1 INCORPORATED 1920 UNDERWRITERS 7 LABORATORIES OF CANADA In Replying Please Refer to File CEx1348 Application No. December 17, 1999 REPORT on WETTING AGENT Pyrocool Technologies Inc. Lynchburg, Virginia Page 1 of 9 General Offices and Testing Station 7 GROUSE ROAD, SCARBOROUGH, ONTARIO, CANADA M1R 3A9 Telephone (416) Fax: Accounting (416) Engineering (416) Follow-Up Services (416) Standards: (416) Visit us at: ulcinfo@ulc.ca

2 CEx1348 Page 2 of 9 December 17, 1999 DESCRIPTION PRODUCT COVERED: Wetting Agents Pyrocool FEF, 0.4% concentrate solution. GENERAL CHARACTER AND USE: The wetting agent is a chemical compound which, when added to water at a 0.4 percent concentration reduces the solution's surface tension, increases its penetrating and spreading abilities and provides some emulsification and foam characteristics. The wetting agent, when added to water at a 0.4 percent concentration, is effective on Class A and Class B fires at a discharge rate of 8 litres/minute per square metre. It may be used in accordance with the Standard of the National Fire Protection Association for Wetting Agents, NFPANo.18. The wetting agent is suitable for use at or above 2 C. MARKING: Each container of listed wetting agent is eligible to bear a label which reads: together with the listee's name and address. Underwriters' Laboratories of Canada Listed Wetting Agent No. C PACKAGING: The wetting agent is packaged in the following: Plastic containers, 19L or 208L, manufactured by Container Corporation of America. THE INVESTIGATION The object of this investigation was to determine compliance of this product with the current requirements of Underwriters' Laboratories of Canada for this class of product as included under ULC Subject C175.

3 CEx1348 Page 3 of 9 December 17, 1999 This wetting agent has also been investigated by Underwriters Laboratories Inc., under Project No. 92NK9626, File EX4406. A review of the data obtained from the earlier investigation indicated that a further complete test program involving container and hose compatibility tests, was not necessary in order to establish a listing. The following tests were conducted at Underwriters' Laboratories of Canada on samples of the product. TEST RECORD CHEMICAL IDENTIFICATION: Qualitative Infrared Analysis - An infrared spectrum of each concentrate was obtained using an infrared spectrophotometer. ph Determination - The ph of the 0.4 percent concentration of the solution was determined using an Accument ph meter, Model 915, at a temperature of 16 C. Solubility - Throughout the storage and use temperature range, the wetting agents were observed to determine that a true solution was formed with water, which was stable at the 0.4 percent concentration. Separation Temperature - Aqueous solutions of the wetting agent at 0.4 percent concentration were observed to determine that there was no separation at any temperature between 0-49 C. Separation on Standing - The wetting agents, at the 0.4 percent concentration specified for use by the manufacturer, were tested to determine that there was no tendency to "layer out" or otherwise separate, on standing for 30 days, at temperature of 2 C, 16 C and 49 C. Action After Freezing - Aqueous solutions of the wetting agent in 0.4 percent concentration were frozen for 1 h and then warmed to 16 C. Observations for separation of the wetting agent after warming up were made. Viscosity - The viscosity of the wetting agent and of the 0.4 percent solution were determined at 16 C by use of a Brookfield Viscometer, Model RUT.

4 CEx1348 Page 4 of 9 December 17, 1999 Surface Tension - The surface tension of the wetting agent concentrates and the 0.4 % solution was determined in accordance with ASTM D1131, Method A. The measurements were taken with a Central Scientific Company Cenco DuNouy Tensiometer, at 25 C. The following results were obtained: 1. Infrared Spectrum - See Appendix A. 2. ph (0.4%). 3. Solubility - True Solution Formed. 4. Separation Temperature - No separation, 2-49 C. 5. Separation on Standing - Acceptable After 30 days. 6. Action After Freezing - No Separation or Layering. 7. Viscosity-0.4 percent-12.5 cps (average) - concentrate cps (average) 8. Surface Tension Dynes/cm Percent Solution Dynes/cm FIRE EXTINGUISHMENT: Class A Fire Tests - Crib - Th Class A extinguishing capability was confirmed from the results of fire tests in freely burning wood cribs constructed as follows: The cribs consisted of cube shaped stacks formed from nominal 38 by 38 mm spruce built upon 64 by 64 mm angle iron supported on an angle iron frame on a weighing platform at a height of 390 mm above the floor.

5 CEx1348 Page 5 of 9 December 17,1999 The wood was placed in layers, with each layer at right angles to the preceding layer and with spaces left between the wood approximately equal to the dimensions of the wood itself. A pan containing N-heptane was placed centrally beneath the crib. The arrangement and dimension of the wood used, the quantity of fuel used for ignition and the rating and classification represented are shown in the following tabulation: Number of Size & Length Arrangement Equivalent Wood Of Each Of Igniting Rating & Members Member (mm) Crib Fuel (L) Classification x38x layers of A In each test the total mass of the crib was determined and the igniting fuel added to the pan. The heptane in the pan was then ignited and the crib allowed to burn until its mass had been reduced to 55 percent of its original mass. The crib was then attacked from three sides, top and bottom, using a continuous discharge of a 19 Litre extinguisher with a 0.4 percent wetting agent solution. The fire was then left for 15 minutes and checked for re-ignition. The following results were obtained: Wetting Equivalent Test Agent Pre-Burn Fire Agent Rating and No. Concentration Min:Sec Extinguisher Discharged (kg) Classification :08 Yes A Yes A Class A Fire Test - Cotton A cylindrical basket of perforated sheet steel, 115 mm in diameter and 180 mm high, was filled with ginned cotton weighing 100 g. One-half of the sample of cotton was stuffed into the basket and a steel rod, 35 mm in diameter and 33 mm long, heated to 600 C, was then placed on the cotton basket. The other half of the cotton was then placed stuffed into the basket. 250 cc of either water or the 0.4 percent solution of the extinguishing liquid was poured onto the cotton and the runoff caught in a pan placed below the basket. Three tests with plain water and three tests with the wetting agent solution were conducted.

6 CEx1348 Page 6 of 9 December 17, 1999 Test No. Agent Type Fire Extinguished Run Off Collected No No No Yes Yes Yes Class A Fire Test - Insulating Board Insulating board squares, measuring 300 by 300 by 12.5 mm, were placed on a grid of wire. Each insulating board sample was exposed to an alcohol flame from a burning pan which was placed immediately below the sample board. The flame was exposed to the board for 1-3/4 minutes. After this time, the pan was removed. 250 cc of either water or the 0.4 percent agent solution was then sprayed on the upper surface of the insulating board using a small spray bottle. Pans were placed underneath the board to catch any runoff which occurred. The total amount of the insulation board consumed was determined by the weight loss. Three tests with plain water and three tests with the wetting agent solution were conducted. Insulating Board Run Off Test No. Agent Type Weight Loss, g Collected, ml CLASS B FIRE TEST: The Class B extinguishing potential was confirmed from the results of tests in freely burning open pans of flammable liquid.

7 CEx1348 Page 7 of 9 December 17, 1999 The pans were 300 mm deep, providing burning areas as shown in the following table. The pans contained 100 mm of water and 50 mm of N-heptane. The fuel was ignited and after a preburn period of 60 sec each fire was attacked with an extinguishing agent solution of 0.4 percent applied at a rate of 38 Litre/minute with a nozzle pressure of 300 kpa at a height of 1 metre above the pan edge and striking a backboard at the back of the pan. The following results were obtained: Extinction Equivalent Test Agent Area Fire Time Ratings & No. Concentration Of Fire (sq m) Extinguished (min:sec) Classification percent 4.65 Yes 10:30 20-B percent 4.65 Yes 8:44 20-B

8 CEx1348 Page 8 of 9 December 17, 1999 \ CONCLUSIONS CONFORMITY: On the basis of the foregoing, the design, construction and performance of the product covered by this Report are judged to be in compliance with the current requirements of Underwriters' Laboratories of Canada as included under ULC-Subj. C175. The wetting agent may be used in accordance with the requirements of the Standard of the National Fire Protection Association for Wetting Agents, NFPA 18.

9 UNDERWRITERS' LABORATORIES OF CANADA DATA SHEET T^waeo PtKlftLi&is CLIENT: '^>1^iOCOOL'lKH^JOL.oerle& J.IJC-- CLAUSE. raxaguhl DEVICE: 'P/gOCOQL. R^3 HQ^io VopfH C.oHj >JTKnrs Jc : ^ 7?3. FILE: ^fe^-f 7 PAGE Jl_o,-l- DATC: ^et- ao/'?^ TAG#:^ TCSTED BY- Q^^V^t^.

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc. December 6, 7 Jain (Americas) Inc. Ms. Sara B. Schopfer 1819 Walcutt Road Suite 1 Columbus, OH 43228 Our Reference: Subject: SV17122 / 7CA56359 Report Of Surface Burning Characteristics Tests On PVC Sheeting

More information

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010 Contents: 1. ASTM E 84 (UL 723) Flame Spread Test Report 1 2. ASTM E 84 (UL 723) Flame Spread Test Report 2 3. ASTM E 84 (UL 723) Flame Spread Test Report 3 Updated April, 2010 4. Report of Surface Burning

More information

Portable Fire Extinguishers

Portable Fire Extinguishers Portable Fire Extinguishers Workbook Activities The following activities have been designed to help you. Your instructor may require you to complete some or all of these activities as a regular part of

More information

File EX3836 Project 05CA54707 Project 06NK13655 Project 06NK29644 Project 06NK25809 Project 08CA19260 Project 07NK04786 Project 08CA42763 REPORT

File EX3836 Project 05CA54707 Project 06NK13655 Project 06NK29644 Project 06NK25809 Project 08CA19260 Project 07NK04786 Project 08CA42763 REPORT File EX3836 Project 05CA54707 Project 06NK13655 Project 06NK29644 Project 06NK25809 Project 08CA19260 Project 07NK04786 Project 08CA42763 Issued: August 3, 2006 Revised: April 29, 2009 REPORT on RESIDENTIAL

More information

PORTABLE FIRE EXTINGUISHERS. Fire Safety.

PORTABLE FIRE EXTINGUISHERS. Fire Safety. WHAT THE RATINGS MEAN: The New Zealand Standard for classifiying, rating, and performance testing of Fire Extinguishers (AS/NZ1850:1997), was introduced at the request of manufacturers, who wanted a method

More information

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing 3M Novec 1230 waterless

More information

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33 File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33 Issued: 1996-11-13 Revised: 2003-02-28 REPORT on SPRINKLERS, AUTOMATIC AND OPEN Viking

More information

A HISTORICAL REVIEW OF FLUORINATED FOAM FIREFIGHTING AGENTS, PERFORMANCE REQUIREMENTS/ ENVIRONMENTAL SAFEGUARDS REVIEW

A HISTORICAL REVIEW OF FLUORINATED FOAM FIREFIGHTING AGENTS, PERFORMANCE REQUIREMENTS/ ENVIRONMENTAL SAFEGUARDS REVIEW A HISTORICAL REVIEW OF FLUORINATED FOAM FIREFIGHTING AGENTS, PERFORMANCE REQUIREMENTS/ ENVIRONMENTAL SAFEGUARDS REVIEW CMDR (ret) John P. Farley, Naval Research Laboratory (NRL), and Joseph L. Scheffey,

More information

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss FIRE RETARDANT ARCHITECTURAL WOOD COATING ASTM E84 CLASS A FIRE SHIELD FS020 FIRE-SHIELD SEALER FS021 FIRE-SHIELD TOP COAT Available in different gloss www.duro-lak.com Easy to apply Water base sealer

More information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility

More information

Spray sprinkler system

Spray sprinkler system Protection, prevention and environmental impact of fire in a tire storage SNCP experience feedback report Spray sprinkler system Recommendations on fire protection in tyre storage facilities using spray

More information

The Science Behind Water Mist Protection of Typical Building Hazards

The Science Behind Water Mist Protection of Typical Building Hazards The Science Behind Water Mist Protection of Typical Building Hazards SUPDET 2014 Zachary Magnone, P.E. Zachary.Magnone@tycofp.com Presentation Goals What is water mist? How does it work? How is it tested

More information

Give It Gas - operates solely as an ONLINE BUSINESS Tel: (011) Cell: (082)

Give It Gas - operates solely as an ONLINE BUSINESS Tel: (011) Cell: (082) Give It Gas - operates solely as an ONLINE BUSINESS Tel: (011) 646 9439 Cell: (082) 452 4488 Email: penny@giveitgas.co.za www.giveitgas.co.za COLD FACTOR 3-WAY CAMPING FREEZERS (200V/ LP GAS/ 12V) 45 litre

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531

File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531 WWW.UL.COM 1.877.ULHELPS / (1.877.854.3577) File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531 Issued: August 4, 2004 Revised: April

More information

Intelligent Signature Series Analog Detection

Intelligent Signature Series Analog Detection Intelligent Signature Series Analog Detection With Signature Series intelligence, you re covered by the most advanced detection technology from the world leader in life safety and security innovation.

More information

EXTINGUISHMENT AND BURNBACK TESTING OF FIRE FIGHTING AGENTS

EXTINGUISHMENT AND BURNBACK TESTING OF FIRE FIGHTING AGENTS AFRL-ML-TY-TR-2005-4581 EXTINGUISHMENT AND BURNBACK TESTING OF FIRE FIGHTING AGENTS Kimberly D. Barrett Jennifer L. Kalberer Applied Research Associates, Inc. P.O. Box 40128 Tyndall AFB, FL 32403 Interim

More information

Foam Products ENGLISH

Foam Products ENGLISH Foam Products ENGLISH Tyco Fire & Building Products Foam Products Today s technological innovations bring chemical and material fire hazards. Our lines of sprinklers and alarm valves have an excellent

More information

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand.

Intelligent. Signature Series Multisensor Detection. An EDWARDS brand. Intelligent Signature Series Multisensor Detection See what s possible now. An EDWARDS brand. Photoelectric and ionization detectors see smoke, but not all fires produce it. Heat detectors spot temperature

More information

Issued: January 13, 2006 Revised: April 21, 2009 REPORT. Automatic Sprinklers. The Viking Corporation Hastings, MI

Issued: January 13, 2006 Revised: April 21, 2009 REPORT. Automatic Sprinklers. The Viking Corporation Hastings, MI File Ex643 Project 05NK21413 Project 06NK07102 Project 05NK31378 Project 06NK21906 Project 07NK02539 Project 06NK25809 Project 06NK27869 Project 07NK05434 Project 07NK05431 Project 07NK05106 Project 07NK15244

More information

Chapter 3 FF II Fire Department Communications

Chapter 3 FF II Fire Department Communications Chapter 3 FF II Fire Department Communications After completing this lesson, the student shall be able to discuss on-scene communications and postincident reports. 1. Describe the aspects that make up

More information

Report of Surface Burning Characteristics Test on Acoustical Panel

Report of Surface Burning Characteristics Test on Acoustical Panel January 02, 2013 Ideacustik Christian Morales Torres Gerente General Av. Quito 3620 y Bolivia Guayaquil, Ecuador Our Reference: Subject: R27636 / 12CA68539 Report of Surface Burning Characteristics Test

More information

2 Examination of Cladding Panels (Laboratory)

2 Examination of Cladding Panels (Laboratory) 30th November 2016 Fire and Safety Department Report To: For the attention of: Our ref: Your ref: LFB/Fire Investigation Team - Dowgate Examination of Cladding Panels Flat 28 Shepherds Court, 21 Shepherd

More information

SECURITY BLANKET Foam Fire Protection Products

SECURITY BLANKET Foam Fire Protection Products SECURITY BLANKET Foam Fire Protection Products REAL DANGERS DEMAND REAL SOLUTIONS If your business manufactures, stores, or transports flammable liquids, the thought of a devastating fire always burns

More information

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS

DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS PART 8. PORTABLE FIRE EXTINGUISHERS DEPARTMENT OF LICENSING AND REGULATORY AFFAIRS DIRECTOR S OFFICE GENERAL INDUSTRY SAFETY STANDARDS (By authority conferred on the director of the department of licensing and regulatory affairs by sections

More information

Fire Safety Checklist

Fire Safety Checklist FIRE SAFETY RISK ASSESSMENT, FIRE HAZARDS PREVENTION & PLANNING: ESSENTIAL MEASURES Fire Safety Checklist Potential causes for fire hazards Fires need three ingredients to start: a heating source, fuel

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL May 18, 2015 Mr. Simone Furiato Ebrille SRL S S Canelli 53/A Nizza Monferrato, AT 14049 Our Reference: Subject: SV29774/4786853196 Report Of Surface Burning Characteristics Tests On Samples As Submitted

More information

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN , Volume 6, Number 4, p.248-254, 04 RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN C.L. Choi Department of Building Services Engineering, The Hong Kong Polytechnic University, Hong Kong, China ABSTRACT Water

More information

Contact person Date Reference Page Alen Rakovic P (19) Fire Research

Contact person Date Reference Page Alen Rakovic P (19) Fire Research Contact person Alen Rakovic 2015-08-28 5P05551 1 (19) Fire Research +46 10 516 51 37 Alen.Rakovic@sp.se PcP. Durk Sverige AB Ruskvädersgatan 3B 418 34 Göteborg Fire Testing of fire protection gratings

More information

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33 File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33 Issued: 1996-11-13 Revised: 2003-02-28 REPORT on SPRINKLERS, AUTOMATIC AND OPEN Viking

More information

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA 1.0 INTRODUCTION This report presents the results of an investigation of the external fire resistance characteristics of the VELUX FCM Deck Mounted Skylight roof covering system in general accordance with

More information

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International January 3, 7 Mr. Danny French Contego International 334 Greyhound Pass West Carmel, IN 4632 Our Reference: Subject: R25382 / 6CA51291 Report Of Surface Burning Characteristics Tests On Fire Retardant Coating

More information

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 Telex: 23588 IMOLDN G IMO E Ref. T4/4.01 MSC/Circ.1007 26 June 2001 GUIDELINES FOR THE

More information

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E. Benefiting Government, Industry and the Public Through Innovative Science and Technology Barry L. Badders, Jr. P.E. 7 December 2011 Part 1 Non-Combustibility Test Part 3 Test for A, B,, and F Class Divisions

More information

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC Mr. Seth Wentz Tile-diy LLC 1965 International Way Hebron, KY 41048 United States Our Reference: Subject: SV17262/08CA11093 Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy

More information

Safety Policy and Procedure

Safety Policy and Procedure Safety Policy and Procedure Policy Number: 007 Authorized By: The Cianbro Companies Alan Burton Title: Watch for Fire, Smoke and Sparks Effective Date: 02/01/93 Page 1 of 5 1 Status 1.1 Update of existing

More information

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors February 2, 16 Rieke Office Interiors Mr. Todd Rieke Fox Ln. Elgin, IL 6123 Our Reference: SV3565 / 4787326412 Subject: Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By

More information

Calgary Fire Department Indoor Special Event Requirements. August calgary.ca /fire call

Calgary Fire Department Indoor Special Event Requirements. August calgary.ca /fire call Calgary Fire Department Indoor Special Event Requirements August 2011 calgary.ca /fire call 3-1-1 1 CALGARY FIRE DEPARTMENT INDOOR SPECIAL EVENTS REQUIREMENTS The purpose of this document is to provide

More information

The Loss prevention Council. Phase 1 report

The Loss prevention Council. Phase 1 report Phase 1 report Title: Investigation of the suitability of the Actual Delivered Density Apparatus (ADD) for the performance evaluation of standard sprinklers as described in Insurance Services project proposal

More information

C E R T I F I C A T E O F C O M P L I A N C E

C E R T I F I C A T E O F C O M P L I A N C E Issued to: SAFETY HI-TECH SRL VIA CAVOUR 96 67051 AVEZZANO AQ ITALY This is to certify that representative samples of CLEAN AGENT EXTINGUISHING SYSTEM UNITS See Addendum Have been investigated by UL in

More information

A. Section Includes: Fire extinguishers and cabinets including necessary accessories.

A. Section Includes: Fire extinguishers and cabinets including necessary accessories. SECTION 10522 FIRE EXTINGUISHERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Fire extinguishers and cabinets including necessary accessories. B. Related Sections: 1. 09900 - Painting 2. 10400 - Identifying

More information

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd November 29, 2010 Revised: January 10, 2013 Revised: January 18, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave Lee, Baie-D Urf QC H9X 3S3 Canada Our Reference: Subject: R26549/09CA56627 Report of Surface

More information

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: 020 7735 7611 Fax: 020 7587 3210 IMO E Ref.: T4/4.01 MSC.1/Circ.1272 4 June 2008 GUIDELINES FOR THE APPROVAL OF FIXED WATER-BASED

More information

ORDINANCE FOR TECHNICAL SPECIFICATIONS PERTAINING TO AEROSOL TYPE EXTINGUISHER APPLIANCES

ORDINANCE FOR TECHNICAL SPECIFICATIONS PERTAINING TO AEROSOL TYPE EXTINGUISHER APPLIANCES This translation is provisional translation for reference, formally refer to the original text. ORDINANCE FOR TECHNICAL SPECIFICATIONS PERTAINING TO AEROSOL TYPE EXTINGUISHER APPLIANCES (Ordinance of the

More information

ESFR sprinkler system

ESFR sprinkler system Protection, prevention and environmental impact of fire in a tire storage SNCP experience feedback report ESFR sprinkler system Recommendations on fire protection in tyre storage facilities using ESFR

More information

Teflon Rotary Drum Pump

Teflon Rotary Drum Pump Operating Instructions & Parts Manual 6005 Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and

More information

Part#: 26B113 HEAVY DUTY CAST IRON ROTARY DRUM PUMP

Part#: 26B113 HEAVY DUTY CAST IRON ROTARY DRUM PUMP Part#: 26B113 Part # 26B113 Description HEAVY DUTY CAST IRON ROTARY DRUM PUMP Operating Instructions & Parts Manual Please read and save these instructions. Read carefully before attempting to assemble,

More information

PART 1 GENERAL 1.01 SUMMARY

PART 1 GENERAL 1.01 SUMMARY Welcome to the SAFTIFIRST TM Guide Specification System prepared as an aid to specifiers in preparing written construction documents. For specification assistance with specific product applications, please

More information

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SECTION FM-200 FIRE SUPPRESSION SYSTEM SECTION 15360 FM-200 FIRE SUPPRESSION SYSTEM 1. GENERAL SPECIFICATION 1.1 A total flooding, ADS FM-200 fire suppression system with separate nitrogen storage used for a propellant shall be installed to

More information

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada

Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Standards Manager Web Standards List ULC-Underwriters Laboratories of Canada Id Number Title Year Organization Page 1 ANSI.CAN.UL. NULL 2016 ULC 64 1201 2 CAN.ULC- NULL 2016 ULC 176 60839-11-1-2016 3 CAN.ULC-IEC

More information

Foam Concentrates Test and Fire Test

Foam Concentrates Test and Fire Test This certificate replaces certificate number SNG1806023/08 issued on 03/03/2018 which is hereby cancelled. Certificate no: Page 1 of 2 SNG1806023/08/A1 Foam Concentrates Test and Fire Test Office: Singapore

More information

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES E 4 ALBERT EMBANKMENT LONDON SE1 7SR Telephone: +44 (0)20 7735 7611 Fax: +44 (0)20 7587 3210 7 December 2018 REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR

More information

STORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop

STORED PRESSURE YES TEST STANDARDS: CAN/ULC S504 & ANSI/UL 229 CAN/ULC S508 & ANSI/UL 711. Available Options: Stationary Design Tow Loop STORED PRESSURE 50, 125/150 lb. Stored Pressure These commercial stored pressure extinguishers are available in a choice of two sizes and three chemical options. The carriage design on both sizes provides

More information

Certificate of Compliance. 1.2 ITEM NUMBER AND SIZES: ml, ml, ml, ml

Certificate of Compliance. 1.2 ITEM NUMBER AND SIZES: ml, ml, ml, ml Certificate of Compliance & Material Safety Data Sheet For Health Emergencies: CALL A POISON CONTROL CENTER For Transportation Emergencies ONLY: Call Chem-Tel USA, Canada, Puerto Rico, US Virgin Islands:

More information

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008 Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,

More information

CAN/ULC-S109 Flame Resistance of "Argo" Fabric

CAN/ULC-S109 Flame Resistance of Argo Fabric CAN/ULC-S109 Flame Resistance of "Argo" Fabric A Report To: Design/Craft Fabric Corporation 2230 Ridge Drive Glenview, IL 60025 USA Phone: Email: (847) 904-7000 x128 mboynton@design-craft.com Submitted

More information

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description.

Model A Pipe Line Strainer 3, 4, 6, 8 & 10 Inch (DN80, DN100, DN150, DN200 & DN250) 175 psi (12,1 bar) General Description. Technical Services: Tel: (00) 31-9312 / Fax: (00) 91-5500 Customer Service/Sales: Tel: (1) 50-5000 / (00) 55-523 Fax: (1) 50-5010 / (00) -1295 Model A Pipe Line Strainer 3,,, & 10 Inch (DN0, DN100,, DN200

More information

CERTIFICATION BULLETIN

CERTIFICATION BULLETIN File: ULC-S527-11 ULC-G5.2 June 1, 2012 CERTIFICATION BULLETIN 2012-04 Effective Date Announcement CAN/ULC-S527-11, 3 rd Edition of the Standard for Control Unit for Fire Alarm Systems To: Subscribers

More information

Fire fighting Portable fire extinguishers Performance and constructionfire fighting Portable fire extinguishers Performance and construction

Fire fighting Portable fire extinguishers Performance and constructionfire fighting Portable fire extinguishers Performance and construction PRIVATE CIRCULATION FSH/2_14_0006 For comment/vote - Action Due Date: 2014/02/14 Annex A INTERNATIONAL STANDARD ISO 7165 Formatted: Font: 10 pt, Not Bold, (Asian) Korean Second edition 2009-03-15 Fire

More information

Port of St Helens SIA Aircraft Hanger Scappoose, OR

Port of St Helens SIA Aircraft Hanger Scappoose, OR Port of St Helens SIA Aircraft Hanger Scappoose, OR AUTOMATIC FIRE SPRINKLER SYSTEM REVISION 2 MARCH 12, 2018 Scope: Furnish and install foam and water fire protection system including underground entrance

More information

GAS CHROMATOGRAPHY PURDUE UNIVERSITY INSTRUMENT VAN PROJECT. DEMYSTIFICATION ACTIVITY FOR THE GAS CHROMATOGRAPH (Revised: ) INTRODUCTION

GAS CHROMATOGRAPHY PURDUE UNIVERSITY INSTRUMENT VAN PROJECT. DEMYSTIFICATION ACTIVITY FOR THE GAS CHROMATOGRAPH (Revised: ) INTRODUCTION INTRODUCTION DEMYSTIFICATION ACTIVITY FOR THE GAS CHROMATOGRAPH (Revised: 1-24-93) Gas chromatography (GC) is a very powerful tool for separating components of a mixture. The GC utilizes the physical and

More information

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc. August 11, 2017 Contego International Inc. Mr. Danny French PO Box 49 Rochester, IN 46975-0049 Our Reference: R25382 / 4788022828 Subject: Report Of Surface Burning Characteristics Tests On Coated Louvered

More information

SOUTHWEST RESEARCH INSTITUTE

SOUTHWEST RESEARCH INSTITUTE SOUTHWEST RESEARCH INSTITUTE 6220 CULEBRA ROAD 78238-5166 P.O. DRAWER 28510 78228-0510 SAN ANTONIO, TEXAS, USA (210) 684-5111 WWW.SWRI.ORG CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT

More information

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation

M E M O R A N D U M. NFPA Technical Committee on Water Additives for Fire Control and Vapor Mitigation National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M To: From: NFPA Technical Committee on Water Additives

More information

CAN/ULC-S109 Flame Resistance of "Xanadu" Material

CAN/ULC-S109 Flame Resistance of Xanadu Material CAN/ULC-S109 Flame Resistance of "Xanadu" Material A Report To: Design/Craft Fabric Corporation 2230 Ridge Dr. Glenview, IL 60025 USA Phone: (847) 904-7000 E-mail: mboynton@design-craft.com Attention:

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-10 44 16 (May 2015) ------------------------ Preparing Activity: NASA Superseding UFGS-10 44 16 (May 2012) UNIFIED FACILITIES GUIDE SPECIFICATIONS References are in agreement

More information

UL CERTIFICATES OF COMPLIANCE

UL CERTIFICATES OF COMPLIANCE FIREBARRIER UL CERTIFICATES OF COMPLIANCE for A/D FIREBARRIER FIRESTOPPING PRODUCTS A/D FIREBARRIER Collars A/D FIREBARRIER Inserts A/D FIREBARRIER Intumescent Caulk A/D FIREBARRIER Mineral Wool A/D FIREBARRIER

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples

More information

Tel Web: dyayan.com

Tel Web: dyayan.com 1 Our Products DYAYAN specializes in three main areas: - Manufacturing of Dry Chemical Powders - Manufacturing of Foam Concentrates - Project designing, assembly and maintenance of Fire Safety Systems.

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 EST. 1860 RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-800-913-9385 e-mail: info@fireretardantsinc.com

More information

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider. by NEENAH EnviroScape Mural pre-pasted printable wallcovering material EnviroScape Mural is a PVC free wall, window or hard surface scaping product that is pre-pasted with a water activated adhesive backing

More information

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY

UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY Fire Safety Technical Note UCL FIRE EXTINGUISHER SCALING & LOCATION POLICY Reference: BS 5306-8: code of practice for fire extinguishing installations and equipment on premises. Selection and installation

More information

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal

More information

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI

TECHNICAL MANUAL for FIRE TAPE. E-Z TAPING SYSTEM PO BOX GREEN BAY, WI TECHNICAL MANUAL for FIRE TAPE E-Z TAPING SYSTEM PO BOX 10887 GREEN BAY, WI 54307 800-721-8273 http://www.e-ztape.com Table of Contents Product Description...3 Fire Tape Manufacturer...3 Fire Tape Listed

More information

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE TERM highly protected risk (HPR) is commonly used in

More information

Certificate of Compliance

Certificate of Compliance Page 1 of 5 Certificate of Compliance & Material Safety Data Sheet For Health Emergencies: CALL A POISON CONTROL CENTER For Transportation Emergencies ONLY: Call Chem-Tel USA, Canada, Puerto Rico, US Virgin

More information

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS Jukka Vaari 1, Amit Lior 2 1 2 VTT Technical Research Centre of Finland, Espoo, Finland Marioff Corporation Oy, Vantaa,

More information

Wet Chemical Fire Extinguishing System for Extreme Low-Temperature Vehicle Applications

Wet Chemical Fire Extinguishing System for Extreme Low-Temperature Vehicle Applications Wet Chemical Fire Extinguishing System for Extreme Low-Temperature Vehicle Applications Stephanie Thomas, Chad Powell, and Brian Stumm Kidde Fenwal 400 Main St., Ashland, MA 01721 508.881.2000 stephanie.thomas@fs.utc.com,

More information

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate PERFORMANCE TEST REPORT Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate Report No: C7626.1-16-31 Report Date: 5/8/13 Test Record Retention Date: 5/8/17 PERFORMANCE TEST REPORT

More information

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO MSC 84/24/Add.2 RESOLUTION MSC.265(84) OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO THE MARITIME SAFETY COMMITTEE, RECALLING Article 28(b) of the Convention on the International Maritime Organization

More information

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED DG TM DualGuard 2000 Fluoropolymer Barrier FRP Duct C U L LISTED US Fluoropolymer Barrier FRP Duct Composites USA A Critical Process Systems Group Company Worried about meeting Insurance Underwriter and

More information

Foam Systems U.S. Quick Reference Guide

Foam Systems U.S. Quick Reference Guide Foam Systems U.S. Quick Reference Guide This guide is intended for general reference only. Prior to the design, layout, and/or installation of any sprinkler system, please refer to Viking s technical documentation

More information

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd October 05, 2011 Eco-Sol Ltd Mr. Paul Allcock Cardiff House Cardiff Rd Barry, Vale of Glamorgan, CF63 2AW Great Britain Our Reference: Subject: R27181/11CA40094 Report of Surface Burning Characteristics

More information

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE 2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of

More information

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design

Building Description Applicable Codes & Standards Prescriptive Requirements. Performance Based Design June 15, 2017 Building Description Applicable Codes & Standards Prescriptive Requirements Structural Fire Protection Fire Sprinkler Fire Alarm Means of Egress Performance Based Design 2 3 Semiconductor

More information

Test Tube Rack. Test Tube

Test Tube Rack. Test Tube Equipment Cards Test Tube A test tube is a tube-shaped piece of glassware or plastic used for holding substances during experiments. Micro test tubes are smaller test tubes that reduce waste and expense.

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd. May 22, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave. Lee Baie-D urf, QX 3S3 Canada Our Reference: Subject: R26549/13CA21763 Report Of Surface Burning Characteristics Tests On Samples As Submitted By

More information

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND 1. GENERAL SPECIFICATION 1.1 A pre-engineered, fixed pipe, automatic dry chemical fire suppression system shall be provided and installed for the hazard including work area, plenums and all exhaust ventilation

More information

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement First Revision No. 1-NFPA 259-2016 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D5865, Standard Test Method

More information

Aerosol Type Fire Extinguisher Aerosol Type Fire Extinguisher

Aerosol Type Fire Extinguisher Aerosol Type Fire Extinguisher IAN SCS Co., Ltd. Indispensability of Fire Extinguisher In case of fire in your house or working place, we usually call 911 but it takes at least 5 to 10 minutes for a fire engine to arrive in the accident

More information

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor www.astm.org ASTM D1230 Flammability of Apparel Textiles Scope: This test method covers the evaluation of the flammability

More information

Certificate of Compliance Section 1 - PRODUCT AND COMPANY IDENTIFICATION

Certificate of Compliance Section 1 - PRODUCT AND COMPANY IDENTIFICATION Certificate of Compliance & Material Safety Data Sheet For Health Emergencies: CALL A POISON CONTROL CENTER For Transportation Emergencies ONLY: Call Chem-Tel USA, Canada, Puerto Rico, US Virgin Islands:

More information

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798 July 22, 2009 Stewart Audio Inc Brian Mccormick Po Box 4058 Mountain View, CA 94040 Our Reference: Subject: File SV17764 / Project 09CA34798 UL Standard 2043, Third Edition "Fire for Heat and Visible Smoke

More information

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input Public Input No. 2-NFPA 259-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM D 5865, Standard Test Method

More information

School Fire Safety. A Guide for Educators. saskatchewan.ca

School Fire Safety. A Guide for Educators. saskatchewan.ca School Fire Safety A Guide for Educators saskatchewan.ca Table of Contents Fire happens when a source of heat and a material that will burn come together. The amount of flammable and combustible material

More information

U.S. Coast Guard Research and Development Center 1082 Shennecossett Road, Groton, CT

U.S. Coast Guard Research and Development Center 1082 Shennecossett Road, Groton, CT U.S. Coast Guard Research and Development Center 182 Shennecossett Road, Groton, CT 634-648 Report No. CG-D-7-4 AN EVALUATION OF TOTAL FLOODING HIGH EXPANSION FOAM FIRE SUPPRESSION SYSTEMS FOR MACHINERY

More information

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW & e. INDUSTRIAL LOSS CONTROL & eng Analisi e Controllo dei Rischi Industriali HUGHES ASSOCIATES EUROPE, srl FIRE SCIENCE & ENGINEERING BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT

More information