Differential pressure sensors

Size: px
Start display at page:

Download "Differential pressure sensors"

Transcription

1 P P03 QBM65-..., QBM QBM Differential ressure sensors for air and nonaggressive gases QBM65... With choice of ressure-linear or extracting-the-root characteristic with adjustable ressure measuring range Oerating voltage AC 24 V or DC V Outut signal DC V Use For very demanding requirements with regard to accuracy and quality in the field of ventilation, air conditioning and heating. To acquire the differential ressure of air or nonaggressive gases. Tyical fields of alication: Chemical industry (laboratories and roduction) In industrial environments (risk of contamination) In hositals (e.g. in the oerating theatre) The differential ressure detectors are used: To measure over- or underressure in air ducts in relation to the ambient resure To measure ressure differentials between different rooms To acquire variable air volumes in VAV lants on the suly and extract air side To monitor filters and to control fans Esecially on alications that demand: great accuracy very short resonse times (monitoring of fans) nonsuscetibility to contamination CA1N1916E Siemens Building Technologies HVAC Products

2 Tye summary Pressure-linear characteristic, without indication Tye Measuring range Overload range reference Standard Limit value (adjustable) QBM65-1U Pa No 5,000 Pa QBM Pa No 5,000 Pa QBM Pa No 5,000 Pa QBM Pa No 10,000 Pa QBM ,000 Pa No 10,000 Pa QBM ,500 Pa No 20,000 Pa Pressure-linear characteristic, with indication Tye Measuring range Overload range reference Standard Limit value (adjustable) QBM Pa No 5,000 Pa QBM Pa No 5,000 Pa QBM Pa No 10,000 Pa QBM ) 0...1,000 Pa No 10,000 Pa QBM ) 0...2,500 Pa No 20,000 Pa 1) Value dislayed x 10 = measured value Extracting-the-root characteristic, without indication Tye Measuring range Overload range reference Standard Limit value (adjustable) QBM Pa Pa 5,000 Pa QBM Pa Pa 5,000 Pa QBM Pa Pa 10,000 Pa QBM Pa ,000 Pa 10,000 Pa QBM Pa 1, ,500 Pa 20,000 Pa (Conversion: 100 Pa = 1 hpa = 1 mbar) Accessories (not included in standard delivery) Name Tye reference/art no. Data sheet no. Duct robes, short FK-PZ Duct robes, long FK-PZ Mounting bracket AQB21.1 Ordering and delivery When ordering, lease give name and tye reference, e.g. differential ressure sensor QBM The differential ressure sensor is sulied comlete with 2 m lastic tubing. Accessories are to be ordered searately, with name and tye reference or order number. The duct robes are sulied only in airs. Equiment combinations Any systems or devices that are caable of acquiring and handling the sensor s DC V outut signal. 2/8

3 Mode of oeration The sensor acquires the differential ressure with the hel of a silicon diahragm. The deflection of the diahragm is sensed and converted to an electric signal. With the extracting-the-root sensors, the otentiometer is used to match the ressure measuring range on an individual basis. Deending on the tye of sensor, the sensor s electronic circuit generates either a ressure-linear or extracting-the-root signal which is calibrated and temeraturecomensated. The measured value is delivered by the sensor as an analog DC V outut signal. Overview of the characteristics and measuring accuracy at an ambient temerature of 20 C: Sensor characteristics and accuracy Linearer outut and total tolerances with a change of ±10 C U A [V] 10,00 9,00 8,00 7,00 6,00 5,00 4,00 3,00 2,00 1,00 0, D01 Sensor characteristic Tolerance with QBM65-1U Tolerance with QBM65-1 Tolerance with QBM Tolerance with other linear tyes [%] Extracting-the-root outut and total tolerances with a change of ±10 C U A [V] 10,00 9,00 8,00 7, D02 6,00 5,00 4,00 3,00 2,00 Sensor characteristic Tolerance with QBM Tolerance with other extracting-the-root tyes 1,00 0, [%] Legend U A Outut voltage in V Pressure measuring range in ercent For detailed information on accuracy, refer to "Technical data". 3/8

4 Mechanical design The differential ressure sensor is designed for wall and ceiling mounting. It consists of: Sensor housing with mounting bracket, cable entry and removable sna-on cover with safety screw Pressure casing with diahragm and lever Printed circuit board with connection terminals and with the extracting-the-root sensor with a otentiometer for adjusting the limit value LCD with the QBM Dislay, setting and connection elements 1916Z Legend 1 Cable entry gland Pg 11 with cable strain relief 2 Digital dislay for sensor signal in Pa (only with the QBM ) 3 Potentiometer, to set the measuring range (only with the QBM ); sulied in the fully clockwise osition (100 % signal) 4 Terminal block 5 Safety screw for hinged cover 6 Nile for tubing connection "+" 7 Nile for tubing connection " " Engineering notes The transformer used must be suited for safety extra-low voltage. It must have searate windings and be designed for 100 % duty. It must be sized and fused in comliance with local safety regulations. If the line length exceeds 50 m and runs arallel to mains cables, screened cable must be used! Mounting and installation notes The QBM65... is suitable for direct mounting on ducts, walls or ceilings and in control anels. The sensor should be mounted vertically. Where ossible, the ressure connection niles should be at the bottom, or if necessary, to the side, and they should always be higher than the duct robes. Horizontal mounting (with the hinged cover to the to or bottom) is NOT RECOMMENDED. If horizontal mounting cannot be avoided, account must be taken of deviations in the measured value (refer to "Factory calibration", below). 4/8

5 + 1916Z02 Caution: If the ressure connection niles face uward or are at a lower level than the duct robes, condensation can collect inside the unit, causing damage to the sensor. When mounting on insulated air ducts, mounting bracket AQB21.1 is required. Sna-on connection between sensor and bracket. A 2 m length of lastic tubing is sulied with the sensor and can be adated to the duct robes on site. The tubing with the higher ressure (lower vacuum) must be connected to nile "P1" or "+", and the tubing with the lower ressure (higher vacuum) must be connected to nile "P2 or " ". The sensor is sulied with mounting instructions. Factory calibration The values given under "Technical data" are valid only when the differential ressure sensor is mounted vertically. Should it be necessary to mount the sensor horizontally, i.e. with the hinged cover at the to or bottom (NOT RECOMMENDED), account must be taken of the deviations in the measured value. Recommended orientation: hinged cover in vertical osition. Signal: as er factory calibration (mandatory with the QBM65-1U) NOT RECOMMENDED: Hinged cover facing downward. Signal: aroximately 10 Pa above actual ressure NOT RECOMMENDED: Hinged cover facing uward. Signal: aroximately 10 Pa below actual ressure 1916Z /8

6 Technical data Power suly Signal outut Oerating voltage Safety extra-low voltage SELV or Protection extra-low voltage PELV Frequence Power consumtion Current consumtion Outut voltage Load (R Last ) Outut AC 24 V ±15 % or DC V HD384 50/ 60 Hz <0.5 VA <10 ma DC V >10 kω not galvanically searated, 3-wire connection, short-circuit roof and rotected against reversed olarity) Functional data Measuring range Measuring element refer to "Tye summary" iezoresistive (Silicone diahragm and ceramic lever) Measuring accuracy when mounted in recommended orientation and at an ambient temerature of 20 C (FS = Full Scale) With linear characteristic Zero oint <±0.7 % FS Total linearity and hysteresis <±1 % FS TC zero oint <±0.04 % FS/ C <±0.02 % FS/ C For QBM65-1 and QBM Zero oint <±1 % FS Total linearity and hysteresis <±2 % FS TC zero oint <±0.10 % FS/ C <±0.05 % FS/ C For QBM65-1U Total zero oint, linearity, reroducibility <±3 % 3 Pa (3 % FS) and hysteresis TC zero oint <±0.10 % FS/ C tyical <±0.05 % FS/ C tyical With extracting-the-root characteristic Absolute error ( % of ressure range) TC zero oint ( % of ressure range) For QBM Absolute error ( % of ressure range) TC zero oint ( % of ressure range) Resonse time Pressure ranges Max. erm. ressure Bursting ressure Dislay (only with QBM ) Range Media ±0.3 <±0.06 FS +1.5 [% of final value] FS <±0.02 % FS/ C ±0.6 <±0.15 in % FS/ C FS +1.5 [% of final value] FS in % FS/ C <±0.05 % FS/ C <10 ms refer to "Tye summary" refer to "Tye summary" 500 hpa/500 mbar liquid crystal standard ressure measuring range in Pa, 3.5 Digit air and nonaggresive gases Perm. temerature of medium C Maintenance no maintenance required 6/8

7 Connection Protective data Environmental conditions Connection terminals screw terminals for mm 2 Cable entry Pg 11 cable gland Pressure connection lastic nozzle 6.2 mm dia. Degree of rotection IP 54 to IEC 529 Safety class III to EN Perm. ambient temerature Oeration C Storage/transort C Perm. ambient humidity <90 % r.h., noncondensing Standards Product standards Automatic electric controls for houshold and similar use EN Electromagnetic comatibility Emmissions to EN Immunity to EN conformity to EMV directive 89/336/EEC conformity to Arobation Fire safety Australian EMC Framework Radio Communication Act 1992 Radio Interference Emmission Standard AS/NZS 3548 UL standard UL First Edition CSA standard CSA C22.2 No Fire class to UL94 Hinged cover HB Pressure casing, comlete V-2 Tubing V-2 Materials Weight Housing Hinged cover Pressure casing Diahragm Tubing Weight (including ackaging), without indication Weight (including ackaging), with indication PC (Polycarbonate) ABS PC with 10 % fibre-glass 2-comonent silicone LSR and PC with 10 % fibreglass, free from gas emissions PVC (Polyvinylchloride, soft) 0.09 kg 0.10 kg 7/8

8 P2P2 For latest rices and delivery to your door visit MyTub Ltd info@mytub.co.uk Connection terminals (0) ( ) (+) M U G 1916G01 G (+) M (0) U ( ) Oerating voltage AC 24 V or DC V GND, measuring neutral Measuring signal DC V Dimensions (all dimensions in mm) , ,5 80 9,6 16,3 1916M01 9 ø 6, P1 18 P2 8/ Siemens Building Technologies Ltd.

for relative humidity and temperature

for relative humidity and temperature 1 861 1861P01 Duct sensor for relative humidity and temperature QFM65 Operating voltage AC 24 V Signal output DC 0...10 V for relative humidity and temperature Measurement accuracy ±3 % r. h. within the

More information

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products

QFM21... Duct Sensors. Siemens Building Technologies HVAC Products For latest prices and delivery to your door visit MyTub Ltd - 0845 303 8383 - wwwmytubcouk - info@mytubcouk 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Use Operating voltage

More information

for relative humidity and temperature

for relative humidity and temperature 1 860 1860P01 Duct sensor for relative humidity and temperature QFM651 Operating voltage AC 24 V Signal output DC 010 V for relative humidity Signal output L&S Ni 1000 (passive) for temperature Measurement

More information

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21... Use Type summary Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for relative humidity Signal output

More information

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature 1 882 1882P01 Symaro Duct Sensors for relative humitidy (high accuracy) and temperature QFM31 Use Examples Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for relative humidity and

More information

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature

QFM21... Duct Sensors. Building Technologies HVAC Products. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct Sensors for relative humidity and temperature QFM21 Operating voltage AC 24 V / DC 13535 V Signal output DC 010 V / 420 ma for relative humidity Signal output DC 010 V / 420 ma

More information

Duct Temperature Sensors

Duct Temperature Sensors 1 762 1761P03 1762P01 Mounting flange AQM630 QAM21 Symaro Duct Temperature Sensors QAM2161040 QAM2171040 Active sensors for acquiring the air temperature in air ducts AC 24 V or DC 13535 V Signal output

More information

for relative humidity and temperature with calibration certificates

for relative humidity and temperature with calibration certificates 1 859 1859P01 1859P02 QFA4160 AQF4150 Symaro Room Sensor for relative humidity and temperature with calibration certificates QFA4160 Operating voltage AC 24 V or DC 13.5...3 Signal output DC 0...10 V for

More information

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature 1 858 1858P01 1858P02 1859P02 Symaro Room Sensors for relative humidity (high accuracy) and temperature AQF3150 QFA31 Use Operating voltage AC 24 V / DC 1353 Signal output DC 010 V / 4 20 ma for r h and

More information

Duct Air Quality Sensors

Duct Air Quality Sensors 1 962 QPM2102D QPM2160D, QPM2162D QPM2100, QPM2102 QPM2160, QPM2162 Duct Air Quality Sensors QPM21 With maintenance-free CO 2 sensing element based on optical infrared absorption measurement (NDIR 1 )

More information

Room Temperature Sensors

Room Temperature Sensors 1 749 1749P01 QAA201 Symaro Room Temperature Sensors QAA201 Active sensors for acquiring the room temperature Operating voltage AC 24 V or DC 135 35 V Signal output DC 010 V or 420 ma Use In heating, ventilation

More information

QFM21... Duct sensors. Symaro. for relative humidity and temperature

QFM21... Duct sensors. Symaro. for relative humidity and temperature 1 864 1864P01 Symaro Duct sensors for relative humidity and temperature QFM21... Operating voltage AC 24 V / DC 13.5...35 V Signal output DC 0...10 V / 4 20 ma for relative humidity Signal output DC 0...10

More information

Room Air Quality Sensors

Room Air Quality Sensors 1 961 1961P1 1961P2 QPA2 QPA2D Room Air Quality Sensors QPA2 With maintenance-free photoacoustic CO 2 sensing element and depending on the type of sensor VOC 1) sensing element, based on a heated tin dioxide

More information

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products 1 821 1821P01 Frost sensors for use on the air side Active capillary tube sensor for measuring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10 V Use On

More information

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side s Frost detector for use on the air side QAF64.2-J QAF64.6-J With active capillary tube sensing element for acquiring the lowest temperature within a range of 0 15 C With startup function Operating voltage

More information

Beck. The differential pressure transmitter for air

Beck. The differential pressure transmitter for air Beck. The differential pressure transmitter for air Differential pressure transmitter 984 General description The differential pressure transmitters of the 984 series are used to measure differential pressure,

More information

QPM21 Series Duct CO 2 and Air Quality Sensors

QPM21 Series Duct CO 2 and Air Quality Sensors Document No. CE1N1962 QPM21 Series Duct CO 2 and Air Quality Sensors Description Features Application The Carbon Dioxide (CO 2 ) Duct Sensors are directly wired to the controller via twisted pair and/or

More information

Room air quality sensors

Room air quality sensors 1 961 1961P01 QPA20 QPA20 D 1961P02 Room air quality sensors QPA20 Use With maintenance-free CO 2 sensing element based on optical infrared absorption measurement (NDIR 1) ) and depending on the type of

More information

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates 1 883 1883P01 1883P02 1859P04 QFM41.. AQF4150 AQF3153 Symaro Duct sensors for relative humidity and temperature with calibration certificates QFM41.. Operating voltage AC 24 V / DC 13.5...35 V Signal output

More information

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air

Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air Document No. 155-755 Q-Series Relative Humidity and Relative Humidity & Temperature Sensors for Critical Environments and Outdoor Air Description Features Application The Q-Series Relative Humidity and

More information

PM100 Room pressure monitor

PM100 Room pressure monitor Room ressure monitor Product descrition Functional descrition Performance features Product descrition For use as a room ressure controller for rooms in which constant air ressure must be maintained. Clean

More information

Gas cylinder scale Model GCS-1

Gas cylinder scale Model GCS-1 Electronic pressure measurement Gas cylinder scale Model GCS-1 WIKA data sheet PE 87.19 Applications Level measurement of liquid gases in gas cabinets and gas distribution systems Level measurement in

More information

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side s Frost detectors for use on the air side QAF63.2-J QAF63.6-J Active capillary tube sensor for acquiring the lowest temperature within a range of 0 15 C Operating voltage AC 24 V Signal output DC 0...10

More information

02/11/2015

02/11/2015 CTH 46 - CTD 43 / 46 CTD 46 Part number 89422108 CTH 46 Heating / cooling function Measurement and setpoint display CTD 43 Heating or cooling function Measurement display Measurement deviation display-setpoint

More information

Use. In ventilating and air conditioning plants to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation.

Use. In ventilating and air conditioning plants to enhance room comfort and to optimize energy consumption by providing demand-controlled ventilation. 1 958 CO 2 /VOC Sensors QPA63 QPA631 QPA632 Sensors designed for sensing indoor air quality in rooms or air ducts; microprocessor-based units consisting of a selective photo-acoustic CO 2 sensor and a

More information

Technical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application

Technical Instructions Document No. CE1N1961 March 17, Room CO 2 and Air Quality Sensors. Description. Features. Application Document No. CE1N1961 QPA20 Room CO 2 and Air Quality Sensors Description The Q-Series Room Carbon Dioxide (CO 2 ) and Air Quality Sensors are especially suited for applications where precise, stable carbon

More information

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode

Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER. Low pressure with PI-control-mode Installation and operation manual DPC200 - DIFFERENTIAL PRESSURE CONTROLLER Low pressure with PI-control-mode Manufacturer: Phone: Fax: E-Mail: Website: Issue: Doc.-no.: Arthur Grillo GmbH Am Sandbach

More information

QPA63... CO 2 /VOC Sensors. Siemens Building Technologies HVAC Products

QPA63... CO 2 /VOC Sensors. Siemens Building Technologies HVAC Products 1 958 1958P01 1958P02 QPA631 QPA632 CO 2 /VOC Sensors QPA63 Sensors designed for sensing indoor air quality in rooms or air ducts; microprocessor-based units consisting of a selective photo-acoustic CO

More information

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power.

QXA2100. Condensation monitor QXA2101. Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power. QXA2100 Condensation monitor QXA2100 Monitor to prevent damage caused by condensation on chilled ceilings and HVAC plants with AC/DC 24 V power. Application Monitors condensation build up in buildings

More information

Room Temperature Controller with LCD

Room Temperature Controller with LCD 3 053 Room Temperature Controller ith LCD for 4-pipe fan coil units for compressors in DX type equipment ith reversing valve Outputs for on / off valve actuators Outputs for 2-stage compressor ith reversing

More information

02/11/2015

02/11/2015 MIC48 With RS 485 link Part number 89422418 Heating and / or cooling function 2 independent alarms Load break detection 2 setpoint which can be selected remotely Manual / automatic power adjustment RS

More information

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications

Pressure sensors. Ex ia I / IIC T6 acc. to ATEX. Features. Description. Measuring ranges. Applications Force Pressure Temperature Switch Pressure sensors Ex ia I / IIC T6 acc. to ATEX with internal diaphragm with front flush diaphragm Accuracy: 0,25% and 0,5 % Standard output: 4...20 ma; 2-wire system Description

More information

Room Temperature Controller

Room Temperature Controller 3 331 Synco 100 Room Temperature Controller with 2 outputs DC 0 RLA162 Room temperature controller for basic ventilation, air conditioning and heating plants Compact design with 2 analog control outputs

More information

FTK+ Application. Types Available. Duct sensor for humidity and temperature. Datasheet

FTK+ Application. Types Available. Duct sensor for humidity and temperature. Datasheet FTK+ Duct sensor for humidity and temperature Datasheet Subject to technical alteration Issue date: 03.04.2018 A002 Application Duct humidity and temperature sensor in new hinged lid enclosure USE for

More information

MSP300 Pressure Transducer

MSP300 Pressure Transducer SECIFICATIONS Analog Output or 14-Bit Digital ressure with 11-Bit Temperature Output One iece Stainless Steel Construction Low Cost 17-4H or 316L Stainless Steel Customizable FEATURES One iece Stainless

More information

PRELIMINARY EDITION

PRELIMINARY EDITION 3 131 PRELIMINARY EDITION 14.01.2003 Synco 700 Heating Controllers Heating controller for medium-size and large buildings. The is used as a heating circuit or primary controller. The controller is supplied

More information

Room Temperature Controller

Room Temperature Controller 3 22 Room Temperature Controller for two-pipe fan coil units with electrical heater RCC2 Outputs for on / off valve actuator and electrical heater Output for three-speed fan Control depending on the room

More information

Air-cooled Condensers

Air-cooled Condensers BNACCSB115 Aircooled Condensers Sales Brochure NTC Series Imroved Energy Efficiency & Reduced Sound Levels Three tiers of fan motor, fixed seed three hase A/C and VSEC (Variable Seed Electronically Commutated),

More information

Preliminary Release. Room Temperature

Preliminary Release. Room Temperature 3 057 Preliminary Release RDF110 RDF110/IR RDF110.2 RDF110.2/IR Room Temperature Controllers with LCD for 2-pipe fan coil units for compressors in DX-type equipment RDF110 Output for an on / off valve

More information

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications Data Sheet 907020 Page 1/9 Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications For measuring relative humidity and temperature For versatile climatic applications and ventilation

More information

MANDÍK MEASUREMENT AND CONTROL SYSTEM

MANDÍK MEASUREMENT AND CONTROL SYSTEM MANDÍK MEASUREMENT AND CONTROL SYSTEM AHU N 17.04.016 Range AHU MANDÍK MANDÍK MEASUREMENT AND CONTROL Characteristics Each variant of the MANDÍK air-conditioning unit can be supplied with a measurement

More information

Differential Pressure and Flow Meter Media 5 Indicator 160 PN 40

Differential Pressure and Flow Meter Media 5 Indicator 160 PN 40 Differential Pressure and Flow Meter Media 5 Indicator 160 PN 40 Application Instrument designed to measure and indicate differential pressure or measured variables derived from it For gases or liquids

More information

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50

Differential Pressure and Flow Meter. Media 5 Indicator 160 Ø PN 50 Differential Pressure and Flow Meter Media 5 Indicator 160 Ø PN 50 Application Transmitter for measuring and indicating the differential pressure or measured variables derived from it Suitable for gases

More information

Duct Temperature Sensors

Duct Temperature Sensors 1 761 1761P03 1761P01 1761P02 Mounting flange AQM63.0 QAM2110.040, QAM2120.040 QAM2120.200, QAM2120.600 Symaro Duct Temperature Sensors QAM21... Passive sensors for acquiring the air temperature in air

More information

I/A Series 716C 1/16 DIN Temperature Controller

I/A Series 716C 1/16 DIN Temperature Controller Product Specifications I/A Series 716C 1/16 DIN Temperature Controller PSS 2C-1B5 A The Foxboro 716C is a powerful compact, 1/16 DIN, microprocessor-based temperature controller that offers a variety of

More information

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products 7 418 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of small to medium capacity (without fan) in intermittent operation. The LGA... and this

More information

Hygro/hygrothermal transducers (hygrometric)

Hygro/hygrothermal transducers (hygrometric) Data Sheet 90.7031 Page 1/7 Hygro/hygrothermal transducers (hygrometric) for measuring relative humidity and temperature for mounting indoors, outdoors, and in air ducts with resistance, current or voltage

More information

Room Temperature Sensor

Room Temperature Sensor 2 701 Synco 900 Room Temperature Sensor QAA910 Wireless room temperature sensor for acquiring the room temperature RF communication based on KNX standard (868 MHz, unidirectional) Battery-powered by commercially

More information

THERMASREG TR 040 THERMASREG TR 060

THERMASREG TR 040 THERMASREG TR 060 THERMASREG TR 040 THERMASREG Temperature controllers, one-step, Mechanical temperature controllers wet room temperature controllers THERMASREG TR 040 with switching output and stainless steel capillary

More information

Fans in Cement Plants. a company of

Fans in Cement Plants. a company of Fans in Cement Plants a comany of Comany overview. TLT-Turbo is one of the world's leading manufacturers of technology-driven industrial fans and ventilation systems. TLT-Turbo offers service for any axial

More information

U86B. Urea Dosing SPECIFICATIONS FEATURES APPLICATIONS

U86B. Urea Dosing SPECIFICATIONS FEATURES APPLICATIONS SPECIFICATIONS Mountable with O-ring seal Stainless Steel wetted surfaces Amplified ASIC calibrated Absolute, sealed gage Cable option Analog output SENT Output Optional (contact factory for details) FEATURES

More information

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20

Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20 Electronic Pressure Measurement Intrinsically Safe Pressure Transmitters for installation in hazardous locations Models IS-20-S, IS-21-S, IS-20-F, IS-21-F WIKA Datasheet IS-20 Applications Chemical, Petrochemical

More information

Semi flush-mount room thermostat

Semi flush-mount room thermostat 3 078 Semi flush-mount room thermostat for CAV / VAV heating and cooling systems for AHU systems for universal heating and cooling systems RDU340 Modulating PI control Control depending on the room or

More information

Oxygen (O2) Single-Point Gas Detection System

Oxygen (O2) Single-Point Gas Detection System Oxygen (O) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in oxygen (O) sensor, accepts one analog remote device such as a secondary gas sensor, temperature or humidity

More information

Room Temperature Controllers

Room Temperature Controllers 3 021 Room Temperature Controllers for two-pipe fan coil units RCC10 Output for on / off valve actuator Outputs for three-speed fan Control depending on the room or return air temperature (RCC10) Automatic

More information

RPS/DPS High Accuracy Resonant Pressure Sensor. GE Measurement & Control. Features:

RPS/DPS High Accuracy Resonant Pressure Sensor. GE Measurement & Control. Features: GE Measurement & Control RPS/DPS 8100 High Accuracy Resonant Pressure Sensor For over 35 years, Druck has manufactured precision pressure sensors with a capability to meet critical applications in industrial,

More information

Protective Vents adhesive series

Protective Vents adhesive series Imrove Your Equiment s Reliability and Durability Venting for Protection Outdoor enclosures are continuously exosed to harsh environments such as rainstorms, dust, sand and high winds. During changing

More information

Room thermostats with LCD for wall mounting

Room thermostats with LCD for wall mounting s 3 181 RDG100 / RDG110 RDG140 / RDG100 RDG100/H Room thermostats with LCD for wall mounting for fan coil unit applications for universal applications for use with compressors in dx type equipment RDG1

More information

Hygro and Hygrothermo Transducers (capacitive) for climatic applications

Hygro and Hygrothermo Transducers (capacitive) for climatic applications Data sheet 907020 Page 1/7 Hygro and Hygrothermo Transducers (capacitive) for climatic applications To measure relative humidity and temperature For versatile climatic applications and ventilation For

More information

154BC SPECIFICATIONS FEATURES APPLICATIONS STANDARD RANGES

154BC SPECIFICATIONS FEATURES APPLICATIONS STANDARD RANGES SPECIFICATIONS Low Cost 316L Stainless Steel or Titanium 19mm Diameter Package 0-100mV Output Gage and Absolute Wide Compensated Temperature Range FEATURES O-Ring Mount -20ºC to +85ºC Compensated Temperature

More information

MS4525 SPECIFICATIONS

MS4525 SPECIFICATIONS SPECIFICATIONS PCB Mounted Pressure Transducers Amplified Ratiometric Analog Output Differential, Gage, Absolute, Compound, & Vacuum Temperature Compensated 3.3 or 5.0 V DC Supply Voltage The MS4525 is

More information

Use. Functions. Key function. Other functions

Use. Functions. Key function. Other functions 2 466 Heating Control System RVP102/SET Heating control system for use in smaller plants. Control of boiler temperature through direct burner control, pump control, weather-compensated setpoint (with or

More information

Sensor unit MC2 with analog output for Freon gases and refrigerants

Sensor unit MC2 with analog output for Freon gases and refrigerants Page 1 Dec. 2018 Sensor unit MC2 with analog output for Freon gases and refrigerants Exchangeable sensor unit including digital value processing and self control for the continuous monitoring of the ambient

More information

The MVR Turbo Fan The next generation of technology. a company of

The MVR Turbo Fan The next generation of technology. a company of The MVR Turbo Fan The next generation of technology a comany of The MVR Turbo Fan. TLT-Turbo Think globally Act locally. We reduce your oerating costs. Innovations of TLT-Turbo GmbH 1873 First centrifugal

More information

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW 1 212 Double thermostat Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW RAZ-TW... 2-position control thermostat and thermal reset limit thermostat with singlepole

More information

RE-PR3-E-27 3-Phase Panel Mount 27kW

RE-PR3-E-27 3-Phase Panel Mount 27kW Page 1 of 6 RE-PR3-E-27 3-Phase Panel Mount 27kW Features: Benefits: 0-10Vdc, 0-5Vdc, 4-20mA or manual via potentiometer control input Over temperature protection with auto reset Enclosed panel mounting

More information

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System Nitrogen Dioxide (NO) Single-Point Gas Detection System DESCRIPTION Wall-mounted gas monitor with built-in nitrogen dioxide (NO)/diesel fume gas sensor, accepts one analog remote device such as a secondary

More information

JBE LED2000 INDUSTRIAL SOLUTIONS FOR LED & INCANDESCENT MAINS LIGHTING FLICKER FREE TRAILING EDGE DIMMER

JBE LED2000 INDUSTRIAL SOLUTIONS FOR LED & INCANDESCENT MAINS LIGHTING FLICKER FREE TRAILING EDGE DIMMER JBE LED2000 INDUSTRIAL SOLUTIONS FOR LED & INCANDESCENT MAINS LIGHTING FLICKER FREE TRAILING EDGE DIMMER JBE LED Dimming Controller for 110V* & 220V/ 240V AC LED Systems Thank you for purchasing high quality

More information

154BC SPECIFICATIONS. Please refer to the 154N uncompensated and constant voltage datasheets for more information on different features of the 154.

154BC SPECIFICATIONS. Please refer to the 154N uncompensated and constant voltage datasheets for more information on different features of the 154. SPECIFICATIONS Low Cost 316L Stainless Steel or Titanium 19mm Diameter Package 0-100mV Output Gage and Absolute Wide Compensated Temperature Range The 154BC is a 19mm small profile, media compatible, piezoresistive

More information

Analog Room Pressure Monitor RPC Series

Analog Room Pressure Monitor RPC Series Description The Room Pressure Monitor is used to measure differential pressure in the range of 0.125 to 1"wc or 30 to 250 Pa. It combines precision high sensitivity silicon sensing capabilities and the

More information

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR

HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR HEAT MONITORING AND CONTROL INSTRUMENTS FOR TRANSFORMERS MB 103 TEMPERATURE CONTROL UNIT PT 100 TEMPERATURE SENSOR 2 MB 103 TRANSFORMER TEMPERATURE CONTROL UNIT WITH CONTROL SIGNAL Recent approval of new

More information

M7100 Pressure Transducer

M7100 Pressure Transducer SPECIFICATIONS Performance standard on and off highway engine and vehicle OEMs Rugged for heavy equipment and outdoor use Designed specifically for high volume applications Stainless steel wetted surfaces

More information

Analog Transmitter AT1000 AT1

Analog Transmitter AT1000 AT1 Technical Information Analog Transmitter AT1000 AT1 Alarm Transmitter for Mechanical Level Gauges Application AT1 analog transmitter is designed to be installed to the LT, and LTC series float level gauge.

More information

Basic Board Mount Pressure Sensors: NBP Series Uncompensated/Unamplified 60 mbar to 10 bar [1 psi to 150 psi]

Basic Board Mount Pressure Sensors: NBP Series Uncompensated/Unamplified 60 mbar to 10 bar [1 psi to 150 psi] Basic Board Mount Sensors: NBP Series Uncompensated/Unamplified 60 mbar to 10 bar [1 psi to 150 psi] DESCRIPTION Honeywell s Basic Board Mount Sensors: NBP Series Uncompensated/Unamplified are low pressure

More information

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements Specifications COMMANDER 150 Universal Process Indicator High visibility 6-digit LED display the clearest view of your process status 0.1% measurement accuracy precise indication of process measurement

More information

Interchangeable thermistor (THE types) Output Contact E5CS-R1KJX-F E5CS-R1PX-F E5CS-R1GX-F Voltage E5CS-Q1KJX-F E5CS-Q1PX-F E5CS-Q1GX-F

Interchangeable thermistor (THE types) Output Contact E5CS-R1KJX-F E5CS-R1PX-F E5CS-R1GX-F Voltage E5CS-Q1KJX-F E5CS-Q1PX-F E5CS-Q1GX-F Temperature Controller 1/16 DIN Sized Controller Offers Selectable Control, Alarm Modes Accurate to ±0.5% of full scale Multiple temperature scale ranges allow flexibility to match application Field-selectable

More information

Immersion Temperature Controller

Immersion Temperature Controller 3 333 Synco 100 Immersion emperature Controller with 2 outputs DC 0 RLE162 Immersion temperature controller for water-side control in heating and cooling plants Compact design with 2 analog control outputs

More information

HT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH

HT-1300 Series. Temperature and Humidity Duct Sensor. Product Bulletin. Power Supply VDC / 24 VAC. Humidity Accuracy 2.5% RH from 10 to 95% RH HT-1300 Series Temperature and Humidity Duct Sensor Product Bulletin Specifically designed for HVAC application, the HT-130x-UD1 sensor is a highly accurate and reliable for measuring relative air humidity

More information

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment 3 057 RDF110 RDF110/IR RDF110.2 RDF110.2/IR Room Temperature Controllers with LCD for 2-pipe fan coil units for compressors in DX type equipment RDF110 Output for on / off valve actuator or 1-stage compressor

More information

VL18LL-M/40a/118/128. VL18LL-M/40a/118/128. Fibre optic sensor for glass fibre optics. with M12, 4-pin metal connector

VL18LL-M/40a/118/128. VL18LL-M/40a/118/128. Fibre optic sensor for glass fibre optics. with M12, 4-pin metal connector Fibre optic sensor for glass fibre optics VL18LL-M/40a/118/128 with M12, 4-pin metal connector U! Clearly aranged control panel with very light LED display! Flashing power on LED in case of short-circuit!

More information

Issue C. Installation Instructions for the Basic Amplified Board Mount Pressure Sensors, ABP Series

Issue C. Installation Instructions for the Basic Amplified Board Mount Pressure Sensors, ABP Series Installation Instructions for the Basic Amplified Board Mount Pressure GENERAL SPECIFICATIONS The ABP Series are piezoresistive silicon pressure sensors offering a ratiometric analog or digital output

More information

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers 1 37 Room Unit for use with heating controllers Digital, multi-functional room unit for the convenient operation of heating controllers from the living room. A setpoint knob and an economy button allow

More information

RH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description

RH & T Sensors & Humidistats. RH-DT Duct Mount RH & T Sensors. Description RH & T Sensors & Humidistats RH-DT Duct Mount RH & T Sensors Description RH-DT Duct Mount RH & T Sensors The RH-DT Duct Mounted Humidity and Temperature Sensors offer the latest technology for high accuracy

More information

EHW 3-KNI The units described in this documentation may only be installed, connected and started up by suitably qualified personnel!

EHW 3-KNI The units described in this documentation may only be installed, connected and started up by suitably qualified personnel! Conductive leakage detectors of the L-Pointer range for extra low voltage SELV or PELV, for connection to NAMUR isolation amplifier or NAMUR fieldbus terminal Jola Spezialschalter K. Mattil & Co. KG Klostergartenstraße

More information

SP-2400 & 2410 Series Smart Valve Positioner (Linear & Rotary)

SP-2400 & 2410 Series Smart Valve Positioner (Linear & Rotary) SP-2400 & 2410 series Positioner are the advanced smart valve positioners which provide easy installation and simple setting and offer the automation systems outstanding reliability in control performance

More information

BC3250. Blowdown Controller

BC3250. Blowdown Controller Local regulations may restrict the use of this product to below the conditions quoted. In the interests of development and improvement of the product, we reserve the right to change the specification without

More information

Hygro/hygrothermal transducers (hygrometric)

Hygro/hygrothermal transducers (hygrometric) Data Sheet 907031 Page 1/7 Hygro/hygrothermal transducers (hygrometric) for measuring relative humidity and temperature for mounting indoors, outdoors, and in air ducts with resistance, current or voltage

More information

ESM x 72 DIN Size Universal Input Temperature Controller

ESM x 72 DIN Size Universal Input Temperature Controller ESM-7720 72 x 72 DIN Size Universal Input Temperature Controller - 4 digits process(v) and 4 digits process set value(sv) display - Universal process input (TC, RTD ) - Configurable ON/OFF,, I, D and ID

More information

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division 7 418 ISO 9001 Gas Burner Controls LGA... The LGA... are used for the startup and supervision of atmospheric gas burners of low to medium capacity, without fan assistance, in intermittent operation. The

More information

ESM x48 DIN 1/16 Temperature Controller. ESM x 48 DIN 1/16 Temperature Controller with Universal Input

ESM x48 DIN 1/16 Temperature Controller. ESM x 48 DIN 1/16 Temperature Controller with Universal Input ESM- 4420 48x48 DIN 1/16 Temperature Controller ESM-4420 48 x 48 DIN 1/16 Temperature Controller with Universal Input - 4 digits process(v) and 4 digits process set value(sv) display - Universal process

More information

Dissolved Oxygen Measurement liquisys M COM 223 / 253

Dissolved Oxygen Measurement liquisys M COM 223 / 253 Technical Information TI 199C/24/ae Dissolved Oxygen Measurement liquisys M COM 223 / 253 Oxygen Controller Benefits at a glance Liquisys M COM 223 Liquisys M COM 253 Due to the modularity of its design,

More information

Frost Protection Thermostat

Frost Protection Thermostat 1 203 Frost Protection Thermostat Electromechanical thermal reset limit thermostat RAK-TW.5..H RAK-TW.5..H.. Use Monitoring of frost protection temperature, with single-pole changeover microswitch Switching

More information

THERMO PRODUCTS USER MANUAL Raffaella IDRO

THERMO PRODUCTS USER MANUAL Raffaella IDRO THERMO PRODUCTS USER MANUAL Raffaella IDRO /INGLESE 2 ... 4 Warnings... 4 Safety... 4 Routine Maintenance... 4 HYDRAULIC SYSTEM... 5 Installation and safety devices... 5 Anti-condensation DEVICE (mandatory)...

More information

Standard SPECIFICATIONS FEATURES APPLICATIONS

Standard SPECIFICATIONS FEATURES APPLICATIONS SPECIFICATIONS PC Board Mountable Pressure Sensor 0-50 mv Output Voltage Excitation Gage, Absolute, and Differential Temperature Compensated FEATURES Dual-in-Line Package 0ºC to 50ºC Compensated Temperature

More information

Dissolved Oxygen Measurement liquisys S COM 223 / 253

Dissolved Oxygen Measurement liquisys S COM 223 / 253 Technical Information TI 199C/07/en No. 51500281 Dissolved Oxygen Measurement liquisys S COM 223 / 253 Oxygen Transmitter Benefits at a glance Measuring transmitter in field or panel-mounted housing Universal

More information

Basic Board Mount Pressure Sensors. NBP Series Uncompensated/Unamplified 60 mbar to 10 bar [1 psi to 150 psi] Datasheet

Basic Board Mount Pressure Sensors. NBP Series Uncompensated/Unamplified 60 mbar to 10 bar [1 psi to 150 psi] Datasheet Basic Board Mount Sensors NBP Series Uncompensated/Unamplified 60 mbar to 0 bar [ psi to 50 psi] Datasheet Basic Board Mount Sensors Honeywell s Basic Board Mount Sensors: NBP Series Uncompensated/Unamplified

More information

Temperature measurement with current output and PNP/NPN transistor switching output output 2 reprogrammable as switching output TS-400-LI2UPN8X-H1141

Temperature measurement with current output and PNP/NPN transistor switching output output 2 reprogrammable as switching output TS-400-LI2UPN8X-H1141 Reading of adjusted values without tools Recessed pushbutton and keylock for secure programming Permanent display of temperature unit ( C, F, K, Ohm) Temperature peak memory Wiring Diagram Type designation

More information

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 contact@arzatoare.ro ; www.arzatoare.ro 7 128 Oil Burner Control LOA44.252A27 Oil burner control for the supervision, startup and control of 1- or

More information

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) IRDH375_D00124_01_D_XXEN/07.2018 Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems) Product

More information

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) T M 1 isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded) Technical Bulletin NAE1012372 / 03.2015 isopv

More information