Testing and Performance Analysis of a Hollow Fibre-Based Core for Evaporative Cooling and Liquid Desiccant Dehumidification

Size: px
Start display at page:

Download "Testing and Performance Analysis of a Hollow Fibre-Based Core for Evaporative Cooling and Liquid Desiccant Dehumidification"

Transcription

1 Testing and Performance Analysis of a Hollow Fibre-Based Core for Evaporative Cooling and Liquid Desiccant Dehumidification M. Jradi 1, *, S. Riffat 2 1 Center for Energy Informatics, The Maersk Mc-Kinney Moller Institute, University of Southern Denmark, 5230 Odense M, Denmark 2 Institute of Sustainable Energy Technology, Department of Architecture and Built Environment, University of Nottingham, Nottingham NG7 2RD, UK * Corresponding author, mjr@mmmi.sdu.dk Phone: ; Address: Campusvej 55, DK-5230 Odense M, Denmark 1

2 Testing and Performance Analysis of a Hollow Fibre-Based Core for Evaporative Cooling and Liquid Desiccant Dehumidification M. Jradi 1, *, S. Riffat 2 1 Center for Energy Informatics, The Maersk Mc-Kinney Moller Institute, University of Southern Denmark, 5230 Odense M, Denmark 2 Institute of Sustainable Energy Technology, Department of Architecture and Built Environment, University of Nottingham, Nottingham NG7 2RD, UK Abstract * Corresponding author, mjr@mmmi.sdu.dk Phone: ; Address: Campusvej 55, DK-5230 Odense M, Denmark In this study, an innovative heat and mass transfer core is proposed to provide thermal comfort and humidity control using a hollow fibre contactor with multiple bundles of micro-porous hollow fibres. The hollow fibrebased core utilizes 12 bundles aligned vertically, each with 1000 packed polypropylene hollow fibres. The proposed core was developed and tested under various operating and ambient conditions as a cooling core for a compact evaporative cooling unit and a dehumidification core for a liquid desiccant dehumidification unit. As a cooling core, the fibre-based evaporative cooler provides a maximum cooling capacity of 502 W with a wet bulb effectiveness of 85%. As a dehumidification core and employing potassium formate as a liquid desiccant, the dehumidifier is capable of reducing the air relative humidity by 17% with an overall dehumidification capacity of 733 W and humidity effectiveness of 47%. Being cheap and simple to design with their attractive heat and mass transfer characteristics and the corresponding large surface area-to-volume ratio, hollow fibre membrane contactors provide a promising alternative for cooling and dehumidification applications. Keywords: Hollow fibre membrane; Liquid desiccant dehumidification; Evaporative cooling; Cooling capacity; Effectiveness. Nomenclature AC alternating current COP coefficient of performance EER energy efficiency ratio (Btu/Wh) h enthalpy (J/kg) HCOOK Potassium Formate LiBr Lithium Bromide LiCl Lithium Chloride m mass flow rate (kg/s) P v vapour pressure (mbar) PE polyethylene PEI polyetherimide PP polypropylene PTFE polytetrafluoroethylene PVC polyvinyl chloride PVDF polyvinylidene fluoride RH relative humidity (%) LiCl Lithium Chloride Q cooling capacity (W) T temperature ( C) w humidity ratio (kg H2O /kg air ) W electric power (W) Greek ε effectiveness 2

3 Subscripts a db Deh dp ele eq in out su wb air dry bulb dehumidification dew point electric equilibrium input output supply wet bulb 1 Introduction As an alternative and environmentally friendly cooling technology, evaporative cooling has a large potential to provide thermal comfort in occupied spaces due to the simple design, cheap materials and high coefficient of performance in addition to the efficient operation compared to conventional vapour compression-based cooling systems (Delfani et al. 2010; Hammoud, Ghali and Ghaddar 2014; Maheshwari, Al-Ragom and Suri 2001; Uçkan et al. 2013). Evaporative cooling systems have a coefficient of performance in the range of 8-20 which is much higher than that of the conventional vapour compression coolers, and thus requiring less electrical power to operate providing high economic feasibility (Anisimov, Pandelidis, and Danielewicz 2014; Cui et al. 2014; Zhan et al. 2011). In addition, such evaporative cooling systems can avoid 44% of the carbon dioxide emissions produced by vapour compression systems with a very high energy efficiency ratio (EER) reaching 80 (Duan et al. 2012). As a comparison, typical values of EER for different air conditioning techniques are presented in Table 1 (Afonso 2006). However, conventional evaporative coolers such as those disclosed in US Patents No. 5,971,370 and 6,079,365 (Galabinski 1999; Medlin and Wilkins 2000), supply water vertically through multiple pads allowing water evaporation and process air cooling. Such evaporative coolers are relatively expensive to manufacture and install and have major drawbacks with a high possibility of drawing water through the pads into the building s interior. This will have negative impacts on the building structure and the indoor air quality including damage to adjacent equipment, high rates of microbial growth and joint and respiratory infections. Nevertheless, high air relative humidity in buildings affects the occupants breathing and skin evaporation rate, in addition to encouraging mould and germs growth and building construction and 3

4 equipment decay. Thus it is favourable to remove water vapour from air through dehumidification. Conventional cooling systems, mainly vapour compression units, are extensive energy consumers using cold coils to reduce air temperature below the dew point temperature allowing water vapour condensation and latent heat release. Recently, a large body of research has been presented regarding the use of solid and liquid desiccant materials and their potential in air dehumidification and cooling applications (Kumar, Chaudhary and Yadav 2014; Mei and Dai 2008; Qiu and Riffat 2010; Uçkana et al. 2014). The major factor governing moisture absorption by a desiccant material is process airdesiccant material surface vapour pressure gradient. As the vapour pressure of the desiccant surface is less than that of the air, moisture absorption continue allowing air dehumidification until the equilibrium in the vapour pressure between air and desiccant is attained (Lownestein 2008). Liquid desiccant air dehumidification units have significant potential providing different advantages compared to solid desiccant units including lower consumption of energy, higher coefficient of performance, higher flexibility with the ability to transport the liquid desiccant between various system units including the dehumidifier and regenerator (She, Yin and Zhang 2014; Daou, Wang and Xia 2006; Oliveira et al. 2000; Qi, Lu and Huang 2014; Yutong and Hongxing 2010). On the other hand, conventional liquid desiccant units still suffer from major drawbacks especially the serious problem of liquid desiccant entrainment by the process air which could affect the indoor air quality and has negative impacts on the thermal comfort of the occupants (Jradi and Riffat 2014). Therefore, it is reported that using semi-permeable micro-porous contactors in liquid desiccant units could help in eliminating the liquid desiccant entrainment problem (Isetti, Nannei, and Magrini 1997). In order to address these issues and to improve the indoor air quality, we are proposing an innovative dehumidification and cooling system using hollow fibres and employing liquid desiccant as the dehumidification working fluid. Compared to the conventional cooling and dehumidification techniques, the proposed system has the following innovative features: - Providing thermal comfort through the use of selective hollow fibres, with high packing density and large heat and mass transfer surface area, allowing no direct contact between air and liquid desiccant and thus no droplets carryover by the air. 4

5 - Employing environmentally friendly working fluids, water and potassium formate liquid desiccant, to reduce the environmental negative impacts of space air conditioning. - Presenting an innovative evaporative cooling core using hollow fibre membrane as a wetting medium with no water-air interaction and thus better indoor air quality. - Using inexpensive materials, hollow fibres and cheap containers in addition to the simple and compact integrated system configuration, resulting into low system capital and running costs. 2 Hollow Fibre Contactor Technology A hollow fibre contactor is composed of bundles of micro-porous hollow fibre membranes having numerous fine pores across the fibre wall with a very small diameter (Gabelman and Hwang 1999). Hollow fibre-based membranes, shown in Fig. 1 (SpinTek), have the ability to act as a passive barrier between two heterogonous fluid phases without dispersion, where one of those fluids occupies the pores void volume on the surface of the membrane. Hollow fibre contactors are typically made of materials with high hydrophobic effect including: polyethylene (PE), polypropylene (PP), polytetrafluoroethylene (PTFE) and polyvinylidene fluoride (PVDF) (Rajabzadeh et al. 2009). Different companies now are manufacturing hollow fibre membrane contactors as an economic and cost effective alternative solution in different fields as shown in Fig. 2 (Mitsubishi). Employing cheap materials and having attractive mass transfer characteristics in addition to their large surface area/volume ratio, hollow fibres have been successfully employed as membrane contactors in various applications including: chemical engineering separation, liquid-liquid extraction, gas absorption, microfiltration processes, brackish water desalination, potable water purification, wastewater treatment, drying processes and biofuels separation (Boributh et al. 2012; Cath et al. 2005; Mansourizadeh and Ismail 2009). The selection of the hollow fibre membrane contactor for a specific application is based on different factors including fibre surface pore size, surface pores distribution, separation layer thickness in addition to the physical, chemical and mechanical properties of the fibre material (Peng et al. 2012). Pabby and Sastre (2013) presented a comprehensive review on the recent research and developments in the field of hollow fibre contactor technology and membrane-based extraction processes. They 5

6 reviewed different hollow fibre membrane aspects including performance, mass transfer modelling, stability issues, applications and the development in the hollow fibre membrane-based separation techniques. In addition to the commercial advancement in the field of hollow-fibre based membrane contactors, different researchers have investigated the performance of such type of contactors employing different configurations and fluid flow patterns, with specific concentration on the heat and mass transfer phenomena within the hollow fibre membrane (Bui, Vu, and Nguyen 2010; Huang et al. 2013; Huang and Yang 2013; Zhang et al. 2012). Very few research studies have investigated the use of hollow fibres in cooling and dehumidification applications. A theoretical and experimental study of a liquid desiccant air dehumidification system utilizing a hollow-fibre based membrane core was presented by Zhang and Zhang (2014). A compression heat pump was used to simultaneously heat and cool the liquid desiccant solution to enhance the system efficiency by passing the solution through the heat pump evaporator and condenser. A dehumidification efficiency of was attained and a satisfactory system performance was reported even in hot and humid conditions. Dijkink et al. (2004) carried out an experimental investigation of polyetherimide (PEI) hollow fibre membrane contactor coated with a thin non-porous silicone layer on the inside and using dilute aqueous glycerol solution as a liquid desiccant. Johnson, Yavuzturk, and Pruis (2003) investigated experimentally hollow fibre based evaporative cooling systems and recommended the use of hollow fibre membranes with larger pore sizes, thinner membrane walls and low tortuosity to increase mass transfer rates in evaporative cooling systems. Das and Jain (2013) studied the performance of air liquid indirect membrane contactors for liquid desiccant cooling systems using hollow fibres. The maximum vapour flux attained was about 1295 g/m 2.h with dehumidification effectiveness between 23% and 45% using LiCl as a desiccant solution. Based on these analytical and numerical investigations and the results reported, it is shown that hollow fibre-based membrane contactors have favourable heat and mass transfer characteristics and possess a large potential to serve dehumidification and cooling applications. 6

7 3 Proposed Hollow-Fibre Based Core Having favourable hydrophobic specifications, large surface area-to-volume ratio, attractive heat and mass transfer characteristics, simple and maintenance-free operation, in addition to employing cheap materials that are corrosion resistant and high-temperature and pollution tolerant, hollow fibre-based membrane presents a cost effective and environmentally friendly alternative solution to serve as a core in evaporative cooling systems and liquid desiccant dehumidification systems. In this work an innovative hollow fibre-based core is proposed to provide thermal comfort and humidity control and improve indoor air quality in occupied spaces. The presented core consists mainly of a hollow fibrebased membrane contactor that could be employed as a dehumidification core in liquid desiccant dehumidification units and as a cooling core in evaporative cooling units. As shown in Fig. 3, the hollow fibre-based core utilizes 12 bundles aligned vertically, each with 1000 packed hollow fibres. The specifications of the hollow fibres utilized in the study are presented in Table 2. The fibres are assembled and packed using short pieces of a plastic tube and potted at both ends of the bundle using epoxy resin and silicone sealant as shown in Fig. 4(a). In addition, the fibre bundles are attached to the plastic water/liquid desiccant distribution network at the top of the unit as shown in Fig. 4(b). Water/liquid desiccant is circulated in the system and a small pump (6 W electric power consumption), shown in Fig. 5(a) is utilized to feed the fluid from a plastic collection tank, placed at the bottom of the cooling unit, through a pipe connected to the 12 fibre bundles. Water/liquid desiccant is circulated at a flow rate ranging between 0.2 and 0.7 l/min where the fluid flows through hollow fibres and drops back into the collection tank. An air duct is employed where fibres are densely spread inside and extend through both ends of the duct. Air is introduced employing a small AC blower, shown in Fig. 5(b), through the duct in a horizontal direction to the vertical fluid flow pattern in the fibre membrane. The developed hollow fibre-based core configuration allows cross-flow heat and mass exchange between the air flow in the duct and fluid flow in the hollow fibres. The semi-permeable membrane hollow fibres employed are water vapour permeable and liquid tight, allowing moisture transport with no direct contact between the liquid flowing inside the fibres and the air passing across the external 7

8 fibres surface. The mass transport of water vapour depends mainly on the water vapour pressure difference between both sides of the fibre membrane wall. When used as a dehumidifier, the humid air is introduced through the duct and gets in contact with the external surface of the fibres, where the liquid desiccant flows inside the fibres absorbing water vapour through the pores distributed along the surface and dehumidifying the process air. Similarly when the core is utilized as an evaporative cooler, hot air is introduced to flow in the duct where water flows inside the fibres, and a portion of the water is evaporated leading to a drop in the air temperature. The large surface area-to-volume ratio provided by the compact and simple design of the fibre membrane enhances heat and mass transfer between the air flowing on the membrane external surface and the fluid flowing inside the hollow fibres. Neither water nor liquid desiccant carryover occurred during cooling and dehumidification processes providing thermal comfort and good indoor air quality. In the following sections, the preliminary testing of the fibre membrane-based core as an evaporative cooler and as a liquid desiccant dehumidification unit is presented and the results are reported. 4 Evaporative Cooling Unit Performance The hollow fibre-based core developed and was tested and investigated as a cooling core for a compact evaporative cooling unit. A climatic chamber was utilized to control the inlet temperature and relative humidity to the cooling core. In addition, two HMP50 temperature and humidity probes were employed to record the intake air and supply air humidity and temperature. The temperature measurement range of these sensors is -40 to +60 C with ±0.3 C accuracy where the relative humidity measurement range is 0-98%. In addition, a K-type thermocouple of ±0.25% accuracy and a maximum temperature measurement of 250 C, was employed to measure the water inlet temperature to the fibre membrane. The recording sensors were connected to a Datataker DT 80 data logger for data monitoring and recording. Throughout the cooling unit preliminary testing sessions, intake air speed of 2.4 m/s was employed. The overall cooling capacity of the evaporative cooling unit can be given by:. Q cooling m ( h h ) (1) su in su 8

9 m su is the supply air mass flow rate in kg/s, h in and h out are the respective air specific enthalpy at the inlet and outlet of the evaporative cooler. The cooler coefficient of performance is given by the ratio of the cooling capacity provided to the electric power consumption. The total electric power consumption, W ele,cooler in W, includes the power required to operate the water circulation pump for and the power required to run the fan employed for air supply. The system overall COP is represented by: COP Q cooling cooler (2).. W ele, cooler The cooling effectiveness of the evaporative cooler can be expressed in terms of the wet bulb effectiveness and the dew point effectiveness given by equations (3) and (4) respectively. T T in, db su, db wb (3) Tin, db Tin, wb T T in, db su, db dp (4) Tin, db Tin, dp T in,db is the inlet air dry bulb temperature, T su, db is the supply air dry bulb temperature, T in,wb is the inlet air wet bulb temperature and T in,dp is the inlet air dew point temperature. 4.1 Climatic Chamber Set Temperature of 30 C Figure 6(a) presents the variation in the inlet and outlet air temperatures across the evaporative cooler employing different water volumetric flow rates. Based on the data recorded, the average temperature drop across the cooler is about 6.1 C, 6.9 C and 6.7 C for water volumetric flow rate of 0.2, 0.4 and 0.5 l/min respectively. In addition, Fig. 6(b) presents the variation in the inlet and outlet air relative humidity at different flow rates. It is shown that the average increase in the outlet air relative humidity is about 22.6%, 24.5% and 24.6% at water volumetric flow rate of 0.2, 0.4 and 0.5 l/min. Figure 7(a) shows the variation in the cooling capacity delivered by the evaporative cooler and the cooler coefficient of performance (COP) at different water volumetric flow rates. The maximum cooling capacity produced by the system increases from 164 W at 0.2 l/min water volumetric flow rate to about 191 W at 0.5 l/min volumetric flow rate. Correspondingly, the COP increases from an 9

10 average of 5.3 to about 6.3 as the water volumetric flow rate increases from 0.2 to 0.5 l/min. In addition, the estimated wet bulb and dew point effectiveness of the system is presented in Fig. 7(b). It is shown that the wet bulb effectiveness increases from 64% to 69% with the increase of volumetric flow rate of water from 0.2 to 0.5 l/min, accompanied with an increase in the dew point effectiveness from 41% to 46%. 4.2 Climatic Chamber Set Temperature of 35 C Increasing the climatic chamber set temperature from 30 C to 35 C, Fig. 8(a) shows the variation in the inlet and outlet air temperatures across the evaporative cooler As shown in the figure, the maximum temperature drop across the cooler is about 7.7 C, 8.2 C and 8.9 C for water volumetric flow rate of 0.4, 0.5 and 0.7 l/min respectively. In addition, Fig. 8(b) shows the variation in the inlet and outlet air relative humidity at different flow rates. It is reported that the average increase in the outlet air relative humidity is about 22.3%, 23.2% and 26.1% at water volumetric flow rate of 0.4, 0.5 and 0.7 l/min. Figure 9(a) presents the cooling capacity produced by the evaporative cooler and the cooler COP at different water volumetric flow rates. It is shown that the maximum cooling capacity produced by the system increases from 278 W at 0.4 l/min water volumetric flow rate to about 334 W at 0.7 l/min volumetric flow rate. The evaporative cooler COP follows an increasing trend as the water volumetric flow rate increases. As shown in the figure, the maximum COP attained increases from 10.7 to 12.9 as the volumetric flow rate increases from 0.4 to 0.7 l/min. Moreover, the evaporative cooler wet bulb and dew point effectiveness data is presented in Fig. 9(b). The system maximum wet bulb effectiveness increases from 71% to 79% as the water volumetric flow rate increases from 0.4 to 0.7 l/min. Similarly, the system dew point effectiveness increases from 50% to 57%. 4.3 Climatic Chamber Set Temperature of 45 C With a climatic chamber set temperature at 45 C, Fig. 10(a) presents the variation in the evaporative cooler inlet and outlet air temperatures at different water volumetric flow rates. It is shown that the maximum temperature drop across the cooler is about 8.2 C, 8.7 C and 9.2 C for water volumetric flow rate of 0.2, 0.4 and 0.5 l/min respectively. In addition, Fig. 10(b) shows the variation in the inlet and outlet air relative humidity at different flow rates. The average increase in the relative humidity of 10

11 the supply air is about 22.2%, 23.3% and 24.5% at water volumetric flow rate of 0.2, 0.4 and 0.5 l/min. Figure 11(a) shows the evaporative cooler cooling capacity in addition to the COP employing different water volumetric flow rates and at a climatic chamber set temperature of 45 C. As the volumetric flow rate of water increases from 0.2 to 0.5 l/min, the maximum system cooling capacity increases form 427 W to 502 W. The COP follows a similar trend and increases from 16.1 to a maximum of 19.3 at water volumetric flow rate of 0.2 and 0.5 l/min respectively. In addition, the system calculated wet bulb effectiveness increases from 78% to 85% with the increase of water volumetric flow rate from 0.2 to 0.5 l/min, accompanied by an increase in the dew point effectiveness from 60% to 65%. 4.4 Effect of Inlet Air Temperature Employing the climatic chamber to control the inlet air temperature to the evaporative cooler allows investigating the impact of inlet air temperature on the overall performance of the cooling system. As presented in the previous sections, three different chamber set temperatures were employed, 30 C, 35 C and 45 C. Figure 12(a) shows the variation in the temperature of the inlet air and outlet air of the cooling system at different set temperatures, employing water volumetric flow rate of 0.5 l/min. It is shown that the maximum temperature drop across the evaporator is about 7.2 C, 8.1 C and 9.1 C at an operating air inlet temperature of 30 C, 35 C and 45 C respectively. In addition, Fig. 12(b) shows the variation in the cooling capacity delivered by the evaporative cooler and the COP of the cooling system employing different inlet air temperatures. It is shown that the cooling capacity produced by the system is directly proportional to the inlet air temperature. The maximum evaporative cooler cooling capacity increases from about 191 W at a set temperature of 30 C up to 502 W at a set temperature of 45 C. In addition, the system COP follows the same trend as the cooling capacity and increases with the increase in the inlet air temperature. As shown in Fig. 12(b), the evaporative cooler maximum COP is about 7.4, 11.2 and 19.3 at a set inlet air temperature of 30 C, 35 C and 45 C. Regarding the water temperature, Fig. 12(c) shows the variation in the water temperature during the evaporative cooler operation at different inlet air set temperatures. As the water, initially at a temperature between C, is recirculated from the tank to the fibres and then back to the tank, its 11

12 temperature increases with time when it gets in contact with the relatively hot air. As shown in the figure, there is a slight increase from 18.7 C to 19.1 C in the water temperature when the inlet air has a temperature in the range of 30 C. However the water temperature increase is much more significant, increasing from about 19.2 C to 23.6 C, employing an inlet air of temperature 45 C. It is shown that the cooling capacity delivered by the evaporative cooling system and coefficient of performance are inversely proportional to the inlet water temperature. Therefore, to attain the system maximum cooling capacity, the inlet water temperature needs to be maintained at C throughout the operation period. This could be done through replenishing the water introduced to the fibre-based evaporative cooling system or using a continuous water supply source. 5 Dehumidification Unit Performance In addition to investigating the developed hollow fibre-based core as a cooling core for indirect evaporative cooling applications, the hollow fibre membrane was investigated and tested as a dehumidification core for a liquid desiccant dehumidification unit. The same experimental setup described in section 3 is employed but potassium formate HCOOK liquid desiccant of 74% mass concentration was circulated and introduced to the fibre membrane instead of water. Potassium formate was used due to its various environmental, physical and thermodynamic advantages compared to conventional liquid desiccants (LiCl, LiBr) with lower density, viscosity and being less corrosive (Longo and Gasprella 2005; Riffat, James and Wong 1998). Humid air was drawn in the duct from the climatic chamber to be dehumidified by the action of the fibre bundles. Throughout the dehumidification unit preliminary testing sessions, intake air speed of 2.6 m/s was employed. The dehumidification capacity of the liquid desiccant dehumidification system can be represented as:. Q Deh m h h ) (5) su( a, in a, out h a,in and h a,out are the respective air specific enthalpy at the inlet and outlet of the dehumidification unit. The humidity effectiveness (ε w ) of the liquid desiccant dehumidification system, is the actual air humidity ratio change over the maximum possible change: w w a, in a, out w (6) wa, in weq 12

13 w a,in and w a,out are the respective air humidity ratio at the inlet and outlet of the dehumidification unit. w eq is the air humidity ratio in equilibrium with the liquid desiccant in kg H2O /kg air. This humidity ratio is the ideal minimum level to which air can be dehumidified and is given in terms of the desiccant partial vapour pressure P v by equation (7): w eq P 0 (7) P v v The enthalpy effectiveness (ε h ) is defined as the actual change in air enthalpy over the maximum ideal enthalpy change and can be given by: h h a, in a, out h (8) ha, in heq h eq in J/kg, is the air enthalpy in equilibrium with the liquid desiccant and can be obtained in terms of the air equilibrium humidity ratio w eq at an air temperature equivalent to that of the liquid desiccant employed. 5.1 Set Conditions: T ain 30 C and RH ain 80% Employing climatic chamber settings of 30 C temperature and 80% relative humidity, Fig. 13(a) shows the variation in the air temperature at the inlet and outlet sections of the dehumidifier in addition to the change in the potassium formate liquid desiccant temperature introduced to the hollow fibres-based system. With the inlet air temperature fixed at about 30 C, the minimum air temperature attained at the outlet of the dehumidifier is about 27.6 C where the maximum drop in the air temperature across the dehumidifier is about 2.4 C. In addition, the liquid desiccant temperature increases with time from 19.3 C to about 26.4 C. This temperature increase is mainly due to the temperature difference between the relatively colder liquid desiccant flowing inside the hollow fibres and the relatively hotter air flowing in direct contact with the external surfaces of the fibres. In addition, the temperature drop across the dehumidifier is inversely proportional to the increase in the liquid desiccant temperature as shown in Fig. 13(a). Fig. 13(b) shows the variation in the relative humidity of air at the inlet and outlet of the dehumidifier. While fixing the inlet air relative humidity at around 80%, the average relative humidity of the outlet air is around 66.1%. The maximum drop in the air relative humidity across the dehumidifier is about 16.6%. In addition, Fig. 13(c) presents the 13

14 variation of the air enthalpy at the inlet and outlet of the dehumidifier along with the cooling capacity delivered by the system. It is shown that the average inlet and outlet air enthalpy is about 85.5 kj/kg and 69.4 kj/kg respectively, where the maximum cooling capacity provided by the dehumidifier is about 733 W with an average capacity of 673 W throughout the experimental session. Fig. 13(d) shows the variation in the system humidity and enthalpy effectiveness along with the variation in the liquid desiccant temperature. It is obvious that the dehumidification system effectiveness is inversely proportional to the liquid desiccant temperature. The maximum humidity and enthalpy effectiveness attained is about 47% and 44% respectively. 5.2 Effect of Inlet Air Relative Humidity Employing the climatic chamber, multiple testing sessions for the liquid-based dehumidification system was carried out to investigate the effect of the inlet air relative humidity on the overall system performance. Figure 14(a) shows the variation in the air relative humidity at the inlet and outlet of the dehumidifier at three inlet air relative humidity settings, 60%, 70% and 80%. It is shown that the drop in the air relative humidity is directly proportional to the relative humidity of the inlet air, with a maximum drop of 4.9%, 9.3% and 16.3% at inlet air relative humidity of 60%, 70% and 80% respectively. In addition, the average air relative humidity at the outlet of the dehumidifier is about 56%, 62% and 66% for a respective inlet air relative humidity of 60%, 70% and 80%. In addition, Fig. 14(b) presents the variation in the dehumidification system cooling capacity in addition to the variation of the liquid desiccant temperature at the three investigated relative humidity settings. The maximum cooling capacity delivered by the dehumidification system is about 426 W, 519 W and 733 W for relative humidity setting of 60%, 70% and 80%. It is shown that the dehumidification capacity decreases as the temperature of the liquid desiccant increases, where the system cooling capacity is directly proportional to the inlet air relative humidity. Similarly, the dehumidification system humidity effectiveness and enthalpy effectiveness is directly proportional to the inlet air relative humidity as shown in Fig. 14(c). The maximum reported wet bulb and dew point effectiveness are (40%, 37%), (43%, 40%) and (47%, 44%) at inlet air relative humidity setting of 60%, 70% and 80% respectively. 14

15 5.3 Effect of Inlet Air Temperature Testing sessions were carried out to investigate the effect of inlet air temperature on the dehumidifier various performance parameters. Figure 15(a) shows the variation in the air temperature at the dehumidifier inlet and outlet at two inlet air temperature settings: 30 C and 35 C, where the set relative humidity is fixed at 80%. As shown in the figure, the average air temperature drop across the dehumidifier is about 1.6 C and 1.1 C at 30 C and 35 C inlet air set temperature. It is shown that the drop in the air temperature decreases with time due to the fact that the liquid desiccant temperature introduced increases with time. This effect is more significant at higher air temperatures where the desiccant temperature exhibits fast increase compared to relatively lower temperatures. In addition, Fig. 15(b) shows the variation in the air relative humidity across the dehumidifier under the two employed inlet air temperature settings. It is shown that the relative humidity drop across the dehumidifier is inversely proportional to the inlet air temperature. The average relative humidity drop across the dehumidifier is about 11.5% and 14.6% at 30 C and 35 C respectively. Figure 15(c) shows the variation in the liquid desiccant temperature and the cooling capacity delivered by the fibre-based dehumidification system at two different inlet air temperature settings. It is shown that the liquid desiccant temperature increases from 19.3 C to 26.4 C at inlet air temperature setting of 30 C, where the desiccant temperature increase rate is more significant at an inlet air temperature setting of 35 C, increasing form about 21.4 C to about 30.9 C. In addition, it is shown that the dehumidification system cooling capacity is inversely proportional to the inlet air temperature where the average cooling capacity attained is around 673 W and 612 W at inlet air temperature setting of 30 C and 35 C respectively. In addition, it is shown that the system cooling capacity follows a decreasing trend as the liquid desiccant temperature increases. This is due to the liquid desiccant recirculation from the tank to the fibre-based dehumidification system and then back to the tank allowing the increase in the potassium formate temperature. Moreover, Fig. 15(d) shows the effect of the inlet air temperature on the dehumidification system effectiveness. It is shown that increasing the inlet air temperature setting from 30 C to 35 C is accompanied by a decrease in the system humidity effectiveness from 47% to 32% and a decrease in the enthalpy effectiveness from 44% to 29%. 15

16 6 Conclusion With the increase in the conventional fuel prices and the global warming problem, a growing body of research has been presented to investigate efficient and environmentally friendly alternative technologies and solutions to provide thermal comfort and good indoor air quality. In this work, an innovative hollow fibre-based energy core is proposed and investigated to provide thermal comfort and humidity control in air-conditioned spaces. The presented core comprises a hollow fibre contactor having multiple bundles of micro-porous hollow fibres packed and assembled together, providing large surface area-to-volume ratio with favourable heat and mass transport characteristics. The employed fibre membrane is cheap, simple and compact in design and corrosion resistant with good hydrophobic properties. The use of the innovative semi-permeable fibre-based membrane eliminates any water or liquid desiccant droplets carryover by the air allowing better indoor air quality. The proposed fibre-based core was tested in the Built Environment laboratories at the University of Nottingham to serve as a cooling core in evaporative cooling systems and a dehumidification core in liquid desiccant systems. As a cooling core, the maximum cooling capacity provided by the fibrebased evaporative cooler was about 502 W with a COP of around 19, wet bulb effectiveness of 85% and dew point effectiveness of 65%. Using potassium formate as a liquid desiccant, the dehumidification core was able to decrease the humid air relative humidity by about 17% with a dehumidification capacity of 733 W and humidity effectiveness of 47%. The satisfactory preliminary testing results reported demonstrate the potential of using hollow fibre-based energy cores for cooling and dehumidification applications allowing technical, economic and environmental benefits compared to conventional cooling and dehumidification systems. Acknowledgement The authors gratefully acknowledge the special support of the Dean of Engineering Research Scholarship for International Excellence Award 2011 from the Faculty of Engineering at the University of Nottingham. References [1] Afonso, C.F.A. (2006). Recent advances in building air conditioning systems. Applied Thermal Engineering 26(16):

17 [2] Anisimov, S., D. Pandelidis, and J. Danielewicz. (2014). Numerical analysis of selected evaporative exchangers with the Maisotsenko cycle. Energy Conversion and Management 88: [3] Boributh, S., et al. (2012). Mathematical modeling and cascade design of hollow fiber membrane contactor for CO2 absorption by monoethanolamine. Journal of Membrane Science : [4] Bui, V.A., L.T.T. Vu, and M.H. Nguyen. (2010). Modelling the simultaneous heat and mass transfer of direct contact membrane distillation in hollow fibre modules. Journal of Membrane Science 353(1 2): [5] Cath, T.Y., et al. (2005). Membrane contactor processes for wastewater reclamation in space: Part I. Direct osmotic concentration as pretreatment for reverse osmosis. Journal of Membrane Science, 257(1 2): [6] Cui, X., et al. (2014). Fundamental formulation of a modified LMTD method to study indirect evaporative heat exchangers. Energy Conversion and Management 88: [7] Daou, K., R.Z. Wang, and Z.Z. Xia. (2006). Desiccant cooling air conditioning: a review. Renewable and Sustainable Energy Reviews 10(2): [8] Das, R.S. and S. Jain. (2013). Experimental performance of indirect air liquid membrane contactors for liquid desiccant cooling systems. Energy 57: [9] Delfani, S., et al. (2010). Energy saving potential of an indirect evaporative cooler as a precooling unit for mechanical cooling systems in Iran. Energy and Buildings 42(11): [10] Dijkink, B.H., et al. (2004). Humidity control during bell pepper storage, using a hollow fiber membrane contactor system. Postharvest Biology and Technology 32(3): [11] Duan, Z., et al. (2012). Indirect evaporative cooling: Past, present and future potentials. Renewable and Sustainable Energy Reviews 16(9): [12] Gabelman, A. and S.-T. Hwang. (1999). Hollow fiber membrane contactors. Journal of Membrane Science 159(1 2): [13] Galabinski, M.J. (1999). Integrated water distribution/cooling pad system. Patent No. US A. [14] Hammoud, M., K. Ghali and N. Ghaddar. (2014). The Optimized Operation of a Solar Hybrid Desiccant/Displacement Ventilation Combined with a Personalized Evaporative Cooler. International Journal of Green Energy 11(2): [15] Huang, S.-M. and M. Yang. (2013). Longitudinal fluid flow and heat transfer between an elliptical hollow fiber membrane tube bank used for air humidification. Applied Energy 112: [16] Huang, S.-M., et al. (2013). Fluid flow and heat transfer across an elliptical hollow fiber membrane tube bank for air humidification. International Journal of Thermal Sciences 73: [17] Isetti, C., E. Nannei, and A. Magrini. (1997). On the application of a membrane air liquid contactor for air dehumidification. Energy and Buildings 25(3): [18] Johnson, D.W., C. Yavuzturk, and J. Pruis. (2003). Analysis of heat and mass transfer phenomena in hollow fiber membranes used for evaporative cooling. Journal of Membrane Science 227(1 2): [19] Jradi, M and S. Riffat. (2014). Experimental investigation of a biomass-fuelled micro-scale tri-generation system with an organic Rankine cycle and liquid desiccant cooling unit. Energy 71: [20] Kumar, A., A. Chaudhary and A. Yadav. (2014). The Regeneration of Various Solid Desiccants by Using a Parabolic Dish Collector and Adsorption Rate: An Experimental Investigation. International Journal of Green Energy 11(9):

18 [21] Longo, G.A., and A. Gasprella. (2005). Experimental and theoretical analysis of heat and mass transfer in a packed column dehumidifier/regenerator with liquid desiccant. International Journal of Heat and Mass Transfer 48: [22] Lownestein, A. (2008). Review of liquid desiccant technology for HVAC applications. HVAC&R Research 14(6): [23] Maheshwari, G.P., F. Al-Ragom, and R.K. Suri. (2001). Energy-saving potential of an indirect evaporative cooler. Applied Energy 69(1): [24] Mansourizadeh, A. and A.F. Ismail. (2009). Hollow fiber gas liquid membrane contactors for acid gas capture: A review. Journal of Hazardous Materials 171(1 3): [25] Medlin, T.D. and H. Wilkins. (2000). Evaporative cooling system for cooling a poultry house. Patent No [26] Mei, L. and Y.J. Dai. (2008). A technical review on use of liquid-desiccant dehumidification for air-conditioning application. Renewable and Sustainable Energy Reviews 12(3): [27] Mitsubishi. Applications of Hollow Fiber Membrane. April 21, 2014]; Available from: [28] Oliveira, A.C., et al. (2000). Thermal performance of a novel air conditioning system using a liquid desiccant. Applied Thermal Engineering 20(13): [29] Pabby, A.K. and A.M. Sastre. (2013). State-of-the-art review on hollow fibre contactor technology and membrane-based extraction processes. Journal of Membrane Science 430: [30] Peng, N., et al. (2012). Evolution of polymeric hollow fibers as sustainable technologies: Past, present, and future. Progress in Polymer Science 37(10): [31] Qi, R., L. Lu, and Y. Huang. (2014). Energy performance of solar-assisted liquid desiccant air-conditioning system for commercial building in main climate zones. Energy Conversion and Management 88: [32] Qiu, G.Q., and S. B. Riffat. (2010). Experimental investigation on a novel air dehumidifier using liquid desiccant. International Journal of Green Energy 7: [33] Rajabzadeh, S., et al. (2009). CO2 absorption by using PVDF hollow fiber membrane contactors with various membrane structures. Separation and Purification Technology 69(2): [34] Riffat, S.B., S.E. James, and C.W. Wong. (1998). Experimental analysis of the absorption and desorption rates of HCOOK/H2O and LiBr/H2O. International Journal of Energy Research 22(12): [35] She, X., Y. Yin, and X. Zhang. (2014). Thermodynamic analysis of a novel energy-efficient refrigeration system subcooled by liquid desiccant dehumidification and evaporation. Energy Conversion and Management 78: [36] SpinTek. Hollow Fiber Membranes. April 19, 2014]; Available from: [37] Uçkan, I., et al. (2013). Experimental investigation of a novel configuration of desiccant based evaporative air conditioning system. Energy Conversion and Management 65: [38] Uçkana, I et al. (2014). Development Artificial Neural Network model for the prediction of the performance of a silica-gel desiccant wheel. International Journal of Green Energy. DOI: / [39] Yutong, L., and Y. Hongxing. (2010). Experimental Study Of An Open-Cycle Solar Collector/Regenerator Using Liquid Desiccant For Air Conditioning. International Journal of Green Energy 7:

19 [40] Zhan, C., et al. (2011). Comparative study of the performance of the M-cycle counter-flow and cross-flow heat exchangers for indirect evaporative cooling Paving the path toward sustainable cooling of buildings. Energy 36(12): [41] Zhang, L.Z. and N. Zhang. (2014). A heat pump driven and hollow fiber membrane-based liquid desiccant air dehumidification system: Modeling and experimental validation. Energy 65: [42] Zhang, L.-Z., et al. (2012). Conjugate heat and mass transfer in a hollow fiber membrane module for liquid desiccant air dehumidification: A free surface model approach. International Journal of Heat and Mass Transfer 55(13 14):

20 List of Tables Cooling Technique EER (Btu/Wh) Table 1 Typical EER values for standard air conditioning techniques (Afonso 2006) Vapour Compression Absorption Adsorption Desiccants Ejector Thermoelectric Table 2 Hollow fibre specifications Material Polypropylene (PP) Outer Diameter (µm) 420~490 Pore size (µm) 0.1~0.2 Wall Thickness (µm) 40~50 Membrane Porosity (%) 45~55 Water Flux (L/h.m 2 ) 100~120 20

21 Figure Captions Fig. 1: Fig. 2: Fig. 3: Fig. 4(a-b): Fig. 5(a-b): Fig. 6(a-b): Hollow fibre-based membranes (SpinTek) Hollow Fibre-based membrane applications (Mitsubishi) Experimental setup for the hollow-fibre based core (a) Hollow fibre bundle, (b) Fluid distribution network (a) Fluid pump, (b) AC air blower Variation of air (a) temperature and (b) relative humidity across the cooler at 30 C set temperature Fig. 7(a-b): Evaporative cooler (a) cooling capacity and COP, (b) wet bulb and dew point effectiveness at 30 C set temperature Fig. 8(a-b): Variation of air (a) temperature and (b) relative humidity across the cooler at 35 C set temperature Fig. 9(a-b): Evaporative cooler (a) cooling capacity and COP, (b) wet bulb and dew point effectiveness at 35 C set temperature Fig. 10(a-b): Variation of air (a) temperature and (b) relative humidity across the cooler at 45 C set temperature Fig. 11(a-b): Evaporative cooler (a) cooling capacity and COP, (b) wet bulb and dew point effectiveness at 45 C set temperature Fig. 12(a-b-c): Fig. 13(a-b-c-d): Fig. 14(a-b-c): Fig. 15(a-b-c-d): Effect of inlet air temperature on the (a) temperature drop across the cooler, (b) cooling capacity and COP and (c) water temperature Variation of (a) air and desiccant temperature, (b) air relative humidity, (c) air enthalpy and dehumidifier cooling capacity and (d) humidity and enthalpy effectiveness at 30 C set temperature and 80% relative humidity Effect of the inlet air relative humidity on the (a) humidity drop across the dehumidifier, (b) cooling capacity and desiccant temperature and (c) humidity and enthalpy effectiveness Effect of inlet air temperature on the (a) air temperature drop, (b) relative humidity drop, (c) dehumidifier cooling capacity and the desiccant temperature and (d) dehumidifier effectiveness 21

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant Proceedings of the World Congress on Momentum, Heat and Mass Transfer (MHMT 16) Prague, Czech Republic April 4 5, 216 Paper No. ENFHT 111 DOI: 1.11159/enfht16.111 Experimental Investigation of a Multi

More information

Impact of indirect evaporative air cooler type on the performance of desiccant systems

Impact of indirect evaporative air cooler type on the performance of desiccant systems Impact of indirect evaporative air cooler type on the performance of desiccant systems Anna Pacak 1,*, Aleksandra Cichoń 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of Science and

More information

Access from the University of Nottingham repository: %20paper_v8.

Access from the University of Nottingham repository:  %20paper_v8. Chen, Ziwei and Bai, Hongyu and Ye, Zihao and Zhu, Jie (2016) Experimental study of a membrane-based dehumidification cooling system. In: International Symposium of Heat Transfer and Heat Powered Cycles

More information

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System Feasibility of a Liquid Desiccant Application in an Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, S.K.Han 1, S.Y. Cho 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang

More information

Recent Advances in Energy, Environment and Economic Development

Recent Advances in Energy, Environment and Economic Development Experimental Investigation of Solar Hybrid Desiccant Cooling System in Hot and Humid Weather of Malaysia MM SALEHI DEZFOULI, Z HASHIM, MH RUSLAN, B BAKHTYAR, K SOPIAN, A ZAHARIM, S MAT, A RACHMAN, Solar

More information

POLYMER HOLLOW FIBRE HEAT EXCHANGERS

POLYMER HOLLOW FIBRE HEAT EXCHANGERS POLYMER HOLLOW FIBRE HEAT EXCHANGERS Current developments and applications under an INNOVATE project David Reay, David Reay & Associates (with thanks to the INNOVATE project partners) Polymer Hollow Fibre

More information

Experimental study of air evaporative cooling process using microporous membranes

Experimental study of air evaporative cooling process using microporous membranes Experimental study of air evaporative cooling process using microporous membranes Sebastian Englart 1,* 1 Wrocław University of Science and Technology, Faculty of Environmental Engineering, Department

More information

K.F. Fong *, C.K. Lee, T.T. Chow

K.F. Fong *, C.K. Lee, T.T. Chow Investigation on radiative load ratio of chilled beams on performances of solar hybrid adsorption refrigeration system for radiant cooling in subtropical city K.F. Fong *, C.K. Lee, T.T. Chow Building

More information

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System M.H.Kim 1, J.Y.Park 1, E.J.Lee 2, and J.W.Jeong 1* 1 Department of Architectural Engineering, Hanyang University,

More information

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling Aleksandra Cichoń,*, Anna Pacak, Demis Pandelidis, and Sergey Anisimov Department of

More information

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area MMS DEZFOULI, SOHIF MAT, K.SOPIAN Solar Energy Research Institute (SERI, Universiti

More information

Dynamic performance of a novel dew point air conditioning for the UK buildings

Dynamic performance of a novel dew point air conditioning for the UK buildings *Corresponding author: xudongzhao@nottingham. ac.uk Dynamic performance of a novel dew point air conditioning for the UK buildings... Xudong Zhao *, Zhiyin Duan, Changhong Zhan and Saffa B. Riffat School

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland Paper ID 0232 ISBN: 978-83-7947-232-1 Experimental study of a novel dew point indirect evaporative cooler Wenhua Chen, Zhiwei Zhang, Jiayu Li,

More information

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem A Simplified model for estimating the regeneration effectiveness of a counter flow regenerator for a liquid desiccant system M.H. Kim 1, H.J. Cho 1, and J.W. Jeong 1* 1 Division of Architectural Engineering,

More information

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE Journal of Sustainability Science and Management Volume 9 Number 1, June 2014: 150-155 ISSN: 1823-8556 Penerbit UMT PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE ARFIDIAN

More information

Desiccant cooling systems: a review

Desiccant cooling systems: a review *Corresponding author. minaalsahlot@icloud.com Desiccant cooling systems: a review... Minaal Sahlot * and Saffa B. Riffat Department of Architecture and Built Environment, University of Nottingham, Nottingham

More information

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System 4 th International Conference On Building Energy Environment Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System J Y Park H W

More information

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions

Experimental study on mass transfer comparison of two liquid desiccants aqueous solutions International Conference on Renewable Energies and Power Quality (ICREPQ ) Cordoba (Spain), th to th April, 0 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 1-03 X, No., April 0 Experimental

More information

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance #1 Jaydev S. Bade, #2 Dr. Nitin U. Korde 1 Department of Mechanical Engineering, Savitribai Phule

More information

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering July 2018 Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to

More information

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm

Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic Algorithm International Journal of ChemTech Research CODEN (USA): IJCRGG ISSN: 0974-4290 Vol.7, No.01, pp 400-407, 2014-2015 Optimization of Moisture condensation rate of Liquid Desiccant Dehumidifier through Genetic

More information

Scholars Research Library

Scholars Research Library Available online at www.scholarsresearchlibrary.com Scholars Research Library Archives of Applied Science Research, 2010, 2 (1) 376-382 (http://scholarsresearchlibrary.com/archive.html) ISSN 0975-508X

More information

A Review on Potential of Indirect Evaporative Cooling System

A Review on Potential of Indirect Evaporative Cooling System IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 09 March 2017 ISSN (online): 2349-784X A Review on Potential of Indirect Evaporative Cooling System Malaysinh D. Borasiya

More information

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System

Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System Performance Of The Dehumidification Cycle Of A 3-Fluid Liquid Desiccant Membrane Air-Conditioning System Devin Storle 1, Mohamed R.H. Abdel-Salam 2, Nader Pourmahmoud 3, Carey J. Simonson 4 1 MSc, University

More information

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner

Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner Feasibility Analysis of Regeneration of Silica Gel Used in Dehumidification Process of Air Conditioning by the Condenser Waste Heat of Air Conditioner Priyanka Nath, Jitul Baruah Guest Lecturer, Department

More information

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air

Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Analysis of freeze protection methods for recuperators used in energy recovery from exhaust air Anna Pacak 1,*, Andrzej Jedlikowski 1, Demis Pandelidis 1, and Sergey Anisimov 1 1 Wrocław University of

More information

Heat pump and energy recovery systems

Heat pump and energy recovery systems SBS5311 HVACR II http://ibse.hk/sbs5311/ Heat pump and energy recovery systems Ir. Dr. Sam C. M. Hui Faculty of Science and Technology E-mail: cmhui@vtc.edu.hk Oct 2017 Contents Basic concepts Air-to-air

More information

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling

Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling Proc. 2nd International Confirence Solar Air-Conditioning, Tarragona (ES), 18.-19.10.07, CD Theoretical Performance Analysis of a Liquid Desiccant Air- Conditioning System for Air Heating and Cooling R.

More information

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air

Experimental & Analytical Investigation on Modified Solar Dryer with Recirculation of Air International Journal of Engineering Research and Technology. ISSN 0974-3154 Volume 6, Number 4 (2013), pp. 441-448 International Research Publication House http://www.irphouse.com Experimental & Analytical

More information

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy

Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy Performance analysis of a liquid desiccant evaporative cooling airconditioning system powered by solar energy F. Zhang 1, Y. Yin 1,2* and X. Zhang 1,2 1 School of Energy and Environment Southeast University,

More information

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,

More information

Journal of Thermal Science and Technology

Journal of Thermal Science and Technology Science and Technology Vol. 5, No. 1, 010 Analysis of Dehumidification Effects on Cooling Capacity of an Evaporative Cooler* Mohammad assan SAIDI**, Cyrus AGANAJAFI*** and Masoud MOAMMADIAN**** **Mechanical

More information

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations

Regenerator Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations Proc. International Conference Air-Conditioning, Staffelstein (DE), 6.-7.10.2005, pp. 236-240 Design for Open Cycle Liquid Desiccant Systems Theoretical and Experimental Investigations M. Krause, W. Saman,

More information

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System

Experimental Performance of Solar Collector cum Regenerator for Coupling with a Liquid Desiccant Cooling System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Experimental Performance of Solar Collector cum Regenerator for Coupling

More information

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER

International Journal of Advance Research in Engineering, Science & Technology SOLAR HUMIDIFIER Impact Factor (SJIF): 4.42 International Journal of Advance Research in Engineering, Science & Technology e-issn: 2393-9877, p-issn: 2394-2444 Volume 4, Issue 11, November-217 SOLAR HUMIDIFIER PATEL RONIT

More information

Energy Efficiency In Air Conditioning Through The Desiccant Technology - A Review

Energy Efficiency In Air Conditioning Through The Desiccant Technology - A Review IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X PP. 75-85 www.iosrjournals.org Energy Efficiency In Air Conditioning Through The Desiccant Technology -

More information

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY Xiaoyun Xie, Yidan Tang, Xiaoqin Yi, Shuanqiang Liu,Yi Jiang Department of Building Science and Technology,

More information

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations

Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations 43rd ANZSES Conference Solar 24, Denedin (NZ), 28.11.-3.11.5, CD Abstract Open Cycle Liquid Desiccant Air Conditioning Systems Theoretical and Experimental Investigations M., W. Saman, K. Vajen* Sustainable

More information

Two Stage Indirect/Direct Evaporative Cooling

Two Stage Indirect/Direct Evaporative Cooling Two Stage Indirect/Direct Evaporative Cooling Abstract The performance of two-stage indirect/direct evaporative cooling system is experimentally investigated. For this purpose, a two-stage evaporative

More information

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS

COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS - 1 - COMPACT ADSORPTION CHILLERS WITH COATED ADSORBER HEAT EXCHANGERS W. Mittelbach, Managing Director, SorTech AG, Weinbergweg 23, 06120 Halle, Germany T. Büttner, Head of R&D / production, SorTech AG,

More information

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump To cite this article: Yefeng Liu et al 2018 IOP

More information

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile Available online at www.pelagiaresearchlibrary.com Advances in Applied Science Research, 2013, 4(5):232-237 ISSN: 0976-8610 CODEN (USA): AASRFC Performance analysis of ejector refrigeration system with

More information

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011 Performance evaluation of two stage indirect/direct evaporative cooler with alternative shapes and cooling media in direct stage Kulkarni.R.K 1, Rajput S.P.S 2 1 SVPM College of Engineering, Malegaon(bk),

More information

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3 1. OBJECTIVE The objective of this experiment is to observe four basic psychrometric processes

More information

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT

FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT FABRICATION SOLAR REFRIGERATION SYSTEM BY PELTIER EFFECT Sivakumar.N a*, Agathiyan.V, Dhanush.S, Gokulnath.V, Jagadhesan.R b, c, d, e UG Scholar, Department of Mechanical Engineering, Gnanamani College

More information

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning

More information

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED International Journal of Mechanical Engineering and Technology (IJMET) Volume 7, Issue 3, May June 2016, pp.329 341, Article ID: IJMET_07_03_030 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=7&itype=3

More information

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System Int. J. of Thermal & Environmental Engineering Volume 5, No. 1 (013) 41-50 A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System Abdulrahman T. Mohammad *,

More information

Solar Heating and Cooling Systems

Solar Heating and Cooling Systems Solar Heating and Cooling Systems Presented by: Dr. Georgios Florides Solar Space heating and Cooling A solar space heating and Cooling system can consist of a passive system, an active system, or a combination

More information

Adsorption refrigeration system using waste heat

Adsorption refrigeration system using waste heat Adsorption refrigeration system using waste heat 1 RISHI SREEKUMAR, 2 SANJEEV SINGH, 3 HIMANSHU SHEKHAR, 4 RAUSHAN KUMAR, 5 Dr. R. S. BINDU 1,2,3,4 BE Students, 5 Professor Mechanical Engineering Department

More information

ANALYSIS OF DESICCANT COOLING SYSTEM

ANALYSIS OF DESICCANT COOLING SYSTEM Int. J. Mech. Eng. & Rob. Res. 2012 Gaurav Pundir and S N Mishra, 2012 Research Paper ISSN 2278 0149 www.ijmerr.com Vol. 1, No. 3, October 2012 2012 IJMERR. All Rights Reserved ANALYSIS OF DESICCANT COOLING

More information

Modified Air Cooler with Split Cooling Unit

Modified Air Cooler with Split Cooling Unit Modified Air Cooler with Split Cooling Unit Nishant Dhanore 1, Krishna Shrivastava 2 1 SSBT s College of Engineering and Technology, Jalgaon (M.S.), India 2 Associate Professor, Mech. Engg. Dept. SSBT

More information

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) 4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015) Multi-stage Series Heat Pump Drying System with Dehumidification Simulation and Experiment Verification Chao

More information

Experimental Study of Direct Contact Condensation of Steam on Water Droplets

Experimental Study of Direct Contact Condensation of Steam on Water Droplets , July 1-3, 2015, London, U.K. Experimental Study of Direct Contact Condensation of Steam on Water Droplets Semra GUMRUK, Murat K. AKTAS Abstract Air or water cooled condensers are used to reduce the moisture

More information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger Abstract Shoeb J. Inamdar 1 H.S. Farkade 2 M. Tech student. (Thermal Engineering) 1, Asst. Professor 2 Department of Mechanical

More information

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Available online at   Energy Procedia 6 (2011) MEDGREEN 2011-LB Available online at www.sciencedirect.com Energy Procedia 6 (2011) 759 768 MEDGREEN 2011-LB Comparison of two methods of improving dehumidification in air conditioning systems: hybrid system (refrigeration

More information

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Available online at   ScienceDirect. Procedia Engineering 121 (2015 ) Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 121 (2015 ) 1222 1229 9th International Symposium on Heating, Ventilation and Air Conditioning (ISHVAC) and the 3rd International

More information

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis PARBHUBHAI R.TAILOR Department of Mechanical Engineering Sardar Vallabhbhai National Institute of Technology Surat,Gujarat-395007,INDIA

More information

Performance Analysis of a Solid Desiccant Air Dehumidifier

Performance Analysis of a Solid Desiccant Air Dehumidifier Performance Analysis of a Solid Desiccant Dehumidifier H. Mohamed Kamar *, N. Kamsah, K. N. A. Ku Shuib and N. A. Mufid Faculty of Mechancial Engineering, Universiti Teknologi Malaysia, 81310 Johor Bahru,

More information

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Available online at   ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang Available online at www.sciencedirect.com ScienceDirect Energy Procedia 7 (215 ) 418 426 International Conference on Solar Heating and Cooling for Buildings and Industry, SHC 214 Theoretical analysis and

More information

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER

STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER , Volume 6, Number 4, p.168-172, 2005 STUDY ON HYBRID SYSTEM OF SOLAR POWERED WATER HEATER AND ADSORPTION ICE MAKER Zhaohui Qi School of Energy Science and Engineering, Centralsouth University, Changsha,

More information

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former A study on reducing the energy demand of a liquid desiccant dehumidifier with a radiant panel system Tae Ha Leigh, 1 Dae Uk Shin, 1 Goo Sang Joe, 1 Min Gi Kim, 1 Myoung Souk Yeo, 2 and Kwang Woo Kim 2,*

More information

Institute of Sustainable Energy Technology, The University of Nottingham, NG7 2RD * Corresponding author

Institute of Sustainable Energy Technology, The University of Nottingham, NG7 2RD * Corresponding author 12 th International Conference on Sustainable Energy Technologies (SET-2013) 26-29th August, 2013 Hong Kong A Novel Solid Oxide Fuel Cell Tri-Generation System for Low Carbon Buildings Theo Elmer 1*, Mark

More information

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos

developed, and parametric studies are conducted with the model. Based on the parameter study results, a dehumidification performance diagram is propos Evaluation of A Plate Desiccant Outdoor Air-conditioning System Utilizing Cogenerated Hot Water Using A Numerical Model T. Baba 1, B. Park 1 1, *1, and T. Nagai 1 Department of Architecture, Tokyo University

More information

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Numbers of Abstract/Session (given by NOC) - 1 - STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE Seok Ho Yoon, Kong Hoon Lee, Chan Ho Song, and Ook Joong Kim Environment and Energy

More information

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER Gourav Roy; Taliv Hussain; Rahul Wandra Department of Mechanical Engineering, Lovely Professional

More information

Available online Journal of Scientific and Engineering Research, 2018, 5(11): Research Article

Available online   Journal of Scientific and Engineering Research, 2018, 5(11): Research Article Available online www.jsaer.com, 2018, 5(11):152-157 Research Article ISSN: 2394-2630 CODEN(USA): JSERBR Evaporation Cooling with Ceramics in Air-conditioning System Attila Szilágyi 1, István Farkas 2,

More information

Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system

Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system Paitoon Laodee 1,a*, Tawat Suriwong 1,b*, Sakda Somkun 1,c and Sukruedee Sukchai 1,d 1 School

More information

AiCARR Journal. 2015, 343, 52-58bis. Research paper ABSTRACT

AiCARR Journal. 2015, 343, 52-58bis. Research paper ABSTRACT AiCARR Journal 2015, 343, 52-58bis Research paper A DOUBLE EFFECT THERMAL DRIVEN AIR CONDITIONING SYSTEM USING AMMONIA/WATER ABSORPTION AND DES- ICCANT EVAPORATIVE COOLING Rossano Scoccia, Mario Motta

More information

Porous polypropylene membrane contactors for dehumidification of gases

Porous polypropylene membrane contactors for dehumidification of gases NANOSYSTEMS: PHYSICS, CHEMISTRY, MATHEMATICS, 2017, 8 (6), P. 798 803 Porous polypropylene membrane contactors for dehumidification of gases D. I. Petukhov, Ar. A. Eliseev, A. A. Poyarkov, A. V. Lukashin,

More information

Experimental Investigation of an Indirect Evaporative Cooler Consisting of a Heat Pipe Embedded in Porous Ceramic

Experimental Investigation of an Indirect Evaporative Cooler Consisting of a Heat Pipe Embedded in Porous Ceramic The Journal of Engineering Research 1 (2004) 46-52 Experimental Investigation of an Indirect Evaporative Cooler Consisting of a Heat Pipe Embedded in Porous Ceramic S. Riffat* and J. Zhu School of the

More information

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road 517583 AUTONOMOUS QUESTION BANK (DESCRIPTIVE) Subject with Code : Refrigeration and Air Conditioning (16ME8806) Course & Branch:

More information

New climate-control units for more energy-efficient electric vehicles: system architecture

New climate-control units for more energy-efficient electric vehicles: system architecture 2017 Twelfth International Conference on Ecological Vehicles and Renewable Energies (EVER) New climate-control units for more energy-efficient electric vehicles: system architecture Carlo Isetti, Enrico

More information

GAS FREE REFRIGERATOR USING PELTIER MODULE

GAS FREE REFRIGERATOR USING PELTIER MODULE GAS FREE REFRIGERATOR USING PELTIER MODULE 1 Shabarinathan K T, 2 Santhosh S, 3 Vishnu Gowtham B, 4 Udhaya Chandran RM [1][4] Assistant Professor, Department of Mechanical Engineering [2][3] UG Scholar,

More information

Experimental Investigation on Vapour Pressure of Desiccant for Air Conditioning Application

Experimental Investigation on Vapour Pressure of Desiccant for Air Conditioning Application Int. J. of Thermal & Environmental Engineering Volume 15, No. 1(17) 31-41 Experimental Investigation on Vapour Pressure of Desiccant for Air Conditioning Application S. Bouzenada a, *, L. Frainkin b, A.

More information

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid Simulation Analysis of Compression Refrigeration Cycle with Different Refrigerants P.Thangavel, Dr.P.Somasundaram, T.Sivakumar, C.Selva Kumar, G.Vetriselvan Abstract --- In this analysis, the performance

More information

GAW - WCCAP recommendation for aerosol drying

GAW - WCCAP recommendation for aerosol drying GAW - WCCAP recommendation for aerosol drying Alfred Wiedensohler and Wolfram Birmili Leibniz Institute for Tropospheric Research Humidity control One particular problem during summertime or in warm and

More information

Experimental study of operation performance of a low power thermoelectric cooling dehumidifier

Experimental study of operation performance of a low power thermoelectric cooling dehumidifier INTERNATIONAL JOURNAL OF ENERGY AND ENVIRONMENT Volume 1, Issue 3, 2010 pp.459-466 Journal homepage: www.ijee.ieefoundation.org Experimental study of operation performance of a low power thermoelectric

More information

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device

Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device Conditioning of outdoor air using rotating disk type liquid desiccant-air contacting device J R Mehta 1, A A Sujela 2 1 Department of Mechanical Engineering, Faculty of Technology and Engineering,The Maharaja

More information

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler International Journal of Thermal Technologies E-ISSN 2277 4114 2015 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Effect of Operating Parameters on the

More information

EXPERIMENTAL STUDY OF COUNTER FLOW AIR DEHUMIDIFIER FOR DIFFERENT PACKING HEIGHTS

EXPERIMENTAL STUDY OF COUNTER FLOW AIR DEHUMIDIFIER FOR DIFFERENT PACKING HEIGHTS EXPERIMENTAL STUDY OF COUNTER FLOW AIR DEHUMIDIFIER FOR DIFFERENT PACKING HEIGHTS Er. Satwinder Singh Assistant Professor, Department of Mechanical Engineering, Chandigarh Group of Colleges, Landran (Mohali),

More information

Thermodynamic Analysis of Combined Vapor Compression and Vapor Absorption Refrigeration System ABSTRACT

Thermodynamic Analysis of Combined Vapor Compression and Vapor Absorption Refrigeration System ABSTRACT Thermodynamic Analysis of Combined Vapor Compression and Vapor Absorption Refrigeration System AAMIR SHAIKH*, IKRAM KHURSHID*, ABDUL GHAFOOR MEMON*, AAKASH DEEP*, AND TAHWER HUSSAIN* RECEIVED ON 09.01.2017

More information

Experimental Analysis on Chemical Dehumidification of Air and Desiccant Regeneration with H2O/LiCl Solution

Experimental Analysis on Chemical Dehumidification of Air and Desiccant Regeneration with H2O/LiCl Solution Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2004 Experimental Analysis on Chemical Dehumidification of Air and Desiccant

More information

Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling

Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling Influences of temperature of vapour-condenser and pressure in the vacuum chamber on the cooling rate during vacuum cooling Tingxiang JIN,Gailian. LI,Chunxia HU School of Mechanical & Electricity engineering,zhengzhou

More information

SOLAR AIR CONDITONING SYSTEM USING DESSICANTS

SOLAR AIR CONDITONING SYSTEM USING DESSICANTS SOLAR AIR CONDITONING SYSTEM USING DESSICANTS Arjit Sharma Student, Mechanical Engineering Department Medicaps Institute Of Technology & Management arjit21sharma@gmail.com ABSTRACT- A new technology for

More information

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

More information

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY MASS & E ERGY BALA CES I PSYCHROMETRIC PROCESSES EXPERIME T 3 1. OBJECTIVE The object of this experiment is to observe four basic psychrometric processes

More information

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET

More information

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS Chainarong Chaktranond *, and Peachrakha Doungsong Department of Mechanical Engineering, Faculty of Engineering,

More information

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA)

INSTITUTE FOR ENVIRONMENTAL RESEARCH & SUSTAINABLE DEVELOPMENT NATIONAL OBSERVATORY OF ATHENS (NOA) 1 SOLAR COOLING An Overview of European Applications & Design Guidelines Costas Balaras, Ph.D. Member ASHRAE, Mechanical Engineer, Research Director GRoup Energy Conservation (GR.E.C.) INSTITUTE FOR ENVIRONMENTAL

More information

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India

Performance of solid desiccant-based evaporative cooling system under the climatic zones of India *Corresponding author: hemant_parmar1@ rediffmail.com Performance of solid desiccant-based evaporative cooling system under the climatic zones of India... H. Parmar 1 * and D.A. Hindoliya 2 1 Department

More information

4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013

4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013 4th IIR International Conference on Thermophysical Properties and Transfer Processes of Refrigerants 2013 Refrigeration Science and Technology Proceedings 2013-3 Delft, The Netherlands 17-19 June 2013

More information

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5 International Journal of Research in Engineering and Innovation Vol-3, Issue- (9), -5 International Journal of Research in Engineering and Innovation (IJREI) journal home page: http://www.ijrei.com ISSN

More information

Performance Analysis of Domestic Refrigeration System with Thermoelectric Module

Performance Analysis of Domestic Refrigeration System with Thermoelectric Module Performance Analysis of Domestic Refrigeration System with Thermoelectric Module #1 Suyog S. Bajaj, #2 S. H. Barhatte #1 Department of Mechanical Engineering, Savitribai Phule Pune University, MIT College

More information

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance Measurement of R32 Vapor Injection Heat Pump System Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 212 Performance Measurement of Vapor Injection Heat Pump System Yunho Hwang

More information

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE

THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE THERMAL PERFORMANCE ASSESSMENT OF GREENHOUSE SOLAR DRYER UNDER PASSIVE MODE Pushpendra Singh 1, Vipin Shrivastava 2 1,2 Mechanical Engineering Department, Lakshmi Narain College of Technology (India) ABSTRACT

More information

Hygrometry. The art or science of humidity observation

Hygrometry. The art or science of humidity observation Hygrometry The art or science of humidity observation Humidity Under normal atmospheric conditions, the amount of water vapor any sample of air can hold depends primarily on its temperature Various terms

More information

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE Proceedings of the Asian Conference on Thermal Sciences 2017, 1st ACTS March 26-30, 2017, Jeju Island, Korea ACTS-P00385 THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK

More information

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger Chetan Papade Department of Mechanical Engineering N.K.Orchid college of Engg.& Tech., Solapur, Maharashtra,

More information

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential

More information