TempMaster OmniElite SINGLE PACKAGED UNITS TMAL

Size: px
Start display at page:

Download "TempMaster OmniElite SINGLE PACKAGED UNITS TMAL"

Transcription

1 PACKAGED ROOFTOP UNITS START-UP GUIDE NEW RELEASE Form TPM-SU1 (516) TempMaster OmniElite SINGLE PACKAGED UNITS TMAL DESIGN LEVEL F LD THROUGH 65 TONS ASHRAE 90.1 COMPLIANT Issue Date: May 12, 2016

2 IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES FORM TPM-SU1 This equipment is a relatively complicated apparatus. During rigging, installation, operation, maintenance, or service, individuals may be exposed to certain components or conditions including, but not limited to: heavy objects, refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of rigging, installation, and operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized rigging, installation, and operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood the on-product labels, this document and any referenced materials. This individual shall also be familiar with and comply with all applicable industry and governmental standards and regulations pertaining to the task in question. SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations: Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken. Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution if proper care is not taken or instructions and are not followed. Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment if proper care is not taken. Highlights additional information useful to the technician in completing the work being performed properly. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the control cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with TempMaster's published specifications and must be performed only by a qualified electrician. TempMaster will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. 2

3 FORM TPM-SU1 CHANGEABILITY OF THIS DOCUMENT In complying with TempMaster's policy for continuous product improvement, the information contained in this document is subject to change without notice. TempMaster makes no commitment to update or provide current information automatically to the manual or product owner. Updated manuals, if applicable, can be obtained by contacting the nearest TempMaster Service office or accessing the TempMaster website at It is the responsibility of rigging, lifting, and operating/ service personnel to verify the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, rigging, lifting, and operating/service personnel should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller. CHANGE BARS Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. ASSOCIATED LITERATURE MANUAL DESCRIPTION TempMaster OmniElite Installation, Operation, and Maintenance, Ton Unit FORM NUMBER TPM1-NOM1 3

4 ASSOCIATED LITERATURE FORM TPM-SU1 NOMENCLATURE BASE MODEL NUMBER EXAMPLE - TMAL050NVE46LSFXN BASE PRODUCT TYPE NOMINAL CAPACITY APPLICATION REFRIGERANT VOLTAGE DUCT LOCATIONS DESIGN SPECIAL GAS HEAT CAPACITY L : Scroll A : Air-Cooled M : Packaged Rooftop T : TempMaster V : VAV, VFD B : R-407C C : R-22 E : R-410A C : Cooling Only N : Staged Natural Gas Heat G : Staged Natural Gas Heat SS HX M : Full Modulating Gas Heat F : Full Modulating Gas Heat SS Staged HX E : Electric Heat H : Hot Water Heat S : Steam Heat : 208 / 3 / / 3 / 60 6 : 460 / 3 / 60 8 : 575 / 3 / 60 0 : 380 / 3 / 60 5 : 400 / 3 / 50 B : Bottom Return R : Rear Return S : Side Return B : Bottom Supply L : Left Supply R : Right Supply X : Std. Product, IPU S : Special Product, IPU F : Revision Level F (initial) N : No Gas Heat L : Low (375 MBH) M : Med (750 MBH) H : High (1125 MBH) 4

5 FORM TPM-SU1 TABLE OF CONTENTS SECTION 1 - INTRODUCTION...7 Tools Needed...8 Options List...8 SECTION 2 - HOW TO PROGRAM USER INTERFACE...9 Password...9 Navigation...10 Data Entry Keys...10 Navigation Keys...10 Menu Select Keys...10 Connecting BAS to a TempMaster OmniElite Unit with the IPU Controller...14 BACnet MS/TP...14 BACnet IP...14 LON...16 N Other Protocols...17 End of Line Termination...17 Miscellaneous...17 Technical Support...17 SECTION 3 - UNIT START-UP...19 All Units...19 Variable Air Volume (VAV) Units...19 Field Wiring...19 Required Connections...19 Single Zone VAV Units...19 Field Wiring...19 Required Connections...19 Miscellaneous Options...19 Building Pressure Control (Exhaust Fan or Return Fan with Exhaust...19 Night Set Back...20 Hot Water / Steam Heat...20 SECTION 4 - FACTORY RUN TEST...47 High POT Test...48 Supply Fan Test...48 Return Fan Test...48 Exhaust Fan, Exhaust Damper Test...48 Condenser Fan Test...49 Compressor System Test...49 Damper Test...50 Staged Electric Heat Test...50 Staged Gas Heat Test...51 Modulating Gas Heat Test...51 Hot Water/Steam Heat Test...52 Parameter Descriptions and Options...53 Condenser Fan VFD Parameters...61 Miscellaneous Information

6 FORM TPM-SU1 LIST OF FIGURES FIGURE 1 - TempMaster OmniElite Unit...7 FIGURE 2 - Options Tag...8 FIGURE 3 - Field Control Wiring - Inputs...12 FIGURE 4 - Field Control Wiring - Outputs...13 FIGURE 5 - IPU Controller Port Locations...15 FIGURE 6 - E-Link Connections and Addressing Instructions...16 FIGURE 7 - CTB1 Terminal Strip for Hardwired Connections...17 FIGURE 8 - VFD Parameter Change...62 LIST OF TABLES TABLE 1 - Factory Run Test...47 TABLE 2 - Definitions...53 TABLE 3-460/400/380V 3PH 60 Hz...61 TABLE 4 - VFD Parameters Supply, Exhaust, Or Return...62 TABLE 5 - Temperature Sensors Tons R-410A...63 TABLE 6 - Transducers Tons R-410A

7 FORM TPM-SU1 SECTION 1 - INTRODUCTION 1 The TempMaster OmniElite unit is a large tonnage rooftop unit, with sizes ranging from tons. It can be configured to run as a Multizone Variable Air Volume unit or Single Zone VAV unit. There are many different options that can be added to the machine, which will add to its complexity. This start up guide indicates required field wiring, connections, and programming to provide proper unit operation. This guide does not include installation information. Please refer to the ton Installation, Operation, and Maintenance (IOM) manual (Form TPM1-NOM1) for this information. In addition, any system alarms indicated by the User Interface should be diagnosed as referenced in the IOM. You can refer to the Fault Description Table located in the Service section of the IOM. Multizone Variable Air Volume (VAV) units do not require any field connected control wiring to operate. They will need pneumatic tubing connected from the duct static transducer to a location 2/3 of the way down the supply duct but before the first take-off. A VAV unit will automatically start the supply fan once in the occupied mode. Once the supply fan is running, and controlling to duct static SP, the unit will monitor the return air temperature to decide which mode is needed. The internal logic will then cycle on/off stages of heating and/or cooling to maintain the supply air temperature SP. There are different options for resetting different parameters with a unit configured for VAV operation. Please refer to the appropriate IOM for a more detailed explanation. If the job specifications call for unoccupied heating/cooling operation of a VAV unit, you MUST have a valid zone sensor input, either hard-wired to CTB1 or communicated through a BAS. If you do not have a valid zone sensor input, the unit will display a Sensor/Misc fault and will not run. Do NOT enable Night Set Back without a valid zone sensor input. Single Zone VAV Mode Units configured for Single Zone VAV operation shall contain a supply fan variable frequency drive. The unit shall switch between cooling mode, heating mode, and standby mode based on zone temperature. In cooling mode, the supply fan speed shall be varied based on zone temperature. If the zone temperature gets warmer, the supply fan speed shall increase. Conversely, if the zone temperature gets cooler, the supply fan speed shall decrease. In heating mode, the supply fan shall run at full speed. When the zone temperature is satisfied, the unit is neither in cooling mode or heating mode and the supply fan shall run at minimum speed vip Figure 1 - OMNIELITE UNIT 7

8 List of Tables This start-up guide will assist you in providing a thorough and effective start-up of your new unit. TOOLS NEEDED Electrical Multimeter: will need to be able to read AC voltage to 600VAC, DC voltage to 24VDC, and check amp draws up to 200A. R-410A refrigeration gauge set. Digital temperature meter (NOT an infra red thermometer). Magnehelic gauge-range of 0-5 WC. TempMaster standard safety equipment. Gas pressure test kit or U-tube manometer (if machine has gas heat). Basic hand tools: screwdrivers, wrenches, nut drivers, allen wrenches, etc. OPTIONS LIST FORM TPM-SU1 1. Refer to model Nomenclature on page 4 and Unit Options tag. Figure 2 - OPTIONS TAG LD Use the User Interface Control Center to check the unit set-up from factory. 3. Please use the unit start-up checklist, and fill in the appropriate data on the checklist. This will aid future personnel if these values are changed or lost. 8

9 FORM TPM-SU1 SECTION 2 - HOW TO PROGRAM USER INTERFACE 2 STATUS SETPOINTS UNIT DATA PROGRAM COOLING OPTIONS COMPRESSOR SYSTEMS DATE/TIME SUPPLY SYSTEM SCHEDULE HEATING OPERATING HOURS START COUNTER ECONOMIZER PRINT VENTILATION SERVICE EXHAUST HISTORY UNIT LDO10669a PASSWORD Passwords are used to allow restricted access to certain parameters using the SETPOINTS, PROGRAM, or OPTIONS menu keys. Each parameter is associated with a level of access. Each level of access is associated with a specific password. The access levels available are Level 1 or Level 2. If a parameter is tagged as Level 1, password 9675 must be entered in order to change the value. If a parameter is tagged as Level 2, password 9725 must be entered in order to change the value. Entering the Level 2 password will also allow the changing of a Level 1 parameter. Pressing the SETPOINTS, PROGRAM, or OPTIONS key will take the user to the Login Prompt. When the user is first presented with the Login Prompt, the password field will be blank. If the user wishes to change Level 1 or Level 2 parameters, the user must know the appropriate password. At that point only the parameters changeable under the specific password level will be displayed. For example, if the user presses the OP- TIONS menu key and then enters a Level 1 password, the user will be presented with a list of option parameters that have been tagged as Level 1. The password is entered by pressing the correct sequence of numerical keys (the 0 key through the 9 key), then pressing the key. As digits are entered, asterisks will be placed in the password field. Once entered, the menu system will compare the password to a list of stored passwords. If the entered password matches one of the stored passwords, the user is allowed access at the specified level, and the display will show the first applicable parameter of the menu list, with the appropriate edit prompts. If the password is not correct, the 9

10 SECTION 2 - HOW TO PROGRAM USER INTERFACE screen will display Password Incorrect for two seconds and then revert back to the Login Prompt. Pressing the X key during password entry will cancel the password entry process and take the user back to the Login Prompt. Once a password has been accepted, reentry of that password will not be required until either the user presses any other menu key, other than the keys on the right hand side of the User Interface, or key activity is idle for fifteen minutes. This ensures that the menu system reverts to password protection within an acceptable timeout. NAVIGATION The keypad allows complete control of the system from a central location. The keypad offers a multitude of commands available to access displays, program parameters, and initiate system commands. The keypad consists of 36 keys, which are divided into three categories: Data Entry, Navigation, and Menu Selection keys. A description of each of the keys is contained below. Data Entry Keys The Data Entry keys provide a means to enter values for items that support edits. The keys available to support numeric input are the 0 through 9 keys, the decimal key, the +/- key, the X key and the key. The keys available to support choice input are the key, the key, the X key, and the key. Once editing has started, the user must press either the key or the X key. Any other key press will result in the Press or X to Exit message displayed for two seconds. If you try to edit an item that is view only, it will be ignored by the menu system. When a numeric value that can be modified is displayed under the SETPOINTS menu key, the Default, High, and Low prompt will be shown in the upper right portion of the display. Pressing the +/- key, the decimal key, or any of the 0 through 9 keys will activate the edit mode and a request for the proper password will be made. After the proper password is entered, the cursor will be shown at the digit to be changed. After the desired numeric value has been entered, press the key to save the new value and exit the edit mode. Pressing the key will fill in the default value. Edits will only be accepted when followed by pressing the key. Pressing the X key while in the edit mode will FORM TPM-SU1 cancel the edit mode and leave the value unchanged. If an out of range value is entered, the Default, High and Low prompt is replaced by the Out of Range message for two seconds. When a choice value that can be modified is displayed under the PROGRAM or OPTIONS menu key, the prompt will be shown to the left of the present choice. The key or the key will allow the different choices to be viewed, and pressing either one will activate the edit mode and a request for the proper password will be made. See Password Section of this manual for the proper procedure for entering the password. When the desired choice is displayed, press the key to save the new value and exit the edit mode. Pressing the X key while in the edit mode will cancel the edit mode and leave the value unchanged. Navigation Keys The Navigation keys provide a means to browse items within a menu. The keys currently available to support navigation are the Menu Select keys: the key, the key, the key, and the key. Menu Select Keys Pressing a Menu Select key brings the user to the first screen under that menu. The screens within each menu are arranged in a circular list. The user may browse through the screens using the key and the key. Pressing the key will advance through the screens in order from top to bottom until the bottom screen has been reached. When the bottom screen is displayed, pressing the key will wrap the display to the top screen of the menu. Pressing the key will move through the screens in order from bottom to top until the top screen has been reached. When top screen is displayed, pressing the key will wrap the display to the bottom screen of the menu. Once either the key or the key is pressed, pressing any Menu Select key will bring the user to the first screen under that menu (even if it is the same menu being viewed). Navigation through the circular list of items can also be achieved by repeated presses of the same Menu Select key as long as no other keys are pressed. For example, pressing the UNIT DATA key three times will bring the user to the third screen of the UNIT DATA menu; pressing the UNIT DATA key once, then pressing the key, then pressing the UNIT DATA key again will bring the user to the first screen of the UNIT DATA menu. 10

11 FORM TPM-SU1 SECTION 2 - HOW TO PROGRAM USER INTERFACE The key and the key are used to scroll sideways between the same displays for each system. For example, when viewing the Sys 1 Pressures under the COMPRESSOR SYSTEMS key, pressing the key will scroll sideways to the Sys 2 Pressures display, and pressing the key will scroll sideways to the Sys Pressures display for the last system on the unit. 2 When programming numeric or non-numeric values, the key and the key are used to scroll forward (down) and backward (up) through the items to be programmed or set. 11

12 SECTION 2 - HOW TO PROGRAM USER INTERFACE FORM TPM-SU1 CTB1 FIELD CONTROL WIRING (INPUTS) 24V - (24VAC) or COM - (24VAC COM) 24V - (24VAC) 1 SD - (SHUTDOWN) OCC - (OCCUPIED/UNOCCUPIED) SMK1 - (SMOKE PURGE 1) SMK2 - (SMOKE PURGE 2) SMK3 - (SMOKE PURGE 3) ZR + (ZONE TEMP SENSOR +) ZR - (ZONE TEMP SENSOR -) SHLD - (SHIELD (GND)) Supply Air Temp. Setpoint Reset +5V (SAT SP + 5V) SAT + (SUPPLY AIR TRMP RESET +) SAT - (SUPPLY AIR TRMP RESET -) Duct Pressure Setpoint Reset V (DUCT STATIC SP + 5V) DSP+ (DUCT STATIC RESET +) 22 DSP- (DUCT STATIC RESET -) LD08184C Wiring Notes 1. Wiring shown indicates typical wiring. 2. All wiring is Class 2, low voltage. 3. Maximum power available from the 24VAC terminal is 40VA. 4. Use shielded wire where shown. 5. Potentiometer application shown. As an alternative, signal inputs can be driven from an analog output of a third party controller. Note: Input resistance is 15 K ohms. 6. * Temperature sensors are all 10K Type III. Figure 3 - FIELD CONTROL WIRING - INPUTS 12

13 FORM TPM-SU1 SECTION 2 - HOW TO PROGRAM USER INTERFACE CTB1 FIELD CONTROL WIRING (OUTPUTS) Supply Fan Fault Cooling/Heating Fault Sensor Misc. Fault AL1C AL1 AL2C AL2 AL3C AL3 HRC HR 2 AL1 AL2 AL3 HR Wiring Notes 1. Wiring shown indicates typical wiring. Refer to IOM for more detailed wiring methods and options. 2. All wiring is Class 2, low voltage. 3. Maximum power available from the 24VAC terminal is 40VA. 4. Use shielded wire where shown. 5. Relay contacts suitable for pilot duty to 1A from 24VAC to 120VAC. LD08186A Figure 4 - FIELD CONTROL WIRING - OUTPUTS 13

14 SECTION 2 - HOW TO PROGRAM USER INTERFACE CONNECTING BAS TO A OMNIELITE UNIT WITH THE IPU CONTROLLER A TempMaster OmniElite Rooftop Unit with the IPU controller ships from the factory ready to connect and communicate with a Building Automation System utilizing BACnet MS/TP protocol. The unit can also communicate via BACnet IP, LON or N2 with the addition of a field provided/installed component. BACNET MS/TP Communication wires MUST be connected to Port 1 using only terminals 3 and 4. Connecting wires to any of the other terminals could result in erratic or no communication. (See Figure 43 on page 136) a. Terminal 3: Receive (+) b. Terminal 4: Transmit (-) MAC address can be set using dip switch SW2 or in the SERVICE Key. Preferred method is through the SERVICE Key. This prevents someone accidentally hitting a dipswitch key and changing the MAC address Using the SERVICE Key to set the MAC address: a. Press the SERVICE Key on the keyboard. b. Enter the level 2 password, 9725, and press the. c. The screen should display Data Log Format. If not, press the SERVICE key again, and Data Log Format should appear. FORM TPM-SU1 d. Use the UP arrow to scroll up through the menu until the screen displays P1 Stop Bits =1. e. This is the part of the menu for Port 1. f. Press the UP arrow again to P1 Protocol. Should be set to BACnet. g. Use the UP arrow again until the screen displays P1 Manual Mac Address. If the value is set to -1, the unit address is set by the dipswitches. Press the and enter the MAC address for the unit using the numbered section of the keypad, then press the to accept this value h. Use the UP arrow again to find the P1 Baud Rate. Set this value to the required Baud Rate. i. Press the X key on the keypad to exit the programming menu. j. Cycle main power OFF then ON for new values to be locked in. The unit is now ready to communicate to the BAS BACNET IP Since the IPU controller does not have a functional IP port, a gateway must be used. We recommend using a JCI NCE (MS- NCE2560-0) The gateway will be connected to Port 1 on the IPU controller like below (See Figure 43 on page 136). 14

15 FORM TPM-SU1 SECTION 2 - HOW TO PROGRAM USER INTERFACE 2 IPU Board SW2: MAC Address Switch SD Card Slot Port 3 (J2) SW1: Not Used Battery 5 VDC Power Port 2 (J5) Port 4 (J3) Port 1 (J4) BACnet MS/TP MUST connect here LD20051 Figure 5 - IPU CONTROLLER PORT LOCATIONS 15

16 SECTION 2 - HOW TO PROGRAM USER INTERFACE FORM TPM-SU1 LON To communicate to a BAS utilizing LON protocol, an E-Link must be used: a. YK-ELNK101-0 b. YK-ELNKE01-1 (with enclosure) The wires from the E-Link to the IPU controller will be connected to Port 1 (See Figure 43 on page 136). P1 Protocol set to BACnet. See above under BACnet MS/TP to locate P1 Protocol in the Service Menu. See Figure 44 on page 137 for addressing the E-Link to the IPU Controller. LD20050 TempMaster OmniElite Setup for MS/TP Bus: DE Modifier Addres set to 50. DE Modifier Offset set to -1. P1 Protocol set to BACnet. P1 Manual MAC Address set to -1. P1 Baud Rate st to P1 Parity set to None. P1 Stop Bits set to 1. MAC Address Switch (SW2) set 1 ON, all others OFF. Note: Do not set the chiller address and the E-Link address to the same value. This causes a conflict on the MS/TP Bus resulting in no communication between the chiller IPU I board and the E-Link Gateway. Figure 6 - E-LINK CONNECTIONS AND ADDRESSING INSTRUCTIONS 16

17 FORM TPM-SU1 SECTION 2 - HOW TO PROGRAM USER INTERFACE N2 To communicate to a BAS utilizing N2, an E-Link must be used a. YK-ELNK100-0 b. YK-ELNKE00-0 (with enclosure) The wires from the E-Link to the IPU controller will be connected to Port 1 (See Figure 43 on page 136). P1 Protocol set to BACnet. See above under BACnet MS/TP to locate P1 Protocol in the Service Menu. See Figure 44 on page 137 for addressing the E-Link to the IPU Controller. OTHER PROTOCOLS The IPU controller is also capable of communicating with other BAS protocols: a. MODBUS Server b. MODBUS Client c. MODBUS I/O d. Terminal e. API END OF LINE TERMINATION While it is not always required to have End-of- Line Termination, it is strongly recommended. For BACnet MS/TP and N2 protocols, TempMaster factory recommends using our End-Of-Line Terminator, p/n: MS-BACEOL-0. Other communication protocols may need to provide/install their own end-of-line terminators if applicable. MISCELLANEOUS Whenever a change is made to a communication setting, please cycle power on/off to the unit to lock in the new setting. Points list are available in Table 50 on page 139 for BACnet MS/TP, BACnet IP, and MODBUS. TECHNICAL SUPPORT For technical support on connecting to and communicating with the IPU controller in the Temp- Master OmniElite rooftop unit, please contact Product Technical Support , prompts LD18810 Figure 7 - CTB1 TERMINAL STRIP FOR HARDWIRED CONNECTIONS 17

18 SECTION 2 - HOW TO PROGRAM USER INTERFACE FORM TPM-SU1 THIS PAGE INTENTIONALLY LEFT BLANK 18

19 FORM TPM-SU1 SECTION 3 - UNIT START-UP The Unit Start-Up is broken down into four different sections: All Units, Multizone Variable Air Volume, Single Zone VAV, and Miscellaneous unit options. There are certain items that ALL units require for operation, while the other two sections will deal with the items needed for each different unit set-up. The Miscellaneous unit options can be installed in any type of unit. ALL UNITS The only input needed for ALL units to operate is a 24 vac input to the SD terminal on CTB1 (Figure 3 on page 12). There is a factory jumper installed between terminals 3 and 4 on CTB1. This jumper can be left in place, or removed for a remote emergency shutdown contact. If providing the unit with an Occ/Unocc input, there are three different ways this can be accomplished. They are listed below in order of priority. 1. A 24 vac input to terminal 5 on CTB1 (See Figure 3 on page 12 This can be a remote timeclock or other device. 2. Use of the internal clock schedule. 3. An Occ/Unocc command from a BAS. VARIABLE AIR VOLUME (VAV) UNITS Field Wiring If applicable, connect all hard-wired accessories to CTB1. Please refer to CTB1 (Figure 3 on page 12) and/or appropriate IOM for further explanations. If applicable, please ensure that BAS wiring is connected to the proper port on the IPU board. If using a BAS to control the unit, the zone senor readings can be provide by the BAS. Please ensure the BAS wiring is connected to the appropriate port on the IPU board Required Connections Field supplied and installed pneumatic tubing from duct static pressure transducer. Field Supplied and installed pneumatic tubing from outdoor pressure reference. Outdoor pressure reference is factory supplied, but shipped loose in unit. Refer to installation section of appropriate IOM for more detailed instructions. SINGLE ZONE VAV UNITS Field Wiring If applicable, connect all hard-wired accessories to CTB1. Please refer to CTB1 (Figure 3 on page 12) and/or appropriate IOM for further explanations. If applicable, please ensure that BAS wiring is connected to the proper port on the IPU board. Required Connections For proper operation a communicated or hard wire zone temp be connected. No pneumatic tubing is required to be connected to the unit for Single Zone VAV. Field installed, factory supplied outdoor pressure reference is not required unless building static pressure is being monitored by the unit. If the BAS is controlling the speed of the Exhaust Fan the BAS Contractor may provide its own atmospheric reference or use the one from the unit. Refer the installation section of the IOM. MISCELLANEOUS OPTIONS Building Pressure Control (Exhaust Fan or Return Fan with Exhaust Field supplied and installed pneumatic tubing from building pressure transducer to an open area in the space. Optional BAS control of the Exhaust Fan can be enabled in the Service Key. This will allow the BAS Contractor to control the Exhaust Fan and take control away from the unit. 3 19

20 SECTION 3 - UNIT START-UP Night Set Back A valid zone sensor input must be supplied to the unit. This can either be hardwired to CTB1 or communicated from a BAS system. See Figure 3 on page 12 and Figure 4 on page 13 for wiring requirements and connections. Hot Water / Steam Heat FORM TPM-SU1 Field supplied and installed piping, including the control valve body, strainers, and shut off valves if applicable. Field supplied and installed valve actuator (24 VAC power, 0-10 VDC signal) Factory wiring is provided to heating section. Field connections are required. 20

21 FORM TPM-SU1 SECTION 3 - UNIT START-UP NEW RELEASE Form TPM-CL1 (516) TempMaster OmniElite PACKAGED ROOFTOP UNITS MECHANICAL CONTRACTOR INSTALLATION CHECKLIST AND UNIT SETUP DATA SHEET CUSTOMER: ADDRESS: PHONE: TEL NO: ORDER NO: JOB NAME: LOCATION: CUSTOMER ORDER NO: CONTRACT NO: 3 UNIT MODEL NO: UNIT SERIAL NO: The work (as checked below) is in process and will be completed by: / / Month Day Year The following work must be completed in accordance with installation instructions: A. Installing Contractor Checklist 1. Has the ductwork been connected to the unit? Has all the power wiring been completed? Has all the control wiring been completed? If the unit is SZVAV, has a hardwired or communicated zone sensor been installed? If applicable, has the Building Automation System been connected to the unit? If applicable, has all pneumatic tubing been installed between duct static, and building static pressure transducers to their proper location per IOM manual? If applicable, has the outdoor pressure reference and tubing been installed? Have all the condensate drains been properly installed and primed? If applicable, has the gas line been installed and purged of air? Is the incoming gas pressure within the specified range? If applicable, has the hot water/ steam piping been completed? If applicable, have clean filters been installed? Has the unit been air balanced? If applicable, has there been freeze stats installed downstream of the unit to protect hot water/steam coils in VAV boxes Has a list of setpoints been supplied to the start-up technician? These will vary by unit application and size.... If TempMaster is performing the start-up, all applicable items MUST be completed before the start-up can be performed. If any of the items are not complete, it will be at the discretion of the TempMaster branch whether to perform start-up or not. Any extra time needed to perform the start-up due to non completion of the above list will be charged to the installing contractor. Owner's operating personnel is responsible for ensuring all installation work is complete: Name: Phone Number: Name: Phone Number: Name: Phone Number: 21

22 SECTION 3 - UNIT START-UP FORM TPM-SU1 UNIT SETUP DATA SHEET If start-up is to be performed by a TempMaster service branch, please fill in the appropriate values on the below checklist. Please determine your unit type (Variable Air Volume (VAV) or Single Zone Variable Air Volume (SZVAV)), and fill in the appropriate settings. Some settings may be used in multiple unit types. Please refer to the Parameter Descriptions and Options on page 53 of Start-Up Guide, Form TPM-SU1 for more detailed explanations or to the Installation, Operation, and Maintenance manual, Form TPM1-NOM1. Any values that are not filled in will be left at the factory default setting. If a TempMaster Technician is required to return to enter a value left blank, the installing contractor may be charged. OPTIONS 1. Push the OPTIONS key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different options for the system components. 4. Compare the options installed to the Options List sticker on the front of the unit or the Factory Order Form to be sure they match. 5. Use the checklist below to verify that all installed OPTIONS are input into the controller. A. UNIT DATA Unit Type Range = Variable Air Volume, Single Zone VAV Default = Constant Volume*... Unit Setting: * Constant Volume is not applicable. Control Method Range = Staged / Wired Zone Temp / Comm Zone Temp Default = Staged Input... Unit Setting: SAT Reset Method Range = Hardwired / Outside Air / Return Air / Supply Fan Speed Default = Hardwired... Unit Setting: Smoke Purge Seq 1 Range = Purge / Pressurization / Evacuation Default = Purge... Unit Setting: Smoke Purge Seq 2 Range = Purge / Pressurization / Evacuation Default = Pressurization... Unit Setting: Smoke Purge Seq 3 Range = Purge / Pressurization / Evacuation Default = Evacuation... Unit Setting: PROGRAM 1. Push the PROGRAM key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different Program parameters for the system components. 4. Verify that all features that are installed are ENABLED. 5. Use the checklist below to verify that all PROGRAM features installed are ENABLED. A. UNIT DATA - NO DATA B. COOLING Sup Air Tempering Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: 2 22

23 FORM TPM-SU1 SECTION 3 - UNIT START-UP UNIT SETUP DATA SHEET (CONT'D) C. HEATING Morn Warm Up Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: * Adapt Morn Warm Up Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: ** Night Set Back Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: HW Valve Action Range = Direct / Reverse Default = Direct... Unit Setting: D. VENTILATION Continuous Vent Range = User Enabled / User Disabled Default = User Enabled... Unit Setting: Comfort Ventilation Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: 3 SETPOINTS 1. Push the SETPOINTS key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different SETPOINTS parameters for the system components. 4. Record the final value of each SETPOINTS parameter. 5. Some SETPOINTS may need to be changed in order to make the unit or certain features operate. A. UNIT DATA Unit Design Airflow Range = 7500 to CFM Default = Unit Setting: B. COOLING Occ Zone Cooling Setpoint Range = 2.0 F Above Occ Zone Heating Setpoint To 85.0 F Default = 72.0 F... Unit Setting: Unocc Zone Cooling Setpoint Range = 2.0 F Above Unocc Zone Heating Setpoint To 95.0 F Default = 85.0 F... Unit Setting: RAT Cooling SP Range = 2.0 F Above RAT Heating Setpoint To RAT For High SAT Default = 70.0 F... Unit Setting: 1st Stage Cooling Setpoint Range = 55.0 F To 65.0 F Default = 60.0 F... Unit Setting: 2nd Stage Cooling Setpoint Range = 50.0 F To 60.0 F Default = 55.0 F... Unit Setting: 23 3

24 SECTION 3 - UNIT START-UP FORM TPM-SU1 UNIT SETUP DATA SHEET (CONT'D) SAT Low Setpoint Range = 50.0 F To SAT High Limit Default = 55.0 F... Unit Setting: SAT High Setpoint Range = 55.0 F To 65.0 F Default = 65.0 F... Unit Setting: OAT Setpoint For Low SAT Range = OAT For High SAT To 90.0 F Default = 80.0 F... Unit Setting: OAT Setpoint For High SAT Range = 60.0 F To OAT For Low SAT Default = 70.0 F... Unit Setting: RAT Setpoint For Low RAT Range = RAT Setpoint For High RAT F To 90.0 F Default = 80.0 F... Unit Setting: RAT Setpoint For High SAT Range = RAT Cooling Setpoint To RAT Setpoint For Low SAT F Default = 70.0 F... Unit Setting: Fan Speed SP For Low SAT Range = Fan Speed Setpoint For High SAT To 100.0% Default = 90.00%... Unit Setting: Fan Speed SP For High SAT Range = 50.0% To Fan Speed Setpoint For Low SAT Default = 70.00%... Unit Setting: *Mech Clg Lockout Temp Range = 0.0 F To 65.0 F Default = 50.0 F... Unit Setting: * Only active with low ambient package. If no low ambient package installed, mech clg lockout will be 50 F and is not changeable. C. COMPRESSOR SYSTEM Comp System 1 System Unloading Pressure Range = 450 Psig Psig Default = 620 Psig... Unit Setting: Comp System 2 System Unloading Pressure Range = 450 Psig Psig Default = 620 Psig... Unit Setting: D. SUPPLY SYSTEM Duct Static Reset Low SP Range = 0.0 WC To Duct Static High Limit Default = 1.5 WC... Unit Setting: Duct Static Reset High SP Range = Duct Static Low Limit To Duct Static Sensor Span Default = 2.5 WC... Unit Setting: Duct Static Over Pressure Range = 0.0 WC To 5.0 WC Default = 3.0 WC... Unit Setting: Fan Speed Instability Time Range = 15 Sec To 300 Sec Default = 120 Sec... Unit Setting: 24

25 FORM TPM-SU1 SECTION 3 - UNIT START-UP UNIT SETUP DATA SHEET (CONT'D) Fan Speed Instability Limit Range = 10% To 50% Default = 25%... Unit Setting: *Fan speed instability time and instability limit are not applicable at this time. E. HEATING Occ Zone Heating Setpoint Range = 60.0 F To 2.0 F Below The Occupied Zone Cooling Default = 68.0 F... Unit Setting: Unocc Zone Heating Setpoint Range = 50.0 F To 2.0 F Below The Unoccupied Zone Heating Default = 60.0 F... Unit Setting: RAT Heating SP Range = 55.0 F To 2.0 F Below The RAT Cooling Setpoint Default = 68.0 F... Unit Setting: Heat Limit Temperature Range = F To F Default = F... Unit Setting: Heating SAT Range = 80.0 F To F Default = F... Unit Setting: 1st Stage Heating Setpoint Range = 80.0 F To 95.0 F Default = 85.0 F... Unit Setting: 2nd Stage Heating Setpoint Range = 95.0 F To F Default = F... Unit Setting: Morning Warmup Max Time Range = 15 Min To 240 Min Default = 120 Min... Unit Setting: F. ECONOMIZER Outside Air Enthalpy Setpoint Range = 22.0 BTU# To 40 BTU# Default = 28 BTU#... Unit Setting: G. VENTILATION CO 2 Offset Setpoint Range = 100 PPM To 1000 PPM Default = 500 PPM... Unit Setting: OA Damper Minimum Position Range = 0.0 % To OA Damper Maximum Position Default = 15.00%... Unit Setting: OA Damper Maximum Position Range = OA Damper Minimum Position To 100.0% Default = 30.00%... Unit Setting: Outside Air Maximum Flow Range = 0.0 CFM To CFM Default = 0.0 CFM... Unit Setting: 3 25

26 SECTION 3 - UNIT START-UP FORM TPM-SU1 UNIT SETUP DATA SHEET (CONT'D) Outside Air Minimum Flow Range = 0.0 CFM To CFM Default = 0.0 CFM... Unit Setting: Minimum OA Flow Setpoint Range = 0.0 CFM To CFM Default = 0.0 CFM... Unit Setting: H. EXHAUST Building Pressure Active Setpoint Range = WC TO WC Default = 0.0 WC... Unit Setting: Building Pressure Cntrl Offset Range = 0.01 WC TO 0.05 WC Default = 0.0 WC... Unit Setting: Econo Output For Fan Start Range = Econo Output For Fan Stop To % Default = 10.0%... Unit Setting: Econo Output For Fan Stop Range = 0.0% To Econo Output For Fan Start Default = 5.0%... Unit Setting: Exhaust Output For Fan Start Range = Exhaust Output For Fan Off To 100.0% Default = 10.0%... Unit Setting: Exhaust Output For Fan Stop Range = 0.0% To Exhaust Output For Fan Start Default = 5.0%... Unit Setting: 26

27 FORM TPM-SU1 SECTION 3 - UNIT START-UP OR CONTRACTOR'S RESPONSIBILITIES AND INSTRUCTIONS TO USE FORM This installation checklist provides a quick way to check if all necessary installation work was completed in accordance with installation instructions found in the units IOM, and when completed, acts as a request for TempMaster to furnish start-up supervision. Complete this form as follows: 1. Complete the previous page. 2. Check off each item as required. Cross out (x) items that do not apply. 3. Enter names and phone numbers of the operating personnel responsible for ensuring all installation work is completed Bottom of Form: Enter the date that the TempMaster start-up technician should be at the job site and the name(s) of the supervisor(s) to be contacted. 5. Retain one copy in files and send one copy to customer / owner, and forward another copy to the local TempMaster branch office. REQUEST FOR START-UP With reference to the terms of the above contract, we are requesting the presence of your TempMaster Authorized Representative at the job site on / / to start the system and instruct operating personnel. Have the TempMaster representative contact: Month Day Year Name/Phone We understand that the services of the TempMaster Authorized Representative will be furnished in accordance with the contract for a period of time of not more than consecutive normal working hours, and we agree that a charge of per diem plus travel expenses will be made to TempMaster if services are required for longer than consecutive normal hours or if repeated calls are required, through no fault of TempMaster. Customer/Contractor Signature: Title: Form Completed by: 7 27

28 SECTION 3 - UNIT START-UP FORM TPM-SU1 THIS PAGE INTENTIONALLY LEFT BLANK 28

29 FORM TPM-SU1 SECTION 3 - UNIT START-UP NEW RELEASE Form TPM-CL2 (516) TECHNICIAN START-UP CHECKLIST TempMaster OmniElite PACKAGED ROOFTOP UNITS OFFICE LOCATION CONTRACT NO. TECHNICIAN S NAME UNIT MODEL NUMBER JOB NAME UNIT SERIAL NUMBER START DATE SOFTWARE (APPLICATION) REV. COMPRESSOR # 1A SERIAL NO. COMPRESSOR # 1B SERIAL NO. COMPRESSOR # 2A SERIAL NO. COMPRESSOR # 2B SERIAL NO. 3 PRE START-UP CHECKLIST Please refer to the IOM manual for more detailed descriptions. TempMaster OmniElite tons TMAL Design Level F: Form TPM1-NOM1 GENERAL UNIT INSPECTION Unit checked for shipping damage Unit installed with proper clearances Unit within slope limitations Refrigeration system check presence of oil (gross leaks) Terminal screws and wiring connections tightened in control panel Clean air Filters installed Economizer hood installed properly Exhaust hoods installed properly Condensate drains properly trapped VAV heat relay signal to VAV boxes wired (VAV only) All Field wiring complete and inspected FAN INSPECTION Sheaves properly aligned and tight on shaft - Fan wheels tight on shaft Belt tension adjusted properly Bearings greased Set screws torque checked Static Pressure Probe installed on outside of unit (VAV & Modulating Power Exhaust) Transducer pneumatic tubing installed for duct static and building pressure transducers (VAV) Verify proper Fan rotation COMPRESSOR OPERATION After checking for proper voltage, verify correct compressor rotation. * IOM SECTION REFERENCE INSTALLATION Unit Inspection INSTALLATION Location and Clearances INSTALLATION Location and Clearances START-UP Unit Checks START-UP Unit Checks INSTALLATION Filters INSTALLATION Airhoods For Economizers INSTALLATION Airhood For Exhaust INSTALLATION Condensate Drain INSTALLATION VAV Heat Relay Output INSTALLATION Field Wiring, Power Wiring * IOM SECTION REFERENCE MAINTENANCE Sheave Alignment MAINTENANCE Belt Tensioning MAINTENANCE Fan Bearing Lubrication / Fan Shaft Bearings INSTALLATION Static Pressure Probe Installation INSTALLATION Static Pressure Control Tubing START-UP Fan Rotation * IOM REFERENCE START-UP Verifying Compressor Rotation Scroll compressors will only pump in one direction and MUST be properly phased. To insure proper rotation, observe discharge and suction pressure when the compressor starts. If the compressor is phased correctly, the discharge pressure will increase and the suction pressure will decrease. If this does not occur, phasing of the power supply must be verified. 29

30 SECTION 3 - UNIT START-UP FORM TPM-SU1 Options, Programs, and Setpoints List (Only fill in the appropriate spaces) Please refer to the setup sheet provided by the installing contractor. Any values not filled in on the unit setup datasheet by the installing contractor should be left at the factory default setting. OPTIONS SINGLE ZONE VAV START-UP DATA SHEET Items listed below may or may not be shown based on the configuration of the unit. 1. Push the OPTIONS key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different options for the system components. 4. Compare the options installed to the Options List sticker on the front of the unit or the Factory Order Form to be sure they match. 5. Use the checklist below to verify that all installed OPTIONS are input into the controller. A. UNIT DATA Unit Type Variable Air Volume / Single Zone VAV Default = As Built... Unit Setting: Unit Size Range = 50, 51, 60, 61 Ton Default = As Built... Unit Setting: Model Generation Range = F or G Default = F... Unit Setting: Refrigerant Type Range = R410a Default = As Built... Unit Setting: Control Method (Single Zone VAV) Range = Staged* / Wired Zone Temp / Comm Zone Temp Default = Staged Input... Unit Setting: * Staged is not applicable. Smoke Purge Seq 1 Range = Purge / Pressurization / Evacuation Default = Purge... Unit Setting: Smoke Purge Seq 2 Range = Purge / Pressurization / Evacuation Default = Pressurization... Unit Setting: Smoke Purge Seq 3 Range = Purge / Pressurization / Evacuation Default = Evacuation... Unit Setting: Display Language Range = English / Spanish Default = English... Unit Setting: Display Units Range = Imperial / Metric Default = Imperial... Unit Setting: 30

31 FORM TPM-SU1 SECTION 3 - UNIT START-UP SINGLE ZONE VAV START-UP DATA SHEET (CONT'D) B. COOLING - NO DATA C. COMP SYSTEM # Comp System 1 State - View Only Press Trans Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Low Ambient Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Condenser Fans are View Only and are automatically chosen by unit size. Comp System 2 State - View Only Press Trans Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Low Ambient Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Condenser Fans are View Only and are automatically chosen by unit size. D. SUPPLY SYSTEM Supply Fan Output - View Only E. HEATING Heating System Type Range = None / Electric / Stage Gas / Modulating Gas / Hot Water Steam Default = As Built... Unit Setting: Elec Heat Capacity - If Used Range = 40 Kw V / 80 Kw / 80 Kw V / 100 Kw / 100 Kw V / 120 Kw / 160 Kw / 200 Kw / 240 Kw Default = As Built... Unit Setting: Gas Heat Capacity - If Used Range = 375 Mbh / 750 Mbh / 1125 Mbh Default = As Built... Unit Setting: F. ECONOMIZER Econo Installed Range = None / Dry Bulb / Single Enthalpy / Dual Enthalpy Default = As Built... Unit Setting: Econo Method To Use Range = Dry Bulb / Single Enthalpy / Dual Enthalpy / Best Available Default = As Built... Unit Setting: G. VENTILATION Damper Hardware Range = None / 2 Position / Standard / Tek Air Full IAQ Default = As Built... Unit Setting: Ventilation Control Range = Demand / Fixed Minimum Default = Fixed Minimum... Unit Setting: 3 31

32 SECTION 3 - UNIT START-UP FORM TPM-SU1 SINGLE ZONE VAV START-UP DATA SHEET (CONT'D) H. EXHAUST POWER EXHAUST; RETURN FAN WITH EXHAUST Range = None / On-Off Damper Ctrl / On-Off Press Cntrl / Module Damper - VFD / Return Fan Without Exh Default = As Built... Unit Setting: PROGRAM Exhaust Fan Output - View Only 1. Push the PROGRAM key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different Program parameters for the system components. 4. Verify that all features that are installed are ENABLED. 5. Use the checklist below to verify that all PROGRAM features installed are ENABLED. A. UNIT DATA - NO DATA B. COOLING - NO DATA C. COMPRESSOR SYSTEMS System 1 *** Pumpdown Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: System 2 *** Pumpdown Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: D. SUPPLY SYSTEM - NO DATA E. HEATING Heating System Range = User Enabled / User Disabled Default = User Enabled... Unit Setting: Morn Warm Up Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: * Adapt Morn Warm Up Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: ** Night Set Back Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: * Only used if utilizing internal timeclock/schedule for Occupancy Command. ** Must have a valid zone sensor input, or unit will display Sensor/Misc fault, and it will not run. *** Leave Pump Down Disabled. F. ECONOMIZER Economizer System Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: 32

33 FORM TPM-SU1 SECTION 3 - UNIT START-UP SINGLE ZONE VAV START-UP DATA SHEET (CONT'D) G. VENTILATION Continuous Vent (Single Zone VAV) Range = User Enabled / User Disabled Default = User Enabled... Unit Setting: Comfort Ventilation (Single Zone VAV) Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: Ventilation System Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: Exhaust - No data 3 SETPOINTS 1. Push the SETPOINTS key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different SETPOINTS parameters for the system components. 4. Record the final value of each SETPOINTS parameter. 5. Some SETPOINTS may need to be changed in order to make the unit or certain features operate. A. UNIT DATA Unit Design Airflow Range = CFM Default = Unit Setting: B. COOLING Occ Zone Cooling Setpoint Range = 2.0 F Above Occ Zone Heating Setpoint To 90.0 F Default = 72.0 F... Unit Setting: Unocc Zone Cooling Setpoint Range = 2.0 F Above Unocc Zone Heating Setpoint To 95.0 F Default = 85.0 F... Unit Setting: 1st Stage Cooling Setpoint Range = 55.0 F To 65.0 F Default = 60.0 F... Unit Setting: 2nd Stage Cooling Setpoint Range = 50.0 F To 60.0 F Default = 55.0 F... Unit Setting: *Mech Clg Lockout Temp - Shown when Low Ambient Installed Range = 0.0 F To 65.0 F Default = 50.0 F... Unit Setting: * Only active with low ambient package. If no low ambient package installed, mech clg lockout will be 50 F and is not changeable. C. COMPRESSOR SYSTEM Comp System 1 System Unloading Pressure Range = 450 Psig Psig Default = 600 Psig... Unit Setting: Comp System 2 System Unloading Pressure Range = 450 Psig Psig Default = 600 Psig... Unit Setting: 33

34 SECTION 3 - UNIT START-UP FORM TPM-SU1 SINGLE ZONE VAV START-UP DATA SHEET (CONT'D) D. SUPPLY SYSTEM Supply Fan VFD Speed - View Only Single Zone VAV MIN VFD Speed Range = % Default = 50.0%... Unit Setting: Exhaust / Return Fan VFD - View Only E. HEATING Occ Zone Heating Setpoint Range = 60.0 F To 2.0 F Below The Occupied Zone Cooling Default = 68.0 F... Unit Setting: Unocc Zone Heating Setpoint Range = 50.0 F To 2.0 F Below The Unoccupied Zone Heating Default = 60.0 F... Unit Setting: RAT Heating Setpoint - View Only Heat Limit Temperature Range = F To F Default = F... Unit Setting: 1st Stage Heating Setpoint Range = 50.0 F To 95.0 F Default = 85.0 F... Unit Setting: 2nd Stage Heating Setpoint Range = 55.0 F To F Default = F... Unit Setting: Daily Warmup Time Day 1 Range = 5 Min To 240 Min Default = 60 min... Unit Setting: Daily Warmup Time Day 2 Range = 5 Min To 240 Min Default = 60 min... Unit Setting: Daily Warmup Time Day 3 Range = 5 Min To 240 Min Default = 60 min... Unit Setting: Morning Warmup Max Time - If Morning Warmup is enabled in Program Key Range = 15 Min To 240 Min Default = 120 Min... Unit Setting: F. ECONOMIZER Outside Air Enthalpy Setpoint Range = 22.0 Btu# To 40 Btu# Default = 28 Btu#... Unit Setting: G. VENTILATION CO 2 Offset Setpoint Demand Ventilation Only Range = 100 Ppm To 1000 Ppm Default = 500 Ppm... Unit Setting: OA Damper Position Current - View Only OA Damper Pos Active SP - View Only Outside Air Total Flow - View Only Outside Airflow Active SP - View Only OA Damper Minimum Position 34

35 FORM TPM-SU1 SECTION 3 - UNIT START-UP SINGLE ZONE VAV START-UP DATA SHEET (CONT'D) Range = 0.0 % To OA Damper Maximum Position Default = 15.00%... Unit Setting: OA Damper Maximum Position Range = OA Damper Minimum Position To 100.0% Default = 30.00%... Unit Setting: Minimum OA Flow Setpoint Range = 0.0 CFM To CFM Default = 0.0 CFM... Unit Setting: H. EXHAUST Building Pressure Setpoint Range = WC TO WC Default = 0.0 WC... Unit Setting: Exhaust Damper Positiom - View Only Exhaust / Return Fan VFD - View Only Exhaust Output For Fan Start Range = Exhaust Output For Fan Off To 100.0% Default = 10.0%... Unit Setting: Exhaust Output For Fan Stop Range = 0.0% To Exhaust Output For Fan Start Default = 5.0%... Unit Setting: 3 35

36 SECTION 3 - UNIT START-UP FORM TPM-SU1 Options, Programs, and Setpoints List (Only fill in the appropriate spaces) Please refer to the setup sheet provided by the installing contractor. Any values not filled in on the unit setup datasheet by the installing contractor should be left at the factory default setting. OPTIONS VARIABLE AIR VOLUME START-UP DATA SHEET Items listed below may or may not be shown based on the configuration of the unit. 1. Push the OPTIONS key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different options for the system components. 4. Compare the options installed to the Options List sticker on the front of the unit or the Factory Order Form to be sure they match. 5. Use the checklist below to verify that all installed OPTIONS are input into the controller. A. UNIT DATA Unit Type Range = Single Zone VAV / Variable Air Volume Default = As Built... Unit Setting: Unit Size Range = 50, 51, 60, 61 Ton Default = As Built... Unit Setting: Model Generation Range = F or G Default = F... Unit Setting: Refrigerant Type Range = R410a Default = As Built... Unit Setting: Control Method Range = Staged* / Wired Zone Temp / Comm Zone Temp Default = Staged Input... Unit Setting: * Staged is not applicable. SAT Reset Method (VAV) Range = Hardwired / Outside Air / Return Air / Supply Fan Speed Default = Hardwired... Unit Setting: Smoke Purge Seq 1 Range = Purge / Pressurization / Evacuation Default = Purge... Unit Setting: Smoke Purge Seq 2 Range = Purge / Pressurization / Evacuation Default = Pressurization... Unit Setting: Smoke Purge Seq 3 Range = Purge / Pressurization / Evacuation Default = Evacuation... Unit Setting: Display Language Range = English / Spanish Default = English... Unit Setting: Display Units Range = Imperial / Metric Default = Imperial... Unit Setting: 36

37 FORM TPM-SU1 SECTION 3 - UNIT START-UP VARIABLE AIR VOLUME START-UP DATA SHEET (CONT'D) B. COOLING - NO DATA C. SUPPLY SYSTEM Supply Fan Output - View Only D. COMP SYSTEM # Comp System 1 State - View Only Press Trans Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Low Ambient Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Condenser Fans are View Only and are automatically chosen by unit size. Comp System 2 State - View Only Press Trans Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Low Ambient Pkg Range = None / Sys 1 / Sys 1, 2 Default = As Built... Unit Setting: Condenser Fans are View Only and are automatically chosen by unit size. E. SUPPLY SYSTEM Supply Fan Output - View Only F. HEATING Heating System Type Range = None / Electric / Stage Gas / Modulating Gas / Hot Water Steam Default = As Built... Unit Setting: Elec Heat Capacity - If Used Range = 40 Kw V / 80 Kw / 80 Kw V / 100 Kw / 100 Kw V / 120 Kw / 160 Kw / 200 Kw / 240 Kw Default = As Built... Unit Setting: Gas Heat Capacity - If Used Range = 375 Mbh / 750 Mbh / 1125 Mbh Default = As Built... Unit Setting: HW Valve Action Hot Water / Steam Installed Range = Reverse Direct Default = Reverse... Unit Setting: G. ECONOMIZER Econo Installed Range = None / Dry Bulb / Single Enthalpy / Dual Enthalpy Default = As Built... Unit Setting: Econo Method To Use Range = Dry Bulb / Single Enthalpy / Dual Enthalpy / Best Available Default = As Built... Unit Setting: H. VENTILATION Damper Hardware Range = None / 2 Position / Standard / Tek Air Full LAQ Default = As Built... Unit Setting: 3 37

38 SECTION 3 - UNIT START-UP FORM TPM-SU1 VARIABLE AIR VOLUME START-UP DATA SHEET (CONT'D) Ventilation Control Range = Demand / Fixed Minimum Default = Fixed Minimum... Unit Setting: I. EXHAUST POWER EXHAUST; TYPE Range = None / On-Off Damper Ctrl / On-Off Press Cntrl / Module Damper - VFD / Return Fan Without Exh, Return Fan with Exhaust Default = As Built... Unit Setting: PROGRAM Exhaust Fan Output - View Only 1. Push the PROGRAM key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different Program parameters for the system components. 4. Verify that all features that are installed are ENABLED. 5. Use the checklist below to verify that all PROGRAM features installed are ENABLED. A. UNIT DATA - NO DATA B. COOLING Sup Air Tempering Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: C. COMPRESSOR SYSTEMS System 1 *** Pumpdown Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: System 2 *** Pumpdown Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: D. SUPPLY SYSTEM Instability Monitor Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: E. HEATING Heating System Range = User Enabled / User Disabled Default = User Enabled... Unit Setting: Morn Warm Up Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: * Adapt Morn Warm Up Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: ** Night Set Back Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: 38

39 FORM TPM-SU1 SECTION 3 - UNIT START-UP VARIABLE AIR VOLUME START-UP DATA SHEET (CONT'D) HW Valve Action - Only shown when Hot Water / Steam Heat is installed Range = Direct / Reverse Default = Direct... Unit Setting: F. ECONOMIZER Economizer System Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: G. VENTILATION Ventilation System Range = User Enabled / User Disabled Default = User Disabled... Unit Setting: Exhaust - No data * Only used if utilizing internal timeclock/schedule for Occupancy Command. ** Must have a valid zone sensor input, or unit will display Sensor/Misc fault, and it will not run. *** Leave Pump Down Disabled. Not applicable at this time. 3 SETPOINTS 1. Push the SETPOINTS key. 2. Scrolling to the left and right will show the headings of the different system components. 3. Scrolling up and down will show the different SETPOINTS parameters for the system components. 4. Record the final value of each SETPOINTS parameter. 5. Some SETPOINTS may need to be changed in order to make the unit or certain features operate. A. UNIT DATA Unit Design Airflow Range = CFM Default = Unit Setting: B. COOLING Occ Zone Cooling Setpoint Range = 2.0 F Above Occ Zone Heating Setpoint To 90.0 F Default = 72.0 F... Unit Setting: Unocc Zone Cooling Setpoint Range = 2.0 F Above Unocc Zone Heating Setpoint To 95.0 F Default = 85.0 F... Unit Setting: RAT Cooling SP Range = 2.0 F Above RAT Heating Setpoint To RAT For High SAT Default = 70.0 F... Unit Setting: SAT Low Setpoint Range = 50.0 F To SAT High Limit Default = 55.0 F... Unit Setting: SAT High Setpoint Range = 55.0 F To 75.0 F Default = 65.0 F... Unit Setting: OAT Setpoint For Low SAT - Shows when SAT Reset Method is selected in OPTIONS - UNIT DATA Range = OAT For High SAT To 90.0 F Default = 80.0 F... Unit Setting: 39

40 SECTION 3 - UNIT START-UP FORM TPM-SU1 VARIABLE AIR VOLUME START-UP DATA SHEET (CONT'D) OAT Setpoint For High SAT - Shows when SAT Reset Method is selected in OPTIONS - UNIT DATA Range = 60.0 F To OAT For Low SAT Default = 70.0 F... Unit Setting: RAT Setpoint For Low SAT - Shows when SAT Reset Method is selected in OPTIONS - UNIT DATA Range = RAT Setpoint For High RAT F To 90.0 F Default = 80.0 F... Unit Setting: RAT Setpoint For High SAT - Shows when SAT Reset Method is selected in OPTIONS - UNIT DATA Range = RAT Cooling Setpoint To RAT Setpoint For Low SAT F Default = 70.0 F... Unit Setting: Fan Speed SP For Low SAT - Shows when SAT Reset Method is selected in OPTIONS - UNIT DATA Range = Fan Speed Setpoint For High SAT To 100.0% Default = 90.00%... Unit Setting: Fan Speed SP For High SAT - Shows when SAT Reset Method is selected in OPTIONS - UNIT DATA Range = 50.0% To Fan Speed Setpoint For Low SAT Default = 70.00%... Unit Setting: *Mech Clg Lockout Temp Range = 0.0 F To 65.0 F Default = 50.0 F... Unit Setting: * Only active with low ambient package. If no low ambient package installed, mech clg lockout will be 50 F and is not changeable. C. COMPRESSOR SYSTEM Comp System 1 System Unloading Pressure Range = 450 Psig Psig Default = 600 Psig... Unit Setting: Comp System 2 System Unloading Pressure Range = 450 Psig Psig Default = 600 Psig... Unit Setting: D. SUPPLY SYSTEM Supply Fan VFD Speed - View Only Exhaust / Return Fan VFD - View Only Duct Press Transducer Range = 1.25, 2.50, 5.00 Default = 5.00 INWC... Unit Setting: Duct Static Reset Low SP Range = 0.0 WC To Duct Static High Limit Default = 1.5 WC... Unit Setting: Duct Static Reset High SP Range = Duct Static Low Limit To Duct Static Sensor Span Default = 2.5 WC... Unit Setting: Duct Static Over Pressure Range = 0.0 WC To 5.0 WC Default = 3.0 WC... Unit Setting: 40

41 FORM TPM-SU1 SECTION 3 - UNIT START-UP VARIABLE AIR VOLUME START-UP DATA SHEET (CONT'D) Fan Speed Instability Time Range = 15 Sec To 300 Sec Default = 120 Sec... Unit Setting: Fan Speed Instability Limit Range = 10% To 50% Default = Unit Setting: 3 E. HEATING Occ Zone Heating Setpoint Range = 60.0 F To 2.0 F Below The Occupied Zone Cooling Default = 68.0 F... Unit Setting: Unocc Zone Heating Setpoint Range = 50.0 F To 2.0 F Below The Unoccupied Zone Heating Default = 60.0 F... Unit Setting: RAT Heating SP Range = 55.0 F To 2.0 F Below The RAT Cooling Setpoint Default = 68.0 F... Unit Setting: Heat Limit Temperature Range = F To F Default = F... Unit Setting: Heating SAT Range = 80.0 F To F Default = F... Unit Setting: Daily Warmup Time Day 1 Range = 5 Min To 240 Min Default = 60 min... Unit Setting: Daily Warmup Time Day 2 Range = 5 Min To 240 Min Default = 60 min... Unit Setting: Daily Warmup Time Day 3 Range = 5 Min To 240 Min Default = 60 min... Unit Setting: Morning Warmup Max Time - If Morning Warmup is enabled in Program Key Range = 15 Min To 240 Min Default = 120 Min... Unit Setting: F. ECONOMIZER Outside Air Enthalpy Setpoint Range = 22.0 Btu# To 40 Btu# Default = 28 Btu#... Unit Setting: G. VENTILATION CO 2 Offset Setpoint Demand Ventilation Only Range = 100 Ppm To 1000 Ppm Default = 500 Ppm... Unit Setting: OA Damper Position Current - View Only OA Damper Pos Active SP - View Only Outside Air Total Flow - View Only Outside Airflow Active SP - View Only 41

42 SECTION 3 - UNIT START-UP FORM TPM-SU1 VARIABLE AIR VOLUME START-UP DATA SHEET (CONT'D) OA Damper Minimum Position Range = 0.0 % To OA Damper Maximum Position Default = 15.00%... Unit Setting: OA Damper Maximum Position Range = OA Damper Minimum Position To 100.0% Default = 30.00%... Unit Setting: Minimum OA Flow Setpoint Range = 0.0 CFM To CFM Default = 0.0 CFM... Unit Setting: H. EXHAUST Building Pressure Setpoint Range = WC TO WC Default = 0.0 WC... Unit Setting: Exhaust Damper Positiom - View Only Exhaust / Return Fan VFD - View Only Exhaust Output For Fan Start Range = Exhaust Output For Fan Off To 100.0% Default = 10.0%... Unit Setting: Exhaust Output For Fan Stop Range = 0.0% To Exhaust Output For Fan Start Default = 5.0%... Unit Setting: 42

43 FORM TPM-SU1 SECTION 3 - UNIT START-UP OPERATING DATA Record the operating data once the unit is running at least 10 minutes. ELECTRICAL DATA (ALL COMPRESSORS ENERGIZED) PARAMETER LEG A LEG B LEG C UNIT SUPPLY VOLTAGE PERCENT IMBALANCE % = (Highest - Lowest) / 460. This should not exceed 2% of the nominal unit voltage. If it is higher, contact the building electrician to correct supply voltage issue. 3 SUPPLY FAN MOTOR AMPS EXHAUST / RETURN FAN MOTOR AMPS COMPRESSOR 1A AMPS COMPRESSOR 1B AMPS COMPRESSOR 2A AMPS COMPRESSOR 2B AMPS CONDENSER FAN 1 AMPS CONDENSER FAN 2 AMPS CONDENSER FAN 3 AMPS CONDENSER FAN 4 AMPS SIZE QUANTITY FILTERS BELTS SUPPLY EXHAUST / RETURN 43

44 SECTION 3 - UNIT START-UP FORM TPM-SU1 DEVICE DIRTY FILTER SWITCH INSTALLED/ NOT INSTALLED ACCESSORY ITEMS RECOMMENDED SETTING 1"WC FREEZESTAT 35 F ACTUAL SETTING AIR TEMPERATURE PARAMETER DRY BULB F WET BULB F OUTDOOR AIR (OPTIONAL) SUPPLY AIR RETURN AIR AIRFLOW DATA SUPPLY FAN HORSEPOWER SUPPLY DUCT PRESSURE WC RETURN DUCT STATIC WC DESIGN CFM MEASURED CFM (TEST AND BALANCE OR ACTUAL) HYDRONIC HEAT (OPTIONAL) PARAMETER TEMPERATURE F PRESSURE PSIG / FT ENTERING WATER / STEAM LEAVING WATER / STEAM ELECTRIC HEAT (OPTIONAL) SIZE KW. TOTAL VOLTAGE AMP DRAW STAGE 1 STAGE 2 STAGE 3 STAGE 4 STAGE 5 STAGE 6 STAGE 7 STAGED GAS HEAT (OPTIONAL) Incoming Gas Pressure MANIFOLD PRESSURE in. WC Low FURN 1 High Low FURN 2 High Low FURN 3 High INDUCER 1 AMPS INDUCER 2 AMPS INDUCER 3 AMPS MODULATING GAS HEAT (OPTIONAL) Incoming Gas Pressure Record operating data at low and high speeds. FURN 1A MANIFOLD PRESSURE Low High FURN 1B High High FURN 2 Low High FURN 3 Low High INDUCER AMPS Low 44

45 FORM TPM-SU1 SECTION 3 - UNIT START-UP POST START-UP DATA REFRIGERANT CIRCUITS VALUE SYSTEM 1 SUBCOOLING SYSTEM 2 SUBCOOLING Liquid Pressure: Liquid Temperature: Liquid Pressure: Liquid Temperature: 3 SYSTEM 1 SUPERHEAT Suc Pressure: Suc Temperature: SYSTEM 2 SUPERHEAT Suc Pressure: Suc Temperature: COMP. SIGHT GLASS LEVEL SYSTEM 1 A B SYSTEM 2 A B OUTSIDE AIR TEMPERATURE SUPPLY AIR TEMPERATURE RETURN AIR TEMPERATURE HOT GAS BYPASS OPERATION/SETTING OPERATION VERIFIED SETTING PSIG COMMENTS: 45

46 SECTION 3 - UNIT START-UP FORM TPM-SU1 Scroll compressors will only pump in one direction and MUST be properly phased. To ensure proper rotation, observe discharge and suction pressure when the compressor starts. If the compressor is phased correctly, the discharge pressure will increase and the suction pressure will decrease. If this does not occur, phasing of the power supply must be verified. After start-up has been completed, all setpoints will be set to default values unless otherwise requested. If the setpoints require changing in the future, contact Product Technical Support for assistance. There may be additional charges for a TempMaster Technician to return and adjust setpoints. TempMaster Technician Signature: Date: Jobsite Foreman/Building Supervisor Signature: Date: FOR ASSISTANCE IN START-UP EQUIPMENT, PLEASE CONTACT: PRODUCT TECHNICAL SUPPORT , PROMPTS Return to office and file with customer stat-up documentation. P.O. Box 1592, York, Pennsylvania USA Copyright by TempMaster 2016 Form TPM-CL2 (516) Issue Date: May 12, 2016 NEW RELEASE Subject to change without notice. Printed in USA ALL RIGHTS RESERVED 46

SA Series Start up Report

SA Series Start up Report SA Series Start up Report Important To ensure warranty validation and continued customer satisfaction, complete this form and return it to Desert Aire immediately after start-up. Validation of this report

More information

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products

TAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate

More information

Digital Precise Air Control - DPAC

Digital Precise Air Control - DPAC Digital Precise Air Control - DPAC Mode Enable Sensor Options The temperature of this sensor will determine if the unit is in heating, cooling or vent mode during Occupied operation. The following options

More information

ZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until

More information

Instruction, Operation, and Maintenance: Controls Software Versions: R37+

Instruction, Operation, and Maintenance: Controls Software Versions: R37+ Instruction, Operation, and Maintenance: Controls Software Versions: R37+ VPR Series VPRX Series VPRE Series VPRP Series Version October 2011 Table of Contents Safety... 3 Special Design Requests... 3

More information

I/O ZONE 560/583 USERS GUIDE

I/O ZONE 560/583 USERS GUIDE I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

York 25-Ton VAV Rooftop Unit

York 25-Ton VAV Rooftop Unit HVAC PRO for Windows User s Manual 637.5 OEM Section Technical Bulletin Issue Date 0996 York 25-Ton VAV Rooftop Unit Introduction Page 3 Overview *3 Configuration 5 Sequence of Operation 7 Modes of Operation

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting

More information

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers. ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page

More information

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET CommStat 6 Controller for Redundant HVAC Systems PRODUCT DATA SHEET General Description The CommStat 6 HVAC controller is designed for controlling up to six redundant air conditioners in an E-House or

More information

Reference Guide for Microprocessor Controller

Reference Guide for Microprocessor Controller Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before

More information

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER CENTRIFUGAL LIQUID CHILLERS INSTALLATION INSTRUCTIONS Supersedes: 160.69-NM3 (912) Form 160.69-NM3 (715) FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and other equipment. B. See Division 23 Section

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

M2 Series Startup Form

M2 Series Startup Form M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there

More information

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA 99336 www.jmcvr.com 1-509-586-9893 Table of Contents TABLE OF FIGURES...1 OVERVIEW OF THE HRC CAPABILITIES...2 INSTALLATION AND

More information

Installation and Maintenance Manual IM

Installation and Maintenance Manual IM Installation and Maintenance Manual IM 1234-1 BACnet Thermostat Group: Applied Air Systems Part Number: IM 1234 Date: December 2014 Use with Daikin MicroTech Integrated Systems or as standalone Table of

More information

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY

C-TRAC3 COMMUNICATION MANUAL FOR. BACnet NOVEMBER 2010 TO JANUARY 2014 USA HEAD OFFICE AND FACTORY A C-TRAC3 COMMUNICATION MANUAL FOR BACnet NOVEMBER 2010 TO JANUARY 2014 UNIT MODEL NO. UNIT SERIAL NO. SERVICED BY: TEL. NO: CANADIAN HEAD OFFICE AND FACTORY 1401 HASTINGS CRES. SE CALGARY, ALBERTA T2G

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

VCM-X Controller Technical Guide

VCM-X Controller Technical Guide 2 2 www.orioncontrols.com VCM-X Controller Technical Guide VCM-X Controller Code: SS1026 & Y200920 Version 2.0 and up; VCM-X Modular Controller: Tulsa - SS1030; Coil - SS1034 VCM-X WSHP Controller: Tulsa

More information

MicroTech Self-Contained Air Conditioning System

MicroTech Self-Contained Air Conditioning System Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O

More information

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems Series 9 Commissioning Checklist S9-CL2017.doc ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 S9-CL2017.doc Commissioning

More information

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE

More information

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer Installation and interface must be performed by a qualified controls technician. IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, INTERFACE AND CONFIGURATION OF THIS EQUIPMENT. READ

More information

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide

*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch

More information

CONTROLS MANUAL For all Innovent and Valent air handling products

CONTROLS MANUAL For all Innovent and Valent air handling products CONTROLS MANUAL For all Innovent and Valent air handling products TABLE OF CONTENTS TABLE OF CONTENTS IMPORTANT INFORMATION Safety information...................................................................................

More information

Table of Contents. W2W Open

Table of Contents. W2W Open W2W Open Points and Properties CARRIER CORPORATION 2013 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-457-01 3/27/2013 Table of Contents Introduction... 1

More information

MicroTech Rooftop/RMC

MicroTech Rooftop/RMC Open Protocol Data Communications Packet Version 4.1 Group: Controls Date: March 1999 MicroTech Rooftop/RMC Data Information Packet for Open Protocol 1999 McQuay International Revision History Version

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

SEQUENCE OF OPERATIONS

SEQUENCE OF OPERATIONS SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,

More information

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS SECTION 23 09 93 SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes control sequences for HVAC systems, subsystems, and equipment. B. See Division 23 Section

More information

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road

ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY (Corporate Sales) 85 Middle Road ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 (Corporate Sales) 85 Middle Road An ISO 9001-2000 Certified Company Dunkirk, NY 14048 www.argoindustries.com P/N 240005498A, Rev. 1.5 [02/07]

More information

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits CommStat 4 PRODUCT DATA SHEET Controller for Redundant Telecom HVAC Systems General Description The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners,

More information

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS AMB4/AMB8 MULTIPLE BOILER SEQUENCERS INSTALLATION MANUAL AND OPERATING INSTRUCTIONS ARGO (Technical Support) 2201 Dwyer Avenue Utica, NY 13501 (Corporate Sales) 85 Middle Road An ISO 9001-2000 Certified

More information

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING Tempered Water Logic Control OPERATION l TROUBLE SHOOTING English For MPE Multiple Chiller Units Control Panel TEMPERED WATER SYSTEMS L-2199 Rev. 20080223 Revision: L-2199 20101104 *** IMPORTANT NOTICE

More information

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module SPECIFICATION GUIDE FLEXAIR Air-cooled packaged Rooftop unit Cooling only or Heat Pump Nominal cooling capacity: 85 to 234 kw Nominal heating capacity: 83 to 226 kw Possibility to add auxiliary heaters:

More information

PACKAGED ROOFTOP UNITS SERIES 100 SINGLE PACKAGED UNITS YPAL DESIGN LEVEL F WITH SIMPLICITY ELITE CONTROL 50 THROUGH 65 TONS

PACKAGED ROOFTOP UNITS SERIES 100 SINGLE PACKAGED UNITS YPAL DESIGN LEVEL F WITH SIMPLICITY ELITE CONTROL 50 THROUGH 65 TONS PACKAGED ROOFTOP UNITS INSTALLATION, OPERATION, MAINTENANCE Supersedes 100.50-NOM6 (316) Form 100.50-NOM6 (817) 035-21979-004 SERIES 100 SINGLE PACKAGED UNITS YPAL DESIGN LEVEL F WITH SIMPLICITY ELITE

More information

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE 11/03/2015 Rev 00 1 Contents INTRODUCTION... 3 WARNING LABELS AND SAFETY INSTRUCTIONS... 4 PARALLEL RACK NOMENCLATURE... 5 GENERAL RACK DESCRIPTION...

More information

1.0 Digital Controller

1.0 Digital Controller Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler

More information

RPM1600 Series Room Pressure Monitors

RPM1600 Series Room Pressure Monitors RPM1600 Series Room Pressure Monitors Technical Bulletin LB-RPM1611-0, LB--0 Code No. LIT-12012228 Issued October 2017 Refer to the QuickLIT website for the most up-to-date version of this document. How

More information

TWLC - Tempered Water Logic Controller. The Intelligent Control

TWLC - Tempered Water Logic Controller. The Intelligent Control TWLC - Tempered Water Logic Controller The Intelligent Control Chiller Controls Features: Up to six (6) stages: individual board for each stage maximizes redundancy. Menu driven access and programming.

More information

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog H3/V3 Series Horizontal and Vertical Indoor Air Handling Units Engineering Catalog Table of Contents AAON H3/V3 Series Features and Options Introduction... 6 H3/V3 Base Model Description... 7 Unit Size...

More information

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL SECTION 15910 SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division

More information

Carbon Monoxide Transmitter

Carbon Monoxide Transmitter Introduction The CO Transmitter uses an electrochemical sensor to monitor the carbon monoxide level and outputs a field-selectable 4-20 ma or voltage signal. The voltage signal may also be set to 0-5 or

More information

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment. SECTION 23 09 93 - SEQUENCE OF OPERATIONS FOR HVAC CONTROLS PART 1 - GENERAL 1 WORK INCLUDES A. Base Bid: Heating Contractor provide: Control sequences for HVAC systems, subsystems, and equipment. B. Alternate

More information

Commercial Touchscreen Thermostat

Commercial Touchscreen Thermostat 55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides

More information

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B 2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE HEATPUMP 100% OUTDOOR AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 2 OCCUPIED MODE: When the program control source calls for

More information

Verasys System Operation Overview Technical Bulletin

Verasys System Operation Overview Technical Bulletin Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.

More information

WaterFurnace FX10 Application Guide Reversible Chiller

WaterFurnace FX10 Application Guide Reversible Chiller 2011 WaterFurnace FX10 Application Guide Reversible Chiller Introduction This manual provides information about the FX10 Water Source Heat Pump (WSHP) controller as it relates to dual compressor water

More information

AdaptAire. Digital Control System. User Manual. Expert Systems

AdaptAire. Digital Control System. User Manual. Expert Systems AdaptAire Digital Control System User Manual Expert Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 10 ADAPTAIRE DEFAULT SETTINGS... 10 UNIT OPERATING MODES... 11 MRT Controls:...

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

Your Home. Jacco & Assoc.

Your Home. Jacco & Assoc. Your Home Fan on with call for heating or cooling Heating on with call from space thermostat Stage as required to maintain The 75F Basics adj. - First stage of heating shall be heat pump Cooling on with

More information

CxA to Answer this Section

CxA to Answer this Section EXHIBIT 01 91 13-3, SAMPLE Construction checklist items are to be completed as part of initial checkout and subsequent startup, preparatory to Functional testing. This checklist does not take the place

More information

CommStat 4 Controller

CommStat 4 Controller CommStat 4 Controller CommStat 4 Telecom HVAC Controller The CommStat 4 is an HVAC controller designed specifically for controlling two redundant air conditioners, heat pumps and air conditioners with

More information

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include: Model Number: 8680-N2 Product/System Title: Room Pressure AOC Controller with N2 Communications Protocol Contents of this manual supplement include: 1) Sequence of Operation 2) Variable map 3) Description

More information

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47

Contents. Appendix E: LonWorks Protocol Implementation Conformance Statement Document revision history... 47 WSHP Open v3 CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-539-01 2/8/2017 Verify that you have the most current version of this document

More information

INSTALLATION, OPERATION & QUICK START GUIDE

INSTALLATION, OPERATION & QUICK START GUIDE INSTALLATION, OPERATION & QUICK START GUIDE Controller CS9B-THOA CS9B-THOCA Models: CS9BE-THOA CS9BE-THOCA Bard Manufacturing Company, Inc. Bryan, Ohio 4506 www.bardhvac.com Manual: 00-684 Supersedes:

More information

MicroTech Series 200 Centrifugal Chiller

MicroTech Series 200 Centrifugal Chiller Protocol Data Information Packet Version 2.2 Group: Controls Date: March 1999 MicroTech Series 200 Centrifugal Chiller Data Communications Packet for Protocol 2002 McQuay International Revision History

More information

Cultivator & Hybrid Cultivator

Cultivator & Hybrid Cultivator Cultivator & Hybrid Cultivator Precision Temperature & Humidity Packaged Unit INTRODUCTION The Cultivator Series package unit is the industry s MOST ENERGY EFFICIENT and HIGHEST capacity dehumidifier on

More information

M2 Series Startup Form

M2 Series Startup Form M Series Startup Form Job Name: Date: Address: Model Number: Serial Number: Tag: Startup Contractor: Address: Phone: Pre Startup Checklist Installing contractor should verify the following items.. Is there

More information

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB Summary 1 CONNECTIONS... 3 1.1 TEMPERATURE PROBES...3 1.2 LOW VOLTAGE DIGITAL INPUTS...3 1.3 LIVE DIGITAL INPUTS...4 1.4 RELAY OUTPUTS...5 2 POWER SUPPLY... 6 3 SERIAL CONNECTIONS... 6 4 SOFTWARE... 7

More information

Introduction. What is the RTU Open controller?

Introduction. What is the RTU Open controller? TU Open v3 CAIE COPOATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-521-01 8/22/2017 Verify that you have the most current version of this document

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

Sales and Engineering Data Sheet ED

Sales and Engineering Data Sheet ED Sales and Engineering Data Sheet ED 15121-7 Group: Controls Part Number: ED 15121 Date: July 2017 MicroTech III Chiller Unit Controller Protocol Information Modbus Networks ANSI/ASHRAE 135-2004, BACnet

More information

Product Manual SZ1009

Product Manual SZ1009 Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional

More information

RSMSD Technical Guide

RSMSD Technical Guide RSMSD Technical Guide www.aaon.com AAON/WattMaster Controls Inc. 8500 NW River Park Drive Parkville, MO 64152 Toll Free Phone: 866-918-1100 PH: (816) 505-1100 FAX: (816) 505-1101 E-mail: mail@wattmaster.com

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER

More information

Flopurge TS. Operation Manual

Flopurge TS. Operation Manual Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com

More information

EXPERT TRI-STAR. Temperature controller. User s Manual

EXPERT TRI-STAR. Temperature controller. User s Manual Temperature controller r s Manual WARNINGS The warranty can be void if this product is used in a manner not specified by the manufacturer. Every effort has been made to ensure that this manual is complete,

More information

Modular Standard HP Chiller 1/4 screw compressor with Carel driver

Modular Standard HP Chiller 1/4 screw compressor with Carel driver Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?

More information

1.0 Digital Controller

1.0 Digital Controller 1.0 Digital Controller...1 1.1 Display Function Keys...1 1.2 Thermostat Display...2 1.3 Controller hardware input output points... 4 2.0 Sequence of Operation...5 2.1 States of Operation...5 2.2 Modes

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

EasyTronic III MANUAL SERVICE

EasyTronic III MANUAL SERVICE rev.6 EasyTronic III MANUAL SERVICE General characteristics: Power supply 24 Vac ±15% Max consumption at 24Vac 300mA Relay outputs 6 Maximum relay current 8 A res. Serial standard RS232 2 Serial standard

More information

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN Installation and Operation Tracer ZN521 Zone Controller CNT-SVX07C-EN April 2005 CNT-SVX07C-EN Tracer ZN521 Zone Controller Installation

More information

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1

VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1 Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-038 08/16 FEATURES SPECIFICATION > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) >

More information

Virginia Tech Standards for Building Automation System

Virginia Tech Standards for Building Automation System March 1, 2016 Virginia Tech Standards for Building Automation System A. Existing Conditions: The Campus Building Automation System is Siemens Apogee and controls all significant campus facilties. Virginia

More information

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS TT-1343 5/06b INSTALLATION INSTRUCTIONS Original Issue Date: 8/03 Model: Automatic Transfer Switches Equipped with Series 1000 Programmable Controller Market: ATS Subject: Remote Annunciator Kits GM28938-KP1,

More information

VPR Series VPRE Series VPRC/P Series VPRX Series. IOM-C Software Version 4 Part Number

VPR Series VPRE Series VPRC/P Series VPRX Series. IOM-C Software Version 4 Part Number C ON TROLS I N STRUCTION O PERATION & MA I NTENANCE VPR Series VPRE Series VPRC/P Series VPRX Series IOM-C1-0616 Software Version 4 Valent Controls IOM 2 IOM-C1-0616 Table of Contents Table of Contents...

More information

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone:

ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION Telephone: ADDISON SEQUENCE OF OPERATION FOR ALC CONTROL AIRSOURCE COOLING-ONLY 100% OUTSIDE AIR VERSION 2.0 www.addison-hvac.com Telephone: +1.407.292.4400 1 SEQUENCE OF OPERATION The ALC controller is turned on

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS 1 AIR HANDLING UNIT TRENDS 2 1. The trending charts provided on the following pages prepared as part of a retro-commissioning investigation. The

More information

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER

SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER SEQUENCE OF OPERATION FOR ALC CONTROL AIR SOURCE HEATPUMP RECIRCULATION AIR WITH ECONOMIZER Printed in the USA ADSOOASHPRAE 0117 Orig SEQUENCE OF OPERATION The ALC controller is turned on by a switch located

More information

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.

VCB-X Modular Service Tool Technical Guide. VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2. VCB-X Modular Service Tool Technical Guide VCB-X Controller Code: SS1051 Version 2.0 Requires Service Tool Code: SS1041 Version 2.0 and up Table of Contents INTRODUCTION... 3 Modular Service Tool...3 SYSTEM

More information

RCS Residential Control Systems Inc.

RCS Residential Control Systems Inc. RCS Residential Control Systems Inc. Model TZ16 Z-Wave Communicating Thermostat with Rev P HVAC Control Unit INSTALLATION AND OPERATION MANUAL DCN: 141-00882 Rev 02 5/18/06 This manual applies to the following

More information

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N DPC-1 Programmable digital thermostat with communication Versión 2.0 Ref: N-27360 1108 Technical Information I S O 9 0 0 1 ER-0028/1991 Johnson Controls Manufacturing España, S.L. is participating in the

More information

Natural Ventilation Controller with 24vDC drive NVC-1204

Natural Ventilation Controller with 24vDC drive NVC-1204 Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11 FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs

More information

AirTrak. Digital Control System. User Manual. Touchscreen Systems

AirTrak. Digital Control System. User Manual. Touchscreen Systems AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...

More information

MicroTech Unit Ventilator

MicroTech Unit Ventilator Open Protocol Data Information Packet Version 2.2 Group: Controls Date: April 1996 MicroTech Unit Ventilator Open Protocol Data Communications 2002 McQuay International - C O N F I D E N T I A L - This

More information

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH CONTROL PANEL INTERFACE USING THE AUTO/OFF/MANUAL SWITCH With the switch set to AUTO, the engine may crank and start at any time without warning. Such automatic starting occurs when utility power source

More information

Programming Guide. Signature Series, Ton Modular Series, Ton. Models AO and later Design Sequence

Programming Guide. Signature Series, Ton Modular Series, Ton. Models AO and later Design Sequence Guide IntelliPak Commercial Self-Contained Signature Series, 20-80 Ton Modular Series, 20-35 Ton Models AO and later Design Sequence SCWG -020, -025, -030, -035 SIWG -020, -025, -030, -035 SCRG -020, -025,

More information

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling

ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence

More information

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...

More information

Introduction. What is the W2W Open controller?

Introduction. What is the W2W Open controller? W2W Open CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No. 11-808-538-01 2/8/2017 Verify that you have the most current version of this document

More information

FAN POWERED VAV TERMINALS

FAN POWERED VAV TERMINALS FAN POWERED VAV TERMINALS Models VFR, CFR and CFRQ INSTALLATION, OPERATION AND MAINTENANCE MANUAL All data herein is subject to change without notice. Refer to www.enviro-tec.com for current catalog data

More information

Halton SAFE / 7.14 user guide and installation instructions

Halton SAFE / 7.14 user guide and installation instructions Halton SAFE / 7.14 user guide and installation instructions VERIFIED SOLUTIONS BY H A LTO N Enabling Wellbeing Table of contents 1 System description 3 2 User Accounts 4 3 Main menu 7 3.1 Main menu - Change

More information

VCM-X Modular E-BUS Controller Technical Guide

VCM-X Modular E-BUS Controller Technical Guide www.orioncontrols.com VCM-X Modular E-BUS Controller Technical Guide VCM-X Modular E-BUS Controller: Tulsa - SS1030; Coil - SS1034 VCM-X WSHP E-BUS Controller: Tulsa - SS1032; Coil - SS1033 Requires Service

More information