PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
|
|
- Tamsin Blake
- 5 years ago
- Views:
Transcription
1 Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B Ontario-NBC CODE REFERENCE: Division B / Division B / (1) SB-2 DESCRIPTION OF THE PROPOSED AMENDMENT This proposed change replaces references to SB2 with references to CAN/ULC-S112.2, "Standard Method of Fire Test of Ceiling Firestop Flap Assemblies". EXISTING 2012 BUILDING CODE PROVISION(S) Plenum Requirements (2) If a concealed space referred to in Sentence (1) is used as a return-air plenum and incorporates a ceiling membrane that forms part of the required fire-resistance rating of the assembly, every opening through the membrane shall be protected by a fire stop flap that shall, (a) stop the flow of air into the concealed space in the event of a fire, (b) be supported in a manner that will maintain the integrity of the ceiling membrane for the duration of time required to provide the required fire-resistance rating, and (c) conform to CAN/ULC-S112.2, Fire Test of Ceiling Firestop Flap Assemblies Fire Stop Flaps (1) Fire stop flaps in ceiling membranes required in Sentence (4) shall be constructed in conformance with MMAH Supplementary Standard SB-2, Fire Performance Ratings. SB-2 Fire-Performance Ratings 5.3. Fire Stop Flaps Construction Requirements (1) Fire stop flaps shall be constructed of steel not less than 1.5 mm thick, covered on both sides with painted asbestos paper not less than 1.6 mm thick and equipped with pins and hinges of corrosion-resistant material (see Figure ). Building and Development Branch Page 1
2 Hold-Open Devices (1) Fire stop flaps shall be held open with fusible links conforming to ULC-S505, "Fusible Links for Fire Protection Service", or other heat-activated devices having a temperature rating approximately 30 C above the maximum temperature that would exist in the system either with the system in operation or shut down. Figure Typical Fire Stop Flaps Building and Development Branch Page 2
3 PROPOSED CODE CHANGE Revise existing Articles , and and SB-2 as follows: Plenum Requirements (2) If a concealed space referred to in Sentence (1) is used as a return-air plenum and incorporates a ceiling membrane that forms part of the required fire-resistance rating of the assembly, every opening through the membrane shall be protected by a fire stop flap that shall, (a) stop the flow of air into the concealed space in the event of a fire, (b) be supported in a manner that will maintain the integrity of the ceiling membrane for the duration of time required to provide the required fire-resistance rating, and (c) conform to CAN/ULC-S112.2, Fire Test of Ceiling Firestop Flap Assemblies and (d) activates at a temperature approximately 30 C above the normal maximum temperature that occurs in the return-air plenum, whether the air duct system is operating or shut down Fire Stop Flaps (1) Fire stop flaps in ceiling membranes requiredreferred to in Sentence (4) shall be constructed in conformance with MMAH Supplementary Standard SB-2, Fire Performance Ratings. (a) conform to CAN/ULC-S112.2., Fire Test of Ceiling Firestop Flap Assemblies, and (b) activate at a temperature approximately 30 C above the normal maximum temperature that occurs in the ducts, whether the air duct system is operating or shut down. SB-2 Fire-Performance Ratings 5.3. Fire Stop Flaps Construction Requirements (1) Fire stop flaps shall be constructed of steel not less than 1.5 mm thick, covered on both sides with painted asbestos paper not less than 1.6 mm thick and equipped with pins and hinges of corrosion-resistant material (see Figure ). Building and Development Branch Page 3
4 Hold-Open Devices (1) Fire stop flaps shall be held open with fusible links conforming to ULC-S505, "Fusible Links for Fire Protection Service", or other heat-activated devices having a temperature rating approximately 30 C above the maximum temperature that would exist in the system either with the system in operation or shut down. RATIONALE FOR CHANGE Problem/General Background Figure Typical Fire Stop Flaps The current code requires fire stop flaps to meet out-of-date requirements referenced in Supplementary Standard SB-2. Additionally, these current requirements are restrictive in that they are very prescriptive, making selection and acceptance of any fire stop flaps other than what is described difficult for code users. Justification/Explanation This proposed change would harmonize requirements with the model National Building Code of Canada. Referencing an appropriate standard will permit designers and enforcement officials to incorporate fire stop flaps that conforms to the standard and not be limited to specific and restrictive construction requirements. Building and Development Branch Page 4
5 So any reference to Supplementary Standard SB-2 for fire stop flaps in Parts 3 and 9 of Division B are replaced by a reference to the CAN/ULC-S112.2, "Standard Method of Fire Test of Ceiling Firestop Flap Assemblies." Consequently, Section D-5.3. Fire Stop Flaps of Division B of Supplementary Standard SB-2 is deleted. Cost/Benefit Implications Products that meet the standard are available: so there should be no cost impact. Enforcement Implications The requested change can be enforced within the infrastructure available and should prove to be advantageous to enforcement officials. Who is Affected N/A Objective Based Analysis Provision Objective/Functional Statement Division B (2) 2 [F03-OS1.2,OS1.3] (2) 2 [F03-OP1.2,OP1.3] Division B (1) 1 [F03-OS1.3,OS1.2] (1) 1 [F03-OP1.3,OP1.2] OTHER SUPPORTING MATERIALS Building and Development Branch Page 5
PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION
More informationPhase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:
Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B-09-32-03 POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: SUMMER AND FALL 2017 CONSULTATION Ministry of Municipal Affairs PROPOSED
More informationPROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015)
PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015) CHANGE NUMBER: CODE REFERENCE: Division B, Sentences 2.13.2.1.(2), 2.13.2.1.(3) DESCRIPTION OF PROPOSED
More information2012 Ontario Building Code Update
2012 Ontario Building Code Update Presented to NORR Dec. 10, 2013 Alek Antoniuk, OAA 2013 Agenda Selected highlights of changes in the 2012 Ontario Building Code related to larger (Pt. 3) buildings O.
More informationRecent Revisions and Proposed Key Changes to Fire Code
Recent Revisions and Proposed Key Changes to Fire Code 2014 CFAA Presentation Kim Bailey - Office of the Fire Marshal and Emergency Management New Section 9.7 Buildings with a Care Occupancy or Retirement
More informationPROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)
PROPOSED TO THE 2007 FIRE CODE (OFC) PROPOSED OFC Record Division: A Reference Number: 1.4.1.2. DESCRIPTION OF PROPOSED EXISTING OFC PROVISIONS Delete the following definitions: Care or detention occupancy
More informationPROPOSED CHANGE TO THE 2007 FIRE CODE (OFC)
TO THE 2007 FIRE CODE (OFC) OFC Record Division: A Reference Number: 1.4.1.2. (dwelling unit) Corresponding NFC Change Division: A Reference Number: 1.4.1.2.(1) OFC Revise definition for Dwelling unit
More informationInterim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017
Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical
More informationBULLETIN BU/EL Revised August 11, 2015
BULLETIN 2000-019-BU/EL Revised August 11, 2015 TRANSMITTING UNIT FROM PROTECTED PREMISES TO FIRE SIGNAL RECEIVING CENTRE IN CONFORMANCE WITH CAN/ULC-S561 The intent of this bulletin is to clarify the
More informationBY-LAW AMENDING THE BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL (RCG )
VILLE DE MONTRÉAL BY-LAW RCG 12-003-1 BY-LAW AMENDING THE BY-LAW CONCERNING THE SERVICE DE SÉCURITÉ INCENDIE DE MONTRÉAL (RCG 12-003) In view of section 62 of the Municipal Powers Act (CQLR, chapter C-47.1);
More informationBuilding Standards Advisory Promoting construction of safe, healthy, habitable buildings
Building Standards Advisory Promoting construction of safe, healthy, habitable buildings Saskatchewan Amendments to the National Building Code 2015 In Canada, provincial and territorial governments have
More informationMAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS
FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are
More informationENERGY EFFICIENCY AFTER DECEMBER 31, 2016
MODULE 2 Energy Efficiency INTRODUCTION In this module the requirements for energy efficiency in buildings is examined with particular attention to the Supplementary Standard to the OBC, SB-10, Energy
More informationDIVISION C ADMINISTRATIVE PROVISIONS
For what s new, check out www.regulationsandstatutes.com 374 DIVISION C ADMINISTRATIVE PROVISIONS SECTION 1.1 GENERAL Subsection 1.1.1. Chief Fire Official Appointment by Fire Marshal 1.1.1.1. (1) The
More informationBUILDING CODE INTERPRETATION
BUILDING CODE INTERPRETATION November 2017 14-BCI-009 Page 1 of 6 FIRE ALARM AND FIRE SUPPRESSION SYSTEM VERIFICATION AND TESTING CERTIFICATES PURPOSE This STANDATA has been developed to give municipalities
More informationCAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED
More informationVERIFICATION OF FIRE ALARM SYSTEMS
DEVELOPMENT, BUILDINGS AND LICENSING Chief Building Official (CBO) and Building Code and Policy Building Policy Branch The intent of this bulletin is to clarify requirements of verification of the fire
More informationCAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning
CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region
More informationRed Deer. AMA Regional Meeting. Electrical, Plumbing, Gas, Private Sewage, Building and Fire
Red Deer AMA Regional Meeting Electrical, Plumbing, Gas, Private Sewage, Building and Fire AGENDA 8:30 am Call to Order and Introductions Mike Hill, AMA 8:35 am 8:45 am AMA General Updates Joe Healy, AMA
More informationErrata Package National Fire Code of Canada (NFC) Selected replacement pages have been produced for the NFC.
2010 National Fire Code of Canada (NFC) Errata Package Selected replacement pages have been produced for the NFC. Please print and insert in your copy of the Code. Preface Code Development Development
More informationBCBC 2012 CHANGES TO PART 3
BCBC 2012 CHANGES TO PART 3 Focus on changes that will have an practical effect. Basic concepts reviewed details to be confirmed. Material from Part 3 and related material from Part 9 Generally a harmonization
More informationBritish Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety
Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These
More informationFEO Initiation Devices Dean McLellan
FEO Initiation Devices Dean McLellan Enforcement Protocol 1. TSSAct 2. Ontario Regulation 209/01 3. Code Adoption Document (CAD) 4. Director s Orders 5. Applicable Code 1. Sub Codes (NBCC, CEC) A17/B44
More informationVariance from Chapter 297, Signs, of the Former City of Toronto Municipal Code Bloor Street West (High Park)
Variance from Chapter 297, Signs, of the Former City of Toronto Municipal Code - 2595 Bloor Street West (High Park) (City Council on August 1, 2, 3 and 4, 2000, adopted this Clause, without amendment.)
More informationCFAA Alberta Technical Seminar October 24, 2013 Calgary
CFAA Alberta Technical Seminar October 24, 2013 Calgary Alberta Fire and Building Code Questions 1 Next Code Editions Anticipated April 1, 2014 Final Text has been provided to NRC NRC currently drafting
More informationPart 3 BUILDING CODE MYTHS & INTERPRETATIONS
Part 3 BUILDING CODE MYTHS & INTERPRETATIONS November 18, 2016 Frank Durante, RBO Building Inspector District of Mission Phone 604 820 3729 Wendy Morrison, AScT, BCQ GHL CONSULTANTS LTD Fire Science and
More informationPORTABLE FIRE EXTINGUISHERS
FIRE CODE BULLETIN February 2018 14-FCB-002 Page 1 of 6 PORTABLE FIRE EXTINGUISHERS PURPOSE This bulletin is to clarify the intent of the Alberta Fire Code 2014 (AFC 2014) and NFPA 10, Standard for Portable
More informationMajor Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing
Major Changes Nova Scotia Building Code 2011 Construction and Maintenance Regulatory Change Industry Briefing Ted Ross Labour & Advanced Education Gerard Donahoe Labour & Advanced Education Overview Where
More informationBUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT
BUILDING MATERIALS EVALUATION COMMISSION (BMEC) AUTHORIZATION REPORT DATE OF AUTHORIZATION June 28, 2001 BMEC REFERENCE BMEC # 01-07-259 BMEC APPLICATION # BMEC #A 2001-10 OATEY CANADA INC. SURE-VENT AND
More informationShort Term Accommodations Fire Code Requirements
Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS
RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY
More information150 Eighth Street Zoning By-law Amendment Application Preliminary Report
REPORT FOR ACTION 150 Eighth Street Zoning By-law Amendment Application Preliminary Report Date: March 27, 2019 To: Etobicoke York Community Council From: Director, Community Planning, Etobicoke York District
More informationBUILDING CODE COMMISSION
Ruling No. 10-20-1256 Application No. B-2010-12 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article Sentences
More informationOutline of Measures for Fire Prevention and Safety under the Laws and Regulations of Fire Fighting
Outline of Measures for Fire Prevention and Safety under the Laws and Regulations of Fire Fighting Materials created by the Fire and Disaster Management Agency were translated by the International Fire
More informationOWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue
OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE John Percy, Public Education Officer Waterloo Fire Rescue AGENDA: Fire Protection and Prevention Act and Ontario Fire Code Role of Assistants to
More informationBUILDING CODE COMMISSION
Ruling No. 10-01-1237 Application No. B-2009-37 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article 3.2.9.1.
More informationCAN/ULC-S561. To comply, or not to comply. actually it s not even a question! Underwriters Laboratories of Canada. By Alan Cavers & Brian McBain
CAN/ULC-S561 To comply, or not to comply. actually it s not even a question! By Alan Cavers & Brian McBain CAN/ULC-S561, Installation And Services For Fire Signal Receiving Centres And Systems is without
More informationAnimals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618
Description Duration Animals:Goats:Bleat.Calls,Warbling.Baa,Movements.Rubbing,Barn,Medium.Close,Interior,BG.Dog.Barks 01:21.618 Animals:Goats:Herd,Bleat.Calls,Intensity.Increase,Warbling,Baby.Baa,Movements.Rubbing,Barn,Occasional.Dog.Barks,Medium.Close,Interior,BG.Crows.Squawks
More informationFire Resistant Cables - Update Alan Cavers Engineering Manager Certificate Services Group
Fire Resistant Cables - Update Alan Cavers Engineering Manager Certificate Services Group History Impact on Standards Where It s At Where It s Going 2 A concern was investigated related to the presence
More information240 and 242 Finch Avenue West Zoning By-law Amendment Application Preliminary Report
REPORT FOR ACTION 240 and 242 Finch Avenue West Zoning By-law Amendment Application Preliminary Report Date: March 1, 2019 To: North York Community Council From: Director, Community Planning, North York
More informationCFAA Technical Seminar Ontario Building Code Updates to 2015
CFAA Technical Seminar Ontario Building Code Updates to 2015 October 28, 2015 2015 Fire Alarm Updates Ontario Building Code Glenn Somerton P.Eng. Senior Code Specialist Morrison Hershfield Limited gsomerton@morrisonhershfield.com
More informationReport to Council. Date: December 15, 2014 Jeff Watson, Policy Planner
Department: Planning Date: December 15, 2014 Prepared by: Jeff Watson, Policy Planner Report to Council Submitted by: Chris Nepszy, Director of Infrastructure and Development Report Number: Planning 2014-54
More informationJOINT CODE INTERPRETATION
JOINT CODE INTERPRETATION May 2018 Mobile/Temporary Cooking Equipment 14-FCI-003 Page 1 of 8 PURPOSE The purpose of this interpretation is to assist owners/operators of mobile cooking operations and safety
More informationCAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015
CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?
More informationThe course only requires the latest edition of the following documents: Building Code Compendium, Volume 1 and 2.
MODULE 1 INTRODUCTION AND INSTRUCTIONS ADMINISTRATIVE REQUIREMENTS flipchart. When asked by the Facilitator, the spokesperson will explain the group s answer, which forms the basis for class discussion.
More informationBuilding and Development
Upcoming Events Building and Development Loyalist Township Development Services Department www.loyalist.ca 613-386-7351 Introduction Issue 2 October 2015 Loyalist Township Building Department proudly introduces
More information112 College Street Zoning Amendment Application Preliminary Report
~TORONTO REPORT FOR ACTION 112 College Street Zoning Amendment Application Preliminary Report Date: January 25, 2019 To: Toronto and East York Community Council From: Director, Community Planning, Toronto
More informationGUIDELINES FOR CULTURAL HERITAGE IMPACT ASSESSMENTS
GUIDELINES FOR CULTURAL HERITAGE IMPACT ASSESSMENTS Purpose A Cultural Heritage Impact Assessment (CHIA) is a study to identify and evaluate built heritage resources and cultural landscapes in a given
More information2018 Revisions and Errata Package
2015 National Fire Code of Canada (NFC) 2018 Revisions and Errata Package Selected replacement pages have been produced for the NFC. Please print and insert in your copy of the Code. Revisions and Errata
More informationFIRE RATED PRODUCTS GENERAL PRODUCT OVERVIEW. Fire Rated Products
IRE RATED PRODUCTS GENERAL PRODUCT OVERVIEW ire Rated Products Nailor offers a wide variety of fire rated products that are designed to provide the unobtrusive appearance required for architectural excellence
More informationBUILDING CODE COMMISSION
Ruling No. 03-31-929 Application No. 2003-38 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.13.7.(1)
More informationConstruction Requirements and the Ontario Building Code
Construction Requirements and the Ontario Building Code Thomas Pepper, P. Eng. October 20, 2017 OSBIE Toronto The Evolution of Construction Laws Building Regulations date back as far as 1900 B.C. to Babylonian
More informationTown of Whitchurch-Stouffville Cultural Heritage Impact Assessment
Revised: March 2012 Town of Whitchurch-Stouffville 1. Purpose of a Heritage conservation involves identifying, protecting and promoting buildings, structures or other elements that have been deemed to
More informationMotion Controlled Apartment Building Corridor Lighting
STAFF REPORT ACTION REQUIRED Motion Controlled Apartment Building Corridor Lighting Date: October 19, 2009 To: From: Wards: Reference Number: Licensing and Standard Committee Executive Director, Municipal
More informationARTICLE 25. FUEL GAS CODE
ARTICLE 25. Rule 1. Indiana Fuel Gas Code, 2003 Edition (Repealed) (Repealed by Fire Prevention and Building Safety Commission; filed Mar 18, 2008, 2:32 p.m.: 20080423-IR-675070479FRA, eff 90 days after
More informationBUILDING CODE COMMISSION
Ruling No. 02-16-871 Application No. 2002-07 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.2.4.20.(2)
More informationPlease think twice about printing this matrix. You can it, along with your ballot to or
Page Line Clause E/G Organization Comment (rationale) ii Foreword E GWM Recommend inserting the following text between the first and second paragraphs, Fire Alarm Systems shall be installed in accordance
More informationSECTION AIR DUCT ACCESSORIES
SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control
More informationGUIDELINES FOR CULTURAL HERITAGE IMPACT ASSESSMENTS
GUIDELINES FOR CULTURAL HERITAGE IMPACT ASSESSMENTS Purpose The purpose of undertaking a Cultural Heritage Impact Assessment, which is provided by the applicant, is to identify and evaluate cultural heritage
More informationCommunity Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007
STAFF REPORT ACTION REQUIRED Community Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007 Date: April 10, 2007 To: From: Wards: North York
More informationFirst Revision No. 82-NFPA [ Section No ] Submitter Information Verification. Committee Statement. 2 of /21/2013 1:03 PM
2 of 326 11/21/2013 1:03 PM First Revision No. 82-NFPA 72-2013 [ Section No. 2.3.4 ] 2.3.4 ISO Publications. International Organization for Standardization, 1, ch. de la Voie-Creuse, Case postale 56, CH-1211
More informationPlanning and Growth Management Committee
STAFF REPORT ACTION REQUIRED By-law to Require and Govern the Construction of Green Roofs in Toronto Date: October 29, 2008 To: From: Wards: Reference Number: Planning and Growth Management Committee Chief
More informationEmployment and Commercial Review Analysis of Policy Directions
Employment and Commercial Review Analysis of Policy Directions Appendix A The following analysis is town staff s response to the policy directions provided by the consultants who prepared the Employment
More information114 Richmond Road Les Soeurs De La Visitation D'Ottawa. Community Discussion
114 Richmond Road Les Soeurs De La Visitation D'Ottawa Community Discussion Overview of the Proposal Ashcroft s Vision The Development Proposal Ashcroft has released its proposal a for development (700+
More informationProject No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10
Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction
More informationMacintosh HD:CURRENT WORK-(JRW):4026 Northumberland Trent River Crossings:4026_Mem- Pannu_Report(jm)Oct2510.docx
MEMORANDUM To: Mobushar Pannu, County of Northumberland From: Nick McDonald Date: October 27, 2010 Re: First Draft of Report (Trent River Crossing) Our File No: 4026 Attached to this memorandum is a first
More informationOberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products
Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code,
More information2014 Alberta Building Code. Part 9 changes relating to Smoke and CO Alarms
2014 Alberta Building Code Part 9 changes relating to Smoke and CO Alarms 9.32.3.9 Carbon Monoxide Alarms What has not changed: 4) & 6) In a residential occupancy containing a fuel burning appliance or
More informationBOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm
1 BOMA Calgary Luncheon Thursday, October 11, 2012 Building Owners Responsibilities for Fire Safety Equipment (Fire Alarm) Canadian Fire Alarm Association 2 Presentation Overview The Codes Your responsibilities
More informationJ-PRO TM Cable Support System
Frequently Asked Questions Cable Support System What references define how and where J-hooks are used? J-hooks are a horizontal pathway promoted in the BICSI TDM manual as a means to route small to medium
More information6 AMENDMENT NO. 637 TO THE VAUGHAN OFFICIAL PLAN (VAUGHAN 400 NORTH EMPLOYMENT AREA SECONDARY PLAN)
Report No. 3 of the Planning and Economic Development Committee Regional Council Meeting of March 24, 2011 6 AMENDMENT NO. 637 TO THE VAUGHAN OFFICIAL PLAN (VAUGHAN 400 NORTH EMPLOYMENT AREA SECONDARY
More informationOfficial Plan Amendment Setbacks from Railway Operations
Official Plan Amendment Setbacks from Railway Operations August 12, 2015 Send your comments to: Krista Libman, Planner City of Ottawa Planning and Growth Management Tel: 613-580-2424 ext. 27893 E-mail:
More informationHousing Division Notice
Housing Division Notice Date: October 1, 2014 HDN# 2014 204 This applicable legislation/policy is to be implemented by the housing provider(s) under the following programs: Please note if your program
More information20 & 50 Ashtonbee Road, 1920 & 1940 Eglinton Avenue East, and 880, 890 & 900 Warden Avenue Zoning Amendment Application Final Report
STAFF REPORT ACTION REQUIRED 20 & 50 Ashtonbee Road, 1920 & 1940 Eglinton Avenue East, and 880, 890 & 900 Warden Avenue Zoning Amendment Application Final Report Date: August 16, 2012 To: From: Wards:
More informationCapital Projects Group Fire Extinguishers Specification
Capital Projects Group Fire Extinguishers Specification Specification 21 20 05 Revision 0 Date: August 2018 Fire Extinguishers Specification Specification 21 20 05 Publication Date: August 2018 COPYRIGHT
More informationPublic Comment No. 2-NFPA [ Section No ]
Public Comment No. 2-NFPA 16-2013 [ Section No. 3.3.6 ] 3.3.6* Foam-Water Sprinkler System. A piping network connected to a source of foam concentrate and to a water supply. The piping network is equipped
More informationMajor Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014
Major Changes to the 2010 National Construction Codes Contractor s Breakfast January 2014 Philip Rizcallah, P. Eng. NRC-IRC Canadian Codes Centre Presented by Stan Dueck CRBO Overview Where are the major
More information150 Elgin - Office Tower and Grant House Renovations
APPLICATION OF THE ONTARIO BUILDING CODE 150 Elgin - Office Tower and Grant House Renovations 150 Elgin Street Ottawa, Ontario Presented to: Mr. Brandon Donnelly Morguard Investments Limited c/o Mr. Harry
More informationPellet Vent INSTALLATION INSTRUCTIONS
Pellet Vent INSTALLATION INSTRUCTIONS A MAJOR CAUSE OF CHIMNEY RELATED FIRES IS FAILURE TO MAINTAIN REQUIRED CLEARANCES (AIR SPACES) TO COMBUSTIBLE MATERIALS. IT IS OF THE UTMOST IMPORTANCE THAT THIS PELLET
More informationSURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin
SURREY FIRE SERVICE Construction Fire Safety Plan Bulletin The B.C. Fire Code requires building owners/contractors to comply with the requirements of the BC Fire Code 5.6 Construction and Demolition Sites
More informationInfrastructure, Development and Enterprise Services. Natural Heritage Action Plan (NHAP) Project Initiation
Staff Report To Service Area Committee of the Whole Infrastructure, Development and Enterprise Services Date Monday, March 6, 2017 Subject Natural Heritage Action Plan (NHAP) Project Initiation Report
More informationFirst Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes
First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] 4.3.11.5.5 Materials within a raised floor plenum exposed to the airflow shall be (a) noncombustible or (b) exhibit a maximum flame spread index of 25
More informationOberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products
Oberon s NEC Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products Manufacturers Statement of Compliance with NFPA 70, National Electric Code Oberon s suspended ceiling
More informationCHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS
CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS 61G15-32.001 61G15-32.002 61G15-32.003 61G15-32.004 61G15-32.005 61G15-32.006 61G15-32.007
More informationRegistered Code Agency
obc - Registered Code Agency Home / Qualification & Registration / Registered Code Agency Registered Code Agency Examination Information Examination Program QuARTS - Online Examination program for Registered
More informationModule 9: Ontario Building Code Fire Fighting Provisions
Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances 1. Sprinklers i) Sprinkler Systems
More informationFIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES
FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES Office of the Fire Marshal and Emergency Management Preface This guideline updates TG-02-1998 published in June 1998. Portions of the guideline
More informationBUILDING CODE COMMISSION
Ruling Numbers 01-14-807 and 01-16-809 Application Numbers 2001-13 and 2001-25 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Sentence
More informationSECTION LOW VOLTAGE POWER PANELBOARDS - SPECTRA
PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Low voltage power panelboards 1.02 RELATED SECTIONS 1.03 REFERENCES
More informationBUSINESS PLAN: Fire Prevention & Education
BUSINESS PLAN: Fire Prevention & Education How does this service contribute to the results identified in the City of London Strategic Plan? A strong economy A vibrant and diverse community A green and
More informationPLANNING COMMITTEE REPORT JULY COMITÉ DE L URBANISME RAPPORT 34 LE 11 JUILLET ZONING 968 ST.
86 COMITÉ DE L URBANISME 6. ZONING 968 ST. LAURENT BOULEVARD ZONAGE 968, BOULEVARD ST-LAURENT COMMITTEE RECOMMENDATION That Council approve an amendment to the Zoning By-law 2008-250 to change the zoning
More informationUnderstanding and Managing Fire Safety in Housing Accommodation
Understanding and Managing Fire Safety in Housing Accommodation Presented at: ONPHA 2015 Annual Conference October 17, 2015 Kevin j. Kelly, P.Eng, Technical Services Office of the Fire Marshal and Emergency
More informationFire Sprinklers Working Group Final Report
Introduction The Building Act received Royal Assent on March 25, 2015. The Act aims to establish more consistent building requirements across British Columbia and create a more robust and modern building
More informationUK Direction BS7671 BS 8492 BS /01/2018
UK Direction BS7671 BS 8492 BS6701 23/01/2018 BS7671:2015 The 17 th Edition Revision 3 details the requirements for an improved fire rating on all cables within a fire route. 422.2.1 In conditions BD2
More informationPROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE
PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated
More informationTitle. Author(s)Yoshida, Fumikazu; Yoshida, Haruyo. Issue Date Doc URL. Type. File Information
Title New directions for the Japanese system of e-waste re Author(s)Yoshida, Fumikazu; Yoshida, Haruyo CitationSeventh International Conference on Waste Management Issue Date 2012-09 Doc URL http://hdl.handle.net/2115/54737
More informationBUILDING CODE COMMISSION
Ruling No. 03-30-928 Application No. 2003-34 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.8.12.(1)
More informationRESIDENTIAL MULTI-USE FIRE SPRINKLER SYSTEMS PERMIT SUBMITTAL REQUIREMENTS
History: RESIDENTIAL MULTI-USE FIRE SPRINKLER SYSTEMS PERMIT SUBMITTAL REQUIREMENTS Per the City adopted 2009 IRC, section R313, automatic fire sprinkler systems are required for all one and two family
More informationGlenwood Springs Fire Protection District Amendments to the 2009 International Fire Code
Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code 060.090.010 Adoption of International Fire Code; Violations; Conflict A. Pursuant to the power and authority conferred
More informationAuditing Association of Canada (AAC) Annual Conference North York, AMEC Environment & Infrastructure
Auditing Association of Canada (AAC) Annual Conference North York, 2013 AMEC Environment & Infrastructure The Role of the Fire Code in Compliance Auditing Peter Beukema, P. Eng., EP(CEA), EP(EMSLA) Senior
More information