3750 Pulpress pressurisation unit. Installation and operating instructions

Size: px
Start display at page:

Download "3750 Pulpress pressurisation unit. Installation and operating instructions"

Transcription

1 3750 Pulpress pressurisation unit Installation and File No: uk Date: september 02, 2016 Supersedes: uk Date: october 05, 2015

2

3 contents 1.0 ce conformities Preface Introduction Warnings symbols Instructions for safe use Typical chilled water sealed system Typical lthw sealed system max. 100 c Typical mthw sealed system max. 120 c Storage Limitations Protection General notes Installation Mechanical Electrical Safety regulations Commissioning Operation Heating system Chiller systems Controller functions User interface Statistics Parameters Warnings and alarms Maintenance checks Fault finding chart 13

4 installation & 3750 Pulpress 4 please read all these notes carefully, 1.0 ce conformities lvd bs en Low voltage switchgear bs en Safety of machinery bs en iso &2 Safety of machinery bs en Electromagnetic compatibility Harmonic emissions bs en Electrostatic discharge bs en Radiated rf immunity bs en Fast transient bursts bs en Voltage surges bs en Conducted rf immunity bs en Voltage dips bs en Generic immunity bs en Generic immunity bs en Generic emissions bs en Generic emissions bs en Safety of stationary circulation bs en pumps for heating and service water installations 2.0 preface 1 The 3750 Pulpress has been designed for ease of setting and operation 2 All packaged pump systems are pre-wired and fully tested, both hydraulically and electrically, prior to dispatch. 3 All parameter data has been entered into the controller in accordance with the system criteria. Once on-site connections have been made, and all pre-checks carried out, the system is ready for commissioning. 4 During commissioning if system conditions are found to vary from those set out in the design criteria, the parameters can be easily changed 4.0 warnings symbols Safety instruction where an electrical hazard is involved. Safety instruction where non-compliance would affect safety. Safety instruction relating to safe operation of the equipment. (attention) 5.0 instructions for safe use 1 This equipment has been designed for the pressurisation of sealed heating, chilled water and closed condenser water systems to the operating conditions shown. 2 No installation of this equipment should take place until this installation, operation and maintenance instructions has been studied and understoodby the person responsible. 3 Handling, transportation and installation of this equipment shall be undertaken with the proper use of lifting gear. 4 The set shall not be used for any purpose other than that for which it was designed and sized. 5 The set shall not be operated with the cover removed and the cover interlocked isolator overridden. During normal operation the pumps will generate pressures sufficient to satisfy system demand. However, abnormal running conditions may cause closed valve pressures to be experienced. 3.0 introduction 1 This installation and operation manual contains specific information regarding safe installation and operation of the 3750 Pulpress. These instructions must be read and understood by anyone responsible for the installation and maintenance of this equipment. 2 Prior to power being applied, it is essential that all pre-commissioning procedures are carried out in full. 3 Operators and installers must familiarise themselves with the operation and controls of the equipment.

5 3750 Pulpress installation & typical chilled water sealed system flow cooling load Air eliminator see leaflet on air eliminators return electrical supply alternative position pump auto-air vent with on-off clock expansion vessels signals to bms to cooling tower chillier condenser antigravity loop 3750 pulpress evaporator chillier pump mains supply test point isolating valve non-return valve electrical safety interlock drain cock lock shield valve system fill connection Equipment within this area supplied by others 7.0 typical lthw sealed system max. 100 c electrical supply flow pump over temperature energy cutout thermostat boiler boiler controls heating load temperature gauge isolating valve pressure gauge safety valve pump alternative position return auto-air vent with on-off clock antigravity loop electrical safety interlock non-return valve expansion vessels drain cock signals to bms mains supply test point lock shield valve system fill connection 3750 pulpress Equipment within this area supplied by others

6 installation & 3750 Pulpress typical mthw sealed system max. 120 c The arrangement of the mthw scheme is similar to the lthw system above but has, in addition, an intermediate vessel installed between the expansion vessels and the system connection. The volume of water contained in this vessel ensures that the return temperatures at the boiler are not transferred to the expansion vessel, where damage to the diaphragm would otherwise occur. warning notes: 1 Packed-gland circulating pumps must not be used in sealed systems. 2 Water treatment must not be added to the system via the 3750 Pulpress break tank. 3 No part of the set, expansion vessel, intermediate vessel or connecting pipe is to be lagged. 4 Precautions should be taken to ensure that Lock Shield Valves are protected against unauthorised closure. 9.0 storage Store in a dry place. Protect against dirt, damage and frost limitations 1 Maximum system working pressure: 10 bar. 2 Maximum flow temperature 120 c. 3 Electrical supplies: 1 phase, 50 or 60 Hz, 220 or 240 volts. 4 Power supply fluctuation: +/- 10% maximum. 5 Humidity non-condensing: 80% rh up to 31 c decreasing linearly to 50% rh at 40 c. 6 Ambient temperature: -5 c to 40 c. 7 Water supply pressure 0.8 bar minimum to 6.8 bar maximum with ballcock fully open. 8 System fill pressure: 8.1 Low pressure pump(s) 0.5 to 2.5 bar. 8.2 Medium pressure pump(s) 1.5 to 5.5 bar. 9 Maximum water temperature for expansion vessels: 9.1 Continuous 70 c above this intermediate vessels must be used. 9.2 Intermittent 100 c. 10 Maximum total boiler rating refer to graph pu protection The set must be protected from the formation of condensation. If there is a likelihood of condensation forming on or in the control panel then an anti-condensation heater should be fitted. Contact our service department for details general notes 1 The sets comprise one or two pumps operating on a duty/ stand-by arrangement. 2 Each set is sized to bs7074 and custom built for a specific application, any change in the system conditions shown may necessitate a change in the design or settings. 3 System must be completely flushed out, to remove any metal particles, dirt etc, which may damage the set. 4 The system should be pressure tested, to eliminate leaks. 5 Under no circumstances must any attempt be made to introduce water treatment to the system via the break-tank. 6 No part of the set, connecting pipe or expansion vessel(s) are to be lagged. 7 Fill the system via the quick-fill connection. Do not use the set to fill the system installation 13.1 mechanical 1 Install the set on a flat and even surface. 2 Site set with sufficient space to the front, left and right sides of the unit for maintenance purposes. 3 Connect the cold water mains supply, via a stopcock, to the ballcock in the break tank. (Water supply pressure 0.8 bar minimum with ballcock fully open). 4 Arrange break tank overflow pipe to discharge into a convenient drain in line with clause 30 of the Water supply Bye-laws 1989 edition. 5 Make a connection from the set to the return side of the boiler and suction side of the circulating pump(s). If intermediate vessels are provided these should be fitted in this connection with the set and expansion vessels connected to the bottom of the vessel and the system to the top of the vessel. A manual air vent should be fitted in the pipe work close to the top of the vessel, see general arrangement drawing provided. Ensure pump(s) are vented by loosening the vent cap on top of the delivery branch of the pump. Care must be taken not to over tighten the system or water inlet connections. 6 Never dry run the pump. 7 For wall mounting, wall structure will need to be determined to select appropriate fasteners. Ensure there are no pipes or electrical cables running behind where the wall bracket is to be secured electrical 1 The power supply required is 240 volt +/-10%, 1 phase, 50 Hz or 60 Hz to suit motors fitted. 2 The incoming supply should be connected to the door interlocked isolator from a local 10 amp switched fused spur and if possible an elcb unit.

7 3750 Pulpress installation & 7 3 All incoming cable glands should be ip54 rated as a minimum. 4 Wire the set control systems (see enclosed wiring diagram) from the volt free terminals to the boiler control system. 5 Boiler/chiller interlock provided via normally open volt free contact. 6 The set must be efficiently earthed. 2 Turn on the water supply feeding the 3750 Pulpress unit and fill the breaktank. 3 Check pumps are primed by loosening cap on the delivery side of the pump let water escape until no air is present, replace caps and pressurize to the ambient temperature set pressure. Never dry run the pumps. 4 With cover interlock isolating switch in the off position switch on the power supply to the unit. attention It is the user s or certified electrician s responsibility to ensure correct earthing and protection in accordance with applicable national and local requirements and standards. important safety information 1 The voltage on the 3750 Pulpress unit is dangerous when it is connected to the mains. Incorrect installation of the set may lead to material damage or serious injury or death. Consequently, you must comply with the instructions in this manual as well as the local rules and safety regulations. 2 Touching the electrical parts may be fatal, even after the mains supply has been disconnected, wait at least 4 minutes. 3 The installation must be fused and isolated correctly. 4 Covers and cable entries must be fitted safety regulations 1 The 3750 Pulpress unit must be disconnected from the mains if repair work is to be carried out. Check the mains supply has been disconnected and the necessary time has passed (4 minutes). 2 The correct protective earthing of the equipment must be established, the user must be protected against supply voltage, and the set must be protected against overload in accordance with applicable national and local regulations. 3 RCDs (elcb relays), multiple protective earthing or earthing can be used as extra protection, provided that local safety regulations are complied with commissioning 1 Fill the system with water via the quick fill connector. It is essential that all air in the system is allowed to escape freely through automatic air vents and radiator bleeds, failure to remove air could result in a system malfunction operation Turn the main isolating switch to the On position. The system pressure will be displayed on the digital readout. The unit will automatically maintain pressure in the system as set out in the design criteria and will operate when the pressure falls between the system fill pressure and the pump cut-in pressure heating system Start the boiler(s). The water from the system will flow into the vessel(s) and the system pressure will rise slowly and settle at a pressure below the maximum pressure shown on the nameplate. If the boiler safety valve lifts, check the valve setting and the system details, against the ordering specification for the 3750 Pressurisation unit chiller systems When the chiller(s) are started the water contracts as it cools and the 3750 will pass water from the tank via the pump, to bring the pressure up to the ambient temperature setting pressure. When the chiller is switched off the expanding water will pass into the expansion vessel, the pressure will rise and settle at a pressure below the maximum pressure shown on the nameplate. note On chiller sets, the highest system pressure will occur when the system is at ambient temperature after operation, whereas on heating sets the highest pressure occurs at maximum system operating temperature. If the system pressure falls due to a slow leak, water in the expansion vessel(s) will run back into the systems. If the system leakage continues causing a drop in pressure below the initial system pressure the pump(s) will start to restore the initial system pressure. In the event of a leak exceeding the pump(s) capacity then, providing the set's volt free contacts have been wired accordingly, the boiler burners will be shut down and the circulating pumps are stopped. The system should then be closed down and the leak rectified.

8 installation & 3750 Pulpress controller functions pressure par 5 - high pressure alarm = mwp(pf1) par 1 - pump cut out = fill pressure (pi) par 1 - pump cut in = (pi) - 0.2bar differential par 4 - low pressure alarm = static height (ph) pump 1 pump 2 pump 1 time par 3 - [pressure dip delay] = 5 sec par 11 - [hrs to pulse cycle] = 720 hrs par 12 - [pulse cycle time] = 1 second Pressure dip delay No message required, no alert. Should not start the pump until value parameter [pressure dip delay] seconds have passed without the pressure coming back to the set point. Digital display Showing system pressure, warning codes, alarm codes and pump run indication. Pump test When the controller is in the normal mode (not programming). When the up p button is pressed and held for 3 seconds Pump 1 will run and continue to run until the button is released. When the down q button is pressed and held for 3 seconds Pump 2 will run and continue to run until the button is released. This will enable the pumps to be tested manually. Hours run meter(s) This cannot be reset, showing the number of hours the pump has been running. (Max. 999 hours). Pump auto cycle On two pump sets pumps will auto-cycle increasing service interval time. Alarm Audible alarms on error condition with mute.

9 3750 Pulpress installation & user interface normal view pressure or alarm Press up or down for 3s = Pump test Press down + Press up and down for 5s = Parameter lock/unlock Press set for 5s = go to view par Press set and Press for 5s = Autotest for 5s = go to view stat for 5s = Reset alarm view par display parameter no. Time out 20s = go to normal Press up or down to select parameter Press set = go to change par change par display parameter values Time out 20s = go to normal Press up or down to change parameter value Press set = go to view par Press set for 5s = save and go to view par view stat display statistics autotest device check Time out 20s = go to normal Press up or down to select statistics Press set = go to detail stat detail stat display statistic values Time out 20s = go to normal Press up or down to scroll logging alarm statistics. Press set = go to view stat Enhanced Only 21.0 statistics number name type from s01 to s30 Alarm logging [30] num s31 Pump 1 run time hrs num s32 Pump 2 run time hrs num s01 Most recent alarm s30 Oldest alarm Lines "---" = no alarm registered

10 installation & 3750 Pulpress parameters 0 = no 1 = nc par no. parameter type default min max inc unit of measure 1 Fill pressure (Pi) dec Bar/25 All 2 Pump cut in (Pi-0.2bar) dec Bar/25 All 3 Pressure dip delay num Seconds All 4 Low pressure alarm (Ph) dec Bar/25 All 5 High pressure alarm (Pf1) dec Bar/25 All 6 Max pump run time num Minutes All 7 nc no alarm relay num 1* Numeric All device mode 8 Excessive no. of starts num Numeric Enhanced 9 Excessive starts minutes num Minutes Enhanced 10 Service months num Numeric Enhanced 11 hrs after which the pump pulse cycle starts adjustable in p12 num Hours Enhanced 12 Pulse cycle time num Seconds Enhanced 13 nc no lpr relay num 1* Numeric Enhanced 14 nc no hpr relay num 1* Numeric Enhanced 15 nc no pf1 relay num 0* Numeric Enhanced 16 nc no pf2 relay num 0* Numeric Enhanced 17 nc no run pump 1 relay num 0* Numeric Enhanced 18 nc no run pump 2 relay num 0* Numeric Enhanced 19 nc no lll relay num 0* Numeric Enhanced 20 nc no hll relay num 0* Numeric Enhanced 21 nc no est relay num 0* Numeric Enhanced 22 nc no comm/power relay num 0* Numeric Enhanced 23 n/a num Days n/a 24 n/a num Minutes n/a 25 n/a num 0* Numeric n/a 26 Lux digital num Numeric All 27 Number of pumps num Numeric All 28 Device_on_off num Numeric All 29 Address num Numeric All 30 ext_relay num Numeric All 99 Firmware release num xx.xx Decimal All (enhanced ) Parameter 28 indicates the start-up or stand-by status of the controller (1 = on, 0 = Stand by) Parameter 29 indicates the address of the controller when it is connected in the MODbus mode, (1 to 247). Parameter 30 indicates the communication mode: 0 = external relay board present, therefore rs485 mode enabled. 1 = MODbus mode enabled. When the external relay board is connected to the MODbus enabled controller please refer to drawing number px10899 for controller setting instructions.

11 3750 Pulpress installation & warnings and alarms break tank low/high water level The low water level alarm will be activated should the break tank level low switch trip. The controller will display: low water level All pump(s) will stop running All pump running contacts de-activate Activates lll alarm on display Activates Low Level alarm contact. (Enhanced +vfc version ) high water level (enhanced ) All pump(s) will stop running All pump running contacts de-activate Activates hll alarm on display Activates High Level alarm contact. (Enhanced +vfc version ) In a high and low level alarm condition the set will trip and stop all pumps until the water level returns to normal. The unit will then auto reset and operate as normal. low system pressure The low water pressure alarm will be activated should the pressure at the transducer drop below the value set in parameter 4. Activates lpr alarm on display Activates Common Alarm contact Activates Low Pressure alarm contact (Enhanced +vfc version ) This is an alarm. The set will stop all pumps until the system pressure returns to normal, if low pressure is due to a system leak it will need to be rectified and system fill pressure restored. The unit will then auto reset and operate as normal. high system pressure The high system pressure alarm will be activated should the pressure at the transducer rise above the value set in parameter 5. All pump(s) will stop running Activates hpr alarm on display Activates Common Alarm contact Activates High Pressure alarm contact This is an alarm. The set will stop all pumps until the system pressure returns to normal. The unit will then auto reset and operate as normal. transducer failure The transducer failure alarm will be activated should the transducer lose its signal. All pump(s) will stop running Activates sf alarm on display This is an alarm. The fault must be rectified before the unit can operate as normal. pump tripped Any pumps that are tripped during operation, either in hand or auto, will activate the following: Pump(s) will stop running. Activates pf1 alarm on display (pump 1) Activates pf2 alarm on display (pump 2) Activates pfa alarm on display (pump 1 & 2) Activates pump 1 or 2 contact. (Enhanced +vfc version ) This is an alarm. Standby pump will take over and the set will operate normally in the event of both pumps being tripped the fault will need to be rectified and alarm manually reset before the unit can operate normally. pump running Any pumps that are running during operation, either in hand or auto, will activate the following: Indicates p1 or p2 running on display Activates relevant Pump Running contact (Enhanced +vfc version )

12 installation & 3750 Pulpress 12 max pump run time The maximum pump run time alarm will be activated if the pump runs for an excessive amount of time. Pump(s) will stop running Activates prt alarm on display This is an alarm. Excessive pump run time may indicate a system fault, rectify and reset manually. excessive pump starts (enhanced ) The excessive pump start alarm will be activated if the pump starts for an excessive number of times over a certain period of time. Pump(s) will stop running Activates est alarm on display This is an alarm. Excessive pump starts may indicate a system fault, rectify and reset manually. service reminder (enhanced ) The service reminder warning is displayed ten months after being activated. Activates ser on display Call Armstrong service to arrange service visit. alarms alarm description p High pressure Low pressure Max. pump time Power - pump 1 Power - pump 2 Power pump all Low water High pressure alarm when the system pressure is above the required set point Low pressure alarm when the system pressure is below the pressure limit basic / enhanced pump relay buzzer display blinking stop 6 basic g yes hpr yes yes 5 basic g yes lpr yes yes Max. pump run time alarm 3 basic d yes prt yes yes Tripped pump alarm Low water alarm not enough water in the break tank 9 basic d yes pf1 yes no 10 basic d yes pf2 yes no 2 basic d yes pfa yes yes 7 basic d yes lll yes yes High water High water alarm 8 enhanced d yes hll yes no Pressure sensor failure Service reminder Excessive starts Sensor failure if the sensor exceeds the check values Service reminder when activated, p10 months will be counted. Armstrong Service intervention is required when Reminder message is displayed. Excessive starts no more than p08 starts in p09 hours are permitted 1 enhanced d yes sf yes yes 11 enhanced no no ser yes no 4 enhanced d yes est yes yes reset auto auto man man man man auto auto man by pass man delay time 500ms 500ms ms 500ms 500ms 500ms 500ms 1000ms p = priority order of displayed messages 1: High Priority, no.: Lower Priority relay = g: General (on board), d: Dedicated on expansion board

13 3750 Pulpress installation & maintenance checks Regular checks (Every 3 months) Check the pump(s) are developing the correct pressure and are not noisy or vibrating or air-locked. Check that the mechanical seal is not leaking. Check that the motor is not over heating. Checks at six monthly intervals Check electrical installation thoroughly for defects. Ensure that the earth connections are making good contact. Check that the break tank is clean. Check the operation of the high and low pressure set points. Check low level float switch, (high if fitted). Maintenance For maintenance please contact our service division on +44 (0) fault finding chart section problem 1 Pump(s) run continuously 2 Pump(s) will not run 3 High pressure 4 Low pressure 5 Low water level 1 Pump(s) run continuously 3 High pressure symptom/cause Incorrect capacity of vessel or larger system than originally specified Failure to maintain air charge 4 Low pressure symptom/cause Pump(s) tripped Pump(s) burntout seized System leakage rate very high No water in tank or spasmodic water supply Delivery/suction isolating valve closed Suction strainer(s) obstructed action action Check system and vessel capacity by re-calculating sizes. Isolate and drain the vessel. Adjust the air charge to match the fill pressure of the system. Check miniature circuit breakers and reset if necessary. Repair or replace pumps Check system for leaks. Check for split vessel bag via the air valve. Check nonreturn valve is not bypassing through second pump. Ensure that incoming water supply is functioning i.e. check isolating valve is open, ballcock operates and water is clean. Open valves. Repair or replace strainers. symptom/cause action 5 Low water level Very high leakage rate Faulty electrical circuit System pressure setting set too high Check system for leaks. Check for split in vessel bag via the air valve. Check non-return valve is not bypassing through second pump. Check that all wiring is in place and not loose at any connections. Compare system setting pressure (System data on display nameplate). with Fill pressure (Pi) on data plate. To reset consult Armstrong Service Dept. i) Break tank symptom/cause No water in break tank or spasmodic water supply Incoming water pressure is not sufficient action Ensure that incoming water supply is functioning (i.e. check isolating valve is open, ballcock operates and water is clean). Increase the water pressure, consult Armstrong Service Dept. 2 Pump(s) will not run ii) Alarm symptom/cause Pump(s) tripped Faulty electrical circuit action Check miniature circuit breakers and reset if necessary. Check that all wiring is in place and not loose at any connections. symptom/cause Faulty electrical circuit Broken or damaged float switch action Check that all wiring is in place and not loose at any connections. Replacement float switch required. Pump(s) burnt-out seized Repair or replace pumps.

14 toronto 23 bertrand avenue toronto, ontario canada m1l 2p buffalo 93 east avenue north tonawanda, new york u.s.a birmingham heywood wharf, mucklow hill halesowen, west midlands united kingdom b62 8dj +44 (0) manchester wolverton street manchester united kingdom m11 2et +44 (0) bangalore #59, first floor, 3rd main margosa road, malleswaram bangalore, india (0) shanghai no hu hang road, xi du township feng xian district, shanghai p.r.c são paulo rua josé semião rodrigues agostinho, 1370 galpão 6 embu das artes sao paulo, brazil armstrong fluid technology established 1934 armstrongfluidtechnology.com tm

Astro 2 circulator models. Installation and operating instructions

Astro 2 circulator models. Installation and operating instructions Astro 2 circulator models Installation and File No: 10.89 Date: august 05, 2013 Supersedes: 10.89 Date: june 26, 2013 contents 1.0 Introduction 4 2.0 Installing 4 2.1 Terminal box 4 2.2 Electrical wiring

More information

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.812 Date: february 24, 2017 Supersedes: 10.812 Date: july 23, 2015 1.0 Typical application 1 2.0 How it

More information

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS

ASTRO 2 SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS ASTRO SERIES HOT WATER RE-CIRCULATION SYSTEM INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.81 Date: july 11, 018 Supersedes: 10.81 Date: february 4, 017 1.0 Typical application 1.0 How it works 1

More information

Sequence of operation

Sequence of operation Sequence of operation IPS 4000 secondary variable speed control File No: 90.96 Date: february 21, 2013 Supersedes: new Date: new sequence of operation ips 4000 2 list of abbreviations: adj: Field Adjustable

More information

E.2 series high efficiency circulator. Installation and operating instructions

E.2 series high efficiency circulator. Installation and operating instructions E.2 series high efficiency circulator Installation and operating instructions File No: 10.84 Date: august 16, 2012 Supersedes: 10.84 Date: july 20, 2010 contents 1.0 Operating limits 4 2.0 Electrical

More information

Installation and operating instructions. E.2 Series high efficiency circulator

Installation and operating instructions. E.2 Series high efficiency circulator Installation and operating instructions E.2 Series high efficiency circulator File No: 10.84 Date: august 16, 2012 Supersedes: 10.84 Date: july 20, 2010 contents 1.0 Operating limits 4 2.0 Electrical

More information

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION Environment IMPORTANT INFORMATION It is not anticipated that this equipment will be exposed to adverse environmental conditions without additional protection. Site the equipment in a frost free area. Ensure

More information

Condensing boiler plant (vp)

Condensing boiler plant (vp) Condensing boiler plant (vp) Design Envelope File No: 9.565uk Date: january 23, 2015 Supersedes: new Date: new design envelope s performance improvements are among the top priorities of many building professionals

More information

Pressurisation units & expansion vessels

Pressurisation units & expansion vessels Pressurisation units & expansion vessels Pressurisation units The new generation of microprocessor controlled pressurisation units Standard Unit/Advanced Unit These microprocessor controlled pressurisation

More information

MAXI & MAXI PLUS Floor mounted Pressure manager TECHNICAL DOCUMENTATION. Issue 06/14

MAXI & MAXI PLUS Floor mounted Pressure manager TECHNICAL DOCUMENTATION. Issue 06/14 INSPIRED EFFICIENCY MAXI & MAXI PLUS Floor mounted Pressure manager TECHNICAL DOCUMENTATION Issue 06/14 Content ontents Technical Data 3 1 Installation 4 1.1 Mains/boosted cold water supply 4 1.2 Connection

More information

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS

COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS COMPASS HIGH-EFFICIENCY WET-ROTOR CIRCULATORS INSTALLATION AND OPERATING INSTRUCTIONS File No: 10.895 Date: march 8, 014 Supersedes: 10.895 Date: december 10, 013 1.0 Symbols used in this document 1.0

More information

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6

1 Dimensions Installation Mains/boosted cold water inlet Connection to the system Drain Dimension for fixing 6 Electronic Filling Device (EFD) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5 1.3 Drain 5 1.4

More information

IMPRESS AND IMPRESS ADVANCED PRESSURISATION SETS INSTALLATION AND OPERATING INSTRUCTIONS

IMPRESS AND IMPRESS ADVANCED PRESSURISATION SETS INSTALLATION AND OPERATING INSTRUCTIONS IMPRESS AND IMPRESS ADVANCED PRESSURISATION SETS INSTALLATION AND OPERATING INSTRUCTIONS Page 1 of 17 Revision 1 Page 2 of 17 Revision 1 GENERAL DATA These installation, operation and maintenance instructions

More information

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Flopurge TS. Operation Manual

Flopurge TS. Operation Manual Flopurge TS Operation Manual Part Number 079-0204 Spectron Gas Control Systems United Kingdom Unit 4, Herald Court, University of Warwick Science Park, Coventry, CV4 7EZ +44 (0)24 7641 6234 sales@spectron-gcs.com

More information

NXM2G Installation and Operating Manual

NXM2G Installation and Operating Manual NXM2G-1001 MARCH 26, 2014 NXM2G Installation and Operating Manual (-1 UL version shown) 40VG This manual must be affixed on or adjacent to the boiler or kept with boiler operating manual or other information.

More information

INSTALLATION & TECHNICAL MANUAL

INSTALLATION & TECHNICAL MANUAL The COMET Range of Boilers the ultimate solution for central heating INSTALLATION & TECHNICAL MANUAL If you require any further assistance: Telephone: 01698 820533 Fax: 01698 825697 E-mail: info@electric-heatingcompany.co.uk

More information

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TRACON MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL TABLE OF CONTENTS FPT 130 Overview... 2 Installation... 3 Power Source and Load Connections... 4 Temperature Sensor... 5 External

More information

Logic+ Combi

Logic+ Combi USER GUIDE Logic+ Combi 24 30 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL

NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL NON-CYCLING REFRIGERATED AIR/GAS DRYERS QPNC 75 to QPNC 250 OPERATOR S MANUAL DATE OF PURCHASE: MODEL: SERIAL NO.: Record above information from nameplate. Retain this information for future reference.

More information

Installation, operating and servicing instructions

Installation, operating and servicing instructions English 57-115 - 144-1 - 259 Installation, operating and servicing instructions ITALIA EN 1 ITALIA English INDEX WARnINGS 3 Who should read these instructions 3 Symbols 3 Recommendations 3 Importants notes

More information

USERS GUIDE. LOGIC+ Combi 24, 30, 35

USERS GUIDE. LOGIC+ Combi 24, 30, 35 USERS GUIDE LOGIC+ Combi 24, 30, 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Instructions for the fan motor control system with integrated wiring terminals SILVER C Instructions for the fan motor control system with integrated wiring terminals SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units.

More information

Instructions for the fan motor control system, SILVER C

Instructions for the fan motor control system, SILVER C Instructions for the fan motor control system, SILVER C 1. General The motor control system is used for controlling the type EC, 0.41-10 kw fan motors in the SILVER C units. The motor control system is

More information

Flostop TS D7E and A8E. Operation Manual

Flostop TS D7E and A8E. Operation Manual Flostop TS D7E and A8E Operation Manual United Kingdom Spectron Gas Control Systems Ltd, Unit 4, ATU1, University of Warwick science Park, Coventry, +44 (0) 24 7641 6234 sales@spectron-gcs.com Germany

More information

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions

CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions 6810850/1 IM-P681-07 ST Issue 1 CRU 200 and 500 Series Condensate Recovery Unit Installation and Maintenance Instructions 1. Safety information 2. General product information 3. Installation 4. Commissioning

More information

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...

More information

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions ! Condensate Return Systems General Installation, Operation, & Service Instructions INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. SAFETY INSTRUCTIONS This safety alert symbol will be used in this

More information

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9

Contents. Commissioning 6 Operation 6 Routine Preventative Maintenance 6 Fault Finding 7 Spares Parts 8 Technical Support 9 Contents Product Description 2 Approvals 2 Warranty 2 Warnings 2 Technical Specification 3 Installation 4 Location 4 Plumbing Connection 4 Electrical connection 5 Commissioning 6 Operation 6 Routine Preventative

More information

6800 Design Envelope Booster. Technical overview

6800 Design Envelope Booster. Technical overview 6800 Design Envelope Technical File No: 100.30in Date: may 26, 2014 Supersedes: 100.30in Date: march 17, 2014 contents 1. Product introduction 4 Summary 4 Background 4 Benefits 4 2. Product data 5 Nomenclature

More information

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel

More information

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge Replaceable LED modules 11 Alarm Sequences as per ISA-18.1 standard Each channel/window fully field programmable RS232 or RS485 MODBUS-RTU communication Repeat relay for each window and multifunction relays

More information

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS TC SERIES OPTIONS TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15,, 5 AIR COOLED PACKAGED WATER CHILLERS CONTENTS EQUIPMENT AND COMPONENT DETAILS PERFORMANCE AND TECHNICAL DATA SCHEMATIC FLOW & SYSTEM

More information

Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013

Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013 Installation, Operation and Maintenance Instructions Thermaflow E Plate Heat Exchanger Package OM013 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail:

More information

Trouble Shooting Guide PWA, 3-phase (D10571)

Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide PWA, 3-phase (D10571) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage Loose wire

More information

Q - Series Boiler. Troubleshooting Manual

Q - Series Boiler. Troubleshooting Manual Q - Series Boiler Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized

More information

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME: Supersedes: 201.28-CL2 (817) Form 201.28-CL2 (1017) MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: PHONE: JOB NAME: CUSTOMER ORDER NO: JCI CONTRACT NO: CHILLER MODEL

More information

Preventative Maintenance Tables

Preventative Maintenance Tables Preventative Maintenance Tables Table of Contents I. Table : Gas Fired Domestic Hot Water Heater II. III. IV. Table : Circulating Pump Table : Convectors Table 4: Grille and Diffusors V. Table 5: Unit

More information

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design TOTAL SOLUTIONS Liquid Level Control Product Guide MATELEC innovative by design Liquid Level Control Contents Dual Pump Controllers Section 1 The Range Common Features Operating Data Control Logic Setup

More information

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES

USER INSTRUCTIONS & CUSTOMER CARE GUIDE Si II SERIES 24-28Si II SERIES G.C. NUMBERS APPLIANCE NATURAL GAS L.P.G. 24Si II 47 311 65 47 311 66 28Si II 47 311 67 47 311 68 USER INSTRUCTIONS & CUSTOMER CARE GUIDE EXCELLENCE COMES AS STANDARD CONTENTS Page No.

More information

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm Operating & Maintenance Manual Alert-4 Ethernet LCD Master Alarm w w w. a m i c o. c o m Contents User Responsibility 4 Introduction 4 Features 5 Description of the Alarm 5 Shipment Details 5 The Alarm

More information

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL

SMARTELEC 2 ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL Instruction Manual. SMARTELEC 2 SmartElec ENERGY SAVING CONTROL INSTALLATION AND OPERATING MANUAL 0 F1 INDEX Section General information ------------------------------------------------------------ 1 Dimensions

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents

More information

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX

MANUAL. OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX MANUAL OEM (Unit) OZONE GENERATOR (100VA, 200VA and 300VA) INDEX 1) Technical Specifications: (100VA, 200VA, 300VA) 2) Introduction 3) Construction 4) Operation and maintenance a) Operating Procedure b)

More information

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table)

Warning: 230V / 1ph / 50Hz V / 3ph / 50Hz. Remarks: Make sure that you have enough power. (See page 15 Cable table) 1 2 Warning: - Do not place your hand or any other objects into the air outlet and fan. It could damage the heat pump and cause injuries; - In case of any abnormality with the heat pump, cut off the power

More information

Snifter ATEX22 VERSION. User Manual. Distributor

Snifter ATEX22 VERSION. User Manual. Distributor Snifter ATEX22 VERSION User Manual Distributor Version 1.4 09/09/2009 Table of Contents 1. INTRODUCTION... 3 1.1. Safety... 3 1.2. Product overview... 4 1.3. How does it work?... 4 2. INSTALLATION... 5

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017 24 1 2 23 3 4 5 20 6 I 19 7 18 8 9 15 14 11 13 12 i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book i 24 OFF MAX E STATUS BURNER RESET MIN PRE MIN MAX HEAT PREHEAT

More information

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15

CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 CROWN WATER HEATERS CPU10 - CPU15 CPOS10 - CPOS15 COMPACT PLUS 10 and 15 Litre Unvented Under and Over Sink Water Heater INSTALLATION AND USER GUIDE 1 DIMENSIONS 10L - 250mm 15L - 310mm 100mm 80mm 410mm

More information

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book USERS GUIDE Esprit eco 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification

More information

Telephone Helpline: (Australia) Blast Chiller / Freezer. Instruction Manual. Model DN492-A DN494-A

Telephone Helpline: (Australia) Blast Chiller / Freezer. Instruction Manual. Model DN492-A DN494-A Blast Chiller / Freezer Instruction Manual Model DN492-A DN494-A 1 Safety Tips Position on a flat, stable surface. A service agent/qualified technician should carry out installation and any repairs if

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

Trouble Shooting Guide RAA, 1-phase (D3627)

Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide RAA, 1-phase (D3627) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

CPX MEDICAL AIR PLANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

CPX MEDICAL AIR PLANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL CPX MEDICAL AIR PLANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL Company Registered Office: Crown House, Stockport, Cheshire, SK13RB No. 850 Registered in England and Wales No. 05058855 VAT VERSION

More information

Trouble Shooting Guide PAA, 1-phase (D3731)

Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide PAA, 1-phase (D3731) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

Trouble Shooting Guide FAA, 3-phase (D3631)

Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide FAA, 3-phase (D3631) Trouble Shooting Guide Problem Possible Cause Possible Remedy Unit does not start Unit does not cool No power to unit, breaker tripped Low voltage tripped Loose

More information

Extended Range. PRESFIX Packaged Pressurisation Sets AUTOMATIC MAKE-UP UNITS FOR SEALED HEATING AND CHILLED WATER SYSTEMS.

Extended Range. PRESFIX Packaged Pressurisation Sets AUTOMATIC MAKE-UP UNITS FOR SEALED HEATING AND CHILLED WATER SYSTEMS. Extended Range PRESFIX Packaged Pressurisation Sets AUTOMATIC MAKE-UP UNITS FOR SEALED HEATING AND CHILLED WATER SYSTEMS. 2 Presfix Beta MK 2 microprocessor single & twin pump unit Heating system Chilled

More information

EBC20. Instructions for fitting, installation and operation. Read and save these instructions!

EBC20. Instructions for fitting, installation and operation. Read and save these instructions! EBC20 UK Instructions for fitting, installation and operation Read and save these instructions! 2 3002878 EBC20 UK 290415 1. Product information............................................... 4 1.1 Delivery.............................................................

More information

REA 105 Arc Protection Module. Operator s Manual

REA 105 Arc Protection Module. Operator s Manual REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5

More information

Original operating instructions Safety switch with guard locking AC901S AC902S

Original operating instructions Safety switch with guard locking AC901S AC902S Original operating instructions Safety switch with guard locking AC901S AC902S 7390914/03 01/2017 Contents 1 Preliminary note...4 1.1 Explanation of symbols...4 2 Safety instructions...4 3 Items supplied...5

More information

Broag Pressurisation equipment

Broag Pressurisation equipment Broag Pressurisation equipment Compact wall mounted and free standing pressurisation units, utilising the latest microprocessor control. For use on sealed heating and cooling systems, offering accurate

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Gobi II. English. Condensate Pump Instruction manual Gobi II

Gobi II. English. Condensate Pump Instruction manual Gobi II Instruction manual Gobi II Gobi II Condensate Pump 004045 1 Contents Introduction 0 General information 0 Important safety notice 0 Technical data 0 Product description 04 Transport and storage 06 Commissioning

More information

/2010 US/CA

/2010 US/CA 6 720 646 148-11/2010 US/CA (en) For the user User s Instructions Condensing gas boiler Logamax plus GB162-L.B. 80 kw/100 kw Please read thoroughly before operating This manual is available in the English

More information

ELECTRIC FIRE PUMP CONTROLLER

ELECTRIC FIRE PUMP CONTROLLER ELECTRIC FIRE PUMP CONTROLLER INSTRUCTION MANUAL CONTENTS 1. INTRODUCTION 1.1 Safety 1.2 Warranty 1.3 Safety Precautions 1.4 Product Overview 1.5 AS2941-2008 Requirements 2. FEATURES 3. FUNCTIONS AND OPERATIONS

More information

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE:

TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: TECHNICAL MANUAL MULTI-ELEC STANDARD BOILER 09/2011 CODE: 560955 CE Directive 2006/95/CEE British Standard EN 60335-1 (C 73800) 1 CONTENTS Page 1) INTRODUCTION 1.1) Description 3 1.2) Dimensions & connections

More information

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners

LATTNER BOILER COMPANY 9.5 HP Low-NOx Installation and Start-Up Checklist for Dry Cleaners 1 1. General Installation Information (to be completed by technician) Date installed: Location (city & state): Cleaner s name: National Board number (boiler): Installed by (company): Installed by (technician):

More information

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER Heating Circuit ZONE Controller RVA 46.531/109 Zonal temperature controller for control of a lowtemperature heating system, for use with condensing gas boilers Instructions for the INSTALLER INDEX Page

More information

SEALED THERMAL STORE

SEALED THERMAL STORE ISSUE 3 0717 INSTALLATION AND USER GUIDE ENERGYMANAGER SEALED THERMAL STORE ADVANCE APPLIANCES LTD PLEASE RETAIN AND ENSURE SERVICE RECORDS ARE KEPT UP TO DATE. SCHEMATIC DIAGRAM OF ENERYMANAGER THERMAL

More information

Instructions for installation and use English. More documents on: H B /09

Instructions for installation and use English. More documents on:  H B /09 TM Instructions for installation and use English EN More documents on: www.zodiac-poolcare.com H0538700.B - 2015/09 Read this manual carefully before installing, maintaining or repairing this appliance!

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

ASPIRE Laboratory Aspirator

ASPIRE Laboratory Aspirator ASPIRE Laboratory Aspirator USER MANUAL Rev 2/14/18 Accuris Instruments / Benchmark Scientific Ph: (908) 769-5555 E-mail: info@accuris-usa.com (C) Benchmark Scientific, 2018 THE ACCURIS ASPIRE LABORATORY

More information

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER JOCKEY PUMP CONTROLLER Model JPCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page 4 Model

More information

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:

More information

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas User s Manual TIGER S EYE E-Series Mark V Jockey TIGERFLOW Systems, Inc. 4034 Mint Way Dallas, Texas 75237 214-337-8780 www.tigerflow.com TABLE OF CONTENTS Introduction... 4 Sequence of Operation... 5

More information

Engineers manual. Pass Through machines P500 P500 A P500 AS P500 A WS P500 AS WS. A- AirBreak WS Water Softener. AS Dual Rinse Element

Engineers manual. Pass Through machines P500 P500 A P500 AS P500 A WS P500 AS WS. A- AirBreak WS Water Softener. AS Dual Rinse Element P500 P500 A P500 AS P500 A WS P500 AS WS A- AirBreak WS Water Softener AS Dual Rinse Element Table of Contents 1. INTRODUCTION... 3 1.1 1.2 1.3 INSTALLATION AND COMMISSIONING... 3 SERVICE AND REPAIRS...

More information

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card

Installation and operating instructions. Temperature difference controller 6 inputs, 3 outputs, integrated data logger for SD card SOLARTHERMIE - SOLAR THERMAL - SOLAR TÉRMICO - SOLAIRE THERMIQUE - SOLARE TERMICO Installation and operating instructions Temperature difference controller 6 inputs, 3 outputs, integrated data logger for

More information

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start

Full Range Systems. Mokon Troubleshooting Guide Model 311. Process/Water Loop. Problem Possible Cause Corrective Measure. Process pump will not start Mokon Troubleshooting Guide Model 311 Process pump will not start Process pump shuts down during operation Pump seal leak Tank overflows or will not fill on systems with autofill option (water makeup valve)

More information

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions GRUNDFOS INSTRUCTIONS LCD 08 Installation and operating instructions Installation and operating instructions Original installation and operating instructions CONTENTS Page. Symbols used in this document.

More information

Mikrofill Ethos Condensing combination boiler

Mikrofill Ethos Condensing combination boiler Mikrofill Ethos Condensing combination boiler User Instructions 24cc CE Mark Mikrofill gas appliances comply with the requirements contained in CE Mark documents contained with European directives applicable

More information

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO: Supersedes: (316) Form QTC4-CL2 (617) MODEL QTC4 EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: ADDRESS: PHONE: JOB NAME: LOCATION: CUSTOMER ORDER NO: TEL NO: ORDER NO: CONTRACT NO: CHILLER MODEL

More information

LAE10 LFE10. Use. Series 02

LAE10 LFE10. Use. Series 02 ISO 00 Flame Safeguards 7 7 LAE L Series 02 Supplementary data sheets 772 and 773 Flame safeguards for burners with intermittent operation. For safety reasons - self-test of flame supervision circuit,

More information

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N

Sentinel. Kinetic MVHR and Kinetic Plus MVHR. Operation & Monitoring. Stock Ref. N V:\Technical\ARTWORK\Fitting & Wiring\Word Files COMPLETE\442073Q.doc Sentinel Kinetic MVHR and Kinetic Plus MVHR Operation & Monitoring Stock Ref. N 438222 Kinetic B 438222A Kinetic BS 443319 Kinetic

More information

OPERATING MANUAL Enertronic Control System 2

OPERATING MANUAL Enertronic Control System 2 OPERATING MANUAL Enertronic Control System 2 The integrated control system for Lennox chillers in the Ecologic range Manufacturer: Lennox Benelux B.V. Postbus 1028, 3860 BA NIJKERK Watergoorweg 87, 3861

More information

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06)

UPM I. Unit Protection Module. Installation and Operation Manual (2015/06) UPM I Unit Protection Module Installation and Operation Manual 6 720 220 321(2015/06) 2 Key to Symbols Contents Key To Symbols...2 Warnings...2 Specifications... 3 Unit Protection Module (UPM)....3 Power

More information

TH100 Three in One Instant Hot Water Tap

TH100 Three in One Instant Hot Water Tap TH100 Three in One Instant Hot Water Tap Installation, Use and Maintenance Customer Care Department The Group Ltd. Harby Road Langar Nottinghamshire NG13 9HY T : 01949 862 012 F : 01949 862 003 E : customer.care@cda.eu

More information

YCIV Hz & Hz

YCIV Hz & Hz YCIV 0590-1500 50Hz & 0157-0397 60Hz Start-up Checklist SERVICE POLICY & PROCEDURES Supersedes: Nothing Form 201.23-CL1 (309) Commissioning PREPARATION Commissioning of this unit should only be carried

More information

GB24 & GB30. User Manual

GB24 & GB30. User Manual GB24 & GB30 User Manual BOILER OUTPUT To Domestic Hot Water:To Central Heating: GB24/30 Minimum 8.0 kw (27,296 Btu/h) GB24 Maximum 24.2 kw (82,570 Btu/h) GB30 Maximum 30.3 kw (103,384 Btu/h) GB24/30 Minimum

More information

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual We manage heat MANUAL Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239

More information

USERS GUIDE 24, 30. For installation guide see reverse of book

USERS GUIDE 24, 30. For installation guide see reverse of book USERS GUIDE 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification

More information

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm Ground Water (DMS-298) Installation & Operating Manual Pump Station High Level Alarm T. E. W. 01992 523 523 info@deltamembranes.com www.deltamembranes.com Delta House, Merlin Way, North Weald, Epping,

More information

Installation Datasheet

Installation Datasheet Safegard EMB Installation Datasheet The panel is built to meet project specific requirements, see project drawings for details. This product forms part of a life safety system. Failure to correctly store,

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

S304 and S305 Dust Emission Monitors. User Manual. Distributor

S304 and S305 Dust Emission Monitors. User Manual. Distributor S304 and S305 Dust Emission Monitors User Manual Distributor Version 6.4 30/5/2012 Table of Contents 1. INTRODUCTION... 3 1.1 Safety... 3 1.2 Product overview... 4 1.3 Principle of operation... 4 2. INSTALLATION...

More information