1 BID DOCUMENTS FOR LINCOLN HIGH SCHOOL MECHANICAL EQUIPMENT PRE-PURCHASE 2600 SW 9 TH STREET DES MOINES, IOWA BID B7427 CONDENSING BOILERS BID B7428 DOMESTIC WATER HEATERS BID B7429 POOL HEATER Owner Des Moines Independent Community School District 1917 Dean Avenue Des Moines, Iowa 50316

2

3 NOTICE OF LETTING LINCOLN HIGH SCHOOL MECHANICAL EQUIPMENT PRE-PURCHASE NOTICE IS HEREBY GIVEN: Sealed proposals will be received by the Purchasing Agent of the Des Moines Independent Community School District at his office, Des Moines Independent Community School District 1915 Prospect Road, Suite 1200, Des Moines, Iowa until three o'clock p.m. on the 11th day of April, 2016, for the pre-purchase of the following mechanical equipment for a mechanical upgrade project at Lincoln High School. Bid No. B7427 Condensing Boilers Bid No. B7428 Fuel Fired Domestic Water Heaters Bid No. B7429 Pool Heater Commencing March 30, 2016 copies of the bid documents are on file with and available from the Des Moines Public Schools 1917 Dean Avenue Des Moines, Iowa Bids must be submitted on the approved bid form available in the bid packet. No oral, facsimile, telegraphic or telephonic bids or modifications will be considered. Lump-sum bids will be received as indicated in the scope of work. Bids will be opened and read aloud immediately after specified closing time for receiving bids. All interested parties are invited to attend. Consideration of the bids received and the award of bids or other action may be made by the Board of Directors of the Des Moines Independent Community School District upon the proposals received in accordance with the law and the bid documents at its meeting to be held at 6:00 p.m. on April 19, 2016 in the District Board Room at 1800 Grand Avenue Des Moines Iowa or at any other published and/or posted location of the Board meeting. The Board of Directors may make the award to the lowest responsive, responsible bidder meeting specifications. The right is reserved to reject any or all bids, or any part thereof, and to waive informalities, and to enter into such purchase orders as shall be deemed in the best interests of the Des Moines Independent Community School District. By virtue of statutory authority, a preference will be given to products and provisions grown and coal produced within the State of Iowa, and to Iowa domestic labor. All bids will be governed by applicable provisions in the Iowa Code and Board Policies. Secretary of the Board Des Moines Independent Community School District

4

5 DES MOINES PUBLIC SCHOOLS LINCOLN HIGH SCHOOL MECHANICAL EQUIPMENT PRE-PURCHASE Scope of Work - March 30, 2016 Bid # B7427 Condensing Boilers Bid # B7428 Fuel Fired Domestic Water Heaters Bid # B7429 Pool Heater The Des Moines School District is seeking bids for pre-purchase of certain mechanical equipment for an upcoming mechanical upgrade at Lincoln High School. DOCUMENTS PROVIDED: 1. Notice of Letting 1 page 2. Scope of Work 2 pages 3. Bid Form 2 pages 4. Non Collusion Affidavit 1 page (complete, notarize and submit with bid) 5. Bidders Status Form 2 pages (complete and submit with bid) 6. TSB Form 2 pages (complete, notarize and submit with bid) 7. Specifications Section Pool Heater Section Fuel Fired Domestic Water Heaters Section Condensing Boilers 8. Three Equipment Schedules Pool heater, Fuel Fired Domestic Water Heaters and Condensing Boilers 9. DMPS standard terms and conditions found on its website at: dmschools.org/departments/operations/purchasing & central stores / open proposals click here near the top of the page. REQUIREMENTS: 1. Submit a signed quotation on the attached bid form. Bids are due at the time and location listed in the Notice of Letting. Include the completed TSB form, the Non Collusion Form and the Bidders Status Form with the bid. 2. Questions shall be directed in writing to douglas.ohde@dmschools.org 3. The successful firm will be notified on April 20, The District will make award to bidders for each of the different bids separately or the District at its discretion can award more than one bid to a supplier based upon low combination pricing provided. 5. A purchase order for each award will be provided from the Des Moines Public Schools. Exclude all State of Iowa sales taxes and use taxes from your proposal. The District will provide a tax exempt certificate with the purchase order. 6. No bid bonds, performance bonds, or payment bonds are required. 7. All bids shall include freight charges for delivery free on board trucks at Lincoln High School 2600 SW 9 th Street, Des Moines Iowa for unloading by the district s contractor. 8. The District will pay for stored equipment in a bonded warehouse in Des Moines upon evidence that the full value is covered by insurance. If the equipment is temporarily stored, the quote shall include the costs to deliver the equipment on trucks to Lincoln High School.

6 Page 2 Lincoln High School Mechanical Equipment Pre-purchase 9. The start of an overall one year warranty period for all equipment shall be the date of substantial completion of the mechanical contract in mid fall of Extended warranties shall be as indicated in each specification section and the warranty period shall also start at the date of substantial completion. 10. The mechanical equipment shall be available for delivery to the school on June 15, Delivery date shall be confirmed on the bid form where indicated. 11. The price shall include all submittals for approval by the mechanical engineers KPE Engineering 12. Awarded bidder shall coordinate with the selected mechanical contractor by providing submittals, delivery coordination, and field requirements. 13. The price shall include all field quality control and demonstration items required of the manufacturer as called out in the specifications to include in part startup and owner training. END OF DOCUMENT

7 BID FORM BIDS DUE NOT LATER THAN 3:00 PM ON APRIL 11, 2016 PROPOSAL FOR: Lincoln High School Mechanical Equipment Pre-Purchase Bid B7427 Condensing Boilers Bid B7428 Fuel Fired Domestic Water Heaters Bid B7429 Pool Heater TO: Des Moines Independent Community School District 1915 Prospect Road Suite 1200 Des Moines, IA SUBMITTED BY: Name of Bidder Des Moines Independent Community School District: The undersigned has examined the bid documents and hereby proposes and agrees to furnish and provide all products, materials, transportation, and services as required for the expeditious furnishing of the equipment required in conformity with this bid request. The undersigned agrees that bids, if accepted by the Owner, will be the basis for a purchase order(s) with the Owner. The Contractor shall comply with the terms and conditions of the District purchasing department. The undersigned further acknowledges the following Addenda: NO. NO. NO. DATE DATE DATE BID FOR CONDENSING BOILERS BID NO. B7427 The undersigned proposes to provide the equipment FOB jobsite as specified for the lump sum price as follows: PRICE EXCLUDING ALL TAXES - $ This bid is based upon utilizing the following equipment manufacturer Confirm delivery date of June 15, Yes No - if no delivery date would be

8 BID FORM BID FOR FUEL FIRED DOMESTIC WATER HEATERS BID NO. B7428 The undersigned proposes to provide the equipment FOB jobsite as specified for the lump sum price as follows: PRICE EXCLUDING ALL TAXES - $ This bid is based upon utilizing the following equipment manufacturer Confirm delivery date of June 15, Yes No - if no delivery date would be BID FOR POOL HEATER BID NO. B7429 The undersigned proposes to provide the equipment FOB jobsite as specified for the lump sum price as follows: PRICE EXCLUDING ALL TAXES - $ This bid is based upon utilizing the following equipment manufacturer Confirm delivery date of June 15, Yes No - if no delivery date would be OPTION FOR A COMBINED BID (may combine 2 or 3 bids state bid numbers included in spots below) The undersigned proposes to provide the equipment FOB jobsite under bids B, B and B for a combined lump sum price as follows: PRICE EXCLUDING ALL TAXES - $ This bid is based upon utilizing the following equipment manufacturers as listed above for each quote. Delivery dates are as listed above for each quote. SUBMITTED BY: Name of Bidder Address: Phone # Fax # address (Authorized Signature)

9 DES MOINES INDEPENDENT NON-COLLUSION AFFIDAVIT COMMUNITY SCHOOL DISTRICT LINCOLN HIGH SCHOOL MECHANICAL EQUIPMENT PRE-PURCHASE NON-COLLUSION AFFIDAVIT The Bidder shall provide this affidavit: NON-COLLUSION AFFIDAVIT TO BE EXECUTED BY BIDDER AND SUBMITTED WITH BID State of Iowa ) ) ss. County of Polk ) (Name) being first duly sworn, deposes and says that he or she is of, (Title) (Bidder) the party making the foregoing bid that the bid is not made in the interest of, or on the behalf of, any undisclosed person, partnership, company, association, organization, or corporation; that the bid is genuine and not collusive or sham; that the bidder has not directly or indirectly induced or solicited any other bidder to put in a false or sham bid, and has not directly or indirectly colluded, conspired, connived, or agreed with any bidder or anyone else to put in a sham bid, or that anyone shall refrain from bidding; that the bidder has not in any manner, directly or indirectly, sought by agreement, communication, or conference with anyone to fix the bid price of the bidder or any other bidder, or to fix any overhead, profit, or cost element of the bid price, or of that of any other bidder, or to secure any advantage against the public body awarding the contract of anyone interested in the proposed contract; that all statements contained in the bid are true; and, further, that the bidder has not, directly or indirectly, submitted his or her bid price or any breakdown thereof, or the contents thereof, or divulged information or data relative thereto, or paid, and will not pay, any fee to any corporation, partnership, company association, organization, bid depository, or to any member or agent thereto to effectuate a collusive or sham bid." The undersigned certifies under penalty of perjury that the foregoing is true and correct; THIS STATEMENT MUST BE NOTARIZED. NAME OF BIDDER: BY: Signature Title Type/Print Name Date STATE OF, COUNTY, ss: Subscribed and sworn to before me by the said day of, on this Notary Public in and for the State of

10

11 DES MOINES INDEPENDENT TSB FORM COMMUNITY SCHOOL DISTRICT Page 1 LINCOLN HIGH SCHOOL MECHANICAL EQUIPMENT PRE-PURCHASE Bidder is / is not a certified Iowa Targeted Small Business, (TSB). Bidder's Company Name Telephone No. Address City State Zip Signature (Same person who signs proposal) Title Type/Print Name Date THIS STATEMENT MUST BE NOTARIZED. STATE OF, COUNTY, ss: day of Subscribed and sworn to before me by the said, 201_. on this Notary Public in and for the State of

12

13 Bidder Status Form To be completed by all bidders Please answer Yes or No for each of the following: Yes Yes Yes Yes Yes No No No No No Des Moines Independent Community School District NON-COLLUSION AFFIDAVIT Document My company s office in Iowa is suitable for more than receiving mail, telephone calls, and . My company has been conducting business in Iowa for at least 3 years prior to the first request for bids on this project. My company is not a subsidiary of another business entity or my company is a subsidiary of another business entity that would qualify as a resident bidder in Iowa. Part A My company is authorized to transact business in Iowa. (To help you determine if your company is authorized, please review the worksheet on the next page). My company has an office to transact business in Iowa. If you answered Yes for each question above, your company qualifies as a resident bidder. Please complete Parts B and D of this form. If you answered No to one or more questions above, your company is a nonresident bidder. Please complete Parts C and D of this form. To be completed by resident bidders My company has maintained offices in Iowa during the past 3 years at the following addresses: Part B Dates: Dates: / / to / / Address: City, State, Zip: / / to / / Address: City, State, Zip: Dates: / / to / / Address: You may attach additional sheet(s) if needed. To be completed by non-resident bidders City, State, Zip: Part C 1. Name of home state or foreign country reported to the Iowa Secretary of State: 2. Does your company s home state or foreign country offer preferences to bidders who are residents? Yes No 3. If you answered Yes to question 2, identify each preference offered by your company s home state or foreign country and the appropriate legal citation. You may attach additional sheet(s) if needed. To be completed by all bidders Part D I certify that the statements made on this document are true and complete to the best of my knowledge and I know that my failure to provide accurate and truthful information may be a reason to reject my bid. Firm Name: Signature: Date: You must submit the completed form to the governmental body requesting bids per 875 Iowa Administrative Code Chapter 156. This form has been approved by the Iowa Labor Commissioner

14 Des Moines Independent Community School District NON-COLLUSION AFFIDAVIT Document Worksheet: Authorization to Transact Business This worksheet may be used to help complete Part A of the Resident Bidder Status form. If at least one of the following describes your business, you are authorized to transact business in Iowa. Yes No My business is currently registered as a contractor with the Iowa Division of Labor. Yes No My business is a sole proprietorship and I am an Iowa resident for Iowa income tax purposes. Yes Yes Yes Yes Yes Yes Yes Yes Yes No No No No No No No No No My business is a general partnership or joint venture. More than 50 percent of the general partners or joint venture parties are residents of Iowa for Iowa income tax purposes. My business is an active corporation with the Iowa Secretary of State and has paid all fees required by the Secretary of State, has filed its most recent biennial report, and has not filed articles of dissolution. My business is a corporation whose articles of incorporation are filed in a state other than Iowa, the corporation has received a certificate of authority from the Iowa secretary of state, has filed its most recent biennial report with the secretary of state, and has neither received a certificate of withdrawal from the secretary of state nor had its authority revoked. My business is a limited liability partnership which has filed a statement of qualification in this state and the statement has not been canceled. My business is a limited liability partnership which has filed a statement of qualification in a state other than Iowa, has filed a statement of foreign qualification in Iowa and a statement of cancellation has not been filed. My business is a limited partnership or limited liability limited partnership which has filed a certificate of limited partnership in this state, and has not filed a statement of termination. My business is a limited partnership or a limited liability limited partnership whose certificate of limited partnership is filed in a state other than Iowa, the limited partnership or limited liability limited partnership has received notification from the Iowa secretary of state that the application for certificate of authority has been approved and no notice of cancellation has been filed by the limited partnership or the limited liability limited partnership. My business is a limited liability company whose certificate of organization is filed in Iowa and has not filed a statement of termination. My business is a limited liability company whose certificate of organization is filed in a state other than Iowa, has received a certificate of authority to transact business in Iowa and the certificate has not been revoked or canceled

15 POOL HEATER LINCOLN HIGH SCHOOL PRE-PURCHASE SECTION POOL HEATER PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Gas-fired, pool heater 1.3 ACTION SUBMITTALS A. Product Data: For each type and size of pool heater indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. B. Shop Drawings: 1. Wiring Diagrams: For power, signal, and control wiring. 1.4 INFORMATIONAL SUBMITTALS A. Product Certificates: For each type of gas-fired, pool heater B. Pool-Water Heater Labeling: Certified and labeled by testing agency acceptable to authorities having jurisdiction. C. Source quality-control reports. D. Field quality-control reports. E. Warranty: Sample of special warranty. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For fuel-fired, pool heaters to include in emergency, operation, and maintenance manuals.

16 POOL HEATER LINCOLN HIGH SCHOOL PRE-PURCHASE QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. ASME Compliance: 1. Where ASME-code construction is indicated, fabricate and label commercial, pool heaters to comply with ASME Boiler and Pressure Vessel Code. C. ANSI Z21.56/CSA COORDINATION A. Coordinate sizes and locations of concrete bases with actual equipment provided. 1.8 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of fuel-fired, pool heaters that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Structural failures including storage tank and supports. b. Faulty operation of controls. c. Deterioration of metals, metal finishes, and other materials beyond normal use. 2. Warranty Periods: From date of Substantial Completion. a. Gas-Fired, Pool Heaters: 1) Heat Exchanger: Ten years. 2) Controls and Other Components: Two years. 3) Thermal Shock: Twenty years PART 2 - PRODUCTS 2.1 GAS-FIRED, POOL HEATER A. Manufacturers: Subject to compliance with requirements, provide products by the following: 1. Laars 2. Raypak 3. Lochinvar. B. General: 1. Fuel Type: Natural Gas.

17 POOL HEATER LINCOLN HIGH SCHOOL PRE-PURCHASE Pressure Rating: 150 psig. 3. Heat Exchanger: Cupro-Nickel. 4. Jacket: Metal, with enameled finish, or plastic. 5. Burner: For use with pool heater. 6. Venting: Direct Vent appliance with sealed combustion, intake and exhaust piping. 7. Automatic Ignition: Manufacturer's proprietary system for automatic, gas ignition. 8. Temperature Control: Adjustable thermostat. 9. Mixing valve: Integral valve with controls to maintain minimum water temperature entering heat exchanger. C. Controls: water heater system shall have an onboard control interface to include following: 1. Operation of low water temperature of 105 degrees F. 2. Building management integration 3. Low water flow safety. 4. High limit control 5. Inlet outlet temperature readout. 6. Error code display 7. Automatic gas valve control. D. Pool Heater pump: 1. Integral pump allowing for circulation of pool water through heater. 2. Pump shall be part of the pool heater and wired for control. 2.2 SOURCE QUALITY CONTROL A. Factory Tests: Test and inspect assembled pool heaters specified to be ASME-code construction, according to ASME Boiler and Pressure Vessel Code. B. Hydrostatically test commercial pool heaters to minimum of one and one-half times pressure rating before shipment. C. Prepare test and inspection reports. PART 3 - EXECUTION 3.1 POOL HEATER INSTALLATION A. Commercial, Pool Heater Mounting: Install commercial pool heaters on concrete base. 1. Exception: Omit concrete bases for commercial pool heaters if installation on stand, bracket, suspended platform, or directly on floor is indicated. 2. Maintain manufacturer's recommended clearances. 3. Arrange units so controls and devices that require servicing are accessible. 4. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base. 5. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor.

18 POOL HEATER LINCOLN HIGH SCHOOL PRE-PURCHASE Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 7. Install anchor bolts to elevations required for proper attachment to supported equipment. 8. Anchor pool heaters to substrate. B. Install pool heaters level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible. C. Install gas-fired, pool heaters according to NFPA Install gas shutoff valves on gas supply piping to gas-fired, pool heaters without shutoff valves. 2. Install gas pressure regulators on gas supplies to gas-fired, pool heaters without gas pressure regulators if gas pressure regulators are required to reduce gas pressure at burner. 3. Install automatic gas valves on gas supplies to gas-fired, pool heaters if required for operation of safety control. 4. Comply with requirements for gas shutoff valves, gas pressure regulators, and automatic gas valves specified in Section "Facility Natural-Gas Piping." D. Install combination temperature-and-pressure relief valves in water piping for pool heaters without storage. Extend commercial-water-heater relief-valve outlet, with drain piping same as domestic-water piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain. E. Install pool heater drain piping as indirect waste to spill by positive air gap into open drains or over floor drains. Install hose-end drain valves at low points in water piping for pool heaters that do not have tank drains. F. Install thermometer on outlet piping of pool heaters. G. Fill pool heaters with water. 3.2 CONNECTIONS A. Comply with requirements for gas piping specified in Section "Facility Natural-Gas Piping." B. Drawings indicate general arrangement of piping, fittings, and specialties. C. Where installing piping adjacent to fuel-fired, pool heaters, allow space for service and maintenance of pool heaters. Arrange piping for easy removal of pool heaters. 3.3 FIELD QUALITY CONTROL A. Perform tests and inspections. 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. 2. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist.

19 POOL HEATER LINCOLN HIGH SCHOOL PRE-PURCHASE Operational Test: After electrical circuitry has been energized, start units to confirm proper operation. 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. B. Prepare test and inspection reports. 3.4 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain gas-fired, pool heaters. END OF SECTION

20 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE SECTION FUEL-FIRED, DOMESTIC-WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section Includes: 1. Gas-fired, tankless, domestic-water heaters. 2. Domestic-water heater accessories. 1.3 ACTION SUBMITTALS A. Product Data: For each type and size of domestic-water heater indicated. Include rated capacities, operating characteristics, electrical characteristics, and furnished specialties and accessories. B. Shop Drawings: 1. Wiring Diagrams: For power, signal, and control wiring. 1.4 INFORMATIONAL SUBMITTALS A. Product Certificates: For each type of gas-fired, tankless, domestic-water heater, from manufacturer. B. Domestic-Water Heater Labeling: Certified and labeled by testing agency acceptable to authorities having jurisdiction. C. Source quality-control reports. D. Field quality-control reports. E. Warranty: Sample of special warranty. 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For fuel-fired, domestic-water heaters to include in emergency, operation, and maintenance manuals.

21 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE QUALITY ASSURANCE A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. ASHRAE/IESNA Compliance: Fabricate and label fuel-fired, domestic-water heaters to comply with ASHRAE/IESNA C. ASME Compliance: 1. Where ASME-code construction is indicated, fabricate and label commercial, domestic-water heater storage tanks to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division Where ASME-code construction is indicated, fabricate and label commercial, finned-tube, domestic-water heaters to comply with ASME Boiler and Pressure Vessel Code: Section IV. D. NSF Compliance: Fabricate and label equipment components that will be in contact with potable water to comply with NSF 61 Annex G, "Drinking Water System Components - Health Effects." 1.7 COORDINATION A. Coordinate sizes and locations of concrete bases with actual equipment provided. 1.8 WARRANTY A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of fuel-fired, domestic-water heaters that fail in materials or workmanship within specified warranty period. 1. Failures include, but are not limited to, the following: a. Structural failures including storage tank and supports. b. Faulty operation of controls. c. Deterioration of metals, metal finishes, and other materials beyond normal use. 2. Warranty Periods: From date of Substantial Completion. a. Gas-Fired, Tankless, Domestic-Water Heaters: 1) Heat Exchanger: Ten years. 2) Controls and Other Components: Two years. PART 2 - PRODUCTS 2.1 GAS-FIRED, TANKLESS, DOMESTIC-WATER HEATERS A. Manufacturers: Subject to compliance with requirements, provide products by the following:

22 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE Intellihot 2. Aerco 3. Lochinvar. B. Standard: ANSI Z /CSA 4.3 for gas-fired, instantaneous, domestic-water heaters for indoor application. C. Construction: Copper piping or tubing complying with NSF 61 Annex G barrier materials for potable water, without or minimal storage capacity. 1. Tappings: ASME B pipe thread. 2. Pressure Rating: 150 psig. 3. Heat Exchanger: Stainless Steel 316L. 4. Insulation: Comply with ASHRAE/IESNA Jacket: Metal, with enameled finish, or plastic. 6. Burner: For use with tankless, domestic-water heaters and natural-gas fuel. 7. Automatic Ignition: Manufacturer's proprietary system for automatic, gas ignition. 8. Temperature Control: Adjustable thermostat. D. Support: Bracket for wall mounting. E. Controls: water heater system shall have an onboard control interface to include following: 1. Cascade sequencing 2. Building management integration 3. Low water flow safety 4. Inlet outlet temperature readout. 5. Error code display 6. Automatic gas valve control. 2.2 DOMESTIC-WATER HEATER ACCESSORIES A. Domestic-Water Compression Tanks: 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: a. AMTROL, Inc. b. Pentair Pump Group. c. Smith, A. O. Corporation. d. Taco, Inc. 2. Description: Steel, pressure-rated tank constructed with welded joints and factory-installed butylrubber diaphragm. Include air precharge to minimum system-operating pressure at tank. 3. Construction: a. Tappings: Factory-fabricated steel, welded to tank before testing and labeling. Include ASME B pipe thread. b. Interior Finish: Comply with NSF 61 Annex G barrier materials for potable-water tank linings, including extending finish into and through tank fittings and outlets.

23 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE c. Air-Charging Valve: Factory installed. B. Drain Pans: Corrosion-resistant metal with raised edge. Comply with ANSI/CSA LC 3. Include dimensions not less than base of domestic-water heater, and include drain outlet not less than NPS 3/4 with ASME B pipe threads or with ASME B garden-hose threads. C. Piping-Type Heat Traps: Field-fabricated piping arrangement according to ASHRAE/IESNA D. Heat-Trap Fittings: ASHRAE E. Manifold Kits: Domestic-water heater manufacturer's factory-fabricated inlet and outlet piping for field installation, for multiple domestic-water heater installation. Include ball-, butterfly-, or gate-type shutoff valves to isolate each domestic-water heater and calibrated balancing valves to provide balanced flow through each domestic-water heater. F. Gas Shutoff Valves: ANSI Z21.15/CSA 9.1-M, manually operated. Furnish for installation in piping. G. Gas Pressure Regulators: ANSI Z21.18/CSA 6.3, appliance type. Include 2-psig pressure rating as required to match gas supply. H. Automatic Gas Valves: ANSI Z21.21/CSA 6.5, appliance, electrically operated, on-off automatic valve. I. Combination Temperature-and-Pressure Relief Valves: Include relieving capacity at least as great as heat input, and include pressure setting less than domestic-water heater working-pressure rating. Select relief valves with sensing element that extends into storage tank. 1. Gas-Fired, Domestic-Water Heaters: ANSI Z21.22/CSA 4.4-M. J. Pressure Relief Valves: Include pressure setting less than domestic-water heater working-pressure rating. 1. Gas-Fired, Domestic-Water Heaters: ANSI Z21.22/CSA 4.4-M. K. Vacuum Relief Valves: ANSI Z21.22/CSA 4.4-M. L. Domestic-Water Heater Stands: Manufacturer's factory-fabricated steel stand for floor mounting, capable of supporting domestic-water heater and water. Provide dimension that will support bottom of domesticwater heater a minimum of 18 inches above the floor. M. Domestic-Water Heater Mounting Brackets: Manufacturer's factory-fabricated steel bracket for wall mounting, capable of supporting domestic-water heater and water. 2.3 SOURCE QUALITY CONTROL A. Factory Tests: Test and inspect assembled domestic-water heaters specified to be ASME-code construction, according to ASME Boiler and Pressure Vessel Code. B. Hydrostatically test commercial domestic-water heaters to minimum of one and one-half times pressure rating before shipment. C. Prepare test and inspection reports.

24 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE PART 3 - EXECUTION 3.1 DOMESTIC-WATER HEATER INSTALLATION A. Commercial, Domestic-Water Heater Mounting: Install commercial domestic-water heaters on concrete base. 1. Exception: Omit concrete bases for commercial domestic-water heaters if installation on stand, bracket, suspended platform, or directly on floor is indicated. 2. Maintain manufacturer's recommended clearances. 3. Arrange units so controls and devices that require servicing are accessible. 4. Install dowel rods to connect concrete base to concrete floor. Unless otherwise indicated, install dowel rods on 18-inch centers around the full perimeter of concrete base. 5. For supported equipment, install epoxy-coated anchor bolts that extend through concrete base and anchor into structural concrete floor. 6. Place and secure anchorage devices. Use setting drawings, templates, diagrams, instructions, and directions furnished with items to be embedded. 7. Install anchor bolts to elevations required for proper attachment to supported equipment. 8. Anchor domestic-water heaters to substrate. B. Install domestic-water heaters level and plumb, according to layout drawings, original design, and referenced standards. Maintain manufacturer's recommended clearances. Arrange units so controls and devices needing service are accessible. 1. Install shutoff valves on domestic-water-supply piping to domestic-water heaters and on domestichot-water outlet piping. Comply with requirements for shutoff valves specified in Section "Ball Valves for Plumbing Piping," Section "Butterfly Valves for Plumbing Piping," and Section "Gate Valves for Plumbing Piping." C. Install gas-fired, domestic-water heaters according to NFPA Install gas shutoff valves on gas supply piping to gas-fired, domestic-water heaters without shutoff valves. 2. Install gas pressure regulators on gas supplies to gas-fired, domestic-water heaters without gas pressure regulators if gas pressure regulators are required to reduce gas pressure at burner. 3. Install automatic gas valves on gas supplies to gas-fired, domestic-water heaters if required for operation of safety control. 4. Comply with requirements for gas shutoff valves, gas pressure regulators, and automatic gas valves specified in Section "Facility Natural-Gas Piping." D. Install combination temperature-and-pressure relief valves in water piping for domestic-water heaters without storage. Extend commercial-water-heater relief-valve outlet, with drain piping same as domesticwater piping in continuous downward pitch, and discharge by positive air gap onto closest floor drain. E. Install water-heater drain piping as indirect waste to spill by positive air gap into open drains or over floor drains. Install hose-end drain valves at low points in water piping for domestic-water heaters that do not have tank drains. Comply with requirements for hose-end drain valves specified in Section "Domestic Water Piping Specialties."

25 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE F. Install thermometer on outlet piping of domestic-water heaters. Comply with requirements for thermometers specified in Section "Meters and Gages for Plumbing Piping." G. Assemble and install inlet and outlet piping manifold kits for multiple domestic-water heaters. Fabricate, modify, or arrange manifolds for balanced water flow through each domestic-water heater. Include shutoff valve and thermometer in each domestic-water heater inlet and outlet, and throttling valve in each domestic-water heater outlet. H. Install piping-type heat traps on inlet and outlet piping of domestic-water heater storage tanks without integral or fitting-type heat traps. I. Fill domestic-water heaters with water. J. Charge domestic-water compression tanks with air. 3.2 CONNECTIONS A. Comply with requirements for domestic-water piping specified in Section "Domestic Water Piping." B. Comply with requirements for gas piping specified in Section "Facility Natural-Gas Piping." C. Drawings indicate general arrangement of piping, fittings, and specialties. D. Where installing piping adjacent to fuel-fired, domestic-water heaters, allow space for service and maintenance of water heaters. Arrange piping for easy removal of domestic-water heaters. 3.3 FIELD QUALITY CONTROL A. Perform tests and inspections. 1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing. 2. Leak Test: After installation, charge system and test for leaks. Repair leaks and retest until no leaks exist. 3. Operational Test: After electrical circuitry has been energized, start units to confirm proper operation. 4. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. B. Domestic-water heaters will be considered defective if they do not pass tests and inspections. Comply with requirements in Section "Quality Requirements" for retesting and reinspecting requirements and Section "Execution" for requirements for correcting the Work. C. Prepare test and inspection reports.

26 FUEL-FIRED, DOMESTIC-WATER HEATERS LINCOLN HIGH SCHOOL PRE-PURCHASE DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain gas-fired, tankless domestic-water heaters. END OF SECTION

27 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE SECTION CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.2 SUMMARY A. Section includes gas-fired, fire-tube, or water-tube condensing boilers, trim, and accessories for generating hot water. 1.3 ACTION SUBMITTALS A. Product Data: For each type of product. 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for boilers. 2. Include rated capacities, operating characteristics, and furnished specialties and accessories. B. Shop Drawings: For boilers, boiler trim, and accessories. 1. Include plans, elevations, sections, and mounting details. 2. Include details of equipment assemblies. Indicate dimensions, weights, loads, required clearances, method of field assembly, components, and location and size of each field connection. 3. Include diagrams for power, signal, and control wiring. C. Delegated-Design Submittal: For each boiler. 1. Design calculations and vibration isolation base details, signed and sealed by a qualified professional engineer. a. Design Calculations: Calculate requirements for selecting vibration isolators and seismic restraints and for designing vibration isolation bases. b. Vibration Isolation Base Details: Detail fabrication, including anchorages and attachments to structure and to supported equipment. Include adjustable motor bases, rails, and frames for equipment mounting. 1.4 INFORMATIONAL SUBMITTALS A. Source quality-control reports. B. Field quality-control reports.

28 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE C. Sample Warranty: For special warranty. D. Other Informational Submittals: 1. ASME Stamp Certification and Report: Submit "A," "S," or "PP" stamp certificate of authorization, as required by authorities having jurisdiction, and document hydrostatic testing of piping external to boiler. 2. CSA B51 pressure vessel Canadian Registration Number (CRN). 1.5 CLOSEOUT SUBMITTALS A. Operation and Maintenance Data: For boilers to include in emergency, operation, and maintenance manuals. 1.6 WARRANTY A. Manufacturer's Warranty: Manufacturer agrees to repair or replace components of boilers that fail in materials or workmanship within specified warranty period. 1. Warranty Period for Fire-Tube Condensing Boilers: a. Leakage and Materials: 10 years from date of Substantial Completion. b. Heat Exchanger Damaged by Thermal Stress and Corrosion: Nonprorated for five years from date of Substantial Completion. 2. Warranty Period for Water-Tube Condensing Boilers: 20 years from date of Substantial Completion. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. ASME Compliance: Fabricate and label boilers to comply with 2010 ASME Boiler and Pressure Vessel Code. C. ASHRAE/IES 90.1 Compliance: Boilers shall have minimum efficiency according to "Gas and Oil Fired Boilers - Minimum Efficiency Requirements." D. DOE Compliance: Minimum efficiency shall comply with 10 CFR 430, Subpart B, Appendix N. E. UL Compliance: Test boilers for compliance with UL 795. Boilers shall be listed and labeled by a testing agency acceptable to authorities having jurisdiction. F. CSA Compliance: Test boilers for compliance with CSA B51.

29 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE G. Mounting Base: For securing boiler to concrete base. 1. Seismic Fabrication Requirements: Fabricate mounting base and attachment to boiler pressure vessel, accessories, and components with reinforcement strong enough to withstand seismic forces defined in Section "Vibration and Seismic Controls for HVAC" when mounting base is anchored to building structure. H. Manufacturers: Subject to compliance with requirements, provide products by one of the following: 1. Fulton 2. RBI 3. Lochinvar 4. Laars 5. Thermal Solutions 6. AWP - Mestek 2.2 FORCED-DRAFT, FIRE-TUBE CONDENSING BOILERS A. Description: Factory-fabricated, -assembled, and -tested, fire-tube condensing boiler with heat exchanger sealed pressure tight, built on a steel base, including insulated jacket; flue-gas vent; combustion-air intake connections; water supply, return, and condensate drain connections; and controls. Water-heating service only. B. Heat Exchanger: Nonferrous, corrosion-resistant combustion chamber. C. Pressure Vessel: Carbon steel with welded heads and tube connections. D. Burner: Natural gas, forced draft. E. Blower: Centrifugal fan to operate during each burner firing sequence and to prepurge and postpurge the combustion chamber. 1. Motors: Comply with NEMA designation, temperature rating, service factor, and efficiency requirements for motors specified in Section "Common Motor Requirements for HVAC Equipment." a. Motor Sizes: Minimum size as indicated; if not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0. F. Gas Train: Combination gas valve with manual shutoff and pressure regulator. G. Ignition: Spark ignition with 100 percent main-valve shutoff with electronic flame supervision. H. Casing: 1. Jacket: Sheet metal, with snap-in or interlocking closures. 2. Control Compartment Enclosures: NEMA 250, Type 1A. 3. Finish: Baked-enamel or Powder-coated protective finish. 4. Insulation: Minimum 2-inch-thick, mineral-fiber or polyurethane-foam insulation surrounding the heat exchanger. 5. Combustion-Air Connections: Inlet and vent duct collars.

30 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE WATER-TUBE CONDENSING BOILERS A. Description: Factory-fabricated, -assembled, and -tested, copper-finned, water-tube condensing boiler with heat exchanger sealed pressure tight, built on a steel base, including insulated jacket; flue-gas vent; combustion-air intake connections; water supply, return, and condensate drain connections; and controls. Water-heating service only. B. Heat Exchanger: Finned-copper primary and stainless-steel secondary heat exchangers. C. Combustion Chamber: Stainless steel, sealed. D. Burner: Natural gas, forced draft drawing from gas premixing valve. E. Blower: Centrifugal fan to operate during each burner firing sequence and to prepurge and postpurge the combustion chamber. 1. Motors: Comply with NEMA designation, temperature rating, service factor, and efficiency requirements for motors specified in Section "Common Motor Requirements for HVAC Equipment." a. Motor Sizes: Minimum size as indicated; if not indicated, large enough so driven load will not require motor to operate in service factor range above 1.0. F. Gas Train: Combination gas valve with manual shutoff and pressure regulator. G. Ignition: Silicone carbide hot-surface ignition that includes flame safety supervision and 100 percent mainvalve shutoff. H. Integral Circulator: Cast-iron body and stainless-steel impeller sized for minimum flow required in heat exchanger. I. Casing: 1. Jacket: Sheet metal, with snap-in or interlocking closures. 2. Control Compartment Enclosures: NEMA 250, Type 1A. 3. Finish: Textured epoxy. 4. Insulation: Minimum 2-inch- thick, mineral-fiber insulation surrounding the heat exchanger. 5. Combustion-Air Connections: Inlet and vent duct collars. 2.4 TRIM A. Include devices sized to comply with ASME B31.1. B. Aquastat Controllers: Operating, firing rate, and high limit. C. Safety Relief Valve: ASME rated. D. Pressure and Temperature Gage: Minimum 3-1/2-inch-diameter, combination water-pressure and - temperature gage. Gages shall have operating-pressure and -temperature ranges, so normal operating range is about 50 percent of full range.

31 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE E. Boiler Air Vent: Automatic. F. Drain Valve: Minimum NPS 3/4 hose-end gate valve. G. Circulation Pump: Nonoverloading, in-line pump with split-capacitor motor having thermal-overload protection and lubricated bearings; designed to operate at specified boiler pressures and temperatures. 2.5 CONTROLS A. Refer to Section "Direct Digital Control (DDC) System for HVAC". B. Boiler operating controls shall include the following devices and features: 1. Control transformer. 2. Set-Point Adjust: Set points shall be adjustable. 3. Operating Pressure Control: Factory wired and mounted to cycle burner. 4. Low-Water Cutoff and Pump Control: Cycle feedwater pump(s) for makeup water control. 5. Sequence of Operation: Electric, factory-fabricated and field-installed panel to control burner firing rate to maintain space temperature in response to thermostat with heat anticipator located in heated space. a. Include automatic, alternating-firing sequence for multiple boilers to ensure maximum system efficiency throughout the load range and to provide equal runtime for boilers. 6. Sequence of Operation: Electric, factory-fabricated and field-installed panel to control burner firing rate to reset supply-water temperature inversely with outside-air temperature. At 0 deg F outsideair temperature, set supply-water temperature at 200 deg F; at 60 deg F outside-air temperature, set supply-water temperature at 140 deg F. a. Include automatic, alternating-firing sequence for multiple boilers to ensure maximum system efficiency throughout the load range and to provide equal runtime for boilers. C. Burner Operating Controls: To maintain safe operating conditions, burner safety controls limit burner operation. 1. High Cutoff: Automatic reset stops burner if operating conditions rise above maximum boiler design temperature. 2. Low-Water Cutoff Switch: Electronic probe shall prevent burner operation on low water. Cutoff switch shall be manual-reset type. 3. Blocked Inlet Safety Switch: Manual-reset pressure switch field mounted on boiler combustion-air inlet. 4. Audible Alarm: Factory mounted on control panel with silence switch; shall sound alarm for above conditions. D. Building Automation System Interface: Factory install hardware and software to enable building automation system to monitor, control, and display boiler status and alarms. 1. Hardwired Points: a. Monitoring: On/off status, common trouble alarm low-water-level alarm. b. Control: On/off operation, hot-water-supply temperature set-point adjustment.

32 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE A communication interface with building automation system shall enable building automation system operator to remotely control and monitor the boiler from an operator workstation. Control features available, and monitoring points displayed, locally at boiler control panel shall be available through building automation system. 2.6 ELECTRICAL POWER A. Controllers, Electrical Devices, and Wiring: Electrical devices and connections are specified in electrical Sections. B. Single-Point Field Power Connection: Factory-installed and -wired switches, motor controllers, transformers, and other electrical devices necessary shall provide a single-point field power connection to boiler. 1. House in NEMA 250, Type 1 enclosure. 2. Wiring shall be numbered and color coded to match wiring diagram. 3. Install factory wiring outside of an enclosure in a metal raceway. 4. Provide branch power circuit to each motor and to controls with a disconnect switch or circuit breaker. 5. Provide each motor with overcurrent protection. 2.7 VENTING KITS A. Kit: Complete system, per manufacturer s recommendations. 2.8 SOURCE QUALITY CONTROL A. Burner and Hydrostatic Test: Factory adjust burner to eliminate excess oxygen, carbon dioxide, oxides of nitrogen emissions, and carbon monoxide in flue gas and to achieve combustion efficiency; perform hydrostatic test. B. Test and inspect factory-assembled boilers, before shipping, according to 2010 ASME Boiler and Pressure Vessel Code. C. Allow Owner access to source quality-control testing of boilers. Notify Architect 14 days in advance of testing. PART 3 - EXECUTION 3.1 EXAMINATION A. Examine roughing-in for concrete equipment bases, anchor-bolt sizes and locations, and piping and electrical connections to verify actual locations, sizes, and other conditions affecting performance of the Work. 1. Final boiler locations indicated on Drawings are approximate. Determine exact locations before roughing-in for piping and electrical connections.

33 CONDENSING BOILERS LINCOLN HS STEAM PRE-PURCHASE B. Examine mechanical spaces for suitable conditions where boilers will be installed. C. Proceed with installation only after unsatisfactory conditions have been corrected. 3.2 BOILER INSTALLATION A. Equipment Mounting: 1. Install boilers on cast-in-place concrete equipment base(s). Comply with requirements for equipment bases. B. Install gas-fired boilers according to NFPA 54. C. Assemble and install boiler trim. D. Install electrical devices furnished with boiler but not specified to be factory mounted. E. Install control wiring to field-mounted electrical devices. 3.3 CONNECTIONS A. Piping installation requirements are specified in other Sections. Drawings indicate general arrangement of piping, fittings, and specialties. B. Install piping adjacent to boiler to allow service and maintenance. C. Install piping from equipment drain connection to nearest floor drain. Piping shall be at least full size of connection. Provide an isolation valve if required. D. Connect piping to boilers, except safety relief valve connections, with flexible connectors of materials suitable for service. Flexible connectors and their installation are specified in Section "Hydronic Piping Specialties." E. Connect gas piping to boiler gas-train inlet with union. Piping shall be at least full size of gas-train connection. Provide a reducer if required. F. Connect hot-water piping to supply- and return-boiler tappings with shutoff valve and union or flange at each connection. G. Install piping from safety relief valves to nearest floor drain. H. Boiler Venting: 1. Install flue venting kit and combustion-air intake. 2. Connect full size to boiler connections. I. Ground equipment according to Section "Grounding and Bonding for Electrical Systems." J. Connect wiring according to Section "Low-Voltage Electrical Power Conductors and Cables."

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

Bids received after scheduled opening time will be returned to Bidder unopened.

Bids received after scheduled opening time will be returned to Bidder unopened. SPECIFICATIONS FOR INSTALLATION OF LOCHINVAR CREST CONDENSING BOILER FBN1251 or SIMILAR SYSTEM FOR THE MANCHESTER RECREATION COMPLEX Requested bidders, please provide a TURNKEY PRICE for the DEMOLISHING

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION FUEL-FIRED DOMESTIC WATER HEATERS

SECTION FUEL-FIRED DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION WATER-TUBE BOILERS

SECTION WATER-TUBE BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 238126 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS HI DELTA, TYPE WH - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 3500.932A Effective: 04-01-17 Replaces: 10-31-16 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY A.

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS XPAK FT TYPE H - MODELS 088AR-398A SUGGESTED SPECIFICATIONS Catalog No.: 2100.91 Effective: 05/01/15 Replaces: new DIVISION 23 52 33.13 WALL-HUNG STAINLESS STEEL HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 2505-4005 SUGGESTED SPECIFICATIONS Catalog No.: 6000.70 Effective: 09-15-16 Replaces: NEW WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes condensing, gas-fired

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. SECTION 238113 - PACKAGED TERMINAL AIR CONDITIONERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

WATER-TUBE POOL HEATERS

WATER-TUBE POOL HEATERS XTHERM, TYPE P - MODELS 1005A-2005A SUGGESTED SPECIFICATIONS Catalog No.: 6000.63B Effective: 3-01-15 Replaces: 9-01-09 WATER-TUBE POOL HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes condensing,

More information

Copyright 2011 AIA MasterSpec Full Length 06/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO CALCANA USA LTD.

Copyright 2011 AIA MasterSpec Full Length 06/11 PRODUCT MASTERSPEC LICENSED BY ARCOM TO CALCANA USA LTD. Copyright 2011 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA This Product MasterSpec Section is licensed

More information

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS

PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS PART 0 A/E INSTRUCTIONS 0.01 DESIGN REQUIREMENTS A. General: 1. To obtain maintenance and repair standards for boiler burners (Section 15555A) and boiler tubes (Section 15555B), contact the DPS Project

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Construction Standards Page

Construction Standards Page Construction Standards Page 236313-1 SECTION 236313 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION ROTARY-SCREW WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS PART 1 GENERAL 1.01 SECTION INCLUDES A. Factory-assembled packaged chiller. B. Charge of refrigerant and oil. C. Controls and control connections. D. Chilled water connections. E. Electrical power connections.

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL SECTION 22 14 00 DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 00 10,

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 6000.611 Effective: 10-31-16 Replaces: NEW FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 2000.932C Effective: 04-01-14 Replaces: 07-15-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

SECTION AIR COILS

SECTION AIR COILS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 504A-2004A SUGGESTED SPECIFICATIONS Catalog No.: 2000.933C Effective: 06-25-15 Replaces: 12-21-09 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

A. This Section includes the following domestic water piping specialties:

A. This Section includes the following domestic water piping specialties: SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Page 236423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical Plant

More information

C. Samples for Initial Selection: For units with factory-applied color finishes.

C. Samples for Initial Selection: For units with factory-applied color finishes. SECTION 238126- SPLIT-SYSTEM AIR-CONDITIONERS PART 1- GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES Page 226119-1 SECTION 226119 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

A. Product Data: Include rated capacities, furnished specialties and accessories.

A. Product Data: Include rated capacities, furnished specialties and accessories. BASE BID: SECTION 15542 FUEL-FIRED RADIANT HEATERS PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install a Co-Ray-Vac Low Intensity Vented Infrared Radiant Vacuum Gas Heating System. System must be certified

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS MVB, TYPE H - MODELS 2503-4003 SUGGESTED SPECIFICATIONS Catalog No.: 2000.934A Effective: 04-01-14 Replaces: 06-01-13 DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC). SECTION 15555 HORIZONTAL FIRE TUBE BOILERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15510 - Piping (HVAC). 2. 15540 - Pumping Equipment (HVAC). 1.02 SUBMITTALS A. Submit properly identified

More information

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

DIVISION COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS MVB, TYPE WH - MODELS 503A-2003A SUGGESTED SPECIFICATIONS Catalog No.: 3500.952C Effective: 06-25-15 Replaces: 12-22-09 DIVISION 23 34 36.29 COMMERCIAL, GRID-TYPE, FINNED-TUBE, GAS DOMESTIC WATER HEATERS

More information

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 SECTION 232116 - HYDRONIC PIPING SPECIALTIES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS

ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS Annex Laundry and Shower Alterations ADDENDUM #1 March 7, 2019 ADDENDUM #1: MODIFICATIONS AND ADDITIONS TO CONTRACT DOCUMENTS A. Invitation to Bid - Call for Bids has been modified as follows: 1. Notice

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS XTHERM, TYPE WH - MODELS 1005A- 2005A Catalog No.: 3500.801 Effective: 11-15-14 Replaces: NEW PART 1 - GENERAL 1.1 SUMMARY DIVISION 23 34 36.29 COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

More information

DIVISION FINNED WATER-TUBE BOILERS

DIVISION FINNED WATER-TUBE BOILERS HI DELTA, TYPE H - MODELS 992C-2342C SUGGESTED SPECIFICATIONS Catalog No.: 2000.953 Effective: 10-31-16 Replaces: NEW DIVISION 23 52 33.13 FINNED WATER-TUBE BOILERS - GENERAL 1.1 SUMMARY A. Section includes

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

FINNED WATER-TUBE POOL HEATERS

FINNED WATER-TUBE POOL HEATERS HI DELTA, TYPE P - MODELS 502C-902C SUGGESTED SPECIFICATIONS Catalog No.: 6000.601A Effective: 07-12-18 Replaces: 10-31-16 FINNED WATER-TUBE POOL HEATERS - GENERAL 1.1 SUMMARY A. Section includes gas-fired,

More information

A. This Section includes the following emergency plumbing fixtures:

A. This Section includes the following emergency plumbing fixtures: Page 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent

HHA Bellerive Apartments 7225 Bellerive Houston, Texas J. Allen Management Managing Agent HHA Bellerive Apartments 7225 Bellerive Houston, Texas 77036 J. Allen Management Managing Agent Scope of Work: 1.) Water Heater Replacement with Vertical Boiler System 2.) Water Conditioning System (Softener)

More information

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PROJ. NO SECTION REFRIGERANT PIPING

PROJ. NO SECTION REFRIGERANT PIPING SECTION 23 23 00 REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

NATURAL GAS PIPING

NATURAL GAS PIPING SECTION 15496 - NATURAL GAS PIPING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent

HHA Lyerly Apartments 75 Lyerly Houston, Texas J. Allen Management Managing Agent HHA Lyerly Apartments 75 Lyerly Houston, Texas 77022 J. Allen Management Managing Agent Scope of Work: 1.) Boiler Replacement with Double Vertical Boiler System (1 Million btu each) 2.) Water Pump Replacement

More information

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features:

SECTION CENTRAL BATTERY INVERTERS. A. This Section includes fast-transfer central battery inverters with the following features: PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fast-transfer central battery inverters with the following features: 1. Emergency-only circuits. 1.2 DEFINITIONS A. LCD: Liquid-crystal display. B.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING SECTION 221123 - DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1.

More information

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube water heaters for heating hot water.

RBI MASTERSPEC. A. This Section includes gas-fired, non-condensing finned copper water tube water heaters for heating hot water. MSWFTIII-7 SECTION 22 34 36.29 - SAMPLE SPECIFICATION FOR RBI FUTERA III MODULATING WATER HEATER PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

SECTION (15767) - UNIT HEATERS

SECTION (15767) - UNIT HEATERS SECTION 23 82 39 (15767) - UNIT HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Unit Heaters. 2. Cabinet Unit Heaters. 3. Duct Heaters. 4. Baseboard Heaters. B. Related Sections: 1. Section

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA

More information

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008 SECTION 15181 - HYDRONIC SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Air separators B. Expansion tanks C. Pump accessories 1.2 RELATED SECTIONS A. Section - Plumbing Piping Specialties B. Section

More information

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services Page 238216-1 Copyright 2003 and 2005 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified by MSU Physical

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION (15530) - REFRIGERANT PIPING

SECTION (15530) - REFRIGERANT PIPING SECTION 23 23 00 (15530) - REFRIGERANT PIPING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Tubes. 2. Fittings. 3. Joining Materials. 4. Specialties. B. Related Sections: 1. Section 07 92 00 (07920)

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 236426.11 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION HEATING BOILER FEEDWATER EQUIPMENT SECTION 23 53 00 HEATING BOILER FEEDWATER EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section includes boiler feedwater pumps, de-aerators, accessories, controls and tanks. 1.2 REFERENCES A. ASME (American

More information

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS SL/SLV SIRIUS LINEAR RANGE HIGH EFFICIENCY CONTINUOUS INFRARED SYSTEMS

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS SL/SLV SIRIUS LINEAR RANGE HIGH EFFICIENCY CONTINUOUS INFRARED SYSTEMS GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS SL/SLV SIRIUS LINEAR RANGE HIGH EFFICIENCY CONTINUOUS INFRARED SYSTEMS SECTION 15540 FUEL- FIRED HEATERS (Alternate - SECTION 235523 - GAS-FIRED RADIANT HEATERS)

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

INVITATION FOR BID. May 17, Purchase Natural Gas Hot Water Boiler MAWSS Purchasing Department

INVITATION FOR BID. May 17, Purchase Natural Gas Hot Water Boiler MAWSS Purchasing Department mawss Buyer II Lisa Russell (251) 694-3162 Office Irussell@mawss.com TO INVITATION FOR BID NUMBER SEPARATE SEALED BIDS FOR BIDS WILL BE RECEIVED AT Prospective Bidders IFB 18-023 INVITATION FOR BID May

More information

BID PROPOSAL-REVISED

BID PROPOSAL-REVISED BID PROPOSAL-REVISED PROJECT: B17-13, Bldg 1300 HVAC ( the Work ) CABRILLO COMMUNITY COLLEGE DISTRICT Bidder Name Bidder Representative(s) Bidder Representative(s) Contact Information Bidder Mailing Address

More information

Sidney, Ohio 1204 FORMAL ISSUANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION... ON OR BEFORE JULY 30, 2015.

Sidney, Ohio 1204 FORMAL ISSUANCE OF CERTIFICATE OF SUBSTANTIAL COMPLETION... ON OR BEFORE JULY 30, 2015. SECTION 000050 - INVITATION AND NOTICE TO BIDDERS PROJECT: OWNER: 3003 Cisco Road Sidney, Ohio 45365 Ohio Presbyterian Retirement Services 1001 Kingsmill Parkway Columbus, Ohio 43229 ARCHITECT: 4685 Larwell

More information

SECTION WATER HEATERS

SECTION WATER HEATERS SECTION 15457 WATER HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete hot water generating system with necessary accessories as indicated on Construction Documents, as specified, and

More information

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler SECTION 15181 - HYDRONIC SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler B. Expansion tanks C. Pump accessories 1.2 RELATED SECTIONS

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

SECTION AIR COOLED WATER CHILLERS

SECTION AIR COOLED WATER CHILLERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Chiller package B. Charge of refrigerant and oil C. Controls and control connections D. Chilled water connections E. Starters F. Electrical power connections 1.2

More information

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS SECTION 15540 FUEL- FIRED HEATERS (Alternate - SECTION 235523 - GAS-FIRED RADIANT HEATERS) This section is based

More information

AFUE 95% Heating Input 50,000 to 200,000 Btuh

AFUE 95% Heating Input 50,000 to 200,000 Btuh PRODUCT SPECIFICATIONS WATER HEATERS / BOILERS GWM-IE Gas-Fired, Modulating, Condensing, Wall Hung Hot Water Boiler Bulletin No. 210650 March 2018 Supersedes December 2015 AFUE 95% Heating Input 50,000

More information

Suggested Specifications Prestige Excellence 110

Suggested Specifications Prestige Excellence 110 Suggested Specifications Prestige Excellence 110 General Requirements A. Furnish and install (qty) completely assembled, modulating, sealed combustion, high efficiency, combination gas-fired boiler(s)

More information

BuildingName The Description of the Project P DOCUMENTS

BuildingName The Description of the Project P DOCUMENTS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information