION

IMPROVEMENT OF BUS ROOF SECTION - 1 - IMPROVEMENT OF BUS ROOF SECTION AHMAD FARHAN HAKIM BIN AZMI UNIVERSITY MALAYSIA PAHANG UNIVERSITI MALAYSIA PAHANG BORANG PENGESAHAN STATUS TESIS JUDUL: IMPROVEMENT OF BUS ROOF SECTION SESI PENGAJIAN:

More information

APPLICATION OF BIM IN EARLY STAGE DESIGN COST ESTIMATION

APPLICATION OF BIM IN EARLY STAGE DESIGN COST ESTIMATION APPLICATION OF BIM IN EARLY STAGE DESIGN COST ESTIMATION RAIHAN MASKURIY Faculty of Built Environment Universiti Teknologi Malaysia APPLICATION OF BIM IN EARLY STAGE DESIGN COST ESTIMATION RAIHAN MASKURIY

More information

AIR CONDITIONING STUDY FOR AUTOMOTIVE APPLICATION ALAUDDIN HAFIZ BIN YUSOF UNIVERSITI MALAYSIA PAHANG

AIR CONDITIONING STUDY FOR AUTOMOTIVE APPLICATION ALAUDDIN HAFIZ BIN YUSOF UNIVERSITI MALAYSIA PAHANG AIR CONDITIONING STUDY FOR AUTOMOTIVE APPLICATION ALAUDDIN HAFIZ BIN YUSOF UNIVERSITI MALAYSIA PAHANG UNIVERSITI MALAYSIA PAHANG BORANG PENGESAHAN STATUS TESIS JUDUL: AIR CONDITIONING STUDY FOR AUTOMOTIVE

More information

A COMPARISON BETWEEN TRADITIONAL PAVEMENT REHABILITATION METHOD AS COMPARED TO RECYCLING METHOD SITI MAZZUANA BINTI SHAMSUDDIN

A COMPARISON BETWEEN TRADITIONAL PAVEMENT REHABILITATION METHOD AS COMPARED TO RECYCLING METHOD SITI MAZZUANA BINTI SHAMSUDDIN A COMPARISON BETWEEN TRADITIONAL PAVEMENT REHABILITATION METHOD AS COMPARED TO RECYCLING METHOD SITI MAZZUANA BINTI SHAMSUDDIN A project report submitted in partial fulfilment of the requirements for the

More information

NAZANEEN AHMED NASROULLA

NAZANEEN AHMED NASROULLA RELATIONSHIP BETWEEN CONE PENETRATION TEST AND UNDRAINED SHEAR STRENGTH OF SOFT SOIL NAZANEEN AHMED NASROULLA A project report submitted in partial fulfillment of the requirements for the award of degree

More information

POROSITY ARCHITECTURE IN ECOLOGICAL DESIGN TAN KWON CHONG

POROSITY ARCHITECTURE IN ECOLOGICAL DESIGN TAN KWON CHONG i POROSITY ARCHITECTURE IN ECOLOGICAL DESIGN TAN KWON CHONG A dissertation submitted in fulfilment of the requirements for the award of the degree of Master of Architecture Faculty of Built Environment

More information

FLOOD MAPPING FOR SUNGAI BUNUS MOHD IRSYAM NOORFAWANA BIN MASRI

FLOOD MAPPING FOR SUNGAI BUNUS MOHD IRSYAM NOORFAWANA BIN MASRI FLOOD MAPPING FOR SUNGAI BUNUS MOHD IRSYAM NOORFAWANA BIN MASRI A project report submitted in fulfilment of the requirements for the award of the degree of Master of Engineering (Hydrology & Water Resources)

More information

UNIVERSITI TEKNIKAL MALAYSIA MELAKA

UNIVERSITI TEKNIKAL MALAYSIA MELAKA UNIVERSITI TEKNIKAL MALAYSIA MELAKA DESIGN AND ANALYSIS OF HEAT FLOW FOR DRYER SYSTEM This report submitted in accordance with requirement of the Universiti Teknikal Malaysia Melaka (UTeM) for the Bachelor

More information

Samsiah binti Mohamad

Samsiah binti Mohamad AN AUTOMATIC HAND WASHER AND DRYER MACHINE Samsiah binti Mohamad Bachelor of Electrical Engineering (Control, Instrumentations & Automation) May 2009 I hereby declared that I have read through this report

More information

A Suitable Development Trend in Linear City Based On Smart Growth A Case Study in Lanzhou Urban Area ZHOU WEI

A Suitable Development Trend in Linear City Based On Smart Growth A Case Study in Lanzhou Urban Area ZHOU WEI A Suitable Development Trend in Linear City Based On Smart Growth A Case Study in Lanzhou Urban Area ZHOU WEI A project report submitted in partial fulfillment of the requirements for the award of the

More information

HEAT TRANSFER CHARACTERISTICS OF A HEAT EXCHANGER JAMIATUL ADAWIAH BT AB. SIDEK UNIVERSITI TEKNIKAL MALAYSIA MELAKA

HEAT TRANSFER CHARACTERISTICS OF A HEAT EXCHANGER JAMIATUL ADAWIAH BT AB. SIDEK UNIVERSITI TEKNIKAL MALAYSIA MELAKA HEAT TRANSFER CHARACTERISTICS OF A HEAT EXCHANGER JAMIATUL ADAWIAH BT AB. SIDEK UNIVERSITI TEKNIKAL MALAYSIA MELAKA HEAT TRANSFER CHARACTERISTICS OF A HEAT EXCHANGER JAMIATUL ADAWIAH BT AB. SIDEK This

More information

VISUAL REPRESENTATION OF NATURE IN THE LIBRARY SOMAYEH ROUSTAEI SADRY UNIVERSITI TEKNOLOGI MALAYSIA

VISUAL REPRESENTATION OF NATURE IN THE LIBRARY SOMAYEH ROUSTAEI SADRY UNIVERSITI TEKNOLOGI MALAYSIA VISUAL REPRESENTATION OF NATURE IN THE LIBRARY SOMAYEH ROUSTAEI SADRY UNIVERSITI TEKNOLOGI MALAYSIA VISUAL REPRESENTATION OF NATURE IN THE LIBRARY SOMAYEH ROUSTAEI SADRY A thesis submitted in partial fulfillment

More information

ANALYSIS OF HEAT GAIN AGAINST COOLING CAPACITY AT OCCUPIED BUILDING KOH KELVIN

ANALYSIS OF HEAT GAIN AGAINST COOLING CAPACITY AT OCCUPIED BUILDING KOH KELVIN ANALYSIS OF HEAT GAIN AGAINST COOLING CAPACITY AT OCCUPIED BUILDING KOH KELVIN Thesis submitted in fulfillment of the requirements for the award of the degree of Bachelor of Mechanical Engineering Faculty

More information

GEOGRAPHICAL ANALYSIS OF LIBYAN AIRPORTS AND THEIR POTENTIAL AS A HUB OF AIR TRANSPORTATION FOUAD D S ABDULWAFI UNIVERSITI TEKNOLOGI MALAYSIA

GEOGRAPHICAL ANALYSIS OF LIBYAN AIRPORTS AND THEIR POTENTIAL AS A HUB OF AIR TRANSPORTATION FOUAD D S ABDULWAFI UNIVERSITI TEKNOLOGI MALAYSIA 1 GEOGRAPHICAL ANALYSIS OF LIBYAN AIRPORTS AND THEIR POTENTIAL AS A HUB OF AIR TRANSPORTATION FOUAD D S ABDULWAFI UNIVERSITI TEKNOLOGI MALAYSIA 4 GEOGRAPHICAL ANALYSIS OF LIBYAN AIRPORTS AND THEIR POTENTIAL

More information

DYNAMIC ANALYSES OF COMPOSITE FOOTBRIDGES EXCITED BY PEDESTRIAN INDUCED LOADS FARAZ SADEGHI UNIVERSITI TEKNOLOGI MALAYSIA

DYNAMIC ANALYSES OF COMPOSITE FOOTBRIDGES EXCITED BY PEDESTRIAN INDUCED LOADS FARAZ SADEGHI UNIVERSITI TEKNOLOGI MALAYSIA DYNAMIC ANALYSES OF COMPOSITE FOOTBRIDGES EXCITED BY PEDESTRIAN INDUCED LOADS FARAZ SADEGHI UNIVERSITI TEKNOLOGI MALAYSIA. DYNAMIC ANALYSES OF COMPOSITE FOOTBRIDGES EXCITED BY PEDESTRIAN INDUCED LOADS

More information

THERMAL PERFORMANCE OF POTTED PLANTS IN MITIGATING INDOOR TEMPERATURE IN TROPICAL CLIMATE SHAHRUL BIN CHE ON UNIVERSITI TEKNOLOGI MALAYSIA

THERMAL PERFORMANCE OF POTTED PLANTS IN MITIGATING INDOOR TEMPERATURE IN TROPICAL CLIMATE SHAHRUL BIN CHE ON UNIVERSITI TEKNOLOGI MALAYSIA THERMAL PERFORMANCE OF POTTED PLANTS IN MITIGATING INDOOR TEMPERATURE IN TROPICAL CLIMATE SHAHRUL BIN CHE ON UNIVERSITI TEKNOLOGI MALAYSIA THERMAL PERFORMANCE OF POTTED PLANTS IN MITIGATING INDOOR TEMPERATURE

More information

EVALUATION OF CRACK RELIEF LAYER FOR ROADS AND HIGHWAYS KHAIRUL HAFIZ BIN MUSTAFA

EVALUATION OF CRACK RELIEF LAYER FOR ROADS AND HIGHWAYS KHAIRUL HAFIZ BIN MUSTAFA EVALUATION OF CRACK RELIEF LAYER FOR ROADS AND HIGHWAYS KHAIRUL HAFIZ BIN MUSTAFA A project report submitted in partial fulfillment of the requirements for the award of the degree of Master of Engineering

More information

CENTRE OF STUDIES FOR BUILDING SURVEYING FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA

CENTRE OF STUDIES FOR BUILDING SURVEYING FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA CENTRE OF STUDIES FOR BUILDING SURVEYING FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA A STUDY DESIGN AND MAINTENANCE OF FACADE FOR GOVERNMENT BUILDING, PUTRAJAYA SAHRIZAN BIN

More information

DESIGN FACTORS THAT INFLUENCE THE EFFECTIVE USE OF MEYDAN IN IRAN REIHANEH SADAT HAJMIRSADEGHI UNIVERSITI TEKNOLOGI MALAYSIA

DESIGN FACTORS THAT INFLUENCE THE EFFECTIVE USE OF MEYDAN IN IRAN REIHANEH SADAT HAJMIRSADEGHI UNIVERSITI TEKNOLOGI MALAYSIA DESIGN FACTORS THAT INFLUENCE THE EFFECTIVE USE OF MEYDAN IN IRAN REIHANEH SADAT HAJMIRSADEGHI UNIVERSITI TEKNOLOGI MALAYSIA DESIGN FACTORS THAT INFLUENCE THE EFFECTIVE USE OF MEYDAN IN IRAN REIHANEH SADAT

More information

IDENTIFICATION OF AUDIO AND ROOM PARAMETERS FOR OPTIMUM SPEECH INTELLIGIBILITY IN ROOM NG TSING CHUN UNIVERSITI TEKNOLOGI MALAYSIA

IDENTIFICATION OF AUDIO AND ROOM PARAMETERS FOR OPTIMUM SPEECH INTELLIGIBILITY IN ROOM NG TSING CHUN UNIVERSITI TEKNOLOGI MALAYSIA IDENTIFICATION OF AUDIO AND ROOM PARAMETERS FOR OPTIMUM SPEECH INTELLIGIBILITY IN ROOM NG TSING CHUN UNIVERSITI TEKNOLOGI MALAYSIA ii I declare that this thesis entitled Identification of Audio and Room

More information

GREEN HIGHWAY ECOLOGY AND ECOSYSTEM PRESERVATION AND RESTORATION MUDATHIR OMER ADAM ARBAB

GREEN HIGHWAY ECOLOGY AND ECOSYSTEM PRESERVATION AND RESTORATION MUDATHIR OMER ADAM ARBAB i GREEN HIGHWAY ECOLOGY AND ECOSYSTEM PRESERVATION AND RESTORATION MUDATHIR OMER ADAM ARBAB A project report submitted in partial fulfilment of the requirements for the award of the degree of Master of

More information

ASSESSMENT OF URBAN GREEN SPACE BASED ON LANDSCAPE ECOLOGICAL PRINCIPLES SITI SYAMIMI BINTI OMAR

ASSESSMENT OF URBAN GREEN SPACE BASED ON LANDSCAPE ECOLOGICAL PRINCIPLES SITI SYAMIMI BINTI OMAR ASSESSMENT OF URBAN GREEN SPACE BASED ON LANDSCAPE ECOLOGICAL PRINCIPLES SITI SYAMIMI BINTI OMAR A dissertation for fulfilment of the requirements for the award of the degree of Master of Urban and Regional

More information

PROPOSE AND DESIGN A CANVAS SHOES CLEANER MACHINE NUR SYAFIQAH BINTI ISMUINI

PROPOSE AND DESIGN A CANVAS SHOES CLEANER MACHINE NUR SYAFIQAH BINTI ISMUINI PROPOSE AND DESIGN A CANVAS SHOES CLEANER MACHINE NUR SYAFIQAH BINTI ISMUINI This Report is submitted in Partial Fulfillment of Requirements for the Award of the Degree of Bachelor in Mechanical Engineering

More information

Final Year Project Report

Final Year Project Report FAKULTI KEJURUTERAAN ELEKTRIK UNIVERSITI TEKNIKAL MALAYSIA MELAKA 2014/2015 Final Year Project Report Mobile Air Conditioning Device CHIN KAR GHAI BACHELOR IN MECHATRONICS ENGINEERING (BEKM) 2014/2015

More information

NAZANEEN AHMED NASROULLA

NAZANEEN AHMED NASROULLA RELATIONSHIP BETWEEN CONE PENETRATION TEST AND UNDRAINED SHEAR STRENGTH OF SOFT SOIL NAZANEEN AHMED NASROULLA A project report submitted in partial fulfillment of the requirements for the award of degree

More information

ASSESSMENT OF PARKING DEMAND IMPACT ON ADJOINING ROADWAY NETWORK WAN NUR ALIFFA WAN RAMLI

ASSESSMENT OF PARKING DEMAND IMPACT ON ADJOINING ROADWAY NETWORK WAN NUR ALIFFA WAN RAMLI ASSESSMENT OF PARKING DEMAND IMPACT ON ADJOINING ROADWAY NETWORK WAN NUR ALIFFA WAN RAMLI A project report submitted in partial fulfillment of the requirements for the award of the degree of Master of

More information

UNIVERSITI PUTRA MALAYSIA INTEGRATING PUBLIC ART IN MALAYSIAN URBAN LANDSCAPE

UNIVERSITI PUTRA MALAYSIA INTEGRATING PUBLIC ART IN MALAYSIAN URBAN LANDSCAPE UNIVERSITI PUTRA MALAYSIA INTEGRATING PUBLIC ART IN MALAYSIAN URBAN LANDSCAPE MOHD FABIAN BIN HASNA FRSB 2012 19 INTEGRATING PUBLIC ART IN MALAYSIAN URBAN LANDSCAPE By MOHD FABIAN BIN HASNA February 2012

More information

A STRUCTURED CRITICAL SUCCESS FACTORS MODEL FOR THE IMPLEMENTATION OF GREEN RETROFIT PROJECTS REHMAASHINI JAGARAJAN UNIVERSITI TEKNOLOGI MALAYSIA

A STRUCTURED CRITICAL SUCCESS FACTORS MODEL FOR THE IMPLEMENTATION OF GREEN RETROFIT PROJECTS REHMAASHINI JAGARAJAN UNIVERSITI TEKNOLOGI MALAYSIA A STRUCTURED CRITICAL SUCCESS FACTORS MODEL FOR THE IMPLEMENTATION OF GREEN RETROFIT PROJECTS REHMAASHINI JAGARAJAN UNIVERSITI TEKNOLOGI MALAYSIA A STRUCTURED CRITICAL SUCCESS FACTORS MODEL FOR THE IMPLEMENTATION

More information

UNIVERSITI TEKNOLOGI MARA IMPLICATION OF NIGHT-TIME LEISURE ACTIVITIES TOWARDS PLACE IDENTITY OF URBAN PUBLIC PARK IN SHAH ALAM AND PUTRAJAYA

UNIVERSITI TEKNOLOGI MARA IMPLICATION OF NIGHT-TIME LEISURE ACTIVITIES TOWARDS PLACE IDENTITY OF URBAN PUBLIC PARK IN SHAH ALAM AND PUTRAJAYA UNIVERSITI TEKNOLOGI MARA IMPLICATION OF NIGHT-TIME LEISURE ACTIVITIES TOWARDS PLACE IDENTITY OF URBAN PUBLIC PARK IN SHAH ALAM AND PUTRAJAYA MOHD RIDUAN BIN NGESAN Thesis submitted in fulfilment of the

More information

AQUAPONIC SYSTEM FOR SELF-SUSTAIN LIVING YAN YEN QUN

AQUAPONIC SYSTEM FOR SELF-SUSTAIN LIVING YAN YEN QUN iv AQUAPONIC SYSTEM FOR SELF-SUSTAIN LIVING YAN YEN QUN A dissertation submitted in fulfilment of the requirements for the award of the degree of Master of Architecture Faculty of Built Environment Universiti

More information

LANDFILL SITE SUITABILITY USING GEOGRAPHIC INFORMATION SYSTEM AND ANALYTICAL HIERARCHY PROCESS

LANDFILL SITE SUITABILITY USING GEOGRAPHIC INFORMATION SYSTEM AND ANALYTICAL HIERARCHY PROCESS i LANDFILL SITE SUITABILITY USING GEOGRAPHIC INFORMATION SYSTEM AND ANALYTICAL HIERARCHY PROCESS IZNI IZZATI BINTI MOHAMAD UNIVERSITI TEKNOLOGI MALAYSIA LANDFILL SITE SUITABILTY USING GEOGRAPHIC INFORMATION

More information

Jurnal Teknologi FALLING HEAD TEST FOR GEOTEXTILE DRAINAGE CAPACITY. Full Paper. Noor Hidayu Amran, A. Naser Abdul Ghani *

Jurnal Teknologi FALLING HEAD TEST FOR GEOTEXTILE DRAINAGE CAPACITY. Full Paper. Noor Hidayu Amran, A. Naser Abdul Ghani * Jurnal Teknologi FALLING HEAD TEST FOR GEOTEXTILE DRAINAGE CAPACITY Noor Hidayu Amran, A. Naser Abdul Ghani * School of Housing, Building and Planning, Universiti Sains Malaysia, 11800, Penang, Malaysia

More information

THE DESIGN AND FABRICATION OF AN OIL VACUUM CLEANER FOR INDUSTRIAL USE

THE DESIGN AND FABRICATION OF AN OIL VACUUM CLEANER FOR INDUSTRIAL USE THE DESIGN AND FABRICATION OF AN OIL VACUUM CLEANER FOR INDUSTRIAL USE NORHAFIS BIN SAMAT BACHELOR OF MECHANICAL ENGINEERING (STRUCTURE AND MATERIALS) 2015 NORHAFIS BIN SAMAT UNIVERSITI TEKNIKAL MALAYSIA

More information

A SINGLE GLOBAL LEGISLATION

A SINGLE GLOBAL LEGISLATION JUNE 2018 ENTRY INTO FORCE OF THE NEW UNI EN ISO 16890:2017 STANDARDS A SINGLE GLOBAL LEGISLATION In June 2018 the new UNI EN ISO 16890:2017 standard will come into force, which will bring substantial

More information

DESIGN OF A RECYCLE BIN TIN CAN CRUSHER MUHAMMAD HANIS BIN MUHAMMAD ZULKIFLI

DESIGN OF A RECYCLE BIN TIN CAN CRUSHER MUHAMMAD HANIS BIN MUHAMMAD ZULKIFLI DESIGN OF A RECYCLE BIN TIN CAN CRUSHER MUHAMMAD HANIS BIN MUHAMMAD ZULKIFLI A report submitted in partial fulfillment of the requirements for the award of the degree of Diploma of Mechanical Engineering

More information

PERFORMANCE OF FORCED CONVECTION EVACUATED TUBE SOLAR GRAIN DRYER. BOOKER ONYANGO OSODO B. Ed.(TECH); M. Phil (Tech. Ed) (J98/25749/2011)

PERFORMANCE OF FORCED CONVECTION EVACUATED TUBE SOLAR GRAIN DRYER. BOOKER ONYANGO OSODO B. Ed.(TECH); M. Phil (Tech. Ed) (J98/25749/2011) PERFORMANCE OF FORCED CONVECTION EVACUATED TUBE SOLAR GRAIN DRYER BOOKER ONYANGO OSODO B. Ed.(TECH); M. Phil (Tech. Ed) (J98/25749/2011) A research Proposal Submitted in Partial Fulfillment of the Requirements

More information

ANALYSIS PERFORMANCE OF WAJA CAR AIR-CONDITIONING SYSTEM MUHAMAD AMIRUDIN BIN KAMALRUL BADRI

ANALYSIS PERFORMANCE OF WAJA CAR AIR-CONDITIONING SYSTEM MUHAMAD AMIRUDIN BIN KAMALRUL BADRI ANALYSIS PERFORMANCE OF WAJA CAR AIR-CONDITIONING SYSTEM MUHAMAD AMIRUDIN BIN KAMALRUL BADRI Thesis submitted in fulfilment of the requirements for the award of the degree of Bachelor of Mechanical Engineering

More information

UNIVERSITI TEKNIKAL MALAYSIA MELAKA

UNIVERSITI TEKNIKAL MALAYSIA MELAKA UNIVERSITI TEKNIKAL MALAYSIA MELAKA AUTOMATIC COOLING SYSTEM USING PELTIER THERMOELECTRIC COOLER FOR LIGHTNING DETECTION APPLICATION WITH SMART CONTROL AND MONITORING SYSTEM This report submitted in accordance

More information

UNIVERSITI TEKNOLOGI MARA

UNIVERSITI TEKNOLOGI MARA UNIVERSITI TEKNOLOGI MARA LANDSCAPE CHARACTER ASSESSMENT AS A TOOL FOR LANDSCAPE PLANNING MOHD ZULHAILI BIN TEH Thesis submitted in fulfillment of the requirements for the degree of Masters of Science

More information

ISO AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY

ISO AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY ISO 16890-2 AIR FILTERS FOR GENERAL VENTILATION: DETERMINING FRACTIONAL EFFICIENCY APPLICATION NOTE AFT-005 (US) Contents Introduction to ISO 16890... 1 How ISO 16890 Compares to EN 779 and ASHRAE 52.2...

More information

Effect of the Electro Breeze Air Filter on Airborne Particles in a Recirculating Air Duct

Effect of the Electro Breeze Air Filter on Airborne Particles in a Recirculating Air Duct LRI TM Lowering Risks by Innovation Effect of the Electro Breeze Air Filter on Airborne Particles in a Recirculating Air Duct Prepared for Electro Breeze Air Cleaner Ltd. 117 De L Eglise, St-Sauveur Quebec,

More information

SMART GARDEN SYSTEM NURSHAHNEEM BINTI MOHD SAID

SMART GARDEN SYSTEM NURSHAHNEEM BINTI MOHD SAID i SMART GARDEN SYSTEM NURSHAHNEEM BINTI MOHD SAID This Report Is Submitted In Partial Fulfillment of Requirements For The Bachelor Degree of Electronic Engineering (Industrial Electronic) Faculty of Electronic

More information

CENTRE OF STUDIES FOR BUILDING SURVEYING FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA

CENTRE OF STUDIES FOR BUILDING SURVEYING FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA CENTRE OF STUDIES FOR BUILDING SURVEYING FACULTY OF ARCHITECTURE, PLANNING AND SURVEYING UNIVERSITI TEKNOLOGI MARA A STUDY ON AWARENESS AMONG PROFESSIONALS TOWARDS THE IMPORTANCE OF BUILDING SURVEYING

More information

DESIGN AND ANALYSIS OF ELECTRICAL IRON USING BOOTHROYD DEWHURST DFMA METHODOLOGY MOHD HAZUAN BIN MOHD ZAWAWI

DESIGN AND ANALYSIS OF ELECTRICAL IRON USING BOOTHROYD DEWHURST DFMA METHODOLOGY MOHD HAZUAN BIN MOHD ZAWAWI DESIGN AND ANALYSIS OF ELECTRICAL IRON USING BOOTHROYD DEWHURST DFMA METHODOLOGY MOHD HAZUAN BIN MOHD ZAWAWI This report is submitted as partial fulfillment of the requirement for the award of Bachelor

More information

HEDGES USED IN BACKGROUND OF THE STUDY SECTIONS OF ENGLISH DEPARTMENT THESES: A CASE STUDY AT DIAN NUSWANTORO UNIVERSITY THESIS

HEDGES USED IN BACKGROUND OF THE STUDY SECTIONS OF ENGLISH DEPARTMENT THESES: A CASE STUDY AT DIAN NUSWANTORO UNIVERSITY THESIS HEDGES USED IN BACKGROUND OF THE STUDY SECTIONS OF ENGLISH DEPARTMENT THESES: A CASE STUDY AT DIAN NUSWANTORO UNIVERSITY THESIS Presented in partial fulfillment of the requirements for the completion of

More information

DESIGN AND DEVELOPMENT OF FOOD WASTE COMPACTOR ROZAIDI BIN ROZMAN

DESIGN AND DEVELOPMENT OF FOOD WASTE COMPACTOR ROZAIDI BIN ROZMAN DESIGN AND DEVELOPMENT OF FOOD WASTE COMPACTOR ROZAIDI BIN ROZMAN This report is submitted in fulfillment of the requirement for the degree of Bachelor of Mechanical Engineering (Design and Innovation)

More information

FLOW AND PERFORMANCE INVESTIGATIONS OF CENTRIFUGAL BLOWERS WITH AEROFOIL BLADED IMPELLERS

FLOW AND PERFORMANCE INVESTIGATIONS OF CENTRIFUGAL BLOWERS WITH AEROFOIL BLADED IMPELLERS FLOW AND PERFORMANCE INVESTIGATIONS OF CENTRIFUGAL BLOWERS WITH AEROFOIL BLADED IMPELLERS BY JAY K. MUKHRAIYA A THESIS SUBMITTED IN FULFILMENT OF THE REQUIREMENTS FOR THE DEGREE OF DOCTOR OF PHILOSOPHY.

More information

EARHTHING PERFORMANCE OF HV/MV SUBSTATION AND ITS EFFECT ON NEARBY STRUCTURES NORNIKMAN BIN RAHIMIN

EARHTHING PERFORMANCE OF HV/MV SUBSTATION AND ITS EFFECT ON NEARBY STRUCTURES NORNIKMAN BIN RAHIMIN EARHTHING PERFORMANCE OF HV/MV SUBSTATION AND ITS EFFECT ON NEARBY STRUCTURES NORNIKMAN BIN RAHIMIN A project report submitted in partial fulfilment of the requirements for the award of the degree of Master

More information

UNIVERSITI PUTRA MALAYSIA

UNIVERSITI PUTRA MALAYSIA UNIVERSITI PUTRA MALAYSIA FACIAL FEATURE EXTRACTION BASED ON IMPROVED HARRIS CORNER DETECTION ALGORITHM ELHAAM BAGHERIAN FSKTM 2011 9 FACIAL FEATURE EXTRACTION BASED ON IMPROVED HARRIS CORNER DETECTION

More information

TABLE OF CONTENTS. iii iv vi. vii. xii xiii xvii xix

TABLE OF CONTENTS. iii iv vi. vii. xii xiii xvii xix TABLE OF CONTENTS ORIGINAL LITERACY WORK DECLARATION ABSTRACT ABSTRAK (MALAY TRANSLATION) ACKNOWLEDGEMENT TABLE OF CONTENTS LIST OF FIGURES LIST OF TABLES LIST OF SYMBOLS AND ABBREVIATIONS LIST OF APPENDICES

More information

NEW CONCEPT OF FURNITURE DESIGN BY USING SPACE SAVING APPROACH TAN BOON CHAI UNIVERSITI TEKNIKAL MALAYSIA MELAKA

NEW CONCEPT OF FURNITURE DESIGN BY USING SPACE SAVING APPROACH TAN BOON CHAI UNIVERSITI TEKNIKAL MALAYSIA MELAKA NEW CONCEPT OF FURNITURE DESIGN BY USING SPACE SAVING APPROACH TAN BOON CHAI UNIVERSITI TEKNIKAL MALAYSIA MELAKA Panel s Verification I / We* hereby confirm that I/we have examined and aware of the contents

More information

12 Pogo Pole Hose Adapter

12 Pogo Pole Hose Adapter 12 Pogo Pole Hose Adapter OPERATING INSTRUCTIONS & PARTS MANUAL Table of Contents Unpacking Instructions 2 Safety Information 2 Reference Pictures 3 Assembly Instructions 3 Operating Instructions 4 Parts

More information

UNIVERSITI PUTRA MALAYSIA SUSTAINABILITY OF STREET FURNITURE DESIGN IN URBAN MALAYSIA

UNIVERSITI PUTRA MALAYSIA SUSTAINABILITY OF STREET FURNITURE DESIGN IN URBAN MALAYSIA UNIVERSITI PUTRA MALAYSIA SUSTAINABILITY OF STREET FURNITURE DESIGN IN URBAN MALAYSIA ARNIS BINTI AZIZ FRSB 2013 2 SUSTAINABILITY OF STREET FURNITURE DESIGN IN URBAN MALAYSIA By ARNIS BINTI AZIZ Thesis

More information

THE RELEVANCE OF TRANSIT-ORIENTED DEVELOPMENT FOR TRANSIT STATION COMMUNITY IN MALAYSIA ZAINUDDIN BIN AB RAHMAN

THE RELEVANCE OF TRANSIT-ORIENTED DEVELOPMENT FOR TRANSIT STATION COMMUNITY IN MALAYSIA ZAINUDDIN BIN AB RAHMAN 3 THE RELEVANCE OF TRANSIT-ORIENTED DEVELOPMENT FOR TRANSIT STATION COMMUNITY IN MALAYSIA ZAINUDDIN BIN AB RAHMAN A dissertation submitted in partial fulfilment of the requirements for the award of the

More information

SISTEM PBNGUJIAN TAPAK CADAI\IGAN BINAAN HALIZAH BINTI AHMAD

SISTEM PBNGUJIAN TAPAK CADAI\IGAN BINAAN HALIZAH BINTI AHMAD SISTEM PBNGUJIAN TAPAK CADAI\IGAN BINAAN t t HALIZAH BINTI AHMAD Laporan projek ini dikemukakan sebagai memenuhi sebahagian daripada syarat penganugerahan ijazah Sarjana Muda Sains Komputer Fakulti Sains

More information

TABLE OF CONTENTS CHAPTER TITLE PAGE DECLARATION DEDICATION ACKNOWLEDGEMENTS ABSTRACT ABSTRAK

TABLE OF CONTENTS CHAPTER TITLE PAGE DECLARATION DEDICATION ACKNOWLEDGEMENTS ABSTRACT ABSTRAK vii TABLE OF CONTENTS CHAPTER TITLE PAGE DECLARATION DEDICATION ACKNOWLEDGEMENTS ABSTRACT ABSTRAK TABLE OF CONTENTS LIST OF FIGURES LIST OF TABLES LIST OF ACROYMS LIST OF APPENDIXES ii iii iv v vi vii

More information

Theatre Classification and Air Particle Count Is that Surveillance?

Theatre Classification and Air Particle Count Is that Surveillance? Theatre Classification and Air Particle Count Is that Surveillance? Codes and Specifications for Theatre Installations The South African National Standards Wiring Code - SANS 10142-1:2006. Occupational

More information

COMPLEXITY OF THE FLORAL PATTERN IN VENTILATION PANEL OF TIMBER BUILDING IN KELANTAN AND TERENGGANU

COMPLEXITY OF THE FLORAL PATTERN IN VENTILATION PANEL OF TIMBER BUILDING IN KELANTAN AND TERENGGANU COMPLEXITY OF THE FLORAL PATTERN IN VENTILATION PANEL OF TIMBER BUILDING IN KELANTAN AND TERENGGANU NURSURIANI BINTI SHAFFEE UNIVERSITI TEKNOLOGI MALAYSIA iv COMPLEXITY OF THE FLORAL PATTERN IN VENTILATION

More information

SUBJECT: Effective Date: Procedure Number:

SUBJECT: Effective Date: Procedure Number: SUBJECT: Effective Date: Procedure Number: Facilities Operations/ Utilities and Energy 9/1/2015 FS 2015 UES0002 Services Division of Responsibility Procedure APPLICABILITY/ACCOUNTABILITY: Supersedes: Page

More information

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering

Development of a Psychrometric Test Chamber. Michael J. Swedish. Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Session 2633 Development of a Psychrometric Test Chamber Michael J. Swedish Associate Professor Mechanical Engineering Department Milwaukee School of Engineering Acknowledgments The design of the Psychrometric

More information

PHYSICAL ATTRIBUTES ON PLACE ATTACHMENT IN MALAYSIAN URBAN PARKS HADI EBADI UNIVERSITI TEKNOLOGI MALAYSIA

PHYSICAL ATTRIBUTES ON PLACE ATTACHMENT IN MALAYSIAN URBAN PARKS HADI EBADI UNIVERSITI TEKNOLOGI MALAYSIA PHYSICAL ATTRIBUTES ON PLACE ATTACHMENT IN MALAYSIAN URBAN PARKS HADI EBADI UNIVERSITI TEKNOLOGI MALAYSIA PHYSICAL ATTRIBUTES ON PLACE ATTACHMENT IN MALAYSIAN URBAN PARKS HADI EBADI A thesis submitted

More information

MECCI Engineers. Institute of Engineering Design & Research

MECCI Engineers. Institute of Engineering Design & Research MECCI Engineers Institute of Engineering Design & Research (An ISO 9001:2015 DAC International Certification for EPC Consulting, Engineering Project & Training Company) HVAC Design Course Content For Regular

More information

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms Min Suk Jo, Jang Hoon Shin, Won Jun Kim and Jae Weon Jeong * Department of Architectural

More information

HVAC 101: Residential Typical system components & cleaning techniques

HVAC 101: Residential Typical system components & cleaning techniques : Typical system components & cleaning techniques Copyright 2018 NADCA, All Rights Reserved No part of this publication may be reproduced or distributed by any means, electronic or mechanical, including

More information

NUTRIENT LEACHING IN PEAT AND LATERITIC SOIL TREATED WITH INORGANIC AND ORGANIC FERTILISER

NUTRIENT LEACHING IN PEAT AND LATERITIC SOIL TREATED WITH INORGANIC AND ORGANIC FERTILISER NUTRIENT LEACHING IN PEAT AND LATERITIC SOIL TREATED WITH INORGANIC AND ORGANIC FERTILISER NUR AIN IZZATI BINTI ZAINI Final Year Project Report Submitted in Partial Fulfilment ofthe Requirement for the

More information

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS AND APPLICATIONS Abdullah Nuhait Ph D. King Saud University AIR-CONDITIONING SYSTEMS Earliest air conditioning system used only for heating (winter) Provided heated air for comfort

More information

Performance Series Indoor Air Quality Systems for Fan Coil Application

Performance Series Indoor Air Quality Systems for Fan Coil Application Performance Series Indoor Air Quality Systems for Fan Coil Application Enjoy Fresher, Cleaner Indoor Air Ultraviolet Germicidal Lamps (UV Lights) Airborne pollutants are simply a fact of life. Pollutants

More information

Healthy Climate Indoor Air Quality Solutions. Solutions that fit your unique needs

Healthy Climate Indoor Air Quality Solutions. Solutions that fit your unique needs i n d o o r a i r q u a l i t y s o l u t i o n s Healthy Climate Indoor Air Quality Solutions Solutions that fit your unique needs Healthy Climate Indoor Air Quality Solutions Custom, whole-home product

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

A SIMPLE ID DETECTION USING INFRARED SENSORS NOOR FARHANA HALIL BT ABDUL RAZAK

A SIMPLE ID DETECTION USING INFRARED SENSORS NOOR FARHANA HALIL BT ABDUL RAZAK A SIMPLE ID DETECTION USING INFRARED SENSORS NOOR FARHANA HALIL BT ABDUL RAZAK This report is submitted in partial fulfillment of the requirements for the award of Bachelor of Electronic Engineering (

More information

HUMIDITY CONTROL SYSTEM FOR ROLLING AND FERMENTING ROOM OF A TEA FACTORY

HUMIDITY CONTROL SYSTEM FOR ROLLING AND FERMENTING ROOM OF A TEA FACTORY HUMIDITY CONTROL SYSTEM FOR ROLLING AND FERMENTING ROOM OF A TEA FACTORY Uduwara Gayan Sameera Senaratne 108864N Dissertation submitted in partial fulfilment of the requirements for the degree Master of

More information

Duct Design and Installation

Duct Design and Installation Duct Design and Installation John Proctor, P.E. Proctor Engineering Group, Ltd. San Rafael, CA 2004 Proctor Engineering Group, Ltd. 1-888-455-5742 mail@proctoreng.com www.proctoreng.com Duct Design ACCA

More information

ANALYZE ThJ SPRINKLER SYSTEM IN tjw LECTURE ROOM USINO CID (COMPUTATIONAL FLUID DYNAMICS) ANALYSIS. WJHAMAD KHUMAJM fin r,jzaiman

ANALYZE ThJ SPRINKLER SYSTEM IN tjw LECTURE ROOM USINO CID (COMPUTATIONAL FLUID DYNAMICS) ANALYSIS. WJHAMAD KHUMAJM fin r,jzaiman ANALYZE ThJ SPRINKLER SYSTEM IN tjw LECTURE ROOM USINO CID (COMPUTATIONAL FLUID DYNAMICS) ANALYSIS WJHAMAD KHUMAJM fin r,jzaiman A report submitted in partial fulfillment,of thp requirements for the award

More information

FIBER NETWORK CABLING. By: Abdul Hak Bin Mahat (ILPS)

FIBER NETWORK CABLING. By: Abdul Hak Bin Mahat (ILPS) FIBER NETWORK CABLING By: TAJUK : Keselamatan Menggunakan Fiber Optik Oleh: TUJUAN Pelajar-pelajar mestilah boleh: Terangkan isu keselamatan dalam bidang fiber optik Terangkan tujuan keselamatan semasa

More information

ANALYSIS AND MEASUREMENT FIBER OPTIC FAULT BY USING OPTICAL TIME DOMAIN REFLECTROMETER (OTDR) AKWANIZAM BIN AZMI

ANALYSIS AND MEASUREMENT FIBER OPTIC FAULT BY USING OPTICAL TIME DOMAIN REFLECTROMETER (OTDR) AKWANIZAM BIN AZMI ANALYSIS AND MEASUREMENT FIBER OPTIC FAULT BY USING OPTICAL TIME DOMAIN REFLECTROMETER (OTDR) AKWANIZAM BIN AZMI This Report Is Submitted in Partial Fulfillment of the Requirements for the award of Bachelor

More information

DESIGN AND CONSTRUCTION OF A MICROCONTROLLER BASED UNDER AND OVER VOLTAGE PROTECTION DEVICE WITH ALARM NAT BEREGHA EREMIEMI (2006/24462EE)

DESIGN AND CONSTRUCTION OF A MICROCONTROLLER BASED UNDER AND OVER VOLTAGE PROTECTION DEVICE WITH ALARM NAT BEREGHA EREMIEMI (2006/24462EE) DESIGN AND CONSTRUCTION OF A MICROCONTROLLER BASED UNDER AND OVER VOLTAGE PROTECTION DEVICE WITH ALARM BY NAT BEREGHA EREMIEMI (2006/24462EE) A THESIS SUBMITTED TO THE DEPARTMENT OF ELECTRICAL AND ELECTRONICS

More information

PRELIMINARY STUDY ON BRICKS DRYING PROCESS USING MICROWAVE TECHNOLOGY SALEM SALAH ABDULLAH BAGABER UNIVERSITI TEKNOLOGI MALAYSIA

PRELIMINARY STUDY ON BRICKS DRYING PROCESS USING MICROWAVE TECHNOLOGY SALEM SALAH ABDULLAH BAGABER UNIVERSITI TEKNOLOGI MALAYSIA PRELIMINARY STUDY ON BRICKS DRYING PROCESS USING MICROWAVE TECHNOLOGY SALEM SALAH ABDULLAH BAGABER UNIVERSITI TEKNOLOGI MALAYSIA 3 PRELIMINARY STUDY ON BRICKS DRYING PROCESS USING MICROWAVE TECHNOLOGY

More information

WIRELESS Temperature Monitoring System for Blood Bank using Zigbee. Keywords: Temperature monitoring system; ZigBee; LabVIEW; internet; alarm

WIRELESS Temperature Monitoring System for Blood Bank using Zigbee. Keywords: Temperature monitoring system; ZigBee; LabVIEW; internet; alarm Jurnal Teknologi Full Paper WIRELESS Temperature Monitoring System for Blood Bank using Zigbee Lau Jye Hui a, Fauzan Khairi Che Harun a*, Yusmeeraz Yusof a, Norlaili Mat Safri a a Faculty of Electrical

More information

MUIHAMAD RUSYDI BIN AL!

MUIHAMAD RUSYDI BIN AL! DESIGN AND FABRICATION OF ADJUSTABLE CEILING FAN BLADE CLEANER MUIHAMAD RUSYDI BIN AL! A project report submitted in partial fulfilment of the requirements for the award of the Diploma of Mechanical Engineering

More information

Performance Optimization of the Evaporative Condenser Design

Performance Optimization of the Evaporative Condenser Design Performance Optimization of the Evaporative Condenser Design Mit. C. Patel P.G.Student, Mech. Engg.Dept. Institute of Technology, Nirma University, Ahmadabad, Prof. B. A. Shah Mechanical Engineering Department

More information

RDG 334 Theory and History of Design (Sejarah dan Teori Seni Reka)

RDG 334 Theory and History of Design (Sejarah dan Teori Seni Reka) UNIVERSITI SAINS MALAYSIA First Semester Examination 2013/2014 Academic Session December 2013 / January 2014 RDG 334 Theory and History of Design (Sejarah dan Teori Seni Reka) Duration : 3 hours (Masa:

More information

Are Your Kitchen Hood Filters Compliant?

Are Your Kitchen Hood Filters Compliant? Are Your Kitchen Hood Filters Compliant? Do your kitchen hood filters comply with the current Australian Standards for fire safety? Why Install Kitchen Exhaust Hood Filters? The purpose of a kitchen exhaust

More information

T-Series Climate Changer Air Handler. It s Hard To Stop A Trane.

T-Series Climate Changer Air Handler. It s Hard To Stop A Trane. T-Series Climate Changer Air Handler TM It s Hard To Stop A Trane. T-Series Climate Changer Air Handler The Trane tradition of excellence continues with the T-Series Climate Changer air handler. Using

More information

CARE GUIDANCE. Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) LEVEL 2 RECOMMENDATIONS ON BEST PRACTICE

CARE GUIDANCE. Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) LEVEL 2 RECOMMENDATIONS ON BEST PRACTICE PUBLICATION: MAY 2012 REVISION: JANUARY 2018 VERSION: 1.2 CARE GUIDANCE RECOMMENDATIONS ON BEST PRACTICE LEVEL 2 Local Exhaust Ventilation (LEV) Systems for High Temperature Insulation Wool (HTIW) 2 LOCAL

More information

SUSTAINABILITY ASSESSMENT OF COMPACT-CITY DEVELOPMENT USING GEODESIGN APPROACH AHMED ABDULHAFEDH OWAID UNIVERSITI TEKNOLOGI MALAYSIA

SUSTAINABILITY ASSESSMENT OF COMPACT-CITY DEVELOPMENT USING GEODESIGN APPROACH AHMED ABDULHAFEDH OWAID UNIVERSITI TEKNOLOGI MALAYSIA SUSTAINABILITY ASSESSMENT OF COMPACT-CITY DEVELOPMENT USING GEODESIGN APPROACH AHMED ABDULHAFEDH OWAID UNIVERSITI TEKNOLOGI MALAYSIA SUSTAINABILITY ASSESSMENT OF COMPACT-CITY DEVELOPMENT USING GEODESIGN

More information

Guidelines for Ideal Layout for an Operating Theater Complex. Dr.R.D.Ravindran Aravind Eye Hospital Madurai

Guidelines for Ideal Layout for an Operating Theater Complex. Dr.R.D.Ravindran Aravind Eye Hospital Madurai Guidelines for Ideal Layout for an Operating Theater Complex Dr.R.D.Ravindran Aravind Eye Hospital Madurai Patient Flow 1. WARD 4. RECOVERY ROOM 2. BLOCK ROOM 3. THEATRE Transfer area This is an area,

More information

CLEAN AIR SYSTEMS DIVISION. An ISO 9001 Certified Company. Nan Technical Trading W.L.L P.O.Box Manama Kingdom of Bahrain

CLEAN AIR SYSTEMS DIVISION. An ISO 9001 Certified Company. Nan Technical Trading W.L.L P.O.Box Manama Kingdom of Bahrain An ISO 9001 Certified Company CLEAN AIR SYSTEMS DIVISION Nan Technical Trading W.L.L P.O.Box - 2683 Manama Kingdom of Bahrain Tel: +973-17212023 Fax: +973-17212289 Email: nan@nantechgroup.com Website:

More information

INFLUENCE OF PASSENGER CAR AIR CONDITIONER SYSTEM THERMOSTAT LEVEL SETTING TO FUEL CONSUMPTION AND THERMAL COMFORT MUHAMAD KHIRIL BIN KAMARUDDIN

INFLUENCE OF PASSENGER CAR AIR CONDITIONER SYSTEM THERMOSTAT LEVEL SETTING TO FUEL CONSUMPTION AND THERMAL COMFORT MUHAMAD KHIRIL BIN KAMARUDDIN iii INFLUENCE OF PASSENGER CAR AIR CONDITIONER SYSTEM THERMOSTAT LEVEL SETTING TO FUEL CONSUMPTION AND THERMAL COMFORT MUHAMAD KHIRIL BIN KAMARUDDIN A project report submitted in fulfillment of the requirement

More information

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET I. S. Hwang and Y. L. Lee Department of Mechanical Engineering, Kongju National University, Korea E-Mail: ylee@kongju.ac.kr ABSTRACT

More information

DETERMINATION OF BASIC SOIL PROPERTIES AND SHEAR STRENGTH OF PEKAN SOFT CLAY MOHD FARUQ BIN SA ADON

DETERMINATION OF BASIC SOIL PROPERTIES AND SHEAR STRENGTH OF PEKAN SOFT CLAY MOHD FARUQ BIN SA ADON DETERMINATION OF BASIC SOIL PROPERTIES AND SHEAR STRENGTH OF PEKAN SOFT CLAY MOHD FARUQ BIN SA ADON A report submitted in partial fulfillment of the requirements for the award of the degree of achieving

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

FMNA SYSTEM (FORGET ME NOT ALERT SYSTEM) SHARON BOON KHAI YEN

FMNA SYSTEM (FORGET ME NOT ALERT SYSTEM) SHARON BOON KHAI YEN FMNA SYSTEM (FORGET ME NOT ALERT SYSTEM) SHARON BOON KHAI YEN This report is submitted in partial fulfillment of the requirement for the Bachelor Degree of Electronic Engineering (Electronic Industry)

More information

or with a higher exposure potential than the processes, types of material, control methods, work

or with a higher exposure potential than the processes, types of material, control methods, work specific process, task, or activity. The data must reflect workplace conditions closely resembling or with a higher exposure potential than the processes, types of material, control methods, work practices,

More information

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline

Topic 2. ME 414/514 HVAC Systems Overview Topic 2. Equipment. Outline ME 414/514 HVAC Systems Overview Equipment Outline 2-1 The Complete System 2-2 The Air-Conditioning and Distribution System 2-3 Mechanical Equipment Air-handling Equipment Heating Equipment Boilers Furnaces

More information

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS By Yuguo Li and SARS Busters * Background The hospital care workers (HCWs) have been the most severely affected professions during the SARS epidemics in

More information

Signature : MOHD ZAMRI BIN IBRAHIM

Signature : MOHD ZAMRI BIN IBRAHIM I hereby declare that I have read this thesis and in my opinion, this thesis is sufficient in terms of scope and quality for the award of the degree of Bachelor of Electrical Engineering (Electronic) Signature

More information

SECTION A : 50 MARKS BAHAGIAN A : 50 MARKAH INSTRUCTION: This section consists of TWO (2) structured essay questions. Answer ALL questions.

SECTION A : 50 MARKS BAHAGIAN A : 50 MARKAH INSTRUCTION: This section consists of TWO (2) structured essay questions. Answer ALL questions. SECTION A : 50 MARKS BAHAGIAN A : 50 MARKAH INSTRUCTION: This section consists of TWO (2) structured essay questions. Answer ALL questions. ARAHAN : Bahagian ini mengandungi DUA (2) soalan esei berstruktur.

More information

DESIGN AND CONSTRUCTION OF OVER-VOLTAGE AND UNDER VOLTAGE PROTECTIVE DEVICE WIT.H REMOTE CONTROL

DESIGN AND CONSTRUCTION OF OVER-VOLTAGE AND UNDER VOLTAGE PROTECTIVE DEVICE WIT.H REMOTE CONTROL DESIGN AND CONSTRUCTION OF OVER-VOLTAGE AND UNDER VOLTAGE PROTECTIVE DEVICE WIT.H REMOTE CONTROL BY LABARAN RILWAN YUNUSA 2005/22045EE A PROJECT REPORT SUBMITTED TO THE DEPARTMENT OF ELECTRICAL AND COMPUTER

More information

Kuliah 1 : Pengenalan Kepada Teknologi Maklumat & Komunikasi

Kuliah 1 : Pengenalan Kepada Teknologi Maklumat & Komunikasi PPISMP Kuliah 1 : Pengenalan Kepada Teknologi Maklumat & Komunikasi 1.2 Impak Teknologi Maklumat dan Komunikasi kepada Masyarakat 1.2.0 Impak Teknologi Maklumat dan Komunikasi kepada Masyarakat 1.2.1 Kepentingan

More information