10/29/01,2:16 PM TUNNEL WARM-UPPROC4--HIGHLITED REQUIRED ACTIONS.DOC KIRSNER CONSULTING ENGINEERING

Size: px
Start display at page:

Download "10/29/01,2:16 PM TUNNEL WARM-UPPROC4--HIGHLITED REQUIRED ACTIONS.DOC KIRSNER CONSULTING ENGINEERING"

Transcription

1 Start-Up Methodology for TSU Tunnel Steam /Condensate System Low Spots. Figure 1 shows an isometric view of the tunnel steam piping system. The steam mains in the tunnel are assumed to slope with the tunnel floor 1 so that condensate within the steam mains tends to drain in the same direction as water runoff along the floor of the tunnel toward UV-2 and out below the tunnel walkin entrance. Thus, with two exceptions, condensate that is not drained from the steam lines eventually flows to the vicinity of the T-4 Trap Assembly at Junction DSA. The two exceptions are the North A steam segment which drains toward T-30 at UV-2 in accordance with the tunnel floor invert; and the North B steam main segment which drains toward the central main at DS-B but, due to the offset of the steam line over the chilled water pipes, cannot drain into the central main line. Figure 1 depicts in blue where condensate will tend to accumulate in the steam mains if not drained. The Critical Trap(s). Note that Trap T-4 is the critical trap in the steam main system in that: (1) it receives condensate from 192 of 12 pipe from the direction of UV-1 and 304 of 10 pipe from west of the trap toward T-5, AND (2) is located at the low point in the system where undrained condensate will tend to accumulate if not drained by the other traps in the mains. If during operation of the steam system in the tunnel, the T-4 trap station can be kept clear of condensate, then all other trap stations should adequately handle their condensate load also. That, in a nutshell, is the start-up strategy. Condensate Backpressure. Condensate lines within the tunnel are normally pressurized by the water column required to lift the condensate roughly 30 feet 2 to the condensate receiver in the Steam Plant. The pressurization of the condensate return (CR) system places a backpressure on steam traps draining condensate from the tunnel steam lines which I estimate should be less than 20 psig 3. At start-up, this backpressure will cause condensate to be retained in the steam mains until steam pressure can build to overcome the condensate backpressure unless condensate is removed by alternate means. During the period traps are disabled by backpressure--which I will term Phase I of the Start-up-- condensate, if it is not drained, will fill drip legs 4 and then overflow to the T-4 trap station (as well as the low points in the north A & B lines). Trap Capacity. The capacity of the traps which are all identical, per SARCO literature for the TLV FS3-10, is slightly under 400#/hr at 90 psid 5 (which equals 110 psig Steam Plant operating pressure 20 psi backpressure). I calculate 6 that the condensate load at 110 psig/ 344 F on T-4 assuming no more than 1% uninsulated pipe is 85 #/hr. Thus, the trap has better than a 4 to 1 safety factor if the 3 insulation covers 99% of the pipe. (If more than 14% of the pipe became bare, the trap will not handle the condensate load). The critical questions to ask for an unsupervised start-up 7 is at what steam pressure could the critical trap handle the condensate load. The table below shows how trap capacity falls off with differential pressure across the trap. At 5 psid/ 25 psig, the trap can handle 100 #/hr of condensate. Trap Capacity #/hr W/ 20 psi backpressure 110 psig psig psid #/hr *manufacturer assumes 11 F subcooling 1 Per Telecom I.C. Thomasson. Drawings requested to verify. I.C. Thomasson cannot locate. Still trying 2 Ditto, footnote 1. 3 Pressure gauge read 20 psi 8 feet above steam line on , i.e psi. Previous reading was 8 psi? (Recommend a pressure and temperature gauge be installed in condensate mains at Junction DSA with communication points to the EMS). 4 Drip legs on the TSU system are very small, holding only about a quart of liquid each so they readily overflow. 5 Psid= pounds per square inch differential pressure 6 See spreadsheet entitled TSU Tunnel Steam Pipe Heat Loss 7 I.E., one where condensate is not drained manually 1

2 Condensate Load. I calculate the condensate load at 25 psig will be 53 #/hr at the critical trap T-4. Thus if my heat transfer presumptions are accurate, at 25 psig (actually 5 psid above the condensate backpressure)- - traps can handle the condensate load being generated in the steam tunnel with a safety factor of 2. The following presumptions were made in the heat transfer calculations: 1. 3 fiberglass insulation covering 99% of pipe being served by T-4 2. Both tunnel ventilation fans on creating a 10 mph breeze at T F in tunnel I calculate that if more than 4% of the pipe being served by T-4 is uninsulated, the T-4 trap will be overcome at 5 psid/25 psig. Therefore, it s paramount to insure pipes stay well insulated. Prior to reaching 5 psid (~25 psig) during warm-up, another method of draining condensate is necessary to keep it from accumulating at low spots in the system. Phase I of Start-Up : 70 F 212 F (0 psig) The steam plant shall admit steam to the steam system at a pressure a few psi above 0 psig after having warmed up the boiler(s) to 212 F. Phase I shall not end until the system is warmed to 212 F as indicated by a reduction in steam flow from the boiler plant and the read out of a temperature sensor near the end of the steam system. Condensate Generated. Over 2,500 # s of condensate (~325 gallons) will form in the tunnel steam mains in warming the steel from 70 F to 212 F not including condensate which forms in the North A & B lines which do not drain into the central steam main. (Not included in this amount is the additional condensate which forms due to heat loss as the pipes warm. This can be substantial where pipes are uninsulated). This condensate must be removed before additional steam flow and pressure is applied to the steam distribution system to warm it the rest of the way to final steam temperature of 344 F at 110 psig. If Trap T-4 had to act alone to remove this condensate after it had all flowed to Junction DSA, I calculate it would take trap T-4 acting alone over 28 hours to drain accumulated condensate 8 after steam pressure was raised above 30 psig (to provide 10 psid of positive pressurization). 8 (See TSU Tunnel Report\CondensateFormation.xls for calculation). Calc does not include condensate formed due to heat loss during period pipes are warming. 2

3 Because this is unacceptable, other provisions have been made to remove condensate during the period traps are inoperable. Thermotons. To help drain condensate at start-up, Sarco Thermotons (pictured above) were provided at trap assemblies in the Summer 1999 Repair of the Tunnel Steam System designed by I.C. Thommason. The thermotons automatically open to discharge condensate to the tunnel floor whenever condensate temperature is less than 212 F 9 -- which it should be during the initial Phase I of start-up. The capacity of thermotons to remove condensate, however, is limited. The CL-6 model provided at TSU has only a 3/8 orifice. At 1 psid (equal to a water head of 2.3 feet with no steam pressure), a thermoton will only discharge about 3.3 # s 10 of condensate a minute or 0.4 gpm. Consequently, unless steam is admitted very slowly to the steam system, condensate can easily overwhelm the capacity of a thermoton to drain it, fill the drip leg, and ultimately flow to the low spot in the system at Junction DSA. Based on the amount of condensate that flows to the nextmost critical trap after T-4 during start-up, the thermoton at T-5 needs as much as an hour to drain condensate during Phase I. If condensate is formed more rapidly, it will overflow the T-5 drip leg toward T-4 at Junction DSA. The T-4 trap station which receives condensate from two directions will take about 1.8 hours to drain just the warm-up condensate it normally receives 11. My guess is that even with a slow and careful start-up employing the thermotons, a substantial amount of condensate from the entire system could overflow trap stations and end up at T-4. If the condensate were allowed to accumulate there, the thermoton at T- 4 would be very slow to drain a large puddle of condensate 12. Manual Verification. Thus, the drain at the T-4 trap assembly as well as those at T-30 and T shall be manually opened at the end of the Phase I warm-up period (as signified by the achievement of 212 F at the end of the steam system) to: (#1) purge any condensate not removed, and (#2) verify that all Phase I condensate has been removed from the steam system. This may be accomplished relatively safely since there is minimum steam pressure in the system. After verification that all condensate is out of the system at each low point, the manual drain may be closed and Phase II of the Start-up may proceed. Air Removal. Another benefit of the thermotons is that they will vent air during warm-up where they have enough time to clear condensate before condensate temperature exceeds their set point. This will be the case at the farthest reaches of the tunnel steam lines. Phase II of Start-up: 212 F 274 F (30 psig) From 70 F to 212 F is a 142 F temp rise. The system has 132 F further to go to warm to 344 F, so during Phase I, just over one-half of the warm-up condensate has been formed and expelled. Above 212 F, Thermotons are closed, so the rest of the condensate to be formed during warm-up about 2400 # s (~300 gallons)-- must be removed by other means. Traps, as discussed earlier, will not remove condensate until the steam pressure exceeds the backpressure in the condensate system which I presume to be not more than 20 psig (based on the height of the riser to the condensate receiver in the steam Plant). Consequently, once it is confirmed that all condensate is drained from Phase I by manually checking for condensate at T-4, steam pressure may be hiked steadily to > 25 psig say 30 psig-- to enable traps to discharge condensate. 9 Temperature setting of thermotons should be verified. 10 See Spreadsheet cell G-19 in Warm-up Condensate 11 If both pipe segments east and west of T-4 drain to T-4, then it receives about 356# of condensate (45 gallons) during warm-up from 70 F to 212 F. At this rate, the thermoton at T-4 would need roughly 356/199= 1.8 hours to discharge all condensate. 12 In the worst case, for example, that one-half of the condensate generated in the entire tunnel steam piping during Phase I, less North A&B, overflowed the drip legs and flowed to T-4, the thermoton at T-4 would require over 6 hours to drain it all at 1 psi head. 13 The thermotons at T-30, T-27, and T-47 should be able to drain condensate accumulated in warming the section of line they serve in.62,.62, and.78 hrs respectively. 3

4 At 30 psig (assuming this is 10 psi above the CR backpressure), the FS3-10 TLV traps will discharge 135 #/hr of condensate about ¼ gpm. T-4, with the greatest condensate load, will receive 156 # s of warm-up condensate in warming from 212 F to 274 F plus roughly 53 #/hr due to heat losses after warming up. The trap can discharge this condensate in less than 2 hours. Thus, the duration of Phase II will be 2 hours. (This time duration could be more than cut in half by replacement of the TLV-FS3 trap with a larger FS5 model). Back-up Bucket Traps. Once again, it is possible that if steam is admitted too quickly to the system, condensate could overflow trap stations and end up at T-4 adding to its condensate load. Thus, to relieve any possible overload at T-4 which could result in a condensate accumulation, a low-pressure high-capacity bucket trap shall be piped in above the T-4 trap in the T-4 trap assembly. The purpose of the bucket will be to discharge any condensate that backs up at T-4. Like the thermotons, the bucket shall discharge to the tunnel floor. But, above 30 psid (~50 psig), the bucket shall be selected to automatically seal closed so it is inactive at normal steam operating pressure. An ARMSTRONG 812 trap with ¼ orifice will discharge 1500 # s of condensate per hour at 10 psid (~30 psig) and seal shut at 30 psid (~50 psig). The bucket will perform the same function as the thermoton in dumping subcooled condensate, but it has 2.4 times the capacity of the thermoton and will remain operable through Phase II of the Start-up Procedure. An additional benefit is that it will speed up Phase I of the Start-up-- the bucket trap will cut the condensate drain time at T-4 in half to less than 1 hour 14. The thermoton at T-4 may be removed from service to simplify the trap assembly. 15 Using the same logic as above, back-up low-pressure bucket traps shall also be installed at T-30 and T- 47. Phase IIIa of Start-up: 274 F(~30 psig) 293 F (60 psig) Increase steam pressure to 60 psig (~40 psid). At 60 psig (40 psid), the trap s capacity increases to 265#/hr. 86 # s of warm-up condensate will form and flow to T-4 during this portion of the warm-up plus condensate generated by heat loss less than 40# s over ½ hour. Condensate can be removed in ½ hour. Phase IIIb of Start-up: 293 F(~60 psig) 344 F (110 psig) At 110psig (90 psid ), trap capacity is almost 400#/hr. Raise steam pressure to 110 psig over the next ¼ hour, allow it to remain at 110 for another ¼ hour. 14 I have not recommended the bucket be used to reduce the duration of Phase II, however, because during Phase II, hot condensate (T> 212 F) would be dumped. 15 An ALTERNATE PLAN is to install a pumped trap at T-4 which can lift condensate the ~45 to the condensate receiver through a dedicated discharge pipe. The pumped trap would act as a regular trap when steam pressure was sufficient to overcome condensate backpressure to expel condensate, but when steam pressure was insufficient, it would be automatically powered by 70 psi air pressure (or an auxiliary steam pressure source) to lift condensate to the condensate receiver. (The air pressure available in the steam plant, I m told, is 100 psig). An advantage of this configuration is that it could avoid dumping some or most of the condensate to the tunnel floor especially if use of the thermotons were abandoned. This could amount to about 2600# s of condensate saved at start-up if the thermotons use were abandoned except for a few at the end of the line for air venting. (Could is in italics since the steam plant dumps most condensate return during start-up due to overfilling of the boilers, so the majority of returned condensate is not recovered). The rest of the condensate would still be emptied by traps once steam pressure exceeded 20 to 30 psig. Like the low-pressure bucket trap, the primary function of the pumped trap would be to act as a backup to catch any condensate not emptied by other traps in the tunnel system (other than those in North A & B lines). It would perform this duty even during normal steam pressure operation (when the bucket trap would be sealed closed by steam pressure). Flow of compressed air to the pump trap could be alarmed and monitored to give a warning when thermotons or traps were not remo ving all condensate formed. The pumped trap solution is more elegant, but is also more costly. An air or steam line would have to be run beneath the street and down the tunnel shaft from the Steam Plant to Junction DSA. I adjudge the additional advantage of the pumped trap to not be worth the extra installation cost. 4

5 At Completion of Warm-up Re-enter Tunnel. (1) To insure no condensate is backed up in steam lines, compare temperature of condensate-filled portion of drip leg at T-30, T-4, and T-47 trap assemblies with steam filled portion using an infrared radiation gun. If temperature of condensate is subcooled compared to steam, a condensate back-up is indicated as shown below. If there is a condensate back up, DO NOT attempt to drain it under full steam pressure. Reduce steam pressure to 0 psig, drain the line, troubleshoot the problem. (2) Close isolation valves upstream of thermotons at each trap assembly to keep them from dribbling condensate. (3) Check for proper contraction of expansion joints and alignment of guides. (4) Check traps for blowing (you ll hear a popping sound) or stopped up traps using the infrared gun. (5) Blow down trap strainers. (6) Open air vents in condensate loops over chilled water pipes at DSA and DSB. Be careful, condensate is hot and under ~20 psig pressure. (These vents should be replaced with automatic air vents or chain pull vents piped away from worker.) Pre-Start-Up Walk-Through Steam Subcooled Steam pipes shall be cleared of water before start-up. The normally closed gate valve located upstream of each Thermoton must be opened prior to start-up to permit the thermoton to drain condensate during start-up. This shall be accomplished during a pre-start-up walk-through of the entire tunnel system to inspect expansion joints, anchors, guides, and condition of insulation as well as open thermoton isolation valves. During walk-through: 1. Expansion joint slips shall be cleaned to bright shiny appearance. Make sure to replace insulation and covers on slips to minimize exposure to environment. 2. Misalignment of guides or joints shall be identified for repair and rectified prior to start-up. 3. After opening thermoton isolation valve, open drains below drip legs to clear drip leg mud accumulation and verify thermoton operation. Close drains. 4. Audit Insulation Condition. Observe condition of insulation and note lineal feet and pipe size where insulation is missing. On pipe segments draining to T-4 at DSA and in the North A line, no more than 1% of the lineal feet of insulation along the length of the pipe shall be missing. No more than 10% of the insulation shall be missing on any other pipe span served by a single trap in the system. If these figures are exceeded, rectify prior to start-up, or adjust start-up procedure. To Trap Assembly 5

6 Recap (Not Finished) Prior to start-up, tunnel entrants shall familiarize themselves with the Tunnel Entry SOP. It states, among other requirements, that the three primary safety systems in the tunnel: the lights, ventilation fans, and communication system must be operational for the Tunnel to be deemed non-hazardous and not permitrequired. The following procedures presume all these systems are fully operational. 1. Preliminary to start-up. Open all isolation gate valves to thermotons through-out the tunnel. Then, open drains from drip legs to clear drip leg mud accumulation and check thermoton operation. Close drains. Make sure to replace insulation and covers on slips to minimize exposure to environment. Clean slips at exp.joints and inspect guides and pipe alignement. Audit insulation. 2. Via telecom, give the steam plant the go ahead to admit steam to the tunnel main to bring the system up to 5 psig and have it dwell there over the span of 1 hour or longer. 3. Steam Plant will hold pressure at minimum level. 4. A steam tunnel qualified maintenance man shall enter the tunnel, travel to UV-1, where he shall observe the operation of the low pressure bucket trap. If it has stopped discharging repeatedly, he shall open the drain at T-3 to insure all condensate has been cleared. If so, he shall close the drain, exit the portion of the tunnel containing the steam main, and radio the steam plant coordinator to slowly raise steam pressure to 30 psig. 5. After 1 hour at 30 psig, steam pressure may be raised slowly over a period of 15 minutes to 110 psig. 6. After start-up is complete (as evidenced by the lack of discharge by the pumped trap, if installed), isolation valves upstream of thermotons at each trap assembly must be closed to keep them from dribbling. The condition of expansion joints and guides should be checked, and traps tested for blowing or stopped up traps. Strainers should also be blown down. 6

7 Figure 1. Isometric View of Tunnel Steam System (Pipe Pitch Based on telecom w/ I.C Thommason. ) Condensate Receiver in Steam Plant Dashed line represents level reference line. Represents a drip leg and trap station UV-1 T-3 12 T-25 ~2500 gal condensate to warm to 212 F T T North A UV-2 T-30 Tunnel Entrance 60,000 cfm from 2 fans North B 792 T-41 T-6 DSB 974 T-7 Slope T-8 T T-10 7

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

Installation and Testing of Inverted Bucket Steam Traps Manual

Installation and Testing of Inverted Bucket Steam Traps Manual Installation and Testing of Inverted Bucket Steam Traps Manual 307-EN Please read and save these instructions Armstrong IB Traps Installation Before Installing Run pipe to trap. Before installing the trap,

More information

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods 230520 HEAT GENERATION Cornell s Design and Construction Standards provide mandatory design constraints and acceptable or required products for all construction at Cornell University. These standards are

More information

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS DRAINAGE of a SINGLE SOURCE of for a CLOSED LOOP SYSTEM PURPOSE: For removing condensate from below steam heat transfer equipment when a modulating valve is used for control and stall conditions will exist.

More information

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle

Steam Trap Presentation for IDEA Distribution Workshop. Presenter: Joe Radle Steam Trap Presentation for IDEA Distribution Workshop Presenter: Joe Radle Proper Piping when Reducing Pipe Size Concentric reducer Eccentric reducer Correct Wrong Typical Steam Main Drip Station D Size

More information

Boiler Steam Supply Piping Basics November 18, ) Q: What kind of condensate traps should be used on vacuum condensate return systems?

Boiler Steam Supply Piping Basics November 18, ) Q: What kind of condensate traps should be used on vacuum condensate return systems? Boiler Steam Supply Piping Basics November 18, 2015 1) Q: What kind of condensate traps should be used on vacuum condensate return systems? A: What is often used in a vacuum system is a thermodynamic disc

More information

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 0772150/4 IM-P077-02 ST Issue 4 S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning

More information

GTX Series Thermal Xchange Cycling Refrigeration Dryers GREAT LAKES AIR ANDARD ELECTRONIC DRAIN 5 -YEAR WARRANTY F PRESSURE DEWPOINT

GTX Series Thermal Xchange Cycling Refrigeration Dryers GREAT LAKES AIR ANDARD ELECTRONIC DRAIN 5 -YEAR WARRANTY F PRESSURE DEWPOINT GREAT LAKES AIR ANDARD ELECTRONIC DRAIN STANDARD ELECTRONIC 5 -YEAR WARRANTY 35-39 F PRESSURE DEWPOIN SS EXPANSION VALVE STANDARD ELECTRONIC DRAIN 35-39 F PRESSURE DEWPOINT GTX Series Thermal Xchange Cycling

More information

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000 SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual 65 SH-2500 SH-2000 AB-3000 Table of Contents General Safety Information.............. 2 Product Information..................3

More information

The. Steam TWO-PIPE STEAM & PUMPED RETURN

The. Steam TWO-PIPE STEAM & PUMPED RETURN FULL-COLOR TRAINING GUIDE SERIES The of Steam TWO-PIPE STEAM & PUMPED RETURN The Color of Steam The Color of Steam A. PUMPED RETURN SYSTEMS 1. When Is a Pump Needed? 2. Pumped Return Systems 3. Boiler

More information

APPLICATION GUIDELINES STEAM MAIN DRAINAGE

APPLICATION GUIDELINES STEAM MAIN DRAINAGE APPLICATION GUIDELINES STEAM MAIN DRAINAGE 1) Steam Main Drip Leg Dimensions 2) Types of Warm-Up a) Supervised b) Automatic 3) Spacing of Drip Legs 4) Low Pressure Drainage-- Sizing Traps for Automatic

More information

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems

HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems HumidiPack CF HumidiPack CF offers the performance of HumidiPackPlus without the need of jacketing steam on pressurized steam applications.

More information

Steam System Best Practices Document No. 11

Steam System Best Practices Document No. 11 Plant Support & Evaluations, Inc 400 Lombardi Ave. Green Bay, WI 54304 888-615-3559 www.plantsupport.com Fax: 888-615-8664 Steam System Best Practices Document No. 11 The Number One Problem in a Steam

More information

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to "HOW TO ORDER" page.

PT15 MATERIAL : DIMENSIONS - Nominal in inches. AVAILABLE SPARES: Disc (Packet of 5) ORDERING INFORMATION: Refer to HOW TO ORDER page. PT5 Thermodynamic Steam Traps MATERIAL : No. PART MATERIAL QTY. (Nos.). BODY ASTM A743 Gr. CA 40 0 (Seat Hardened) (Cast Equiv. AISI 420) 2. DISC CAP ASTM A743 Gr. CA 40 0 (Cast Equiv. AISI 420) 3. DISC

More information

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016 Boiler Condensate Return Basics Presented by Steve Connor February 24, 2016 What We Are Covering Today? Brief review of the total steam system Why a proper condensate return system is so important Condensate

More information

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw

INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw INSTALLATION & MAINTENANCE MANUAL FOR QuickDraw SEMI-INSTANTANEOUS ENERGY: STEAM TO WATER U-TUBE SINGLE-WALL & DOUBLE-WALL HEAT EXCHANGERS FLOOR DRAIN Typical Construction Figure 34-1 FLOOR DRAIN 1. U-tube

More information

The. Steam ONE-PIPE STEAM SYSTEMS

The. Steam ONE-PIPE STEAM SYSTEMS FULL-COLOR TRAINING GUIDE SERIES The of Steam ONE-PIPE STEAM SYSTEMS ONE-PIPE STEAM SYSTEMS PIPING AND TROUBLESHOOTING ONE-PIPE STEAM SYSTEMS ONE-PIPE STEAM SYSTEMS A. HOW ONE-PIPE SYSTEMS WORK 1. movement

More information

WATER HAMMER something that never should occur in a steam system

WATER HAMMER something that never should occur in a steam system BEST PRACTICE NO. 11 WATER HAMMER something that never should occur in a steam system 1. STEAM AND CONDENSATE WATER HAMMER Water hammer is never normal in a steam and condensate system, and it is totally

More information

InterSeptor Centrifugal Separators Operating & Maintenance Manual

InterSeptor Centrifugal Separators Operating & Maintenance Manual General Information: This manual was prepared to assist in the installation, operation, and maintenance of PEP ICS centrifugal separator systems. For immediate response to questions not covered in this

More information

Removal of Non-condensable Gases and Air Is Critical In A Steam System

Removal of Non-condensable Gases and Air Is Critical In A Steam System Removal of Non-condensable Gases and Air Is Critical In A Steam System Air and non-condensable gases are one of the major problems in a steam system. Both can cause production problems for a steam system

More information

Electric Pumps. Introduction. W4100, W4200 & W4300 Condensate Pumps. Typical Condensate Pump Features

Electric Pumps. Introduction. W4100, W4200 & W4300 Condensate Pumps. Typical Condensate Pump Features Electric Pumps Introduction W4100, W4200 & W4300 Condensate Pumps Watson McDaniel s Condensate Return and Boiler Feed Pumps are equipped with Cast Iron bodies and Bronze Impellers. The pump receiver tanks

More information

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT CEMLINE Unfired Steam Generators are designed to produce clean steam with steam or high temperature hot water as an energy source for use where there is a need to produce clean steam from boiler steam

More information

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes.

A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Introduction to Hydronics A hydronic system controls comfort by delivering heated or cooled fluid to the conditioned space through pipes. Hydronic heating systems use hot water or steam to deliver the

More information

Steam Trap Inspection Methods And Steam Cost Analysis

Steam Trap Inspection Methods And Steam Cost Analysis Steam Trap Inspection Methods And Steam Cost Analysis 14 Hayes Street, Elmsford NY 10523-2536 USA Tel: 914-592-1220 Toll Free USA & Canada 24 Hour Fax Email: Internet 800-223-1325 914-347-2181 info@uesystems.com

More information

WHY IS BUILDING SCIENCE IMPORTANT?

WHY IS BUILDING SCIENCE IMPORTANT? OUTLINE Why Building Science is Important Building Science Key Components Controlling Air Flow Controlling Thermal Flow Controlling Moisture Flow ENERGY STAR Solutions Action Plan WHY IS BUILDING SCIENCE

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin ACU_O&I 02 August 2016 Condensing Unit Installation and Operating Instructions ACU Air Cooled Condensers Table of Contents Section 1. General Information... 2 Section 2. Refrigeration Piping...

More information

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual

SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual SH-300, SH-900, SH-1500, SH-1600 and SH-1700 Bimetallic Steam Trap Installation and Operation Manual 111-EN SH-300 SH-900 SH-1500 SH-1600 SH-1700 Table of Content. General Safety Information. 3 Product

More information

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN VALVES VESSELS SYSTEMS CONTROLS PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN System drawings shown in this bulletin are for illustration purposes only. Refrigeration systems

More information

Condensing Unit Installation and Operating Instructions

Condensing Unit Installation and Operating Instructions Bulletin WCU_O&I 01 June 2003 Condensing Unit Installation and Operating Instructions WCU Air Cooled Condensing Unit Table of Contents Section 1. Section 2. Section 3. Section 4. Section 5. Section 6.

More information

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001

Air Handler Unit. Installation & Operations Manual. Table of Contents. Bulletin No. H-IM-AH August 2002 Part Number 4346B001 Bulletin No. HIMAH August 2002 Part Number 4346B001 (Replaces HIM71A, August 2002) Installation & Operations Manual Air Handler Unit Table of Contents Inspection...2 Shipment of Units Handling Suspended

More information

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT

KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT KEEP YOUR TRAP SHUT OR GET THE CONDENSATE OUT Jerry Wright Paramount Supply Company Eugene, OR Introduction Keep your trap shut or get the condensate out. Which way is it? Can you have it both ways? Which

More information

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL

PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL FloorHeat PRE-ASSEMBLED RADIANT CONTROL PANEL INSTALLATION MANUAL Thank you for purchasing this radiant control panel assembly. Following are some important notes that will make the installation successful.

More information

Daikin Water Cooling, Heating, and High Capacity Booster Coils

Daikin Water Cooling, Heating, and High Capacity Booster Coils Installation and Maintenance Manual IM 900 Daikin Water Cooling, Heating, and High Capacity Booster Coils Group: Applied Air Part Number: IM 900 Date: February 2008 Types HI-F5, E-F5 2008 Daikin International

More information

B. A. T. Basic Appliance Training

B. A. T. Basic Appliance Training B. A. T. Basic Appliance Training BASIC REFRIGERATION presented by Phil Whitehead Program Objective The objective of this program is to give you some of the basic elements that are essential to understanding

More information

Niles Steel Tank Hot Water Generator Installation and Operation Manual

Niles Steel Tank Hot Water Generator Installation and Operation Manual Niles Steel Tank Hot Water Generator Installation and Operation Manual Contents: Contents 1 Hazard definitions 1 1. General Information.... 2 Availability... 3 Optional Control Packages... 5 2. Installation....

More information

THERMAL ICE STORAGE: Application & Design Guide

THERMAL ICE STORAGE: Application & Design Guide THERMAL ICE STORAGE: Application & Design Guide Table of Contents: 1. Introduction A. History of Thermal Energy Storage B. Operating and Cost Benefits 2. Applications A Fundamental System B. HVAC Cooling

More information

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com Spray Flow II Pressurized and Atmospheric Deaerators.005 cc/liter Atmospheric Deaerator CONSTANT RECYCLING guarantees deaeration of all dissolved oxygen in excess of.005 cc/liter from 0% to 100% of deaerator

More information

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com

Spray Flow II cc/liter Atmospheric Deaerator. industrialsteam.com Spray Flow II.00 cc/liter Atmospheric Deaerator Pressurized and Atmospheric Deaerators CONSTANT RECYCLING guarantees deaeration of all dissolved oxygen in excess of.00 cc/liter from 0% to 100% of deaerator

More information

TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY

TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY TESTING STEAM TRAPS TO KEEP YOUR SYSTEM OPERATING EFFECTIVELY AND EFFICIENTLY A steam trap, which is a fully automated condensate drainage device, generally does not require routine maintenance. Steam

More information

Economical and simplified solutions that offer quality and optimum steam trap service.

Economical and simplified solutions that offer quality and optimum steam trap service. Economical and simplified solutions that offer quality and optimum steam trap service. It All Comes Down To Protection Regardless of the temperature and pressure characteristics of steam line drips or

More information

PIP PNE00004 Steam Trap Guidelines

PIP PNE00004 Steam Trap Guidelines July 2016 Piping PIP PNE00004 Steam Trap Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from

More information

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S SERIES PB, 29, 129Y AND 29S Economical and simplified solutions that offer quality and optimum steam trap service FEATURES 29S 29 Thermostatic traps Pressure assisted fail-open design Freeze proof Easy

More information

Irrigation for Lawns and Gardens

Irrigation for Lawns and Gardens Irrigation for Lawns and Gardens Contents Planning the Irrigation System... 3 Sprinkler Irrigation... 3 Drip Irrigation... 6 The Distribution System... 8 The Water Source... 10 Backflow Prevention... 11

More information

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS

Inverted Bucket Float & Thermostatic Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS Inverted Float & Radiator Traps STEAM CONTROL PRODUCTS STEAM TRAPS ABOUT US In 1916, the company, then known as the Sterling Engineering Company, began designing and manufacturing valves, traps, strainers

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.05 PLUMBING GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.05 It is expected that the plumbing design professional will conform to accepted good engineering design practices.

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS

FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS FLO-RITE-TEMP INSTANTANEOUS WATER HEATER INSTALLATION AND ADJUSTMENT INSTRUCTIONS FOR SINGLE AND DOUBLE WALL UNITS Bulletin No. AY-780-L This bulletin should be used by experienced personnel as a guide

More information

Condensate Pumps Jones Boulevard Limerick Airport Business Center Pottstown PA Tel:

Condensate Pumps Jones Boulevard Limerick Airport Business Center Pottstown PA Tel: www.watsonmcdaniel.com 428 Jones Boulevard Limerick Airport Business Center Pottstown PA 19464 Tel: 610-495-5131 129 Return Introduction Return System Shown below is a simplified view of a steam system

More information

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A

CS 2. Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual. Form No. 6120A CS 2 Central Station Air Handlers Double Wall & Single Wall Installation, Operation & Maintenance Manual Form No. 6120A TABLE OF CONTENTS Page Inspection... 2 Shipment of Units... 2 Handling... 2 Installation...

More information

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No.

STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY. Information Reviewed and Reaffirmed. August No. STEAM TRAPS FOREST PRODUCTS LIBRARY FOREST RESEARCH LABORATORY OREGON STATE UNIVERSITY Information Reviewed and Reaffirmed August 196 No. 1664 11111111111134 areillin1111111 1 11111111 1 1[1 11 nin FOREST

More information

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!! Sample Written Program For Your Company For BOILER SAFETY Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-781-1446 Email: info@se-safety.com Purpose Boiler Safety Program The

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com Tray ST5 Pressurized and Atmospheric Deaerators Tray Type Deaerator Pressurized.005 cc/liter COUNTER FLOW TRAY design provides guaranteed removal of all dissolved oxygen in excess of.005 cc/liter from

More information

STEAM AND TRAP FUNDAMENTALS

STEAM AND TRAP FUNDAMENTALS STEAM AND TRAP FUNDAMENTALS Nick Westerberg Westerberg and Associates Newman Lake, WA Steam is an invisible gas that is generated by adding heat energy to water, usually from burning fuel in a boiler.

More information

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

For an administrative fee of $9.97, you can get an un-locked, printable version of this book. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. For an administrative fee of

More information

Operations and Maintenance Manual

Operations and Maintenance Manual IMPORTANT: READ THIS MANUAL THOROUGHLY BEFORE INSTALLING AND OPERATING UNIT. INSURE THERE IS ALWAYS LUBRICATING OIL IN THE FRONT FILTER LUBRICATOR FOR THE FLUID PUMP AIR MOTOR. CHECK OIL LEVEL REGULARLY

More information

So far 2010 is proving to be

So far 2010 is proving to be Optimising steam systems: part I Simple techniques to reduce the cost of ownership of a refinery s steam distribution system and condensate return using steam traps and separators Ian Fleming Spirax Sarco

More information

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION $7.50 Installation, Operation, and Maintenance Manual CEMLINE CORPORATION Unfired Steam Generators (USG Series) Horizontal USG Vertical USG CEMLINE CORPORATION P. O. Box 55, Cheswick, PA, 15024 Phone:

More information

VS SERIES NH3 STEAM VAPORIZERS OPERATION MANUAL

VS SERIES NH3 STEAM VAPORIZERS OPERATION MANUAL VS SERIES NH3 STEAM VAPORIZERS Revised March 1997 OPERATION MANUAL CONTENTS PAGE 1. GENERAL................................... 1 Figure 1-1 - VS Series Vaporizer......................... B How to Select

More information

Standard Features. Performance/Capacities

Standard Features. Performance/Capacities TSC-66 Traditional Power/Connections Approximate Total Load AMPS 208V / 60HZ / 3PH 51.8 208V / 60HZ / 1PH 88.3 230V / 60HZ / 3PH 47.8 230V / 60HZ / 1PH 81.5 460V / 60HZ / 3PH 23.9 Booster Heater Options

More information

Phoenix C4XE - Membrane Based Portable Lube and Hydraulic Oil Purifier Cart For use in Hazardous Duty Locations.

Phoenix C4XE - Membrane Based Portable Lube and Hydraulic Oil Purifier Cart For use in Hazardous Duty Locations. IMPORTANT: READ THIS MANUAL THOROUGHLY BEFORE INSTALLING AND OPERATING UNIT. IT IS THE CUSTOMERS RESPONSIBILITY TO WIRE UNIT WITH THE APPLICABLE ELECTRICAL CORD AND PLUG FOR USE IN HAZARDOUS DUTY ENVIRONMENTS

More information

BOHEC R CRS86A DISHWASHER STANDARD FEATURES MODEL ACCESSORIES DIRECTION OF OPERATION VOLTAGE OPTIONS AT EXTRA COST

BOHEC R CRS86A DISHWASHER STANDARD FEATURES MODEL ACCESSORIES DIRECTION OF OPERATION VOLTAGE OPTIONS AT EXTRA COST Item # Quantity C.S.I. Section 11400 DISHWASHER STANDARD FEATURES 244 racks per hour Opti-RinSe system Ball detent clutch conveyor drive mechanism Top mounted controls Stainless steel anti-clogging wash

More information

How to Trap: Installation and Testing

How to Trap: Installation and Testing How to Trap: Installation and Testing 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

A M E M B E R O F T H E K E N D A L L G R O U P

A M E M B E R O F T H E K E N D A L L G R O U P A M E M B E R O F T H E K E N D A L L G R O U P Presented by: Dan Gallagher Energy Opportunities in a Steam System What makes up your Steam System Boiler Room Distribution System Mechanical Rooms Point

More information

BASIL 6000 TUNNEL CAGE WASHER

BASIL 6000 TUNNEL CAGE WASHER BASIL 6000 TUNNEL CAGE WASHER APPLICATION For thorough, efficient cleaning of cages, debris pans, bottles, feeder bowls, and miscellaneous items used in the care of laboratory animals. DESCRIPTION The

More information

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL

HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL HEATLESS DESICCANT AIR DRYER INSTRUCTION & MAINTENANCE MANUAL H-Series & 203 THRU 223 SERIES ARROW PNEUMATICS, INC. REGENERATIVE DRYER DIVISION 2111 WEST 21ST STREET BROADVIEW, IL 60155 708-343-9595 708-343-1907

More information

SYSTEM DESIGN REQUIREMENTS

SYSTEM DESIGN REQUIREMENTS P a g e 1 SYSTEM DESIGN REQUIREMENTS WFC-S SERIES WATER-FIRED SINGLE-EFFECT ABSORPTION CHILLERS / CHILLER-HEATERS Yazaki WFC-S Series water-fired chillers and chiller-heaters are available with nominal

More information

Installation, Operation and Maintenance

Installation, Operation and Maintenance Bulletin No. 534 Installation, Operation and Maintenance Unfired Steam Generators (Series RB) Horizontal USG Vertical USG Disclaimers This Installation, Operation, and Maintenance Manual is intended to

More information

Silhouette. Feedwater Heater. Boiler Feedwater

Silhouette. Feedwater Heater. Boiler Feedwater Roth Roth Low Low Silhouette Silhouette TRAY DEAERATORS Boiler Boiler Feedwater Feedwater Heater Heater Capacities Capacities to to 50,000 50,000 lb/hr lb/hr Model RDTV-150-5-1-2 vertical tray type deaerator

More information

Strategic Alignment Network wide Steam Trap Monitoring System

Strategic Alignment Network wide Steam Trap Monitoring System Track 11, Session 2 Strategic Alignment Network wide Steam Trap Monitoring System James Zellander Energy Manager, Birmingham and Tuscaloosa VA August 16, 2017 Tampa Convention Center Tampa, Florida Objectives

More information

Industrial Fiberglass Specialties, Inc. 521 Kiser Street Dayton, OH Tel: Fax:

Industrial Fiberglass Specialties, Inc. 521 Kiser Street Dayton, OH Tel: Fax: 06-26-00 Page #1 of 6 This guide provides specific information about the material requirements, design criteria, assembly and testing methods recommended to assure a successful steam condensate return

More information

Inverted Bucket Steam Traps

Inverted Bucket Steam Traps INSTALLATION AND MAINTENANCE INSTRUCTIONS IM-2-00-US December 201 Inverted Bucket Steam Traps Safety Information Safe operation of these products can only be guaranteed if they are properly installed,

More information

Media Service Instructions 1500 Series BAT Media Plants

Media Service Instructions 1500 Series BAT Media Plants R Media Service Instructions 1500 Series BAT Media Plants J-500 MEDIA SERVICE Read these instructions and perform every step. After servicing 2 or 3 installations, you will only have to refer to these

More information

Liquid Drainers LIQUID DRAINERS

Liquid Drainers LIQUID DRAINERS Liquid Drainers 206 Liquid Drainers Model/Series Type Body Material PMO Sizes Connection Page No. (PSIG) WLDE Float Ductile Iron 200 1 1 /2, 2, 2 1 /2 NPT WLDES Float Cast Steel 300 2 1 /2 NPT, SW, FLG

More information

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C)

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-315(C) Models 51, 51-S and 53 Boiler Water Feeders Models 51-2, 51-S-2 and 53-2 Feeder Cut-Off Combinations McDonnell & Miller Installation & Maintenance Instructions MM-315(C) OPERATION Maximum Water Supply

More information

Kirsner Consulting Engineering, Inc. for BP 4/19/2010. Chapter 10. Water in Steam Lines (This is the BP title in existing Manual)

Kirsner Consulting Engineering, Inc. for BP 4/19/2010. Chapter 10. Water in Steam Lines (This is the BP title in existing Manual) Chapter 10. Water in Steam Lines (This is the BP title in existing Manual) When saturated steam gives up heat, it turns to water, more commonly referred to in steam parlance as condensate. Thus, as saturated

More information

Operation & Maintenance Manual

Operation & Maintenance Manual (Vertical Model) Semi-Instantaneous Water Heater Steam to Water Design Manual # 9636-0550 Rev. C Operation & Maintenance Manual 340 West 8 th Street Peru, IN 46970 PH: 765-472-3351 FX: 765-472-3968 www.thrushco.com

More information

INSTALLATION & MAINTENANCE MANUAL EZ PLATE INSTANTANEOUS WATER HEATER

INSTALLATION & MAINTENANCE MANUAL EZ PLATE INSTANTANEOUS WATER HEATER INSTALLATION & MAINTENANCE MANUAL EZ PLATE INSTANTANEOUS WATER HEATER Installation and service must be performed by a qualified service installer, service agency or qualified plumbing contractor. IMPORTANT:

More information

Phoenix C 1 GPM - Membrane Based Portable Lube and Hydraulic Oil Purifier Cart

Phoenix C 1 GPM - Membrane Based Portable Lube and Hydraulic Oil Purifier Cart IMPORTANT: READ THIS MANUAL THOROUGHLY BEFORE INSTALLING AND OPERATING UNIT. INSURE THERE IS A PARTICULATE FILER ELEMENT INSTALLED IN PARTICULATE HOUSING BEFORE STARTING. With Optional Aquatrex Moisture

More information

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018

STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS. July, 2018 STEAM SYSTEMS TOP SAFETY ITEMS FOR STEAM OPERATIONS July, 2018 Inveno Engineering LLC Tampa, Florida www.invenoeng.com kelly.paffel@invenoeng.com 239-289-3667 graham.thorsteinson@invenoeng.com 404-375-0785

More information

Unfired Steam Generators (Series RB) Installation, Operation and Maintenance

Unfired Steam Generators (Series RB) Installation, Operation and Maintenance Unfired Steam Generators (Series RB) Installation, Operation and Maintenance Horizontal USG Vertical USG 534-EN Please read and save these instructions Disclaimers This Installation, Operation, and Maintenance

More information

SAS Steadyair Make-Up Air Units Technical Guide

SAS Steadyair Make-Up Air Units Technical Guide TGSAS-3 SAS Steadyair Make-Up Air Units Technical Guide A COMPLETE AIR TEMPERING PACKAGE FOR COMMERCIAL, INSTITUTIONAL, AND INDUSTRIAL APPLICATIONS S ince 1875, the L.J. Wing Company has been a leader

More information

CL64T INDUSTRIAL TOTE WASHER

CL64T INDUSTRIAL TOTE WASHER Item # Quantity C.S.I. Section 11400 STANDARD FEATURES Selectable Speed 4, 5, 6 feet/minute Opti-RinSe system Rapid return conveyor drive mechanism Insulated hinged double doors with door interlock switches

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

Steam Systems 101. Understanding Your Energy Systems Better. May 5, 2016

Steam Systems 101. Understanding Your Energy Systems Better. May 5, 2016 Steam Systems 101 Understanding Your Energy Systems Better May 5, 2016 Introductions Background in Heating/Power plants associated with large industrial and central plants associated with campus distribution

More information

How to Trap: Troubleshooting

How to Trap: Troubleshooting How to Trap: Troubleshooting Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less energy consumed means

More information

Above Ground Fuel Tank Requirements

Above Ground Fuel Tank Requirements FIRE DEPARTMENT in cooperation with Above Ground Fuel Tank Requirements The purpose of this document is to provide information about general Fire Code requirements for above ground storage within the unincorporated

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

GASEOUS HYDROGEN SYSTEMS

GASEOUS HYDROGEN SYSTEMS CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall

More information

Contact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone

Contact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone Contact Information Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone 509 335 9300 steve_potratz@wsu.edu WSU Utilities WSU primary systems are all based on district type

More information

Form 2143 Date: 4/3/03 Repl: 2/1/99 BRYAN STEAM LLC. Installation and Operating Service Manual BOILER FEED SYSTEM

Form 2143 Date: 4/3/03 Repl: 2/1/99 BRYAN STEAM LLC. Installation and Operating Service Manual BOILER FEED SYSTEM 0 Form 2143 Date: 4/3/03 Repl: 2/1/99 BRYAN STEAM LLC Installation and Operating Service Manual BOILER FEED SYSTEM INSTALLATION AND OPERATION SERVICE MANUAL BOILER FEED SYSTEM Bryan Steam LLC 783 North

More information

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL Section 23 20 00 FLUID SYSTEMS EQUIPMENT PART 1 GENERAL 1. CHILLERS Page 23 20 00-1 A. Provide chiller packages with centrifugal compressors, or screw compressors, and water cooled condensers. B. Design

More information

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton G Series ENCASED/UNCASED AIR COILS Geothermal/Water Source Heat Pumps R-410A Refrigerant 2- Ton Dimensional Data G Series Air Coils Installation ti Manual Installation Information Maintenance IM1018AG1

More information

How to Trap: Steam Tracer Lines

How to Trap: Steam Tracer Lines How to Trap: Steam Tracer Lines 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information