FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss
|
|
- Ursula Haynes
- 5 years ago
- Views:
Transcription
1 FIRE RETARDANT ARCHITECTURAL WOOD COATING ASTM E84 CLASS A FIRE SHIELD FS020 FIRE-SHIELD SEALER FS021 FIRE-SHIELD TOP COAT Available in different gloss Easy to apply Water base sealer Solvent base top coat Fire retardant system Fast drying Excellent mar & scratch resistance Good chemical resistance ASTM E84 Class A duro-lak inc 3020 Le Corbusier, Laval, Quebec,Canada, H7L-3W2 Phone: (450) Fax: (450) Stacey Court, Mississauga, Ontario, Canada, L4W-2X7 Phone: (905) Fax: (905)
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24 1325 North 108th East Avenue Tulsa, OK ph fx. CLIENT: DURO-LAK INC Le Corbusier Laval, Quebec, H7L-3W2 Test Report No: TJ Date: August 23, 2016 SAMPLE ID: SAMPLING DETAIL: The client identified the following test material as FS020 + FS021 ON DOUGLA FIR Test samples were submitted to the laboratory directly by the client. No special sampling conditions or sample preparation were observed by QAI. DATE OF RECEIPT: Samples were received at QAI facilities on July 23, 2016 TESTING PERIOD: August 19, 2016 AUTHORIZATION: TEST REQUESTED: Signed work order 16GR07062 Perform standard flame spread and smoke density developed classification tests on the sample supplied by the Client in accordance with ASTM Designation E84-16, "Standard Method of Test for Surface Burning Characteristics of Building Materials". The foregoing test procedure is comparable to UL 723, ANSI/NFPA No. 255, and UBC No TEST RESULTS: Flame Spread Smoke Developed CLASSIFICATION: The material resulted in a class A. Detailed test results are presented in the subsequent pages of this report. Prepared By Signed for and on behalf of QAI Laboratories, Inc. Jeff Foster Fire Test Technician J. Brian McDonald Operations Manager Page 1 of 4 THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. info@qai.org
25 Duro-Lak Inc. Report No.: TJ August 23, 2016 Page 2 of 5 PREPARATION AND CONDITIONING: The sample was submitted in three 8 foot long panels measuring 18 inches wide and approximately 1 thick. The sample material was placed into conditioning at 73ºF (±5ºF) and 50% (±5%) relative humidity until day of testing. E 84 TEST DATA SHEET: MOUNTING METHOD: The sample was supported during testing by ½ round metal rods placed at 2 intervals across the width of the test chamber, with cement board place between the sample and tunnel lid. CLIENT: Duro-Lak Inc. DATE: August 23, 2016 SAMPLE: FS020 + FS021 on Douglas Fir IGNITION: 0 minutes, 20 seconds FLAME FRONT: 2 feet maximum TIME TO MAXIMUM SPREAD: 10 minutes, 00 seconds TEST DURATION: 10 minutes, 00 seconds SUMMARY: FLAME SPREAD: 5 (3.8 unrounded) SMOKE DEVELOPED: 140 (139 unrounded) OBSERVATIONS: Bubbling was seen at 9 seconds, at 16 seconds charring was seen. Sustained ignition was at 20 seconds and falling could be seen at 1 minute 50 seconds. Flame spread was slow and only reached 2 feet at 10 minutes with very light smoke. At the conclusion of the ten minute test there was no after burn noted. CALIBRATION DATA: Time to Ignition of Last Red Oak (sec): 34 Red Oak Smoke Area (%A*Min): Total Fuel Burned (ft³) 55.0 THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. info@qai.org
26 Duro-Lak Inc. Report No.: TJ August 23, 2016 Page 3 of 5 SUMMARY OF ASTM E84 RESULTS: Because of the possible variations in reproducibility, the results are adjusted to the nearest figure divisible by 5. Smoke Density values over 200 are rounded to the nearest figure divisible by 50. In order to obtain the Flame Spread Classification, the above results should be compared to the following table: NFPA CLASS IBC CLASS FLAME SPREAD SMOKE DEVELOPED A A 0 through 25 Less than or equal to 450 B B 26 through 75 Less than or equal to 450 C C 76 through 200 Less than or equal to 450 BUILDING CODES CITED: 1. National Fire Protection Association, ANSI/NFPA No. 101, "Life Safety Code", 2006 Edition. 2. International Building Code, 2006 Edition, Chapter 8, Interior Finishes, Section 803. THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. info@qai.org
27 Duro-Lak Inc. Report No.: TJ August 23, 2016 Page 4 of 5 THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. info@qai.org
28 Duro-Lak Inc. Report No.: TJ August 23, 2016 Page 5 of 5 PHOTOS: AFTER TEST IMAGES ***END OF TEST REPORT*** THIS REPORT IS THE CONFIDENTIAL PROPERTY OF THE CLIENT ADDRESSED. THE REPORT MAY ONLY BE REPRODUCED IN FULL. PUBLICATION OF EXTRACTS FROM THIS REPORT IS NOT PERMITTED WITHOUT WRITTEN APPROVAL FROM QAI. ANY LIABILITY ATTACHED THERETO IS LIMITED TO THE FEE CHARGED FOR THE INDIVIDUAL PROJECT FILE REFERENCED. THE RESULTS OF THIS REPORT PERTAIN ONLY TO THE SPECIFIC SAMPLE(S) EVALUATED. info@qai.org
The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 21 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-8-913-9385 e-mail: info@fireretardantsinc.com
More informationREPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:
Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112
More informationReport Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International
January 3, 7 Mr. Danny French Contego International 334 Greyhound Pass West Carmel, IN 4632 Our Reference: Subject: R25382 / 6CA51291 Report Of Surface Burning Characteristics Tests On Fire Retardant Coating
More informationTEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1
REPORT NUMBER: 101145164COQ-005 ORIGINAL ISSUE DATE: April 25, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO udecor Inc.
More informationRENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3
REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries
More informationRetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
EST. 1860 RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-800-913-9385 e-mail: info@fireretardantsinc.com
More informationTEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota
Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard
More informationRENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy
REPORT NUMBER: 100900037COQ-002 ORIGINAL ISSUE DATE: October 10, 2012 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, BC V3K 7C1 RENDERED TO Laminam S.P.A.
More informationRENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5
REPORT NUMBER: 3189147COQ-002 ORIGINAL ISSUE DATE: September 30, 2009 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Radial Engineering
More informationReport Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.
August 11, 2017 Contego International Inc. Mr. Danny French PO Box 49 Rochester, IN 46975-0049 Our Reference: R25382 / 4788022828 Subject: Report Of Surface Burning Characteristics Tests On Coated Louvered
More informationSIGMADEK, LTD. FIRE TEST REPORT
SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION
More informationTest Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6
Art3d LLC Test Report No. AJFS1809009217FF Date: OCT.17, 2018 Page 1 of 6 1600 N State Route 291 Unit 250, Sugar Creek, Missouri 64058 USA 中国认可国际互认检测 TESTING CNAS L4743 The following sample(s) was / were
More informationPRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona
Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device
More informationFABRITRAK SYSTEMS, INC. FIRE TEST REPORT
FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES
More informationTEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria
TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:
More informationWe Identify and S.T.O.P. Your Noise Problems
ASTM E-84 TESTING FOR MANUFACTURER, RENDERED TO: Acoustical Surfaces Inc. 123 Columbia Court North, Suite 201 Chaska, MN 55318 Noise S.T.O.P. Fabrisorb Acoustical Wall Panels TESTED: OCTOBER 3, 2002 October
More informationFUNDERMAX GMBH FIRE TEST REPORT
FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT
More informationReport Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors
February 2, 16 Rieke Office Interiors Mr. Todd Rieke Fox Ln. Elgin, IL 6123 Our Reference: SV3565 / 4787326412 Subject: Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By
More informationReport Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.
December 6, 7 Jain (Americas) Inc. Ms. Sara B. Schopfer 1819 Walcutt Road Suite 1 Columbus, OH 43228 Our Reference: Subject: SV17122 / 7CA56359 Report Of Surface Burning Characteristics Tests On PVC Sheeting
More informationTech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5
INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol
More informationTest Report No. AJD Date: JUN.09, 2013 Page 1 of 6
Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)
More informationFire Performance of Translucent Systems
Fire Performance of Translucent Systems ASTM E-108 Burning Brand Test on Quadwall Class A Approved Light Transmitting Plastics Fire Test Performance Meets Building Code Requirements: Self-Ignition ASTM
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D
November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples
More informationPERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome
PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.
May 22, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave. Lee Baie-D urf, QX 3S3 Canada Our Reference: Subject: R26549/13CA21763 Report Of Surface Burning Characteristics Tests On Samples As Submitted By
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC
Mr. Seth Wentz Tile-diy LLC 1965 International Way Hebron, KY 41048 United States Our Reference: Subject: SV17262/08CA11093 Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy
More informationBURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL
BURNING BRAND PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR 022 0000 (Acrylic Dome) VELUX SUN TUNNEL ACCESSORY PRODUCTS: Tubular Skylight with ZTA 022 000090 9" Turrets
More informationJuly 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798
July 22, 2009 Stewart Audio Inc Brian Mccormick Po Box 4058 Mountain View, CA 94040 Our Reference: Subject: File SV17764 / Project 09CA34798 UL Standard 2043, Third Edition "Fire for Heat and Visible Smoke
More informationReport of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd
October 05, 2011 Eco-Sol Ltd Mr. Paul Allcock Cardiff House Cardiff Rd Barry, Vale of Glamorgan, CF63 2AW Great Britain Our Reference: Subject: R27181/11CA40094 Report of Surface Burning Characteristics
More informationContents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010
Contents: 1. ASTM E 84 (UL 723) Flame Spread Test Report 1 2. ASTM E 84 (UL 723) Flame Spread Test Report 2 3. ASTM E 84 (UL 723) Flame Spread Test Report 3 Updated April, 2010 4. Report of Surface Burning
More informationASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS
ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS SPANK 9901101 REPORT NO. 75157 Septemer 11, 00 Prepared For: Pollack 150 Varick Street New York, NY 10013 F-316-A 555 76TH STREET S.W., GRAND RAPIDS.
More informationPERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product
PERFORMANCE TEST REPORT Rendered to: EVERBLOCK SYSTEMS, LLC PRODUCT: Modular Block Product Report No.: G1320.01-106-31 Report Date: 08/04/16 Test Record Retention Date: 07/29/20 130 Derry Court York, PA
More informationAcoustical Surfaces, Inc.
S.T.O.P. February 21, 2013 Our Reference: Subject: SV19452/13CA09185 Report Of Surface Burning Characteristics Tests On Samples This is a Report summarizing the results of a test conducted under the Commercial
More informationReport Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL
May 18, 2015 Mr. Simone Furiato Ebrille SRL S S Canelli 53/A Nizza Monferrato, AT 14049 Our Reference: Subject: SV29774/4786853196 Report Of Surface Burning Characteristics Tests On Samples As Submitted
More informationTEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source
NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source TEST REPORT Kolay 5mm 20mil Wear Layer LVT with Fiberglass Core Project
More informationReport of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd
November 29, 2010 Revised: January 10, 2013 Revised: January 18, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave Lee, Baie-D Urf QC H9X 3S3 Canada Our Reference: Subject: R26549/09CA56627 Report of Surface
More informationCAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"
ELECTRONIC DRAFT COPY CAN/ULC-S12.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate" A Report To: Polygal Plastics Industries, Ltd. Ramat Hashofet 19238 Israel Phone: 972-4-9596271 Email:
More informationEnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.
by NEENAH EnviroScape Mural pre-pasted printable wallcovering material EnviroScape Mural is a PVC free wall, window or hard surface scaping product that is pre-pasted with a water activated adhesive backing
More informationReport of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)
February, 11 Revised February 28, 11 Jotun UAE Ltd (LLC) Mr. Richard Mann Al Quozind District Dubai, 3671 UAE Our Reference: Subject: SV18666/11CA24 Report of Surface Burning Characteristics Tests on Samples
More informationMaterials Testing by Gregory Havel
Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics
More informationTEST REPORT DATE: TEST NUMBER: DESCRIPTION OF TEST SAMPLE
Professional Testing Laboratory, Inc. TEST REPORT DATE: 06-16-2014 TEST NUMBER: 0209182 CLIENT Artistry Hardwood Flooring TEST METHOD CONDUCTED IDENTIFICATION CONSTRUCTION REFERENCE ASTM E648 Standard
More informationSizes. Colors. Features
LAUNDRY ACCESSORIES 10 28 13 Construction Solutions, LLC 1. Product Name DBX1000 Dryer Vent Boxes with Snap-On Trim Rings 2. Manufacturer Construction Solutions, LLC 7801 E. Gray Rd. Suite 110-120 Scottsdale,
More informationResearch-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly
Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal
More informationREPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015
REPORT NUMBER: 101960325MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 TEST REPORT
More informationPERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate
PERFORMANCE TEST REPORT Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate Report No: C7626.1-16-31 Report Date: 5/8/13 Test Record Retention Date: 5/8/17 PERFORMANCE TEST REPORT
More informationReport of Surface Burning Characteristics Test on Acoustical Panel
January 02, 2013 Ideacustik Christian Morales Torres Gerente General Av. Quito 3620 y Bolivia Guayaquil, Ecuador Our Reference: Subject: R27636 / 12CA68539 Report of Surface Burning Characteristics Test
More informationPublic Comment No. 2-NFPA [ Section No ]
Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard
More informationASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet
UNCONTROLLED ELECTRONIC COPY ASTM D 635-14 Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet A Report To: Brett Martin Ltd. 24 Roughfort Road Mallusk, Co. Antrim United
More informationCAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum
UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum A Report To: DiZal inc. 12 rue Bouvier, Suite 4 Québec, QC G2K K9 Phone:
More informationCAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"
UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "ezobord 9 mm (Green)" A Report To: ivekter Inc. 1625 Drew Rd. Mississauga, Ontario L5S 1J5 Phone: 416-665-3571 Attention: E-mail:
More informationCAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"
ELECTRONIC DRAFT COPY CAN/ULC-S12 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel" A Report To: ABET Corporation 5 Paxman Road, Unit 1 Toronto, Ontario M9C 1B7
More informationPERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio
PERFORMANCE TEST REPORT Report No.: F6398.01-121-24 Test Date: March 9 th & 10th, 2016 Rendered to: Metal Building Manufacturers Association Cleveland, Ohio ASSEMBLIES: Metal Roof Panels and Clay Roof
More informationRetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
EST. 1860 RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-800-913-9385 e-mail: info@fireretardantsinc.com
More informationBCTC CARPET TECHNICAL CENTRE
Wira House West Park Ring Road Leeds, LS16 6QL Tel: +44 (0)113 259 1999 Fax: +44 (0)113 278 0306 Web: http://www.bttg.co.uk/bctc Email: CSLeeds@bttg.co.uk 7 September 2010 Page 1 of 7 Client: Rectory Farm
More informationGUARDIAN FIRE TESTING LABORATORIES, INC.
GUARDIAN FIRE TESTING LABORATORIES INC. Testing & Listing Field Labeling Page 1 of 5 Engineering & Product Certification Services Factory Inspections Guardian Fire Testing Laboratories, Inc. Phone: 716
More informationUL 94 Flammability Ratings: Introduction
UL 94 Flammability Ratings: Introduction UL intends this standard to serve as a preliminary indication of a plastics acceptability for use as part of a device or appliance with respect to its flammability.
More informationTRANSLUCENT FIRE RATED SYSTEMS
28662 N. Ballard Drive Lake Forest, IL 60045 PHONE (800) 759-6985 FAX (847) 816-0425 TRANSLUCENT FIRE RATED SYSTEMS Committed to Fire Safety QUADWALL CLASS A IS SHOWN IN ACTUAL ASTM E-108 TESTS. ASTM E-108
More informationUL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information
UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility
More informationTechnical Training International Textiles Training September 2018 Ellen Roaldi Instructor
Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor www.astm.org ASTM D1230 Flammability of Apparel Textiles Scope: This test method covers the evaluation of the flammability
More informationForbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.
Return address: P.O. box 337, 7500 AH Enschede, TNO Centre for Textile Research Ariënsplein 3 7511 JX ENSCHEDE Forbo Flooring Attn. Mr. A. Tijhof Postbus 13 1560 AA Krommenie Report Sponsor : Contractor,
More informationTitle: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report
More informationASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"
UNCONTROLLED ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB" A Report To: Ciucevich 7200 Vermilion Ct. Wake Forest, NC 27587 USA Phone: (919) 570-291 E-mail:
More informationJ. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441
J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite
More informationFire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY
Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE
More informationPublic Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] Statement of Problem and Substantiation for Public Input. Related Public Inputs for This Document
1 of 19 10/21/2015 1:20 PM Public Input No. 1-NFPA 99B-2015 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three ASME International, Two
More informationASTM E 662 Rate of Smoke Generation of OXIFREE TM198"
ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" A Report To: Oxifree Global LLC 22955 State Highway 249, Suite 6 Tomball, TX 77375 USA Phone: (281) 251-7171 E-mail: ed.hall@oxifree.com
More informationBS EN ISO : 2010
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2010 Fire Tests For Determination
More informationFirst Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes
First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except
More informationSecond Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement
Second Revision No. 1-NFPA 90A-2016 [ Section No. 2.3.2 ] 2.3.2 ASTM International Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM C411, Standard
More informationAddendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017
Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor
More informationAustralian Standard. Methods for fire tests on building materials, components and structures
AS 1530.3 1989 Australian Standard Methods for fire tests on building materials, components and structures Part 3: Simultaneous determination of ignitability, flame propagation, heat release and smoke
More informationThe Cannabis Industry: Fire Department Requirements
The Cannabis Industry: Fire Department Requirements RVFD Standard 4.1 Rio Vista Fire Department 350 Main St. Rio Vista, CA. 94571 By: Jeff Armstrong, Fire Chief Updated December 2018 1 The purpose of this
More informationPERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws
PERFORMANCE EVALUATION TEST REPORT Rendered to: GREENFIELD MANUFACTURING COMPANY PRODUCT: Hanger Screws Report No: Report Date: 01/12/11 Expiration Date: 12/28/14 Product: Hanger Screws PERFORMANCE EVALUATION
More informationBS EN : 2001 & IEC :2000
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000
More informationIMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:
IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249 Page 2 of 13 Bodycote warringtonfire
More informationChange all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
1 of 9 10/21/2015 1:22 PM First Revision No. 3-NFPA 99B-2015 [ Global Input ] Change all instances of "flame resistant (hypobaric)" to "Limited-Combustible (material)" in all instances in the document.
More informationFIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD
FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD Revised 1/1/17 The Fire Department has a vested interest to ensure the fire and life safety of all events and activities within the city. The
More informationReport on Public Input June 2014 NFPA 101
101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and
More informationUNDERWRITERS 7 LABORATORIES OF CANADA
INCORPORATED 1920 UNDERWRITERS 7 LABORATORIES OF CANADA In Replying Please Refer to File CEx1348 Application No. December 17, 1999 REPORT on WETTING AGENT Pyrocool Technologies Inc. Lynchburg, Virginia
More informationF, T, L and W Ratings - What are the Code & Testing Requirements?
F, T, L and W Ratings - What are the Code & Testing Requirements? Rich Walke Underwriters Laboratories Inc. April 27, 2010 Copyright 1995-2007 Underwriters Laboratories Inc. All rights reserved. No portion
More informationBS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com BS EN ISO 92391: 2002 Fire Tests For
More informationM E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)
National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169 7471 Phone: 617 770 3000 Fax: 617 770 0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Furnishings
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More information1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c
1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire
More informationFirst Revision No. 6-NFPA [ Section No. 2.2 ]
Page 1 of 18 First Revision No. 6-NFPA 555-2014 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 12, Standard on Carbon
More informationRE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES
Limassol 20 th August, 2015 RE: USE OF FIREPRO IN POTENTIALLY EXPLOSIVE ATMOSPHERES This document is intended to provide clarification on the use of FirePro Condensed Aerosol Generators in Potential Explosive
More informationIEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IEC 60331-11-21 Method of test defined in
More informationReview Fire Test Report
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review Fire Test Report Determination of
More informationRequirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011
1.0 GENERAL: Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011 1.1 PURPOSE -The intent of this guideline is to provide the requirements for the protection
More informationPublic Comment No. 1-NFPA [ Section No ]
Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard
More informationRiverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)
Riverside County Fire Department Office of the Fire Marshal 2300 Market St., Ste. 150, Riverside, CA 92501 Ph. (951) 955-4777 Fax (951) 955-4886 Technical Policy Title: Plant Processing and Extraction
More informationIMO Resolution MSC 61(67): Annex 1: Part 2
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 61(67): Annex 1: Part
More informationFirst Revision No. 2-NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of 11 1/18/2016 5:43 PM
1 of 11 1/18/2016 5:43 PM First Revision No. 2-NFPA 51-2015 [ Global Input ] Throughout standard remove references to the following and replace with the following: (1) CGA C-7 Guide to Precautionary Labelling
More informationIntertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008
Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,
More informationFirst Revision No. 7-NFPA [ Global Input ] Submitter Information Verification. Committee Statement
of 29 6/9/2016 1:42 PM First Revision No. 7-NFPA 289-2016 [ Global Input ] Add comman between "reconstruction or research" throughout the document as follows: "reconstruction, or research" Submittal Date:
More informationSGS-CSTC Standards Technical Services (Shanghai) Co., Ltd. FCC MPE REPORT
No. 588 West Jindu Road, Songjiang District, Shanghai, China Telephone: +86 (0) 21 61915666 Fax: +86 (0) 21 61915678 ee.shanghai@sgs.com Page 1 of 8 1 Cover Page Application No.: Applicant: FCC MPE REPORT
More informationEVALUATION SUBJECT: DIVISION: HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: HYDRONIC PIPING.
ICC-ES Report Reissued 08/2016 This report is subject to renewal 08/2017 EVALUATION SUBJECT: UNIPIPE PEX-AL-PEX DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION: 23 21 13 HYDRONIC
More informationFire Department HEADQUARTERS Cathedral Oaks Road Santa Barbara, CA (805) FAX: (805) CODE SUMMARY
Fire Department HEADQUARTERS 4410 Cathedral Oaks Road Santa Barbara, CA 93110-1042 (805) 681-5500 FAX: (805) 681-5563 Michael W. Dyer Fire Chief County Fire Warden Eric Peterson Deputy Fire Chief CODE
More informationFIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES
FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES Report number FSP 1360 CSIRO job number SP3241 Date of issue 31 JULY 2009 Client SNAP FIRE SYSTEMS PTY LTD. Commercial-in-confidence
More informationFIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS
FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS Report number FSP 1290A CSIRO job number LP46ASP3085 Date of issue 30 NOVEMBER 2007 Client EFFICIENCY MATRIX PTY LTD and YOUNGEN
More information