Surgeons Panels, including performance, operational procedures, training and maintenance.

Size: px
Start display at page:

Download "Surgeons Panels, including performance, operational procedures, training and maintenance."

Transcription

1 Guidance note: DRAFT Surgeons Panels, including perfmance, operational procedures, training and maintenance. 1. Introduction 1.1. Surgeons Panels theatre panels are very common, every operating theatre is provided with one, they are a vital communication interface between the engineering systems in the theatre and the user The auths of this guidance note have become acutely aware, of the following operational problems: Medical staff, commonly don t can t operate the functions on surgeons control panels crectly e.g. they are not able to turn on off the ventilation systems put them into set back, f all types of theatre. This because of: po training and not being familiar with the functions of the surgeons panel, po labelling/signage is not clear absent, the controls not wking only partly wking.

2 The medical staff, commonly do not understand there is a problem with one me of the engineering services provided in the operating theatre these include electrical supply, medical gas alarm, AGSS, Radiation, Laser, Fire alarm etc. because the alarm indicat f an alarm: has not been fitted, po training and not being familiar with the meaning of the alarms of the surgeons panel, po labelling/signage is not clear absent, has been fitted, but is not wking, either because it was never commissioned, installed crectly, the light has failed, it has failed f other reasons f example the air flow failure alarm not being installed commissioned crectly resulting in air flow failure not being indicated when the ventilation rate has fallen to an unsafe level f the patient. A common failure in most operating theatres. Medical teams are commonly not aware of the dangers to themselves and the patient if one me of the engineering services are not operating crectly have failed. One me of these problems are present in most theatres; resulting in the various engineering systems being operated increctly one me of the engineering systems required f the safe operation of the operating theatre not being available not wking crectly. Thereby potentially compromising the safety of the patient and the medical teams others wking in the operating theatre. The risks commonly include: electrocution of the patient staff, loss of power, leading to immediate imminent failure of supply to medical equipment, loss partial loss of ventilation, increasing the risk if the patient becoming infected, loss of medical gases only being picked up by the anaesthetist after the gas pressure has fallen significantly, loss of AGSS, resulting in high concentrations of anaesthetic agents higher than permitted by COSHH As can be seen from table 1 later, the various HTMs and HBN 26 outline requirements f the provision of alarms, but commonly do not make it clear how these are to be provided. from table 1 me alarms are clearly required to provide appropriate warnings of failing the loss of various engineering systems and to provide the medical teams clear warning of the failure of engineering systems. 2 of 28

3 This guidance note in table 1 and this document outlines the requirements of the HTMs and HBN 26 and where the gaps exist makes recommendations as to how these might be provided This document is intended to draw together the existing requirements of HTMs and HBN 26, including additional facilities (controls and alarms etc.) and to be used by: clinicians, theatre managers, project managers, engineering designers, manufacturers of surgeons panels, clerks of wks, authised persons, authising Engineers, including, staff with responsibility f testing, commissioning and maintaining surgeons panels and associated alarm systems The following attempts to outline the published requirements f the facilities and functions f surgeons control panels. 2. Legal and Requirements of guidance 2.1. Helpfully the DoH and other bodies publish HTM and other guidance, detailing the requirements? 2.2. Firstly, these include the statuty requirements often these are mandaty (they have to be provided) and are not to be provided only where reasonably practicable Any and that is the vast majity of services provided in an operating theatre and also nearly all alarms, these have to be provided as they are provided f patient safety, so if not provided and functioning crectly the health care ganisation would not be able to demonstrate providing a safe environment f the patient, required by the Health and Social Care Act (HaSCA) Similarly, The Wkplace (Health, Safety and Welfare) Regulations 1992 (WPR) in terms of f example provision of sufficient and appropriately purified air. Medical teams must be infmed by and alarm immediately on failure to e nsure operations are not started if the ventilation system is not wking crectly (failure to meet these requirements would also lead to a failure to meet the requirements of the health and social care act) Similarly, The Control of Substances Hazardous to Health Regulations 2002 (COSHH) in terms of f example provision of sufficient ventilation to control to safe levels bacteria and chemicals such as anaesthetic agents. This requires an immediate local alarm if the ventilation AGSS is not wking crectly. 3 of 28

4 2.6. The Electricity at Wk Regulations 1989 (EaWR), f example provision of safe and crectly operating electrical services to prevent electrocution of the patient either by traditional electric shock micro shock, that could cause ventricular fibrillation (without medical team in theatre being aware they electrical equipment had very likely electrocuted the patient) Many of the above relate to the operation of systems and services so if say the alarm system is very old does not provide the appropriate alarm the alarm warning was not installed, these would still be required as not to have it installed operating would put the patient at risk and therefe the healthcare ganisation would not be able to demonstrate they had provided a safe environment f the patient. An example would include the operation of an electrical system without appropriate earthing (as defined when the system is being operated) and an IPS system, as both are mandaty under regulation 8 of the electricity at wk regulations, where this regulation and others in this document are defined as absolute. Another example would include the crect operation of the ventilation system (e.g. air flow), as the system is designed to remove/control the level of harmful agents (bacteria, chemicals etc.) under the COSHH regulations; an alarm is required locally to infm those in the theatre there is a fault with the ventilation system, warning them there is a danger to the patient (typically infection) and to the staff (typically anaesthetic gases agents exceeding safe levels) so they can take appropriate action to manage the danger to themselves and the patient There has been a HTM f ventilation and other services f many years, much of the content f earlier editions as well as the current edition s are based on peer reviewed research that demonstrated that these systems are installed and perfmance if installed as detailed in the HTM reduce danger Therefe, the legislation and guidance in HTMs should be followed As discussed earlier, f some years the UK Government has been passing and updating legislation concerning the safe operation and provision of healthcare facilities in the UK, these f example suppted by: Building regulations, the wkplace (health, safety and welfare) regulations, Control of substances hazardous to health regulations, these suppted and giving details on how compliance can be achieved with legislation, the DoH (Department of Health) publishes f example HTMs f specific engineering topics and HBNs with requirements f specific departments e.g. Theatres. These, together with other requirements f ventilation systems in HTM 03, electrical services, HTM 06, medical gases, HTM 02. The following outlines the requirements where these concern the provision, maintenance and safe operation of surgeons panels in a healthcare facility Clearly adhering to the guidance outlined in the Health Technical Memandum (HTM) should be taken into account as evidence towards compliance with these legal requirements and 4 of 28

5 standards; And, where the principles of the guidance are not to be followed, ganisations should document how the expectations are being met by equal and alternative means The statuty and guidance requirements f designing new modifying ventilation systems on healthcare sites are demonstrably effective at removing infection & chemical hazards, providing a suitable environment f carrying out medical procedures f the patient and medical practitioners, there essential controls and alarms are discussed in this guidance note. Similar also applies to other service provisions it s wth discussing HTM 00 (Policies and principles of healthcare engineering), in chapter 1 makes many references to statute e.g. health and safety at wk act, COSHH, etc. inferring compliance with HTMs, complies with legal requirements Me directly in HTM 00:2014 (applicable to all other HTMs), clause 1.3 Adhering to the guidance outlined in this Health Technical Memandum (HTM) will be taken into account as evidence towards compliance with these legal requirements and standards. From this DoH are saying follow the HTMs and you have followed the legal requirements, if you don t follow HTM you won t be following legal requirements, effectively the HTMs are ACOPs, generally follow them and you have met legal aspects. Then in the following clause Where the principles of the guidance are not to be followed, ganisations should document how the expectations are being met by equal and alternative means As in clause 1.4 there is the documented, equal better route, this effectively means evidence based, research and the like, not in my view experience as these are just wds unless backed up by something substantial, not very likely as much in HTMs are evidence based Therefe, appropriate engineering services are required, backed up with alarms. These required to enable the medical teams (and Healthcare Organisation) take the appropriate action to preserve the safety of patients and staff. 3. Requirements of HTM and HBN guidance 3.1. The requirements of HTMs and HBN 26 are outlined in table 1, where there are no requirements in the various HTMs HBN 26 suggestions and recommendation have been made. These suggestions and recommendations are further added to in the text that follows; with the objective of providing a complete list of alarms and other facilities that are needed in a surgeons panel/theatre panel and f these to be well understood by medical teams that use the theatre. Therefe, enabling medical teams to make optimized decisions to protect the safety of the patient and staff when there are problems with the engineering services provided in an operating theatre. 5 of 28

6 Table 1 Signals and displays f surgeons / theatre control panel Engineering services No. Description User control type User indicat type Light colour Notes 1 Plant failure na RND RND Suggest text Plant failure indication light colour RED 2 Low air flow na RND RND Suggest text Low air flow indication light colour RED 3 Room temperatureindicating gauge 4 Room humidityindicating gauge 5 Room Temperature adjustment 6 Room humidity adjustment 7 Ventilationplant status indication na Analogue digital RND Suggested text Room Temperature should be large enough to be read from the nmal wking position na RND RND Suggested text Room Humidity clearly-readable to be read from nmal wking position Adjusta ble by user 8 Ventilation off Switch na na Suggested text Room temperature adjustment should be marked either raise and lower + and A control tolerance ±1 C Adjusta na na Suggested text Room ble by humidity adjustment %RH user humidity values should be graduated between 35% and 60% with a (calibrated) control knob, slider provided with set point read out na RND RND should also be located at the staff control base Light RED* RND, suggested text Ventilation off Could be combined with indicat light HTM/HBN clause number (where appropriate) HTM 03-01A 6.53 HTM 09-01A 6.53 HTM 03-01A 6.34, 7.79 & HBN 26: HTM 03-01A 7.79 & HBN 26: HTM 03-01A 6.33, 7.79 & HBN 26: HBN 26: HTM 03-01A 7.79 HTM 03-01A of 28

7 9 Ventilation setback Switch 10 Ventilation on Switch 11 Other rooms, temperature adjustment Adjusta ble by user Light AMBER * 12 UCV setback na Light AMBER * 13 UCV System off 14 AHU and UCV full speed Suggested text Ventilation setback, Could be combined with indicat light Light GREEN Suggest text Ventilation on Could be combined with indicat light na na Suggest text Room temperature adjustment e.g. in Lay-Up Preparation B Suggest text UCV setback To limit air supplied through terminal to > 25 air changes per hour na Light RED Suggest text UCV system off Switch off UCV and AHU UCV AHU failed na Light GREEN Suggest text Ventilation and UCV full speed Both AHU and UCV operating at full speed 15 UCV filter dirty na Light BLUE Suggested text UCV filter dirty UCV terminal s Low air flow C HTM 03-01A 7.79 HTM 03-01A 7.79 HTM HTM 03-01A 7.143, 7.93 HTM 03-01A HTM 03-01A HTM 03-01A Suggested text UCV low air flow 16 Refrigerant alarm na RND RND Suggest text refrigerant alarm D 17 Room Pressure na RND RND Suggested text theatre room pressure low indication light colour RED 18 X-Ray Warning lights 19 Laser Warning lights 20 Fire Alarm (warning) Switch Switch RND RND Suggested text theatre perimeter X-Ray warning light(s) indication light colour AMBER* RND RND Suggested text theatre perimeter laser warning light(s) indication light colour AMBER* na RND RND RND, suggested text Fire alarm nearby indication light colour AMBER, alternative flashing light frequency similar to medical gas alarm HTM 03-01A 3.54 HTM HBN 26: HBN 26: HTM Part B: of 28

8 21 Fire Alarm (evacuate) na RND RND RND, suggested text Fire alarm evacuate indication light colour RED HTM Part B: Clock na na na With sweep second hand E HBN 26: Time Lapse clock 24 Electric Socket Controls 25 Electric sockets 26 X-ray viewing screens 27 Staff to staff call point 28 Operating light controls (main light) 29 Operating light controls (satellite) 30 General lighting Switch Switch No switch control na na Control by switch switches suggested text Time lapse clock fmat digital minutes and second na na In the past these have been provided, these are not recommended f existing new panels na na If located in panel, should be completely electrically and mechanically segregated HBN 26: na na na Unlikely to be required HBN 26: Switch RND RND Suggested text Staff to HBN 26:2004 staff emergency call 6.6 indication light colour RED, panels also required at communications base and rest facilities (also with fault condition) Switch Switch Adjusta ble by user 31 UCV lighting Adjusta ble by user 32 Patient/staff music systems Adjusta ble by user RND RND Dimmable, suggest text main operating light control F RND RND Dimmable, suggest text satellite light control F RND RND Suggested text General lighting All should be individually collectively dimmable G RND RND Suggested text UCV lighting All should be individually collectively dimmable G na na F playing patient music provide background music f staff H na na HBN 26:2004 also see 7.115, & HBN 26:2004 also see 7.115, & HBN 26: HBN 26: HBN 26: & of 28

9 33 IPS Alarms na RND RND RND, suggested text Blue medical equipment only sockets safe to use indication colour light GREEN 34 IPS Alarms Na RND RND RND, suggested text Blue medical equipment only sockets unsafe to use indication colour light YELLOW J 35 IPS Alarms na RND RND RND, suggested text Blue medical equipment only sockets unsafe to use indication colour light RED 36 IPS alarm LCD Display 37 IPS Mute Switch 38 IPS Test Switch 39 IPS Menu Switch 40 IPS Scroll keys Switch na na na If provided should only give unambiguous text e.g. IT 1 Earth (Insulation) Fault, ITU bed 4, left side RND RND RND, Mutes, but does not reset warning sounder na na Button to test IPS operational and warning lights suggested text IPS light test na na Where provided, should not be operable by user (only appropriately trained electrical staff), users must not be able to read off technical infmation make alterations accept alarms of any type. na na Where provided, should only be usable to access the location of a fault as described in LCD display, users must not be able to read off technical infmation make alterations accept alarms of any type. 41 UPS available na RND RND Suggested text UPS available indicat colour GREEN Testing Testing Testing Testing Testing Testing Testing Testing testing of 28

10 42 UPS Fault na RND RND RND, suggested text UPS not available indicat colour RED, indicates with any fault, off line, including when in by pass 43 Mains fail/ups running 44 Emergency generat available 45 Emergency generat fault 46 Emergency generat supply on 47 Emergency power off, (EPO) 48 Medical gas alarm General Fault 49 Medical gas alarm warning na RND RND RND, suggested text Mains failed/ups running indicat colour RED na RND RND Suggested text Emergency generat available indicat colour GREEN, (when the generat(s) serving this medical location is available, light goes out when generat is taken off line goes offline na RND RND RND, suggested text Emergency generat not available indicat colour RED, illuminates if generat taken off line is not available na RND RND Suggested text Emergency Generat supply on indication light colour RED, (when the generat(s) serving this medical location are on and delivering power to any circuit connected to it) Contact na na RND RND Not nmally in panel, but required in some medical locations. example text Xray system Emergency Power Off. RND suggest RED indicat light suggested text X-ray system Emergency Power Off operated Light with sounder Light with sounder Red RND, suggested text General alarm medical gas services may be affected (12.31 communications/power failure etc.) testing & Testing Testing RND Testing R ND Testing RND Testing RND HTM testing Yellow Text as HTM HTM etc testing of 28

11 50 Medical gas alarm warning 51 AGSS (Anaesthetic Gas Scavenging System) 52 AGSS duty pump fail 53 AGSS system fail General Notes na RND Switch Light with sounder RED Text as HTM HTM etc testing RND RND RND, suggested text AGSS available indicat colour GREEN, light stays on if duty fail na RND RND RND, suggested text AGSS duty Fail indicat colour AMBER na RND RND RND, suggested text AGSS system fail indicat colour RED HTM testing HTM testing HTM testing na RND not applicable Required, no definition in HTM HBN Theatre air-conditioning control senss should be actively ventilated, located in a sampling duct mounted in the surgeon s panel and be accessible f cleaning and the removal of fluff and lint HTM 03-01A, 7.75, fan to draw air over senss. The switching devices and indicats should be incpated in the surgeon s panel and their functions clearly labelled HTM 03-01A, A Temperature adjustment this would be better adjustable with a graduated (calibrated) control knob, slider provided with set point read out. B Temperature adjustment this would be better adjustable with a graduated (calibrated) control knob. C UCV terminal s HEPA-filter resistance causes the air delivered to fall below 80% of the design flow rate (this often only achievable through velocity probe) note would apply to each fan section of UCV. D A refrigerant gas detect mounted in the base of the duct and an alarm system audible to the end-user will also need to be provided (as dictated by the COSHH Regulations). E Should be radio controlled ( otherwise synchronised), powered from essential lighting circuit. F Where me than one operating luminaire is provided, each luminaire should be separately supplied with no commonality of transfmer, rectifier, battery equipment control equipment also see EFAs e.g. DH (2010) 04, 06/05/2010. G Multi way switching at each entrance including from clean crid and disposal f example, should be fed from multiple circuits, emergency lighting to same levels as general lighting. 11 of 28

12 H Integral music systems are the preferred option, as there are potential hazards from crossinfection and interference with the existing power supply from stand-alone systems. The system should be integral to the engineering system and be located within the fabric of the building HBN 26:2004, connection to system to be by cable blue tooth, to tablet, phone (in flight mode) etc. J note where these lights illuminate, the user could not be sure the electrical system is safe f patient and staff, therefe the sockets should not be used. A light with no text is not a clear indicat as to the safety otherwise of the electrical system, so must be defined by a clear sign (text), no abbreviations given seriousness of potential fault to patient and staff. note f installations not complying with where a single IPS has been installed in a medical location with an alarm and no suppting LCD display giving a clear and unambiguous location of the fault the electrical sockets should not be used (with immediate effect, as medical staff could not be sure the system was safe). f systems where two me IPS have been installed to provide circuit protection and safety to a medical location unless there is an indicat to give a clear and unambiguous location of the fault warning the electrical sockets should not be used (with immediate effect, as medical staff could not be sure the system was safe). where the warning light can only illuminate if there is NO danger to patient and staff then the text could be changed to Blue medical equipment only sockets safe to continue use * should not be provided with sounder. Ventilation 3.2. The following requirements of HTM 03-01:2007 f controls and alarms in surgeons panels/theatre control panels are detailed in table Additionally, the perfmance and installation guidance would be best followed as detailed in the guidance on medical gas alarm panels in this document The objective is to ensure alarm and communication systems installations that are fit f purpose equal better than guidance such as HTMs, BS, BS ENs, industry standards and the like in addition, the following are based on the requirements of HTM 03 f controls and alarms in surgeons panels/theatre control panels COSHH 3.6. Regulation 13 Arrangements to deal with accidents, incidents and emergencies (1) Subject to paragraph (4) and without prejudice to the relevant provisions of the Management of Health and Safety at Wk Regulations 1999, in der to protect the health of his employees from an 12 of 28

13 accident, incident emergency related to the presence of a substance hazardous to health at the wkplace, the employer shall ensure that (a) procedures, including the provision of appropriate first-aid facilities and relevant safety drills (which shall be tested at regular intervals), have been prepared which can be put into effect when such an event occurs; (b) infmation on emergency arrangements, including (i) details of relevant wk hazards and hazard identification arrangements; and (ii) specific hazards likely to arise at the time of an accident, incident emergency, is available; and (c) suitable warning and other communication systems are established to enable an appropriate response, including remedial actions and rescue operations, to be made immediately when such an event occurs. (2) The employer shall ensure that infmation on the procedures and systems required by paragraph (1)(a) and (c) and the infmation required by paragraph (1)(b) is (a) made available to relevant accident and emergency services to enable those services, whether internal external to the wkplace, to prepare their own response procedures and precautionary measures; and (b) displayed at the wkplace, if this is appropriate. (3) Subject to paragraph (4), in the event of an accident, incident emergency related to the presence of a substance hazardous to health at the wkplace, the employer shall ensure that (a) immediate steps are taken to (i) mitigate the effects of the event; (ii) reste the situation to nmal; and (iii) infm those of his employees who may be affected; (b) only those persons who are essential f the carrying out of repairs and other necessary wk are permitted in the affected area and they are provided with (i) appropriate personal protective equipment; and (ii) any necessary specialised safety equipment and plant, which shall be used until the situation is rested to nmal; and (c) in the case of an incident accident which has may have resulted in the release of a biological agent which could cause severe human disease, as soon as practicable thereafter his employees their representatives are infmed of (i) the causes of that incident accident; and (ii) the measures taken to be taken to rectify the situation. (4) Paragraph (1) and, provided the substance hazardous to health is not a carcinogen, mutagen biological agent, paragraph (3) shall not apply where (a) the results of the risk assessment show that, because of the quantity of each substance hazardous to health present at the wkplace, there is only a slight risk to the health of employees; and (b) the measures taken by the employer to comply with the duty under regulation 7(1) are sufficient to control that risk. (5) An employee shall rept fthwith, to his employer to any other employee of that employer with specific responsibility f the health and safety of his fellow employees, any accident incident which has may have resulted in 13 of 28

14 the release of a biological agent which could cause severe human disease Electrical 3.8. The following requirements of HTM 06:2017 f controls and alarms in surgeons panels/theatre control panels are detailed in table Additionally, the perfmance and installation guidance would be best followed as detailed in the guidance on medical gas alarm panels in this document The objective is to ensure alarm and communication systems installations that are fit f purpose equal better than guidance such as HTMs, BS, BS ENs, industry standards and the like IPS fed Equipment, although the first fault to earth has been identified, it may only be a matter of time befe a second fault occurs. Therefe, upon second fault there is a risk that the final circuit will be lost along with any alarm signals. There is a significant risk to all using the equipment circuit(s) after the first fault alarm has been sounded as there is no way of predicting when the second electrical fault occurring e.g. the saline solution leaking into an adjacent part of the electrical installation. The immediacy and imptance of this risk should be reflected in the operations manual, the theatre departments operational procedure manual and medical teams training Where theatre control panels are provided, their power supply could be derived from a dedicated tertiary battery supply off the local theatre UPS. Note in of f operating lights the minimum autonomy should be 3 hours, this would clearly also be extended to any component circuits used to control deliver power to operating lights. This 3-hour requirement is a minimum and may be extended considerably to meet the requirements to provide sufficient time to close the patient as discussed in : discusses in many parts including chapter 4 and others the need to provide resilient electrical services and safety services e.g. clause BS 7671 also makes clear recommendations to the resilience of power supply to essential medical systems in chapter 56, these include circuits shall be independent of other circuits. Independent of other circuits meaning that any electrical fault any intervention modification in one system must not affect the crect functioning of the other. This may necessitate separation by fire-resistant materials different routes enclosures, this very likely to be applicable to services run through theatre control panels as any failure could render the essential facility unavailable e.g. operating light and any alarm e.g. ventilation, electrical, fire, medical gas etc. Fire The following requirements of HTM Part B f controls and alarms in surgeons panels/theatre control panels are detailed in table 1. Additionally the perfmance and installation guidance would be best followed as detailed in BS 5839 Parts and guidance on medical gas alarm panels in this document. The objective is to ensure alarm and communication systems installations that are fit f purpose 14 of 28

15 equal better than guidance such as HTMs, BS, BS ENs, industry standards and the like. Medical gas alarms HTM 02-01: The following requirements of HTM 02:2006 f controls and alarms in surgeons panels/theatre control panels are detailed in table Additionally, the perfmance and installation guidance would be best followed as detailed in the guidance in this section of the document The objective is to ensure alarm and communication systems installations that are fit f purpose equal better than guidance such as HTMs, BS, BS ENs, industry standards and the like Area warning systems are required as follows, these requirements based on those in HTM also have many perfmance and installation requirements that are applicable to other alarm perfmance and installation requirements as follows: Introduction These required as note 10 of table 11 to be Installed in the operating room in the main panel (surgeons/theatre control panel) The area warning system should give an alarm f each gas service there should be local pressure switches f low pressure; high pressure switches are also required when oxygen, nitrous oxide and medical air are installed together Area panels other functions carry no indication of the warnings f cylinder replacement and plant functions that are given on central indicat panels The HTM f medical gas alarms has many and very particular requirements, these include (these are also applicable to surgeons/theatre control panels): Labelling All visual signal panels should be permanently, labelled accding to their function, including clear identification of the areas, rooms departments served Visual signals Flashing visual signals should have alternate on and off periods, each of equal duration between 0.25 and 0.50 seconds. There should be two separately energised light sources f each signal, arranged so that the failure of one source does not affect the other. The light sources should have a design life of at least five years of continuous operation Audible signals All audible signal tones should be modulated equally at a rate of 4 Hz ±10% between two tones of 440 Hz ±10% and 880 Hz ±10% Automatic resetting When a warning alarm signal occurs and the system condition subsequently reverts to nmal, the cresponding visual and audible signals should automatically reset to nmal Tempary muting Means must be provided on each panel f the user to mute the audible signal. The signal must resound after a nominal 15-minute period if the fault condition still exists. 15 of 28

16 3.28. Operation of the mute on area alarm repeater panels should not be accompanied by a change from flashing to steady illumination Continuous muting An internally-mounted switch should be provided to allow continuous muting during periods of maintenance. Should auto reset on clearance of fault. When the system condition returns to nmal, the continuous muting should automatically reset to nmal operation. When The continuous muting is in operation on any alarm condition, it should not prevent the operation of the audible signal on other alarm conditions when a fault condition arises Electrical wiring All electrical wiring should be in accdance with IET regulations System integrity If extra low voltage (ELV), maximum 50 V, is superimposed on the signal communication circuit (f example by cross-connection), the system design should ensure that any damage to the system is limited to replaceable panel components and that such damage is indicated as a system fault The perfmance of the system should not be compromised by the use of multi-ce cabling that carries ELV and communication signals in adjacent ces The system should be designed to reject spurious radio frequency (RF) mains noise typically arising in hospitals, examples being diathermy equipment and current spikes caused by plant start-up etc. also has further guidance on EMC and interference Relay conditions If relays are used to transmit alarm signals, the relays should be energised in their nmal closed condition Mains power supply The mains electricity supply should be derived from the essential power supply (that is, must be on the emergency system) Safety extra low voltage/functional extra low voltage power supply The panel power may be designed either as a safety extra low voltage (SELV) system as a functional extra low voltage (FELV) system, as defined in Part 4 of the IET Wiring Regulations The ELV power supply may be housed either in the alarm panels in a separate metal enclosure. The power supply should be rated f the full load of the panel, with visual and audity signals on all nmal and alarm conditions Test facility Each panel should be provided with a means to test all visual and audible signals on that panel. The power supply should be capable of sustaining all indicats and audible signals. Warning and alarm system faults General A flashing red visual indicat and an audible signal should operate on all panels when any of the following conditions occur: a. line fault from the initiating device; 16 of 28

17 b. communication fault other wiring fault; c. mains power failure Line fault The system should monit the integrity of the lines between the initiating devices and the panel transmitter units. The alarm system fault condition should be indicated on loss of integrity, f example open sht circuits, together with the visual alarm indicat(s) associated with the faulty wiring Communication/wiring fault The system should indicate an alarm system fault in the event of loss of data transmission between panels and transmitters Mains power failure Failure of mains power should be shown by a flashing red indicat and an audible signal, which should be powered from an internal battery. The audible signal may be muted and not automatically reinstate as required under nmal power supply (see other paragraphs), but the visual indicat should continue to flash until either the fault has been rectified the battery has discharged Stand-by battery A battery should be provided with sufficient capacity to power the visual and audible alarm system fault signal f a minimum period of four hours. The battery should be sealed and exchangeable, and should automatically recharge within 72 hours. See also clause this discusses a minimum battery autonomy and suggests that the autonomy may be extended to allow patient closure, this is not defined, but should be obtained in writing from the medical teams using the facility (medical location) and should be based on the longest period to safely close a patient plus a safety margin to allow f an unexpected medical requirement, battery degradation, battery deteriation, and a period of time f the medical team to realise the emergency and fmulate a plan to make the patient s condition safe Legend The legend on this indicat should be alarm system fault. Indicat panel requirements f all systems (medical gas) Indicats Panels should be provided with all indicats f the gas services in local use. The visual indicats should be arranged vertically in priity der, with the nmal indicats at the top. The sequence of gas services should be, from left to right: a. medical oxygen (cryogenic and cylinders/ pressure swing adsber (PSA) systems); b. nitrous oxide; c. nitrous oxide/oxygen mixture; d. medical air 400 kpa (compress plant, cylinders and synthetic air); e. surgical air 700 kpa; f. medical vacuum (pumps); g. helium/oxygen mixture. In addition to the gas service signal indicats, each panel must include: a. a green power on indicat without an audible signal; b. a red alarm system fault indicat with an audible signal. 17 of 28

18 3.46. Labelling Panels should be labelled as follows: a. medical gas alarm; b. with the identification of the medical gas services indicated, and the areas and departments served. E.g. Theatre 1 (note f clarity there should not be multiple theatre 1s on any given hospital site) Construction The fascia panel should be removable to allow access to the rear of the fascia to the panel f maintenance purposes. The dos facias should be so suppted that one person can easily handle and move it, the panels dos should give clear and unrestricted access to facilitate all maintenance and repair activities, the access dimensions and distances required by and BS 7671 and suppting guidance notes and guidance should also be full adhered with. Access to the interi of the panel should be tamper-proof. It should be possible to replace the source of illumination without removing the legend. Panels should have electrical sections with protection at least equal to BS EN 60529:2013. Panels and their housings should be of adequate strength f their purposes and be manufactured from crosion-resistant materials. If gas services are brought into the panel, they should be housed in separate, enclosed compartments, which are vented to the outside. There should be gas-tight seals where electrical services pass through any gas compartment Remote audible sounder All panels should have provision f connection to a remote audible sounder. HBN 26 Operating Theatres The following requirements of HBM 26:2004 f controls and alarms in surgeons panels/theatre control panels are detailed in table 1 and in the following text. Additionally the perfmance and installation guidance would be best followed as detailed in the guidance on medical gas alarm panels in this document. The objective is to ensure alarm and communication systems installations that are fit f purpose equal better than guidance such as HTMs, BS, BS ENs, industry standards and the like. Theatre Control Panel The control panel should be fully recessed and ideally should be accessible f maintenance from outside the theatre. All internal cabling should be LSF insulated. 18 of 28

19 Room Pressure A room pressure alarm should be provided to give warning that the room pressure has fallen to unacceptable levels, the common areas of failure being dos left open into out of the theatre, the alarm should be delayed by 2 minutes to allow good time f the patient to be brought into the theatre and out of theatre at the end of their operation, and at other times staff to enter and leave the theatre. Computer Equipment Computer equipment is commonly incpated into surgeons/theatre control panels, these are commonly incpated to access patient recds, telemetry, the control of patient moniting equipment, creating and amending the patient recd, repting systems, etc. F these purposes, touch screen monits can be incpated, these should be of a suitable size to be able to be read from the centre of the theatre standing at the screen(s) as appropriate f each task, these where possible should also have a screen based key board. The screen(s) and key board should be so designed and installed to minimise the chance of dirt build up and cross infection, the surfaces should be easy clean; the same also applies to any cooling sampling fans installed in the panel and where the air is drawn from and to, these should be sealed such that an air tight seal is preserved at all times between the location of the fan and the theatre (typically by a seal between the front of the surgeon/theatre control panel and the surrounding wall). Swab count board(s) These may be incpated into the surgeon/theatre control panel, these to have a minimum size of 800mm x 600mm. the board should be permanently fixed and have no gaps (the seal should not be achieved by a proprietary builders sealant). Mounting height and position should facilitate access and visibility. Theatre warning light(s) These are often incpated in the surgeon/theatre control panel, these f example turn on X-Ray, Laser Warning lights at eye level outside all entrances to the operating theatre. These should be provided each having an activation switch and light confirming the lights have all illuminated coloured AMBER the suppting text should read theatre perimeter X-Ray warning light(s) similar f the laser lights. Note safety precautions regards the use of lasers should also comply fully with BS EN 60825, and the incpation of suitable interlocks preventing entry to the theatre when the laser is in use. Laser use, finishes and fittings In theatres where it is possible laser surgery could be carried out there should be no reflective surfaces in the area including the surgeon/theatre control panel. 19 of 28

20 Finishes Quality of finishes, should be of a high standard. Finishes should be robust enough to withstand accidental impact. Surface finishes and materials used in the panel should be suitable f cleaning with any cleaning agents used in healthcare facilities. Finishes, should be durable and able to withstand wet cleaning and the accidental impact. Especially vulnerable points should have additional protection. Protection measures should be incpated at the panel to prevent the need f regular maintenance which would require the unit to be closed f long periods. X-Ray Protection Walls in the panel and opening in walls to accommodate the panel should be constructed to provide radiation protection in accdance with SI 2000/1059 (with amendments 2006/2523 and 2011/1567) and SI 1999/3232. Modular and conventionally build operating theatres There is no difference in the requirements of a modular theatre with a conventionally constructed theatre, as they are subject to the same standards and regulations, therefe there are also no differences in the requirements of surgeons/theatre control panels (see also HBN 26:2004 appendix 1). Other alarm and condition warning systems The perfmance and installation guidance f other alarms should followed as detailed in the guidance on medical gas alarm panels in this document. The objective is to ensure alarm and communication systems installations that are fit f purpose equal better than guidance such as HTMs, BS, BS ENs, industry standards and the like. All other alarms should perfm as the other requirements and recommendations of this document. F system failure the light should be coloured red, f system warning(s) coloured amber alarms). Sounders, General, all systems When an alarm warning light operates (red amber, yellow blue light alarms respectively), this should operate a sounder with the following perfmance outputs: Audible signals All audible signal tones should be modulated equally at a rate of 4 Hz ±10% between two tones of 440 Hz ±10% and 880 Hz ±10%. 20 of 28

21 Automatic resetting When a warning alarm signal occurs and the system condition subsequently reverts to nmal, the cresponding visual and audible signals should automatically reset to nmal. Tempary muting Means must be provided on each panel f the user to mute the audible signal. The signal must resound after a nominal 15-minute period if the fault condition still exists. Operation of the mute on area alarm repeater panels should not be accompanied by a change from flashing to steady illumination. Continuous muting An internally-mounted switch should be provided to allow continuous muting during periods of maintenance. Should auto reset on clearance of fault. When the system condition returns to nmal, the continuous muting should automatically reset to nmal operation. When The continuous muting is in operation on any alarm condition, it should not prevent the operation of the audible signal on other alarm conditions when a fault condition arises. Sounders are required, as there would be no guarantee the medical team would see one of the lights had illuminated. Screen based, instruction, help and emergency instructions The unplanned failure of an engineering system can be very dangerous to a patient undergoing a procedure being cared f in any medical location. the sudden warning failure of a system needs to be understood clearly by all in the medical team treating and carrying f the patient often being kept alive by life suppt systems etc. The actions to be taken by the medical teams need to be agreed (between all) and recded f the immediate reference in an emergency to all medical personnel in the department. To facilitate prompt and reliable actions by medical teams in an emergency situation the use of screen based, instruction, help and emergency instructions is encouraged. The text should use high contrast colour text and backgrounds, to facilitate easy and reliable reading and understanding of the requirements by medical teams. The following is an example of fmat and instruction. 21 of 28

22 Suggested text fmat: Warning alarm condition. Limits of conditions. Description of risks to patient and then staff as appropriate using NON-TECHNICAL language. What actions to take on behalf of the patient to make them safe and then staff as appropriate using NON-TECHNICAL language. How to rept the alarm condition to Estates with description e.g. on call/help desk with number. Theatre operational procedure files should be accessible by all medical staff located to facilitate immediate reference. Validation and Verification Ventilation system alarms Each ventilation system should be Validated and Verified as follows: Each system shall be treated as specialist ventilation system as defined in chapter 7 of HTM Part A and commissioned and validated as required in chapter 8. Each and all test results to be recded on project specific signed test recd fms. Verification carried out to fully comply with HTM Part B and BESA SFG 20 HTM aligned (current edition), including a check of control functions where the crect operation of each control and alarm is verified annually. Verified as required by HTM Part B Electrical system alarms, shall be commissioned as required by :2017, including emergency generats, IPS, UPS, Indications and alarms: 22 of 28

23 All local and remote indications and associated alarm combinations f nmal use failure in operation should be demonstrated and recded. medical IT systems: Verification of alarm indicats, local and remote, should be demonstrated. Additionally: Testing of Generat alarms. Each and all test results to be recded on project specific signed test recd fms Medical Gas and AGSS alarms Medical gas alarm systems Commission alarm systems as and chapter using also commissioning recd fm B11. AGSS alarms The operation of user-controlled switches, power on indicats and alarm systems should also be checked. Each and all test results to be recded on project specific signed test recd fms Other alarms and functions controlled connected provided in the medical location. All other alarms listed in this document including those in table 1, should be commissioned and tested. Each and all test results to be recded on project specific signed test recd fms Sounders located in connected provided in the medical location. All sounders listed in this document including those in table 1, should be commissioned and tested. Each and all test results to be recded on project specific signed test recd fms. As-installed drawings Schematics should be provided in all HV/ LV panel locations and (in case of emergency switching requirements) show all points of isolation including interconnection points between all distribution power supplied from the PES and any SPS, generats tertiary power supplies within the installation. The following list provides a minimum acceptable level f the as-installed drawings. Project contract documentation should be written and agreed with the healthcare ganisation and should clearly indicate which drawings are relevant to the particular project and any additional drawings that fm part of the installation as required: The layout drawings should use the building s general arrangement as background. The layout drawing should show all containment sizes; 23 of 28

24 The schematic drawing should indicate all cable sizes, protective device ratings and settings, switchgear and fault levels at distribution boards; System and control wiring: where the project includes any associated electrical services (f example, fire alarms, nurse-call systems, emergency lighting, building management), then layout drawings (using the building s general arrangement drawing as a background) showing the location of any associated devices and a single-line schematic of the system should be provided, including any associated panel wiring diagrams; As many of the services associated with the theatre control panel would be considered as essential medical system safety services, BS 7671 in chapter 56 in clause etc. places me and additional requirements to provide detailed drawings and plans of the installation as installed, therefe the additional requirements should be complied with Recds should be kept of all alarms and outages of the UPS, and details from all tests and servicing. Operational and estates managers may wish to consider a standard fm to recd all test results from any UPS, inverter battery within the healthcare facility. The recd of alarms should be reviewed at the next electrical safety group meeting. Maintenance Ventilation systems alarms Maintenance, e.g. quarterly tests, annual tests, check of control functions as required by HTM 03-01, BESA SFG 20 HTM aligned Electrical systems alarms All to be fully tested and proved at least annually and as required by:, IET GN 3 and IET GN Medical Gas systems alarms All to be fully tested and proved at least annually and as required by HTM Other alarms and functions controlled connected provided in the medical location All to be fully tested and proved at least annually Sounders located in connected provided in the medical location All to be fully tested and proved at least annually. 24 of 28

FM MEDICOL. Cableflow International Limited. The FLUSH MEDICOL (FM) Patient Care Services. Column has evolved from a market requirement for a

FM MEDICOL. Cableflow International Limited. The FLUSH MEDICOL (FM) Patient Care Services. Column has evolved from a market requirement for a Cableflow International Limited TM FM MEDICOL The FLUSH MEDICOL (FM) Patient Care Services Column has evolved from a market requirement for a stylish adaptable vertical trunking system which can be wall

More information

Product Data Sheet. Remote Terminals. Features:

Product Data Sheet. Remote Terminals. Features: Remote Terminals Product Data Sheet Features: Based around two core products, the Mx- 4010 Remote Display Terminal (RDT) and the fully functional Mx-4020 Remote Control Terminal (RCT). Both remote terminals

More information

Theatre Control Panels

Theatre Control Panels Theatre Control Panels Improving Workflow in the Operating Room a Progility company Powering Healthcare 2014 Starkstrom s Theatre Control Panels Starkstrom s Theatre Control Panels (TCP), sometimes called

More information

PANEL. Cableflow International Limited

PANEL. Cableflow International Limited Cableflow International Limited PANEL TM The PANEL, a simple yet understated name for this extremely flexible medical supply unit, embodies our experience and innovative approach to bedhead services attained

More information

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4 PREMIER EX8 EXTINGUISHING PANEL USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN 12094 PART 1 & EN54 PARTS 2 & 4 USER MANUAL Approved Document No: GLT.MAN-132 INDEX Extinguishing

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2008 + Amendment 1:2011 (Corrigendum June 2013) Requirements for Electrical Installations IET Wiring Regulations Seventeenth Edition ISBN-13: 978-1-84919-730-4 BS 7671 Requirements

More information

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual Syncro AS Analogue Addressable Fire Control Panel User Manual Man-1100 Issue 02 Nov. 2008 Index Section Page 1. Introduction...3 2. Safety...3 3. Panel Controls...4 3.1 Access Level 1...4 3.2 Access Level

More information

EXTINGUISHING AGENT RELEASE MODULE

EXTINGUISHING AGENT RELEASE MODULE EXTINGUISHING AGENT RELEASE MODULE Operation, Installation & Programming Manual Revision 3.00 Distributors For: 18-20 Brookhollow Ave telephone 02 8850 2888 www.firesense.com.au Baulkham Hills NSW 2153

More information

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

SmartLINK Module Ei3000MRF for Mains Powered Multi-Sensor Fire / Smoke / Heat / CO Alarms - Ei3000 Series

SmartLINK Module Ei3000MRF for Mains Powered Multi-Sensor Fire / Smoke / Heat / CO Alarms - Ei3000 Series SmartLINK Module Ei3000MRF for Mains Powered Multi-Sensor Fire / Smoke / Heat / CO Alarms - Ei3000 Series Instruction Manual Read and retain carefully for as long as the product is being used. It contains

More information

REQUEST FOR PROPOSAL No Fire Extinguishers, Fire Suppression, Fire Alarms, Emergency Lighting & Sprinkler Systems Maintenance

REQUEST FOR PROPOSAL No Fire Extinguishers, Fire Suppression, Fire Alarms, Emergency Lighting & Sprinkler Systems Maintenance PURCHASING DEPARTMENT REQUEST FOR PROPOSAL No. 1895 Fire Extinguishers, Fire Suppression, Fire Alarms, Emergency Lighting & Sprinkler Systems Maintenance Addendum No. 2 July 18 2017 This addendum shall

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description

More information

Project Briefing Document. Section 3 Electrical Services design guide and specifications

Project Briefing Document. Section 3 Electrical Services design guide and specifications ESTATES SUPPORT SERVICE Project Briefing Document Section 3 Electrical Services design guide and specifications Issue 1.1 June 2014 Project Ref. Project Name Project Manager Date issued... Consultant/Contractor...

More information

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system SenTRI ONE panel-based Fire detection and alarm system one 042bc/14 4188-978 issue 2_04-10_SenTRI ONE system oper Part of Document pack 2535-235 issue 2 1 Contents User responsibility - - - - - - - - -

More information

Control Panel User Guide

Control Panel User Guide Fire Detection & Alarm System Control Panel V4.14 Control Panel User Guide (TO BE RETAINED BY USER) 26-0397 Issue 6 Fike s policy is one of continual improvement and the right to change a specification

More information

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3 INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change

More information

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL 6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)

More information

CERTIFICATE OF FIRE APPROVAL

CERTIFICATE OF FIRE APPROVAL LR427.201.12 CERTIFICATE OF FIRE APPROVAL This is to certify that The product detailed below will be accepted f compliance with the applicable Lloyd s Register Rules and Regulations and with the International

More information

THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS

THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS 0800 2211 8034 Table of Contents Part 1: Introduction Part 2: Who is Responsible? Part 3: What is Required? Fire Risk Assessments Appointment of Competent Persons

More information

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES

Prem1er EVACS16. Installation Manual VOICE ALARM CONTROL PANEL 4 16 ZONES Prem1er EVACS16 VOICE ALARM CONTROL PANEL 4 16 ZONES Installation Manual Approved Document No: GLT.MAN-141 PAGE 1 INDEX INDEX... 2 Summary... 3 Safety information & use of this manual... 5 Installation

More information

Electrical Management

Electrical Management 5 WHS PROCEDURE P23-01 Page 1 of 9 Issue: 2 1. Intent The Salvation Army Australia Eastern Territory (TSA-AUE) is committed to the provision of a safe, healthy and injury free environment within the mission

More information

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS

Emergency Voice Communication System (EVCS) Consu ltant s Specific atio n CONTENTS CONTENTS 100 PERFORMANCE OBJECTIVES 200 DESIGN PARAMETERS 300 SYSTEM DESIGN 310 Design Guidance 320 Outstation Choice 330 Outstation Position 340 Documentation 400 SYSTEM COMPONENTS 410 Master Handsets

More information

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual

Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Syncro Matrix Analogue Addressable Fire Alarm Mimic Panel Product Manual Australia Issue 01 April 2012 Contents 1 Introduction 3 2 Safety 3 3 Installation 4 3.1 Mounting the Cabinet 4 4 Specifications

More information

Instruction Manual. Orayonne plus. Glass radiation convector

Instruction Manual. Orayonne plus. Glass radiation convector Instruction Manual Orayonne plus Glass radiation convect Table of Contents General...18 Safety infmation...19 Imptant notes...19 Construction...20 Minimum distances...20 Assembly of the wall holder...20

More information

User Instructions For TopTronic RS-30

User Instructions For TopTronic RS-30 User Instructions F TopTronic RS-30 430294ENG-Jun02 Hoval Ltd Nthgate Newark Nottinghamshire NG24 1JN Phone 01636 672711 Fax 01636 673532 2 Index 430294ENG-Jun02 Introduction Introduction... 3 Controls...

More information

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...

More information

POLICY FOR THE SAFE WORKING WITH ELECTRICITY

POLICY FOR THE SAFE WORKING WITH ELECTRICITY AGENDA ITEM 2.3 7 October 2010 POLICY FOR THE SAFE WORKING WITH ELECTRICITY Report of Executive Director of Planning Paper prepared by Purpose of Paper Action/Decision required Link to Health Care Standards:

More information

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear IEC/PAS 62271-109 Edition 1.0 2002-07 High-voltage switchgear and controlgear Part 109: Alternating-current series capacitor by-pass switches PUBLICLY AVAILABLE SPECIFICATION INTERNATIONAL ELECTROTECHNICAL

More information

Installation and Instructions for Use BSO99

Installation and Instructions for Use BSO99 Installation and Instructions f Use BSO99 SAFETY INSTRUCTIONS Read this Instruction Manual carefully to obtain the best perfmance from your oven. Keep this manual so that it can be read by a new owner.

More information

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual ANALOX 5001 ANALOX 5001 Carbon Dioxide Monitor User Manual Analox Sensor Technology Ltd 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT T: +44 (0)1642 711400 F: +44 (0)1642 713900

More information

CPX RIGID PENDANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL

CPX RIGID PENDANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL CPX RIGID PENDANT INSTALLATION, OPERATIONS & MAINTENANCE MANUAL O&M Manual Rigid Pendant Page 1 of 17 VERSION HISTORY Version Implemented Revision Approved Approval Reason # By Date By Date 1.0 Kevin Pugh

More information

Electrical Safety Policy

Electrical Safety Policy SH HS 10 Version 2 Summary: Keywords (minimum of 5): (To assist policy search engine) This policy has been produced in order that all employees & contractors are aware of both the Trust s and their own

More information

Amendment Number 3 of BS how it might affect you

Amendment Number 3 of BS how it might affect you Amendment Number 3 of BS7671 2008 - how it might affect you Geoff Cronshaw provides us with a look ahead at the proposals of Amendment 3 to BS 7671:2008 IET Wiring Regulations and the resulting changes

More information

USER GUIDE. Control panel-siren W W.

USER GUIDE. Control panel-siren W W. USE GUIDE Control panel-siren -W -W www.daitem.com User guide You have just bought a DAITEM security system, designed to cover all your protection needs. We would like to thank you f your confidence. With

More information

UK Experience with HTM-03 and Preventing Bio-contamination in Hospital OTs. Richard Knight CEng, MCIBSE, FIHEEM

UK Experience with HTM-03 and Preventing Bio-contamination in Hospital OTs. Richard Knight CEng, MCIBSE, FIHEEM UK Experience with HTM-03 and Preventing Bio-contamination in Hospital OTs Richard Knight CEng, MCIBSE, FIHEEM Connolly Memorial Hospital, Blanchardstown, Dublin 1 st December 2016 Content Objectives Basis

More information

RadioLINK + Module EIB600MRF for Battery Powered Smoke / Heat Alarms EIB600 Series

RadioLINK + Module EIB600MRF for Battery Powered Smoke / Heat Alarms EIB600 Series RadioLINK + Module EIB600MRF for Battery Powered Smoke / Heat Alarms EIB600 Series EIB600MRF Module (for use with EIB600 Series compatible Alarms only) Instructions Read and retain carefully for as long

More information

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO)

A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO) 4 PEEL HOUSE,TAUNTON STREET,SHIPLEY,BN18 3NA TEL: 01274 595015 FAX: 01274 580804 EMAIL:sales@rosse-systems.co.uk A GUIDE TO THE REGULATORY REFORM ORDER (FIRE SAFETY) 2005 (RRO) THE PURPOSE OF THIS DOCUMENT

More information

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-5:2000+A1:2002 EN54-25:2008 0359 Electro Detectors Ltd. Electro House Edinburgh

More information

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL 3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:

More information

Install guide 8010 ENGLISH. Customer Support: or Visit our webiste Made in China

Install guide 8010 ENGLISH. Customer Support: or Visit our webiste  Made in China Install guide 8010 ENLISH ustomer Suppt: 888-515-2585 Visit our webiste www.ritetemp-thermostats.com Made in hina 1-402-033 Install guide 8010 aution Tools 1 Location To avoid electrical shock and to prevent

More information

Intelligent Security & Fire Ltd

Intelligent Security & Fire Ltd Product Data Sheet Mx-4000 Series User Manual MX-4100, MX-4200, MX-4400, Mx-4400/LE & Mx-4800 Fire Alarm Control Panels The operation and functions described in the manual are available from Software Versions

More information

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL USER MANUAL 1 Table of Contents 1 SAFETY INFORMATION...3 1.1 SAFETY PRECAUTIONS DURING NORMAL OPERATION OF PANEL...3 1.3 BATTERY INFORMATION...3

More information

Fire Safety Policy SH HS 06. Version: 4. Summary:

Fire Safety Policy SH HS 06. Version: 4. Summary: SH HS 06 Fire Safety Policy Summary: Keywords: Target Audience: The Fire Safety Policy sets out the Trusts approach to a proactive fire safety culture to protect its staff, patients, service users, all

More information

Cerber C Zone and 2-Partition Burglary Control Panel for your home and office. Hook-Up & Programming Book[draft] / version 1.

Cerber C Zone and 2-Partition Burglary Control Panel for your home and office. Hook-Up & Programming Book[draft] / version 1. Cerber C612 12-Zone and 2-Partition Burglary Control Panel f your home and office Hook-Up & Programming Book[draft] 25.10.2006/ version 1.9 B Table of contents 1. INSTALLING AND COMMISSIONING... 5 1.1.

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

VPS FIREALERT WES+ IS AN INNOVATIVE FIRE SAFETY AND EVACUATION SYSTEM THAT HELPS PROTECT PEOPLE, PROPERTY AND ASSETS IN BUILDING AND CONSTRUCTION SITES. This proven FireAlert system is mobile and wireless,

More information

Installer: (Name, address, telephone)

Installer: (Name, address, telephone) Installer: (Name, address, telephone) UNAC GUIDE No. 3 FOR THE MOTORISATION OF UP-AND-OVER GARAGE DOORS IN ACCORDANCE WITH MACHINERY DIRECTIVE 98/37/EEC AND THE APPLICABLE PARTS OF STANDARDS EN 13241-1,

More information

Audible warning devices for external alarm

Audible warning devices for external alarm VdS SCHADENVERHÜTUNG VdS Publisher: Gesamtverband der Deutschen Versicherungswirtschaft e.v. (GDV) Büro Schadenverhütung Publishing house: VdS Schadenverhütung Rules for Intruder Alarm Systems Audible

More information

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update Technical Paper Functional Safety Update IEC 61511 Edition 2 Standards Update Functional Safety Update Table of Contents 1.0 Introduction 2.0 IEC 61511-1 changes 3.0 IEC 61511-2 changes 4.0 IEC 61511-3

More information

CABLEFLOW RO - RH & RV renal services bedhead trunking systems

CABLEFLOW RO - RH & RV renal services bedhead trunking systems V1.2016 TM CABLEFLOW RO - RH & RV renal services bedhead trunking systems H E A L T H C A R E applications Innovation is at the heart of an evolutionary healthcare infrastructure. Challenging boundaries

More information

The EN54 Part 2 and 4 Fire System

The EN54 Part 2 and 4 Fire System Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire

More information

Mediclean Complanate Ultra Clean Ventilation

Mediclean Complanate Ultra Clean Ventilation Complanate Ultra Clean Ventilation complanate adjective com pla nate \ kämpləˌn t\ : made level : in one plane, flattened to a level surface : Latin complantus Brandon Medical Brandon Medical is a British

More information

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU

Moduflex. Desiccant Air Dryer P3TJA13A1AN - P3TJA13A7AN. USER GUIDE (Original Language) Dry Air System NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU Moduflex Dry Air System Desiccant Air P3TJA13A1AN - P3TJA13A7AN EN USER GUIDE (Original Language) NL DE FR FI SV NO DA EL ES PT IT PL SK CS ET HU LV LT RU SL TR MT CONTENTS 1 Safety Information...2 1.1

More information

Washing Machine OWNER S MANUAL MODEL:MB45T. Before using your washing machine, please read this manual carefully and keep it for future reference.

Washing Machine OWNER S MANUAL MODEL:MB45T. Before using your washing machine, please read this manual carefully and keep it for future reference. Befe using your washing machine, please read this manual carefully and keep it f future reference. Washing Machine OWNER S MANUAL MODEL:MB45T Read This Manual Inside you will find many helpful hints on

More information

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99 Sharon S. Gilyeat, P.E. Lauren Schrumpf August 8, 2018 Expertly Engineering

More information

The EN54 Part 2 & 4 Fire System

The EN54 Part 2 & 4 Fire System Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54

More information

SYSTEM 5000 USER MANUAL

SYSTEM 5000 USER MANUAL SYSTEM 5000 USER MANUAL Table of Contents Section Page No 1 Introduction: -... 3 1.1 Procedure:... 3 1.2 Warnings and Cautions:... 3 2 User Control Levels:... 4 3 User Passwords:... 4 4 Controls and Displays:

More information

New Silent Alert Fire Safe System

New Silent Alert Fire Safe System 1 New Silent Alert Fire Safe System TECHNICAL MANUAL This manual covers the FSTX-2225-EU - Fire Alarm Interface PG3A-2204-EU - Pager Unit - Fire Safe Compatible FSCH-2226-IN - Fire Safe Charger or CH3A-2205-IN

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

USER MANUAL & MAINTENANCE GUIDE OG OO

USER MANUAL & MAINTENANCE GUIDE OG OO M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to

More information

CW9000 Wireless Fire System. Installation Manual

CW9000 Wireless Fire System. Installation Manual CW9000 Wireless Fire System Installation Manual CONTENTS 1 PROJECT PROCESS...4 1.1 PLANNING...4 1.2 SITE SURVEY...4 1.3 EQUIPMENT INSTALLATION...4 1.4 COMMISSIONING / CONFIGURATION...4 2 SYSTEM INSTALLATION...5

More information

Statutory Compliance Checklist

Statutory Compliance Checklist Date of Issue: April 2017 Statutory Compliance Checklist This document is for clergy and churchwardens to help them in the maintenance of their Churches. Refer to supplementary notes for further guidance.

More information

Where Process Safety meets Machine Safety

Where Process Safety meets Machine Safety Where Process Safety meets Machine Safety A document to aid understanding between the end-user and machine builder for functional safety issues. by The 61508 Association Overriding key principle...it must

More information

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions EN54-3:2001+A1:2002+A2:2006 EN54-7:2000+A1:2002+A2:2006 EN54-25:2008 0359 Electro Detectors Ltd. Electro

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Zeus 15 Central Alarm

Zeus 15 Central Alarm 0088 Central Alarm Zeus Medical Gas Alarm Systems Installation, Operation and Maintenance Manual Published by Pneumatech Medical Gas Solutions All possible care has been taken in the preparation of this

More information

V medisys integra fully integrated bedhead services trunking systems

V medisys integra fully integrated bedhead services trunking systems V1.2016 TM medisys integra fully integrated bedhead services trunking systems H E A L T H C A R E applications Innovation is at the heart of an evolutionary healthcare infrastructure. Challenging boundaries

More information

Fire detection and alarm

Fire detection and alarm Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.

More information

14300 MAINS SEPARATOR ALARM MANUAL

14300 MAINS SEPARATOR ALARM MANUAL Conder Environmental Solutions 14300 MAINS SEPARATOR ALARM MANUAL Separator and Alarm provided by: Alarm Installation, Commissioning & Servicing Support Please contact: www.envirotank.com.au www.envirotank.co.nz

More information

FIRE SAFETY FOR PRE-SCHOOLS AND CHILDCARE FACILITIES GENERAL GUIDANCE COUNTY COMMITTEE LIMERICK CHILDCARE

FIRE SAFETY FOR PRE-SCHOOLS AND CHILDCARE FACILITIES GENERAL GUIDANCE COUNTY COMMITTEE LIMERICK CHILDCARE COUNTY COMMITTEE CHILDCARE LIMERICK COISTE CHONTAE LUIMNIGH UM CHÚRAM LEANAÍ Limerick County Fire & Rescue Service GENERAL GUIDANCE FIRE SAFETY FOR PRE-SCHOOLS AND CHILDCARE FACILITIES Foreword We are

More information

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL

CO Guardian LLC Document: E. AIRPORT DRIVE Date: 11/15/05 OWNERS MANUAL OWNERS MANUAL CARBON MONOXIDE DETECTOR MODELS Panel mount and Remote Detectors (R) (353 and 353R) 353 FAMILY MODEL OWNERS/INSTALLATION MANUAL Page 1 of 22 LOG OF REVISIONS REV NO. PAGE NO. DATE DESCRIPTION

More information

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL

NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL NEUTRONICS MINI ID R-1234yf REFRIGERANT IDENTIFIER OPERATION MANUAL 456 Creamery Way, Exton, PA 19341, USA Phone: 610.524.8800 Fax: 610.524.8807 Email: info@refrigerantid.com www.refrigerantid.com Page

More information

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV LC1 & 2 Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV ZIRCONLC1 One Zone Conventional Fire Panel ZIRCONLC2 Two Zone Conventional Fire Panel Compliant with EN54-2:1998 & EN54-4:1998

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

Installation, Operating and Maintenance Manual

Installation, Operating and Maintenance Manual STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS

More information

SIL725 Safety Annunciator

SIL725 Safety Annunciator SIL725 Safety Annunciar Configurable SIL2 Annunciar certified IEC61508 SIRA certified at safety integrity level SIL2 IEC61508 Modular construction from 1 128 alarm channels Multi-redundant design Choice

More information

Ambient Weather WS-091-C Three Channel Display Wireless Thermometer (Console Only) User Manual

Ambient Weather WS-091-C Three Channel Display Wireless Thermometer (Console Only) User Manual Ambient Weather WS-091-C Three Channel Display Wireless Thermometer (Console Only) User Manual Table of Contents 1 Introduction... 2 2 Getting Started... 2 Parts List... 3 2.2 Display Console Set Up...

More information

WIRELESS WATER CONTROLLER. MC-503RC Installation and Operation Manual

WIRELESS WATER CONTROLLER. MC-503RC Installation and Operation Manual WIRELESS WATER CONTROLLER MC-503RC Installation and Operation Manual Suitability Suitable for the following Rinnai continuous flow water heaters with Quick Connect cable connector and controllers: Water

More information

Product overview. Alarm indicator, operator and display panels

Product overview. Alarm indicator, operator and display panels Product overview Alarm indicator, operator and display panels 1 2 Innovative operating concepts for safe power supply in all medical locations Despite all technology that is necessary in medical locations

More information

Consultant Specification AGILE Wireless Fire Detection System

Consultant Specification AGILE Wireless Fire Detection System Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...

More information

APC BC300 Series 40kW 208/450/480V User Guide

APC BC300 Series 40kW 208/450/480V User Guide APC BC300 Series 40kW 208/450/480V User Guide Copyright 2002 APC Denmark ApS This manual is subject to change without notice and does not represent a commitment on the part of the vendor Thank You Thank

More information

Alarm Controller Fire and CO

Alarm Controller Fire and CO Alarm Controller Fire and CO Model: Ei450 Instruction Manual Read and retain carefully for as long as the product is being used. It contains vital information on the operation and installation of your

More information

ID2000. operating manual

ID2000. operating manual ID2000 operating manual 997-434-000-2, Issue 2 Contents ID2000 Series Operating Manual Contents 1 Introduction 1 1.1 Associated Documents 1 1.2 The ID2000 Panels 1 1.3 Cleaning 2 2 Panel Controls and Indicators

More information

IGEM/G/5 Edition 2 Communication 1762 Gas in multi-occupancy buildings

IGEM/G/5 Edition 2 Communication 1762 Gas in multi-occupancy buildings Communication 1762 Gas in multi-occupancy buildings Founded 1863 Royal Charter 1929 Patron: Her Majesty the Queen Communication 1762 Gas in multi-occupancy buildings Price Code: C5H The Institution of

More information

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm

AlertMaxx2. Installation & Operating Manual. Ground Water (DMS-298) Pump Station High Level Alarm Ground Water (DMS-298) Installation & Operating Manual Pump Station High Level Alarm T. E. W. 01992 523 523 info@deltamembranes.com www.deltamembranes.com Delta House, Merlin Way, North Weald, Epping,

More information

Operation & Maintenance Manual

Operation & Maintenance Manual Operation & Maintenance Manual for Model 2100 Fire+Smoke systems from Smoke Guard, Inc. 287 N. Maple Grove - Boise, ID 83704 Phone: (800) 574-0330 Fax: (208) 639-7851 E-Mail: info@smokeguard.com Website:

More information

Digital Electronic Thermostat With RF

Digital Electronic Thermostat With RF Digital Electronic Thermostat With RF Instruction Manual Model No RT300RF PRODUCT COMPLIANCE This product complies with the essential requirements of the following EC Directives: Electro-Magnetic Compatibility

More information

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL

MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL MAINS KLARGESTER SEPARATOR ALARM INSTALLATION & OPERATIONS MANUAL Contents IMPORTANT... 3 General Description... 4 General Operation... 4 Changing Factory Settings... 4 Alarm Type... 4 Check Interval...

More information

Electrical Safety Policy and Management System

Electrical Safety Policy and Management System TITLE: PAGE: 1 OF 14 Housing Solutions Limited Electrical Safety Policy and Management System Page 1 of 15 TITLE: PAGE: 2 OF 14 FOREWORD This document details the system for the management of electrical

More information

St Edward s Oxford FIRE SAFETY POLICY

St Edward s Oxford FIRE SAFETY POLICY FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9

More information

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B

Dear Customer. Section Old F8 January 2017 Amendment 4. Replace with new title page and document history pages 1 2B Dear Customer Please find enclosed Amendment 4, effective 14 February 2014, to the Acceptable Solution and Verification Method for Clause F8 Signs of the New Zealand Building Code. THe previous amendment

More information

Greenstar 12i/24i System

Greenstar 12i/24i System USER INSTRUCTIONS & CUSTOMER CARE GUIDE Greenstar 12i/24i System WALL HUNG GAS-FIRED CONDENSING SYSTEM BOILER FOR SEALED CENTRAL HEATING SYSTEMS & INDIRECT FED DOMESTIC HOT WATER THIS BOILER IS USED WITH

More information

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard SOCIAL ACCOUNTABILITY ACCREDITATION SERVICES To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard Background: After an

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

CA5000 Liquid CO 2 Freezer Backup System

CA5000 Liquid CO 2 Freezer Backup System CA5000 Liquid CO 2 Freezer Backup System OPERATING INSTRUCTIONS MANUAL HAMPSHIRE CONTROLS CORPORATION ONE GROVE STREET / P.O. BOX 516, DOVER, NEW HAMPSHIRE USA 03821 TEL. (603) 749-9424 FAX (603) 749-9433

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60364-4-44 Edition 1.1 2003-12 Edition 1:2001 consolidated with amendment 1:2003 Electrical installations of buildings Part 4-44: Protection for safety Protection against voltage

More information

Ambient Weather WS-16 8-Channel Wireless Thermometer with Min/Max Display User Manual

Ambient Weather WS-16 8-Channel Wireless Thermometer with Min/Max Display User Manual Ambient Weather WS-16 8-Channel Wireless Thermometer with Min/Max Display User Manual Table of Contents 1 Introduction... 2 2 Getting Started... 3 2.1 Parts List... 3 2.2 Thermometer Sensor Set Up... 3

More information