MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A

Size: px
Start display at page:

Download "MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A"

Transcription

1 FORM EG1 (915) MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A 50 Through 170 Tons 175 Through 597 Kw 60Hz R-410a

2 FORM EG1 (915) Nomenclature YCRL 0118 S E 46 X A UNIT TYPE YORK Water Cooled Scroll Compressor Condenser Unit MODEL # REFRIGERANT R-410A UNIT DESIGNATOR H = High Efficiency S = Standard Efficiency VOLTAGE CODE 17 = 200/3/60 28 = 230/3/60 46 = 380/3/60 50 = /3/50 58 = 575/3/60 DESIGN SERIES STARTER X = Across The Line Start Performance data provided in this document was created in accordance with Johnson Controls software: YORKworks version and DXCHILL version Approvals ASME Boiler and Pressure Vessel Code Section Vlll Division 1 AHRI Standard 550/590 c/u.l. Underwriters Laboratory ASHRAE 15 Safety Code for Mechanical Refrigeration ASHRAE Guideline 3 Reducing Emission of Halogenated Refrigerants in Refrigeration and Air Conditioning Equipment and Systems N.E.C. National Electrical Code OSHA Occupational Safety and Health Act 2 JOHNSON CONTROLS

3 Table of Contents FORM EG1 (915) EQUIPMENT OVERVIEW... 5 MICROPROCESSOR CONTROLS... 7 ACCESSORIES AND OPTIONS REFRIGERANT FLOW DIAGRAM DESIGN PARAMETERS PRESSURE DROP CURVES SELECTION DATA UNIT COMPONENTS RATINGS PHYSICAL DATA HIGH EFFICIENCY ISOLATOR SELECTION DATA ISOLATOR INFORMATION SOUND DATA UNIT DIMENSIONS SINGLE POINT ELECTRICAL DATA DUAL POINT ELECTRICAL DATA ELECTRICAL NOTES GROUND WIRE SIZING TYPICAL CONTROL PANEL WIRING CUSTOMER WIRING INFORMATION APPLICATION DATA GUIDE SPECIFICATIONS JOHNSON CONTROLS 3

4 FORM EG1 (915) THIS PAGE INTENTIONALLY LEFT BLANK. 4 JOHNSON CONTROLS

5 Equipment Overview FORM EG1 (915) YORK YCRL Remote Condenser Liquid Chillers provide chilled water for all air conditioning applications that use central station air handling or terminal units. They are self-contained and are designed for indoor (new or retrofit) installation. Each unit includes hermetic scroll compressors, a liquid evaporator, and a user-friendly, diagnostic Microcomputer Control Center all mounted on a rugged steel base. Remote condensers (model VDC) are available separately from Johnson Controls. The units are produced at an ISO 9001 registered facility. The YCRL chillers are rated in accordance with AHRI Standard 550/590. GENERAL The chiller will be completely assembled with all interconnecting refrigerant piping and internal wiring, ready for field connection to a remote condenser. The unit will be pressure-tested, evacuated, and charged with a nitrogen holding charge, and York V (POE) synthetic oil. The unit can be covered with an optional overspray coat of Caribbean Blue enamel. Units are designed in accordance with NFPA 70 (National Electric Code), ASHRAE/ANSI 15 Safety Code for Mechanical Refrigeration. All units are produced at an ISO 9001 registered facility. All YCRL condensing units are rated in accordance with AHRI Standard 550/590 at AHRI conditions. COMPRESSORS The chiller has suction-gas cooled, hermetic, scroll compressors. The YCRL s compressors incorporate a compliant scroll design in both the axial and radial direction. All rotating parts are statically and dynamically balanced. A large internal volume and oil reservoir provides greater liquid tolerance. Compressor crankcase heaters are also included for extra protection against liquid migration. All compressors are mounted on isolator pads to reduce transmission of vibration to the rest of the unit. REFRIGERANT CIRCUIT Two independent refrigerant circuits will be furnished on each unit. All piping will be copper with brazed joints. The liquid line will include: a shutoff valve with charging port; sightglass with moisture indicator; thermal expansion valve; solenoid valve; and high-absorption removable-core filter drier. The entire suction line and the liquid line between the expansion valve and the cooler will be insulated with flexible, closed-cell, foam insulation. POWER AND CONTROL PANELS All controls and motor starting equipment necessary for unit operation shall be factory wired and function tested. The panel enclosures shall be designed to NEMA 1 (IP 32) and manufactured from powder-painted galvanized steel. The Power and Control Panel shall be divided into a power section for each electrical system, a common input section and a control section. JOHNSON CONTROLS 5

6 FORM EG1 (915) Equipment Overview (Cont'd) Each power panel shall contain: compressor starting contactors, control circuit serving compressor capacity control, compressor contactor coils, and compressor motor overloads. The compressor motor overloads contain current transformers which sense each phase, as an input to the microprocessor, to protect the compressor motors from damage due to low input current, high input current, unbalanced current, single phasing, phase reversal, and compressor locked rotor. The common input section shall contain: the control supply transformer providing 115V, customer relay board and control circuit switch disconnect/emergency stop device. 6 JOHNSON CONTROLS

7 Microprocessor Controls FORM EG1 (915) MICROPROCESSOR CONTROLS The control section shall contain: On/Off rocker switch, microcomputer keypad and display, microprocessor board, I/O expansion board, relay boards, and 24V fused power supply board. The control display shall include: Liquid Crystal Display with Light Emitting Diode backlighting for outdoor viewing: Two display lines Twenty characters per line Color coded 12-button non-tactile keypad with sections for Display/Print of typical information: Chilled liquid temperatures System pressures (each circuit) Operating hours and starts (each compressor) Print calls up to the liquid crystal display: Operating data for the systems History of fault shutdown data for up to the last six fault shutdown conditions An RS-232 port, in conjunction with this press-to-print button, is provided to permit the capability of hard copy print-outs via a separate printer (by others). Entry section to: ENTER setpoints or modify system values Setpoints updating can be performed to: Chilled liquid temperature setpoint and range Remote reset temperature range Set daily schedule/holiday for start/stop Manual override for servicing Number of compressors Low liquid temperature cutout Low suction pressure cutout High discharge pressure cutout Anti-recycle timer (compressor start cycle time) Anti-coincident timer (delay compressor starts) JOHNSON CONTROLS 7

8 FORM EG1 (915) Microprocessor Controls (Cont'd) Unit section to: Set time Set unit options The microprocessor control center is capable of displaying the following: Return and leaving chilled liquid temperature Low leaving liquid temperature cutout setting English or Metric data Suction pressure cutout setting Each system suction pressure Discharge pressure Liquid Temperature Reset via a Building Automation System via a 4-20 milliamp input or a 0-10 VDC input Anti-recycle timer status for each system Anti-coincident system start timer condition Compressor run status No cooling load condition Day, date and time Daily start/stop times Holiday status Automatic or manual system lead/lag control Lead system definition Compressor starts & operating hours (each compressor) Status of hot gas valves (if supplied) Run permissive status Number of compressors running Liquid solenoid valve status Load & unload timer status 8 JOHNSON CONTROLS

9 Microprocessor Controls (Cont'd) FORM EG1 (915) The standard controls shall include: automatic pumpdown, run signal contacts, demand load limit form external building automation system input, remote reset liquid temperature reset input, unit alarm contacts, chilled liquid pump control, automatic reset after power failure, automatic system optimization to match operating conditions. The operating program software shall be stored in nonvolatile memory (EPROM) to eliminate chiller failure due to AC power failure. Programmed setpoints are retained in lithium battery-backed regulated time clock (RTC) memory for 5 years minimum. COMMUNICATIONS Native communication capability for BACnet (MS/TP) and Modbus Optional communciation available for N2 and LON via elink option JOHNSON CONTROLS 9

10 FORM EG1 (915) Accessories and Options All accessories and options are factory mounted unless otherwise noted. POWER OPTIONS Single Point Supply Terminal Block The standard power wiring connection on all models is a single point power connection to a factory provided terminal block. Components included are the enclosure, terminal block and interconnecting wiring to the compressors. Separate external protection must be supplied, by others, in the incoming power wiring. Single Point Circuit Breaker An optional unit mounted circuit breaker with external, lockable handle (in compliance with N.E.C. Article ), can be supplied to isolate the power voltage for servicing. Multiple Point Circuit Breaker Optional multiple point supply with independent system circuit breakers and locking external handles (in compliance with Article of N.E.C.) can be factory supplied. Control Transformer Converts unit power voltage to (0.5 or 1.0 KVA capacity). Factory mounting includes primary and secondary wiring between the transformer and the control panel. CONTROLS OPTIONS Language LCD And Keypad Standard display language and keypad is in English. Spanish, French, German, and Italian are available as an option. HEAT EXCHANGER OPTIONS Flow Switch An optional flow switch can be factory supplied for the evaporator. Vapor proof SPDT, NEMA 3R switch, 150 PSIG (10.3 bar) DWP, 20 F to 250 F ( 29 C to 121 C) with 1 NPT (IPS) connection for upright mounting in horizontal pipe. The flow switch or its equivalent must be furnished with each unit. (Field Mounted) Differential Pressure Switch An alternative option to the paddle type flow switch PSIG (0.2 3 bar) range with ¼ NPTE pressure connections. (Field Mounted) Pressure Vessel Codes Evaporator is supplied (Standard) in conformance with the A.S.M.E. pres sure codes. Flanges (ANSI/AWWA C 606 Couplings Type) Consists of (2) flange adapters for grooved end pipe on evaporator (note: the 0064HE units do not include evaporator flanges). Standard 150 PSIG (10.3 bar). (Field Kit, matching pipe flange by contractor.) Double Thick Insulation Doubled thickness (totalling 1 1/2 or 38mm) insulation provided on the evaporator 10 JOHNSON CONTROLS

11 Accessories and Options (Cont'd) FORM EG1 (915) CHILLER OPTIONS Final Paint Overspray Overspray painting of unit after assembly. Service Isolation Valve Service suction isolation valve added to unit per system in addition to the standard discharge service valve. Hot Gas By-Pass Permits continuous, stable operation at capacities below the minimum step of compressor unloading to as low as 5% capacity (depending on both the unit and operating conditions) by introducing an artificial load on the evaporator. Hot gas by pass is installed on only refrigerant system #2 on two circuited units. Compressor Acoustic Sound Blanket Each compressor is individually enclosed by an acoustic sound blanket. The sound blankets are made with one layer of acoustical absorbent textile fiber of 5/8 (15mm) thickness; one layer of anti vibrating heavy material thickness of 1/8 (3mm). Both are closed by two sheets of welded PVC, reinforced for temperature and UV resistance. VIBRATION ISOLATION Rubber Isolators Recommended for normal in stallations. Provides very good performance in most applications for the least cost. (Field Installed) 1 Spring Isolators Level adjustable, spring and cage type isolators for mounting under the unit base rails. 1 nominal deflection may vary slightly by ap plication. (Field Installed) 2 Spring Isolators Restrained Spring Flex Mount ings incorporate a rugged welded steel housing with vertical and horizontal limit stops. Housings designed to withstand a minimum 1.0g accelerated force in all directions to 2. Level adjustable, deflection may vary slightly by application. (Field Installed) JOHNSON CONTROLS 11

12 FORM EG1 (915) Refrigerant Flow Diagram Low-pressure liquid refrigerant enters the evaporator tubes and is evaporated and superheated by the heat energy absorbed from the chilled liquid passing through the evaporator shell. Low-pressure vapor enters the compressor where pressure and superheat are increased. High-pressure vapor is passed through a remote condenser where heat is rejected to the air flow passing through the coil. The fully condensed and subcooled liquid leaves the condenser and enters the expansion valve, where pressure reduction and further cooling take place. The low pressure liquid refrigerant then returns to the evaporator. 12 JOHNSON CONTROLS

13 Design Parameters FORM EG1 (915) YCRL EVAPORATOR FLOW (GPM) DESIGN PARAMETERS LEAVING EVAPORATOR WATER TEMP. F (C ) MIN SAT. DISCH. TEMP. F (C ) MAX. SAT DISCH TEMP F (C ) EQUIPMENT ROOM TEMP. F (C ) MIN MAX MIN 1 MAX 2 MIN MAX MIN MAX 0064HE HE HE HE HE HE ) HE SE SE NOTES: 1. For leaving brine temperature below 40 F (4.4 C), contact the nearest Johnson Controls Office for application requirements. 2. For leaving water temperature higher than 50 F (10 C), contact the nearest Johnson Controls Office for application guidelines. JOHNSON CONTROLS 13

14 FORM EG1 (915) Pressure Drop Curves YCRL Evaporator Pressure Drop (English) A B D Pressure Drop (ft. H 2 O) 10.0 C Water Flow Rate (GPM) LD18634 EVAPORATOR A B C D YCRL 0064HE 0074HE, 0084HE, 0118HE, 0096HE 0126HE, 0156HE, 0177SE, 198SE YCRL Evaporator Pressure Drop (SI) Pressure Drop (kpa) C A B D Water Flow Rate (l/s) LD JOHNSON CONTROLS

15 Selection Data FORM EG1 (915) GUIDE TO SELECTION Complete water chilling capacity ratings for YORK YCRL condensing units are shown on the following pages to cover the majority of job requirements. For any application beyond the scope of this Engineering Guide, consult your nearest Johnson Controls office. SELECTION RULES 1. Ratings - All YCRL ratings are in accordance with AHRI Standard 550/590, at the AHRI standard condi tions. Ratings not at standard AHRI conditions are rated in accordance with AHRI rating procedures. These ratings may be interpolated but extrapolated. 2. Cooling Water Quantity - Ratings are based on 10ºF chilled water range with the evaporator at sea level. Use the chilled water correction factors (below) for other ranges except as limited by water pressure drop, minimum or maximum water flows for the evaporator. 3. Fouling Factors Ratings are based on evaporator fouling factor. For other fouling factors, consult the table below or contact your Johnson Controls representative. EVAPORATOR CORRECTION FACTORS FF=TEMP SPLIT TONS COMPR KW TONS COMPR KW Ethylene Glycol Correction Factors The following factors are to be applied to the standard ratings for units cooling ethylene glycol. ETHYLENE GLYCOL %WEIGHT TONS COMPR PRESS FREEZE GPM KW DROP POINT Propylene Glycol Correction Factors The following factors are to be applied to the standard ratings for units cooling propylene glycol. PROPYLENE GLYCOL %WEIGHT TONS COMPR PRESS FREEZE GPM KW DROP POINT < JOHNSON CONTROLS 15

16 FORM EG1 (915) Selection Data (Cont'd) METHOD OF SELECTION If the duty requires a 10ºF (6 C) range on the evaporator, see Ratings. For water ranges other than 10ºF (6 C), use the following procedure. Line sizes can be determined by reviewing York DX Piping Guide ES2. 1. Determine capacity required from the following formula: Capacity (Tons) = GPM x Chilled Water Range ( F) After applying any fouling factor corrections, the actual condenser heat rejection may be determined as follows: Heat Rejection (MBH) = Heat Rejection (Btuh) 1000 = (Tons x 12) = (kw x 3.415) 3. Size condenser using manufacturer s recommendations. SAMPLE SELECTION Water Cooled Chiller (YCRL) GIVEN Chill 200 GPM of water from 56ºF to 44ºF and evaporator fouling factor with 125 F saturated discharge temperature. FIND The required unit size capacity, kw, EER, and water pressure drop, and the condenser MBH heat rejection. SOLUTION: 1. Chilled water range = 56ºF - 44ºF = 12ºF and correction factors are for Tons and for kw for the evaporator. Capacity (Tons) = GPM x Chilled Water Range ( F) 24 = 200 x = 100TR 2. From the rating, a model YCRL0118HE has a capacity range required. For the evaporator leaving water temperature of 44ºF and a saturated discharge temperature of 125 F, the unit capacity rating table indicates: Tons = KW = EER = 11.1 Correcting for the 12ºF chilled water range: Tons = x = TR KW = x = kw 16 JOHNSON CONTROLS

17 Selection Data (Cont'd) FORM EG1 (915) 3. Determine the average full load kw and EER at 100 Tons x (110.1) = EER = Tons x x 12 = kw = Determine the condensing Heat rejection as follows: Heat Rejection (MBH) = (Tons x 12) + (kw x 3.415) = (102.6 x 12) + (110.1 x 3.415) = = From "Pressure Drop Curves" on page 14, locate the pressure drops with 200 GPM through the evaporator of the Model YCRL118HE: The unit is suitable. Evaporator Pressure Drop at 200 GPM = 8 ft JOHNSON CONTROLS 17

18 FORM EG1 (915) Selection Data (Cont'd) REFRIGERANT PIPING General When the unit has been located in its final position, the unit piping may be connected. Normal installation precautions should be observed in order to receive maximum operating efficiencies. System piping should conform to the York DX Piping Guide form ES2 or ASHRAE refrigeration handbook guidelines. All piping design and installation is the responsibility of the user. JOHNSON CONTROLS ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM OPERATION OR FAILURES DUE TO IMPROPER PIPING OR PIPING DESIGN. All filter driers, sight glasses, expansion valves and liquid line solenoid valves are factory installed on each refrigerant circuit. Interconnecting refrigerant piping and refrigerant charge are supplied and installed by others. Table 1 lists refrigerant line connections sizes per unit model number. Table 1 - YCRL LINE CONNECTION SIZES YCRL LIQUID LINE SYSTEM 1, IN. LIQUID LINE SYSTEM 2, IN. DISCHARGE LINE SYSTEM 1, IN. DISCHARGE LINE SYSTEM 2, IN. 0064HE 7/8 7/8 1-3/8 1-3/8 0074HE 1-1/8 7/8 1-5/8 1-3/8 0084HE 1-1/8 1-1/8 1-5/8 1-5/8 0096HE 1-1/8 1-1/8 1-3/8 1-3/8 0118HE 1-1/8 1-1/8 1-5/8 1-5/8 0126HE 1-1/8 1-1/8 2-1/8 2-1/8 0156HE 1-1/8 1-1/8 2-1/8 2-1/8 0177SE 1-1/8 1-1/8 2-1/8 2-1/8 0198SE 1-1/8 1-1/8 2-1/8 2-1/8 REFRIGERANT LINE SIZING Refrigerant piping systems must be designed to provide practical line sizes without excessive pressure drops, prevent compressor oil from being trapped in the refrigerant piping, and ensure proper flow of liquid refrigerant to the thermal expansion valve. Be sure to review form ES2. Considerations should be given to: 1. Discharge line pressure drop due to refrigerant flow. 2. Discharge line refrigerant velocity for oil return. 3. Liquid line pressure drop due to refrigerant flow. 4. Liquid line pressure drop (or gain) due to vertical rise of the liquid line. To ensure a solid column of liquid refrigerant to the expansion valve, the total liquid line pressure drop should never exceed 40 PSIG (2.8 barg). Refrigerant vapor in the liquid line will measurably reduce valve capacity and poor system performance can be expected. To allow adequate oil return to the compressor, discharge risers should be sized for a minimum of 1000 FPM (5.08 m/s) while the system is operating at minimum capacity to ensure oil return up the suction riser. 18 JOHNSON CONTROLS

19 Selection Data (Cont'd) FORM EG1 (915) Chiller Below Condenser On a system where the chiller is located below the condenser, the discharge line must be sized for both pressure drop and oil return. In some cases a double discharge riser must be installed to ensure reliable oil return at reduced loads. Condenser Below Chiller When the condenser is located below the chiller, the liquid line must be designed for both friction loss and static head loss due the vertical rise. The value of static head loss of 5 PSI/ft. (3.4 kpa/30 cm) must be added to the friction loss pressure drop in addition to all pressure drops due to driers, valves, etc. OIL TRAPS All horizontal discharge lines should be pitched at least 1/4 per foot (2 cm/m) in the direction of the refrigerant flow to aid in the return of oil to the chiller. All discharge lines with a vertical rise exceeding 3 feet (.91 meters) should have a P trap at the bottom and top of the riser. Discharge lines with a vertical rise exceeding 25 feet (7.6 meters) should be trapped every 15 feet (4.6 meters). REFRIGERANT CHARGE The chiller is charged and shipped with a dry nitrogen holding charge. The operating charge for the chiller, remote condenser and refrigerant piping must be weighed in after all refrigerant piping is installed, leak checked, and evacuated. Final adjustment of refrigerant charge should be verified by subcooling values (refer to IOM section on Pre-Startup for checking subcooling). REFRIGERANT PIPING REFERENCE For more details, refer to ASHRAE Refrigeration Handbook, Chapter 2. Table 2 - YCRL CHILLER CHARGES YCRL TOTAL HFC-410A CHARGE, LBS PER SYSTEM, LBS 0064HE HE HE HE HE HE HE SE / SE JOHNSON CONTROLS 19

20 FORM EG1 (915) Unit Components (OPT) LD JOHNSON CONTROLS

21 Unit Components (Cont'd) FORM EG1 (915) LD18645 JOHNSON CONTROLS 21

22 FORM EG1 (915) Ratings YCRL0064HE IPLV= 17.7 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0074HE IPLV= 17.7 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0084HE IPLV= 18.7 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0096HE IPLV= 18.4 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0118HE IPLV= 18.5 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER NOTES: 1. Tons = Unit Cooling Capacity Output 2. KW = Compressor Input Power 3. MBH = Condenser Heat Rejection 4. EER = Chiller Energy Efficiency Ratio 5. LCWT = Leaving Chilled Water Temperature 6. Provided ratings are in accordance with AHRI 550/590 but condenserless chillers are outside the scope of the AHRI certification program. 22 JOHNSON CONTROLS

23 Ratings (Cont'd) FORM EG1 (915) YCRL0126HE IPLV= 19.6 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0156HE IPLV= 18.0 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0177SE IPLV= 19.0 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER YCRL0198SE IPLV= 19.1 SATURATED DISCHARGE TEMP LCWT ( F) TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER TONS KW EER NOTES: 1. Tons = Unit Cooling Capacity Output 2. KW = Compressor Input Power 3. MBH = Condenser Heat Rejection 4. EER = Chiller Energy Efficiency Ratio 5. LCWT = Leaving Chilled Water Temperature 6. Provided ratings are in accordance with AHRI 550/590 but condenserless chillers are outside the scope of the AHRI certification program. JOHNSON CONTROLS 23

24 FORM EG1 (915) Physical Data High Efficiency YCRL 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE 0177SE 0198SE GENERAL UNIT DATA NOMINAL UNIT CAPACITY (TONS) NUMBER OF INDEPENDENT REFRIGERANT CIRCUITS OIL CHARGE, CKT. 1/CKT. 2, (GAL.) 2.2/ / / / / / / / /4.7 SHIPPING WEIGHT (LBS.) OPERATING WEIGHT (LBS.) COMPRESSORS, SCROLL QUANTITY PER CHILLER NOMINAL SIZE CKT. 1/ CKT / / / / / / / / / EVAPORATOR WATER VOLUME (GALS.) MAXIMUM WATER SIDE PRESSURE (PSIG) MAXIMUM REFRIGERANT SIDE PRESSURE (PSIG) DIA. X LENGTH (INCHES X FEET) 13 X 8 16 X 8 16 X 8 15 X X WATER NOZZLE CONNECTION SIZE, (IN.) JOHNSON CONTROLS

25 Isolator Selection Data FORM EG1 (915) LD18636 YCRL UNIT SHIPPING WEIGHT TOTAL OPERATING WEIGHT WEIGHT ON EACH FRONT ISOLATOR WEIGHT ON EACH BACK ISOLATOR 1" SPRING ISOLATOR SELECTION NEOPRENE ISOLATOR 2" SPRING ISOLATOR SLRS-2-C2-0064HE CP-1D-1200 GRAY 0074HE CP-1D-1200 GRAY 0084HE CP-1D-1200 GRAY 0096HE CP-1D-1360 WHITE 0118HE CP-1D-1360 WHITE 0126HE CP-1D-1785N GRAY/RED 0156HE C2P-1D-2400 GRAY 0177SE SE CP-1D-1785N GRAY/RED C2P-1D-1800 DARK GREEN RD-3 CHARCOAL RD-4 BRICK RED RD-4 BRICK RED RD-4 BRICK RED RD-4 BRICK RED RD-4 BRICK RED RD-4 BRICK RED RD-4 BRICK RED RD-4 BRICK RED RED/BLACK RED/BLACK RED/BLACK PINK PINK PINK/GRAY PINK/GRAY PINK PINK/GRAY JOHNSON CONTROLS 25

26 FORM EG1 (915) Isolator Information ELASTOMERIC ISOLATOR RDX- DW DW HF CD MOLDED DURULENE HF CD MOLDED DURULENE L AL Ø = AD Thru Typ 2 Places BT W BT AL L R = Slot Typ 2 Places W LD17304 MOUNT TYPE DIMENSION DATA (INCHES) L W HF AL AD BT CD DW RD1-WR /16-18 UNC X 3/ RD2-WR /8-16 UNC X RD3-WR /2-13 UNC X RD4-WR /2-13 UNC X MODEL NUMBER ISOLATOR COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS) RD-3-CHARCOAL-WR CHARCOAL Up thru 825 UP TO 374 RD-4-BRICK RED-WR BRICK RED 826 thru RD-4-CHARCOAL-WR CHARCOAL 1689 thru JOHNSON CONTROLS

27 Isolator Information (Cont'd) FORM EG1 (915) ONE INCH DEFLECTION SPRING ISOLATOR CP- EQUIPMENT BASE (BY OTHERS) POSITIONING PIN LD18443 MOUNT TYPE DIMENSION DATA (INCHES) W D L B C T H CP 3 5/8 7-3/4 6-1/2 4-3/4 1/2 5-5/8 C2P 3 5/8 10-1/2 9-1/4 7-3/4 9/16 6 MODEL NUMBER COLOR CODE RATED CAPACITY (FOR UNITS WITH ALL LOAD POINTS LESS THAN 1785 LBS (810 KG) LBS. KG CP-1D-510 BLACK Up thru 434 Up thru 197 CP-1D-900 DARK GREEN 435 thru thru 347 CP-1D-1200 GRAY 766 thru thru 463 CP-1D-1360 WHITE 1021 thru thru 524 CP-1D-1785N GRAY/RED 1157 thru thru 810 MODEL NUMBER COLOR CODE RATED CAPACITY (FOR UNITS WITH ANY LOAD POINT ABOVE 1518 LBS (689 KG) LBS. KG C2P-1D-1350 DARK PURPLE Up thru 1148 Up to 521 C2P-1D-1350 DARK PURPLE Up thru 1148 Up to 521 C2P-1D-1800 DARK GREEN 1149 thru C2P-1D-2400 GRAY 1531 thru C2P-1D-2400 GRAY 1531 thru C2P-1D-2720 WHITE 2041 thru C2P-1D-3570N GRAY/RED 2313 thru JOHNSON CONTROLS 27

28 FORM EG1 (915) Isolator Information (Cont'd) TWO INCH DEFLECTION, SPRING ISOLATOR Y2RS- 1-1/8 5/8 2-3/4 2-3/4 3/8 GAP 3/4 TYP. (4) 8 P 4 3/4 7/8 4 4 STOP & 8-3/8 OPER. HEIGHT 8 LD18442 MODEL NUMBER ISOLATOR COLOR WEIGHT RANGE (LBS) WEIGHT RANGE (KGS) Y2RSI-2D-460 GREEN Up thru 391 UP TO 177 Y2RSI-2D-710 DARK BROWN 392 thru Y2RSI-2D-870 RED 605 thru Y2RSI-2D-1200N RED/BLACK 741 thru Y2RSI-2D-1690 PINK 1021 thru Y2RSI-2D-2640N PINK/GRAY 1438 thru Y2RSI-2D-2870N PINK/GRAY/ORANGE 2245 thru Y2RSI-2D-3280N PINK/GRAY/DK.BROWN 2619 thru JOHNSON CONTROLS

29 Sound Data FORM EG1 (915) BASE UNITS (ARI 575 SOUND PRESSURE LEVELS DB RE: 20 YCRL MICROPASCALS) DBA 0064HE HE HE HE HE HE HE SE SE COMPRESSOR ACOUSTIC BLANKETS (ARI) 575 SOUND PRESSURE YCRL LEVELS DB RE: 20 MICROPASCALS) DBA 0064HE HE HE HE HE HE HE SE SE JOHNSON CONTROLS 29

30 FORM EG1 (915) Unit Dimensions FOUR COMPRESSOR YCRL 0064HE 0074HE 0084HE 0118HE W H L A B D E F G J K M N R S T U X AA BB CC DD EE FF GG GG HH H* - for 200/230 volt units, which require a larger electrical enclosure 30 JOHNSON CONTROLS

31 Unit Dimensions (Cont'd) FORM EG1 (915) FOUR COMPRESSOR ( 0,0 ) SEE NOTE 1 RELIEF VALVE INLET OUTLET LD18637 NOTES: 1. Recommended service clearances. Rear to wall: 20 (508mm) Front to wall: 36 (915mm) Top: 43 (1092mm) Tube cleaning and removal: 132 (3353mm) either end 2. Relief valve connection sizes. Low side (suction line): 1/2 flare JOHNSON CONTROLS 31

32 FORM EG1 (915) Unit Dimensions (Cont'd) FIVE & SIX COMPRESSOR YCRL 0096HE 0126HE 0156HE 0177SE 0198SE W H L A B D E F G J K M N R S T U X AA BB CC DD EE FF GG GG HH H* - for 200/230 volt units, which require a larger electrical enclosure 32 JOHNSON CONTROLS

33 Unit Dimensions (Cont'd) FORM EG1 (915) FIVE & SIX COMPRESSOR ( 0,0 ) SEE NOTE 1 INLET OUTLET RELIEF VALVE EE LD18638 NOTES: 1. Recommended service clearances. Rear to wall: 20 (508mm) Front to wall: 36 (915mm) Top: 43 (1092mm) Tube cleaning and removal: 132 (3353mm) either end 2. Relief valve connection sizes. Low side (suction line): 1/2 flare JOHNSON CONTROLS 33

34 FORM EG1 (915) Single Point Electrical Data WITHOUT OPTIONAL EXTERNAL COMPRESSOR OVERLOADS YCRL 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE 0177SE 0198SE MINIMUM CIRCUIT AMPS MCA MIN N/F DISC SW MDSW MIN DUAL ELEM FUSE MAX DUAL ELEM FUSE LUGS PER PHASE VOLT HZ CIRCUIT BREAKER LUG TERMINAL BLOCK LUG SIZE (OPT) SIZE (STD) QTY/ LUG INFO QTY/ LUG INFO KCM 1 # KCM KCM 1 # KCM # KCM 1 # KCM # 2-4/0 AWG 1 # KCM # 2-4/0 AWG 1 # KCM KCM 1 # KCM KCM 1 # KCM # KCM 1 # KCM # 2-4/0 AWG 1 # KCM # 2-4/0 AWG 1 # KCM KCM 1 # KCM KCM 1 # KCM # KCM 1 # KCM # 2-4/0 AWG 1 # KCM # 2-4/0 AWG 1 # KCM KCM 2 # KCM KCM 2 # KCM # KCM 1 # KCM # KCM 1 # KCM # KCM 1 # KCM KCM 2 # KCM KCM 2 # KCM KCM 1 # KCM # KCM 1 # KCM # KCM 1 # KCM KCM 2 # KCM KCM 2 # KCM # KCM 1 # KCM # KCM 1 # KCM # KCM 1 # KCM KCM 2 # KCM KCM 2 # KCM KCM 2 # KCM KCM 1 # KCM KCM 1 # KCM * * 2 # KCM KCM 1 # KCM #6 AWG KCM 1 # KCM KCM 2 # KCM #3/0-250 KCM 1 # KCM KCM 1 # KCM * - Contact Johnson Controls 34 JOHNSON CONTROLS

35 Single Point Electrical Data (Cont'd) FORM EG1 (915) WITHOUT OPTIONAL EXTERNAL COMPRESSOR OVERLOADS SYSTEM # 1 SYSTEM # 2 YCRL COMPR 1 COMPR 2 COMPR 3 COMPR 1 COMPR 2 COMPR 3 RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA RLA LRA 0064HE 0074HE 0084HE 0118HE 0096HE 0126HE 0156HE 0177SE 0198SE JOHNSON CONTROLS 35

36 FORM EG1 (915) Dual Point Electrical Data WITHOUT EXTERNAL COMPRESSOR OVERLOADS YCRL VOLT HZ 0064HE 0074HE 0084HE 0118HE 0096HE 0126HE 0156HE 0177SE 0198SE MINIMUM CIRCUIT AMPS SYSTEM 1 WIRING MIN N/F DISC SW MIN DUAL ELEM FUSE & MIN CB MAX DUAL ELEM FUSE & MAX CB MINIMUM CIRCUIT AMPS SYSTEM 2 WIRING MIN N/F DISC SW MIN DUAL ELEM FUSE & MIN CB MAX DUAL ELEM FUSE & MAX CB JOHNSON CONTROLS

37 Dual Point Electrical Data (Cont'd) FORM EG1 (915) WITHOUT EXTERNAL COMPRESSOR OVERLOADS YCRL VOLT QTY SYSTEM 1 CIRCUIT BREAKER LUG SIZE LUG INFO SYSTEM # 1 SYSTEM 2 CIRCUIT SYSTEM # 2 COMPR COMPR COMPR BREAKER LUG SIZE COMPR 1COMPR 2COMPR 3 RLA LRA RLA LRA RLA LRA QTY LUG INFO RLA LRA RLA LRA RLA LRA 0064HE 0074HE 0084HE 0096HE 0118HE 0126HE 0156HE 0177SE 0198SE #6-350 kcmil #6-350 kcmil #6-350 kcmil #6-350 kcmil #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #6-350 kcmil #6-350 kcmil #6-350 kcmil #6-350 kcmil #2-4/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #6-350 kcmil #6-350 kcmil #6-350 kcmil #6-350 kcmil #2-4/0AWG #2-4/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG kcmil #6-350 kcmil kcmil #6-350 kcmil #6-350 kcmil #6-350 kcmil #6-350 kcmil #2-4/0AWG #2-4/0AWG #14-1/0AWG #6-350 kcmil #6-350 kcmil #6-350 kcmil #6-350 kcmil #2-4/0AWG #2-4/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG #14-1/0AWG kcmil kcmil kcmil kcmil #2-4/0AWG #2-4/0AWG #2-4/0AWG #2-4/0AWG #14-1/0AWG #14-1/0AWG kcmil kcmil kcmil kcmil #6-350 kcmil #6-350 kcmil #6-350kcmil #6-350 kcmil #2-4/0AWG #2-4/0AWG (2) #3/0 AWG-250 kcmil (1) kcmil (2) #3/0 AWG-250 kcmil (1) kcmil (1) #4 AWG-300 kcmil (1) #6 AWG-350 kcmil (1) #4 AWG-300 kcmil (1) #2-4/0 AWG (1) #2-4/0 AWG (1) #2-4/0 AWG (1) kcmil (1) kcmil (1) kcmil (1) kcmil (1) #6 AWG-350 kcmil (1) #6 AWG-350 kcmil (1) #4 AWG-300 kcmil (1) #4 AWG-300 kcmil (1) #2-4/0 AWG (1) #2-4/0 AWG JOHNSON CONTROLS 37

MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A

MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A FORM 150.27-EG1 (1115) MODEL YCRL REMOTE CONDENSER SCROLL LIQUID CHILLER STYLE A 50 Through 170 Tons 175 Through 597 Kw 60Hz R-410a FORM 150.27-EG1 (1115) Nomenclature YCRL 0118 S E 46 X A UNIT TYPE YORK

More information

Model YCRL Remote Condenser Scroll Liquid Chiller Style A

Model YCRL Remote Condenser Scroll Liquid Chiller Style A Model YCRL Remote Condenser Scroll Liquid Chiller Style A 50 THROUGH 150 TONS 175kW THROUGH 530 kw 60Hz Products are produced at a facility whose qualitymanagement systems are ISO9001 certified. Table

More information

YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT. COOLING CAPACITIES 141 kw to 360 kw

YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT. COOLING CAPACITIES 141 kw to 360 kw YCAL-SB Millennium AIR COOLED LIQUID CHILLER R407C REFRIGERANT COOLING CAPACITIES 141 kw to 360 kw YORK YCAL-SB Millennium air cooled scroll liquid chillers provide chilled liquid for all air conditioning

More information

MODEL YLUA AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITS STYLE A

MODEL YLUA AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITS STYLE A MODEL YLUA AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITS STYLE A 80 160 TON 281 562 kw 60 Hz R-410A Nomenclature YL U A 0148 Z E 46 X C DESIGN SERIES TYPE START X = ACROSS THE LINE Z = STANDARD EFFICIENCY

More information

Call us today! (800)

Call us today! (800) 500 TON AIR-COOLED CHILLER PA-ACCTR-500 Call us today! (800)341-4297 The 500-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

MODEL QTC3 AIR-COOLED SCROLL CHILLERS

MODEL QTC3 AIR-COOLED SCROLL CHILLERS MODEL QTC3 AIR-COOLED SCROLL CHILLERS 55 200 TON 195 700 kw 60 Hz R-410A LD18971a Nomenclature QTC3120T E 46 X B B DESIGN SERIES X = ACROSS THE LINE VOLTAGE CODE: 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60

More information

Call us today! (800)

Call us today! (800) PA-ACCTR-200 Call us today! (800)341-4297 The 200-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable, efficient and quiet chiller

More information

TON kw

TON kw form QTC3-EG6 (515) Model qtc3 Air-Cooled Scroll Chillers 55 175 TON 195 615 kw 60 Hz R-410A LD18971a FORM qtc3-eg6 (515) Nomenclature QTC3120T E 46 X B B DESIGN SERIES X = ACROSS THE LINE VOLTAGE CODE:

More information

Call us today! (800)

Call us today! (800) 150 TON AIR-COOLED CHILLER PA-ACCTR-150 Call us today! (800)341-4297 The 150-Ton portable chiller package features a Trane RTAC chiller unit. Trane leads the industry in providing some of the most reliable,

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B

MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B 50 150 TON 180 530 kw 50 Hz R-410A Nomenclature Y L A A 0320 S E 50 X A B DEVELOPMENT LEVEL = B (BPHX) DESIGN SERIES A (MCHX)

More information

MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B

MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B FORM 150.72-EG6 (817) MODEL YLAA AIR-COOLED SCROLL CHILLERS WITH BRAZED PLATE HEAT EXCHANGERS STYLE B 55 200 TON 195 700 kw 60 Hz R-410A FORM 150.72-EG6 (817) Nomenclature YL A A 0125 H 46 X C B DESIGN

More information

YCWL0240SE-YCWL0395SE & YCWL / YCRL0200HE-YCWL / YCRL0610HE. Revision 2 Form EG2 (0709)

YCWL0240SE-YCWL0395SE & YCWL / YCRL0200HE-YCWL / YCRL0610HE. Revision 2 Form EG2 (0709) YCWL0240SE-YCWL0395SE & YCWL / YCRL0200HE-YCWL / YCRL0610HE ENGINEERING GUIDE Revision 2 Form 201.26-EG2 (0709) WATER AND REMOTE AIR COOLED CHILLERS WITH SCROLL COMPRESSORS STYLE A (188-580 KW) SE - STANDARD

More information

FORM EG6 (513) Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B TON kw 60 Hz R-410A

FORM EG6 (513) Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B TON kw 60 Hz R-410A Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B 70 175 TON 246 615 kw 60 Hz R-410A Table of Contents Introduction... 3 Nomenclature... 5 Equipment Overview... 6 Unit Components...

More information

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R Products That Perform...By People Who Care FORM NO: MS0455A WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS R134a HXWC SERIES 205 to 560 Tons 60Hz INTRODUCTION Dunham-Bush's HXWC water cooled

More information

MODEL YSAA AIR-COOLED SCREW CHILLERS STYLE A

MODEL YSAA AIR-COOLED SCREW CHILLERS STYLE A MODEL YSAA AIR-COOLED SCREW CHILLERS STYLE A 55 115 TON 190 405 kw 50 Hz R-134A Nomenclature YS A A 0110 H A 50 A A DESIGN SERIES VOLTAGE CODE: 50 = 400-3-50 DEVELOPMENT LEVEL REFRIGERANT = R-134a A =

More information

MODEL QTC3 AIR-COOLED SCROLL CHILLERS

MODEL QTC3 AIR-COOLED SCROLL CHILLERS MODEL QTC3 AIR-COOLED SCROLL CHILLERS 55 230 TON 195 800 kw 60 Hz R-410A LD18971a Nomenclature QTC3120T E 46 X B B DESIGN SERIES X = ACROSS THE LINE VOLTAGE CODE: 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60

More information

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION 100 TON AIR-COOLED SCROLL PACKAGED SPECIFICATIONS Call us today! (800)341-4297 Trane Portable Packaged Air Conditioner units contain the best compressor technology available, in order to achieve the highest

More information

Model YCIV Air-Cooled Screw Liquid Chillers with Variable Speed Drive Style A

Model YCIV Air-Cooled Screw Liquid Chillers with Variable Speed Drive Style A Model YCIV Air-Cooled Screw Liquid Chillers with Variable Speed Drive Style A 150-400 TONS (527-1407 kw) 2, 3, and 4 Compressor 60 Hz Design Series H Nomenclature YC I V 0207 H A XX XX = VOLTAGE CODE A

More information

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes). Guide Specifications PART 1 GENERAL 1.01 SYSTEM DESCRIPTION Microprocessor controlled, air-cooled liquid chiller utilizing scroll compressors, low sound fans, hydronic pump system and optional fluid storage

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

MAC N-407 Air-Cooled Chiller

MAC N-407 Air-Cooled Chiller MAC036-01-N-407 Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial MicroClimates MAC036 NOMENCLATURE BREAKDOWN MAC036-01 - N - 407 Refrigerant Type Air-Cooled Chiller 036=

More information

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days Proposal Trane A Division of American Standard Inc. Prepared For: John Weston Desmet Ballestra Job Name: LAUER1 Biodiesel Chiller Pennsylvania Date: August 21, 2006 Proposal Number: G1-95502-1 Engineer:

More information

MACH N-407 Heat Pump Air-Cooled Chiller

MACH N-407 Heat Pump Air-Cooled Chiller MACH060-01-N-407 Heat Pump Air-Cooled Chiller Heat Pump Air-Cooled Chillers for Global Residential and Light Commercial Microclimates MACH NOMENCLATURE BREAKDOWN MACH-060-01 - N - 407 Refrigerant Type

More information

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES 60 TON AIR-COOLED CHILLER PA-ACCTR-60 Call us today! (800)341-4297 The 60-Ton portable chiller package features a Trane CGAM chiller unit. Trane leads the industry in providing some of the most reliable,

More information

FORM EG2 (405) Air Cooled Screw Liquid Chillers STYLE A FPO 28971AR. R134a kw 50 Hz

FORM EG2 (405) Air Cooled Screw Liquid Chillers STYLE A FPO 28971AR. R134a kw 50 Hz FORM 201.21-EG2 (405) Air Cooled Screw Liquid Chillers STYLE A FPO 28971AR R134a 492-879 kw 50 Hz TABLE OF CONTENTS Introduction...3 Specifications...4 Accessories and Options...7 Temperatures and Flows...10

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-194 REV. 2 Supersedes Form No. A22-194 Rev. 1 Commercial High-Efficiency Condensing Units RAWL High Efficiency 6.5 & 7.5 TON MODEL [22.86 & 26.38 kw] TABLE OF CONTENTS Model Number Designation...2

More information

Model YVFA Air-Cooled Liquid Chillers With VSD Screw Compressor And Integrated Free Cooling Style A

Model YVFA Air-Cooled Liquid Chillers With VSD Screw Compressor And Integrated Free Cooling Style A Model YVFA Air-Cooled Liquid Chillers With VSD Screw Compressor And Integrated Free Cooling Style A 115-380 Tons 400-1340 kw 2 Compressor 50 and 60 Hz HFC-134a Nomenclature YVFA 025 9 B X X 46 A A REFRIGERANT

More information

AVAILABLE MODELS, NOMINAL CAPACITIES TABLE 1 and SOUND PRESSURE LEVELS. Optional acoustic component enclosure and two speed fans

AVAILABLE MODELS, NOMINAL CAPACITIES TABLE 1 and SOUND PRESSURE LEVELS. Optional acoustic component enclosure and two speed fans YAES AIR COOLED SCREW CHILLER R407C REFRIGERANT COOLING CAPACITIES 369 kw to 613 kw The YAES (QPak) range of chillers are designed for water or water-glycol cooling. There are two product families, standard

More information

SECTION CHILLERS

SECTION CHILLERS SECTION 15650 PART I - GENERAL 1.01 WORK INCLUDED A. Extent of work shall be as indicated on Drawings and provisions of this section, including schedules and equipment lists associated with either Drawings

More information

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811 Description These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of Refrigerant R-410A for storage

More information

SECTION AIR COOLED WATER CHILLER

SECTION AIR COOLED WATER CHILLER Note: Shading in the body of the specification is to identify work that will be given to the installing contractor in the subsequent Request for Chiller Installation documents to be issued by the Owner.

More information

MAC-120HE-03 Air-Cooled Chiller

MAC-120HE-03 Air-Cooled Chiller MAC-120HE-03 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 380/415/460-3-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-03

More information

Water-Cooled Dual Compressor Screw Chiller

Water-Cooled Dual Compressor Screw Chiller Installation Manual IM 692-1 Group: Chiller Part Number: 629955 Effective: May 1997 Supersedes: IM663-1 IM683 IM692 Water-Cooled Dual Compressor Screw Chiller Installation Manual PFS 155C through PFS 210C,

More information

.2 Section Waste Management and Disposal.

.2 Section Waste Management and Disposal. Issued 2005/06/01 Section 15624 Packaged Rotary Screw Water Chillers Page 1 of 5 PART 1 General 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Air Cooled Screw Liquid Chillers (STYLE G)

Air Cooled Screw Liquid Chillers (STYLE G) FORM 201.19-EG3 (803) Better ecology, Better economy. Air Cooled Screw Liquid Chillers (STYLE G) 28971AR R-407C Optimized 260 kw 1200 kw 50 Hz Table of Contents Introduction...3 Specifications...4 Accessories

More information

PACKAGED AIR COOLED Product Data Catalog

PACKAGED AIR COOLED Product Data Catalog PACKAGED AIR COOLED Product Data Catalog MODELS ASP-10A ASP-15A ASP-20A ASP-00P ASP-00F ASP-00G A MEMBER OF MARDUK HOLDING COMPANY, LLC The Leader in Modular Chillers ETL and CSA Approved CHILLER MODULES

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number:

Submittal. Date: September 04, Customer P.O. Number: Customer Project Number: Submittal Prepared For: All Bidders Sold To: Date: September 04, 2012 Customer P.O. Number: Customer Project Number: Job Number: Job Name: DCS 12473 80 Ton Chiller Dept of Wildlife 1801 N Lincoln OKLAHOMA

More information

Air-Cooled Global Chiller

Air-Cooled Global Chiller Product Manual PM 970 Group: Chiller Effective: June 1997 Supersedes: None Air-Cooled Global Chiller Type AGR 055AS through 100AS Reciprocating Compressor with R-22 60 hertz 1997 McQuay International Table

More information

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.2 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

VariCool VAV Engineering Guide

VariCool VAV Engineering Guide Engineering Guide Effective September 2017 Water-Cooled and Chilled Water, Variable Air Volume Contents Product Features... 3 UNIT FEATURES... 3 Product Features... 4 Marvel Plus Microprocessor Control

More information

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) SECTION 23 64 01 AIR COOLED WATER CHILLERS (LESS THAN 150 TONS) PART 1: GENERAL 1.1 GENERAL A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish

More information

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Product Data. Features/Benefits. 19XB Positive Pressure Storage System Product Data 19XB Positive Pressure Storage System 19XB028 Copyright 1992 Carrier Corporation 19XB052 Carrier s Positive Pressure Storage (PPS) System ensures the critical conservation of refrigerants

More information

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127. Product Data GEMINI 38AKS028-044 Commercial Air-Cooled Split Systems 50/60 Hz 25 to 40 Nominal Tons (82.8 to 127.0 kw) These dependable split systems match Carrier s indoor-air handlers with outdoor condensing

More information

Commercial High-Efficiency Condensing Units

Commercial High-Efficiency Condensing Units FORM NO. A22-193 REV. 3 Supersedes Form No. A22-193 Rev. 2 Commercial High-Efficiency Condensing Units 15 & 20 TON MODEL [52.8 & 70.3 kw] 10 & 12.5 TON MODEL [35.2 & 44.0 kw] 10 THROUGH 20 NOMINAL TON

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz) DESCRIPTION These units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging. Each unit is pressurized with a holding charge of refrigerant-22 for storage

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1. MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.1 HVAC Guide Specifications Air-Cooled Liquid Chiller with Low Ambient

More information

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT:

TECHNICAL GUIDE GENERAL SPECIFICATIONS COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM OUTDOOR UNIT: INDOOR UNIT: GENERAL SPECIFICATIONS OUTDOOR UNIT: TECHNICAL GUIDE COMMERCIAL SPLIT-SYSTEM COOLING UNITS FOUR PIPE SYSTEM MODELS HB 180 & HB 240 MODELS LB 180 & LB 240 15 & 20 NOMINAL TONS 9.7 EER Two independent refrigerant

More information

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons

Product Data. Features/Benefits. 07DA, DB 07EA, EB, ED Condensing Units. 06D, 06E Compressors. 3 to 40 Nominal Tons Product Data 07DA, DB 07EA, EB, ED Condensing Units 3 to 40 Nominal Tons 06D, 06E Compressors An excellent choice for your built-up system Carrier 07 Series condensing units built for the engineer who

More information

R4H4. Product Specifications

R4H4. Product Specifications ENVIRONMENTALLY SOUND REFRIGERANT R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

RECORD SUBMITTAL COVER SHEET

RECORD SUBMITTAL COVER SHEET RECORD SUBMITTAL COVER SHEET PROJECT TITLE: AXCELLERATE PHARMA EQUIPMENT DESCRIPTION: CARRIER AQUASNAP AIR-COOLED CHILLER CH-1 OWNER: AXCELLERATE PHARMA MECHANICAL ENGINEER: ARDEN DATE: JUNE 27, 2014 SUBMITTED

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual u Air Cooled Screw Chillers SLS 1202 to 4004 With or without total heat recovery 262 to 916 kw Engineering Data Manual EDM SLS407-A.4GB Date : December 2008 Supersedes : TM SLS407-A.3GB/11.06 Specifications

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15684 ROTARY SCREW WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236423 An optional

More information

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE:

JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: REFERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED BY: DATE: T2HA, T3HA, and T4HA with CAHB Systems Limited Range Multi-Zone Heat Pumps Rev. 1.1 [07/07] JOB NAME: LOCATION: PURCHASER: ENGINEER: SUBMITTED TO: FOR: ERENCE [ ] APPROVAL [ ] CONSTRUCTION [ ] SUBMITTED

More information

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz

N4H4. Product Specifications 14 SEER HEAT PUMP. ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz ENVIRONMENTALLY SOUND REFRIGERANT N4H4 Performance Series Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1 phase, 60 Hz REFRIGERATION

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Compact, Self-Contained unit that offer low installation cost plus dependable performance. 0 Compact, Self-Contained unit that offer low installation cost plus dependable performance. From carrier s excellence in engineering come a new, compact of single package horizontal and vertical water

More information

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons

Product Data. 50LJS/TJS Single- Package. Features / Benefits. Rooftop Units - 50 Hz 6 to 12 Nominal Tons 007-014 Single- Package Rooftop Units - 50 Hz 6 to 12 Nominal Tons Product Data Single package rooftop cooling units with electric heat option. Compact, horizontal discharge units (vertical discharge option),

More information

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X

Water-Cooled Modular Chillers. Product Data Catalog. Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Product Data Catalog Standard and Total Access Modules MS010X, MS015X, MS020X, MS030X, MS040X, MS050X, MS070X, MS085X Variable Speed Total Access Modules MS010W, MS020W, MS030W, MS050W MS010V, MS020V,

More information

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01355 Waste Management and Disposal..3

More information

Catalog Water-Cooled Scroll Compressor Chillers

Catalog Water-Cooled Scroll Compressor Chillers Water-Cooled Scroll Compressor Chillers Model WGZ, D Vintage 30 to 200 Tons (100 to 700 kw) HFC-410A Refrigerant 60/50 Hz Packaged and Condenserless Units Catalog 613-3 Table of Contents Table of Contents

More information

30GN FLOTRONIC II AIR-COOLED CHILLERS

30GN FLOTRONIC II AIR-COOLED CHILLERS 30GN-19SB 30GN040-110 FLOTRONIC II AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GN-19SB Supersedes 30GN-6SB, 30GN-7SB, 30GN-8SB, Printed

More information

Liebert CSU3000 Chiller

Liebert CSU3000 Chiller CSI 15620 - Packaged Water Chillers Liebert CSU3000 Chiller Guide Specifications for 7.5-37 Ton CS/CD/CT Models 1.0 GENERAL 1.1 CS/CD MODELS The main-frame coolant supply unit shall be a Liebert Model,

More information

PACKAGE AIR CONDITIONER

PACKAGE AIR CONDITIONER PACKAGE AIR CONDITIONER FORM NO. ATZ-206 TZAA- HIGH EFFICIENCY SERIES NOMINAL SIZE 10 TON [35.2 kw] 10 TON MODEL [35.2 kw] This product is shipped with a nitrogen holding charge that must be vented prior

More information

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM

UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM EFFICIENT UP TO 17.5 SEER / 13.5 EER / 9.5 HSPF HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 2 THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase REFRIGERATION CIRCUIT S 2- stage scroll compressors

More information

FORM EG6 (712) Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B TON kw 60 Hz R-410A

FORM EG6 (712) Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B TON kw 60 Hz R-410A Model YLAA Air-Cooled Scroll Chillers with Brazed Plate Heat Exchangers Style B 70 120 TON 246 527 kw 60 Hz R-410A Table of Contents Form 150.72-Eg6 (612)... 1 Introduction... 3 Nomenclature... 5 Equipment

More information

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

CHS. Product Specifications COMMERCIAL SPLIT SYSTEMS HEAT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE COMMERCIAL SPLIT SYSTEMS HT PUMP UNITS R 410A, 6 10 TONS BUILT TO LAST, SY TO INSTALL AND SERVICE Single stage cooling capacity control on all models All models utilize round copper tube, aluminum plate

More information

R4H4. Product Specifications

R4H4. Product Specifications R4H4 Product Specifications EFFICIENT 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED REFRIGERANT 1-1/2 THRU 5 TONS SPLIT SYSTEM 208 / 230 Volt, 1- phase, 60 Hz REFRIGERATION CIRCUIT S Scroll compressors on

More information

30GXN,R AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz

30GXN,R AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz 30GXN-3SB 30GXN,R080-528 AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz PERFORMANCE DATA S FIELD WIRING DIAGRAMS Copyright 2002 Carrier Corporation Syracuse, New York 13221 Form 30GXN-3SB

More information

Water-to-Water Heat Pump Product Data Catalog R-134a Modules MR010AN, MR015AN, MR020AN, MR030AN, MR040AN, MR050AN, MR070AN, MR085AN

Water-to-Water Heat Pump Product Data Catalog R-134a Modules MR010AN, MR015AN, MR020AN, MR030AN, MR040AN, MR050AN, MR070AN, MR085AN Water-to-Water Heat Pump Product Data Catalog R-134a Modules MR010AN, MR015AN, MR020AN, MR030AN, MR040AN, MR050AN, MR070AN, MR085AN R-410A Modules MR010XN, MR015XN, MR020XN, MR030XN, MR040XN, MR050XN,

More information

N4H4. Product Specifications

N4H4. Product Specifications 14 SEER HEAT PUMP ENVIRONMENTALLY BALANCED R- 410A REFRIGERANT 1½ THRU 5 TONS SPLIT SYSTEM 208/230 Volt 1- phase, 208/230 Volt 3- phase, 460 Volt 3- phase; 60 Hz REFRIGERATION CIRCUIT S Scroll compressors

More information

Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD Ph Fax Addendum # 1

Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD Ph Fax Addendum # 1 Addendum No. 1 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Addendum # 1 Date: 3/11/2016 Bid: Chiller Removal and Installation A Pre-Bid

More information

30GT FLOTRONIC AIR-COOLED CHILLERS

30GT FLOTRONIC AIR-COOLED CHILLERS 30GT-41SB 30GT040-110 FLOTRONIC AIR-COOLED CHILLERS PERFORMANCE DATA FIELD WIRING DIAGRAM 1998 Carrier Corporation Syracuse, New York 13221 Form 30GT-41SB Supersedes 30GT-21SB, 30GT-22SB, 30GT-23SB, Printed

More information

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons 560.20-TG1Y (388) EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons Each circuit includes a fully hermetic compressor with a crankcase

More information

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers GUIDE SPECIFICATIONS WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers WW024-072 Reverse Cycle Chillers / Low Temperature Boilers GENERAL Units shall be Underwriter Laboratories (UL) listed

More information

Packaged Air-Cooled Water Chiller

Packaged Air-Cooled Water Chiller Installation, Operation and Maintenance Manual IOMM ALR-3 Group: Chiller Part Number: 330145710 Effective: September 2001 Supersedes: IM ALR-2 Packaged Air-Cooled Water Chiller ALR 110F - ALR 150F Refrigerant

More information

Model YVAA Air-Cooled Screw Compressor Liquid Chillers With Variable Speed Drive Style A

Model YVAA Air-Cooled Screw Compressor Liquid Chillers With Variable Speed Drive Style A FORM 201.28-EG1 (7) Model YVAA Air-Cooled Screw Compressor Liquid Chillers With Variable Speed Drive Style A 150-500 Tons 525-1750 kw 2 Compressor 50 and 60 Hz HFC-134a or HFC-513A FORM 201.28-EG1 (7)

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

SCROLL LIQUID CHILLERS

SCROLL LIQUID CHILLERS SCROLL LIQUID CHILLERS Application Manual Model NWC and NCC 15 TO 70 Tons (60 Hz) Water Cooled and Compressor 410A Chillers INTRODUCTION The NAPPS 410A Scroll Liquid Chiller Compressor Design Napps NWC

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Catalog Cat WGS Water-Cooled Screw Compressor Chillers WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A,

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED:

THE FOLLOWING CHANGES/ADDITIONS TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED: Business Services Procurement and Contracting 16550 SW Merlo Road Beaverton, OR 97003 (503) 356-4324 February 20, 2018 SOLICITATION ADDENDUM NO. 2 ITB 18-0003 Kinnaman-Hiteon Chiller Replacement THE FOLLOWING

More information

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT

NH4H4. Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT ENVIRONMENTALLY SOUND REFRIGERANT NH4H4 Product Specifications 14 SEER HORIZONTAL DISCHARGE HEAT PUMP FOR USE WITH DUCTED INDOOR UNIT ENVIRONMENTALLY SOUND R 410A REFRIGERANT 1 1/2 THRU 5 TONS, 208/230

More information

Air-Cooled Scroll Condensing Units

Air-Cooled Scroll Condensing Units Installation, Operation and Maintenance Manual IOMM ACZB1-1 Group: Chiller Part Number: 331975101 Effective: October 2008 Supersedes: October 2007 Air-Cooled Scroll Condensing Units ACZ 010B ACZ 039B 10

More information

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons Product Data OMNIZONE 50BRN,BZN006-024 Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems 5 to 20 Nominal Tons The 50BRN,BZN water-cooled and remote air-cooled indoor, self-contained units

More information

MODELS LIST. Nominal Capacity RT

MODELS LIST. Nominal Capacity RT 1. MODELS LIST. NOMENCLATURE 3. FEATURES 4. PRODUCT DATA 5. PERFORMANCE CORRECTION 6. ANTIFREEZE 7. INSTALLATION 8. ELECTRICAL DATA 9. SCHEMATIC WIRING DIAGRAM 10.MICROPROCESSOR CONTROLLER 11.APPLICATION

More information

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower SECTION 15682 CENTRIFUGAL WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC) 3. 15711 - Induced Draft Cooling Tower B. Removal

More information

Water-Cooled Screw Compressor Chillers

Water-Cooled Screw Compressor Chillers Water-Cooled Screw Compressor Chillers Catalog 617-4 WGS 130AW To WGS 190AW, Packaged Water-Cooled Chiller WGS 130AA To WGS 190AA, Chiller with Remote Condenser 120 to 200 Tons, 420 to 700 kw R-134A, 60

More information

GUIDE SPECIFICATIONS AQUARIUS ii

GUIDE SPECIFICATIONS AQUARIUS ii Catalog (AP Technical Data Sheet) GUIDE SPECIFICATIONS AQUARIUS ii AP Series Two Stage R-410A GENERAL Units shall be performance certified to ISO standard 13256-1 for Water Loop Heat Pump, Ground Water

More information

Model YVAA Air-Cooled Screw Compressor Liquid Chillers With Variable Speed Drive Style A

Model YVAA Air-Cooled Screw Compressor Liquid Chillers With Variable Speed Drive Style A Model YVAA Air-Cooled Screw Compressor Liquid Chillers With Variable Speed Drive Style A 150-500 Tons 525-1750 kw 2 Compressor 50 and 60 Hz HFC-134a Nomenclature YVAA 021 3 A X X 46 A A REFRIGERANT HFC

More information

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series Type of Compressors Compressor Rotary Scroll Reciprocating Screw Centrifugal Air Cooled Chiller 77 ~ 329TR (270 ~ 1156 kw) ACDX Series 100 ~ 520TR

More information

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers

Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Catalog 221-1 Air-Cooled Split System Condensing Unit for Rooftop Systems and Air Handlers Model RCS 025C to 135C R-22/R-407C Refrigerant Contents Introduction............................... 3 The Condensing

More information

Air-Cooled Modular Split Systems. Product Data Catalog

Air-Cooled Modular Split Systems. Product Data Catalog sm Air-Cooled Modular Split Systems Product Data Catalog MS010XN_A, MS015XN_A, MS020XN_A, MS030XN_A, MS040XN_A, MS050XN_A, MS070XN_A, MS085XN_A Standard and Total Access Configurations Features & Benefits

More information