LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual

Size: px
Start display at page:

Download "LTS Liquid-to-Steam Humidifier. Installation, Operation and Maintenance Manual"

Transcription

1 LTS Liquid-to-Steam Humidifier Installation, Operation and Maintenance Manual

2 Overview LTS models....3 Dimensions....4 Output capacities....6 Weights, connections and heated water properties Installation Selecting a location....8 Clearance recommendations....9 Mounting Mounting methods Trapeze hanger Support legs H-legs Wall brackets Outdoor Enclosure Piping Overview Drain Alternative water seal and drain valve Water supply Wiring Dispersion General instructions Interconnecting piping requirements Drip tee installation Single and Multiple dispersion tubes Rapid-sorb Operation Start-up procedures Start-up LW417 control LW417 automatic drain and flush...48 LW417 variable skim times...49 LW417 end-of-season drain LW417 Onboard diagnostics Maintenance Standard water models DI water models Troubleshooting LTS and LTS-DI LW Outdoor Enclosure replacement parts Replacement parts Humidifier tank Control cabinet Warranty....Back cover

3 Overview Figure 3-1: LTS standard water model Modulating valve Hot liquid return Hot liquid supply Figure 3-2: LTS DI/RO water model Modulating valve Hot liquid return Steam outlet Water seal Steam outlet Float valve Manual drain or optional motorized drain valve Air gap Open drain Heat exchanger Manual drain valve LTS-OM-8 Heat exchanger Standard water models (LTS) Standard water LTS humidifiers heat potable or softened fill water into steam for humidification. A conductivity probe controls water level, requiring water conductivity to be at least 100 μs/cm (2 grains/gallon) to operate properly. Therefore, standard water LTS models will not operate with demineralized water. For demineralized water operation (using deionized or reverse osmosis treated water), use LTS-DI model humidifiers (described below). Deionized water models (LTS-DI) LTS-DI humidifiers heat deionized (DI) or reverse osmosis (RO) fill water into steam for humidification. LTS-DI models control water levels using a float valve. Notes: not covered by your DRI-STEEM warranty. converted in the field for use with deionized/reverse osmosis (DI/RO) water. LTS-DI models can be converted in the field for use with potable or softened water. 212 F (100 C) water. provided by installer. Hot liquid supply Water seal Air gap Open drain LTS-OM-09

4 Overview Figure 4-1: Dimensions, LTS models 25C and 100C (one heat exchanger) Front view Side view K L H J A 5/16" dia. (M8) mounting holes D E F C B OM-931 OM-932 Table 4-1: LTS dimensions LTS model number Description 25C 100C inches mm inches mm A Overall height* B Face width C Face length D E F Distance from bottom to return outlet of heat exchanger Distance from bottom to supply inlet of heat exchanger Distance from side to heat exchanger H Hot liquid return outlet J Hot liquid supply inlet K Distance from side to steam outlet L Distance from front to steam outlet Notes: * Add 23.5" (597 mm) to overall height when LTS is mounted on optional support legs. C = Copper heat exchanger with nickel coating

5 Overview Figure 5-1: Dimensions, LTS models 400C (two heat exchangers) Front view Side view K L H A J D E F G B C LTS-OM-03 Table 5-1: LTS dimensions LTS model Description 400C inches mm A Overall height* B Face width C Face length D Distance from bottom to return outlets of heat exchangers E Distance from bottom to supply inlets of heat exchangers F Distance from side to first heat exchanger G Distance from side to second heat exchanger H Hot liquid return outlet J Hot liquid supply inlet K Distance from side to steam outlet L Distance from front to steam outlet Notes: * Add 22.5" (572 mm) for total height with H-legs. C = Copper heat exchanger with nickel coating

6 Overview Table 6-1: LTS output capacities using hot water Output (lbs/hr and kg/h) LTS model number Flow Hot water supply temperature 240 F 116 C 250 F 121 C 260 F 127 C 280 F 138 C Pressure drop through heat exchanger gpm L/m lbs/hr kg/h lbs/hr kg/h lbs/hr kg/h lbs/hr kg/h psi kpa C C C* Notes: * Two heat exchangers and two valves C = Copper heat exchanger with nickel coating The LTS is not ASME-certified.

7 Overview Table 7-1: LTS connection sizes Description Water makeup (fill) Drain Steam outlet Condensate return Hot liquid supply inlet and return outlet Connection size ¼" pipe thread (DN8), except in Europe where it is DN10 ¾" (DN20) for models 25C and 100C 1" (DN25) for models 400C Varies with capacity and dispersion type. To determine outlet size, see Dri-calc or the Maximum steam carrying capacity of interconnecting hose, tubing, or pipe table in the DRI-STEEM Design Guide. ¾" pipe thread (DN20) See dimensions tables. Table 7-2: LTS weights LTS model number Shipping weight Operating weight lbs kg lbs kg 25C C C Table 7-3: Properties of water 212 F to 340 F (100 C to 171 C) * Temperature Pressure F C psia kpa Note: * Valves supplied by DRI-STEEM have a maximum inlet water temperature of 280 F (138 C).

8 Installation Locating the humidifier When selecting a location for the humidifier, consider the following: primarily top, left side, and front (see clearance recommendations hose, tubing, or piping optional equipment condensate return piping such as power distribution transformers and high horsepower motors controlled by variable frequency drives.

9 Installation Figure 9-1: LTS clearance recommendations For recommended service and maintenance purposes, maintain the following clearances: Left side with control cabinet mounted: 36" (914 mm) Left side: 24" (610 mm) for access to cleanout plate Top: 18" (457 mm) Rear: 6" (152 mm) Angle iron support leg Front: 36" (914 mm) Right side: 6" (152 mm) Bottom: 24" (610 mm) LTS-OM-04

10 Installation Table 10-1: Mounting options by model Mounting method Trapeze H-legs Support legs Wall brackets LTS/LTS-DI models 25C, 100C 400C Standard Optional Standard Optional X X X X Mounting methods To ensure that the water level control system works properly, the tank must be mounted level side to side and front to back. water damage. Support legs, trapeze hanger, and wall brackets are not available for LTS/LTS-DI models 400. These models must use H-legs. The mounting methods described in this manual are the only options available to maintain compliance to the UL 998 standard; alternate mounting methods will compromise the humidifier s CE, ETL, and C-ETL approvals. IMPORTANT: Installation must comply with governing codes.

11 Installation Trapeze hanger (LTS/LTS-DI models 25 and 100 only) Secure threaded rod to an overhead structure that is strong enough to support the operating weight of the LTS/LTS-DI humidifier and field installed piping, plus the weight of the control cabinet if it is mounted on the humidifier. Adjust the mounting so that the tank sets level side to side and front to back. Verify level after the tank is filled and is at operating weight. Figure 11-1: Trapeze hanger (LTS models 25C and 100C only) Secure rods to overhead construction Overhead installation Do not install water piping and humidifiers above expensive apparatus or equipment. A broken water pipe, leaking valve gland, condensation or other water leaks can occur causing serious damage and costly repairs to the equipment below. If this type of installation cannot be avoided, install a drip tray constructed of galvanized sheet metal under the humidifier, valve, etc., to catch potential water drips (see Figure 11-1). Pipe the overflow from the LTS directly to a floor drain do not drain the LTS into the drip pan. Terminate the drip pan and the LTS overflow drains above an open floor drain. Provide 18" (457 mm) minimum clearance above cover 1¼" (DN32) minimum Drip pan recommended in overhead installations (by installer) to prevent possible water damage 3/8" (M10) threaded rod of length required Angle or channel sized to properly support humidifier Humidifier drain to appropriate building waste. Do not drain humidifier directly into drip pan. Install water seal as shown on Pages 24 and % larger than humidifier DC-1453 IMPORTANT: Installation must comply with governing codes.

12 Installation Figure 12-1: Support legs (LTS models 25C and 100C only) Optional set of four legs and hardware OM-933 Figure 12-2: H-legs (required for LTS models 400C) Support legs (LTS/LTS-DI models 25 and 100 only) Use enclosed bolts, nuts, and washers to fasten legs to tank. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and is at operating weight. H-legs (LTS/LTS-DI models 400 only) While the LTS and LTS-DI tank is securely held in the air, be accomplished by having the bolts slightly loose as the tank is lowered to the floor. Then tighten them after the unit is place. Adjust the mounting so the tank sets level side to side and front to back. Verify the tank is level after it is filled and at operating weight. LTS-OM-05 IMPORTANT: Installation must comply with governing codes.

13 Installation Wall brackets (LTS/LTS-DI models 25 and 100 only) W minimum fasteners as described below. Mounting the LTS/LTS-DI on concrete or block walls: Position the wall brackets so that when fastened they will be flush with the inside of the front and back flanges of the LTS/ LTS-DI tank. humidifier. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and at operating weight. Mounting Model LTS/LTS-DI 25 on a wood stud wall: center. Position the wall brackets so that when fastened they will be flush with the inside of the front and back flanges of the LTS/ LTS-DI tank, and fasten to the horizontal timbers. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and at operating weight. Mounting Model LTS/LTS-DI 100 on a wood stud wall: center. Position the wall brackets so they are flush with the inside of the front and back flanges of the LTS/LTS-DI tank, and fasten to the horizontal timbers. Shim or adjust so the tank sets level side to side and front to back. Verify level after the tank is filled and at operating weight. Mounting the LTS/LTS-DI on metal stud walls: backside of the wall. Run a bolt with a washer through the face IMPORTANT: Installation must comply with governing codes. Figure 13-1: Wall brackets (LTS models 25C and 100C only) A DRI-STEEM optional wall brackets (two required) LTS model A B in. mm in. mm 25C C B DC-1454

14 Figure 14-1: LTS Outdoor Enclosure with standard or optional steam outlet, elevation view Standard steam outlet K Ventilation fans Optional steam outlet LTS humidifier A Power block See Note 2 below 6.5" Knockouts, 4" (102 mm) on center Enclosure drain 1½" pipe thread (DN40) with male nipple L Pipe chase G DC-1476 Notes: 1. The Outdoor Enclosure has two available steam distribution configurations. The standard configuration has a steam outlet on the right side of the Outdoor Enclosure for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the Outdoor Enclosure and down through the enclosure pipe chase into a building. 2. There are four knockouts located on the right and left side of the enclosure. Knockout sizes are 1½" (hole dia. 50 mm) for LTS models , and 2" (hole dia mm) for LTS models Run the electrical power into the enclosure at these knockouts. 3. All piping from the LTS unit to the steam outlet is stainless steel pipe. Depending on the application, interconnecting piping from the steam outlet to the dispersion assembly can be tubing, pipe or DRI-STEEM vapor hose. 4. The preferred location for the LTS hot liquid valve is inside the Outdoor Enclosure. If one of these valves must be located inside the building, it must be located within 6' (1.8 m) of the humidifier to reduce pressure drop. 5. See the dimensions table on the next page.

15 Figure 15-1: LTS Outdoor Enclosure, top view Valve access door: Optional steam outlet (exits enclosure through pipe chase) C J E Valve access door Pipe chase extending 1" (25 mm) above enclosure floor D H F Valve section heater Intake ventilation fan Enclosure drain Standard steam outlet (exits enclosure here) LTS humidifier Control panel Control panel heater Electrical and cleanout access door Intake ventilation fan B Table 15-1: LTS Outdoor Enclosure dimensions* LTS or LTS-DI model number Item Description inches mm inches mm A Enclosure height B Enclosure width C Pipe chase position D E Pipe chase size F G H Steam pipe position J K L Enclosure length Note: * See drawings on this and the previous page.

16 Specifications using an Outdoor Enclosure with a heater package. using an Outdoor Enclosure without a heater package. Note: The Outdoor Enclosure is only available in the United States and Canada. Table 16-1: LTS Outdoor Enclosure weights LTS or LTS-DI model number Outdoor Enclosure shipping weight* Table 16-2: LTS Outdoor Enclosure connection sizes Outdoor Enclosure operating weight* lbs kg lbs kg LTS LTS LTS Note: * Includes humidifier Description LTS or LTS-DI model number Water makeup (fill) ¼ pipe thread (DN8) ¼ pipe thread (DN8) Drain ¾ (DN20) 1 (DN25) Condensate return ¾ pipe thread (DN20) ¾ pipe thread (DN20) Steam outlet See the LTS catalog

17 Figure 17-1: Outdoor enclosure installation detail Normally closed fill valve (by factory) Make-up water supply piping (by installer) (See Note 2) Open to drain Vent with check valve (by installer) Humidifier Disconnect (by installer); see Detail A 120 V supply 120 V from unit disconnect or other source (See Note 1) Roof decking Drain line, min. 1½" electric valve (See Note 3) 120 V N Detail A Normally closed (fail closed) min 3/8" electric valve (by installer) Optional water seal (P-trap) drain line, min. 1½" (DN40) (See Note 3) Normally open (fail open) min ½" electric valve (by installer) Disconnect box Domestic water, 80 psig (582 kpa) maximum Open drain (See Note 4) Open drain (See Note 4) Heated building interior To valves (by installer) (See Note 1) To LTS humidifier OM-7558 Piping notes: 1. Insulate supply water piping to avoid dripping from condensation. To ensure that water does not remain in the fill line and freeze if there is a loss of power, DRI-STEEM recommends field installing additional valves upstream of the fill valve in a conditioned space. Power these valves on the same circuit as the LTS; if the power goes off, water drains out of the fill line to prevent freezing (see Figure 17-1). Supply power for these valves from the same circuit that supplies the LTS. 2. Ensure that water lines are protected from freezing conditions. thermostat with a remote sensor on the fill line to cut power to the LTS and safety valves to stop fill water to the LTS and drain the fill piping when the temperature is below freezing. 3. DRI-STEEM recommends copper or iron drain piping for outdoor enclosures. On a loss of power the tank water will drain, but not be cooled by the Drane-kooler because of the field supplied safety shut-off valves. If it is critical to keep the Drane-kooler functional in the case of a power loss, disconnect the Drane-kooler and relocate it down inside the conditioned space of the building. Pipe the supply water for the Drane-kooler before the safety shut-off valves. 4. If copper or iron piping is used for both the fill and drain piping, these drains may be tied together. Locate 1" air gap only in spaces with adequate temperature and air movement to absorb flash steam; otherwise, condensation may form on nearby surfaces. Refer to governing codes for drain pipe size and maximum discharge water temperature.

18 Figure 18-1: Outdoor Enclosure mounting options Flush Curb 14" (356 mm) Legs (LTS ) 14" (356 mm) DC-1110 OM-1095 OM-1096 Outdoor Enclosure mounting enough clearance for opening the access doors. support the unit and that support structure dimensions coincide with unit dimensions. fan outlets, gasoline storage, or other contaminants that could potentially cause dangerous situations. The use and storage of gasoline or other flammable vapors and liquids in open containers in the vicinity of this appliance is hazardous. intake of snow or splashed rain. Locate the Outdoor Enclosure so that prevailing winds do not blow into the air intakes. to installing the unit. may have become loosened. Check that all nuts are tightened. enclosure. It is recommended that the electrical power is run into the enclosure at these knockouts. In both cases it must be lifted from the bottom base using a method that holds it level, and keeps it from tipping, falling, or twisting. If the unit is severely twisted during handling, permanent damage may occur. It is the installer s responsibility to verify the handling equipment s capability to safely handle the unit. across the entire unit could cause tipping resulting in unsafe conditions or damage to the unit. base frame and/or special lifting lug hooks installed on the unit. All lifting operations must be accomplished with a load spreader of sufficient width to ensure that the lifting cables clear the side of the unit. If this type of spreader is not available, wood strips should be inserted between the cables and unit where necessary. All four lifting points must be used and will be marked lift here on the unit.

19 configurations. The standard configuration has a steam outlet on one side of the Outdoor Enclosure for connecting to steam dispersion unit piping. The optional internal steam distribution configuration routes steam within the Outdoor Enclosure and down through the pipe chase into a building. See drawings on Page 15. pipe chase is provided to maintain proper pressure within the enclosure in the event that this opening is not utilized. However, it is recommended that this pipe chase be used for both the supply water piping and drain piping, in which case the pipe proper enclosure pressure. cannot be used, the supply water and drain piping can be run through the knockouts, although preferably on the opposite side from the utility connections. controlled heaters are provided: one strip heater is located in the control cabinet section, and one strip heater is located in the front section to keep the enclosure at a constant minimum temperature. drain from the enclosure through this drain. Outdoor Enclosure. The keypad must not come in contact with the strip heaters or block the intake ventilation hood. located in a severe climate, a remote mount keypad should are available as an option for this mounting configuration transporting to the roof. Curbs are manufactured of 16-gauge galvanized steel and shipped with all hardware for bolt-together assembly. All holes are matched before leaving the factory. Curb curb gasket with adhesive on one side is supplied with hardware. The gasket must be installed between the top of the curb and the base surface of the Outdoor Enclosure to prevent moisture from leaking into the building from either driving rain or melting snow. An installation drawing is also included. Important note about Outdoor Enclosure installation hot liquid valve is inside the Outdoor Enclosure. If one of these valves must be located inside the building, it must be located within 6' (1.8 m) of the humidifier to reduce pressure drop. Figure 19-1: Outdoor Enclosure clearances Left side: 36" (914 mm) Front: 36" (914 mm) Top: Keep open for access Back: 12" (305 mm) OM-955 Right side: 24" (610 mm)

20 Note: If your LTS humidifier uses a LW417 controller, the aquastat option must be purchased to provide freeze protection. are provided with all the necessary hardware for elevating stand legs should be securely mounted to the grade by the installing contractor. To prevent the outdoor environment from penetrating the enclosure, close-off provisions must be made between the stand legs. steel pipe. Depending on the application, interconnecting piping from the steam outlet to the dispersion assembly can be tubing, pipe or DRI-STEEM vapor hose. Enclosure is recommended. Insulated or heat taping of water piping is recommended. Figure 20-1: Typical rooftop installation overview Flue Humidifier in Outdoor Enclosure Roof surface Electrical connections Steam piping Remote Vapor-logic3 keypad Drain piping Water piping Curb DC-1210M

21 Operation When power is applied to the Outdoor Enclosure: humidifier is not allowed to operate unless the temperature The strip heaters will power down when the temperature inside humidifier will allow the humidifier to continue operating until to cool the electronic components. greater, a high limit switch powers down the humidifier. The ventilation fans will continue to run and, once the enclosure automatically resume normal operation. Maintenance Outdoor Enclosure electrical service door. annually. CAUTION: Always shut off electrical service disconnect prior to working on the humidifier.

22 Installation Figure 22-1: Field piping overview for LTS models 25C and 100C (models with one heat exchanger) ¾" pipe thread (DN20) dispersion unit condensate return inlet Water supply shut-off valve, by installer Water supply line; water pressure range 25 psi to 80 psi (172 kpa to 582 kpa); water conductivity minimum 2 grains/gallon (100 μs/cm) Shock arrester recommended to reduce water hammer, by installer Steam vapor outlet Install level Optional condensate return piping from dispersion unit Unions, by installer Air vent tube Modulating valve Install level Manual or electric drain valve LTS-OM-01 6" (152 mm) minimum H2: Air vent height must be equal to or greater than H2 (see table below) Hot liquid return Hot liquid supply ¾" (DN20) minimum condensate drain piping rated for 212 F (100 C) See valve detail drawing on Page 23 H1 Pitch 1/8"/ft (1%) ¾" (DN20) minimum drain, skim and overflow piping rated for 212 F (100 C) Overflow line Water seal line If run is over 10' (3 m), increase pipe to 1¼" (DN32) Water seal line MUST be below drain valve to ensure humidifier drains correctly 1" (25 mm) air gap Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements Table 22-1: Heights required to overcome humidifier internal pressure (H1, H2) Unit output Water seal height (H1) Air vent height (H2) lbs/hr kg/h inches mm inches mm > 183 > Figure 22-1 notes: recommended for constant system flow. If variable system flow is desired, a two-way valve located in the hot liquid return line is recommended. rising into the humidifier. skim/overflow port, eliminating the possibility of backflow or required; however, governing codes prevail. of entrained air. DRI-STEEM warranty.

23 Installation Figure 23-1: Field piping overview for LTS-DI 400C (DI model with two heat exchangers) Steam vapor outlet ¾" pipe thread (DN20) dispersion unit condensate return inlet Water supply line; water pressure range 25 psi to 80 psi (172 kpa to 582 kpa); first 3' (1 m) is recommended to be stainless steel tubing with a 2" (50 mm) water seal or loop in the supply line to isolate steam during DI/RO water system maintenance Install level Optional condensate return piping from dispersion unit Strainer, by installer Air vent tube Modulating valve Hot liquid return Install level Hot liquid supply Manual or electric drain valve 6" (152 mm) minimum Air vent height must be equal to or greater than H2 (see table on Page 22) ¾" (DN20) minimum condensate drain piping rated for 212 F (100 C) See valve detail below Unions, by installer H1 Overflow line Pitch 1/8"/ft (1%) 1" (DN25) minimum drain and overflow piping rated for 212 F (100 C) Water seal line If run is over 10' (3 m), increase pipe to 1¼" (DN32) Water seal line MUST be below drain valve to ensure that humidifier drains correctly 1" (25 mm) air gap Open floor drain. Refer to governing codes for drain pipe size and maximum temperature requirements LTS-OM-13 Figure 23-1 notes: for constant system flow. If variable system flow is desired, a twoway valve located in the hot liquid return line is recommended. rising into the humidifier. overflow port, eliminating the possibility of backflow or siphoning however, governing codes prevail. of entrained air. DRI-STEEM warranty. standard water system or for piping a system with one heat Figure 23-2: Three-way valve detail AB B Hot liquid return From heat exchanger To heat exchanger Hot liquid supply When the three-way valve is retracted (in the up position), flow is from B to AB, bypassing the heat exchanger. LTS-OM-21 A

24 Installation Figure 24-1: Drane-kooler water tempering device Drain piping The drain line piped from the humidifier must be run to an approved sanitary waste or suitable drain. If nonmetallic pipe continuous operating temperature. DRI-STEEM's Drane-kooler, shown mounted to a typical humidifier, tempers discharged water temperature. For other Drane-kooler mounting options or for more information, contact DRI-STEEM or view the Drane-kooler product data sheet in the literature section at OM-951a and drain water dumped into the floor drain will cause flash steam. This steam will rise and saturate electrical components, adversely affecting component life and performance. skim water from the humidifier be tempered before it is discharged into the building drain piping. The Drane-kooler option will To allow normal operation and prevent steam from escaping through the drain line, the installer must provide a water seal of a sufficient height to contain the pressure developed in the humidifier system. See the table on Page 22 for water seal heights. Drain piping after the water seal must be pitched a minimum of pitch. water to be lifted by a pump, DRI-STEEM offers a condensate pump option. A check valve is required on the discharge of the pump. Electrical power for the pump is independent of the humidifier. Plug the pump into a wall outlet; an integral float switch turns the pump on and off.

25 Installation Drain piping (continued) LTS humidifier should place a union directly after the factory drain fitting, provide mount the humidifier closer to the floor, use the Alternate water seal and drain valve piping diagram shown on this page. The installer needs to rework the factory piping that connects the drain valve to the skim/overflow fitting, cut out the elbow, and repipe per the diagram. The LTS-DI humidifier has a pipe thread fitting on the drain valve and on the overflow fitting. Prior to dumping into a drain, the installer needs to connect the drain and overflow, provide a water the humidifier closer to the floor, use the Alternate water seal and drain valve piping diagram shown on this page. Alternate water seal and drain valve piping Typically, the water seal height dictates the minimum dimension the bottom of the humidifier can be above the floor. The alternate water seal reduces the water seal piping below the humidifier up to Figure 25-1: Alternate water seal and drain valve piping Skimmer outlet Top of water seal must be below skimmer outlet H1 (see table on Page 22) Drain connection Air gap Open drain OM-945 Notes: drain connection, such as when the humidifier is mounted near the floor.

26 Installation Water supply piping general instructions air gap to prevent back siphoning into a potable water system. However, some governing codes may require additional protection such as a vacuum breaker or backflow preventer. The supply water pressure range must be 25 psi to 80 psi (172 kpa LTS model (standard water) water supply piping The water supply assembly includes a strainer, needle valve, and fill Since the primary component of the water supply assembly is a solenoid valve, there may be noise issues that surface during a fill cycle. During a fill cycle, the supply water drops the water temperature in the tank and may collapse the steam, which can cause a low rolling sound. To diminish this, adjust the needle valve to decrease the water fill rate and/or use hot supply water. In cases where water hammer occurs when the fill solenoid closes, a shock arrester is recommended. Reducing the supply water may diminish the noise, but installing a shock arrester is the best solution. The minimum water conductivity for the LTS standard water

27 Installation Water supply piping (continued) LTS-DI model water supply piping drain option, a solenoid valve is added on the inlet of the float valve. The end-of-season feature shuts off the fill water supply and drains the tank when there is no demand for humidity for 72 hours. (This length of time is a default setting and is user-adjustable if your system has a Vapor-logic3 controller. See the Vapor-logic3 Installation and Operation Manual Note: Damage caused by chloride corrosion is not covered by your DRI-STEEM warranty. When using nonmetallic tubing for supply water, it must be rated of noninsulated stainless steel pipe directly off the humidifier prior to connecting to the nonmetallic tubing. When using nonmetallic water seal/loop in the supply line to isolate steam during DI/RO water system maintenance. DRI-STEEM recommends installing a strainer in the water supply line to prevent clogging of the float valve orifice. A strainer is highly recommended when the humidifier has the end-of-season drain option. The strainer will prevent particulate from collecting at the solenoid valve seat. If the LTS-DI humidifier is supplied with tap water, the float valve assembly will become clogged and the humidifier will operate without water.

28 Installation CAUTION: Only qualified electrical personnel should perform installation procedures. Where to find wiring diagrams interconnection requirements. devices: airflow proving switches, high limits, transmitters, or humidistats. All wiring must be in accordance with all governing codes and with LTS wiring diagrams. CAUTION: When drilling holes in the control cabinet, make sure the unit is powered off, protect all internal components from debris, and vacuum out the control cabinet when finished. Failure to comply with this directive can damage sensitive electronic components and void your DRI-STEEM warranty. Electrical installation Wiring and branch circuit protection is provided by the installer LTS humidifiers have a 120-volt, single phase electrical supply and capacity requirements against those listed on the name plate. Wiring requirements The length of wire from the control cabinet to the humidifier must the controller is the LW417, the length of wire from the control The top portion of the control cabinet contains control circuitry; the bottom portion of the control cabinet contains power circuitry. Place conduit connection holes in the control cabinet so that the control and power wire routing is limited to their respective sides of the control cabinet. Control wiring and power wiring must be run in dedicated or separated earthed metal conduit, cable trays, or trunking. The control cabinet should be mounted in a location convenient for door. The installer is responsible for making electrical connections at the power terminals.

29 Installation Control wiring wiring should minimize electrical noise problems: wiring must be minimum 18-gauge (1 mm 2 grounding. (1 mm 2 can be wired using minimum 18-gauge (1 mm 2 grounding. transmitter end. be minimum 18-gauge stranded wire run in a separate conduit 2 18-gauge (1 mm 2 wire with a bare drain wire for grounding. CAUTION: When drilling holes in the control cabinet, make sure the unit is powered off, protect all internal components from debris, and vacuum out the control cabinet when finished. Failure to comply with this directive can damage sensitive electronic components and void your DRI-STEEM warranty. IMPORTANT: Do not use shielded (screened) cable for water level control devices.

30 Installation IMPORTANT: Failure to follow these wiring procedures can result in erratic operation or failure. This product has been tested at the factory for proper operation. Product failures resulting from faulty handling, incorrect wiring, or shorting of wires together on external components are not covered under your DRI-STEEM warranty. Review information and diagrams before proceeding. Grounding requirements The approved earth ground must be made with solid metal-tometal connections and must be a good conductor of radio Ground wire should be the same AWG (mm 2 When the control cabinet is mounted remotely from the humidifier, a ground wire is necessary from the machine ground lug on the humidifier to the machine ground lug in the control cabinet. The bonding machine ground wire should be no less than 14-gauge AWG (mm 2 requirements. Figure 30-1: Humidifiers with Vapor-logic3 control Brown or black, top probe rod (full water condition) Orange or white, middle probe rod (refill water condition) Violet or red, bottom probe rod (low water condition on standard water models) OM-VL3-11 Figure 30-2: Humidifiers with LW417 control To humidifier probe head on tank Brown, top probe rod (full water condition) Orange, middle probe rod (refill water condition) Violet, bottom probe rod (low water condition ) Probe wiring V O BR OM-829a

31 Installation Selecting the dispersion assembly location the water vapor being discharged is carried off with the airstream and does not cause condensation or dripping from the duct. air can most readily absorb the moisture being added without causing condensation at or after the unit. This normally will be after the heating coil or where the air temperature is highest. high efficiency filter. The filter can remove the visible moisture and become waterlogged. impinge on a metal surface. impinge on fire or smoke detection devices. duct. The unit can put more moisture in one branch than the other. DRI-STEEM's Humidification System Design Guide available at Note: Most DRI-STEEM literature is available for downloading and printing from our website, Where to find specific installation instructions by product about interconnecting piping and drip tee installation Ultra-sorb LV and LH Installation, Operation and Maintenance manual. instructions, see Pages

32 Installation IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s). Connecting humidifier to dispersion assembly with vapor hose that can affect humidifier system performance adversely. Using hose from alternative manufacturers increases the possibility of discharge at the dispersion assembly. aging, causing the vapor hose to become hard and susceptible to failure due to cracks. smaller than the humidifier steam outlet. use the recommend installation as shown on Page 34. chart on Page 35. Connecting humidifier to dispersion assembly with tubing or pipe adapters convert a tubing outlet on the humidifier to threaded pipe, allowing a pipe connection. apart. heavy wall pipe.

33 Installation Connecting humidifier to dispersion assembly with tubing or pipe (continued) condensation. lubricants used to thread the pipe. This will minimize the possibility of tank foaming. Denatured alcohol or mineral spirits work best for removing lubricant. use the recommend installation as shown on Page 34. Table 33-1: Maximum steam carrying capacity and length of interconnecting vapor hose, tubing, and pipe* Vapor hose Copper or stainless steel tubing and Schedule 40 steel pipe Hose I.D. Maximum capacity Maximum length** Tube or pipe size*** Maximum capacity Maximum developed length inches DN lbs/hr kg/h ft m inches DN lbs/hr kg/h ft m 1½ ½ * Based on total maximum pressure drop in hose, tubing, or pipe of 5" wc (1244 Pa) ** Maximum recommended length for vapor hose is 10' (3 m). Longer distances can cause kinking or low spots. *** To minimize loss of capacity and efficiency, insulate tubing and pipe. Developed length equals measured length plus 50% of measured length to account for pipe fittings. Requires flange connection When using vapor hose, use DRI-STEEM vapor hose for best results. Field-supplied hose may have shorter life and may cause foaming in the evaporating chamber resulting in condensate discharge at the dispersion assembly. Do not use vapor hose for outdoor applications.

34 Installation Install a drip tee as show below when the humidifier is mounted higher than the dispersion assembly, when interconnecting hose or piping needs to go over an obstruction, or when interconnecting piping runs are long. IMPORTANT: Vapor hose must be supported to prevent sagging or low spots. Figure 34-1: Drip tee installation (piping over an obstruction) 90 long sweep or two 45 elbows Pitch Obstruction Insulate tubing and hard pipe to reduce steam loss LTS humidifier To dispersion assembly 6" (150 mm) minimum 8" (200 mm) minimum Tubing or pipe drip tee, by installer ¾" (DN20) Notes: 1" (25 mm) air gap Funnel or floor drain DC-1470

35 Installation Installation installing Single and Multiple dispersion tube assemblies tube applications Dispersion tube mounting point up. Condensate drain piping IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s). Table 35-1: Hose kit sizing by capacity Maximum humidifier capacity Hose kit lbs/hr kg/h ½" (DN40) with drain " (DN50) with drain > 85.2 >38.6 These models require Multiple dispersion tube assemblies and cannot use a hose kit. Table 35-2: Pitch of dispersion tube(s) and interconnecting piping for Single or Multiple dispersion tubes evaporative units* Condensate drain Type of interconnecting piping Diameter of dispersion tube and interconnecting piping Pitch of interconnecting piping Pitch of dispersion tube(s) Pitch of condensate drain Without drain Vapor hose Tubing or pipe 1½" (DN40) 2"/ft (15%) toward 2" (DN50) humidifier 1½" (DN40) 1/8"/ft (1%) toward humidifier 2" (DN50) 2"/ft (15%) toward humidifier No drain With drain Vapor hose Tubing or pipe 1½" (DN40) 2"/ft (15%) toward 2" (DN50) humidifier 1½" (DN40) ½"/ft (5%) toward humidifier ¼"/ft (2%) 2" (DN50) toward humidifier Note: When piping over an obstruction, see the drip tee installation illustration on the previous page. 1/8"/ft (1%) toward condensate drain ¼"/ft (2%) toward floor drain or toward humidifier if humidifier is below dispersion unit

36 Installation Figure 36-1: Single dispersion tube with condensate wasted to floor drain Vapor hose, tubing or pipe Duct Maximum capacity of dispersion tube: (25.8 kg/h) (38.6 kg/h) 90 long sweep or two 45 elbows Pitch* 3/8" (M10) mounting nut LTS humidifier 6" (152 mm) recommended ¼" (DN8) pipe thread Pitch tube toward drain 1/8"/ft (1%) Water seal 5" (127 mm) 1" (25 mm) air gap Notes: * Pitch vapor hose, tubing or pipe toward humidifier: 2"/ft (15%) when using vapor hose ½"/ft (5%) when using 1½" tubing or pipe ¼"/ft (2%) when using 2" tubing or pipe Condensate drain tube, by installer, minimum ¾" (DN20); must be suitable for 212 F (100 C) water Open drain. Refer to governing codes for drain pipe size and maximum temperature requirements. ½" (DN15) O.D. condensate drain tube; pitch ¼"/ft (2%) DC-1473a Figure 36-2: Dispersion tube escutcheon plates Figure 36-3: Single dispersion tube with condensate drain Dispersion tube plate 2.5" (64 mm) 3.25" (83 mm) Condensate drain plate 3.25" (83 mm) Thermal-resin tubelets (steam orifice inserts) Mounting bracket 1.5" (38 mm) 3.25" (83 mm) 3.25" (83 mm) OM-351c ¼" (DN8) pipe thread end Movable escutcheon plate. Plate can be mounted within limits of 2.5" (64 mm). ½" O.D. (DN15) copper tubing condensate drain OM-351b

37 Installation Figure 37-1: Single dispersion tube with condensate returned to humidifier Vapor hose, tubing, or pipe Duct Single dispersion tube with condensate drain 90% long sweep or two 45 elbows Pitch* Mounting nut, 3/8" (M10) ½" (13 mm) air vent 6" (152 mm) minimum 6" (152 mm) minimum ¼" pipe thread (DN8) 5" (127 mm) water seal Pitch tube toward drain 1/8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) LTS humidifier ¾" (DN20) condensate return connection (on face plate) Notes: * Pitch vapor hose, tubing or pipe toward humidifier: 2"/ft (15%) when using vapor hose ½"/ft (5%) when using 1½" tubing or pipe ¼"/ft (2%) when using 2" tubing or pipe H2 (see table, Page 22) Condensate drain tube, by installer, ¾" DN20 minimum. Return line piping material must be suitable for 212 F (100 C) water. DC-1473b

38 Installation Figure 38-1: Multiple dispersion tube with condensate wasted to floor Duct Multiple dispersion tube Vapor hose, tubing, or pipe 90 long sweep or two 45 elbows LTS humidifier Pitch* Water seal 5" (127 mm) 1" (25 mm) air gap 6" (152 mm) ¼" (DN8) pipe thread Open drain Mounting nut, 3/8" (M10) Pitch tube toward drain 1/8"/ft (1%) ½" (DN15) O.D. condensate drain tube, pitch ¼"/ft (2%) Condensate drain tube provided by installer, ¾" (DN20) minimum Notes: * Pitch vapor hose, tubing or pipe toward humidifier: 2"/ft (15%) when using vapor hose ½"/ft (5%) when using 1½" tubing or pipe ¼"/ft (2%) when using 2" tubing or pipe DC-1048a

39 Installation General Rapid-sorb installation instructions this manual. of all Rapid-sorb components with packing list. Report any shortages to DRI-STEEM factory immediately. provides necessary access in and around the ductwork or air handler. duct, or is installed across the face of a coil in an air handler. handler wall. duct or air handler wall. an additional hole in the center of the L-bracket. duct or air handler, refer to ALL pitch requirements for the The size, quantity, and location of penetrations are determined by the specific dimensions and configuration of the Rapid-sorb assembly you received. Note: The hardware for mounting the L-bracket to the duct or air handler wall and the hardware for the header support bracket is not provided. with Rapid-sorb header either inside or outside the duct. Contact your representative/distributor or DRI-STEEM for installation instructions for air handler or vertical airflow applications. IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s).

40 Installation IMPORTANT: Failure to follow the recommendations in this section can result in excessive back pressures on the humidifier. This will result in unacceptable humidification system performance such as leaking gaskets, blown water seals, erratic water level control, and spitting condensate from the dispersion tube(s). Rapid-sorb pitch requirements airflow duct, consider the following pitch issues: accomplished in the length of the hose cuffs used to connect the tubes to the header. pitch requirements. Table 40-1: Pitch of interconnecting piping, dispersion tubes, and headers for Rapid-sorb evaporative dispersion units Airflow Type of interconnecting piping Diameter of interconnecting piping Pitch of interconnecting piping Pitch of dispersion tubes Pitch of header Horizontal Vapor hose Tubing or pipe 1½" (DN40), 2" (DN50) 1½" (DN40), 2" (DN50), 3" (DN80), 4" (DN100), 5" (DN125), 6" (DN150) 2"/ft (15%) toward Rapid-sorb 1/8"/ft (1%) toward Rapid-sorb Vertically plumb 1/8"/ft (1%) toward condensate drain Vertical Vapor hose Tubing or pipe 1½" (DN40), 2" (DN50) 1½" (DN40), 2" (DN50), 3" (DN80), 4" (DN100), 5" (DN125), 6" (DN150) 2"/ft (15%) toward Rapid-sorb 1/8"/ft (1%) toward Rapid-sorb 2"/ft toward header 1/8"/ft (1%) toward condensate drain

41 Installation Figure 41-1: Rapid-sorb installed in a horizontal airflow with header outside the duct L-bracket Dispersion tube Airflow Tubelets (steam orifices) Duct 90 long sweep or two 45 elbows Slip coupling or hose cuff Pitch: 1/8"/ft (1%) Support bracket Vapor hose, tubing, or piping Header ¾" pipe thread (DN20) condensate drain ¾" (DN20) copper 1" (25 mm) air gap 5" (127 mm) 6" (152 mm) Open drain LTS humidifier DC-1471 Assembly and installation instructions for a Rapid-sorb installed with header outside the duct (horizontal airflow) 1. Locate and cut the holes in the ductwork for the dispersion tubes. Use the L-bracket as a template to locate the holes on the duct floor. 2. Temporarily, loosely suspend or support the header below the tube length dictates where the header should be suspended or supported temporarily. 3. Mount the dispersion tubes to the header with the provided connector, either a slip coupling or a hose cuff. take care not to shear the O-rings. the O-ring is resting on the face of the tubing. lubricant. 4. Position the flange of the L-bracket so it is upstream of the tubes

42 Installation Note: See Page 45 for steam supply and condensate drain line connection instructions. Assembly and installation instructions for a Rapid-sorb installed with header outside the duct (continued) L-bracket to the end of the dispersion tubes with the provided bolt, lock washer, and flat washer. 5. Before tightening the L-bracket bolts to the dispersion tubes follow these instructions: The dispersion tube will rotate in the slip coupling. Verify that the dispersion tube orifices are directed perpendicular to the airflow. The dispersion tube and slip coupling must be fully engaged on to the header stub for the O-rings to provide a seal. Before securing the hose cuff in place with the hose clamps on the dispersion tube and the header stub, verify that the dispersion tube orifices are directed perpendicular to the airflow. 6. Slide the assembly up until the L-bracket aligns with the mounting holes in the duct. The header pitch is duplicated in the L-bracket. The dispersion tube and slip coupling must be fully engaged on to the header stub for the O-rings to provide a seal. The high end of the L-bracket can be fastened tight to the duct or air handler. On the low end of the L-bracket, the fastener must be long enough to compensate for the pitch, and a nut should be provided and secured on both sides of the L-bracket and the duct or air handler for stability. cuffs to compensate for the pitch of the header. Before securing the hose cuff in place with the hose clamps on the dispersion tube and the header stub, verify that the 7. Permanently secure both ends of the header and verify that the 8. Verify that all fasteners are secure: 9. Secure and seal the dispersion tube escutcheon plate and condensate drain tube escutcheon plate around the respective tubes, if applicable.

43 Installation Figure 43-1: Rapid-sorb installed in a horizontal airflow with header inside the duct L-bracket Dispersion tube Tubelets (steam orifices) Airflow 90 long sweep or two 45 elbows Slip coupling or hose cuff Pitch: 1/8"/ft (1%) Duct Support bracket Vapor hose, tubing, or piping Header ¾" pipe thread (DN20) condensate drain ¾" (DN20) copper 5" (127 mm) 6" (152 mm) 1" (25 mm) air gap Open drain LTS humidifier DC-1472 Assembly and installation instructions for a Rapid-sorb installed with header inside the duct (horizontal airflow) 1. Locate and cut the holes in ductwork or air handler for steam header penetration, condensate drain piping, and header support support bracket when you drill the hole for the header support bracket fastener. 2. Loosely fasten the header in place. the duct. piping requirements, the header can be set on the floor of the air handler, assembled in the vertical position, and then raised and mounted in place. 4. Mount the dispersion tubes on the header with the slip couplings or hose cuffs. tubes, take care not to shear the O-rings. the O-ring is resting on the face of the tubing.

44 Installation Assembly and installation instructions for a Rapid-sorb installed with header inside the duct (continued) lubricant. 5. Allow the dispersion tubes to rest against the bottom of the duct. 6. Position the flange of the L-bracket so it is upstream of the tubes to the end of the dispersion tubes with the provided bolt, lock washer, and flat washer. 7. Rotate the assembly up until the L-bracket aligns with the mounting holes in the duct or air handler. The header pitch is duplicated in the L-bracket. The dispersion tube and slip coupling must be fully engaged on to the header stub for the O-rings to provide a seal. The high end of the L-bracket can be fastened tight to the duct or air handler. On the low end of the L-bracket, the fastener must be long enough to compensate for the pitch, and a nut should be provided and secured on both sides of the L-bracket and the duct or air handler for stability. use the hose cuffs to compensate for the pitch of the header. Before securing the hose cuff in place, with the hose clamps on the dispersion tube and the header stub, verify that the dispersion tube orifices are directed perpendicular to the airflow. 8. Verify that all fasteners are secure: 9. Secure and seal the header escutcheon plate around the header. 10. See Page 45 for steam supply and condensate drain line connection instructions.

STS Steam-to-Steam Humidifier

STS Steam-to-Steam Humidifier IMPORTANT: Read and save these instructions. STS Steam-to-Steam Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNING Indicates a hazardous situation that could result

More information

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual

CRUV. Electric Humidifier. Installation, Operation, and Maintenance Manual CRUV Electric Humidifier Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical support 800-328-4447

More information

Vaporstream Electric Humidifier. Installation, Operation, and Maintenance Manual

Vaporstream Electric Humidifier. Installation, Operation, and Maintenance Manual Vaporstream Electric Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNING Indicates a hazardous situation that could result in death or serious injury if instructions

More information

Vapormist Electric Humidifier. Installation, Operation and Maintenance Manual

Vapormist Electric Humidifier. Installation, Operation and Maintenance Manual Vapormist Electric Humidifier Installation, Operation and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical support 800-328-4447

More information

Vaporstream Electric Humidifier. Installation, Operation and Maintenance Manual

Vaporstream Electric Humidifier. Installation, Operation and Maintenance Manual Vaporstream Electric Humidifier Installation, Operation and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical support 800-328-4447

More information

READ AND SAVE THESE INSTRUCTIONS STS. Steam-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS STS. Steam-to-Steam Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS STS Steam-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNINGS AND CAUTIONS Warnings and cautions WARNING Indicates a hazardous situation that could

More information

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

XT Series Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual XT Series Electrode Steam Humidifier Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing humidifier. Leave manual with product owner. DRI-STEEM technical

More information

READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH. Electric Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH. Electric Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS HUMIDI-TECH Electric Humidifier Installation, Operation, and Maintenance Manual WARNINGS AND CAUTIONS Warnings and cautions WARNING Indicates a hazardous situation that

More information

GTS Gas-to-Steam Humidifier

GTS Gas-to-Steam Humidifier IMPORTANT: Read and save these instructions. GTS Gas-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNING! If the information in this manual is not followed exactly, a fire or explosion

More information

GTS Gas-to-Steam Humidifier

GTS Gas-to-Steam Humidifier IMPORTANT: Read and save these instructions. GTS Gas-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNING! If the information in this manual is not followed exactly, a fire or explosion

More information

DRI-STEEM MODEL STS and STS- DI

DRI-STEEM MODEL STS and STS- DI DRI-STEEM MODEL STS and STS- DI STEAM-TO-STEAM HUMIDIFIERS Installation, Operation, For toll-free technical support call 1-800-328-4447 TABLE OF CONTENTS To the purchaser and the installer and Maintenance

More information

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk VAPORSTREAM Electric-to-Steam Humidifier With Vapor-logic controller Web-enabled access Interoperability via Modbus or optional BACnet or LonTalk High-performance humidification APPLICATION VERSATILITY

More information

DRI-STEEM Models and LTS-DI

DRI-STEEM Models and LTS-DI READ AND SAVE THESE INSTRUCTIONS DRI-STEEM Models LTS and LTS-DI LIQUID-TO-STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Technical Support, Call: 1-800-328-4447

More information

READ AND SAVE THESE INSTRUCTIONS VAPORMIST. Electric-to-Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS VAPORMIST. Electric-to-Steam Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS VAPORMIST Electric-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNINGS AND CAUTIONS Warnings and cautions WARNING Indicates a hazardous situation

More information

DRI-STEEM Models LTS and LTS-DI

DRI-STEEM Models LTS and LTS-DI READ AND SAVE THESE INSTRUCTIONS DRI-STEEM Models LTS and LTS-DI LIQUID-TO-STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Technical Support, Call: 1-800-328-4447

More information

GTS. Installation, Operation, and Maintenance Manual WARNING. Gas-to-Steam Humidifier

GTS. Installation, Operation, and Maintenance Manual WARNING. Gas-to-Steam Humidifier READ AND SAVE THESE INSTRUCTIONS GTS Gas-to-Steam Humidifier Installation, Operation, and Maintenance Manual WARNING Fire or explosion hazard If the information in this manual is not followed exactly,

More information

Ultra-sorb Models LV and LH

Ultra-sorb Models LV and LH Ultra-sorb Models LV and LH Steam Dispersion Panels Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DRI-STEEM steam generating humidifier. Overview

More information

Steam Humidifier Models 1150 and 1160

Steam Humidifier Models 1150 and 1160 Humidifier Steam Humidifier Models 1150 and 1160 Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS PRODUCT OVERVIEW.............................. 3 Materials

More information

VAPORSTREAM Models VLC and VLDI

VAPORSTREAM Models VLC and VLDI READ AND SAVE THESE INSTRUCTIONS VAPORSTREAM Models VLC and VLDI ELECTRIC STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Customer Support, Call 1-800-328-4447

More information

READ AND SAVE THESE INSTRUCTIONS XTR. Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XTR. Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS XTR Electrode Steam Humidifier Installation, Operation, and Maintenance Manual Warnings and cautions WARNINGS AND CAUTIONS WARNING Indicates a hazardous situation that

More information

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS XT SERIES Electrode Steam Humidifiers Installation, Operation, and Maintenance Manual Warnings and cautions WARNINGS AND CAUTIONS WARNING Indicates a hazardous situation

More information

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual XTR Electrode Steam Humidifier Installation, Operation, and Maintenance Manual Safety precautions ATTENTION INSTALLER Read this manual before installing humidifier. Leave manual with product owner. DRI-STEEM

More information

Ultra-sorb Steam Dispersion Panels

Ultra-sorb Steam Dispersion Panels Ultra-sorb Steam Dispersion Panels PR0DUCT CATALOG Ultra-sorb Model LH Ultra-sorb Model LV Ultra-sorb Model XV DRI-STEEM takes the lead again with Ultra-sorb, establishing the industry standard for energy

More information

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS XT SERIES. Electrode Steam Humidifiers. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS XT SERIES Electrode Steam Humidifiers Installation, Operation, and Maintenance Manual Warnings and cautions WARNINGS AND CAUTIONS WARNING Indicates a hazardous situation

More information

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option XT SERIES Electrode Steam Humidifiers Easy to maintain Adaptable Comprehensive control with Vapor-logic option Cost-effective steam humidification XT Series electrode steam humidifiers from DriSteem provide

More information

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual Steam Injection Humidifiers for use with steam boilers Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. Where to

More information

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual Steam Injection Pressurized Steam Humidifiers Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical

More information

DRI-STEEM Models GTS and GTS-DI

DRI-STEEM Models GTS and GTS-DI READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. DRI-STEEM Models GTS and GTS-DI TM GAS-TO-STEAM HUMIDIFIERS TM User's/Installation Instructions

More information

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual Steam Injection Pressurized Steam Humidifiers Installation, Operation, and Maintenance Manual Safety precautions ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner.

More information

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL

ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. ULTRA-SORB STEAM DISPERSION TUBE HUMIDIFIER PANEL For Applications Using Steam From A Boiler

More information

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels Installation Instructions For the 18 Built-In Dishwasher and Front Color Panels Printed in USA 154232102 Before You Begin DO NOT INSTALL DISHWASHER UNTIL YOU HAVE READ ALL INSTRUCTIONS. FOR YOUR SAFETY,

More information

DRI-STEEM Models GTS. and GTS -DI

DRI-STEEM Models GTS. and GTS -DI READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. DRI-STEEM Models GTS and GTS -DI GAS-TO-STEAM HUMIDIFIERS Installation, Operation and Maintenance

More information

ES Series Electric Humidifier

ES Series Electric Humidifier Read and Save These Instructions Standard Water ES Series Electric Humidifier Installation Instructions Operation and Maintenance Manual ETL LISTED HUMIDIFIER Our results are comforting Form No: ESOM-08-08

More information

Ultra-sorb Steam Dispersion Tube Humidifier Panel

Ultra-sorb Steam Dispersion Tube Humidifier Panel Ultra-sorb Steam Dispersion Tube Humidifier Panel Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DRI-STEEM steam generating humidifier. Table of

More information

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option

XT SERIES. Electrode Steam Humidifiers. Easy to maintain Adaptable Comprehensive control with Vapor-logic option XT SERIES Electrode Steam Humidifiers Easy to maintain Adaptable Comprehensive control with Vapor-logic option Cost-effective steam humidification Model XTP XT Series electrode steam humidifiers from DriSteem

More information

Installation Instructions. Operation and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual TM READ AND SAVE THESE INSTRUCTIONS Deionized, Demineralized, or Reverse Osmosis Water SXDDR Series Steam Heat Exchanger Humidifier Installation Instructions Operation and Maintenance Manual Our results

More information

Quick Start Installation Guide

Quick Start Installation Guide Quick Start Installation Guide Nortec EL Electrode Steam Humidifier Overview Mounting Installation Requirements Standard Mounting Steam Distribution Installation Requirements Plumbing Water and Drainage

More information

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers. Issued 2006/08/01 Section 15751 Humidifiers Page 1 of 7 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section 01810 Commissioning..4 Section

More information

"SXDDR" Series Steam Heat Exchanger Humidifiers

SXDDR Series Steam Heat Exchanger Humidifiers SXDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "SXDDR" Series Steam Humidifiers Looking for an alternative to electrically generated humidification? Concerned about using chemically treated

More information

READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER. Water Tempering Device. Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER. Water Tempering Device. Installation, Operation, and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS DRANE-KOOLER Water Tempering Device Installation, Operation, and Maintenance Manual Table of Contents Overview Features Summary...................................... 1

More information

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY TM READ AND SAVE THESE INSTRUCTIONS CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Flex connectors (by PURE) AHU/duct casing Injection tube Stainless

More information

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual

XTR Electrode Steam Humidifier. Installation, Operation, and Maintenance Manual XTR Electrode Steam Humidifier Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing humidifier. Leave manual with product owner. DRI-STEEM technical support

More information

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access I nteroperability via Modbus or optional BACnet or LonTalk

VAPORSTREAM. Electric-to-Steam Humidifier. With Vapor-logic controller Web-enabled access I nteroperability via Modbus or optional BACnet or LonTalk VAPORSTREAM Electric-to-Steam Humidifier With Vapor-logic controller Web-enabled access I nteroperability via Modbus or optional BACnet or LonTalk High-performance humidification dristeem offers a complete

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

Installation Instructions. Operation and Maintenance Manual

Installation Instructions. Operation and Maintenance Manual READ AND SAVE THESE INSTRUCTIONS Standard Water SX Series Steam Heat Exchanger Humidifier Installation Instructions Operation and Maintenance Manual Our results are comforting PURE HUMIDIFIER and INTAC

More information

Installation Instructions

Installation Instructions Installation Instructions For the 18" Built-In Dishwasher Sears, Roebuck and Co. Sears Canada, Inc. Hoffman Estates, IL 60179 U.S.A. Toronto, Ontario, Canada M5B 2B8 154435201 Before You Begin DO NOT INSTALL

More information

Steam Injection. Humidification system

Steam Injection. Humidification system Steam Injection Humidification system Standard and CLEAN-STEEM TM models suitable for a wide range of applications DRI-STEEM s Steam Injection humidifiers use steam from an external source, such as an

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

DRI-STEEM Models GTS

DRI-STEEM Models GTS READ AND SAVE THESE INSTRUCTIONS This manual must be left with the owner and should be accessible for reference. DRI-STEEM Models GTS and GTS-DI GAS-TO-STEAM HUMIDIFIERS Installation, Operation and Maintenance

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

L A signature series TA T N E RE O, A L L A T S IN

L A signature series TA T N E RE O, A L L A T S IN signature series COMMERCIAL STEAM GENERATORS INSTALLATION, OPERATION AND MAINTENANCE MANUAL INSTALLATION MANUAL COMMERCIAL STEAM GENERATOR SIGNATURE SERIES (SS) INTRODUCTION Steam Sauna manufactures steam

More information

Installation Instructions for. OmniFount

Installation Instructions for. OmniFount Installation Instructions for OmniFount Congratulations, you have just purchased the finest watering fountain on the market. This unit is built to give you excellent service when properly installed and

More information

"ER" Series Electric Humidifier

ER Series Electric Humidifier ER-1 Standard Water "ER" Series Electric Humidifier The Electric Humidifier from PURE Humidifier Co. is loaded with features and options. All you need is tap water, electricity, and a sanitary drain the

More information

DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS

DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS READ AND SAVE THESE INSTRUCTIONS DRI-STEEM CRU SERIES ELECTRIC STEAM HUMIDIFIERS Installation Instructions and Maintenance Operations Manual For Toll-Free Customer Support, Call: 1-800-328-4447 UL RECOGNIZED

More information

CLe-series Dishwashers

CLe-series Dishwashers CLe-series Dishwashers Blower-dryer electric (CLe SERIES) ML-138211 ML-138212 ML-138213 ML-138214 electric (CLeR SERIES) ML-138325 ML-138326 ML-138327 ML-138328 STEAM (CLe SERIES) ML-138226 ML-138227 ML-138228

More information

THE SIX STEPS OF HUMIDIFICATION DESIGN

THE SIX STEPS OF HUMIDIFICATION DESIGN THE SIX STEPS OF HUMIDIFICATION DESIGN To help you better understand the humidification process, this issue of Engineering Humidification will walk you through the basic steps of humidification system

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications READ AND SAVE THESE INSTRUCTIONS ULTRA-SORB MODEL XV Steam Dispersion Panel Installation, Operation, and Maintenance Manual For pressurized steam applications Table of contents MECHANICAL SPECIFICATIONS..................................................1

More information

HE360 Humidifier Installation Kit

HE360 Humidifier Installation Kit HE360 Humidifier Installation Kit INSTALLATION INSTRUCTIONS WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and that

More information

Installation Instructions Owner s Manual

Installation Instructions Owner s Manual Installation Instructions Owner s Manual FOR USE WITH GAS, OIL and HYDRONIC FORCED AIR FURNACES SEQUENCE OF OPERATION The AUTOFLO Model s SC15 & 250 use the evaporative principal to add moisture to the

More information

Residential Steam Humidifier

Residential Steam Humidifier Residential Steam Humidifier Model HUMXXSTM3034 Residential Steam Humidifier Owner s Manual Includes Safety & Operating Instructions READ AND SAVE THESE INSTRUCTIONS TABLE OF CONTENTS Safety... 2 Introduction...

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 8413 - HUMIDIFIERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT

installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT installation and start-up instructions HUMIDIFIERS AND HUMIDISTAT HUM Cancels: II 912D-56-3 II HUM-56-1 7-98 MODEL HUMBBLFP1025-A-- FAN-POWERED HUMIDIFIER MODEL HUMBBLBP2018-A-- BYPASS HUMIDIFIER MODEL

More information

B.C.S. Shop Heaters 26, 30 & 36 (36 shown)

B.C.S. Shop Heaters 26, 30 & 36 (36 shown) BIOMASS COMBUSTION SYSTEMS, INC. 67 MILLBROOK ST., SUITE 502 WORCESTER, MA 01606 508-798-5970 - FAX 508-798-5971 B.C.S. Shop Heaters 26, 30 & 36 (36 shown) INSTALLATION MANUAL HAND FIRED SYSTEMS 8-09 Biomass

More information

VT Series. Service Kit Manual CAUTION

VT Series. Service Kit Manual CAUTION VT Series Electric Humidifier Service Kit Manual WARNING Indicates a hazardous situation that could result in death or serious injury if instructions are not followed. CAUTION Indicates a hazardous situation

More information

HE120, HE160 Humidifier Installation Kit

HE120, HE160 Humidifier Installation Kit HE120, HE160 Humidifier Installation Kit INSTALLATION INSTRUCTIONS WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and

More information

"ESDDR" Series Electric Humidifier

ESDDR Series Electric Humidifier ESDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "ESDDR" Series Electric Humidifier The Electric Humidifier from PURE Humidifier Co. is loaded with features and options. All you need is deionized,

More information

Installation. 15 W. Undercounter/Freestanding Ice Machine FGIM515 / CFGIM515 FPIM515 / CFPIM515

Installation. 15 W. Undercounter/Freestanding Ice Machine FGIM515 / CFGIM515 FPIM515 / CFPIM515 Installation 15 W. Undercounter/Freestanding Ice Machine FGIM515 / CFGIM515 FPIM515 / CFPIM515 TABLE OF CONTENTS Warnings & Important Safety Instructions 3 Dimensions (Professional) 5 Dimensions (Custom

More information

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½" bit

Electrical cable Water supply tube Fittings for tube Coupler Teflon tape. Hole saw min. 2½ bit Installation Parts and Tools Parts not Provided Electrical cable Water supply tube Fittings for tube Coupler Teflon tape Air gap Wire nuts for 6-gauge wiring Hose clamp ⅞" UL approved strain relief Electrical

More information

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panels

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panels READ AND SAVE THESE INSTRUCTIONS ULTRA-SORB MODEL MP Steam Dispersion Panels Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DriSteem steam generating

More information

Installation Instructions

Installation Instructions HUMBBSFP1016 HUMCCSFP1016 Small Fan Powered Humidifier and Humidistat Installation Instructions! WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death.

More information

Read and save these instructions! DRANE-KOOLER. Water tempering device Installation, operation and maintenance manual

Read and save these instructions! DRANE-KOOLER. Water tempering device Installation, operation and maintenance manual Read and save these instructions! DRANE-KOOLER Water tempering device Installation, operation and maintenance manual PLEASE: read this manual! This manual will guide you through installation, operation

More information

Installation Instructions for. CattleMaster Series Fountains

Installation Instructions for. CattleMaster Series Fountains Installation Instructions for CattleMaster Series Fountains Congratulations, you have just purchased the finest watering fountain on the market. This unit is built to give you excellent service when properly

More information

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual

Armstrong J Series Float, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual Armstrong J Series, Thermostatic Steam Traps, Condensate Controllers & Liquid Drainers Installation and Maintenance Manual This bulletin should be used by experienced personnel as a guide to the installation

More information

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here:

DISHWASHER. Models DW2432 and DW2432SS. Installation Manual. Write Serial Number (on inner door of unit) here: DISHWASHER Models DW2432 and DW2432SS Installation Manual Write Serial Number (on inner door of unit) here: Felix Storch, Inc. Summit Appliance Division 770 Garrison Avenue Bronx, New York 10474 www.summitappliance.com

More information

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL

TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL TIDALWAVE I/G POOL PUMP INSTRUCTION MANUAL READ THIS MANUAL CAREFULLY BEFORE USING YOUR PUMP 88 PUMP PARTS BREAKDOWN REF # Order # Mfr # Description 1 NEP4 AC 348 Lid Knobs NEP AC 380 Strainer Lid 3 NEP6

More information

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204 1976-360 (1-02) PP TABLE OF CONTENTS 1. Warnings......................................................

More information

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS

FLANGED CORR/GUARD CORR/GUARD INSTALLATION INSTRUCTIONS CORR/GUARD INSTALLATION INSTRUCTIONS This symbol on the nameplate means this product is listed by Underwriters Laboratories Inc. Tested to UL1738 / CAN / ULCS636-08 Listing No. MH26687 Testing No. 11EN

More information

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS VIKING 111 Front Street Greenwood, Mississippi 38930 USA (662) 455-1200 IMPORTANT - PLEASE READ AND FOLLOW Before beginning - please read these instructions

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS ,t_2007 Lennox Industries Inc. Dallas, Texas, USA INSTALLATION INSTRUCTIONS CH33 Series Units EVAPORATOR 505,264M (65484504) 10/07 Supersedes 09/06 COILS n _putech blications ical Litho U.S.A. RETAIN THESE

More information

HE220, HE260 Humidifier Installation Kit

HE220, HE260 Humidifier Installation Kit HE220, HE260 Humidifier Installation Kit WELCOME To the comfortable world of humidified air. When you use your Honeywell humidifier, you notice that your skin is not as dry, and that your scratchy throat

More information

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS CROWN Boiler Co Santa-Fe Series Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS These instructions must be affixed on or adjacent to the air handler Models: SAC049A20 SAC059A25

More information

SAFETY AND INSTALLATION MANUAL MODEL 8100

SAFETY AND INSTALLATION MANUAL MODEL 8100 SAFETY AND INSTALLATION MANUAL ENERGY RECOVERY VENTILATORS MODEL 8100 Provides year-round fresh air Recovers 77% of the apparent heating or cooling energy from the exhausted air See Warnings Page 3 Table

More information

Steam Humidification Light Commercial Applications. Better technology means better business.

Steam Humidification Light Commercial Applications. Better technology means better business. Steam Humidification Light Commercial Applications Better technology means better business. Aprilaire Steam Humidifiers are built to last. Through extensive research and over 50 years expertise in humidification

More information

READ AND SAVE THESE INSTRUCTIONS SEISMIC. Cer tification Option. Installation Manual

READ AND SAVE THESE INSTRUCTIONS SEISMIC. Cer tification Option. Installation Manual READ AND SAVE THESE INSTRUCTIONS SEISMIC Cer tification Option Installation Manual Warnings and cautions Indicates a hazardous situation that could result in death or serious injury if instructions are

More information

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS

RECOMMENDED LOCATION STEP BY STEP INSTALLATION. MODEL S 200P, 800BP and 97 POWER HUMIDIFIERS FOR USE WITH ALL FORCED AIR SYSTEMS SEQUENCE OF OPERATION The AUTOFLO Model s 200P, 800BP and 97 Humidifiers use the evaporative by-pass principal to add moisture into the return air duct of your central

More information

INSTALLATION MANUAL. Manufactured by AQUA-AIR MANUFACTURING. (801) or (800) FAX (801)

INSTALLATION MANUAL. Manufactured by AQUA-AIR MANUFACTURING. (801) or (800) FAX (801) INSTALLATION MANUAL Manufactured by AQUA-AIR MANUFACTURING 542 W. 47 Confluence East 800 South, Ave., Salt Ivins, Lake Utah City, 84738 Utah 84123 (801) 265-9699 or (800) 916-5777 FAX (801) 268-3856 (435)

More information

User s Information Manual

User s Information Manual Gas-fired Water boiler Series 2 NOTICE: Series 1/Series 2 identification Read the boiler rating plate to determine the series number. The rating plate is located on the right side of the boiler. User s

More information

Installation Instructions

Installation Instructions 8GXM / 0GXM Multi---Split High---Wall Duct Free Split System 8GXM --- Size 18k, k, and 0k 0GXM --- Size 9k, 1k, and 18k Installation Instructions NOTE: Read the entire instruction manual before starting

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL ELECTRONICALLY CONTROLLED STEAM HUMlDlFlERS DESIGN SERIES C & D INSTALLATION, OPERATION AND MAINTENANCE MANUAL CARNES COMPANY, P.O. Box 930040,446 S. Main St., Verona, WI. 53593-1499 - Phone: 608/845-6411

More information

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. EMIP INSTY-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Tube support AHU/duct Injection tube Typ. centers Flexible

More information

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC INSTALLATION INSTRUCTIONS GEO PRIME TANK (Patent Pending) GPC Table of Contents General Description 2 Installation 3 Flushing and Purging 5 Initial Start up 7 Adding or Checking Fluid 8 Replacing a Pump

More information

Installation Electric Dryers Instructions 01

Installation Electric Dryers Instructions 01 Installation Electric Dryers Instructions 01 Questions? Call 800.GE.CARES (800.432.2737) or visit our Web site at: GEAppliances.com This is the safety alert symbol. This symbol alerts you to potential

More information

Vapor-logic 3 to Vapor-logic4

Vapor-logic 3 to Vapor-logic4 Vapor-logic 3 to Vapor-logic4 Adaptor Board Installation Manual Warnings and c autions Warnings and cautions WARNING Indicates a hazardous situation that could result in death or serious injury if instructions

More information

Installation Guide. 15 W. Undercounter/Freestanding Nugget Ice Machine U L. Viking Range, LLC. 111 Front Street

Installation Guide. 15 W. Undercounter/Freestanding Nugget Ice Machine U L. Viking Range, LLC. 111 Front Street Installation Guide Viking Range, LLC 111 Front Street Greenwood, Mississippi 38930 USA (662) 455-1200 For product information, call 1-888-(845-4641) or visit our web site at vikingrange.com in the US or

More information