ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS

Size: px
Start display at page:

Download "ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS"

Transcription

1 Schneider Electric NEC January 15, 2008 ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS by Grant Van Hemert, P.E., application engineer, Water and Wastewater Competency Center, Schneider Electric Industrial control panels can be found in lift stations, OEM-supplied equipment, or as main control system cabinets. Traditionally, industrial control panel design depended on several different articles in the National Electrical Code (NEC ). This resulted in confusion and disagreements. In 2005, NEC 409 was introduced to address this confusion. To understand the technical and liability ramifications, an overall introduction to the issue is required. What is an Industrial Control Panel? According to the NEC 409.2, an industrial control panel is an assembly of a systematic and standard arrangement of two or more components such as motor controllers; overload relays; fused disconnect switches; and circuit breakers and related control devices including pushbutton stations, selector switches, timers, switches, and control relays, with associated wiring, terminal blocks, pilot lights and similar components. Industrial control panels are designed to handle a custom application with an enclosure that has one or more doors. When the enclosure is opened, an unobstructed area is available to house controls for multiple motors, valves, etc. Power and control signals are routed via dedicated wires. Another assembly, the motor control center (MCC), could meet this definition. However, MCCs have distinct features, such as a hidden three-phase horizontal bus, that distinguishes them from an Industrial Control Panel. MCCs must comply with separate codes and standard. Furthermore, MCCs are made by mainline electrical equipment suppliers, such as Square D/Schneider Electric. Motor control center Control panel with door open and closed Figure 1 A system integrator, electrical contractor or consultant can identify these different types of equipment more clearly. 1

2 What Does NEC 409 Say? NEC 409 is mostly calculations and references to other sections within the NEC. However, three sentences in section (3) require an industrial control panel to have a marked short circuit current rating (SCCR). Satisfying these sentences requires a major shift in industrial control panel design. What is a Short Circuit Current Rating? The SCCR is the amount of momentary energy that a device must withstand without compromising the physical integrity of the control panel. This is to protect workers near the closed panel from arc flash, or shrapnel. If the fault current is less than the device s SCCR, then the device should contain the energy. However, the device could sacrifice its functionality and may need replacing. The SCCR is different than the current rating of the device. The current rating is the continuous current that the device can handle without degradation of the anticipated life (or tripping, in the case of a circuit breaker). Every device has both ratings. Circuit breakers call this the Amperage Interrupting Current (AIC) rating. The final SCCR of the control panel can be influenced by other factors outside of the actual components being examined. Before NEC 409, it was unclear how to address SCCR in a control panel. Control panel designers might have been unaware of the topic, or used a variety of rule of thumb techniques. Often the result was a control panel with potential vulnerabilities. Obviously, vulnerable control panels are not what any operator wants. NEC (3) increases reliability by ensuring that a fault in the panel can only traverse through devices that can handle the current until a breaker clears. Therefore, if a 17,000 amp fault occurred downstream of the starter, then the starter must hold together until the circuit breaker can open and clear the fault. The intent of the code is clear; but, how can control panel builders ensure they are in incompliance? NEC (3) says that a panel builder is responsible for marking the SCCR of his panel. While several methods exist to determine the rating, the code suggests UL-508A-2001 Supplement SB. What is UL-508A? Underwriters Laboratories (UL) standard 508A is one of the most popular methods for ensuring quality industrial control panel construction, and satisfying the requirement of NEC NEC 90.7 indicates that an inspector, at their discretion, is not obligated to examine third-party labeled panels. A full discussion of UL-508A is well beyond the scope of this article. However, Supplement SB is the short circuit guideline for that standard. Supplement SB provides two basic methods for satisfying NEC (3). For the purposes of this article they will be referred to as Straight-Line, and Combination. These are illustrated in Figure 2 2

3 23KA Available 5KA Rated Group tested to 25KVA 15KA Rated Straight Line Method: Each device must be individually rated for available fault current Combination Method: Different rated devices tested together for a rated combination Figure 2 In the Straight-Line method, every component within a fault path has to be rated for the maximum available fault current. The Combination method uses groups of devices that have been tested together to achieve a rating. It is possible that individual device SCCR may be less then the tested rating. A full discussion of this reason is beyond the The Combination method allows for more economical choices than the Straight-Line method. Combinations cannot be created without testing and approval by a third party testing agency. Most panel shops are ill-equipped to determine a combination. Electrical equipment suppliers, like Schneider Electric, assist control panel builders by testing various combinations for use. The result is a simple tool to aid the designer. Schneider Electric s tool can easily be accessed via the Web by searching Schneider Electric UL 508A Frameset Commitment. Who has ultimate liability? This discussion is well beyond the scope of this article. In summery, NEC says that equipment installed must be able to withstand the available fault current. However, only require panel builders to mark the panel. It does not say that they have to provide a panel sufficient for the fault current. According to NEC 90.4 the Authority Having Jurisdiction (AHJ) is responsible for compliance with the code. NEC 100 says that the AHJ can be a governmental entity, or person responsible for the facility. Thus, the facility must insure that consultanting engineers require each panel builder to adhere to NEC when complying with NEC 409. To accomplish this, the contract documents need to address this, and the plans should have SCCR ratings for each location where an Industrial Control panel can connect to the facilities power distribution system. 3

4 How does a facility determine the Available Fault Current? During design, the consultant s power distribution engineer (PDE) will contact the utility to determine the available fault current at the point of tie-in. It might seem obvious that this rating would determine the available current at all points in the facility, but this is not the case. Ohms Law indicates, transformers, reactors, filters, VFDs, and conductor impedance will decrease available fault current. Thus, the available fault current at a given point in a facility is dependent on the upstream equipment, wire diameter, wire composition, and wired distance to the facilities utility tie in. To insure proper control panel protection, the PDE should show the available fault at each level on their power diagrams drawings or one-line (See Figure 3). This will insure that an industrial control panel engineer can properly comply with NEC during design. 480VAC at 65KA 480VAC at 65KA 480VAC at 65KA 240VAC at 32.5KA Figure 3 However, calculating the available fault current for every location where an Industrial Control Panel connects to the facilities power distribution system can be laborious. This brings us to the next point. Why not use the Available Fault Current at the point of utility tie-in for all panel designs? There are two reasons for this the first being cost. Devices that have a lower SCCR/AIC rating tend to be made up of materials that are less expensive. For example, in the above scenario, designing for 50,000 Amps when only 6,250 is available would needlessly increase cost. The second reason involves how circuit breakers and fuses respond to fault currents. Under normal operating conditions, a circuit breaker or fuse has an intentional time delay when an overload is encountered to prevent nuisance tripping. However, during a fault condition, this delay is bypassed. The closer the fault current is to the rated interrupting capacity the faster the opening. Let s assume the facility has a 100KA rating at the point of Utility tie-in. If a breaker has a 100 KA 4

5 rating, and a 93 KA fault is encountered, then the breaker s magnetic mechanism would open almost instantaneously. However, if the available fault current at the connection point of the Industrial Control Panel is actually 4.5 KA, then the 100KA breaker will delay a few microseconds before opening. This delay will allow damaging energy to pass through the equipment. Thus, a 5 KAIC rated breaker should be used with an available fault current of 4.5 KA to insure a instantaneous opening time. When does NEC 409 Go Into Effect? While section 409 was added to the 2005 NEC, states and municipality adoption has occurred at different rates. Figure 5 shows adoption as of January Color Purple Green Blue Orange Code Enacted 2005 NEC Code 2002 NEC Code 1999 NEC Code State s Discretion Figure 5 What About Existing Industrial Control Panels? Generally, when equipment is installed, it only has to comply with the codes at the time of installation. This means that a control panel installed in 1984 only has to comply with the 1984 code. However, successful lawsuits have been brought against building owners for not complying with current sprinkler codes in older buildings. Thus, a legal precedence has been set. Therefore, a facility might want to create a proactive plan to address older control panels. A consulting engineer 5

6 or well qualified system integrator may have guidance on how to best proceed. More information also can be found at Compliance with NEC (3) will better enable industrial control panels to limit the damage from a fault, allowing municipalities to recover faster at a minimized cost, and better protect the health and safety of on-site personnel. About the Author Grant Van Hemert is an applications engineer for the Schneider Electric Water Wastewater Competency Center. Mr. Van Hemert has over 12 years of water and wastewater experience. Previously he was a design and implementation engineer where he designed and commissioned automation and instrumentation systems dealing with aeration, screening, and clarification. Van Hemert, a licensed professional engineer in the state of North Carolina, can be reached at Grant.VanHemert@us.schneider-electric.com. Square D is a registered trademark of Schneider Electric and/or its affiliates in the United States and/or other countries. Other marks used herein are the property of their respective owners. 6

Understanding NFPA, NEC 2005 Article 409 a White Paper by Paul A. Terry, P.E.

Understanding NFPA, NEC 2005 Article 409 a White Paper by Paul A. Terry, P.E. a White Paper by Paul A. Terry, P.E. NFPA 70, NEC 2005: Article 409 Industrial Control Panel Short Circuit Panel Ratings Executive Summary Many panel shops are providing industrial control panels with

More information

Guide Specification Model CTG Automatic Transfer Switch

Guide Specification Model CTG Automatic Transfer Switch Guide Specification Model CTG Automatic Transfer Switch PART 1 GENERAL 1.1 Scope A. It is the intent of this specification to secure a transfer switch that has been prototype tested, factory built, production

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G E SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF DATE: 11/13/06 2/1/07 1 Copyright, E, Inc. E 1. ENERAL...4 1.1 Scope Of Work... 4 1.2 Codes and Standards... 4 2. PRODUCTS...5

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers on September 6, 2011. Officer approval of this revision is not required. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Utility with

More information

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100 Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training

More information

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 by Reza Tajali, Schneider Electric Engineering Services Summary 1.0 Abstract 2.0 OSHA and NFPA Rules 3.0 Use of NFPA 70E

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES SECTION 26 36 23 AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION 4000 LIFT STATIONS

SECTION 4000 LIFT STATIONS SECTION 4000 LIFT STATIONS LIFT STATIONS PART 1 GENERAL 1.01 Section Summary A. Lift station control panels. B. Related requirements include those established in the General Requirements Division 1, Division

More information

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides

More information

Short Circuit Current Rating

Short Circuit Current Rating Short Circuit Current Rating Customer Need There has been a significant increase in the misapplication of control panel products that brings into question the safety of those installing and using this

More information

2017 NEC: Impact to Electrical System Designs

2017 NEC: Impact to Electrical System Designs 2017 NEC: Impact to Electrical System Designs We will begin shortly. Turn up your speakers in order to hear the hold music. Feel free to ask questions now in the Q&A widget! Today s broadcast is sponsored

More information

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass

Model VPS Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass Project: Customer: Engineer: Pump Manufacturer: Submittal Document Model VPS Pressure Limiting (VFD) with Soft Start Bypass Contents: Data Sheets Dimensional Data Wiring Schematics Field Connections Note:

More information

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S.

CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. CALL FOR TENDER - MUNICIPALITY OF THE DISTRICT OF CLARE LITTLE BROOK, N.S. NAME OF TENDER: CONSTRUCT, DELIVER AND COMMISSION 3 (THREE) LIFT STATION ELECTRICAL LOCATION OF WORK: 3 Separate work sites in

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators

GPS 140 NEC Requirements for Generators. Professional Development Seminar Series NEC Requirements for Generators GPS 140 NEC Requirements for Generators WHAT YOU WILL LEARN NEC requirements for on-site power generation. Recent events have created increased interest in standby power This module organizes NEC requirements

More information

Elevator Control ES Switch

Elevator Control ES Switch Technical Data TD00801003E Contents Description Page Danger and Warnings...................... 2 Overview, Standard & Optional Features........3 Catalog Number System.................... 3 Other Options............................

More information

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch

Model VPS + VPU Pressure Limiting (VFD) Electric Fire Pump Controller with Soft Start Bypass with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Technical Data Submittal Document Model VPS + VPU Pressure Limiting (VFD) with Soft Start Bypass with Automatic Transfer Switch Contents: Data Sheets Dimensional

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

Property risk solutions

Property risk solutions Property risk solutions Inside this issue Welcome to this edition of the Property risk solutions newsletter. This quarterly publication focuses on fixed fire protection and human element safety solutions

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

SECTION ENCLOSED CONTROLLERS

SECTION ENCLOSED CONTROLLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes ac,

More information

Exhibit J. Subcontract Agreement No.

Exhibit J. Subcontract Agreement No. Exhibit J SUBCONTRACTOR TRADE INTERFACE AGREEMENT Subcontract Agreement No. PROJECT: NEW EASTSIDE REGIONAL PARK PHASE I PARTICIPANTS (PARTIES): Sundt Construction, Inc. PURPOSE: General Contractor (Sundt)

More information

GE Industrial Solutions. Residential Electronic Circuit Interrupters

GE Industrial Solutions. Residential Electronic Circuit Interrupters GE Industrial Solutions Residential Electronic Circuit Interrupters Dual Function Circuit Interrupter (DFCI) Provides ground fault and arc fault circuit protection in one unit The 2014 National Electric

More information

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device

More information

PGR-8800 TECHNICAL FAQ

PGR-8800 TECHNICAL FAQ PGR-8800 SOLAR ARC-FLASH PRODUCTS RELAY CATALOG TECHNICAL FAQ What are the typical applications / system voltages? The PGR-8800 can be used on electrical systems operating at any voltage (AC or DC) since

More information

Molded Case Circuit Breakers, Bulletin 140G

Molded Case Circuit Breakers, Bulletin 140G ROCKWELL AUTOMATION PROCUREMENT SPECIFICATION PROCUREMENT SPECIFICATION Molded Case Circuit Breakers Bulletin 140G NOTICE: The specification guidelines in this document are intended to aid in the specification

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

Product Specifications 4 Breaker Main Disconnect Panel with Undervoltage Trip

Product Specifications 4 Breaker Main Disconnect Panel with Undervoltage Trip NOVA Energy & Automation Product Specifications 4 Breaker Main Disconnect Panel with Undervoltage Trip Model NEAS-44125-G-UVR-C 03 January 2012 Product Description 1. Standard Applications The Nova 4 Breaker

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

PUMP CONTROL CENTER (PCC)

PUMP CONTROL CENTER (PCC) PART 1 SUMMARY A. In accordance with the plans and specifications, the Contractor shall provide and install a complete pre-fabricated, pre-tested ArcSafe Pump Control Center including all required equipment,

More information

Combination Type AFCI

Combination Type AFCI Combination Type AFCI Evolution of the Arc Fault Circuit Interrupter www.usa.siemens.com/afci 2 Alarming Statistics According to the U.S. Fire Administration (USFA), an estimated 67,800 fires, 485 deaths,

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

PART 4 ELECTRICAL STANDARDS

PART 4 ELECTRICAL STANDARDS PART 4 ELECTRICAL STANDARDS 1.0 INTRODUCTION AND SCOPE: These standards reflect the general requirements and recommendations of elevator contractors, with respect to the power distribution system to achieve

More information

ANSI/NETA Standards Update

ANSI/NETA Standards Update Specifications and Standards Activity ANSI/NETA Standards Update NOW AVAILABALE!!!! NETA Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems The NETA Acceptance Testing

More information

Arc Fault Circuit Interrupters The Next Generation of Fire Prevention - The Next Generation of Recovery Opportunities

Arc Fault Circuit Interrupters The Next Generation of Fire Prevention - The Next Generation of Recovery Opportunities Arc Fault Circuit Interrupters The Next Generation of Fire Prevention - The Next Generation of Recovery Opportunities By: William N. Clark, Esq. Cozen O Connor 1900 Market Street Philadelphia, PA 19103

More information

Data Bulletin. Determining the Cause of AFCI Tripping Class 760

Data Bulletin. Determining the Cause of AFCI Tripping Class 760 Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document

More information

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to: PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.

More information

CHAPTER 20 SERVICE EQUIPMENT

CHAPTER 20 SERVICE EQUIPMENT SERVICE EQUIPMENT CHAPTER 20 SERVICE EQUIPMENT Service equipment includes service cabinets and the equipment and materials necessary for installation. 20.1 Signal Service Cabinet For MnDOT traffic control

More information

ELECTRICAL PANEL SAFETY ALERT I N S T I T U T E

ELECTRICAL PANEL SAFETY ALERT I N S T I T U T E ELECTRICAL PANEL SAFETY ALERT CONSUMER SAFETY I N S T I T U T E Dangerous Panels brochure.indd 1 9/29/08 11:41:48 AM The Electrical Panel The Heart of a Home s Electrical System The home s electrical system

More information

Fixed Fire Protection Getting it right, Ensuring Performance and Value

Fixed Fire Protection Getting it right, Ensuring Performance and Value Fixed Fire Protection Getting it right, Ensuring Performance and Value 18 th May 2017 Stuart Lloyd, EngTech TIFireE Principal Risk Engineer Practice Leader Fire Protection Engineering Zurich Risk Engineering

More information

MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning

MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning CAMPUS FIRE SAFETY CODE TALK Campus Fire Safety e-newzone MULTI-PHASED FIRE ALARM AND MASS NOTIFICATION SYSTEM UPGRADES: The Authority Having Jurisdiction (AHJ) and Proper Planning By Ernesto Vega Janica,

More information

Construction Electrical

Construction Electrical INDEECO offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the previous section, makes it easy to specify

More information

Mains Power Filter 970MF10 970MF20. Installation Instructions

Mains Power Filter 970MF10 970MF20. Installation Instructions Mains Power Filter Installation Instructions and Table of Contents 1.0 Warnings... 3 2.0 Introduction... 3 3.0 Quick Installation Overview... 3 4.0 Typical Installations... 3 5.0 Protection Concepts...

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip

Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip NOVA Energy & Automation Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip Model NEAS-XXXX-G-UVR 03 January 2012 Product Description 1. Standard Applications The Nova 3 Breaker

More information

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc. Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional

More information

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts

Electrical. Bi-Metallic Thermal Cutouts. Linear Thermal Cutouts Standard Construction Control Options HEATREX offers a broad range of electrical components for temperature, safety, and power control. For most applications, the Control Option system, described in the

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage

Root Cause Analysis Report Tesoro Golden Eagle Refinery Refinery Power Outage Summary of Event: The Golden Eagle Refinery (Refinery) experienced a partial electrical outage December 10, 2010 at 10:12 hrs when a transformer at Switching Station #7 failed. A CWS Level 1 report was

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

whole house safety Pocket Guide to Whole House Safety Siemens Energy & Automation, Inc Old Milton Parkway Alpharetta, GA 30005

whole house safety Pocket Guide to Whole House Safety Siemens Energy & Automation, Inc Old Milton Parkway Alpharetta, GA 30005 Pocket Guide to Whole House Safety whole house SAFETY whole house Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com/afci

More information

DRAFT INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information

DRAFT INSTALLATION INSTRUCTIONS. Solid-State Series !! NOTE!! Covers the following models: Refer to INSERT for additional information INSTALLATION INSTRUCTIONS Solid-State Series!! NOTE!! Covers the following models: " CS6100 - CS7100 " CS6200 - CS9200 " CS6220 - CS9220 " CS6230 - CS9230 " CS6500 - CS7500 " CS6330 - CS9300 " CS9400 -

More information

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS PREFACE This service manual is primarily intended for the use of qualified individuals specially trained and experienced in the service of this type of equipment

More information

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie

More information

Welcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo

Welcome DISCLAIMER. Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard 5/1/ NFPA Conference & Expo 2017 NFPA Conference & Expo Testing Electric Fire Pumps You Need to Understand the Arc Flash Hazard Presented by: Tracey D. Bellamy, PE, CFPS Chief Engineering Officer Telgian Corporation Welcome Instructor

More information

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC

Changes to NFPA 70E. - The Role of PdM &Safe PdM Work Practices. Tim Rohrer Exiscan LLC Changes to NFPA 70E - The Role of PdM &Safe PdM Work Practices Tim Rohrer Exiscan LLC Tim@Exiscan.com 585-705-7775 Joe Gierlach ABM Joseph.Gierlach@ABM.com 412-394-4678 Preview Electrical Safety Risk Management

More information

Products :: Circuit Protection :: Thermal Circuit Breakers

Products :: Circuit Protection :: Thermal Circuit Breakers Products :: Circuit Protection :: Thermal Circuit Breakers Thermal Circuit Breaker CTB-Series CTB-Series PDF elibrary The CTB-Series is a compact, single pole, rocker actuated family of thermal circuit

More information

Guide to Compliance with the Electrical Workplace Safety Standards in the United States

Guide to Compliance with the Electrical Workplace Safety Standards in the United States Guide to Compliance with the Electrical Workplace Safety Standards in the United States July 2011/1910DB1102 by Joseph H. Weigel, Product Manager Schneider Electric USA, Inc. Make the most of your energy

More information

Welcome! Siemens Industry Inc All rights reserved.

Welcome! Siemens Industry Inc All rights reserved. Welcome! Siemens Industry Inc. 2014. All rights reserved. Welcome! Introduction to Industrial control panels for North America and Europe Overview about important: - North American standards and regulations

More information

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS) PART 1 GENERAL 1.01 Scope Furnish and install manual transfer switches (3MTS) with number of poles, amperage, voltage, and withstand

More information

How to reduce exposure to arc flash hazards

How to reduce exposure to arc flash hazards GE Electrical Distribution How to reduce exposure to arc flash hazards Multiple solutions for new and existing facilities imagination at work Multiple Issues Today s power system engineer must not only

More information

ELECTRICAL BULLETIN

ELECTRICAL BULLETIN PO Box 697 Halifax, Nova Scotia B3J 2T8 Labour and Workforce Development ELECTRICAL BULLETIN 2011-01 From: David MacLeod,C.E.I.,P.Eng. Pg 1 of 6 Provincial Chief Electrical Inspector Date: January 5,2011

More information

Introduction Consultant shall incorporate the material in the DSS into the project specifications.

Introduction Consultant shall incorporate the material in the DSS into the project specifications. DIVISION 16 - ELECTRICAL Section 16000 - General Discussion Introduction Consultant shall incorporate the material in the DSS into the project specifications. Refer any questions, clarifications regarding

More information

Control Panel Technical guide. How to ensure trouble-free approval of your UL-compliant control panels

Control Panel Technical guide. How to ensure trouble-free approval of your UL-compliant control panels Control Panel Technical guide How to ensure trouble-free approval of your UL-compliant control panels This guide* explains certain points requiring special attention for trouble-free export sales. *This

More information

Please think twice about printing this matrix. You can it, along with your ballot to or

Please think twice about printing this matrix. You can  it, along with your ballot to or Page Line Clause E/G Organization Comment (rationale) ii Foreword E GWM Recommend inserting the following text between the first and second paragraphs, Fire Alarm Systems shall be installed in accordance

More information

How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers

How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers AFCI and GFCI Homeowner s Guide How to keep you, your family, and your possessions safe usa.siemens.com/circuitbreakers Congratulations on the purchase of your new home. This guide will help you understand

More information

Drawing Submittal Package

Drawing Submittal Package Project: Customer: Engineer: Pump Manufacturer: Drawing Submittal Package Model GPL + GLU Limited Service Full Voltage Across the Line Start Electric Pump Controller with Automatic Power Transfer Switch

More information

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL AR C Rev.06 WARNING 1. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to

More information

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch

Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU. with Automatic Power Transfer Switch Project: Customer: Engineer: Pump Manufacturer: Model GPY + GPU with Automatic Power Transfer Switch Contents: NOTE: The drawings included in this package are for controllers covered under our standard

More information

Machinery Room Electrical Best Practices

Machinery Room Electrical Best Practices Machinery Room Electrical Best Practices Brad Heeres Angus-Young Associates February 8, 2007 Understand and comply with applicable codes and standards The National Electrical Code requirements for a safe

More information

Subcontract Agreement No.

Subcontract Agreement No. ATTACHMENT G TRADE INTERFACE AGREEMENT Subcontract Agreement No. PROJECT: TEXASTECH UNIVERSITY HEALTH SCIENCES CAMPUS, EL PASO, TEXAS MEDICAL SCIENCE BUILDING II PARTICIPANTS: Sundt Construction, Inc.

More information

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)

More information

SECTION FIRE PUMP AND CONTROLS

SECTION FIRE PUMP AND CONTROLS SECTION 15320 FIRE PUMP AND CONTROLS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire pump, jockey pump, and controls including necessary accessories as shown in Construction Documents, specified

More information

Operational Overview and Controls Guide

Operational Overview and Controls Guide DOCUMENT: ECSEQ2-2 EFFECTIVE: 02/26/10 SUPERSEDES: 02/14/07 Operational Overview and Controls Guide Standard Two or Three Pump Type VFD Booster Controls 6700 Best Friend Road. Norcross, GA 30071. (770)

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Cold Deck Canopy and Shelf Lights and Retrofit Kit

Cold Deck Canopy and Shelf Lights and Retrofit Kit PAGE 1 OF 8 General Information Cold Deck LED lighting systems are intended for use inside of commercial refrigerated display merchandisers for food zone, splash zone, and non-food zones only. Cold Deck

More information

Risk Mitigation of Aging Electrical Infrastructure

Risk Mitigation of Aging Electrical Infrastructure Risk Mitigation of Aging Electrical Infrastructure 2014 WWOA Annual Conference 10:55am Thursday October 9 th, 2014 Presented by and Authored by Jeff M. Miller, PE, ENV SP About the Presenter Jeff M. Miller,

More information

I P. Tough Starters for Tough Environments. Explosion Proof Starter. Ready to Install, Completely Wired and Assembled

I P. Tough Starters for Tough Environments. Explosion Proof Starter. Ready to Install, Completely Wired and Assembled I P Explosion Proof Starter 1Ø & 3Ø, 115~600VAC, 1 75HP START/STOP AND RESET PUSHBUTTONS ELECTRONIC MOTOR PROTECTION Tough Starters for Tough Environments Ready to Install, Completely Wired and Assembled

More information

Sec False alarms.

Sec False alarms. Sec. 16-5. - False alarms. (a) Definitions. The following words, when used in this section, shall have the meanings ascribed herein unless the context indicates otherwise: Agreement [means] police and/or

More information

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc MASTER PRESSRE MAINTANENCE CONTROLLER Models PMCE INSTRUCTION MANUAL C 2018 Master Control Systems, Inc TABLE OF CONTENTS Important Safety Information. Page 3 General Description and Installation.. Page

More information

WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY

WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY WHITE PAPER: THE IMPORTANCE OF ARC FAULT CIRCUIT INTERRUPTER TECHNOLOGY 1 Introduction Thousands of deaths and billions of dollars in property loss occur every year due to residential structure fires.

More information

National Electrical Code

National Electrical Code National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation

More information

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

THE SS90 SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL S S S S S S OLID TATE ECURITIES, INC S S 90 SOLID STATE FAIL-SAFE UNIT * PATENT PENDING LISTED 99Y9 RESET U L RELEASING DEVICE SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE

More information

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut Electrical Safety Through Design Mersen EP formerly Ferraz Shawmut Agenda Who is Mersen? Selective Coordination Code Requirements Coordination Made Easy Mitigating Arc Flash Energy on Transformer Secondary

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

Welcome! Siemens Industry Inc All Rights Reserved.

Welcome! Siemens Industry Inc All Rights Reserved. Welcome! Industrial Control Panels and Machinery for North America Industrial Control Panels in accordance with the Standard UL508A Electrical Equipment of Machinery in accordance with the Standard NFPA79

More information

PANELBOARDS & BUILDING DISTRIBUTION

PANELBOARDS & BUILDING DISTRIBUTION 262416 PANELBOARDS & BUILDING DISTRIBUTION PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Distribution panelboards 2. Power panelboards B. Related Sections: 1.02 POLICY 1. CU Standard 260500, Basic

More information

Instruction Manual: IM E. Installation and Operation Manual for Powerware PVL 50, 80, 100, 120, 160, 200 KA

Instruction Manual: IM E. Installation and Operation Manual for Powerware PVL 50, 80, 100, 120, 160, 200 KA Installation and Operation Manual for Powerware PVL 50, 80, 100, 120, 160, 200 KA Instruction Manual: For more information visit: www.eatonelectrical.com Effective: 01/06 PVL Page 2 Effective Date: 01/06

More information

AF/GF dual-purpose receptacles

AF/GF dual-purpose receptacles Eaton Wiring Devices OBC AF/GF dual-purpose receptacles AF/GF dual-purpose receptacles Arc fault and ground fault protection in one device In Stock July 2016! Eaton Wiring Devices OBC AF/GF dual-purpose

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

Control Circuits in acc. with UL508A

Control Circuits in acc. with UL508A Control Circuits in acc. with UL508A UL guideline, chapter 4.3 Definition of Control Circuits Disconnecting Means Protection of Control Circuits Dimensioning of the wires and cables Loads in the Control

More information

ARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES

ARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES ARC MAPPING IN THE ADVENT OF AFCI, GFCI, AND GFEP CIRCUIT PROTECTION DEVICES Kevin R. Davis, PE, CFEI, CVFI And Mark Goodson, PE Goodson Engineering, Denton, TX ABSTRACT Arc mapping is a tool that can

More information

Afci TR Duplex 20A 125V La. Features amperage rating 20. Dimensions and Weight Width 3.3. Long Description

Afci TR Duplex 20A 125V La. Features amperage rating 20. Dimensions and Weight Width 3.3. Long Description 3804 South Street 75964-7263, TX Nacogdoches Phone: 936-569-7941 Fax: 936-560-4685 TRAFCI20LA Afci TR Duplex 20A 125V La Eaton Wiring Devices Catalog Number Manufacturer Weight per unit Product Category

More information

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120

Surge Protective Devices Installation, Operation and Maintenance Manual. LowProfile Series: 080 and 120 LowProfile Series: 080 and 120 Surge Protective Devices Installation, Operation and Maintenance Manual P.O. Box 3760 Winter Park, FL 32790 USA 1.800.647.1911 www.tpssurge.com LOWPROFILE InstaLLatIOn, OPERatIOn

More information

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL TABLE OF CONTENTS Product Overview... 2 Operation... 3 Installation... 5 Troubleshooting... 9 Ordering Information, Warranty and Service...10

More information

Model GIT 4 Gutter Snow and Ice Melting Control

Model GIT 4 Gutter Snow and Ice Melting Control We manage heat Model GIT 4 Gutter Snow and Ice Melting Control Part Number 19556 Installation and Operation Manual WARNING Hazard of electrical shock. Follow all safety procedures. Any installation involving

More information