APPLICATION GUIDELINES

Size: px
Start display at page:

Download "APPLICATION GUIDELINES"

Transcription

1 APPLICATION GUIDELINES HUMIDIFYING EQUIPMENT SELECTION PART 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 1

2 Table of Contents Purpose... 3 Summary... 3 Steam Humidifier Specification... 3 Evaporative Type Humidifiers ) Water Spray ) Absorbent Medium ) Evaporative Pan... 4 Steam Type Humidifiers ) Steam Grid or Pipe ) Steam Cup Type ) Dry Conditioned Steam... 5 a) History... 5 b) Separator... 5 c) Drain Connection... 7 d) Temperature Switch... 7 e) Re-evaporation Chamber... 7 f) Non-Ducted (Area) Type... 8 g) Control Valve Design h) Valve Operator i) Steam Distribution Manifolds j) Manifold Piping Adaptors k) Steam Discharge Holes l) Steam Trap Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

3 Purpose The job of a humidifier is to introduce water vapor into an air stream or a space to control relative humidity (RH) in a specific space. How the water vapor is introduced is critical to the reliability and exactness of control of RH. This paper will describe the manner of operation, examine the effectiveness of control, and critique the virtues of various types of humidification equipment available for larger scale commercial, institutional, and industrial environment control applications. A properly designed humidifier is an integrated control system composed of several discrete components each with a unique but complimentary function. The components must be specified and provided as a fully integrated and complete system or the humidifier may not control relative humidity properly, and it may deposit water in ducts and/or humidified spaces. Summary Water spray and water saturated medium types are slow to react to RH changes. They use energy to evaporate water adding to the heating system load. Water absorption may not be complete, so water may collect in the duct or droplets may be carried into the humidified space. Dust from mineral solids in the water may be entrained in the air and deposited in ducts and humidified spaces or deposited on the absorbent medium requiring frequent and costly maintenance. Water lying in ducts or on the medium promotes bacterial and fungal microorganism growth, and thusly aseptic conditions may exist in the air distribution system and be established in the humidified spaces. Evaporative pan types are limited in capacity, slow to respond to RH change, and they use energy from the heating system to evaporate water. Dissolved minerals concentrate in the water and deposit in a hard adherent and insulating layer on pan surfaces. This causes loss of capacity, consequently maintenance cost is high. Microorganisms may grow in the water stored in the pan and be transmitted to the humidified spaces by the air stream thereby causing aseptic conditions. Dry conditioned steam types introduce hot dry steam (water vapor) directly into the air stream or space where it is thoroughly mixed with the air and absorbed rapidly without using heat from the air. The amount of steam injected can be changed immediately and controlled precisely, so response to RH change is quick, thus close RH control is assured. Steam contains no mineral contaminants, so solids are neither entrained nor deposited. Steam temperature is high, therefore microorganisms cannot grow, so only sterile water vapor is added to the air. Installed cost per unit of moisture, and maintenance costs are lowest of all types. Especially where close control of RH is required, dry conditioned steam is best on all counts. Steam Humidifier Specification The steam humidifier shall have a thick wall cast iron or stainless steel separator with two stages of 180 deg. turn baffles and an integral full flow high pressure steam jacketed re-evaporation chamber containing stainless steel silencing medium. The steam control valve shall be mounted integral to the separator, and the valve plug shall be in the high pressure steam space. It shall be a long, C\v stroke, wide flow rangeability valve with a parabolic modified linear characteristic plug. The valve shall adapt to mounting any available industrial grade operator type (pneumatic, electric motor, hydraulic, or electric solenoid) without disconnecting plumbing. Capacity also may be changed by replacing valve plug and seat without changing or disconnecting plumbing. The steam distribution manifold shall be steam jacketed, have a stainless steel mesh screen full length silencer, and have aerodynamic shape and small cross sectional area to minimize air duct pressure drop. A suitably sized strainer shall be supplied for mounting in the steam inlet to remove solids. A fail open (inverted bucket) steam trap with capacity of 20% of maximum steam flow shall be supplied for mounting at the separator drain connection with a large drain leg to collect and store start-up load and slugs of condensate for drainage by the steam trap. A temperature switch shall be supplied to prevent control valve opening before metal system components are heated to steam temperature. Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 3

4 Evaporative Type Humidifiers These types either spray water mists into the air stream for evaporation or the air stream flows across an exposed surface from which the air evaporates water. Therefore, all use energy from the air stream to evaporate water thus reducing air temperature and increasing heating system loading. 1) Water Spray (Fig. 3-1) Water under pressure flows through a nozzle or many nozzles discharging as a fine mist into an air stream. The air stream evaporates the water, and the resultant water vapor is absorbed into the air. About 1000 Btu of heat is removed from the air to evaporate each pound of water (540 Kcal/Kg). Air dry bulb temperature is reduced, and the heating system is taxed further to replace lost heat. Evaporation is slow, so the system doesn t respond quickly to RH changes, and control is erratic. All water contains some amount of dissolved mineral solids. Evaporation releases minerals from solution as an adherent solid which may cling to nozzles and ducts or disperse in the air as fine dust. Fig Water Spray Method Mineral buildup on nozzles may clog reducing flow capacity and forcing expensive shutdown for cleaning. Mineral dust settles on duct surfaces and is transported to humidified spaces to settle on exposed surfaces and be breathed by people causing respiratory problems. Dust increases maintenance cleaning costs. Water not evaporated by the air and dripping from nozzles falls to the duct bottom or coats exposed metal equipment causing corrosion and decay and expensive downtime and parts cost for replacement. Bacteria and algae in the water multiply causing odor and sanitation problems, and bacteria are conveyed into humidified spaces. 2) Absorbent Medium An air stream flows across an expansive exposed absorbent medium surface, from which water is evaporated and absorbed by the air. This method has problems similar to the spray method. However, the surface area necessary for evaporation of large quantities of water vapor is excessive. This method is not practical for high capacity applications. 3) Evaporative Pan (Fig. 4-1) An air stream passes over a large area exposed surface of a pan shaped water reservoir. Water in the pan is heated by electrodes or heating coils to prepare it to be evaporated and absorbed by the air stream. Since heat is removed from the air for water evaporation, the heating system loading is increased to maintain air temperature. Evaporation is somewhat faster than with water spray, but response to RH change still is quite slow, and precise stable control is not probable. Dissolved solids concentrate above sustainable levels in the pan eventually leaving solution as an adherent mass. This mass clings to and solidifies on electrodes which may result in burn out requiring the system to be shut down periodically for cleaning. Fig Evaporative Pan Method Hot water in the pan is a perfect breeding ground for all manner of microorganisms contained in the water supply. Frequent cleaning is required to prevent odors and contamination of ducts and humidified spaces. High capacity applications would require huge pans and heating elements, so this type also is limited to small and medium size systems. 4 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

5 Steam Type Humidifiers Dry conditioned steam humidifiers distribute and mix superheated steam uniformly across a duct or into a space. The water vapor is dry, therefore it is absorbed quickly, its flow rate can be adjusted rapidly and accurately, and already being a vapor, it does not require heat from air for evaporation. Consequently, RH is readjusted promptly and accurately, control is stable, and no heating load is added to the system. Steam contains no minerals, and it is sterile, so no minerals and dust are deposited or distributed and no micro-organic or bacterial growth is supported or conveyed. Maintenance costs are low, and additional health hazards are not promoted. 1) Steam Grid or Pipe (Fig. 5-1) The system includes a separator/header and multiple dispersion tube assembly packaged with control valve, strainer, steam supply drip trap, and one or two header drain traps. The tubes are spaced evenly in the duct or air handler so that steam may be distributed across the duct (or AHU) cross section. Dry steam passes from the header into each of the dispersion tubes and flows through nozzles which extend from the center of each tube, before discharging through orifices into the airstream. Each system is intended to provide uniform distribution and shortened wettable vapor trail. Condensate from the header drain traps cannot be lifted or discharged into a pressurized return system. 2) Steam Cup Type (Fig. 5-2) Wet steam is injected through a cuplike apparatus in the bottom of the duct. Steam flows into the cup from an inlet on two sides. Moisture may fall to the bottom of the cup for removal, but water usually is entrained in the steam in a mist which does not separate, therefore moist steam enters the duct. The steam flow is not distributed well in the air stream, so the water is not absorbed completely, and it drops out to the bottom of the duct where it causes corrosion, microbe growth and odors. A steam type humidifier must be designed so only perfectly dry steam is discharged into the duct. Fig Steam Grid Type 3) Dry Conditioned Steam How well any one type of humidifier may perform depends on the design of the component parts and their functioning reliably, accurately, and responsively as a system. To illustrate the importance of each component and its integration into a system, we compare Armstrong s design approach with that of two typical competitors. Figure 5-2. Steam Cup Type a) History The first dry conditioned steam humidifier was developed by Armstrong to solve a problem associated with the crude separator and steam trap systems used to supply steam for humidifying paper making production and storage spaces. The Separator/Trap system could not completely dry steam, and consequent water carryover caused spitting of hot water droplets into the humidified space, onto people, machinery and product. To solve the problem, Armstrong designed a more efficient separator with an integral large volume re-evaporation chamber downstream of the control valve which superheated the full flow of steam assuring that only dry steam was injected into the space. This separator is the heart of any humidifier and the point at which comparisons begin. b) Separator (Fig. 6-1) The purpose of a separator is to ensure that all entrained water is removed so that maximally dry steam is carried to and through the control valve. An effective separator must have a large volume with a wide cross section to reduce steam velocity and effective internal baffles to change flow direction abruptly. Low velocity and abrupt directional change fling water from the steam and direct it to an integral drain at the bottom for removal by a steam trap. Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 5

6 Armstrong Design Armstrong features a large volume and wide cross section thick wall cast iron or fabricated stainless steel separator with two baffle stages. One baffle is immediately after the steam inlet. The U shape causes abrupt 180 changes in flow direction and splits the steam into two streams before passing into the large wide separator body. The velocity decrease and direction change cause water droplets to separate from steam and fall to the drain at the bottom. More condensate forms on the separator walls as heat is lost to outside air, and the amount formed depends on the thickness and thermal conductivity of separator wall material. Thick cast or formed walls minimize heat loss and condensate formation. If volume and cross section of the separator are too small, velocity isn t reduced sufficiently to permit water to fall or condensate to trickle down the walls. Instead the rapidly flowing steam picks up moisture and carries it to the steam outlet. Even though our separator is large, Armstrong uses a second stage of baffle to reduce carryover to a minimum. Competitive Designs (Fig. 6-2 and 7-1) Both use low cost thin wall formed and welded stainless steel separators with smaller volumes and cross sections and a single stage baffle. In the Spirax-Sarco design, the steam inlet passes through a nozzle at the bottom, away from the discharge at the top. The steam flow changes direction in order to exit the separator. In the Dri-Steem design, steam enters the separator at the bottom. Directly above is a plate with downward baffle projections. The steam is directed centrifugally across the baffles and out to the walls. The centrifugal flow and agitation of the baffles drop water to the drain. In both separators, most steam is channeled up the side wall where heat flows quickly from the steam through the thin wall to outside air. The resulting condensate must slide down the wall to the drain. Small volume and cross section induce high velocity steam flow up the wall carrying moisture with it to the outlet. If there is not a second outlet baffle stage to help remove this moisture, so it continues to the valve where it wears metal parts. Fig Armstrong Steam Separator Fig Spirax-Sarco Separator Fig Dri-Steem Separator 6 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

7 c) Drain Connection Condensation does not flow smoothly at any time. Flow is caused by friction as fast moving steam moves across the water surface pulling it along in surges. Modulating or intermittent valve opening also varies steam flow and causes condensate surges. The drain connection and piping should be large and long enough to store condensate until pressure builds up to increase steam trap capacity on start-up and to handle the surging slugs at all times. Otherwise, condensate may carry over or the trap must be grossly oversized and unreliable during periods of low flow. Armstrong separators have 1, 1Z v, and 2 inch connections through a range of 5 separator sizes, whereas the competitors provide ¾ inch connection through a range of 5 sizes from Dri-Steem and only two sizes from Spirax-Sarco. In addition, Armstrong suggests a minimum 6 inch (15 cm) vertical drip leg before the takeoff to the horizontally mounted steam trap. d) Temperature Switch At start-up, condensate forms as the many metal system components heat to steam temperature. Total metal system weight doesn t vary much regardless of separator material, therefore start-up condensate load is about the same with all separator designs. The steam supply piping from the isolation valve to the humidifier must be heated and this often represents the majority of condensate generated during start-up. Spitting of water from the manifold is most likely on start-up if the control valve is allowed to open before the system heats up to steam temperature. Armstrong suggests installing a temperature switch to prevent premature valve opening. All manufacturers offer a switch as an accessory. e) Re-evaporation Chamber Water passing through the control valve should be evaporated before it enters the distribution manifold. This is done best in an integral large volume chamber located at the valve outlet inside the separator body. All low pressure steam and condensate from the valve should pass through the chamber which is surrounded by high pressure, higher temperature steam. Heat from the higher temperature steam re-evaporates condensate and superheats all low pressure steam ensuring that only perfectly dry steam enters the distribution manifold. Velocity through a throttled valve is high, consequently humidifier noise level may also be high. Many humidifiers are used in quiet hospitals, buildings, and office spaces in which a noisy whistling valve can be irritating and distracting, so the chamber should be filled with a stainless steel silencing medium. Armstrong Design The chamber is located well within the separator body almost surrounded by high pressure steam. The large chamber at the valve outlet causes decreased velocity, so water is not carried through. All water is evaporated and all steam is superheated, so only dry steam enters the distribution manifold. The chamber is filled with a stainless steel wool silencing medium. Competitive Designs The control valve in both designs is external to the separator, therefore flow from the valve outlet is not directly into and through a re-evaporation chamber. Spirax-Sarco offers no chamber for either the size 150 or 200 separators. It depends entirely on the manifold steam jacket to dry and to superheat the low quality steam before it is injected into the air steam. With high steam velocity at the valve outlet, most water is entrained by turbulent flow through the valve and into the manifold. Low quality steam enters the manifold, and the manifold s high pressure steam jacket must dry and superheat the mixture before it is discharged into the air. The probability of water spitting into the duct is high. Spirax-Sarco design also does not have silencing medium directly after the valve, therefore valve noise may be transmitted throughout the system. Dri-Steem design doesn t have a re-evaporation chamber. (See Fig. 7-1). It depends entirely on the manifold steam jacket to dry and to superheat the low quality steam before it is injected into the air stream. The silencer causes a pressure drop in the nearly atmospheric pressure steam entering the manifold. Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 7

8 f) Non-Ducted (Area) Types Area type humidifiers discharge directly into warm air in the humidified space, therefore there is no manifold to re-evaporate water or to superheat steam. Any ejected hot water is spit directly into the space to fall on people, equipment, and product. To prevent spitting, humidifier discharge must be dry superheated steam only. Armstrong Design (Fig. 9-1) The Armstrong standard duct type design has a reevaporation chamber ensuring that only dry superheated steam is discharged. It does not depend on a steam jacketed manifold to dry steam, therefore no additions or alternations are necessary to use the same separator in area type applications also. Competitive Design (Fig. 9-2) Dri-Steem provides a single baffle plate and a dispersion port in the separator which is mounted after the valve. One separator size is offered for all applications. Dryness should be acceptable. Maximum operating pressure is limited to 15 psig (1 bar). There is no silencing media in this design so valve noise will be heard in the humidified space. Maximum steam operating pressure is 15 psig (1 bar) in the smallest valves and less in larger sizes. The position of the valve relative to the separator dictates that steam and condensate in the separator is at atmospheric steam pressure. An F&T trap is suggested and the condensate must be drained by gravity to a return line with no back pressure. g) Control Valve Design Just as the separator and re-evaporation chamber are essential to ensure dry steam in the duct or space, a properly designed valve and operator are essential for accurate, stable, and responsive control. Area type applications discharge directly into a huge volume of warm air. Steam mixes with and is absorbed by dry warm air quickly, so acceptable control of RH can be achieved with on-off solenoid type valves. However, duct type humidifiers discharge steam into a limited volume of colder air traveling at high velocity. Temperature can be as low as 55 F (13 C), so steam absorption is slow and unreliable unless absolutely dry steam is introduced in exactly the amount necessary for conditions of the moment. Otherwise, water may drop out and collect in the duct, and RH control will be erratic. Properly placed and designed valves are needed. Fig Armstrong Area Type The valve should be mounted integral to the separator with valve plug and seat surrounded by a high pressure steam jacket and with its discharge direct into the re-evaporation chamber. The Fig Armstrong Area Type main mass of body, valve plug and seat of the integral mount valve is in a high pressure steam space not exposed to outside air, thus added condensate isn t generated in the valve. Additional condensation occurs in externally mounted valves and the external piping joining them to separator and manifold. The added field piping raises installation cost for external mount valves. Steam flow must be readjusted precisely and repeatedly to control RH accurately and with stability. Humidifier maximum capacity is selected for the driest air and highest heating load condition, yet a humidifier must operate most of the time when outside air is warmer and contains more moisture. Consequently, a control valve must control steam flow accurately and with stability despite widely changing requirements. 8 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

9 The valve should be reverse acting and normally closed. Steam pressure assists in closing reverse acting valves, hence heavy springs are not needed to aid closure. The valve operator encounters less resistance to movement in either direction, so hysteresis is slight, and positioning accuracy and repeatability are high. The valve should have modified linear output characteristics (Fig. 10-1) rather than equal percentage. Modified linear output changes flow relative to incremental position change as an equal percentage of actual flow rate regardless of valve position. This promotes stable control at all flow rates, whereas equal percentage valves do not have such favorable characteristics at low flow rates. The operation will resemble on-off control at low flows, and RH control will be erratic. Armstrong Design (Fig. 10-2) The valve is mounted integral to the separator with the valve internals surrounded by high pressure steam, and it discharges directly into the large volume full flow re-evaporation chamber. It has extremely wide rangeability because of a specially designed ¾ inch stroke parabolic plug with modified linear characteristics. This coupled with reverse action makes the valve stable and accurate with excellent modulating action over a wide range of flow requirements. The valve may be fitted with a wide variety of manufacturer s valve operators without disconnecting or altering any plumbing. Capacity changes are made simply by replacing only the plug and orifice which also is done without disturbing the plumbing. Competitive Design (Fig. 11-1) Both competing designs employ an external globe type valve field mounted in piping between the separator and manifold, thus both the valve body and the pipe are exposed to surrounding air and subject to condensate formation. The valve is an outside purchased commercial grade direct acting zone control valve with short stroke and equal percentage characteristics. It has limited flow rangeability and controls erratically at low flows. Any greater or more reliable capacity change requires removing the valve and altering piping to accept a different size valve. Fig Modified Linear Valve Characteristics The Control Valve Fig Parabolic Plug Metering Valve Fig Pneumatic Operator Characteristics Fig Positioning Hysterisis Fig Globe Valve Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 9

10 h) Valve Operator Accurate and stable control of RH depends on quick, accurate, and repeatable change of steam flow in response to RH control signals, and this depends on fast, accurate and repeatable valve positioning. To accomplish this, a pneumatic operator must have a large diaphragm to permit using heavy springs which stabilize positioning and which prevent hysteresis from mechanism drag and flow velocity effects that destroy positioning accuracy and repeatability. The positioner stroke must be long to match the valve and preserve its rangeability. Armstrong Design Armstrong has designed its own pneumatic operator with a 12 square inch (34mm2) diaphragm, full ¾ inch stroke, and low drag. It is designed to match and enhance the superb characteristics of its specially designed valve. The combination perfectly compliments the rest of the humidification control system. Competitive Design Both use the inexpensive small diaphragm operator supplied with the standard low grade valve. It has only ½ inch stroke, and is not powerful enough to overcome valve drag, velocity effects, and the heavy spring of the directacting valve. Positioning accuracy and repeatability are poor. Maximum steam operating pressure for the standard pneumatic operator is 35 psig (2.4 bar). i) Steam Distribution Manifolds (Fig & 12-2) A manifold should be steam jacketed to prevent condensation and to provide final drying and superheating of steam before it is injected into the duct. It should have enough holes so that steam is distributed equally across the duct and is not injected as distinct high velocity jet streams which require long open duct lengths to ensure complete mixing and vapor absorption before moisture forms on duct surfaces and other equipment. The manifold should have an internal stainless steel mesh silencer along its full length to prevent high velocity noise transmission. The profile should be aerodynamic, and the face height should be limited to minimize air pressure drop. Armstrong s design incorporates all of these features, and its face height causes 40% less air pressure drop. The competitive designs don t have aerodynamic cross section, so they contribute additional pressure drop. j) Manifold Piping Adaptors Steam pressure at the manifold inlet is near atmospheric. System capacity is reduced by any restriction between the control valve and the manifold, therefore the transition adaptor should have an ID as large as the manifold pipe. The sealing O rings should be on the outside of the manifold tube and should have an external compression fitting which will allow retightening of the joint over many years. Armstrong Design (Fig. 12-3) Fig Distribution Manifold The manifold inlet pipe slips inside the overly large separator outlet. The O ring on the outside of the tube is sealed by a compression nut which screws into a male thread on the separator outlet. The manifold tube is schedule 5 pipe which will not distort from the O ring compression and will maintain the same ID from the separator outlet through the manifold length. The rigid tube permits retightening of the O ring allowing resealing of any leaks over many years. Fig Armstrong Distribution Manifold Fig Armstrong Adaptors 10 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information.

11 Competitive Design (Fig. 13-1) Dri-Steem uses an adaptor which screws into the control valve outlet. The adaptor has a larger ID than the manifold tube which slips inside it. The manifold tube is sealed by friction as it is slipfitted inside two O rings within the adaptor. The slip-fit assembly procedure may damage the O ring initially, nonetheless the construction does not allow retightening of the joint after leaks begin at any time. For this reason, the manufacturer suggests changing the O ring every 2 to 3 years. To replace the O ring, the entire humidifier must be removed from both the steam and return piping. k) Steam Discharge Holes (Fig & 13-3) Discharge from Armstrong s manifold is through holes drilled into the face, and the manifold is mounted so that steam is ejected into the oncoming air stream. Tests show that the steam is split into two streams, one over the top and one under the bottom of the manifold. The splitting tends to disperse and mix the steam and air quickly enhancing absorption and preventing long vapor trails. Nozzles used in the past whistled because of steam velocity at high flow rates, and they tended to support separate longer vapor trails. Dri-Steem uses nozzles alternately angled upward and downward. This creates separate distinct vapor trails for each nozzle delaying mixing and complete absorption thereby lengthening the overall vapor trail and increasing the probability of water settling on air system components. l) Steam Traps The steam trap should be a fail open mechanical type which will not permit water backup under any condition. Only the Inverted Bucket type qualifies. The trap capacity should be 20% of maximum steam flow. Armstrong supplies an IB trap (Fig. 14-3) sized individually to match the capacity of each size of humidifier. Both competitors supply a ¾ inch F&T trap regardless of the humidifier capacity. (Fig. 14-4) The trap may be too small for the largest humidifier or unnecessarily large for the smallest, and the F&T can fail closed letting water back into the humidifier. Fig Dri-Steam Adaptors Fig Manifold Discharge Fig Manifold Discharge Fig Armstrong Steam Trap Fig Dri-Steem Steam Trap Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. 11

12 INTELLIGENT SOLUTIONS IN STEAM, AIR AND HOT WATER Armstrong International 816 Maple Street, P.O. Box 408, Three Rivers, MI USA Phone: (616) Parc Industriel Des Hauts-Sarts, B-4040 Herstal/Liege, Belgium Phone: (04) Armstrong International, Inc. APP-508-EN Printed in USA - 3/17

HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems

HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems HumidiPack,HumidiPackPlus and HumidiPackPlus CF Steam Humidifier Systems HumidiPack CF HumidiPack CF offers the performance of HumidiPackPlus without the need of jacketing steam on pressurized steam applications.

More information

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG Suitable for a wide range of applications Steam Injection humidifiers from DRI-STEEM use steam from an external source, such as an

More information

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual

Steam Injection Humidifiers for use with steam boilers. Installation, Operation, and Maintenance Manual Steam Injection Humidifiers for use with steam boilers Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. Where to

More information

Steam Injection. Humidification system

Steam Injection. Humidification system Steam Injection Humidification system Standard and CLEAN-STEEM TM models suitable for a wide range of applications DRI-STEEM s Steam Injection humidifiers use steam from an external source, such as an

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

APPLICATION GUIDELINES STEAM MAIN DRAINAGE

APPLICATION GUIDELINES STEAM MAIN DRAINAGE APPLICATION GUIDELINES STEAM MAIN DRAINAGE 1) Steam Main Drip Leg Dimensions 2) Types of Warm-Up a) Supervised b) Automatic 3) Spacing of Drip Legs 4) Low Pressure Drainage-- Sizing Traps for Automatic

More information

Insty-Pac Steam Humidifiers

Insty-Pac Steam Humidifiers IP-1 Insty-Pac Steam umidifiers The PURE umidifier Co. Insty-Pac (patent no. 6,065,740) steam injection humidifier is jobengineered to assure highly efficient steam release into the air stream. Each humidifier

More information

High-Pressure Atomizing System

High-Pressure Atomizing System High-Pressure Atomizing System PR0DUCT CATALOG Energy-efficient humidification Reduces cooling load Reduces water waste DRI-STEEM High-Pressure Atomizing System installed in an air handler Pure pressurized

More information

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual Steam Injection Pressurized Steam Humidifiers Installation, Operation, and Maintenance Manual ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner. DRI-STEEM technical

More information

The Ultimate in Direct Contact Water Heating. by Thermal Engineering of Arizona, Inc. An Inc. 500 Company

The Ultimate in Direct Contact Water Heating. by Thermal Engineering of Arizona, Inc. An Inc. 500 Company SWERHMTER The Ultimate in Direct Contact Water Heating - by Thermal Engineering of Arizona, Inc. An Inc. 500 Company TEA'S "S U P E R H E ATE R" When high volumes of hot water are needed, Thermal Engineering's

More information

THE SIX STEPS OF HUMIDIFICATION DESIGN

THE SIX STEPS OF HUMIDIFICATION DESIGN THE SIX STEPS OF HUMIDIFICATION DESIGN To help you better understand the humidification process, this issue of Engineering Humidification will walk you through the basic steps of humidification system

More information

THE THERMOSTATIC STEAM TRAP

THE THERMOSTATIC STEAM TRAP THE THERMOSTATIC STEAM TRAP The purpose of any steam trap is to discharge, promptly, all condensate (as well as air and other non-condensible gases) without discharging live steam. Since steam is a vapor

More information

Discover the Difference

Discover the Difference Discover the Difference In virtually every application, Scientific Dust Collectors are sized to operate at air-to-cloth ratios significantly higher than those required by less sophisticated dust collectors.

More information

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT

Technical Data TYPE T14 & T14D TEMPERATURE PILOT SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY SD 4511A T14 PILOT Technical Data SD 4511A SPENCE ENGINEERING COMPANY, INC. 150 COLDENHAM ROAD, WALDEN, NY 12586-2035 TYPE T14 & T14D TEMPERATURE PILOT PRINTED IN U.S.A. SD 4511A/9811 5 13 /16 D 4 7 /8 1 13 /16 T14 PILOT

More information

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual

Steam Injection Pressurized Steam Humidifiers. Installation, Operation, and Maintenance Manual Steam Injection Pressurized Steam Humidifiers Installation, Operation, and Maintenance Manual Safety precautions ATTENTION INSTALLER Read this manual before installing. Leave manual with product owner.

More information

Armstrong Cool-Fog Systems

Armstrong Cool-Fog Systems Armstrong Cool-Fog Systems Armstrong International, Inc. is a leading supplier of hydropneumatic fogging systems used for both humidification and evaporative cooling. Its systems were first developed in

More information

Installation and Operation

Installation and Operation Bulletin 544-I Installation and Operation Humidifiers for Air Handling Systems AM-90M, -91M, -92M, -1200M, -93M, -1300M, -94M, -1400M; HEM-90M, -91M, -92M, -1200M, -93M, -1300M, -94M, -1400M; DSA-90, -91,

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION STEAM HUMIDIFIERS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS. Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14

READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS. Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14 READ AND SAVE THESE INSTRUCTIONS OWNER S MANUAL FOR BYPASS AND FAN POWERED HUMIDIFIERS Type Installed: Maintenance page: Small or Large Bypass 12 Water Saver Bypass 13 Fan Powered 14 Includes Safety, Operating

More information

"SXDDR" Series Steam Heat Exchanger Humidifiers

SXDDR Series Steam Heat Exchanger Humidifiers SXDDR-1 Deionized, Demineralized, or Reverse Osmosis Water "SXDDR" Series Steam Humidifiers Looking for an alternative to electrically generated humidification? Concerned about using chemically treated

More information

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers Bulletin 1200/4 (Revised 5/12) Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers INNOVATORS IN HEAT TRANSFER I. INSTALLATION OF HEAT EXCHANGERS A. HEAT EXCHANGER SETTINGS 1)

More information

OIL MIGRATION IN R-12 & R-22 SYSTEMS By: Norman Sharpe Professor, Air Conditioning & Refrigeration Dept., California State Polytechni College

OIL MIGRATION IN R-12 & R-22 SYSTEMS By: Norman Sharpe Professor, Air Conditioning & Refrigeration Dept., California State Polytechni College Service Application Manual SAM Chapter 630-34 Section 1M OIL MIGRATION IN R-12 & R-22 SYSTEMS By: Norman Sharpe Professor, Air Conditioning & Refrigeration Dept., California State Polytechni College INTRODUCTION

More information

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components:

CENTRIFUGAL PUMPS. STATE the purposes of the following centrifugal pump components: Pumps DOE-HDBK-1018/1-93 CENTRIFUGAL PUMPS CENTRIFUGAL PUMPS Centrifugal pumps are the most common type of pumps found in DOE facilities. Centrifugal pumps enjoy widespread application partly due to their

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

THE EVAPORATION AND SPRAY SYSTEMS OF COOLING CREAM 1

THE EVAPORATION AND SPRAY SYSTEMS OF COOLING CREAM 1 THE EVAPORATION AND SPRAY SYSTEMS OF COOLING CREAM 1 W. H. MARTIN, W. J. CAULFIELD, AND A. C. FAY INTRODUCTION The production of butter fat in Kansas in 1934 amounted to 121 million pounds, of which 57

More information

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY

CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY TM READ AND SAVE THESE INSTRUCTIONS CUFFED FAST-PAC EXTERNAL MOUNT MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Flex connectors (by PURE) AHU/duct casing Injection tube Stainless

More information

Ultra-sorb Models LV and LH

Ultra-sorb Models LV and LH Ultra-sorb Models LV and LH Steam Dispersion Panels Installation, Operation, and Maintenance Manual For applications using steam from a boiler or from any DRI-STEEM steam generating humidifier. Overview

More information

DFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE.

DFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE. DFE T ECHNOLOGY As components become smaller, component mixes become more diverse, and board densities continue to increase, the processes of packaging, interconnection, and assembly are challenging the

More information

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers.

.4 Section Ductwork Low Pressure Metallic to 500 Pa..3 ANSI/ARI 640 Commercial and Industrial Humidifiers. Issued 2006/08/01 Section 15751 Humidifiers Page 1 of 7 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Section 01330 Submittal Procedures..2 Section 01780 Closeout Submittals..3 Section 01810 Commissioning..4 Section

More information

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

AIR CONDITIONING. Carrier Corporation 2002 Cat. No AIR CONDITIONING Carrier Corporation 2002 Cat. No. 020-016 1. This refresher course covers topics contained in the AIR CONDITIONING specialty section of the North American Technician Excellence (NATE)

More information

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass

Ball Float Controlled. Thermo Dynamic(TD) Trap Safety Valve Condensate Pump Flash Vessel Moisture Separators Deaerator Head Steam Injector Sight Glass Product of Quality Best Performance Ball Float Controlled Steam Traps Auto Drain Traps Float Valve Air Vent Valves Feed Control Valve Drain Control Valve Thermo Dynamic(TD) Trap Safety Valve Condensate

More information

BYPASS AND POWER HUMIDIFIER OWNER S MANUAL

BYPASS AND POWER HUMIDIFIER OWNER S MANUAL ResearchPr 57 Bypass v2 4/15/03 10:22 AM Page 1 READ AND SAVE THESE INSTRUCTIONS BYPASS AND POWER HUMIDIFIER OWNER S MANUAL Includes Safety, Operating, and Maintenance Instructions and Warranty ResearchPr

More information

HEALTHY CLIMATE HUMIDIFIER

HEALTHY CLIMATE HUMIDIFIER Humidifiers 0,880M /00 HEALTHY CLIMATE HUMIDIFIER OPERATING INSTRUCTIONS FOR MODELS WB-, WB-7, WB-7A, WP-8 & WP-8A Includes Safety, Operating, and Maintenance Instructions Introduction Thank you for your

More information

Yarway Narvik Steam Desuperheater Series 4300 TempLow

Yarway Narvik Steam Desuperheater Series 4300 TempLow For precise and economical control of steam temperature Features and benefits Easy installation Installation in straight, vertical or horizontal pipe. Minimal headroom is required for mounting Only standard

More information

How to Trap: Trap Selection and Safety Factors

How to Trap: Trap Selection and Safety Factors How to Trap: Trap Selection and Safety Factors Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less

More information

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion s Circulate Steam Boost Low- Steam Compress and Mix Gases in Desired Proportion S&K s are used in the process, paper, petroleum, power, gas, and other industries to circulate steam, boost low-pressure

More information

Installation and Testing of Inverted Bucket Steam Traps Manual

Installation and Testing of Inverted Bucket Steam Traps Manual Installation and Testing of Inverted Bucket Steam Traps Manual 307-EN Please read and save these instructions Armstrong IB Traps Installation Before Installing Run pipe to trap. Before installing the trap,

More information

Air-Cooling Evaporators

Air-Cooling Evaporators Air-Cooling Evaporators Types of construction Circuit Configurations Methods of Refrigerant Feed Methods of Air Circulation Methods of Defrost Type of Construction Bare tube Finned Tube Plate-surface Bare

More information

ADVANCE TECHNOLOGIES FOR ADIABATIC COOLING AND HUMIDIFICATION Nortec Humidity, Inc. Fred Valentini Direct Room Systems Regional Manager Randall

ADVANCE TECHNOLOGIES FOR ADIABATIC COOLING AND HUMIDIFICATION Nortec Humidity, Inc. Fred Valentini Direct Room Systems Regional Manager Randall ADVANCE TECHNOLOGIES FOR ADIABATIC COOLING AND HUMIDIFICATION Nortec Humidity, Inc. Fred Valentini Direct Room Systems Regional Manager Randall Potter Regional Manager, Western US Agenda Humidification

More information

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois

PowerPoint Presentation by: Associated Technical Authors. Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois Althouse Turnquist Bracciano PowerPoint Presentation by: Associated Technical Authors Publisher The Goodheart-Willcox Company, Inc. Tinley Park, Illinois Chapter 5 Explain the purpose and operation of

More information

OPTIMIZING PERFORMANCE IN SPRAY OPERATIONS

OPTIMIZING PERFORMANCE IN SPRAY OPERATIONS OPTIMIZING PERFORMANCE IN SPRAY OPERATIONS CONFIRM THAT YOU ARE USING THE BEST NOZZLES AVAILABLE FOR YOUR OPERATION The nozzle is the heart of your spray operation. They are precision-engineered components

More information

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction: Refrigeration Systems Theoretical hours: 2 Practical hours: 2 Units: 6 COOLING TOWERS First 10 minutes: review the last lecture. Then explain the new lecture, solve an example. Last 10 minutes review the

More information

Steam Trap Selection

Steam Trap Selection Steam Trap Selection Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less energy consumed means less

More information

Hoffman Specialty General Catalog

Hoffman Specialty General Catalog Hoffman Specialty General Catalog HS-900E ESP-PLUSTM For computer aided selection of Steam Trap and Regulators, please refer to the Steam Specialty Component Selectors in the Hoffman Specialty website

More information

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU) AIR HANDLERS Central Station (CS3) (Modular AL Frame AHU) Roof Mounted (RT) CONTENTS 1. CS3 Modular Aluminium Frame AHU : Unit Types 2. Casing Structure 3. Blowers and Drives 4. Coils 5. Options and Accessory

More information

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN Air Conditioning Clinic Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 11 LA CROSSE,

More information

Air Handling Units. T F E.

Air Handling Units.  T F E. Air Handling Units Extract from BS EN ISO 15138:2007 Petroleum & natural gas industries- Offshore production installations-heating, ventilation & air-conditioning. A.12.1 Function Installations provided

More information

VIFB Coil Technical Guide

VIFB Coil Technical Guide TGVIFB-4 VIFB Coil Technical Guide VERTICAL TUBE INTEGRAL FACE AND BY-PASS HEATING COILS FOR PREHEATING Since 1875, the L.J. Wing Company has been a leader in providing innovative solutions for diffi cult

More information

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107

TABLE OF CONTENTS STEAM TRAPS INVERTED BUCKET SERIES PAGE FLOAT AND THERMOSTATIC SERIES PAGE THERMOSTATIC THERMODISC B0 26. How to Select All 107 TABLE OF CONTENTS FLOAT AND THERMOSTATIC SERIES PAGE How to Select All 107 C 14 H 8 I 12 X 14 Competitive Changeover 18 THERMOSTATIC 8C 22 9C 2 17C 20 Competitive Changeover 17C 24 Replacement Modules

More information

Wallace & Tiernan Gas Feed Systems V2000 Chlorinator

Wallace & Tiernan Gas Feed Systems V2000 Chlorinator Wallace & Tiernan Gas Feed Systems V2000 Chlorinator Introduction Siemens Water Technologies chlorination equipment has the benefit of 100 years of experience in gas feed technology. V2000 chlorinators

More information

INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. LSIP-EM INSTY-PAC EXTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Tube Support AHU/Duct Injection Tube Strainer Typ.

More information

Solar Still - Improved Distillation

Solar Still - Improved Distillation Solar Still - Improved Distillation Herbert Weidner a Abstract: An analysis of the steam cycle in an humidification-dehumidification desalination system shows that reheating of the air can drastically

More information

INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY

INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY Read and Save These Instructions Sheet No. LSIP-IM INSTY-PAC INTERNAL MOUNT WELDED MULTIPLE TUBE ASSEMBLY INSTALLATION AND ASSEMBLY INSTRUCTIONS Fig. 1 Strainer Secure to AHU/duct casing with 3/8-16 UNC

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA242H WA36H NOTE: Electrical data presented in this manualsupersedes any other data for the above listed models. Bard Manufacturing

More information

Series 1140 and 1141 Temperature Regulators

Series 1140 and 1141 Temperature Regulators Hoffman Specialty Installation & Maintenance Instructions HS-504(E) Series 1140 and 1141 Temperature Regulators! CAUTION FOLLOW ALL INSTALLATION AND OPERATING INSTRUCTIONS. TURN OFF WATER OR STEAM BEFORE

More information

DEFROSTING METHODS Adapted from material originally provided by Kenneth S. Franklin, C.M., Director of Service, Hussmann Corporation

DEFROSTING METHODS Adapted from material originally provided by Kenneth S. Franklin, C.M., Director of Service, Hussmann Corporation EVAPORATOR DEFROSTING: WHEN AND WHY The refrigeration evaporator is a container that provides room for the evaporating refrigerant. The refrigerant receives heat by conduction through the walls of the

More information

THERMOSTATIC EXPANSION VALVES Part 1

THERMOSTATIC EXPANSION VALVES Part 1 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 THERMOSTATIC EXPANSION VALVES Part 1 Revised by Loren Shuck, CMS INTRODUCTION The thermostatic expansion valve (frequently

More information

GORD COOKE. issues associated with humidification and dehumidification systems. In this article, humidification

GORD COOKE. issues associated with humidification and dehumidification systems. In this article, humidification humidification BY GORD COOKE OPTIONS IN STEAM Since the thermal comfort of occupants in buildings is dependent on the amount of moisture in the air, HVAC contractors need to understand proper sizing, installation

More information

CPC PRODUCT DESCRIPTION

CPC PRODUCT DESCRIPTION CPC 40 60 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPC 40-60 compressor is a quiet, complete and readyfor-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

PNEUMATIC & HYDRAULIC SYSTEMS

PNEUMATIC & HYDRAULIC SYSTEMS PNEUMATIC & HYDRAULIC SYSTEMS CHAPTER THREE AIR GENERATION, TREATMENT & DISTREBUTION Dr. Ibrahim Naimi Air preparation For the continuing performance of control systems and working elements it is necessary

More information

Moisture can be very disruptive to a dust. Preventing moisture problems in your dust collector

Moisture can be very disruptive to a dust. Preventing moisture problems in your dust collector As appeared in March 2017 PBE Copyright CSC Publishing www.powderbulk.com Preventing moisture problems in your dust collector Brian Mathews Scientific Dust Collectors This article discusses how moisture

More information

Double Intelligence Two adiabatic humidification methods intelligently combined. Humidification and Evaporative Cooling. humidity.

Double Intelligence Two adiabatic humidification methods intelligently combined. Humidification and Evaporative Cooling. humidity. Double Intelligence Two adiabatic humidification methods intelligently combined Nortec DL-Series Humidification and Evaporative Cooling humidity.com Nortec DL-Series for humidification and evaporative

More information

EVAPORATIVE COOLING AND HUMIDIFICATION. High-Pressure System Wetted Media System

EVAPORATIVE COOLING AND HUMIDIFICATION. High-Pressure System Wetted Media System EVAPORATIVE COOLING AND HUMIDIFICATION High-Pressure System Wetted Media System Energy efficient Provides both direct and indirect evaporative cooling Multiple zone capabilities in air handlers, ducts,

More information

High Capacity Instantaneous Steam Fired Water Heater

High Capacity Instantaneous Steam Fired Water Heater MODEL F High Capacity Instantaneous Steam Fired Water Heater Features Compact High Capacity Design Packaged System Water heater is factory assembled on an all welded steel mounting frame to save time and

More information

Economical and simplified solutions that offer quality and optimum steam trap service.

Economical and simplified solutions that offer quality and optimum steam trap service. Economical and simplified solutions that offer quality and optimum steam trap service. It All Comes Down To Protection Regardless of the temperature and pressure characteristics of steam line drips or

More information

CONDAIR ESCO. Live steam humidifier with 100% steam tight rotary valve. Humidification and Evaporative Cooling

CONDAIR ESCO. Live steam humidifier with 100% steam tight rotary valve. Humidification and Evaporative Cooling CONDAIR ESCO Live steam humidifier with 100% steam tight rotary valve Humidification and Evaporative Cooling Patented precision nozzles ensure condensate-free steam Inner nozzles draw steam from the middle

More information

CPF PRODUCT DESCRIPTION

CPF PRODUCT DESCRIPTION CPF 175 340 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPF 175-340 compressor is a quiet, complete and ready-for-use unit for the production of compressed air in industrial applications. OVERVIEW The CHICAGO

More information

INTELLIGENT SOLUTIONS FOR ADIABATIC COOLING IN DATA CENTERS

INTELLIGENT SOLUTIONS FOR ADIABATIC COOLING IN DATA CENTERS INTELLIGENT SOLUTIONS FOR ADIABATIC COOLING IN DATA CENTERS INTELLIGENT SOLUTIONS FOR ADIABATIC COOLING IN DATA CENTERS GLOBAL EXPERTISE FOR DATA CENTERS As global leaders in energy management and humidification,

More information

1.1 This section applies to air handling units for HVAC Systems.

1.1 This section applies to air handling units for HVAC Systems. AIR HANDLING UNITS GENERAL INFORMATION 1.1 This section applies to air handling units for HVAC Systems. DESIGN REQUIREMENTS 2.1 Design Criteria a. The decision to use modular central station air handling

More information

Cold Energy Saver. Thermal Mass Cycling Refrigerated Air Dryers ( scfm)

Cold Energy Saver. Thermal Mass Cycling Refrigerated Air Dryers ( scfm) aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Cold Energy Saver Thermal Mass Cycling Refrigerated Air Dryers (200-1000

More information

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime.

Mini Pump Trap. Features: n Low maintenance - No leaking seals, impeller or motor problems reducing maintenance and downtime. Armstrong Mini Pump Bulletin AFH-223 The Armstrong mini pump trap is the smallest non-electric solution that can move condensate or other liuids from lower to higher points and from lower to higher pressures.

More information

Bringing Energy Down to Earth

Bringing Energy Down to Earth Liquid Drainers Bringing Energy Down to Earth Say energy. Think environment. And vice versa. Any company that is energy conscious is also environmentally conscious. Less energy consumed means less waste,

More information

INTELLIGENT HUMIDIFICATION. Two adiabatic humidification methods intelligently combined Condair DL. Humidification and evaporative cooling

INTELLIGENT HUMIDIFICATION. Two adiabatic humidification methods intelligently combined Condair DL. Humidification and evaporative cooling INTELLIGENT HUMIDIFICATION Two adiabatic humidification methods intelligently combined Condair DL Humidification and evaporative cooling Efficient low-pressure systems The low-pressure mode of operation

More information

Boiler Basics. Design and operation

Boiler Basics. Design and operation Boiler Basics Design and operation A boiler is an enclosed vessel that provides a means for combustion heat to be transferred into water until it becomes heated water or steam. The hot water or steam under

More information

WATER HAMMER something that never should occur in a steam system

WATER HAMMER something that never should occur in a steam system BEST PRACTICE NO. 11 WATER HAMMER something that never should occur in a steam system 1. STEAM AND CONDENSATE WATER HAMMER Water hammer is never normal in a steam and condensate system, and it is totally

More information

Saving Energy With Evaporative Media

Saving Energy With Evaporative Media Saving Energy With Evaporative Media Introduction In recent years building designers and engineers have been faced with a challenge: to develop buildings that operate more efficiently than ever before.

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

GESTRA Information A 1.7

GESTRA Information A 1.7 Issue Date: 9/06 GESTRA Systems GESTRA Information A 1.7 Automatic Deaeration of -Heated Heat Exchangers Preface For optimum efficiency of steam-heated heat exchangers several requirements should be fulfilled,

More information

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions

S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 0772150/4 IM-P077-02 ST Issue 4 S and SF Inverted Bucket Steam Traps Installation and Maintenance Instructions 1. General safety information 2. General product information 3. Installation 4. Commissioning

More information

HIGH-PRESSURE ATOMIZING SYSTEM. Humidification and adiabatic cooling. Energy efficient Reduces cooling load Multiple zone capabilities

HIGH-PRESSURE ATOMIZING SYSTEM. Humidification and adiabatic cooling. Energy efficient Reduces cooling load Multiple zone capabilities HIGH-PRESSURE ATOMIZING SYSTEM Humidification and adiabatic cooling Energy efficient Reduces cooling load Multiple zone capabilities Preliminary 02071 Advanced, efficient humidification PURE PRESSURIZED

More information

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM BEST PRACTICE NO. 30 WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM Air and noncondensable gases are one of the major problems in a steam system that can cause production

More information

Water Movement in Soils

Water Movement in Soils Water Movement in Soils by DR. WALTER H. GARDNER Professor Emeritus, Washington State University A LIQUID or vapor, water is nearly always moving in the soil. ~ It moves downward after rain or irrigation.

More information

Pulse Jet Baghouse ASTEC PULSE JET BAGHOUSE. for Asphalt Facilities

Pulse Jet Baghouse ASTEC PULSE JET BAGHOUSE. for Asphalt Facilities Pulse Jet ASTEC PULSE JET BAGHOUSE for Asphalt Facilities ASTEC PULSE JET BAGHOUSE FOR ASPHALT MIXING PLANTS Astec baghouses deliver superior performance and efficiency, while helping your plant meet

More information

ChE 441: Paper Manufacture

ChE 441: Paper Manufacture ChE 441: Paper Manufacture Lecture # 13 by Kazi Bayzid Kabir Introduction Paper consists of a web of pulp fibers usually formed from an aqueous slurry on a wire or screen, and held together by hydrogen

More information

How to Trap: Process Air Heaters

How to Trap: Process Air Heaters How to Trap: Process Air Heaters 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information

DRI-STEEM STEAM INJECTION HUMIDIFIERS

DRI-STEEM STEAM INJECTION HUMIDIFIERS READ AND SAVE THESE INSTRUCTIONS DRI-STEEM STEAM INJECTION HUMIDIFIERS Installation Instructions and Maintenance Operations Manual TABLE OF CONTENTS TO THE PURCHASER AND THE INSTALLER Thank you for purchasing

More information

Chapter 2.3: Steam System

Chapter 2.3: Steam System Part I: Objective type Questions and Answers Chapter 2.3: Steam System 1. For industrial process heating, the best quality of steam is: a) dry saturated steam b) superheated steam c) wet steam d) high

More information

CPVS PRODUCT DESCRIPTION

CPVS PRODUCT DESCRIPTION CPVS 20 30 PRODUCT DESCRIPTION The CHICAGO PNEUMATIC CPVS 20-30 compressor is a quiet, complete and ready-for-use unit for the production of compressed air for light and medium industrial applications.

More information

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications

ULTRA-SORB. Installation, Operation, and Maintenance Manual MODEL. Steam Dispersion Panel. For pressurized steam applications READ AND SAVE THESE INSTRUCTIONS ULTRA-SORB MODEL XV Steam Dispersion Panel Installation, Operation, and Maintenance Manual For pressurized steam applications Table of contents MECHANICAL SPECIFICATIONS..................................................1

More information

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S

YARWAY NON-REPAIRABLE DRIP AND TRACER STEAM TRAPS SERIES PB, 29, 129Y AND 29S SERIES PB, 29, 129Y AND 29S Economical and simplified solutions that offer quality and optimum steam trap service FEATURES 29S 29 Thermostatic traps Pressure assisted fail-open design Freeze proof Easy

More information

SKG Advantages. Typical Applications. Typical Installation

SKG Advantages. Typical Applications. Typical Installation The SKG gas fired humidifier by Neptronic uses the latest gas technology to produce steam. On a call for humidity, the combustion blower creates a negative pressure across the combined gas valve with venturi

More information

Changes of phase usually involve a transfer of energy Evaporation

Changes of phase usually involve a transfer of energy Evaporation Changes of phase usually involve a transfer of energy. The four possible forms of matter solid, liquid, gas, and plasma are called phases. Matter can change from one phase to another. The phase of matter

More information

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016 Boiler Condensate Return Basics Presented by Steve Connor February 24, 2016 What We Are Covering Today? Brief review of the total steam system Why a proper condensate return system is so important Condensate

More information

2. Sketch and describe a steam drum internal feedwater pipe. 3. Identify and describe a steam drum continuous blowdown line.

2. Sketch and describe a steam drum internal feedwater pipe. 3. Identify and describe a steam drum continuous blowdown line. Drum Internals Learning Outcome When you complete this module you will be able to: Describe drum internals. Learning Objectives Here is what you will be able to do when you complete each objective: 1.

More information

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University 2 Objectives Differentiate between dry air and atmospheric air. Define and calculate

More information

Steam System Best Practices Document No. 11

Steam System Best Practices Document No. 11 Plant Support & Evaluations, Inc 400 Lombardi Ave. Green Bay, WI 54304 888-615-3559 www.plantsupport.com Fax: 888-615-8664 Steam System Best Practices Document No. 11 The Number One Problem in a Steam

More information

Ultra-sorb Steam Dispersion Panels

Ultra-sorb Steam Dispersion Panels Ultra-sorb Steam Dispersion Panels PR0DUCT CATALOG Ultra-sorb Model LH Ultra-sorb Model LV Ultra-sorb Model XV DRI-STEEM takes the lead again with Ultra-sorb, establishing the industry standard for energy

More information

How to Trap: Steam Tracer Lines

How to Trap: Steam Tracer Lines How to Trap: Steam Tracer Lines 1 Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit for up-to-date information. Bringing Energy Down to Earth

More information

Efficient Steam System Design

Efficient Steam System Design Efficient Steam System Design The word Efficient is often used to describe the general performance of a system. However it is important to distinguish between efficiency and effectiveness. Efficiency is

More information