BUILDING CODE COMMISSION

Size: px
Start display at page:

Download "BUILDING CODE COMMISSION"

Transcription

1 Ruling No Application No. B BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article of the Regulation 350/06, as amended, (the Building Code). AND IN THE MATTER OF an application by Frank Calandra Jr., Jennmar Corporation for the resolution of a dispute with Alain Bazinet, Chief Building Official, Municipality of West Nipissing, to determine whether the proposed compensating measures offered in lieu of a standpipe and hose system in a new one storey, 5300 m², Group F, Division 3 major occupancy building, provides sufficiency of compliance with Article of Division B of the Building Code at Jennmar Canada Inc, 11 Toulouse Crescent, Sturgeon Falls, Ontario. APPLICANT RESPONDENT PANEL PLACE Frank Calandra Jr. Jennmar Corporation Pittsburgh, PA Alain Bazinet Chief Building Official Municipality of West Nipissing Tony Chow, Chair Leslie Morgan Yaman Uzumeri Toronto, Ontario DATE OF HEARING January 14, 2010 DATE OF RULING January 14, 2010 APPEARANCES Gene Stewart Jennmar Corporation Pittsburg, PA The Agent for the Applicant Alain Bazinet Chief Building Official Municipality of West Nipissing Sturgeon Falls, ON The Respondent

2 RULING 1. Particulars of Dispute The Applicant has received a permit under the Building Code Act, 1992, to construct a Group F, Division 3, low hazard industrial occupancy building at 11 Toulouse Crescent, Sturgeon Falls, Ontario. The subject building is a newly constructed one storey, non-combustible, manufacturing plant, having approximately a 4000 m² building area for the plant, 690 m² building area for the mechanical office, and 626 m² area for a covered storage area. The subject building has a building height of 10 m, is equipped with a fire alarm system and is not sprinklered. The technical dispute involves the proposal by the Applicant to provide several compensating measures including a fire alarm system monitored by the fire department, and the provision of additional fire extinguishers, in lieu of constructing a standpipe system in the subject building. In accordance with Article and Table of the Building Code, an unsprinklered, one storey, Group F, Division 3 occupancy building, having a building area in excess of 3000 m², is required to be equipped with a standpipe system based on its size and occupancy. Therefore, the dispute is whether the compensating measures offered in lieu of providing a standpipe system provide sufficiency of compliance with Article of Division B of the Building Code. 2. Provisions of the Building Code in Dispute Standpipe Systems Where Required (1) Except as provided in Sentences (4) to (7), a standpipe system shall be installed in every building that, (a) is more than 3 storeys in building height, (b) is more than 14 m high measured between grade and the ceiling of the top storey, or (c) is not more than 14 m high measured between grade and the ceiling of the top storey but has a building area exceeding the area shown in Table for the applicable building height if the building is not sprinklered. (2) A standpipe system shall be installed in every basement of a building that requires a standpipe system above grade. (3) A standpipe system shall be installed in every basement of a building that is regulated by Sentence (2). Table Building Limits without Standpipe Systems Forming Part of Sentence (1) Column 1 Column 2 Column 3 Column 4 Occupancy Classification Building Area, m 2 1 Storey 2 Storeys 3 Storeys A

3 C D F, Division F, Division (4) A standpipe system is not required to be installed in the lowest storey in a building if this storey is a service room that has an area not more than 50 m 2. (5) A standpipe system is not required to be installed in a roof-top enclosure if this enclosure has an area not more than 50 m 2. (6) A standpipe system is not required to be installed in a storage garage conforming to Article provided the building is not more than 15 m high. (7) A standpipe system is not required to be installed in a dwelling unit that, (a) extends not more than 3 storeys above adjacent ground level, (b) is completely cut off from the remainder of the building so that there is no access to the remainder of the building, and (c) has direct access to its interior by means of an exterior doorway located not more than mm above or below adjacent finished ground level. 3. Applicant s Position The Agent for the Applicant submitted that the subject building is being constructed for the purpose of fabricating mine roof support products. The Agent described the facility as consisting of a one storey manufacturing area having a 4000 m² building area with an attached one storey office portion of 690 m² in building area. The Agent submitted that the plant will contain rollforming, shearing, stamping, threading and electrical induction forging equipment and that the production materials will include various grades, sizes and types of steel materials susceptible to corrosion from the adverse effects of water exposure. The Agent explained that a standpipe system was not considered in the design of the building due to the nature of the manufacturing undertaken at the subject plant. The Agent expressed that the Applicant had particular concerns with regards to the potential adverse effects water exposure would have on the various electrical controls, electrical equipment and specialty metals located within the plant, in the event of a fire or accidental water leakage. The Agent expressed concern that water discharged from a standpipe system could come into contact with the electrical equipment, which could then lead to potential injuries to the building occupants, if they were to use the standpipe system s hose that is attached to the 35 mm connections. The Agent advised that all such similar facilities operated by the Applicant in the United States are not equipped with such systems and further, a number of past BCC rulings have accepted compensating measures in lieu of a required standpipe system in industrial buildings with comparable low hazard levels. The Agent submitted that as compensation for the omission of the standpipe and hose system, the Applicant offered the following measures for consideration to achieve sufficiency of compliance with the Code: The subject building complex is comprised of non-combustible construction and contains minimal combustible materials. The fire load for the building area is approximately 0.55 kg/m 2 (1.1 lb/ft²).

4 The building will be equipped with a fire alarm system monitored by the fire department, although not a requirement of the Code for this building. The fire department is located within 3 km of the plant. The building has an 18 m clearance around the perimeter thereby permitting the Fire department full access to the building. The building contains a low occupant load, approximately one person/100 m². More fire extinguishers than the minimum number required by the Building Code will be provided throughout the building and building staff will be trained to properly operate the fire extinguishers in the event of a fire. The fire extinguishers will be inspected once a month by staff and annually by the supplier. The building will be equipped with one fire hydrant located off the southeast corner of the building. In response to questions, the Agent agreed that the Applicant would install a 65 mm hose connection at the entrance of the subject building, which is located within 45 m of a fire hydrant. The Agent concluded that the above mentioned compensating measures offered in lieu of installing a standpipe system would provide sufficiency of compliance with Article of the Building Code. 4. Respondent s Position The Respondent submitted that according to the Code, an unsprinklered Group F, Division 3 building with a building area greater than 4000 m², as is the case in this matter, requires a standpipe system as per Article of the Code. Further, the Respondent submitted that in his opinion the omission of the standpipe system in lieu of the proposed compensating measures is not acceptable and does not comply with the Code. 5. Commission Ruling, BCC Application B It is the Decision of the Building Code Commission that the proposed compensating measures offered in lieu of a standpipe and hose system in a new one storey, 5300 m², Group F, Division 3 major occupancy building, provides sufficiency of compliance with Article of Division B of the Building Code at Jennmar Canada Inc, 11 Toulouse Crescent, Sturgeon Falls, Ontario on condition that: a) The Applicant shall install a system of piping within the building, complete with 65 mm hose connections, for use by the fire department. 6. Reasons i) As a compensating measure, the Applicant has offered to provide more fire extinguishers throughout the building than the minimum number required by the Building Code. The Commission was advised that building staff would be trained to properly operate the fire extinguishers in the event of a fire.

5 ii) iii) iv) The Commission was advised that the fire load for the building area is approximately 0.55 kg/m 2 (1.1 lb/ft².), which is significantly less than the maximum load permitted for F3 occupancies. It is the Commission s opinion that the fire load of the subject building is low. The Commission heard that the Applicant will install a fire alarm system that is monitored by the fire department, even though a fire alarm system is not a requirement of the Building Code for the subject building. The Applicant agreed to install a 65 mm hose connection at the entrance of the subject building, which is located within 45 m of a fire hydrant.

6 Dated at Toronto this 14 th day in the month of January in the year 2010 for application number B Tony Chow, Chair Leslie Morgan Yaman Uzumeri

Module 9: Ontario Building Code Fire Fighting Provisions

Module 9: Ontario Building Code Fire Fighting Provisions Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances Ontario Building Code (OBC) 1. Sprinklers 2. Standpipes 3. Fire Alarms 4. Entrances 1. Sprinklers i) Sprinkler Systems

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 10-20-1256 Application No. B-2010-12 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF with Article Sentences

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-30-928 Application No. 2003-34 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.8.12.(1)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 03-31-929 Application No. 2003-38 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.1.13.7.(1)

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling No. 02-16-871 Application No. 2002-07 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24(1) of the Building Code Act, S.O. 1992, c. 23, as amended. AND IN THE MATTER OF Sentence 3.2.4.20.(2)

More information

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017

Interim Amendments to Ontario s 2012 Building Code Retirement Homes. August 17, 2017 Interim Amendments to Ontario s 2012 Building Code Retirement Homes August 17, 2017 Notice This presentation is intended for general information purposes only. It is not intended as legal or technical

More information

Date of Authorization May 26, 2005 BMEC Authorization BMEC Application # A

Date of Authorization May 26, 2005 BMEC Authorization BMEC Application # A Building Materials Evaluation Commission 777 Bay Street, 2 nd Floor Toronto, Ontario, M5G2E5 Tel: 416: 585. 4234 / Fax: 416. 585. 7531 www.obc.mah.gov.on.ca Date of Authorization May 26, 2005 BMEC Authorization

More information

BUILDING CODE COMMISSION

BUILDING CODE COMMISSION Ruling Numbers 01-14-807 and 01-16-809 Application Numbers 2001-13 and 2001-25 BUILDING CODE COMMISSION IN THE MATTER OF Subsection 24 (1) of the Building Code Act, 1992. AND IN THE MATTER OF Sentence

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS CHAPTER 23.45 LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS 23.45.100 Local Amendments To The International Fire Code, 2000 Edition 23.45.102.1 Construction and Design Provisions

More information

CHAPTER 7 ALTERATIONS LEVEL

CHAPTER 7 ALTERATIONS LEVEL CHAPTER 7 ALTERATIONS LEVEL 2 SECTION 701 GENERAL 701.1 Scope. Level 2 alterations as described in Section 404 shall comply with the requirements of this chapter. Exception: Buildings in which the reconfiguration

More information

The course only requires the latest edition of the following documents: Building Code Compendium, Volume 1 and 2.

The course only requires the latest edition of the following documents: Building Code Compendium, Volume 1 and 2. MODULE 1 INTRODUCTION AND INSTRUCTIONS ADMINISTRATIVE REQUIREMENTS flipchart. When asked by the Facilitator, the spokesperson will explain the group s answer, which forms the basis for class discussion.

More information

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES

FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES FIRE SAFETY UPGRADING CONSIDERATIONS for EXISTING SENIOR CITIZEN LODGES 1. The major objective is to provide an acceptable degree of life safety from fire in existing senior citizen lodges. This document

More information

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION CHAPTER 23.45 Sections LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION 23.45.100 Local amendments to the International Fire Code, 2006 Edition... 2 23.45.102.1 Construction and design provisions...

More information

COUNCIL ORDER No

COUNCIL ORDER No COUNCIL ORDER No. 0015449 BEFORE THE FIRE TECHNICAL COUNCIL On June 22, 2015 IN THE MATTER OF the Safety Codes Act, Revised Statutes of Alberta 2000, Chapter S-1. AND IN THE MATTER OF the Order dated January

More information

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE:

RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: RESIDENTIAL CARE USER GUIDE UPDATES TO MANITOBA BUILDING/FIRE CODE: Manitoba Regulation 221/2015 and Manitoba Regulation 222/2015 DATE: MARCH 17, 2016 1. INTRODUCTION On April 1, 2016, new building and

More information

Understanding and Managing Fire Safety in Housing Accommodation

Understanding and Managing Fire Safety in Housing Accommodation Understanding and Managing Fire Safety in Housing Accommodation Presented at: ONPHA 2015 Annual Conference October 17, 2015 Kevin j. Kelly, P.Eng, Technical Services Office of the Fire Marshal and Emergency

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings

Building Standards Advisory Promoting construction of safe, healthy, habitable buildings Building Standards Advisory Promoting construction of safe, healthy, habitable buildings Saskatchewan Amendments to the National Building Code 2015 In Canada, provincial and territorial governments have

More information

PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015)

PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015) PROPOSED CHANGE TO THE 2015 ONTARIO FIRE CODE (O. Reg. 213/07, as amended current to January 1, 2015) CHANGE NUMBER: CODE REFERENCE: Division B, Sentences 2.13.2.1.(2), 2.13.2.1.(3) DESCRIPTION OF PROPOSED

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE Address: Permit #: Inspector: Date Inspected: Status: Inspector: Date Inspected: Status: A-Approved,

More information

Guidelines for Fire Safety Plans at Construction or Demolition Sites

Guidelines for Fire Safety Plans at Construction or Demolition Sites Guidelines for Fire Safety Plans at Construction or Demolition Sites Sun Peaks Fire Rescue P.O. Box 1000, Sun Peaks, V0E 5N0 Phone 250-578-8985 Fax 250-578-8905 Guidelines for Fire Safety Plans at Construction

More information

150 Elgin - Office Tower and Grant House Renovations

150 Elgin - Office Tower and Grant House Renovations APPLICATION OF THE ONTARIO BUILDING CODE 150 Elgin - Office Tower and Grant House Renovations 150 Elgin Street Ottawa, Ontario Presented to: Mr. Brandon Donnelly Morguard Investments Limited c/o Mr. Harry

More information

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED

PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-03-02-07 Ontario-NBC CODE REFERENCE: Division B / 3.2.4.22. and 3.2.4.23. DESCRIPTION

More information

At the Montréal city council meeting of April 10, 1995, it was enacted that:

At the Montréal city council meeting of April 10, 1995, it was enacted that: CITY OF MONTRÉAL BY-LAW 95-065 BY-LAW AMENDING THE BUILDING BY-LAW (B-1) At the Montréal city council meeting of April 10, 1995, it was enacted that: 1. Article 3 of the Building By-law (R.B.C.M., chapter

More information

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014

2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles

More information

Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code

Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code Glenwood Springs Fire Protection District Amendments to the 2009 International Fire Code 060.090.010 Adoption of International Fire Code; Violations; Conflict A. Pursuant to the power and authority conferred

More information

ENERGY EFFICIENCY AFTER DECEMBER 31, 2016

ENERGY EFFICIENCY AFTER DECEMBER 31, 2016 MODULE 2 Energy Efficiency INTRODUCTION In this module the requirements for energy efficiency in buildings is examined with particular attention to the Supplementary Standard to the OBC, SB-10, Energy

More information

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION

Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Steven Craft, PhD, P.Eng. FIRE SAFETY DURING THE COURSE OF CONSTRUCTION Mid-Rise Workshop, Coast Plaza Inn, Calgary, Feb. 4 th, 2016 Outline Overview of risks Regulations Changes to 2015 NFC for mid-rise

More information

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012 SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015423

More information

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS

SERIES & NO. SMI SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF SPECIAL ELECTRICAL SYSTEMS 1 of 4 SUBJECT: SAFE CONSIDERATIONS FOR AN APPLICATION OF I. PURPOSE To provide basic guidelines for identifying electrical systems required for special installations. II. REFERENCES National Electric

More information

Short Term Accommodations Fire Code Requirements

Short Term Accommodations Fire Code Requirements Short Term Accommodations Fire Code Requirements 1 Foreward The following is a comprehensive reference to Retrofit 9.3 of Division B of the Ontario Fire Code (OFC). Retrofit provisions were developed to

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why

More information

Plan Submittal Checklist

Plan Submittal Checklist City of Aurora Public Works Department HIGH-PILED COMBUSTIBLE STORAGE Plan Submittal Checklist Building Division 15151 E. Alameda Parkway, Ste 2400 Aurora, CO 80012 303-739-7420 Fax: 303-739-7551 Project

More information

OBC INDUSTRIAL CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011

OBC INDUSTRIAL CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011 OBC INDUSTRIAL MAJOR OCCUPANCY CLASSIFICATION OBOA ANNUAL MEETING AND TRAINING SESSIONS LONDON ON OCTOBER 4, 2011 Randal Brown & Associates Ltd. 2011 1 PRESENTERS RANDAL BROWN P.ENG., PE, BDS, FSPFE PRESIDENT

More information

FIRE PREVENTION CODE

FIRE PREVENTION CODE 164.01 Purpose 164.03 Amendments to Fire Prevention Code 164.02 Adoption of Fire Prevention Code 164.04 Board of Appeals 164.01 PURPOSE. The purpose of this chapter is to prescribe regulations governing

More information

Fire Chief/General Manager of Fire and Rescue Services

Fire Chief/General Manager of Fire and Rescue Services ADMINISTRATIVE REPORT Report Date: May 27, 2014 Contact: Rick Cheung Contact No.: 604.873.7028 RTS No.: 10545 VanRIMS No.: 08-2000-20 Meeting Date: July 8, 2014 TO: FROM: SUBJECT: Vancouver City Council

More information

(House Bill 849) Public Safety Rental Dwelling Units Carbon Monoxide Alarms

(House Bill 849) Public Safety Rental Dwelling Units Carbon Monoxide Alarms Chapter 175 (House Bill 849) AN ACT concerning Public Safety Rental Dwelling Units Carbon Monoxide Alarms FOR the purpose of altering certain requirements relating to carbon monoxide alarms as the requirements

More information

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)

AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with

More information

BCBC 2012 CHANGES TO PART 3

BCBC 2012 CHANGES TO PART 3 BCBC 2012 CHANGES TO PART 3 Focus on changes that will have an practical effect. Basic concepts reviewed details to be confirmed. Material from Part 3 and related material from Part 9 Generally a harmonization

More information

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content

2018 IFC Update. Based on the 2018 International Fire Code, (IFC ) Goal. Objectives. Content Based on the 2018 International Fire Code, (IFC ) The International Fire Code (IFC ), establishes minimum regulations for fire safety. This handout will identify important changes in the IFC from 2015

More information

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August

Secondary Suites. Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August Secondary Suites Guidelines for the construction of Accessory Secondary Suites in the City of Abbotsford August 2015 PLANNING & DEVELOPMENT SERVICES Building Permits & Licences 1st Floor, 32315 South Fraser

More information

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification

Public Input No. 4-NFPA [ Section No. 4.2 ] Statement of Problem and Substantiation for Public Input. Submitter Information Verification Public Input No. 4-NFPA 214-2013 [ Section No. 4.2 ] 4.2 * Fire Risk Analysis. A fire risk analysis shall be conducted. The following are some of the factors that shall be considered in determining the

More information

Large Family Daycare Guideline

Large Family Daycare Guideline Moreno Valley Fire Department Fire Prevention Bureau Large Family Daycare Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: April 10, 2017 Large Family Daycare Guideline Purpose

More information

Western Michigan University Facilities Management Engineering Division

Western Michigan University Facilities Management Engineering Division Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General

More information

CHAPTER II BUILDINGS PART 1 BUILDING CODE PART 2 FLOOD PLAIN REGULATIONS. See Ordinance 3251 on file in the office of the Manager.

CHAPTER II BUILDINGS PART 1 BUILDING CODE PART 2 FLOOD PLAIN REGULATIONS. See Ordinance 3251 on file in the office of the Manager. CHAPTER II BUILDINGS PART 1 BUILDING CODE 301 Adoption of Building Code 302 Amendments Made in BOCA BASIC BUILDING CODE PART 2 FLOOD PLAIN REGULATIONS See Ordinance 3251 on file in the office of the Manager.

More information

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property City of Chilliwack Bylaw No. 3464 A bylaw to regulate fire prevention and the protection of life and property NOW THEREFORE the Council of the City of Chilliwack in open meeting assembled enacts as follows:

More information

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection

More information

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project

More information

DIVISION C ADMINISTRATIVE PROVISIONS

DIVISION C ADMINISTRATIVE PROVISIONS For what s new, check out www.regulationsandstatutes.com 374 DIVISION C ADMINISTRATIVE PROVISIONS SECTION 1.1 GENERAL Subsection 1.1.1. Chief Fire Official Appointment by Fire Marshal 1.1.1.1. (1) The

More information

Town of Cochrane Policy

Town of Cochrane Policy Town of Cochrane Policy Policy No.: Policy Title: Approval Date: Revision Date: Department: 1401-01 Fire Department Lock Box Program January 22, 1996 September 24, 2007 Community and Protective Services

More information

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS TEN STEP PROCESS PREPARING FIRE SAFETY PLANS STEP 1 CONDUCT FIRE SAFETY AUDIT IDENTIFY BUILDING FEATURES AND HUMAN RESOURCES. STEP 2 APPOINTMENT OF SUPERVISORY STAFF IDENTIFY TRAINED SUPERVISORY STAFF

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:. 2012 B.C. Building Code Checklist (Division B Part 3) This checklist is provided as a reference only. The submission of this checklist with a Building Permit application should not be considered as a substitute

More information

OAA Conference ,

OAA Conference , OAA Conference 2013 OUR PROFILE OVERVIEW Amongst the world s leaders in professional services Listed on the Toronto Stock Exchange (GNV) $1.8 bn pro forma 2011 revenues 15,000 +300 35 EVERY CONTINENT EMPLOYEES

More information

COMPLIANCE ALTERNATIVES

COMPLIANCE ALTERNATIVES CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES

FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES FIRE ALARM AUDIBILITY IN EXISTING RESIDENTIAL OCCUPANCIES Office of the Fire Marshal and Emergency Management Preface This guideline updates TG-02-1998 published in June 1998. Portions of the guideline

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

FIRE FIGHTER II APPLICATION PENNSYLVANIA VOLUNTARY FIRE SERVICE CERTIFICATION PROGRAM NFPA Edition

FIRE FIGHTER II APPLICATION PENNSYLVANIA VOLUNTARY FIRE SERVICE CERTIFICATION PROGRAM NFPA Edition FIRE FIGHTER II APPLICATION PENNSYLVANIA VOLUNTARY FIRE SERVICE CERTIFICATION PROGRAM NFPA 1001 2008 Edition SECTION I Last Name First Name M.I. SSN (last four digits required) Street Address City State

More information

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES

FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES Established 1949 FIRE PREVENTION OFFICE Placer Hills Fire Protection District NEW PROJECT GUIDELINES The following are guidelines for new development. Any submitted plans must comply with these guidelines,

More information

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951) Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Guideline Title: Residentially Based Care Facilities Group

More information

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT

TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT TRI-LAKES MONUMENT FIRE PROTECTION DISTRICT LOCAL AMENDMENTS INTERNATIONAL FIRE CODE 2009 December 5, 2012 1 Chapter 1 Administration Chapter 5 Fire Service Features Chapter 9 Fire Protection Systems Chapter

More information

2012 B.C. Building Code Compliance Review (Division B Part 3)

2012 B.C. Building Code Compliance Review (Division B Part 3) Planning and Building Department 2012 B.C. Building Code Compliance Review PROJECT NAME:.. CIVIC ADDRESS:...... PERMIT APPLICATION NO.:. DATE:... I,, have: 1. reviewed the design, plans and supporting

More information

Fire Suppression Introduction Contact Information

Fire Suppression Introduction Contact Information Contact Information Jeffrey Mayers Fire Safety Engineering Manager Georgia State Fire Marshal s Office 404-617-8515 E-mail: jmayers@sfm.ga.gov 1 Goal of This Seminar: Hierarchy of Codes List reference

More information

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS Part 3 BUILDING CODE MYTHS & INTERPRETATIONS November 18, 2016 Frank Durante, RBO Building Inspector District of Mission Phone 604 820 3729 Wendy Morrison, AScT, BCQ GHL CONSULTANTS LTD Fire Science and

More information

Community Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007

Community Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007 STAFF REPORT ACTION REQUIRED Community Festival Permit Application - Cypriot Community of Toronto Inc. - Cultural and Wine Festival June 23 and 24, 2007 Date: April 10, 2007 To: From: Wards: North York

More information

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT

PINETOP FIRE DEPARTMENT TIMBER MESA FIRE AND MEDICAL DISTRICT Amendments for 2015 IFC CHAPTER 1 SCOPE AND ADMINISTRATION Section 101.2.1 Appendices. All appendices to be adopted Section 113.2 Schedule of permit fees. Is AMENDED to read: A fee for each permit shall

More information

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property

City of Chilliwack. Bylaw No A bylaw to regulate fire prevention and the protection of life and property City of Chilliwack Bylaw No. 3464 A bylaw to regulate fire prevention and the protection of life and property NOW THEREFORE the Council of the City of Chilliwack in open meeting assembled enacts as follows:

More information

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS

Pismo Beach, CA Municipal Code. Chapter 8.08 FIRE PREVENTION REGULATIONS Pismo Beach, CA Municipal Code 8.08.010 Amendments; California Fire Code. Chapter 8.08 FIRE PREVENTION REGULATIONS The California Fire Code adopted in Section 8.04.010 is modified, amended and/or supplemented

More information

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:

More information

150 Eighth Street Zoning By-law Amendment Application Preliminary Report

150 Eighth Street Zoning By-law Amendment Application Preliminary Report REPORT FOR ACTION 150 Eighth Street Zoning By-law Amendment Application Preliminary Report Date: March 27, 2019 To: Etobicoke York Community Council From: Director, Community Planning, Etobicoke York District

More information

STAFF REPORT ACTION REQUIRED

STAFF REPORT ACTION REQUIRED STAFF REPORT ACTION REQUIRED Residential Demolition Application 595 Vaughan Road Date: December 15, 2011 To: From: Wards: Reference Numbers: North York Community Council Director and Deputy Chief Building

More information

Fire Safety Plan Information. For Construction and Demolition Sites

Fire Safety Plan Information. For Construction and Demolition Sites Fire Safety Plan Information For Construction and Demolition Sites FIRE CODE INTERPRETATION November 2009 FCI-09-03 Page 1 of 8 ISSUE: FIRE SAFETY PLAN Construction and Demolition Sites Safety provisions

More information

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour.

4/13/2015. Everything a firefighter wants to tell a design professional or building code official, in one hour. Everything a firefighter wants to tell a design professional or building code official, in one hour. 1 2 3 1 4 The job of the fire department is to put the wet stuff on the red stuff. 5 Job #1. of the

More information

Winnipeg Fire Department Fire Prevention Branch

Winnipeg Fire Department Fire Prevention Branch Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of

More information

For additional information regarding R-3.1 residential care facilities please contact (951)

For additional information regarding R-3.1 residential care facilities please contact (951) Riverside County Fire Department Fire/Life Safety Inspection Division Riverside Office: 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4823 Fax (951) 955-4886 Palm Desert Office: 77-933 Las

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

AUTOMATIC FIRE SPRINKLER SYSTEMS

AUTOMATIC FIRE SPRINKLER SYSTEMS MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system

More information

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE:

Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: Phase Two Change Proposal for the Next Edition of the Building Code: 2-CC-B-09-32-03 POTENTIAL CHANGE TO ONTARIO S BUILDING CODE: SUMMER AND FALL 2017 CONSULTATION Ministry of Municipal Affairs PROPOSED

More information

Tire Storage. Michigan Fire Inspectors Society Fall Conference

Tire Storage. Michigan Fire Inspectors Society Fall Conference Tire Storage Michigan Fire Inspectors Society Fall Conference September 15, 2016 This material, including the illustrations, represent the opinion of the author and instructor. This material is not designed,

More information

TOM BURNS, PLANNING DIRECTOR

TOM BURNS, PLANNING DIRECTOR ~~ 0 173 COUNTY OF SANTA CRUZ August 4,2005 PLANNING DEPARTMENT 701 OCEAN STREET, qth FLOOR, SANTA CRUZ, CA 95060 (831) 454-2580 FAX: (831) 454-2131 TDD: (831) 454-2123 TOM BURNS, PLANNING DIRECTOR Agenda:

More information

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES

WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES 1 WORKSHEET 2-1 THE MANITOBA RESIDENTIAL OCCUPANCY FIRE RISK INDEX FIRE SAFETY PARAMETER VALUES TABLE 2.1 CONSTRUCTION OF STRUCTURAL MEMBERS AND FLOOR AND ROOF (1) ASSEMBLIES (Applies to each fire zone)

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 SCOPE OF WORK A. Design, installation and testing shall be in accordance with NFPA 13 except for specified exceptions. B. The demolition

More information

Fire Protection Coffee Break Training August 2016

Fire Protection Coffee Break Training August 2016 Fire Protection Coffee Break Training August 2016 Agenda Introduction - Phelan NFPA 13 versus NFPA 13R systems for Residential Occupancies - Homa NFPA 72 Record of Completion - Homa Questions and Answers

More information

Residential Based Care Facility Guidelines

Residential Based Care Facility Guidelines Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities

More information

Town of Cicero Local Code Amendments

Town of Cicero Local Code Amendments Town of Cicero Local Code Amendments 2009 International Residential Code Local Amendments: DELETE Table R302.1 (Exterior Walls), see Attachment A. DELETE Exception for Subsection R313.2 (One and Two-Family

More information

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION CHAPTER 23.45 LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2012 EDITION Sections 23.45.100... Local amendments to the International Fire Code, 2012 Edition.... 2 23.45.105.4.2 Information on construction

More information

THE CORPORATION OF THE TOWNSHIP OF MUSKOKA LAKES BY-LAW NUMBER

THE CORPORATION OF THE TOWNSHIP OF MUSKOKA LAKES BY-LAW NUMBER THE CORPORATION OF THE TOWNSHIP OF MUSKOKA LAKES BY-LAW NUMBER 2018 16 Being a by-law to regulate the setting of fires, prevent the spreading of fires, and to establish a fire permit system for The Township

More information

Sprinkler Permit Applications

Sprinkler Permit Applications REQUIREMENTS FOR NFPA 13 SYSTEM Building Inspections Sprinkler Permit Applications A complete application for a Sprinkler Permit will comply with the requirements of Chapter 8 of NFPA 13. Hydraulic calculations

More information

Fire Protection Coffee Break Training May 2016

Fire Protection Coffee Break Training May 2016 Fire Protection Coffee Break Training May 2016 Introduction High-Rise Requirements Questions and Answers Agenda Overview Site Fire Access Aerial Access Power/Back-up Power Elevators and Access Sprinklers

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

ERRATA TO THE 2000 INTERNATIONAL FIRE CODE. Fourth Printing, January 2002 Updated March 29, 2002

ERRATA TO THE 2000 INTERNATIONAL FIRE CODE. Fourth Printing, January 2002 Updated March 29, 2002 ERRATA TO THE 2000 INTERNATIONAL FIRE CODE Fourth Printing, January 2002 Updated March 29, 2002 Table 2306.2 General Fire Protection and Life Safety Requirements In column 2 (Size of High Piled Storage

More information

PLAN REVIEW CHECKLIST

PLAN REVIEW CHECKLIST PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

FORM MUST BE SIGNED AND RETURNED FOR VENDOR PARTICIPATION

FORM MUST BE SIGNED AND RETURNED FOR VENDOR PARTICIPATION Fire Prevention Bureau 95 Culver Street, Simcoe, Ontario N3Y 2V5 519-426-4115 Fax: 519-426-4140 Administration Headquarters Norfolk County Fire and Rescue Services Approval Form Vendor Fire Safety Requirements

More information

VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California (707)

VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California (707) VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California 95688 (707) 447-2252 Requirements for new construction within the boundaries of the Vacaville Fire Protection District include,

More information

FIRE PROTECTION SYSTEMS

FIRE PROTECTION SYSTEMS CHAPTER 9 FIRE PROTECTION SYSTEMS > SECTION 901 GENERAL 901.1 Scope. The provisions of this chapter shall specify where fire protection systems are required and shall apply to the design, installation,

More information

PERFORMANCE COMPLIANCE METHODS

PERFORMANCE COMPLIANCE METHODS CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter ((shall)) apply to the alteration, repair, addition and change of occupancy of existing structures,

More information

Request for Decision. Recommendation. Presented: Monday, Jul 07, Report Date Friday, Jun 20, Type: Public Hearings

Request for Decision. Recommendation. Presented: Monday, Jul 07, Report Date Friday, Jun 20, Type: Public Hearings Presented To: Planning Committee Request for Decision Application for rezoning in order to permit a place of worship on a vacant lot zoned for C1, Local Commercial uses, Cam Street, Sudbury Sitiri Investments

More information