442 Chapter 16. Figure 16-5 Gas leak detection

Size: px
Start display at page:

Download "442 Chapter 16. Figure 16-5 Gas leak detection"

Transcription

1 BRORANE BRORANEBRORANEBRORANEBRORANEBRORANEBRORANEBRORANE 442 Chapter 16 Tur n e r BRORANE FUEL EBRORANEBRORANEBRORANEBRORANEBRORANE Figure 16-5 Gas leak detection is easy. This sensitive halide detector pinpoints Freon leaks in a short time. Used on all noncombustible refrigerant (Freon) leaks, the flame changes color when the exact location of the leak is determined. (Courtesy Tumer Corporation.) 8. Open the suction valve and suction gage hose to purge the refrigerant from the system. On refrigerant Freon-12 systems where pressure is 50 psi or less, and Freon-22 systems where pressure is 90 psi or less, the expansion valve will open, allowing piping from the expansion valve to the suction service valve to purge also. If pressure is higher, it is necessary to purge the low side through the suction service valve. This can be accomplished by removing the suction-valve gage port plug and carefully opening the suction valve slightly. When the gage reads 0 pounds of pressure, close the suction service and suction-gage valves. 9. Repeat this leak check until all leaks are found and repaired. 10. When repaired, close the suction valve and disconnect the charging manifold from the unit. 11. Back-seat (open) the suction and discharge service valves. Electronic Leak Detector Although leak testing with a halide torch is considered satisfactory in most instances, a more reliable test is made by means of the electronic-type tester. This easy-to-use instrument reduces the guesswork in leak testing because it is more sensitive, faster responding, and capable of detecting a leak even though the surrounding air may be contaminated. The electronic detector contains an internal pump, which draws air and leaking halogen tracer gas (halogen gases are chlorine, bromine, fluorine, and iodine, or any of their compounds) through a probe and hose as the probe is passed over leaking joints, gaskets, welds, and so on. The air/gas mixture is drawn between two electrodes in the control unit the ion emitter and collector.

2 Maintenance 443 The leak detector contains an automatic balance circuit so that a constant or slowly changing contamination in the atmosphere will not cause the lamp to flash. Refrigerant gas will cause the lamp to flash only when there is an abrupt increase of gas going into the tip of the probe (such as when the probe tip passes near a leak). To check for a leak with the electronic detector, proceed as follows: 1. Plug the test detector into a 120-volt AC outlet. 2. Turn the sensitivity knob to the right and allow a 1-minute warm-up. 3. Check the operation by turning the sensitivity knob quickly from one position to another, which should light the probe lamp. 4. Probe for leaks, starting with maximum sensitivity. 5. If the probe lamp lights twice for each leak, reduce the sensitivity. 6. Recheck the suspected leaks for confirmation. After replacing a component in the refrigerating system, always test all joints for leaks before recharging. The extra time it takes is negligible compared to the loss of a charge caused by a faulty connection. Be sure to clean the excess soldering flux (if used) from the new joints before testing, since the flux could seal off pinhole leaks that would show up later. For new refrigerants (such as R-134a used in car air-conditioning units), use an electronic leak detector for more accurate results than with soap and water or the flame test. Evacuating the System When necessary to remove the entire refrigerant charge from the system (as in the case when an exchange of compressor or any other component of the condensing unit is necessary), proceed as follows: 1. Front-seat (close) the suction and discharge service valves. 2. Attach the charging manifold suction hose to the suction valve. 3. Connect the vacuum pump to the center port on the charging manifold. 4. Start the vacuum pump and open the suction valve. Adjust the test manifold valves so that the vacuum pump is open to the suction valve. Evacuate the system to obtain the highest vacuum possible with the vacuum pump used.

3 444 Chapter During the early stage of evacuation, it may be desired to shut off the pump at least once to see if there is a rapid loss of vacuum, indicating the presence of leaks in the system. 6. Time required for proper evacuation depends on the system and the vacuum pump. It is recommended that the vacuum pump be allowed to run for two hours or even overnight after maximum vacuum is obtained to evacuate the system. 7. Close the charging manifold valve to the vacuum pump. Stop the pump. Note the reading on the vacuum gage and allow the system to stand for 1 hour. If the vacuum has not decreased, the system is tight. 8. When the unit is checked and repaired, close the suction valve and disconnect the charging manifold from the valve. 9. To put the system in operation, back-seat (open) the suction and discharge service valves. 10. Be sure you do not allow the refrigerant to escape into the atmosphere. This is forbidden by law and strictly enforced by the Environmental Protection Agency (EPA). Checking Compressor Valves To check the compressor valves, proceed as follows: 1. Front-seat (close) the suction service valve. 2. Start the compressor and operate the unit until the compound gage shows 15 inches of vacuum. 3. Stop the compressor. 4. Back-seat (open) the suction service valve slightly to permit the vapor in the suction line to bring the gage reading back to zero. Close the valve. 5. If the pressure on the gage starts to increase, a discharge valve leak is indicated and the compressor should be replaced. 6. If the compressor will not pull at least 15 inches of vacuum on the compound gage, a suction-valve leak is indicated and the compressor should be replaced. Troubleshooting Guide In addition to the foregoing servicing details, shows the most common operating faults that can occur in residential yearround air conditioning.

4 Maintenance 445 Air-Conditioning Troubleshooting Guide Drafts. Poor air distributon. Readjust air grilles and outlets. Room temperature too low. Check thermostat setting, return-air damper, and low-pressure cutout. Shortage of air supply at grilles. Short on cooling capacity. Incorrect fan speed and incorrect pressure drop across fan. Incorrect pressure drop across evaporator coil. Excessive air turbulence at fan discharge. Improper adjustment of splitters or dampers. High duct resistance. Low fan speed. Wrong rotation of fan. Dirty filters. Check for correct change in wet-bulb temperature between entering and leaving air to cooling coil. Check refrigerating unit for capacity. Check pressure drop across the fan with draft gage, and correct fan speed. Check pressure drop across coil with draft gage. Check filters, baffles, air supply, and coil fins for obstructions. Install turning vanes in short radius elbows. Readjust dampers and check air. Check duct sizes and elbows. Inspect duct for internal obstructions. Check the drive belt for slippage. Check fan motor static control. If a multispeed fan is employed, check pulley sizes of drive. Check rotation with arrow marking on fan housing, if supplied, or by throat opening in fan housing. Change rotation by reversing motor direction. Change if throwaway type.

5 446 Chapter 16 Excessive air. Motor drive pulley too large. Check air and change pulley to correct speed. Improper damper Readjust dampers. adjustments. Lower resistance than estimated. Lower the fan speed. Air noise. Scraping noise in plenum. Squeaking and rumble. Rattles. Sharp obstruction in air stream. Small slits or openings in duct or plenum. Fan speed too high in relation to noise level and system. Obstructions in outlets. Air velocity too high at outlets. Fan hitting the fan housing. Loose belts. Dirt in bearings. Bearings sticking. Loose filter compartment. Electrical BX cable loose. Thermal-bulb tube vibrating. Housing touching pipe. Loose screws in housing. Streamline internal surfaces of the ducts. Smooth out rough edges. Close all holes or openings. Decrease fan speed, if possible, or install sound-absorption material in ducts. (Sound insulation should be fireproof material.) Remove obstruction, if possible, without throwing system out of balance. If removal is not possible, try changing location of angle. Rebalance air in system. Adjust fan to turn free on all sides. Tighten belts. Clean the bearings. Remove and replace. Examine shaft. Tighten. Fasten securely. Clear vibrating point of tube. Insulate metal-to-metal location. Tighten.

6 Maintenance 447 Water leaking or dripping from unit. Vibration. Hissing noise at expansion valve. Improper drain piping. Dirt in condensate pan and screen. Loose pipe fittings and valves. Condensate overshooting drain pan. Loose motor mounting. Improper weight distribution on hangers or feet. Belt too tight, causing whip in shaft. Pulleys loose or out of line. Fan shaft sprung. Shaft bearings worn. Fans out of balance or loose on shaft. No canvas breaker strips to duct connection. Shortage of refrigerant. Clogged strainer. Pressure drop in liquid. Drain should pitch 1 / 4 to 1 in/ft. Drain should be properly trapped. Condensate pan must pitch water toward the drain. Remove screen, clean pan, and flush with water. Tighten all connections and packing glands of valves. Air velocity too high through coils. Check resistance pressure and fan speed to determine if they are in accordance with design conditions. Tighten motor mounting bolts. Level unit on all sides. Adjust belt tension. Align pulleys and tighten pulley set screws. Remove and replace with new shaft. Replace with new bearings. Tighten if shaft is not worn from loose play. Replace if badly damaged. Install breaker strips. Add refrigerant to proper liquid level. Remove and clean screen. Check head pressure.

7 448 Chapter 16 Heating of liquid Subcooling necessary. line from outside surroundings. No liquid at top expansion valve in bank of coils. Install gas head on liquid line about 2 feet higher than top valve. Partial frosting and sweating of coil. Failure to cool and no frost. Failure to cool and complete frosting. Too cool. Shortage of refrigerant. Restricted or clogged liquid line. Too much outside air being taken on one side of coil. Expansion valve too small or improperly adjusted. Solenoid valve sticking. Solenoid valve clogged. Solenoid coil burned out. Condensing unit shut off. Liquid line valve closed. Thermostat faulty. Fan not running. Insufficient air. Air outlets closed. Coil clogged with dirt. Improper setting of room thermostat, or thermostat faulty. Wrong outlet distribution. Add refrigerant. Pump down system and clean out. Change mixing chamber for better distribution. Check valve capacity and superheat adjustment. Remove and clean. Remove and clean. Replace coil. Start compressor. Open valve. Repair or replace. Start fan. Dirty filters. Dampers stuck shut. Correct air distribution. Remove coil and clean thoroughly. Correct thermostat. Balance air distribution correctly.

8 Maintenance 449 Frequent Clogged liquid line. Clean out. cycling of unit. Insufficient Add refrigerant. refrigerant. Improper setting of Adjust valves properly. expansion valves. Fan stopped Check fan circuit and start fan. running. Thermostat Reset differential. differential setting too close. Thermostat in direct Relocate thermostat. line of air-throw from grille. Evaporator coil frosted. Run fan with compressor shut off to defrost coil. Motor overheats. Motor fails to run. Failure of system to heat properly. Lack of oil or improper oil. Wrong voltage. Overload. Belts too tight. Ambient room temperature high. Improper fuse. Thermal overload too small. Improper wiring. Heating coils not properly trapped. Air trapped in coils. Heating coils improper distance above boiler. Oil bearings with recommended oil. Check with electrician and power company. Reduce fan speed, if possible, without impairing air quantity. Replace with larger motor if necessary. Adjust belt tension. Check motor rating with manufacturer of motor. Check fuses for proper sizing. Check with motor data sheet. Check with wiring diagram. Separate trap should be provided for each coil. Coils should be properly vented. Distance above boiler line should be at least 18 inches.

9 450 Chapter 16 Supply or return lines too small. Install proper size piping for coils. Resistance too great Install proper size piping. in system. Too much outside air being introduced. Use as much recirculated air as possible without impairing the calculated ratio of outside recirculated air. Heating coils not leveled. Level coils to obtain proper coil drainage. Condensate in coils. Traps may contain scale and sediment preventing operation. Failure of system to humidify. Water supply failure. Too much outside air. Control valve on humidifier supply closed or clogged. Capacity of humidifier insufficient. Humidistat not functioning. Air passing directly over and through humidistat. Water valve closed. Strainer plugged. Nozzle clogged. Close down on outside damper. Remove and clean. Install larger or additional humidifier and supply line. Inspect humidistat for adjustment and dirt, especially the hair suspension. Place baffle on upstream side of humidistat to break air around instrument. Summary A malfunctioning system may be caused by one portion of the system or a combination of several portions. It is necessary and advisable to check the more obvious causes first. Each part of the system has a certain function to perform, and, if any individual part does not function properly and efficiently, the performance of the entire airconditioning system will be affected. To simplify servicing a system, the service technician should remember that the refrigerant, under proper operating conditions,

10 Maintenance 451 travels through the system in one specific direction. The service technician can trace the path of refrigerant through any system, beginning at the compressor. Pressure, temperature, volume, and heat-absorbing characteristics of the refrigerant in the various parts of the system are essential in analyzing air-conditioning problems. When a refrigerant piping system is completed, the system should be checked very carefully for leaks. The most effective way of finding a leak in a Freon system is with a halide-leak detector. Testing with soap and water or with oil at the joints will locate only the larger leaks. To test for noncondensables, run the condenser fan for 10 minutes with the compressor off. Measure the head pressure. Add 10 For 5.6 C to the ambient air temperature. Convert this temperature to pressure. It should equal the head pressure. If the head pressure is greater than this, there is a probability of a noncondensable gas in the system. Review Questions 1. What is the general practice in the diagnosis of a malfunctioning air-conditioning system? 2. When do you use a systematic procedure in checking to determine the source of trouble in an inoperative system? 3. Describe head-pressure checking methods. 4. What may the reason be for a low suction pressure? 5. What are the usual causes of low back pressure? 6. What is the method used in checking refrigerant charge? 7. Describe the types of compressor gages and give pressure ranges. 8. What is the advantage in using a combination gage set? 9. Describe the method of adding and removing refrigerant. 10. What is meant by system pump-down and how is it accomplished? 11. Why is it necessary to leak-test a refrigeration system prior to operation? 12. Describe the method of evacuating a refrigeration system. 13. What is the procedure used in checking compression valves? 14. What does backseat mean? 15. List three noncondensables.

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11

SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING. Bard Manufacturing Company, Inc. Bryan, Ohio Manual Page 1 of 11 SERVICING PROCEDURE R-410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company, Inc. Bryan, Ohio 43506 Since 1914...Moving ahead, just as planned. Manual No.: 2100-479 Supersedes: NEW File: Volume

More information

Trouble Shooting Guide FAA, 3-phase (D3631)

Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com

More information

Trouble Shooting Guide RAA, 1-phase (D3627)

Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

Trouble Shooting Guide PWA, 3-phase (D10571)

Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire

More information

Trouble Shooting Guide PAA, 1-phase (D3731)

Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

A/C-HEATER SYSTEM - MANUAL

A/C-HEATER SYSTEM - MANUAL A/C-HEATER SYSTEM - MANUAL 1986 Isuzu Trooper II 1986 A/C-HEATER SYSTEM Isuzu A/C-Heater Systems - Manual P UP, Trooper II * PLEASE READ THIS FIRST * CAUTION: When discharging air conditioning system,

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

CENTRAL, SPLIT SYSTEM REFRIGERATED AIR-CONDITIONING INSPECTION INTERIOR

CENTRAL, SPLIT SYSTEM REFRIGERATED AIR-CONDITIONING INSPECTION INTERIOR Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. CENTRAL, SPLIT SYSTEM REFRIGERATED AIR-CONDITIONING INSPECTION

More information

Room Air Conditioner Service and Parts Manual

Room Air Conditioner Service and Parts Manual Cool Dry Temp Mode Room Air Conditioner Service and Parts Manual F Fan Speed hr Timer 0n 0ff Money Saver Fan Only Auto Swing Power CP06 CP08 93011401_01 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News, VA 23606 Tel: 757 873 6800 Fax: 757 873 3632 Website: www.ebacusa.com UNPACKING

More information

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL EBAC MODEL K100 DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 700 Thimble Shoals Boulevard Newport News VA 23606-2575 Telephone (757) 873-6800 Fax (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL WM150 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL WM150 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the WM150 is a rugged, industrial unit, which utilizes an

More information

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING

SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING SECTION 7 AIR CONDITIONING (COOLING) UNIT 41 TROUBLESHOOTING UNIT OBJECTIVES After studying this unit, the reader should be able to Select the correct instruments for checking an air conditioning unit

More information

Beverage Air IMPORTANT

Beverage Air IMPORTANT Beverage Air IMPORTANT INFORMATION FOR CT96 MODEL This cooler has passed the QUALITY CONTROL INSPECTION And meets the high standards for Beverage-Air Refrigeration products IMPORTANT PLEASE RETAIN FOR

More information

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions

UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions UNDERCOUNTER LABORATORY REFRIGERATORS and FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill

More information

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5

Table of Contents. Specifications... page 2. Installation... page 3. Customizing... page 4. Reversing door swing... page 5 Introduction The Scotsman Compact Refrigerator is a unique product, capable of being built into a cabinet because of its front vented, forced-air cooling system. It s also designed to be a companion to

More information

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD425 (1018110) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632

More information

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS Before using the heater, read and understand all instructions and follow them carefully. The manufacturer is not responsible for damages to goods

More information

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8)

Table of Contents. Service Procedures. Service Procedures. Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Table of Contents Refrigeration Cycle Service Procedures Measuring Superheat (4) Measuring Subcooling (5) Airflow Calculation (6-8) Solving Problems Identifying Low System Charge (9-11) Identifying High

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features.

Operation Manual SCT14B and SCT18B. Inspection. 3 General Description. 3 General Requirements. 3 Standard Features. Spot Cooling Systems, Inc. 120 Century Drive Suite 00 Carrollton, TX 7006 00-6-776 Operation Manual SCT1B and SCT1B Warning! Improper installation, adjustment, alteration, service, or maintenance can cause

More information

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD30 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products, Inc. 700 Thimble Shoals Blvd, Suite 109 Newport News, VA. 23606-2575 Tel: (757) 873 6800 Fax: (757) 873 3632 Website www.ebacusa.com

More information

2004 HVAC. Heating, Ventilation and Air Conditioning - Hummer H2. Fastener Tightening Specifications Specification Application

2004 HVAC. Heating, Ventilation and Air Conditioning - Hummer H2. Fastener Tightening Specifications Specification Application SPECIFICATIONS 2004 HVAC Heating, Ventilation and Air Conditioning - Hummer H2 FASTENER TIGHTENING SPECIFICATIONS Fastener Tightening Specifications Specification Application Metric English A/C Accumulator

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH TXV Horizontal Slab Coils WLSH These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

USER'S MANUAL PGE Single Package Rooftop

USER'S MANUAL PGE Single Package Rooftop USER'S MANUAL PGE Single Package Rooftop Gas Heating/Electric Cooling Units Sizes 036-150 3 to 12-1/2 Tons NOTE TO INSTALLER: This manual should be left with the equipment owner. WARNING: If the information

More information

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 8 Product Support Questions: Contact Ebac USA at (757) 873 6800 Sales Inquiries: Contact Sylvane at (800) 934-9194 or visit

More information

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL CD60 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL CD60 OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the CD60 dehumidifier is a rugged, industrial unit which utilizes

More information

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC.

GENERAL 2004 HVAC SYSTEMS. Manual HVAC System - Sorento SPECIFICATIONS. Fig. 1: Air Conditioner Specifications Courtesy of KIA MOTORS AMERICA, INC. Fig. 2: Blower & Evaporator Unit Specifications 2004 HVAC SYSTEMS Manual HVAC System - Sorento GENERAL SPECIFICATIONS AIR CONDITIONER Fig. 1: Air Conditioner Specifications BLOWER AND EVAPORATOR UNIT HEATER

More information

TROUBLESHOOTING GENERAL TROUBLESHOOTING PROBLEM PROBABLE CAUSE CORRECTIVE ACTION

TROUBLESHOOTING GENERAL TROUBLESHOOTING PROBLEM PROBABLE CAUSE CORRECTIVE ACTION GENERAL TROUBLESHOOTING Compressor Conditioning system OFF Turn ON conditioning system will not run No electrical power Check fuses Wrong voltage to applied to unit Compressor internal overload tripped

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

HEATING AND VENTILATION

HEATING AND VENTILATION SECTION 14-102.04 14-102.04/ 1 2007OC19 DESCRIPTION The heating, ventilation and air conditioning (HVAC) system is designed to optimize passenger comfort. The system regulates interior vehicle atmosphere,

More information

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL KOMPACT INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL KOMPACT OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the Kompact is a rugged, industrial unit, which utilizes

More information

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD TXV Horizontal Duct s EHD These instructions must be read and understood completely before attempting installation. It is important that the Blower and Duct System be properly sized to allow the system

More information

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions GENERAL LABORATORY REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL HOT WATER HEATING BOILERS DOMESTIC WATER HEATERS 150,000-300,000 Btu/hr MODELS EB-EWU-02 IMPORTANT INSTALLER - AFFIX INSTALLATION MANUAL ADJACENT TO THE BOILER CONSUMER - RETAIN

More information

Installation, Operation, and Maintenance Information

Installation, Operation, and Maintenance Information Installation, Operation, and Maintenance Information Low Velocity Unit Coolers Bulletin No. IOM 110.3 Table of Contents Inspection... 2 Installation... 2 4 General... 2 Location... 2 Drain Line... 3 Refrigerant

More information

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL BD-150 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL BD-150 (1025000) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL BD-150 OWNERS MANUAL Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the BD-150 dehumidifier is a super high capacity

More information

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual Standard Evaporative Cooler CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check

More information

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL NEPTUNE INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL NEPTUNE OWNERS MANUAL Page 1 of 9 INTRODUCTION Designed for a wide range of applications, the Neptune dehumidifier is a super high capacity industrial

More information

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL

50BY, BL. Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL 50BY, BL Ÿà Õ µ µ Èß ËÕߪ Õ» å Single-Package Cooling Units 50BY, BL 50BY, BL Contents Safety Considerations... 4 Danger... 4 Warning... 4 Installation... 5-6 Air Duct Connection... 6 Electrical Wiring...

More information

User s Information Manual

User s Information Manual 48AJ,AK,AW,AY020-060 Single-Package Rooftop Gas Heating Units with COMFORTLINK Controls and Scroll Compressors User s Information Manual NOTE TO INSTALLER This manual should be left with the equipment

More information

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer 5/16 Rev. A 57-02509 2 Contents INTRODUCTION... 4 WARNING LABELS AND SAFETY INSTRUCTIONS... 5 PS SERIES PARALLEL

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) CS*/CD*/CP* Series Air Cooled Condensing Units Operating and Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment 2 II. Piping...4 III. System

More information

REFRIGERANT ON-VEHICLE INSPECTION AC 14

REFRIGERANT ON-VEHICLE INSPECTION AC 14 14 REFRIGERANT ON-VEHICLE INSPECTION 1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET (a) This is a method to specify trouble areas by using a manifold gauge set. Read the manifold gauge pressure

More information

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP AXIAL HEATER TROUBLE SHOOTING GUIDE Page 1 July 2009 Table of Contents Frequently Asked Questions... 3 Axial Heater CONTROL (Siemens LME69) Troubleshooting Chart... 4 Axial Heater BURNER Troubleshooting

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER

UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER Room Air Conditioner Installation and Operation Manual UNIT MODEL/ POWER SUPPLY VOLTAGE VARIATION AMBIENT AIR ON CONDENSER (VOLTS) MIN. MAX. MIN. F ( C) MAX. F ( C) WAC060K7A 127-1-60 114.3 139.7 70(20.1)

More information

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL EBAC MODEL AD850 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Ebac Industrial Products 704 Middle Ground Boulevard Newport News VA 23606 Telephone (757) 873-6800 FAX (757) 873-3632 Website: www.ebacusa.com INTRODUCTION

More information

AIR CONDITIONER ELECTRONIC CONTROL

AIR CONDITIONER ELECTRONIC CONTROL READ AND SAVE THESE INSTRUCTIONS AIR CONDITIONER ELECTRONIC CONTROL ROOM AIR CONDITIONER WARRANTY Your product is protected by this warranty Your appliance is warranted by Electrolux. Electrolux has authorized

More information

Product Information and Technical Guide

Product Information and Technical Guide Product Information and Technical Guide Side by Side and Top Mount Refrigerators July 2003 - December 2003 White-Westinghouse 5995540384 January 2004 TABLE OF CONTENTS Safe Servicing Practices ------------------------------------------------------------------------------------------

More information

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02

Room Air Conditioner CP06 & CP08. Chill 115 Volts. Service & Parts Manual THE EXPERTS IN ROOM AIR CONDITIONING _02 Room Air Conditioner Service & Parts Manual 2014-2015 CP06 & CP08 Chill 115 Volts THE EXPERTS IN ROOM AIR CONDITIONING 93011401_02 CONTENTS 1. PREFACE 1.1 SAFETY PRECAUTIONS...2 1.2 INSULATION RESISTANCE

More information

POWDER GUIDE. Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings

POWDER GUIDE. Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings POWDER GUIDE From ASIAN PAINTS (I) LTD Trouble shooting tips to maximise the benefits of Apcoshield Powder Coatings Section A : Powder Application Problems Trouble Possible Causes Solutions 1. Poor charging

More information

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning

Experienced Worker Assessment Blueprint HVAC - Heating, Ventilation and Air Conditioning Blueprint HVAC - Heating, Ventilation and Air Conditioning Test Code: 0144 / Version: 02 Specific Competencies and Skills Tested in this Assessment: Electricity Demonstrate understanding of basic AC/DC

More information

CD85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

CD85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL CD85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL Page 1 of 15 www.eipl.co.uk Page 2 of 15 INTRODUCTION Designed for a wide range of applications, the CD85 dehumidifier is a rugged, industrial unit which utilizes

More information

REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions

REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions REFRIGERATORS AND FREEZERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the bill of lading to insure all

More information

SLIDER CASEMENT AIR CONDITIONER

SLIDER CASEMENT AIR CONDITIONER OWNER S GUIDE READ AND SAVE THESE INSTRUCTIONS SLIDER CASEMENT AIR CONDITIONER ROTARY CONTROL P/N 309000854 (11/03) ROOM AIR CONDITIONER WARRANTY Your product is protected by this warranty Your appliance

More information

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS DLCLRA INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 Fig. 1 - Size 36 TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS... 2 PARTS LIST... 3 SYSTEM REQUIREMENTS... 4 WIRING...

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X400 Bio B10 E90-803-001-001-03 Rev 13-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL CD30 / CD30E INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 CD30 PACKAGE CONTENTS Item Description Quantity 1133500 Dehumidifier 1 3014338 PVC tube 12mm I/D 3 M 3086101 Jubilee clip

More information

Some of these procedures need to be performed to conform to requirements of the Clean Air Act.

Some of these procedures need to be performed to conform to requirements of the Clean Air Act. Leak Detection, Recovery, Evacuation and Charging Four basic service procedures used to repair and maintain a mechanical refrigeration system are leak detection, evacuation, recovery, and refrigerant charging.

More information

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s)

Electrical Problems. Fuse(s) blow or circuit breaker trips. Does the unit use circuit breakers or fuses? Replace with correct fuse(s) Electrical Problems Fuse(s) blow or circuit breaker trips Does the unit use circuit breakers or fuses? Fuse(s) Circuit breakers Are the fuses dual element time delay? Is the circuit breaker HACR rated?

More information

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. SECTION 15650 REFRIGERATION EQUIPMENT PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories. B. Related Section: 1. 11400

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration

Calhoon MEBA Engineering School. Study Guide for Proficiency Testing Refrigeration Calhoon MEBA Engineering School Study Guide for Proficiency Testing Refrigeration 1. To prevent an injury when working with refrigerants, what safety precautions are necessary? 2. When halogens are in

More information

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems

More information

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS **WARNING TO INSTALLER, SERVICE PERSONNEL AND OWNER** Altering the product or replacing parts with non authorized factory parts voids all warranty

More information

Part 3 Troubleshooting

Part 3 Troubleshooting Part Troubleshooting What is in this part? This part contains the following chapters: Chapter See page Troubleshooting 2 Error Codes: Hydro-box 7 Error Codes: Outdoor Units Error Codes: System Malfunctions

More information

Preventative Maintenance Tables

Preventative Maintenance Tables Preventative Maintenance Tables Table of Contents I. Table : Gas Fired Domestic Hot Water Heater II. III. IV. Table : Circulating Pump Table : Convectors Table 4: Grille and Diffusors V. Table 5: Unit

More information

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual

(PD[ $LU 'U\HU 5 ( ) 5, * ( 5 $ 7 ( ' 7 < 3 ( & ( 6 6 ( ' $, 5 ' 5 < ( 5 6 ('5&) ದ ('5&) Instructions Manual Instructions Manual 1. Important safety notes - Please read... 1 1.1. Transportation... 1 1.2 Positioning... 1 1.3 Installation... 1 1.4 Before operating... 1 1.5 Maintenance by an engineer... 1 1.6 Maintenance

More information

BLAST-IT-ALL BUMPER BLASTER

BLAST-IT-ALL BUMPER BLASTER LARRY HESS AND ASSOCIATES, INC 185 PIPER LANE / SALISBURY, NC 28147 PHONE: 1-800-535-2612 / FAX: 1-704-638-9311 WWW.BLAST-IT-ALL.COM BLAST-IT-ALL BUMPER BLASTER SUCTION BLAST CABINET NOTE: It is the responsibility

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 INTRODUCTION Designed for a wide range of applications, the RM85 is a rugged, industrial unit, which utilizes an energy-efficient

More information

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions

DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions DIRECT DRAW BEER COOLERS Installation, Operation and Maintenance Instructions INSPECTION When the equipment is received, all items should be carefully checked against the Bill of Lading to ensure all crates

More information

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL

3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL 3500 SERIES CONVECTION STEAM COOKER PARTS AND SERVICE MANUAL EFFECTIVE JULY 30, 2014 Superseding All Previous Parts Lists. The Company reserves the right to make substitution in the event that items specified

More information

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13 R 410A Duct Free Split System Air Conditioner and Heat Pump Product Family: DFS4(A/H) System, DFC4(A/H)3 Outdoor, DFF4(A/H)H Indoor NOTE: Read the entire instruction manual before starting the installation.

More information

Climate Control System

Climate Control System Page 1 of 13 SECTION 412-00: Climate Control System General Information DESCRIPTION AND OPERATION 1998 Mark VIII Workshop Manual Climate Control System Cautions and Warnings WARNING: To avoid accidental

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

SEA FROST SHORE ASSIST SA-1 R-12 THIS MANUAL IS SUPPLEMENTAL TO THE SEA FROST R-12 ENGINE DRIVE MANUAL INSTALLATION INSTRUCTIONS

SEA FROST SHORE ASSIST SA-1 R-12 THIS MANUAL IS SUPPLEMENTAL TO THE SEA FROST R-12 ENGINE DRIVE MANUAL INSTALLATION INSTRUCTIONS 148 OLD CONCORD TURNPIKE BARRINGTON, NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:sales@seafrost.com www.seafrost.com SEA FROST SHORE ASSIST SA-1 R-12 THIS MANUAL IS SUPPLEMENTAL

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500 Bio B10 E90-803-001-001-00 Rev 7-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1 Page 1 WHY should I install the XSTREAM Valve System? XDX is more efficient, saving on power consumption. Use of XDX system decreases defrost cycles. XDX maintains more consistent product temperatures,

More information

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931)

DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee Phone (931) DOLE REFRIGERATING COMPANY 1420 Higgs Road Lewisburg, Tennessee 37091 Phone (931) 359-6211 1-800-251-8990 www.doleref.com PHO WATER DEFROST OPERATION & MAINTENANCE MANUAL June 2002 PHO WATER DEFROST Table

More information

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system

a. CFCs. b. HCFCs. c. Pressurized nitrogen. d. Compressed dry air. 17. The state of the refrigerant leaving the condenser of a refrigeration system Core 1. Ozone in the stratosphere above the earth consists of: a. Molecules containing 3 oxygen atoms. b. Molecules of 2 oxygen atoms. c. Radioactive particles. d. Pollutants that have risen from ground

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No

HEAT PUMPS. Carrier Corporation GT72-01 Cat. No HEAT PUMPS Carrier Corporation 2003 GT72-01 Cat. No. 020-018 1. This refresher course covers topics contained in the HEAT PUMPS specialty section of the North American Technician Excellence (NATE) certification

More information

RPI Industries, Inc.

RPI Industries, Inc. RPI Industries, Inc. AIR SCREEN and SELF-SERVE OPERATION AND SERVICE MANUAL WARRANTY INFORMATION For Models Stratus SCRFC48R-SSI SCRFC60R-SSI SCRFC72R-SSI SCRFC48R-SSII SCRFC72R-SSII SCRFC48R-SSIII SCRFC72R-SSIII

More information

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL RM85 INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL www.eipl.co.uk Page 1 of 12 RM85 PACKAGE CONTENTS Item Description Quantity 10560RG-US Dehumidifier 1 3086144 Quick release hose coupling 1 3944110 PVC Tube

More information

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION

SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION SECTION 2 SAFETY, TOOLS & EQUIPMENT, SHOP PRACTICES UNIT 8 SYSTEM EVACUATION UNIT OBJECTIVES After studying this unit, the reader should be able to Describe a standing pressure test. Choose a leak detector

More information

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6

Table of Contents SPECIFICATIONS Page 2. FOR THE INSTALLER Page 3. FOR THE PLUMBER Page 4. INSTALLATION Page 5. INITIAL START UP Page 6 INTRODUCTION This service manual covers the installation, operation, maintenance and service of this ice machine. Table of Contents SPECIFICATIONS Page 2 FOR THE INSTALLER Page 3 FOR THE PLUMBER Page 4

More information

National Maritime Center

National Maritime Center National Maritime Center Providing Credentials to Mariners U.S.C.G. Merchant Marine Exam (Sample Examination) Page 1 of 26 Choose the best answer to the following Multiple Choice Questions. 1. If a condenser

More information

CIRRUS AIRPLANE MAINTENANCE MANUAL

CIRRUS AIRPLANE MAINTENANCE MANUAL COOLING 1. DESCRIPTION On aircraft serials 183 and subsequent, an optional air condition system is available. This section contains the maintenance practices pertinent to this system. Cabin ventilation

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500-2 Low voltage 12v dc Brushed motor E90-803-001-005-01 Rev 4-1 - Contents Technical specifications Technical data...3 Working field...3 Dimensions...4 Head

More information

Component. Maintenance. Manual Z SERIES. Evaporator Assembly

Component. Maintenance. Manual Z SERIES. Evaporator Assembly Component Maintenance Manual with Illustrated Parts List for Z21-701-SERIES Evaporator Assembly 1 of 16 Record of Revision REVISION ISSUE POSTED NO: DATE DATE INSERTED BY: 2 of 16 List of Effective Pages

More information

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual CELDEK Evaporative Cooler RECEIVING AND INSPECTION Upon receiving unit, check for any interior and exterior damage, and

More information

WineZone Ceiling Mount Ductless Split 15

WineZone Ceiling Mount Ductless Split 15 WineZone Ceiling Mount Ductless Split 15 Requires an HVAC technician to install and charge with R-22 refrigerant. Easy to install. Unit plugs into wall outlet. Industrial grade unit for longer life. Indoor

More information

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A

Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A Condensing Unit and Refrigeration System Installation & Operations Manual R448A/R449A 57-06 REV. -04-7_BJ TABLE OF CONTENTS INTRODUCTION... WARNING LABELS AND SAFETY INSTRUCTIONS...4 M-SERIES CONDENSING

More information

ROTARY CONTROL AIR CONDITIONER

ROTARY CONTROL AIR CONDITIONER USE & CARE MANUAL NOTE: This USE & CARE MANUAL provides specific operating instructions for your model. Use the room air conditioner only as instructed in this USE & CARE MANUAL. These instructions are

More information

Product Information and Technical Guide

Product Information and Technical Guide Product Information and Technical Guide Side by Side and Top Mount Refrigerators January 2004 - March 2004 White-Westinghouse 5995413308 July 2004 TABLE OF CONTENTS Safe Servicing Practices ------------------------------------------------------------------------------------------

More information