Peak Performance Home and Building Inspections LLC

Size: px
Start display at page:

Download "Peak Performance Home and Building Inspections LLC"

Transcription

1 Your Property Inspection Report Cover Page Inspection prepared for: Real Estate Agent: - Date of Inspection: 6/22/2016 Size: 6921 SQFT Additional Inspector: Gina Sullivan Inspector: Chris Sullivan 57 Windsor St, Randolph Phone: pphbi@roadrunner.com

2 We appreciate the opportunity to conduct this inspection for you! Please carefully read your entire Inspection Report. Call us after you have reviewed your report, so we can go over any questions you may have. Remember, when the inspection is completed and the report is delivered, we are still available to you for any questions you may have, throughout the entire closing process. Properties being inspected do not "Pass" or "Fail. - The following report is based on an inspection of the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFI outlets may not be installed; this report will focus on safety and function, not current code. This report identifies specific noncode, non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repair any critical concerns and defects. Note that this report is a snapshot in time. We recommend that you or your representative carry out a final walk-through inspection immediately before closing to check the condition of the property, using this report as a guide. Page 1 of 81

3 Summary of Items of Concern Summary of Items of Concern On this page you will find, in RED, a brief summary of any concerns of the inspection, as they relate to Safety and Function. Examples would be bare electrical wires, or active drain leaks. The complete list of items noted is found throughout the body of the report, including Normal Maintenance items. Be sure to read your entire report! For your safety and liability, we recommend that you hire only licensed contractors when having any work done. If the living area has been remodeled or part of an addition, we recommend that you verify the permit and certificate of occupancy. This is important because our inspection does not tacitly approve, endorse, or guarantee the integrity of any work that was done without a permit, and latent defects could exist. Depending upon your needs and those who will be on this property, items listed in the body of the report may also be a concern for you; be sure to read your Inspection Report in its entirety. Note: If there are no comments in RED below, there were no system or safety concerns with this property at the time of inspection. Exterior Page 7 Item: 1 Roof Roof shingles appear to be near the end of their serviceable life. Recommend further evaluation and or repair/ replacement by a certified roofing contractor. Page 12 Item: 5 Decks & Steps Railing loose or damaged at steps. Suggest securing for safety. Railing loose or damaged at deck side. Suggest repair/ replacement or proper securing for safety. Interior Page 17 Item: 1 Laundry Washing machine over commercial space with no catch pan and drain installed. Page 18 Item: 3 Interior Electric Outlet(s) need new cover plates. Suggest repair. Shock Hazard. Utilities Shop Page 29 Item: 2 Heating Flue vent pipe needs proper high heat resistant sealant. Possible source of CO leak. Suggest having repaired for life safety reasons. Page 31 Item: 3 Water Heater Temperature Pressure drain line: more than 6" from floor. One should be installed to terminate within six inches of the floor to minimize personal injury which may be caused by scalding water, in the event of a pressure blow off. Interior Unit 1 Page 32 Item: 1 Kitchen Dishwasher door springs failed or damaged allowing door to fall open. Possible risk of injury. Recommend repair for safety reasons. Page 35 Item: 5 Laundry Unused laundry over finished living space with no catch pan and drain installed. Page 35 Item: 6 Smoke and CO Detectors Some smoke detectors inoperable. Strongly recommend to install or replace for life safety reasons. Utilities Unit 1 Page 38 Item: 1 Electrical Panel Over current electrical panels not to be located in closet near combustibles. Interior Unit 2 Page 2 of 81

4 Page 40 Item: 3 Bedrooms Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 41 Item: 5 Smoke and CO Detectors CO detector mounted too high above sleeping level. Suggest installation at proper level for life safety reasons. Utilities Unit 2 Page 44 Item: 2 Water Heater Electrical wires are not properly secured. Shock hazard. Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Interior Unit 3 Page 45 Item: 1 Kitchen GFCI trip test failed to the outlets to the right of the sink. Recommend electrical contractor for repair. Outlet inoperable. Shock hazard. Suggest Repair. Page 47 Item: 4 Smoke and CO Detectors CO detector mounted too high above sleeping level. Suggest installation at proper level for life safety reasons. Utilities Unit 3 Page 50 Item: 2 Water Heater Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Interior Unit 4 Page 53 Item: 3 Bedrooms Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 53 Item: 4 Smoke and CO Detectors Some smoke detectors inoperable. Strongly recommend to install or replace for life safety reasons. Utilities Unit 4 Page 56 Item: 1 Electrical Panel Double tapped breaker inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. Page 3 of 81

5 Page 56 Item: 2 Water Heater Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Temperature Pressure drain line is missing. One should be installed to terminate within six inches of the floor to minimize personal injury which may be caused by scalding water, in the event of a pressure blow off. Interior Unit 5 Page 58 Item: 1 Kitchen GFCI trip test failed. Recommend electrical contractor for repair. Page 60 Item: 3 Bedrooms Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 60 Item: 4 Smoke and CO Detectors No smoke/ CO detector was noted at time of inspection. Recent state law requires buyer insure the installation of a carbon monoxide detector at the time of any real estate transaction. Strongly recommend installation for life safety reasons. Page 61 Item: 7 Interior Electric Outlet needs new cover. Suggest repair. Shock Hazard. Utilities Unit 5 Page 63 Item: 1 Electrical Panel Double tapped breaker(s) inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. Page 63 Item: 2 Water Heater Electrical wires are not properly secured. Shock hazard. Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Interior Unit 6 Page 65 Item: 1 Kitchen GFCI trip test failed at the far left outlet. Recommend electrical contractor for repair. Page 67 Item: 4 Utilities Unit 6 Smoke and CO Detectors Some smoke detectors inoperable. Strongly recommend to install or replace for life safety reasons. Page 4 of 81

6 Page 70 Item: 1 Electrical Panel Double tapped breaker(s) inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. Page 70 Item: 3 Water Heater Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Interior Unit 7 Page 74 Item: 3 Bedrooms Bedroom does not have proper egress window. An egress window must satisfy four International Residential Code (IRC) criteria: Minimum width of opening: 20 in. Minimum height of opening: 24 in. Minimum net clear opening: 5.7 sq. ft. (5.0 sq. ft. for ground floor). Maximum sill height above floor: 44 in. Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 74 Item: 4 Smoke and CO Detectors Some smoke detectors missing/ inoperable. Strongly recommend to install or replace for life safety reasons. Utilities Unit 7 Page 77 Item: 1 Electrical Panel Double tapped breaker(s) inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. Page 77 Item: 2 Water Heater Temperature Pressure drain line is missing. One should be installed to terminate within six inches of the floor to minimize personal injury which may be caused by scalding water, in the event of a pressure blow off. Page 5 of 81

7 Exterior As with all areas of the house, we recommend that you carefully examine the roof immediately prior to closing the deal. Note that walking on a roof voids some manufacturer s warranties. Adequate attic ventilation, solar / wind exposure, and organic debris all affect the life expectancy of a roof (see for roof info). Always ask the seller about the age and history of the roof. On any home that is over 3 years old, experts recommend that you obtain a roof certification from an established local roofing company to determine its serviceability and the number of layers on the roof. We certainly recommend this for any roof over 5 years of age. Metal roofs in snow areas often do not have gutters and downspouts, as there is a concern that snow or ice cascading off the roof may tear gutters from the house. Likewise, be advised that such cascading may cause personal injury or even death. If this house has a metal roof, consult with qualified roofers or contractors regarding the advisability of installing a damming feature which may limit the size and amount of snow / ice sliding from the roof. Grading and drainage are probably the most significant aspects of a property, simply because of the direct and indirect damage that moisture can have on structures. More damage has probably resulted from moisture and expansive soils than from most natural disasters. Also, there should be gutters and downspouts with splash blocks that discharge away from the building. We have discovered evidence of moisture intrusion inside structures when it was raining that would not have been apparent otherwise. In addition, we recommend that downspouts do not terminate over paved areas such as walks or driveways, as they can contribute to icy slip and fall hazards in winter. Minor settlement or hairline cracks in drives, walks or even foundations are are normal to properties of any age. They should, however, be monitored for expansion and sealed as necessary. Note that any siding, but especially composition or hardboard siding must be closely monitored. A classic example is the older style Louisiana Pacific siding, where the failure and deterioration provided grounds for a class action lawsuit. Even modern composition siding and, especially, trim, is particularly vulnerable to moisture damage. All seams be must remain sealed and paint must be applied periodically (especially the lower courses at ground level). It is imperative that continued moisture be kept from it, especially from sprinklers, rain splash back or wet grass. Swelling and deterioration may otherwise result. Vegetation too close to the home can contribute to damage through root damage to the foundation, branches abrading the roof and siding, and leaves providing a pathway for moisture and insects into the home. Although rails are not required around drop-offs less than 30, consider your own personal needs and those of your family and guests. By today s standards, spindles at decks and steps should be spaced no more than 4 apart for the safety of children. Open window wells should have either grates or, preferably, a weatherproof shield installed over them. This will keep rain and snow from building up inside the well and possibly leaking into the home, as well as minimizing your liability from children and non-residents falling inside them. An egress ladder should also be installed within the well, especially at below-grade bedrooms. Page 6 of 81

8 1. Roof Materials: Roof Material - Composition Shingle Roof Material - Rubber Inspection Method - Traversed Shingles tabs pitting. Shingles tabs deteriorated. Exposed nail(s) at roof top. Suggest sealing/ caulking to prevent potential water intrusion. Debris noted at roof. Suggest cleaning. Moss present at roof, as moss tends to hold moisture this can accelerate shingle deterioration. Suggest removal, you can use a non toxic oxygen bleach powder mixed with water. If you keep the roof surface wet with the solution for just 20 minutes, and then lightly scrub the roof surface, the algae almost always comes off. Use caution at roof top. Introduction of copper at the roof can help the growth of moss. Visit a roofing supply store. Drip edge/ flashing damaged/ missing. The drip edge is to keep the rain water from soaking up under the roofing shingles and causing dry rot of the plywood under the felt paper. It also diverts water into the gutter instead of going behind the gutter, which could also dryrot of the wood behind the gutter. This can cause the gutter to come loose and even make it pull away from the fascia board or rafter tails. Recommend repair or replacement. Roof deck sagging or buckling. Semi flat roof noted. Suggest monitor for snow loads and clear as needed. Building permits are generally designed to carry snow loads of 40lbs per square foot. Roof has many peaks and valleys. Suggest clearing of gathered debris and snow loads to extend the life of the roof/ shingles. Damaged/ deteriorated flashing at plumbing vent. Suggest repair or replacement to prevent water penetrating underneath shingles. Multiple layered shingles. Maximum amount shingle layers is two. Recommend repair or replacement. Flashing/ caulk needs repair back semi flat roof. Roof shingles appear to be near the end of their serviceable life. Recommend further evaluation and or repair/ replacement by a certified roofing contractor. Composite shingled roof Roof has many peaks and valleys Page 7 of 81

9 Shingles tabs pitting Exposed nail(s) at roof top Rubber membrane Debris at rubber membrane Multiple layered shingles Drip edge/ flashing damaged/ missing Page 8 of 81

10 Shingles tabs deteriorated Flashing/ caulk needs repair back semi flat roof Exposed nail heads Missing shingles Composite shingle roof Shingle tabs loose Page 9 of 81

11 2. Chimney Moss present on the roof Plumbing vent needs caulk repair Chimney Material - Brick Chimney mortar shows sign of deterioration. Recommend having repaired as necessary. Chimney crown is damaged. Chimney has 1 flue. 3. Foundation Chimney mortar shows sign of deterioration No major system safety or function concerns noted at time of inspection. Page 10 of 81

12 4. Siding Concrete block foundation Information: Wood/ vinyl siding, wood frame construction, Concrete block foundation. Areas of eaves (Fascia) are in need of paint, repairs or replacement. Caulk and seal all gaps, cracks and openings. Dryer vent cover needs cleaning. Vinyl siding damage noted. Recommend repair or replacement of damaged sections to keep moisture and insects from harming structure. Some siding missing/ damage noted. Have repaired as necessary. Areas of eaves (Fascia) are in need of repairs Siding missing in areas Page 11 of 81

13 Clear dryer vent Seal all gaps/ cracks 5. Decks & Steps Vinyl siding missing Steps are deteriorated and should be evaluated for repair or replacement. Deck support posts/ girder improperly constructed, as the support relies strictly on the shear strength of nails. Damaged/ deteriorated steps. Possibly trip hazard. Suggest repair for safety reasons. Seal steps: Recommend treating with a waterproof sealant claiming to waterproof, block ultraviolet light, and stop mildew. Stairways physically shake. Recommend evaluation/ repair by contractor. Railing loose or damaged at steps. Suggest securing for safety. Railing loose or damaged at deck side. Suggest repair/ replacement or proper securing for safety. Page 12 of 81

14 Deck support posts/ girder improperly constructed Damage steps at front entry Handrails missing Railing loose Stairways physically shake Page 13 of 81

15 6. Electrical, Exterior Overhead service noted. Main service breaker noted at electrical meter. Suggest caulking around where service cable enters the house to prevent water intrusion into the interior panel. Overhead main electric service 100 amp main breakers 7. Window Condition Suggest caulking around where service cable enters the house Some window screens missing. Check with seller to determine if they are on the property. Window frame(s) need painting and or sealing. Page 14 of 81

16 8. Gutters Window frames need paint Information: No gutters or downspouts. Installation recommended, at least over entranceways and walks, to keep water away from structure. Water can weaken the foundation and deteriorate the siding. Be sure to install splashblocks or extensions to carry water away, and keep water from areas such as driveways or walks where it can be an ice hazard in winter 9. Grading Information Grading appears to be adequate to shed water away from foundation. 10. Exterior Fuel Tanks Kerosene/ oil tank noted. 11. Exterior Misc Kerosene/ oil tank noted Heat pumps noted at the exterior. Monitor heater direct vent does not meet clearance standard from roof. Monitor for snow loads and proper venting. Page 15 of 81

17 Heat pumps noted at the exterior Monitor heater direct vent does not meet clearance Page 16 of 81

18 Interior This inspection does not include testing for radon, mold or other hazardous materials unless specifically requested. Plumbing is an important concern in any structure. Moisture in the air and leaks can cause mildew, wallpaper and paint to peel, and other problems. The home inspector will identify as many issues as possible but some problems may be undetectable due to problems within the walls or under the flooring. Note that if in a rural location, sewer service and/or water service might be provided by private waste disposal system and/or well. Inspection, testing, analysis, or opinion of condition and function of private waste disposal systems and wells is not within the scope of a home inspection. Recommend consulting with seller concerning private systems and inspection, if present, by appropriate licensed professional familiar with such private systems. If a Septic System is on the property, pumping is generally recommended prior to purchase, and then every three years. Interior areas consist of bedrooms, baths, kitchen, laundry, hallways, foyer, and other open areas. All exposed walls, ceilings and floors will be inspected. Doors and windows will also be investigated for damage and normal operation. Although excluded from inspection requirements, we will inform you of obvious broken gas seals in windows. Please realize that they are not always visible, due to temperature, humidity, window coverings, light source, etc. Your inspection will report visible damage, wear and tear, and moisture problems if seen. Personal items in the structure may prevent the inspector from viewing all areas, as the inspector will not move personal items. An inspection does not include the identification of, or research for, appliances and other items that may have been recalled or have had a consumer safety alert issued about it. Any comments made in the report are regarding well known notices and are provided as a courtesy only. Product recalls and consumer product safety alerts are added almost daily by the Consumer Product Safety Commission. We recommend visiting the following Internet site if recalls are a concern to you: 1. Laundry Coin operated laundry. Washing machine over commercial space with no catch pan and drain installed. 2. Smoke and CO Detectors Washing machine over commercial space This building has a smoke/fire/security system installed. Inspection of this system is beyond the scope of this inspection. Suggest having seller demonstrate use. Functioning combination smoke and CO detector noted in building. Page 17 of 81

19 This building has a smoke/fire/security system installed 3. Interior Electric Outlet(s) need new cover plates. Suggest repair. Shock Hazard. Functioning smoke/co Detectors Outlets needs covers Page 18 of 81

20 Utilities Electric: Note that only actual GFCI outlets are tested and tripped. Some baths may have non- GFCI outlets which are protected by a GFCI outlet in a remote area (garage, another bath, etc.). Confirm with owner that apparent non-gfci outlets within 6 of wet areas are thus protected. Also, note that most electricians agree that smoke detectors are good for about 5 years, and the breakers in your panel box have an expected life of about 20 years. Therefore, if this home was built before 1990, consider having the panel box and breakers evaluated by a licensed electrician, as an overheated breaker can result in a structural fire. If your home does not have a carbon monoxide detector (few do!), we recommend making that investment. Any home that has a Bulldog Pushmatic, Zinsco, Sylvania Zinsco or Federal Pacific Electric panel should have it evaluated by a licensed electrician, as these older types of panels and breakers have been known to overheat and cause house fires. Heat: The heating, ventilation, air conditioning and cooling system (often referred to as HVAC) is the climate control system for the structure. The goal of these systems is to keep the occupants at a comfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs at a minimum. The HVAC system is usually powered by electricity and natural gas, but can also be powered by other sources such as butane, oil, propane, solar panels, or wood. The inspector will test the heating and air conditioner using the thermostat or other controls. A more thorough investigation of the system, including the heat ( firebox ) exchanger, should be conducted by a licensed HVAC service person every year. Failure to do so may result in carbon monoxide escaping through cracks in a heat exchanger or flue pipe, resulting in death. 1. Electrical Panel Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located at laundry room. Panel Manufacturer - Siemens No major system safety or function concerns noted at time of inspection at main panel box. 2. Water Supply Main water shutoff/ meter located in Basement. Electrical panel Page 19 of 81

21 Main water shutoff/ meter Page 20 of 81

22 1. Comments Basement Materials: Basement Traversed Support Beam Wood Support Post Wood/ Steel Insulation noted at - ceiling Lack of insulation at rim joist. Suggest installation. Two 275 gal oil tanks appear to be good condition. Tanks not fully visible due to obstruction. Wood soil contact recommend concrete footer to protect wood. Wood beam needs replacing as soon as possible. Concrete block damage/ movement. Monitor for any further movement and repair as needed. Support joist deteriorated/ damaged noted. Suggest installation of sister joist or remove and replace of damaged joist. Twisting at main beam. Plumbing in unconditioned space should be insulated/ heat taped. Two 275 gal oil tanks appear to be good condition Support post is deteriorated Wood joist damage above beam Twisting at main beam Page 21 of 81

23 Plumbing in unconditioned space should be insulated View of crawlspace/ basement Wood soil contact recommend concrete footer Concrete block damage/ movement Page 22 of 81

24 1. Comments Attic Materials: Attic access through - Hallway Inspection Method - Viewed from hatch Insulation Material - Fiberglass No ventilation for the attic Attic hatch is not insulated over. Suggest insulating and even sealing attic hatch to reduce energy costs. Compressed insulation noted in attic. Compressed insulation will not provide its full rated R- value. If adding insulation in an older, the electrical system should be checked by an electrician if the wiring is degraded, overloaded, or uses knob- and- tube wiring. It is hazardous to add insulation when conditions such as these exist. Adding thermal insulation within a closed cavity around wires could cause the wires to overheat. Code does not allow the installation of loose- fill, rolled or foam- in- place insulation around knoband- tube wiring. Drop ceiling space Drop ceiling space Drop ceiling space Attic access Page 23 of 81

25 Limited access in the attic Lack of ventilation in the attic Exhaust vent terminates out the roof Page 24 of 81

26 1. Kitchen Interior Shop No evidence of active leaking at kitchen sink at the time of the inspection GFCI trip test operated properly at time of inspection. 2. Half Bath Utility room Toilet functioned properly at time of inspection. No evidence of active leaking at sink at time of inspection. GFCI trip test operated properly at time of inspection. 3. Half Bath 1 Half bathroom Toilet functioned properly at time of inspection. GFCI trip test operated properly at time of inspection. Sink drain plug missing. Suggest installation. Sink drain line leaks. Recommend repair by professional plumber. Water temperature Page 25 of 81

27 Half bathroom 1 4. Smoke and CO Detectors Sink drain line leaks This space has a smoke/fire/security system installed. Inspection of this system is beyond the scope of this inspection. Suggest having seller demonstrate use. 5. Floors, Ceilings & Walls Fire suppressant system Past or present water stains, dry at time of inspection. Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. Sloping floor, bulges and or dips in floor. Determining the exact cause of any sloping/bulges/dips would require removal of the floor covering or other destructive testing, which is not within the scope of the home inspection. Note that this phenomena is common for a house of this age, but a structural engineer or contractor should be consulted to verify integrity of structure. Potential trip hazards at entrances to different floor levels, throughout house. Use caution. Wear to floor finish materials noted. This is not a structural issue but you may want to consider repair. Page 26 of 81

28 Dry ceiling stains Foor damage is not structural concern 6. Heating Interior of the shop Baseboard heat throughout home functioned properly at time of inspection. Forced hot air heat/ cooling throughout home functioned properly at time of inspection. Heat did not function in shop at time of inspection. Suggest having seller demonstrate proper functioning heater before closing. Page 27 of 81

29 Air conditioning functioned properly Heat functioned properly Heat functioned properly Heat did not function Page 28 of 81

30 1. Electrical Panel Utilities Shop Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located at wall Panel Manufacturer - Cutler Hammer Cutler hammer panel in shop storage glued/ sealed shut. 2. Heating Cutler hammer panel in shop storage glued/ sealed shut Information: Manufacturer - Buderus Location - Utility room Oil fired boiler Heating in shop - Hot water baseboard Emergency shutoff in utility room. Boiler was tested and run for minimum of 10 minutes and was found to function properly at time of inspection. Oil Tank are two 275 gallon tank and appears to be in good condition. The oil line is properly sleeved to protect from damage. While not required, it is suggested the oil filter be protected to prevent damage from items falling and hitting it which can cause oil leaks. No fire resistant ceiling below a finished living area. Suggest installation of.26 gauge sheet metal. Chimney cleanout door deteriorated/ damaged. Unable to verify if chimney flue is properly lined. Suggest further evaluation by a certified chimney contractor. Flue vent pipe needs proper high heat resistant sealant. Possible source of CO leak. Suggest having repaired for life safety reasons. Page 29 of 81

31 Oil fired boiler No fire resistant ceiling below a finished living area High heat sealant needs repair Chimney cleanout door deteriorated/ damaged Emergency shutoff in utility room Page 30 of 81

32 3. Water Heater Information: Location - Utility Closet Location - Bathroom Bradford White Manufacturer - GE Capacity unknown Type - Electric water heater (Shutoff is located at panel box) No major system safety or function concerns noted at time of inspection Bradford White. Temperature Pressure drain line: more than 6" from floor. One should be installed to terminate within six inches of the floor to minimize personal injury which may be caused by scalding water, in the event of a pressure blow off. Temperature Pressure drain line: more than 6" from floor Electric hot water tank Page 31 of 81

33 1. Kitchen Interior Unit 1 No evidence of active leaking at kitchen sink at the time of the inspection Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Microwave functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. Dishwasher was checked for power and water, but was not run for a full cycle without owner present. GFCI trip test operated properly at time of inspection. Water Temperature checked and it held constant between /- degrees F. Water staining noted at sink cabinet bottom. Possible past leaking or stored cleaning products residue. Dishwasher door springs failed or damaged allowing door to fall open. Possible risk of injury. Recommend repair for safety reasons. Unit 1 Kitchen Hot water temperature Prong stuck in an outlet Page 32 of 81

34 2. Main Bath Oven functioned properly Double trap under the kitchen sink Toilet needs a new assembly. Tub and shower function properly at time of inspection. No evidence of active leaking at sink at time of inspection. GFCI trip test operated properly at time of inspection. No operable exhaust fan in bathroom with shower. Recommend installing properly vented bathroom exhaust fan. Main bathroom Hot water temperature Page 33 of 81

35 3. Bath 2 Leaking from toilet tank Toilet needs a new assembly Toilet functioned properly at time of inspection. Tub and shower function properly at time of inspection. No evidence of active leaking at sink at time of inspection. GFCI trip test operated properly at time of inspection. No operable exhaust fan in bathroom with shower. Recommend installing properly vented bathroom exhaust fan. Tub drain plug damaged/ missing. Tub drains slowly. Recommend clearing drain. Sink drain plug damaged. 4. Bedrooms Bathroom 2 No major system safety or function concerns noted at time of inspection. Hot water temperature Page 34 of 81

36 5. Laundry Bedroom(s) Washing machine water supply lines lack water hammer protection. This is common in houses of this age but todays code require this feature. It is a minor cost and I suggest adding water hammers to the supply lines. Unused laundry over finished living space with no catch pan and drain installed. Laundry supply lack water hammer protection 6. Smoke and CO Detectors Laundry over a finished living space No CO detector was noted at time of inspection. Recent state law requires buyer insure the installation of a carbon monoxide detector at the time of any real estate transaction. Strongly recommend installation for life safety reasons. Some smoke detectors inoperable. Strongly recommend to install or replace for life safety reasons. Page 35 of 81

37 Missing smoke detector 7. Floors, Ceilings & Walls Fire suppressant system Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. Sloping floor, bulges and or dips in floor. Determining the exact cause of any sloping/bulges/dips would require removal of the floor covering or other destructive testing, which is not within the scope of the home inspection. Note that this phenomena is common for a house of this age, but a structural engineer or contractor should be consulted to verify integrity of structure. 8. Heating Sloping floors Loose floating floor Electric baseboard heat throughout home functioned properly at time of inspection. Page 36 of 81

38 Electric baseboard heat functioned properly Page 37 of 81

39 1. Electrical Panel Utilities Unit 1 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Panel box located in closet Panel Manufacturer - Siemens Access to panel box blocked. Panel box was not fully inspected internally. Over current electrical panels not to be located in closet near combustibles. 2. Water Heater Siemens sub panel not accessible Information: Location - Utility Closet Manufacturer - GE Type - Electric water heater (Shutoff is located at panel box) Size /- gallons No major system safety or function concerns noted at time of inspection. Electric water heater Page 38 of 81

40 1. Kitchen Interior Unit 2 No evidence of active leaking at kitchen sink at the time of the inspection Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. GFCI trip test operated properly at time of inspection. Water Temperature checked and it held constant between /- degrees F. 2. Main Bath Kitchen Hot water temperature Toilet functioned properly at time of inspection. Tub and shower function properly at time of inspection. No evidence of active leaking at sink at time of inspection. GFCI trip test operated properly at time of inspection. No operable exhaust fan in bathroom with shower.recommend installing properly vented bathroom exhaust fan. Shower surround needs caulk. Tub drain plug missing. Sink has no overflow drain, use with caution. Page 39 of 81

41 Main Bathroom Hot water temperature 3. Bedrooms Shower surround needs caulk Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 40 of 81

42 4. Stairways Smoke detector missing in the bedroom No major system safety or function concerns noted at time of inspection. 5. Smoke and CO Detectors Main stairway Functioning combination smoke and CO detector noted in home. This home has a smoke/fire/security system installed. Inspection of this system is beyond the scope of this inspection. Suggest having seller demonstrate use. CO detector mounted too high above sleeping level. Suggest installation at proper level for life safety reasons. Page 41 of 81

43 6. Doors Fire suppressant system No major system safety or function concerns noted at time of inspection. 7. Windows CO detector mounted too high above Some window screens missing. Check with seller to determine if they are on the property. 8. Interior Electric No major system safety or function concerns noted at time of inspection. 9. Floors, Ceilings & Walls Past or present water stains, dry at time of inspection. Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. Dry ceiling stains Page 42 of 81

44 10. Interior Misc Unit Heating Unit 2 Forced hot air heat/ cooling throughout home functioned properly at time of inspection. Heat functioned properly Air conditioning functioned properly Page 43 of 81

45 1. Electrical Panel Utilities Unit 2 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located at hallway Panel Manufacturer - Murray Panel cover missing 1 screw. Panel not accessible sealed in frame. 2. Water Heater Panel not accessible sealed in frame Information: Location - Utility Closet Manufacturer - Bradford White Manufacturer and capacity unknown Type - Electric water heater (Shutoff is located at panel box) Electrical wires are not properly secured. Shock hazard. Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Electrical wires are not properly secured Page 44 of 81

46 1. Kitchen Interior Unit 3 No evidence of active leaking at kitchen sink at the time of the inspection Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Microwave functioning properly at time of inspection. Range hood light functioning properly at time of inspection. Range hood fan functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. GFCI trip test operated properly at time of inspection. Water Temperature checked and it held constant between /- degrees F. GFCI trip test failed to the outlets to the right of the sink. Recommend electrical contractor for repair. Outlet inoperable. Shock hazard. Suggest Repair. Unit 3 Kitchen GFCI trip failed/ outlets inoperable Hot water temperature Page 45 of 81

47 2. Main Bath Oven functioned properly Toilet gurgling noted when flushed. Shower function properly at time of inspection. No evidence of active leaking at sink at time of inspection. Exhaust fan noted and functioning properly. GFCI trip test operated properly at time of inspection. Sink faucet is poorly anchored. Main bathroom Hot water temperature Page 46 of 81

48 3. Bedrooms Faucet is loose No major system safety or function concerns noted at time of inspection. 4. Smoke and CO Detectors Bedroom Functioning combination smoke and CO detector noted in home. CO detector mounted too high above sleeping level. Suggest installation at proper level for life safety reasons. Page 47 of 81

49 Combination Smoke / CO 5. Floors, Ceilings & Walls Fire suppressant Past or present water stains, dry at time of inspection. Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. 6. Heating Dry bedroom ceiling stain Electric baseboard heat throughout home functioned properly at time of inspection. Forced hot air heat/ cooling throughout home functioned properly at time of inspection. Page 48 of 81

50 Electric baseboard heat Functioning air conditioning Forced hot air functioned properly Page 49 of 81

51 1. Electrical Panel Utilities Unit 3 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located in bedroom Panel Manufacturer - Siemens No major system safety or function concerns noted at time of inspection at main panel box. 2. Water Heater Electrical panel Information: Size /- gallons Type - Electric water heater (Shutoff is located at panel box) Location - Utility Closet of unit 4 Manufacturer - Bradford - White Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Electric water heater/ no catch pan Page 50 of 81

52 1. Kitchen Interior Unit 4 Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Microwave functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. GFCI trip test operated properly at time of inspection. Refrigerator handle damaged/ missing. Water Temperature checked and it held constant between /- degrees F. Kitchen Refrigerator handle damaged/ missing Hot water temperature Page 51 of 81

53 2. Main Bath Toilet functioned properly at time of inspection. Tub and shower function properly at time of inspection. Sink drain/ trap not accessible due to personal items. GFCI trip test operated properly at time of inspection. No operable exhaust fan in bathroom with shower. Recommend installing properly vented bathroom exhaust fan. Shower surround needs caulk. Tub drain plug missing. Sink has no overflow drain, use with caution. Toilet loose and may need re-anchoring. Main Bathroom Hot water temperature 3. Bedrooms Shower surround needs caulk Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 52 of 81

54 4. Smoke and CO Detectors Smoke detector missing in the bedroom This home has a smoke/fire/security system installed. Inspection of this system is beyond the scope of this inspection. Suggest having seller demonstrate use. Some smoke detectors inoperable. Strongly recommend to install or replace for life safety reasons. 5. Doors Missing smoke detector No major system safety or function concerns noted at time of inspection. 6. Windows Fire suppressant system Some window screens missing. Check with seller to determine if they are on the property. Some window screens damaged. Page 53 of 81

55 7. Interior Electric Outlet did not function. Some window screens damaged 8. Floors, Ceilings & Walls Outlet did not function Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. Sloping floor, bulges and or dips in floor. Determining the exact cause of any sloping/bulges/dips would require removal of the floor covering or other destructive testing, which is not within the scope of the home inspection. Note that this phenomena is common for a house of this age, but a structural engineer or contractor should be consulted to verify integrity of structure. 9. Interior Misc Unit 4 Page 54 of 81

56 10. Heating Unit 4 Propane fired forced hot air heat throughout home functioned properly at time of inspection. Gas shutoff inline. Heat functioned properly Page 55 of 81

57 1. Electrical Panel Utilities Unit 4 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located at kitchen Panel Manufacturer - Murray Double tapped breaker inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. 2. Water Heater Electrical panel Double tapped breaker(s) Information: Location - Unit 3 Utility Closet Size /- gallons Type - Electric water heater (Shutoff is located at panel box) Manufacturer and capacity unknown visibly restricted. Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Temperature Pressure drain line is missing. One should be installed to terminate within six inches of the floor to minimize personal injury which may be caused by scalding water, in the event of a pressure blow off. Page 56 of 81

58 Temperature Pressure drain line is missing/ no catch pan Page 57 of 81

59 1. Kitchen Interior Unit 5 No evidence of active leaking at kitchen sink at the time of the inspection Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Microwave functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. Range dials unreadable. GFCI trip test failed. Recommend electrical contractor for repair. Kitchen GFCI trip test failed Hot water temperature Range dials unreadable Page 58 of 81

60 2. Main Bath Toilet functioned properly at time of inspection. Tub and shower function properly at time of inspection. No evidence of active leaking at sink at time of inspection. GFCI trip test operated properly at time of inspection. No operable exhaust fan in bathroom with shower. Recommend installing properly vented bathroom exhaust fan. Tub drain plug missing. Sink faucet is loose at sink top. Sink has no overflow drain, use with caution. Toilet loose and may need re-anchoring. Main bathroom Sink faucet is loose at sink top 3. Bedrooms Hot water temperature Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. Page 59 of 81

61 4. Smoke and CO Detectors Smoke detector missing in the bedroom This home has a smoke/fire/security system installed. Inspection of this system is beyond the scope of this inspection. Suggest having seller demonstrate use. No smoke/ CO detector was noted at time of inspection. Recent state law requires buyer insure the installation of a carbon monoxide detector at the time of any real estate transaction. Strongly recommend installation for life safety reasons. 5. Doors No smoke/ CO detector was noted at time of inspection No major system safety or function concerns noted at time of inspection. 6. Windows No major system safety or function concerns noted at time of inspection. Page 60 of 81

62 7. Interior Electric Outlet did not function. Outlet needs new cover. Suggest repair. Shock Hazard. Outlet did not function 8. Floors, Ceilings & Walls Outlet needs new cover Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. 9. Interior Misc Unit Heating Unit 5 Electric baseboard heat throughout home functioned properly at time of inspection. Page 61 of 81

63 Electric heat functioned properly Page 62 of 81

64 1. Electrical Panel Utilities Unit 5 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located in kitchen Panel Manufacturer - Murray Double tapped breaker(s) inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. 2. Water Heater Electrical panel Double tapped breakers Information: Location - Utility encased Manufacturer and capacity unknown Type - Electric water heater (Shutoff is located at panel box) Capacity unknown Electrical wires are not properly secured. Shock hazard. Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Page 63 of 81

65 Electrical wires are not properly secured Page 64 of 81

66 1. Kitchen Interior Unit 6 No evidence of active leaking at kitchen sink at the time of the inspection Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. GFCI trip test operated properly at time of inspection. Water Temperature checked and it held constant between /- degrees F. Water staining noted at sink cabinet bottom. Possible past leaking or stored cleaning products residue. GFCI trip test failed at the far left outlet. Recommend electrical contractor for repair. Unit 6 Kitchen GFCI trip failed Hot water temperature Page 65 of 81

67 2. Main Bath Oven functioned properly Toilet functioned properly at time of inspection. Shower function properly at time of inspection. No evidence of active leaking at sink at time of inspection. GFCI trip test operated properly at time of inspection. No operable exhaust fan in bathroom with shower. Recommend installing properly vented bathroom exhaust fan. Shower/ floor junction needs caulk. Main bathroom Hot water temperature Page 66 of 81

68 3. Bedrooms Shower/ floor junction needs caulk No major system safety or function concerns noted at time of inspection. 4. Smoke and CO Detectors Bedroom Smoke Detectors are hardwired but not interconnected. No CO detector was noted at time of inspection. Recent state law requires buyer insure the installation of a carbon monoxide detector at the time of any real estate transaction. Strongly recommend installation for life safety reasons. Some smoke detectors inoperable. Strongly recommend to install or replace for life safety reasons. Page 67 of 81

69 Smoke detector needs battery back up Smoke Detectors not hardwired 5. Heating Inoperable/ not connected Electric baseboard heat throughout home functioned properly at time of inspection. Page 68 of 81

70 Electric heat functioned properly Page 69 of 81

71 1. Electrical Panel Utilities Unit 6 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located in kitchen Panel Manufacturer - Murray Double tapped breaker(s) inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. 2. Heating Electrical panel Information: Heating in home - Electric baseboard heaters Double tapped breakers 3. Water Heater Information: Location - Kitchen Manufacturer and capacity unknown visibly restricted. Hot water tank lacks overflow catch pan and drain over a living space. Recommend installation to prevent the possibility of water damage at below living space. Page 70 of 81

72 Electric water heater Page 71 of 81

73 1. Kitchen Interior Unit 7 No evidence of active leaking at kitchen sink at the time of the inspection Range top functioning properly at time of inspection. Oven/ broiler functioning properly at time of inspection. Refrigerator/ Freezer functioning properly at time of inspection. GFCI trip test operated properly at time of inspection. Water Temperature checked and it held constant between /- degrees F. Unit 1 R Kitchen Hot water temperature Oven functioned properly Page 72 of 81

74 2. Main Bath Toilet functioned properly at time of inspection. Shower functioned properly at time of inspection. No evidence of active leaking at sink at time of inspection. Exhaust fan noted and functioning properly. GFCI trip test operated properly at time of inspection. Reset in the electric panel. Drop in water pressure noted when more than one water supply source was turned on. Recommend having a qualified plumbing contractor evaluate and repair. Sink drains slowly. Recommend clearing drain. Toilet loose and may need a new seal and re-anchoring. Main bathroom Toilet is loose Hot water temperature Page 73 of 81

75 3. Bedrooms Bedroom does not have proper egress window. An egress window must satisfy four International Residential Code (IRC) criteria: Minimum width of opening: 20 in. Minimum height of opening: 24 in. Minimum net clear opening: 5.7 sq. ft. (5.0 sq. ft. for ground floor). Maximum sill height above floor: 44 in. Smoke detectors missing in bedrooms which is common for homes of this age as they may not have been required by code when home was built. Today's code requires hardwired/interconnected detectors be placed in each bedroom and in areas outside bedrooms. Installation strongly recommended for life safety reasons. This should be done by licensed electrician. 4. Smoke and CO Detectors Non egress window (s) Some smoke detectors missing/ inoperable. Strongly recommend to install or replace for life safety reasons. Smoke Detectors missing Building fire suppressant Page 74 of 81

76 5. Floors, Ceilings & Walls Past or present water stains, dry at time of inspection. Normal wear and tear damage to walls and ceilings noted. This is a cosmetic issue and not a material defect. Numerous wall and floor surfaces were obscured by large amounts of furniture and/or stored items, preventing a full evaluation of some areas. Dry bathroom ceiling stain Dry ceiling stain in the living room 6. Heating Dry bedroom ceiling stain Forced hot air heat throughout home functioned properly at time of inspection. Air conditioning did not function at time of inspection. Page 75 of 81

77 Air conditioning did not function Heat functioned properly Page 76 of 81

78 1. Electrical Panel Utilities Unit 7 Materials: Service Entrance - Overhead Service Panel Amperage Amp Service Main disconnect at exterior meter Panel box located in bedroom Panel Manufacturer - Murray Double tapped breaker(s) inside panel box (more than one electrical conductor attached).this is not standard practice, and may cause overheating or even an electrical fire. Recommend evaluation by an electrician. Double tapping and lugging can create hot spots on breakers and neutral bars because they are not tightened to the correct torque--especially if two different size conductors are used. Because the hot [black] and neutral [white]wires are both current carrying conductors, the chance is then greater for potential hot spots. If the double tap or lug becomes loose, it begins to arc. As it arcs it builds up carbon. Carbon is then resistance and with more carbon buildup the more difficult it is for the conductor to make contact, thus increasing the current. The end result can be the breaker tripping because of the loose connection [current exceeding the rating of the breaker], or signs of overheating such as discolored wires, melted wires, etc, or even fire. 2. Water Heater Electrical panel Double tapped breakers Information: Location - Utility Closet Manufacturer - Whirlpool Size /- gallons Type - Electric water heater (Shutoff is located at panel box) Temperature Pressure drain line is missing. One should be installed to terminate within six inches of the floor to minimize personal injury which may be caused by scalding water, in the event of a pressure blow off. Page 77 of 81

79 Electric water heater Page 78 of 81

Troy's Home Inspection Services LLC

Troy's Home Inspection Services LLC Cover Page Property Inspection Report 33706 Inspection prepared for: Cord King & Patricia King Real Estate Agent: Jane Freel - RE/MA Date of Inspection: 3/4/2017 Time: 8:30 Age of Home: 2008 Size: 3279

More information

Inside Out Home Inspections

Inside Out Home Inspections Cover Page Inside Out Home Inspections Property Inspection Report Inspection prepared for: John Doe & Jane Doe Date of Inspection: 5/10/2014 Inspector: Lucas Sargent PO Box 514, Tioga, PA 16946 Phone:

More information

Extra Mile Inspection, Inc.

Extra Mile Inspection, Inc. Cover Page Property Inspection Report Inspection prepared for: Jerry and Lynne Richardson Real Estate Agent: Polly Richardson - BHKR Lake Forest Date of Inspection: 3/13/2017 Time: 12 pm Age of Home: built

More information

1921 River Birch Dr., Shawnee, OK Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny

1921 River Birch Dr., Shawnee, OK Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny Cover Page 74804 Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny Inspector: John Crouch License #70001257 Newalla, OK 74857 Phone: 4054815032 Email: john@goodlivinghomes.com

More information

All In One Home Inspections

All In One Home Inspections Cover Page All In One Home Inspections Property Inspection Report 34241 Inspection prepared for: Jane Smith Date of Inspection: 6/15/2015 Time: 10:00AM Age of Home: 29 Yrs Size: 1631 Lving Weather: Sunny

More information

Inspector Gadget Homes

Inspector Gadget Homes Cover Page Inspector Gadget Homes Property Inspection Report 34105 Inspection prepared for: Mike Cranley Date of Inspection: 3/20/2017 Time: 5:30pm Age of Home: 25 yrs old Size: 3,039 sq ft Weather: Sunny

More information

I. STRUCTURAL SYSTEMS

I. STRUCTURAL SYSTEMS I. STRUCTURAL SYSTEMS A. Foundations Type of Foundation(s): Pier & Beam - Crawlspace Opinion: All exposed areas of the foundation were examined visually. Examination of the foundation was limited to photographs

More information

Axiom Property Inspections

Axiom Property Inspections Cover Page Axiom Property Inspections Property Inspection Report 868 Wally Avenue, Henderson NV, 89178 Inspection prepared for: John Doe Agent: David Lawson - Axiom Inspection Date: 8/12/2010 Time: 2:30

More information

Canadian Property Inspections

Canadian Property Inspections Cover Page Canadian Property Inspections Home Inspection Report L9Z-1K4 Inspection prepared for: K.C. Pitman Date of Inspection: 3/6/2017 Time: 3pm Age of Home: 42 Size: 500-1000 Weather: Cloudy, cool.

More information

Cascade Inspection Services, LLC

Cascade Inspection Services, LLC Cover Page Property Inspection Report 97330 Inspection prepared for: John Smith & Sarah Smith Date of Inspection: 6/8/2015 Time: 8:30 A.M. Age of Home: 14 years old Size: 2352 Sq Ft Weather: Sunny Inspector:

More information

Bayshore House Inspections LLC

Bayshore House Inspections LLC Cover Page Bayshore House Inspections LLC Property Inspection Report 32963 Inspection prepared for: Ron Rosenthal Date of Inspection: 3/23/2017 Time: 10:30am Age of Home: 1950 Size: 3284 Weather: Clear

More information

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski -

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Cover Page Property Inspection Report Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski - Date of Inspection: 3/28/2017 Time: 2:00 Age of Home: Built 1999 Size: 2015 Weather: 50 Overcast.

More information

Excellent Home Inspection Services, LLC

Excellent Home Inspection Services, LLC Property Inspection Report Cover Page 46143 Inspection prepared for: John and Jane Doe Date of Inspection: 4/15/2015 Age of Home: About 12 years Size: 1,600 sq ft Weather: About 60 degrees F The house

More information

John Sample. Property Address: 123 Main St. Alpharetta GA Inspector: Jason David. Residential Inspector of America, Inc.

John Sample. Property Address: 123 Main St. Alpharetta GA Inspector: Jason David. Residential Inspector of America, Inc. John Sample Property Address: 123 Main St. Alpharetta GA 30022 Inspector: Jason David Residential Inspector of America, Inc. 3276 Buford Drive, Ste. 104-306 Buford, GA 30519 770.476.4963 ICC Certified

More information

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM SUMMARY 1234 Main St.Severn 21144 Buyer Name 07/18/2018 9:00AM Henry Toman MD License 32391 1st American Home Inspection, LLC 443-685-4062 henrytoman61@gmail.com The summary is meant to organize the defects

More information

Space Coast Home Inspections LLC

Space Coast Home Inspections LLC Cover Page Property Inspection Report 32908 Inspection prepared for: Melvin Jones & Melvin Jones Real Estate Agent: Anita Uhrmann - Caldwell Banker Date of Inspection: 12/16/2014 Time: 11am Age of Home:

More information

Watson Home Inspection Services, LLC.

Watson Home Inspection Services, LLC. Cover Page Watson Home Inspection Services, LLC. Property Inspection Report 16466 Olalee Rd, Apple Valley Ca., 92307 Inspection prepared for: Jesse Owens & Zona Owens Agent: Ofir Andrews - Hamilton Landon

More information

RW West Consultants. Property Inspection Report

RW West Consultants. Property Inspection Report Cover Page RW West Consultants Property Inspection Report 98122 Inspection prepared for: Faira Date of Inspection: 4/27/2017 Time: 9:00 AM Age of Home: 1992 Size: 3000 Weather: Cloudy 45 degrees Order

More information

Hearth and Homes Inspections, llc

Hearth and Homes Inspections, llc Cover Page Property Inspection Report 44092 Inspection prepared for: Ember Griffith Real Estate Agent: Samantha Elly - Keller Williams Date of Inspection: 3/4/2017 Time: 10:00 AM Age of Home: 63 Years

More information

RW West Consultants. Property Inspection Report NE 199th St, Kenmore, WA Inspection prepared for: FAIRA/ Chris Ellis Real Estate Agent: -

RW West Consultants. Property Inspection Report NE 199th St, Kenmore, WA Inspection prepared for: FAIRA/ Chris Ellis Real Estate Agent: - Cover Page RW West Consultants Property Inspection Report 98028 Inspection prepared for: FAIRA/ Chris Ellis Real Estate Agent: - Date of Inspection: 5/26/2017 Time: 9:00 AM Age of Home: 2012 Size: 2480

More information

Jeff Brown Inspections

Jeff Brown Inspections Cover Page Jeff Brown Inspections Property Inspection Report Vegas NV, 89145 Inspection prepared for: Jim Shen Agent: Lauren Paris - Resolution Realty Inspection Date: 6/13/2013 Time: 10:00 Age: 26 years

More information

The Ultimate Home Maintenance Schedule

The Ultimate Home Maintenance Schedule The Ultimate Home Maintenance Schedule On-Going Quarterly Maintenance Schedule Check interior and exterior faucets for leaks. Clean aerators. Replace washers if Clean with baking soda. Pour water down

More information

FAIRA TRANSPARENCY REPORTS. November 21, 2016

FAIRA TRANSPARENCY REPORTS. November 21, 2016 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 7307 22 nd Ave NW, Seattle, WA

More information

FAIRA TRANSPARENCY REPORTS Waverly Dr, Snohomish, WA May 10 th, 2017

FAIRA TRANSPARENCY REPORTS Waverly Dr, Snohomish, WA May 10 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98296 May 10 th, 2017 We have coordinated

More information

FAIRA TRANSPARENCY REPORTS th Ave NE B-3, Kenmore, WA March 28 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave NE B-3, Kenmore, WA March 28 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 17817 80th Ave NE B-3, Kenmore,

More information

Inspection Report. Cheri Maisonneuve. Property Address: 103 Dogleg Dr Moultrie GA. Welcome Home! Premier Home Inspections of Valdosta, LLC

Inspection Report. Cheri Maisonneuve. Property Address: 103 Dogleg Dr Moultrie GA. Welcome Home! Premier Home Inspections of Valdosta, LLC Inspection Report Cheri Property Address: 103 Dogleg Dr Moultrie GA Welcome Home! Shea Wynn 1709A Gornto Rd, UPS #131 Valdosta, GA 31601 229-292-4694 Table of Contents Cover Page...1 Table of Contents...2

More information

CMHC HOME MAINTENANCE CHECKLIST

CMHC HOME MAINTENANCE CHECKLIST Make sure air vents indoors and outdoors (intake, exhaust and forced air) are not blocked by snow or debris. Check and clean range hood filters on a monthly basis. Test ground fault circuit interrupter(s)

More information

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013 Inspection Report Prepared for: Tonia Mann Property Address: 402 Leslie Court McDonough, GA 30253 Date: March 07, 2013 Inspector: Charles Mann Edifice Inspections, Inc. (770) 594-2222 www.edificeinspections.com

More information

1710 ANYWHERE DRIVE, MONTGOMERY, AL 36109

1710 ANYWHERE DRIVE, MONTGOMERY, AL 36109 1710 ANYWHERE DRIVE, MONTGOMERY, AL 36109 INFRARED VIEW OF HOME Attention: Mr. John Smith SUBJECT PROPERTY The following inspection of a property located at 1710 Anywhere Drive, Montgomery, AL 36109, was

More information

Canadian Property Inspections

Canadian Property Inspections Cover Page Canadian Property Inspections Home Inspection Report N6J-3A8 Inspection prepared for: Josh Baran Date of Inspection: 3/7/2017 Time: 9am Age of Home: 40 Size: 1500 Weather: Cloudy,cool,light

More information

The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM

The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM Property Address: Age of Quarters: Years Date of Inspection: INSPECTION TEAM: Names: Profession/Position (i.e. Board Member,

More information

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on HOME PROPERTY SCAN INSPECTIONS The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on January 11, 2010 and

More information

FAIRA TRANSPARENCY REPORTS. February 28 th, 2018

FAIRA TRANSPARENCY REPORTS. February 28 th, 2018 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 5650 24 th Ave NW, #407, Seattle, WA 98107 February 28 th, 2018 Thank you for your interest

More information

SPS Home Inspections, LLC

SPS Home Inspections, LLC Cover Page SPS Home Inspections, LLC Property Inspection Report 00000 Inspection prepared for: Mr. & Mrs. Homeowner Real Estate Agent: - Date of Inspection: 5/1/2012 Time: 11:00 am Age of Home: 39 Size:

More information

fieldwork report contains the Functional

fieldwork report contains the Functional December 6, 2010 Dear Bill and Ann, On October 2, 2010, Cities Inspection Service, Inc. completed a home inspection of the property located at 2344 Arbour Lane, St. Paul, Minnesota for you. Doug Hastings

More information

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 11550 Stone Ave N, #205, Seattle, WA 98133 Thank you for your interest in this Faira Certified

More information

FAIRA TRANSPARENCY REPORTS. March 14 th, 2017

FAIRA TRANSPARENCY REPORTS. March 14 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 4106 38 th Ave SW, Seattle, WA

More information

This Report Was Prepared For: Property Address Inspected:

This Report Was Prepared For: Property Address Inspected: This Report Was Prepared For: Jane Do (to protect the identity and privacy of our clients) Property Address Inspected: 321 Sample Dr Example Report, FL 32828 Date: August 11, 2115 File # H50855255 The

More information

FAIRA TRANSPARENCY REPORTS Country Club Dr, B-203, Mill Creek, WA April 5 th, 2017

FAIRA TRANSPARENCY REPORTS Country Club Dr, B-203, Mill Creek, WA April 5 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 15433 Country Club Dr, B-203, Mill Creek, WA 98012 Thank you for your interest in this Faira

More information

FAIRA TRANSPARENCY REPORTS th Ave, Seattle, WA April 28 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave, Seattle, WA April 28 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98122 Thank you for your interest in this Faira Certified home. April 28 th, 2017 We have

More information

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc Inspection Report 1 Inspection Way Orlando, FL 32825 Prepared for: Wanda Figueroa Prepared by: Page 1 of 25 Needs Service Summary This summary is not the entire report. The complete report may include

More information

FAIRA TRANSPARENCY REPORTS th Ave N, Edmonds, WA January 19 th, 2018

FAIRA TRANSPARENCY REPORTS th Ave N, Edmonds, WA January 19 th, 2018 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98020 January 19 th, 2018 We have

More information

FAIRA TRANSPARENCY REPORTS th Ave N, Seattle, WA 98109

FAIRA TRANSPARENCY REPORTS th Ave N, Seattle, WA 98109 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98109 Thank you for your interest in this Faira Certified home. We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS NE 178th St, Lake Forest Park, WA May 2 nd, 2017

FAIRA TRANSPARENCY REPORTS NE 178th St, Lake Forest Park, WA May 2 nd, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98155 May 2 nd, 2017 We have coordinated

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Your New Address, Your Town, USA Inspection Date: Inspection Date Prepared For: New Homeowner Prepared By: Complete Home Inspectors P.O. Box 1104 Smiths Station, Alabama 36877 Phone:

More information

FAIRA TRANSPARENCY REPORTS. November 21, 2016

FAIRA TRANSPARENCY REPORTS. November 21, 2016 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 32712 SE 43 rd St., Fall City,

More information

FAIRA TRANSPARENCY REPORTS nd Ave SE, Renton, WA March 21, 2018

FAIRA TRANSPARENCY REPORTS nd Ave SE, Renton, WA March 21, 2018 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98059 March 21, 2018 Thank you for your interest in this Faira Certified home. We have coordinated

More information

FAIRA TRANSPARENCY REPORTS SE Woody Creek Ln, Snoqualmie, WA October 12, 2017

FAIRA TRANSPARENCY REPORTS SE Woody Creek Ln, Snoqualmie, WA October 12, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98065 Thank you for your interest in this Faira Certified home. October 12, 2017 We have

More information

FAIRA TRANSPARENCY REPORTS th Dr NE, Marysville, WA June 14 th, 2017

FAIRA TRANSPARENCY REPORTS th Dr NE, Marysville, WA June 14 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98270 June 14 th, 2017 We have

More information

FAIRA TRANSPARENCY REPORTS th St SW, Lynnwood, WA 98037

FAIRA TRANSPARENCY REPORTS th St SW, Lynnwood, WA 98037 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98037 Thank you for your interest in this Faira Certified home. We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS th St SW, 301, Lynnwood, WA May 31 st, 2017

FAIRA TRANSPARENCY REPORTS th St SW, 301, Lynnwood, WA May 31 st, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 5801 200th St SW, 301, Lynnwood,

More information

SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM

SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM SUMMARY 1234 Main St.Edmonton AB T5T3E9 Buyer Name 07/05/2018 9:00AM Banti Shaw InspecUs InspecUs 7808623549 bantishaw@inspecus.ca This Summary outlines potentially significant issues from a cost, safety

More information

MHI Services Inc. Property Inspection Report

MHI Services Inc. Property Inspection Report Cover Page MHI Services Inc. Property Inspection Report 333 Some place Ave, Some Place OR, 970245 Inspection prepared for: SAMPLE REPORT & SAMPLE REPORT Inspection Date: 3/29/2009 Time: 8AM Age: 9 YEARS

More information

Home Maintenance Schedule

Home Maintenance Schedule Home Maintenance Schedule Regular Maintenance is the Key Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether

More information

While most maintenance is seasonal, there are some things you should do on a frequent basis year-round:

While most maintenance is seasonal, there are some things you should do on a frequent basis year-round: Inspecting your home on a regular basis and following good maintenance practices are the best way to protect your investment in your home. Whether you take care of a few tasks at a time or several all

More information

FAIRA TRANSPARENCY REPORTS th Ave NE, Arlington, WA 98223

FAIRA TRANSPARENCY REPORTS th Ave NE, Arlington, WA 98223 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98223 Thank you for your interest in this Faira Certified home. We have coordinated the efforts

More information

Maintence/Renewal Report

Maintence/Renewal Report Maintence/Renewal Report Property Address: C4U Inspections Lloyd Kenzle CPBC # 47652 3518 Webber Rd. West Kelowna, BC V4T 1H9 866 765-4434 Table of Contents Cover Page... 1 Table of Contents...2 I SUMMARY...

More information

RW West Consultants, Inc. Property Inspection Report Inspector: Clifton Moody (Skip), RW West Consultants, Inc. Cover Page

RW West Consultants, Inc. Property Inspection Report Inspector: Clifton Moody (Skip), RW West Consultants, Inc. Cover Page Property Inspection Report Inspector: Clifton Moody (Skip), RW West Consultants, Inc. Cover Page 98126 Inspection prepared for: Faira.com Real Estate Agent: - Date of Inspection: 11/1/2018 Time: 9:00 AM

More information

FAIRA TRANSPARENCY REPORTS. July 6, 2016

FAIRA TRANSPARENCY REPORTS. July 6, 2016 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 13301 NE 135 th St, Kirkland, WA 98034 July 6, 2016 Thank you for your interest in this Faira

More information

FAIRA TRANSPARENCY REPORTS Alaskan Way, 514, Seattle, WA 98101

FAIRA TRANSPARENCY REPORTS Alaskan Way, 514, Seattle, WA 98101 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 1900 Alaskan Way, 514, Seattle, WA 98101 Thank you for your interest in this Faira Certified

More information

FAIRA TRANSPARENCY REPORTS Spruce Way, Lynnwood, WA August 21, 2017

FAIRA TRANSPARENCY REPORTS Spruce Way, Lynnwood, WA August 21, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98037 August 21, 2017 We have coordinated

More information

FAIRA TRANSPARENCY REPORTS th Ave SE, Renton, WA June 13 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave SE, Renton, WA June 13 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98058 June 13 th, 2017 We have

More information

Final Phase Inspection

Final Phase Inspection Cover Page Property Inspection Report 98258 Inspection prepared for: David Peterson Real Estate Agent: Andrew Freeman - Latham Realty Date of Inspection: 3/10/2017 Time: 2:00 PM Age of Home: Built in 2004

More information

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651)

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651) Page 1 Doc #: Inspector: Date: Dwelling Address: Client Name: Client's Agent: Real Estate Company: Please refer to the General Home Inspection Contract. Thank you for using Minnesota and Western Wisconsin's

More information

FAIRA TRANSPARENCY REPORTS Bothell Everett Hwy, D304, Bothell, WA February 6, 2018

FAIRA TRANSPARENCY REPORTS Bothell Everett Hwy, D304, Bothell, WA February 6, 2018 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 18930 Bothell Everett Hwy, D304, Bothell, WA 98012 Thank you for your interest in this Faira

More information

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 12527 NE 117th Pl, #F8, Kirkland, WA 98034 Thank you for your interest in this Faira Certified

More information

FAIRA TRANSPARENCY REPORTS nd Ave S, E-2, SeaTac, WA 98198

FAIRA TRANSPARENCY REPORTS nd Ave S, E-2, SeaTac, WA 98198 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98198 Thank you for your interest in this Faira Certified home. We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS SE 265th St, Covington, WA October 10, 2017

FAIRA TRANSPARENCY REPORTS SE 265th St, Covington, WA October 10, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98042 Thank you for your interest in this Faira Certified home. October 10, 2017 We have

More information

Inspection Report. Mr. Happy Homeowner. Property Address: Focal Point Home Inspection Ltd.

Inspection Report. Mr. Happy Homeowner. Property Address: Focal Point Home Inspection Ltd. Page 1 of 19 Inspection Report Mr. Happy Property Address: Joseph Poelsterl 450.010220 6334 W. Grace st Chicago Illinois 60634 1-773-454-6700 Page 2 of 19 Table of Contents Cover Page Table of Contents

More information

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA 27966 Thackeray Avenue/ Mail address Hayward, Calif. 94544 2011 150TH AVENUE SAN LEANDRO, CALIFORNIA 21:12 August 07, 2015 Page 1 of 11 Table of Contents Definitions 2 General Information 2 Lots and Grounds

More information

Tennessee Valley Property Inspections

Tennessee Valley Property Inspections Cover Page Tennessee Valley Property Inspections Property Inspection Report Inspection prepared for: Billy Bob & Eula May Jones Date of Inspection: 1/9/2017 Time: 0900 Size: 4900sf Weather: 30 degrees.

More information

FAIRA TRANSPARENCY REPORTS st Pl SE, Sammamish, WA May 18 th, 2017

FAIRA TRANSPARENCY REPORTS st Pl SE, Sammamish, WA May 18 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98075 May 18 th, 2017 Thank you for your interest in this Faira Certified home. We have coordinated

More information

FAIRA TRANSPARENCY REPORTS. January 27 th, 2017

FAIRA TRANSPARENCY REPORTS. January 27 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 4700 115 th Pl SE, Everett, WA

More information

FAIRA TRANSPARENCY REPORTS NE 182nd St, C101, Kenmore, WA 98028

FAIRA TRANSPARENCY REPORTS NE 182nd St, C101, Kenmore, WA 98028 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 6700 NE 182nd St, C101, Kenmore,

More information

FAIRA TRANSPARENCY REPORTS Harbour Pointe Blvd, #301h, Mukilteo, WA 98275

FAIRA TRANSPARENCY REPORTS Harbour Pointe Blvd, #301h, Mukilteo, WA 98275 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 5300 Harbour Pointe Blvd, #301h, Mukilteo, WA 98275 Thank you for your interest in this Faira

More information

Inspection Report 123 My Street Midland, GA

Inspection Report 123 My Street Midland, GA Buying, Selling or Building Your Home Inspection Company ROFESSIONAL INSPECTION SERVICES, LLC P.O. Box 9774 Columbus, GA 31908 706-565-0333 1-866-298-4251 Inspection Report 123 My Street Midland, GA This

More information

FAIRA TRANSPARENCY REPORTS. 405 SW 346th Pl, Federal Way, WA Nov 09th, 2015

FAIRA TRANSPARENCY REPORTS. 405 SW 346th Pl, Federal Way, WA Nov 09th, 2015 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98023 Nov 09th, 2015 We have coordinated

More information

Home Inspection Report

Home Inspection Report Pfeifer Home Inpsection, LLC 8332 Crystal Pointe Lane Indianapolis, Indiana 46236 317-340-1734 Lic #HI01700103 Home Inspection Report Columbus, IN 47201 Page 1 of 20 Table of Contents Definitions 2 General

More information

FAIRA TRANSPARENCY REPORTS Interlake Ave N, Seattle, WA February 1, 2018

FAIRA TRANSPARENCY REPORTS Interlake Ave N, Seattle, WA February 1, 2018 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98133 February 1, 2018 We have

More information

Advanced Property Inspections

Advanced Property Inspections Cover Page Home Inspection Report Inspector: Darren Taylor License #672-106 12421-32nd Ave, Pleasant Prairie, WI 53158 Phone: 262-458-4176 Email: darren.advpi@gmail.com kenoshahomeinspection.com The following

More information

Lighthouse. Prepare for your LHA inspection. Inspection Guide

Lighthouse. Prepare for your LHA inspection. Inspection Guide Guiding landlords to a successful relationship with LHA Lighthouse Inspection Guide (402) 434-5500 www.l-housing.com Prepare for your LHA inspection LHA adheres to HUD s Housing Quality Standards to ensure

More information

FAIRA TRANSPARENCY REPORTS

FAIRA TRANSPARENCY REPORTS 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 122 26 th Avenue E, Seattle WA 98112 Thank you for your interest in this Faira Certified

More information

FAIRA TRANSPARENCY REPORTS Brighton Pl, Mukilteo, WA 98275

FAIRA TRANSPARENCY REPORTS Brighton Pl, Mukilteo, WA 98275 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98275 Thank you for your interest in this Faira Certified home. We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS NE 116th Pl, Kirkland, WA April 20 th, 2017

FAIRA TRANSPARENCY REPORTS NE 116th Pl, Kirkland, WA April 20 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98034 April 20 th, 2017 We have

More information

FAIRA TRANSPARENCY REPORTS th Ave SE, Bothell, WA 98012

FAIRA TRANSPARENCY REPORTS th Ave SE, Bothell, WA 98012 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98012 We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS SE 41st Ln, E203, Bellevue, WA April 7 th, 2017

FAIRA TRANSPARENCY REPORTS SE 41st Ln, E203, Bellevue, WA April 7 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 12834 SE 41st Ln, E203, Bellevue,

More information

Inspector FX Field Forms

Inspector FX Field Forms Inspector FX Field Forms PROPERTY / CLIENT Customer File # Customer Contact Address City, St, Zip Phone Fax Email Inspection location Send report to Phone Neightborhood Main entry faces East North South

More information

FAIRA TRANSPARENCY REPORTS S 236th St, 10-5, Kent, WA 98032

FAIRA TRANSPARENCY REPORTS S 236th St, 10-5, Kent, WA 98032 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 5427 S 236th St, 10-5, Kent, WA 98032 Thank you for your interest in this Faira Certified

More information

Coast Home Inspection

Coast Home Inspection Cover Page Property Inspection Report Inspection prepared for: Client Real Estate Agent: Support - Home Inspector Pro Date of Inspection: 4/1/2015 Time: 10 am Age of Home: 1994 Size: 2618 SQ. FT. Weather:

More information

Terry Building Inspection report summary with all items addressed or explained in red

Terry Building Inspection report summary with all items addressed or explained in red Terry Building Inspection report summary with all items addressed or explained in red Health & Safety Summary The following are health and safety concerns. Recommend all evaluations and repairs / corrections

More information

FAIRA TRANSPARENCY REPORTS SE 240th Pl, Maple Valley, WA June 5th, 2017

FAIRA TRANSPARENCY REPORTS SE 240th Pl, Maple Valley, WA June 5th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98038 June 5th, 2017 We have coordinated

More information

FAIRA TRANSPARENCY REPORTS. 706 N 103rd St, Seattle, WA August 14, 2017

FAIRA TRANSPARENCY REPORTS. 706 N 103rd St, Seattle, WA August 14, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98133 August 14, 2017 We have coordinated

More information

McKinney Inspection Company

McKinney Inspection Company McKinney Inspection Company Copyright 2013 New Image Software, Inc. All rights reserved. Rev 7/1/2013 Copyright 2013 New Image Software, Inc. All rights reserved General Terminology McKinney Inspection

More information

FAIRA TRANSPARENCY REPORTS Highland Dr, Bellevue, WA 98006

FAIRA TRANSPARENCY REPORTS Highland Dr, Bellevue, WA 98006 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 98006 Thank you for your interest in this Faira Certified home. We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS th Ave S, Auburn, WA June 15 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave S, Auburn, WA June 15 th, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98001 June 15 th, 2017 We have

More information

HOME INSPECTION REPORT

HOME INSPECTION REPORT HOME INSPECTION REPORT 75-5748 Alahou Street 2F Report Prepared For: Barbara Little Report Prepared By: Warren d'aquin Page 2 of 23 TABLE OF CONTENTS TABLE of CONTENTS... 2 SUMMARY REPORT... 3 GENERAL

More information

FAIRA TRANSPARENCY REPORTS th Pl W, Lynnwood, WA 98087

FAIRA TRANSPARENCY REPORTS th Pl W, Lynnwood, WA 98087 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 98087 We have coordinated the efforts

More information

FAIRA TRANSPARENCY REPORTS W Manor Pl, #413, Seattle, WA August 25, 2017

FAIRA TRANSPARENCY REPORTS W Manor Pl, #413, Seattle, WA August 25, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR Thank you for your interest in this Faira Certified home. FAIRA TRANSPARENCY REPORTS 2510 W Manor Pl, #413, Seattle,

More information

Inspection Report. Eagle Eye Home Inspectors. John R. Dixon 24GI McKinley Court Princeton, NJ

Inspection Report. Eagle Eye Home Inspectors. John R. Dixon 24GI McKinley Court Princeton, NJ Inspection Report : Eagle Eye Home Inspectors John R. Dixon 24GI00094900 625 McKinley Court Princeton, NJ 08540 732.397.3527 Table of Contents Cover Page... 1 Table of Contents... 2 Intro Page... 3 1 Roofing...

More information

FAIRA TRANSPARENCY REPORTS S 272nd St, #39, Kent, WA September 1 st, 2017

FAIRA TRANSPARENCY REPORTS S 272nd St, #39, Kent, WA September 1 st, 2017 608 State St. South Kirkland, WA 98033 www.faira.com hello@faira.com +1.800.571.FAIR FAIRA TRANSPARENCY REPORTS 2609 S 272nd St, #39, Kent, WA 98032 Thank you for your interest in this Faira Certified

More information