1 Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE Prepared by: Peter Golding Tech IOSH and Mark Alderson BSc Hons IEng MIFireE (IFE ) Safety Management (UK) Ltd Holme Suite Clawthorpe Business Park Burton in Kendal LA6 1NU T: E:

2 Fire Risk Assessment Summary Fire Risk Assessment Type (FRA) FRA 3 Date FRA was completed: 6 th September 2017 Date of FRA Summary Action Update: On completion of the remedial work and prior to the re-introduction of the Stay Put Policy. Court Name: Address: Princess Court Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE Priority A* - Top Priority None Priority A - High Priority This building is fitted with a cladding material that has failed BRE testing and a program is in place to remove the cladding and replace with an approved system. Time scales for removal can be confirmed with Trafford Housing. To mitigate the risk associated with the combustible cladding national guidance issued by the DCLG is being followed and regular consultation is being undertaken with the local fire authority. Trafford Housing are consulting with the local Fire Authority and implementing DCLG guidance issued following the Grenfell fire. The electrical cupboards should be checked and a course of work instigated if the fire stopping is not to the required standard. The fire door sets should be checked to ensure that the intumescent around the door sets is to the required standard. There is a metal type loft hatch to the roof space, I could not confirm the fire resistance rating of the hatch. This should be checked to ensure 60 minutes fire resistance is achieved. The riser cupboards on each level require checking for their fire resistance. The bin and recycling chutes on each floor have metal type loading doors, the standard of separation could not be determined and a Type 4 inspection is required. There are services and ducting that pass-through compartment walls and floors. They should all be checked to ensure that the fire stopping used is to the 60 min standard. Type 4 invasive inspections should be undertaken with areas identified within this report. A full specification for the Type 4 inspections needs to be drawn up. Access was gained to two flats. They both had a hard-wired smoke detector in the entrance corridor and a fire door as their front door. The gas-powered boiler for the whole building was located on the roof. The pipework from the flat boiler required fire stopping, this was found inside the cupboards in the lounge. Further type 4 inspections are required to other flats. At the time of this assessment the fire evacuation strategy had been changed from a stay put, to an evacuation. It is recommended that Trafford Housing work towards confirming the long-term fire evacuation strategy. The works that were being carried out at the time of this assessment were improving the fire protection. Further Type 4 inspections are required. The program for removal and replacement of the cladding with an approved system is available from Trafford Housing. 3 months

3 Priority B - Medium Priority There is an issue with the signage, as at the time of the assessment the fire evacuation strategy had changed from a stay put policy to an evacuation policy. With this in mind because of the change in strategy, should this be a full-time change then all of the store rooms, ancillary rooms and intake rooms would require signage on the outside, (fire door keep locked). The premises have a simple layout with a single staircase and residents are familiar with the escape route from the building. Clear fire action notices are displayed at ground floor to indicate action to be take in the event of a fire. A full evacuation strategy is currently in place. The medium-term plan is to return to a stay put policy. In this building there is no central fire alarm panel. For a building with a stay put policy this is acceptable, as each of the flat units has a working hard-wired smoke detector to warn the individual units of a fire. Then the compartmentation of the building will assist in the prevention of a fire spreading. For an evacuation policy, a full fire alarm system to BS5839 would be required. The fire alarm is being extended to cover the communal areas and confirmation of the type, operation and management of the system requires confirming. The flats inspected had hard-wired smoke detectors in the flat entrance hall. After talking to the flat occupier and the caretaker, they confirmed that the detectors are stand alone. It only warns the occupants of the flat of a fire. The rest of the occupants in the building would be unaware of a fire. For a building with a stay put policy, this is acceptable. For a building moving to an evacuation policy this would not be acceptable. There is firefighting equipment in the caretaker s room. The firefighting equipment provided appears to be adequate for the risks. At the time of the assessment the extinguishers that were found had last been serviced in October There was no CO2 extinguisher in the lift motor room. An extinguisher should be supplied for this area. 6 months Priority C - Low Priority The building has a lightning protection system and the Trust should ensure that it is inspected and tested annually as per BS6651 and BS-EN / 12 months Observations This block of flats was in a good condition. I would suggest that the management of Trafford Housing work towards deciding on the long-term fire evacuation strategy. Further level 4 investigations are required and what is going to be done about the cladding to the building. KEY Priority A* Items that should take priority in an action plan (Serious breach of legislation, having the potential for serious injury to occupants. Should be implemented as soon as possible, including, where relevant, interim measures necessary to ensure the safety of occupants until permanent measures can be implemented.) Priority A Items that should be urgent in an action plan (Matters that breach legislation but are not considered to constitute a serious threat to life safety. Should be implemented as soon as is reasonably practicable.) Priority B Items that should be resolved as an ongoing priority within a fixed timescale (Items could be regarded as suitable for immediate implementation, simply because there is no reason to delay doing so, regardless of whether there is a major benefit to the safety of occupants.) Priority C Items that should be resolved as good practice (Should be implemented as and when the opportunity arises.)

4

5 Types of Fire Risk Assessments Type 1 - Fire Risk Assessment Non-destructive assessment of the common parts of a building. Completion of a fire risk assessment template Consideration of the external materials of the building Consideration of compartmentation between common areas and the flats Inspection of a sample of service risers on all floors Inspection above a sample of readily accessible demountable false ceilings if present Inspection of a sample of flat front doors Comprehensive assessment report to include the significant findings, issues identified and actions required Entry into the flats beyond the front door is not included in a type 1 assessment Type 2- Fire Risk Assessment Destructive inspection of the common parts of a building. All of the items in a type 1 assessment Inspection of areas of construction in the common parts by use of a camera and borescope as appropriate Inspection of areas of construction in the common parts opened up as necessary Entry into the flats beyond the front door is not included in a type 2 assessment Type 3 - Fire Risk Assessment Non-destructive inspection of the common parts of a building and the flats. All of the items in a type 1 & 2 assessment Plus the following in a sample of flats: Consideration of compartmentation between flats Consideration of the fire resistance of doors between rooms Consideration of the means of escape from the flat Consideration of the means of fire detection in the flat Testing of the smoke alarm (where present) in the flat Type 4 - Fire Risk Assessment Destructive inspection of the common parts of a building and the flats. All of the items in types 1, 2 and 3 assessments and: Inspection of areas of construction in the flats by use of a camera and borescope as appropriate Inspection of areas of construction in the flats opened up as necessary N.B. THT has also engaged specialist contractor to undertake type 4 FRA s in Q3.

6

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation

Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory

More information

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)

FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

Cladding Screening Test Result

Cladding Screening Test Result Cladding Screening Test Result Submitting body Building address L&Q, One Kings Hall Mews, SE13 5JQ Flats 1-18, Burnell House, E20 1GY Organisation type: Contact details for test result Location of where

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Assessment prepared by - Chris Caton MIFireE Pennine Fire & Safety Limited Pleasington Street Blackburn BB2 1UF info@penninefire.co.uk

More information

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group. FIRE SAFETY POLICY Approver Executive Management Team Policy Fire Safety Policy Monitored By Health, Safety and Fire Steering Group. Date last revised April 2017 Revised by James Warne Next Revision Date

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 161-185, FLORA GARDENS, LONDON Assessment Date 16/01/2018 Assessment Valid Until 23/08/2018 Assessor Details Gary

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA

More information

Fire Safety Management

Fire Safety Management Fire Safety Management Wednesday 20 th June 2018 Russ Timpson www.bcptesting.com 24-storey Grenfell Tower in Kensington, West London June 14, 2017 We shape our buildings, thereafter they shape us Winston

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General

More information

Appendix 1 Fire safety and the Council s response to the Grenfell Tower Tragedy

Appendix 1 Fire safety and the Council s response to the Grenfell Tower Tragedy Appendix 1 Fire safety and the Council s response to the Grenfell Tower Tragedy A. Introduction 1. This appendix sets out the fire safety arrangements that are already in place in Barnet and the additional

More information

FIRE RISK ASSESSMENT. Hatton House. Page 1 of 21

FIRE RISK ASSESSMENT. Hatton House. Page 1 of 21 FIRE RISK ASSESSMENT Hatton House Page 1 of 21 CONTENTS Page 1 Introduction 3-6 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 General Description Of Premises 9 6 Fire

More information

REVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN

REVISED. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN REVISED Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF SHEPHERD S COURT, SHEPHERD S BUSH GREEN July 2017 Responsible Person (e.g. employer) or person having control of the

More information

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

Areas of the building to which access was not available. Details of any onsite management (if known)

Areas of the building to which access was not available. Details of any onsite management (if known) SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

FINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN

FINAL VERSION. Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN FINAL VERSION Report for London Borough of Hammersmith and Fulham FIRE RISK ASSESSMENT OF WOODFORD COURT, SHEPHERD S BUSH GREEN August 2017 Responsible Person (e.g. employer) or person having control of

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

Fire Risk Assessment Standish House Saint Peters Grove W6 9AY 22/06/17

Fire Risk Assessment Standish House Saint Peters Grove W6 9AY 22/06/17 Assessment Standish House Saint Peters Grove W6 9AY 22/06/17 Page 1 of 23 Section One: Details of Premises All questions on this page are compulsory LBHF Ward Ravenscourt Park UPRN Name of Premises (known

More information

Fire Enforcement Report

Fire Enforcement Report AGENDA ITEM 4.4 Fire Enforcement Report Executive Lead: Director of Planning Author: Senior Fire Safety Adviser, Capital Planning & Estate Management Contact Details for further information: Frank Barrett,

More information

Managing fire safety. What s the risk? Bruce Kirkham Principal Consultant Capstone Ltd

Managing fire safety. What s the risk? Bruce Kirkham Principal Consultant Capstone Ltd Managing fire safety What s the risk? Bruce Kirkham Principal Consultant Capstone Ltd Managing Fire Safety What s the risk? Bruce Kirkham PGDip, MCGI, MIFireE, MICPEM, MEPS Annual Conference February 2018

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

Fire Safety in Schools Post-Grenfell Fire

Fire Safety in Schools Post-Grenfell Fire Fire Safety in Schools Post-Grenfell Fire Joint Guidance to School Leaders from the National Education Union (NEU), National Association of Headteachers (NAHT) and the Association of School and College

More information

Independent Living Scheme Fire Risk Assessment. Independent living sheltered residential accommodation and public library

Independent Living Scheme Fire Risk Assessment. Independent living sheltered residential accommodation and public library Independent Living Scheme Fire Risk Assessment Strelley Court Strelley Road Strelley ttingham NG8 3BJ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly

More information

Waking Watch / Common Fire Alarm. Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats

Waking Watch / Common Fire Alarm. Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats Waking Watch / Common Fire Alarm Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats Contents 1. Introduction... 3 2. Definitions... 5 3. Competence... 6

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Manor House HS.F.119 (rev03) delivering promises improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management systems... 1 4 General description

More information

fire risk assessments shepherds court and bush court, charecroft estates off shepherds bush green, london w12 8ra

fire risk assessments shepherds court and bush court, charecroft estates off shepherds bush green, london w12 8ra fire risk assessments shepherds court and bush court, charecroft estates off shepherds bush green, london w12 8ra October 2009 Contents 1 Purpose of Report 2 Summary 3 Background 4 Legislation and Guidance

More information

Independent Living Scheme Fire Risk Assessment. Independent Living Sheltered residential accommodation

Independent Living Scheme Fire Risk Assessment. Independent Living Sheltered residential accommodation Keverne Close Wendover Drive Aspley ttingham NG8 5EF At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire

More information

HOMES FIRE RISK ASSESSMENT. Hatton House. Page 1 of 24

HOMES FIRE RISK ASSESSMENT. Hatton House. Page 1 of 24 HOMES FIRE RISK ASSESSMENT Hatton House Page 1 of 24 CONTENTS Page 1 Introduction 3-5 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 Generai Description Of Premises 9

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Science Block Hillcrest Rd, London W5 2JL 020 8997 2022 Bursar J Powell

More information

Fire risk management plan. MH/05/Revised/06/17

Fire risk management plan. MH/05/Revised/06/17 Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford

More information

Fire Risk Assessment Report

Fire Risk Assessment Report Fire Risk Assessment Report Fire Risk Assessment Report Company Site Address Contact details Date of Assessment St Augustine s Priory Clockhouse Nursery and Early ears Hillcrest Rd, London W5 2JL 020 8997

More information

Millfield Schools Fire Risk Prevention Policy

Millfield Schools Fire Risk Prevention Policy Millfield Schools Fire Risk Prevention Policy This policy refers to the Senior School, Preparatory School, Pre-Preparatory School and EYFS 1. Introduction This policy sets out the approach that the school

More information

General needs sleeping accommodation

General needs sleeping accommodation Colwick Woods Court Colwick Road Colwick, ttingham NG2 4BA At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory

More information

Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017

Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017 Fire Risk Assessment 69-77A Black Lion Lane South Hammersmith, Ravenscourt Park W6 9BG 25/07/2017 Page 1 of 23 Section 1: Details of Premises all questions on this page are compulsory LBHF Ward UPRN Name

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

Building Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof

Building Construction i. approx. age ii. building structure iii. cladding iv. floors v. walls vi. roof SECTION ONE UPRN Address 1 (block name and/or street number) Address 2 (flat numbers) Address 3 (street) Address 4 (area) Postcode Date of inspection Suggested review date Fire Risk Assessor Property Designation

More information

HOMES FIRE RISK ASSESSMENT. Stockholm House. Page 1 of 25

HOMES FIRE RISK ASSESSMENT. Stockholm House. Page 1 of 25 HOMES FIRE RISK ASSESSMENT Stockholm House Page 1 of 25 CONTENTS Page 1 Introduction 3-6 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 General Description Of Premises

More information

Management Standard: Fire Safety

Management Standard: Fire Safety OHSS: H&S Management 201 Fire Safety Management : Fire Safety 1. Legal framework This standard is produced to comply with the following legislation in respect to fire safety: 1.1. Regulatory Reform (Fire

More information

Chesterfield Borough Council

Chesterfield Borough Council Reviews December 2013 Prepared For: Town Hall Rose Hill Chesterfield S40 1LP Prepared By: Savills UK Limited 33 Margaret Street London W1G 0JD CHESTERFIELD BOROUGH COUNCIL FIRE RISK ASSESSMENT Report by:

More information

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Mandatory Fire Safety Instruction Reference A: Reference B: NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION REQUIREMENTS Approved Document B Fire Safety

More information

TOTAL FIRE SERVICES LTD

TOTAL FIRE SERVICES LTD TOTAL FIRE SERVICES LTD Fire Risk Assessment Review Conducted at: Moorcot Court Wythenshawe Manchester M23 0WQ 12 July 2018 Contents TERMS AND CONDITIONS OF BUSINESS Part 2: erences and Methodology Index

More information

Q) What should I do if the fire alarm sounds in the building? Q) What do I do if I discover a fire?

Q) What should I do if the fire alarm sounds in the building? Q) What do I do if I discover a fire? ITEM 7(a)(i) Information from Milton Keynes Council and Buckinghamshire and Milton Keynes Fire and Rescue Service Dear resident You may have questions regarding fire safety at Stephenson House, especially

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

Fire Safety, Procedures and Risk Assessment Policy

Fire Safety, Procedures and Risk Assessment Policy Fire Safety, Procedures and Risk Assessment Policy Policy Type Regulatory Last Review Summer 2017 Next Review Summer 2018 Fire Safety, Procedures and Risk Assessment Policy 1. Fire Safety Introduction

More information

Kensington Aldridge Academy, London W10

Kensington Aldridge Academy, London W10 Kensington Aldridge Academy, London W10 Fire Safety Review Job Number: 1103 June 2018 FIRE SAFETY REVIEW CONTENTS EXECUTIVE SUMMARY 1.0 INTRODUCTION 2.0 FIRE SAFETY REQUIREMENTS 3.0 EXTERNAL WALL SPECIFICATION

More information

Fire Risk Assessment 2018

Fire Risk Assessment 2018 Document Ti tle Client ame Fire Risk Assessment 2018 Wolverhampton Homes Grosvenor Court Pickering Road Wolverhampton WV11 3RD WHF FRA 050 2018 11 th April 2018 Fire Risk Assessment 2018 Project no: BU000904

More information

Fire Safety Policy Date: 0

Fire Safety Policy Date: 0 Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Document Ti tle Fire Risk Assessment 2017 Wolverhampton Homes Connaught House Upper Vauxhall Wolverhampton WV1 4ST WHF FRA 078 2017 14 th September 2017 Fire Risk Assessment 2017 Project no: BU9980iL Task

More information

ST Edmunds Scout and Guide Headquarters. Fire Risk Assessment

ST Edmunds Scout and Guide Headquarters. Fire Risk Assessment ST Edmunds Scout and Guide Headquarters Fire Risk Assessment Address: St Edmunds Church, Lidgett Park Road, Leeds, LS8 1JN Body responsible for building: St Edmunds Scout and Guide Parent Association.

More information

EAST DEAN & FRISTON VILLAGE HALL FIRE RISK ASSESSMENT

EAST DEAN & FRISTON VILLAGE HALL FIRE RISK ASSESSMENT EAST DEAN & FRISTON VILLAGE HALL FIRE RISK ASSESSMENT March 2017 Fire Risk Assessment Contents Introduction Page 2 Fire hazards Page 2 People at risk Page 3 Evaluate, remove, reduce, protect from risk

More information

Fire Safety Policy 2018/19

Fire Safety Policy 2018/19 Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all

More information

Dan Gray, Property Director. Date: November 2017 Review Due Date: November 2020

Dan Gray, Property Director. Date: November 2017 Review Due Date: November 2020 Policy title: Scope: Policy owner & job title: Approver: Fire Safety Policy Group-wide Dan Gray, Property Director Aspire Housing Board Date: November 2017 Review Due Date: November 2020 POLICY SUMMARY

More information

Fire Evacuation Policy

Fire Evacuation Policy Fire Evacuation Procedures Policy Fire Evacuation Policy Contents Page Number Introduction 2 Staff Responsibilities and Training 2 Protective Equipment Fire Extinguishers 3 Inspection Procedures/Good Housekeeping

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Document Ti tle Client Name Fire Risk Assessment 2017 Wolverhampton Homes Lathe Court Lakefield Road Wolverhampton WV11 3RB WHF FRA 020 2017 9th February 2017 Fire Risk Assessment 2016 Project no: BU89800T

More information

Fire Safety Policy. Investing in success. Dukes Centre Dukes Avenue Kingston KT2 5QY 1. Policy

Fire Safety Policy. Investing in success. Dukes Centre Dukes Avenue Kingston KT2 5QY   1. Policy Fire Safety Policy 1. Policy It is the policy of Malden Oaks to minimise the risks to students, staff and others which may arise from fire. This is achieved by ensuring precautions are taken to avoid fires

More information

Design Guidelines Fire Safety in New and Refurbished Buildings

Design Guidelines Fire Safety in New and Refurbished Buildings Design Guidelines Fire Safety in New and Refurbished Buildings Introduction All major new or refurbishment projects must comply with the Technical Standards (Scotland) Regulations as a matter of course.

More information

technical specification smoke venting systems

technical specification smoke venting systems technical specification smoke venting systems An Introduction to FDS FDS sets the standards the rest of the industry follows Providing a complete service for all of your smoke ventilation system needs.

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

BRE: Stay-put or Evacuate? Carl Sherwood BRE Fire Safety Group 22 nd July Part of the BRE Trust

BRE: Stay-put or Evacuate? Carl Sherwood BRE Fire Safety Group 22 nd July Part of the BRE Trust BRE: Stay-put or Evacuate? Carl Sherwood BRE Fire Safety Group 22 nd July 2016 Part of the BRE Trust Introduction New buildings: Building Regulations 2010 Existing buildings: Regulatory Reform (Fire Safety)

More information

Inspection & maintenance of fire doors a credible action plan. Presented by Clive Reilly Checkmate Fire Solutions Ltd

Inspection & maintenance of fire doors a credible action plan. Presented by Clive Reilly Checkmate Fire Solutions Ltd Inspection & maintenance of fire doors a credible action plan Presented by Clive Reilly Checkmate Fire Solutions Ltd Fire Doors The installation of a fire door is a complex procedure requiring a detailed

More information

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

HOMES FIRE RISK ASSESSMENT. Grafton House. Page 1 of 28

HOMES FIRE RISK ASSESSMENT. Grafton House. Page 1 of 28 HOMES FIRE RISK ASSESSMENT Grafton House Page 1 of 28 CONTENTS Page 1 Introduction 3-6 2 Premises Particulars 7 3 General Statement Of Policy 7 4 Management Systems 7 5 General Description Of Premises

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma

The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma Reference Number: This risk assessment and ALL associated documents must be retained. Date : Sept 17 The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Proforma This Fire Risk Assessment

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

Independent Living Scheme Fire Risk Assessment. General needs residential sleeping accommodation

Independent Living Scheme Fire Risk Assessment. General needs residential sleeping accommodation Sutton House 1 Forster Street Radford ttingham NG67 3DQ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire

More information

Local Rules: Fire Safety

Local Rules: Fire Safety 1. Potential Effects of a Fire A small fire is most likely to cause damage to equipment and furniture, with the potential to cause additional smoke damage to the room of origin. A large and protracted

More information

Bristol City Council Private Rented Sector Fire Safety Standards

Bristol City Council Private Rented Sector Fire Safety Standards Bristol City Council Private Rented Sector Fire Safety Standards Introduction The purpose of this document is to provide a basic guide to the fire precautions that are required in privately rented properties

More information

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires?

Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Are we using the wrong design fires for tall building fire strategies, in light of recent full height fires? Tall Building Fire Safety Network meeting & seminar FIREX, London, 22 nd June 2016 Eoin O Loughlin

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carried out on behalf of EF international School On the 30 Aug 2017 By Matt Pate Copyright FCS Live Ltd 2017 Page 1 of 30 CONTENTS 1. Risk Summary 2. Risk Assessment 01 Persons at

More information

Code of Practice for the Management of Overhead Corridor Ducts in the Main Building.

Code of Practice for the Management of Overhead Corridor Ducts in the Main Building. Issue Status: Issue No. Date Issued Comments 1. 14/08/2013 DRAFT 2. 15/08/2013 UPDATED FOLLOWING MEETING (15/08/13) 3. 19/08/2013 UPDATED TO INCORPORATE EMAIL COMMENTS (16/08/13) 4. 24/09/2013 ACCESS OF

More information

FIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018.

FIRE SAFETY POLICY. This policy document replaces any previously published documents and comes into effect September 2018. FIRE SAFETY POLICY This policy document replaces any previously published documents and comes into effect September 2018. 1.0 Fire Safety: The priority of Shrewsbury School is to minimise the risk to life

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

All Saints' & St John's Church Centre SAINT GILBERT OF SEMPRINGHAM CHURCH SCHOOL CHARITY Reg no:

All Saints' & St John's Church Centre SAINT GILBERT OF SEMPRINGHAM CHURCH SCHOOL CHARITY Reg no: 1. Introduction All Saints and St John s Centre FIRE RISK ASSESSMENT January 2018 1.1 The Regulatory Reform (Fire Safety) Order 2005, which came into force on 1st October 2006, replaces most fire safety

More information

FIRE SAFETY IN SPECIALISED HOUSING GUIDANCE. Seamus Doyle Health & Safety Manager Pembrokeshire Housing Group

FIRE SAFETY IN SPECIALISED HOUSING GUIDANCE. Seamus Doyle Health & Safety Manager Pembrokeshire Housing Group FIRE SAFETY IN SPECIALISED HOUSING GUIDANCE Seamus Doyle Health & Safety Manager Pembrokeshire Housing Group Why a new guide? Changing social care landscape (3/4 million residents) Impact of Fire Safety

More information

FIRE SAFETY POLICY in COUNCIL HOUSING FIRE SAFETY ACTION PLAN - appendix 2 v a Fire Risk Assessment are current [ FRAs ] Software Ltd have

FIRE SAFETY POLICY in COUNCIL HOUSING FIRE SAFETY ACTION PLAN - appendix 2 v a Fire Risk Assessment are current [ FRAs ] Software Ltd have Item Policy position Current position [ 31115 1 100 % of Blocks to have Fire Risk Assessments a Fire Risk Assessment are current [ FRAs within a 12 month 100% of blocks are rolling period, compliant Nulogic

More information

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT

Fire Risk Assessment Report - Initial. 23 Newhaven Court, Nantwich, CW5 5GT Fire Risk Assessment Report - Initial Prepared by Your Company Name This report took 5 SECONDS to produce & a few MINUTES to collect the data on site! Download the app for FREE at www.pocketsurvey.com

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of premises: Tel: Responsible person (e.g. employer) or person having control of the premises: Person(s) consulted: Rodwell House

More information