PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

Size: px
Start display at page:

Download "PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate"

Transcription

1 PERFORMANCE TEST REPORT Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate Report No: C Report Date: 5/8/13 Test Record Retention Date: 5/8/17

2 PERFORMANCE TEST REPORT Rendered to: PALRAM AMERICAS, INC Commerce Circle Arcadia West Industrial Park Kutztown, Pennsylvania 1953 Report No: C Test Date: 4/3/13 Report Date: 5/8/13 Test Record Retention Date: 5/8/17 Product: Clear Palsun Type: Polycarbonate Project Summary: Architectural Testing, Inc. was contracted by Palram Americas, Inc. to evaluate the smoke density of their Clear Palsun polycarbonate. The product description, test procedures and test results are reported herein. The average results obtained from testing are shown in the following table. Clear Palsun Smoke Density Average.118" Thickness " Thickness 66.3 Test Method: The test specimens were evaluated in conformance with ASTM D , Standard Test Method for Density of Smoke from the Burning or Decomposition of Plastics. Note that there was one deviation to the method: Palram specified the thicknesses of the test specimens to be nominally.118" and.5" instead of the specified 1/4" thickness. Product Description: The Clear Palsun polycarbonate was submitted to Architectural Testing by Palram Americas and consisted of the following: ten nominal 1" x 1" x.118" pieces and ten nominal 1" x 1" x.5" pieces. Each piece had a UV coating on one 1" x 1" side. The material was tested as-received with the exception of removing the protective film from both sides prior to testing.

3 Architectural Testing C Page 2 of 4 Test Procedure and Test Results: Testing procedure and the results obtained from testing are reported as follows. All conditioning of test specimens and test conditions were at standard laboratory conditions. ASTM D Smoke Density A test specimen was exposed to a flame inside a Smoke Chamber (ICN 4388). The horizontal light absorption was measured across the light beam path of a photoelectric cell, and the condition of the smoke chamber was observed. The test specimen was tested with the UV coated side towards the flame. The Light Absorption Curves are presented in Appendix A. Caveat: This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions. Test Specimen Smoke Density - Clear Palsun Polycarbonate -.118" Thickness Maximum Smoke Density (%) Smoke Density Rating Average Smoke Density Rating: 61.8 Note: During the first smoke density test, the letters on the exit sign were visible and readable through the smoke. During the second and third smoke density tests, the letters on the exit sign were visible and readable through the smoke, but became unreadable for about one minute. The test specimens melted, flamed, charred, dripped to the pan below and extinguished during the test. Test Specimen Smoke Density - Clear Palsun Polycarbonate -.5" Thickness Maximum Smoke Density (%) Smoke Density Rating Average Smoke Density Rating: 66.3 Note: During all smoke density tests, the letters on the exit sign became obscured. The test specimens melted, flamed, charred and dripped to the pan below. Test specimens two and three extinguished near the end of the test.

4 Architectural Testing C Page 3 of 4 Architectural Testing will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Architectural Testing, Inc. for the entire test record retention period. Results obtained are tested values and were secured using the designated test methods. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimens tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC.: Dawn M Chaney - Senior Technician Components / Materials Testing Gary Hartman, P.E. - Director Components / Materials Testing DMC:dmc/nlh Attachments (pages) This report is complete only when all attachments listed are included. Appendix A - Smoke Density Light Absorption Curves (8)

5 Architectural Testing C Page 4 of 4 Revision Log Rev. # Date Page(s) Revision(s) 5/8/13 N/A Original report issue. This report produced from controlled document template ATI 331, issued 7/1/8.

6 Architectural Testing C APPENDIX A Smoke Density Light Absorption Curves

7 : ATI No.: C Technician: DMC/KAG % Light (min:sec) : Palram Americas Clear Palsun -.118" Polycarbonate : : : : : : : : : : : : : : : : : : : : : Calibration Resistance (kw) 3: % Light : : Curve for Sample 1 (min:sec) Maximum Smoke Density % Smoke Density Rating* 6.3 ATI427(c) Date Issued: 1//1

8 : ATI No.: C Technician: DMC/KAG % Light (min:sec) : Palram Americas Clear Palsun -.118" Polycarbonate : : : : : : : : : : : : : : : : : : : : : : % Light : : Curve for Sample 2 (min:sec) Calibration Resistance (kw) 24 Maximum Smoke Density 9.21 % Smoke Density Rating* 67.2 ATI427(d) Date Issued: 1//1

9 : ATI No.: C Technician: DMC/KAG % Light (min:sec) : Palram Americas Clear Palsun -.118" Polycarbonate : : : : : : : : : : : : : : : : : : : : : Calibration Resistance (kw) 3: % Light : : Curve for Sample 3 (min:sec) Maximum Smoke Density 85.9 % Smoke Density Rating* 58. ATI427(e) Date Issued: 1//1

10 : ATI No.: C Technician: DMC/KAG Average (min:sec) :.6 AVERAGE Palram Americas Clear Palsun -.118" Polycarbonate.993 :5 :15 :25 :35 : : : : :25 1:35 1: : : :15 2:25 2: : : :5 73. (min:sec) 3:15 3: Calibration Resistance (kw) 3:35 3: % Light : Average Curve Maximum Smoke Density % Smoke Density Rating* Average 61.8 ATI427(f) Date Issued: 1//1

11 : ATI No.: C Technician: DMCKAG % Light (min:sec) : Palram Americas Clear Palsun -.5" Polycarbonate : : : : : : : : : : : : : : : : : : : : : : % Light : : Curve for Sample 1 (min:sec) Calibration Resistance (kw) 24 Maximum Smoke Density % Smoke Density Rating* 64.6 ATI427(c) Date Issued: 1//1

12 : ATI No.: C Technician: DMCKAG % Light (min:sec) : Palram Americas Clear Palsun -.5" Polycarbonate : : : : : : : : : : : : : : : : : : : : : Calibration Resistance (kw) 3: % Light : : Curve for Sample 2 (min:sec) Maximum Smoke Density % 15.5 Smoke Density Rating* 62.7 ATI427(d) Date Issued: 1//1

13 : ATI No.: C Technician: DMCKAG % Light (min:sec) : Palram Americas Clear Palsun -.5" Polycarbonate : : : : : : : : : : : : : : : : : : : : : : % Light : : Curve for Sample 3 (min:sec) Calibration Resistance (kw) 24 Maximum Smoke Density % Smoke Density Rating* 71.6 ATI427(e) Date Issued: 1//1

14 : ATI No.: C Technician: DMCKAG Average (min:sec) : -.15 AVERAGE Palram Americas Clear Palsun -.5" Polycarbonate :5 :15 :25 :35 : : : : :25 1:35 1:45 1: : :15 2:25 2: : :55 3:5 3:15 3: Calibration Resistance (kw) 3: % Light :45 3: Average Curve (min:sec) Maximum Smoke Density Smoke Density Rating* Average 95.9 % 66.3 ATI427(f) Date Issued: 1//1

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product PERFORMANCE TEST REPORT Rendered to: EVERBLOCK SYSTEMS, LLC PRODUCT: Modular Block Product Report No.: G1320.01-106-31 Report Date: 08/04/16 Test Record Retention Date: 07/29/20 130 Derry Court York, PA

More information

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard

More information

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device

More information

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws PERFORMANCE EVALUATION TEST REPORT Rendered to: GREENFIELD MANUFACTURING COMPANY PRODUCT: Hanger Screws Report No: Report Date: 01/12/11 Expiration Date: 12/28/14 Product: Hanger Screws PERFORMANCE EVALUATION

More information

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:

More information

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL BURNING BRAND PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR 022 0000 (Acrylic Dome) VELUX SUN TUNNEL ACCESSORY PRODUCTS: Tubular Skylight with ZTA 022 000090 9" Turrets

More information

FUNDERMAX GMBH FIRE TEST REPORT

FUNDERMAX GMBH FIRE TEST REPORT FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT

More information

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio PERFORMANCE TEST REPORT Report No.: F6398.01-121-24 Test Date: March 9 th & 10th, 2016 Rendered to: Metal Building Manufacturers Association Cleveland, Ohio ASSEMBLIES: Metal Roof Panels and Clay Roof

More information

SIGMADEK, LTD. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION

More information

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES

More information

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC.

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC. PERFORMANCE TEST REPORT Rendered to: SOLATUBE INTERNATIONAL, INC. Report No.: Test Date: 06/11/08 Report Date: 07/15/08 Record Retention End Date: 06/11/12 2524 E. Jensen Ave Fresno, CA 93706 phone: 559-233-8705

More information

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008 Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,

More information

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL May 18, 2015 Mr. Simone Furiato Ebrille SRL S S Canelli 53/A Nizza Monferrato, AT 14049 Our Reference: Subject: SV29774/4786853196 Report Of Surface Burning Characteristics Tests On Samples As Submitted

More information

We Identify and S.T.O.P. Your Noise Problems

We Identify and S.T.O.P. Your Noise Problems ASTM E-84 TESTING FOR MANUFACTURER, RENDERED TO: Acoustical Surfaces Inc. 123 Columbia Court North, Suite 201 Chaska, MN 55318 Noise S.T.O.P. Fabrisorb Acoustical Wall Panels TESTED: OCTOBER 3, 2002 October

More information

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors February 2, 16 Rieke Office Interiors Mr. Todd Rieke Fox Ln. Elgin, IL 6123 Our Reference: SV3565 / 4787326412 Subject: Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By

More information

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1 REPORT NUMBER: 101145164COQ-005 ORIGINAL ISSUE DATE: April 25, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO udecor Inc.

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd. May 22, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave. Lee Baie-D urf, QX 3S3 Canada Our Reference: Subject: R26549/13CA21763 Report Of Surface Burning Characteristics Tests On Samples As Submitted By

More information

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy REPORT NUMBER: 100900037COQ-002 ORIGINAL ISSUE DATE: October 10, 2012 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, BC V3K 7C1 RENDERED TO Laminam S.P.A.

More information

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc. August 11, 2017 Contego International Inc. Mr. Danny French PO Box 49 Rochester, IN 46975-0049 Our Reference: R25382 / 4788022828 Subject: Report Of Surface Burning Characteristics Tests On Coated Louvered

More information

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3 REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries

More information

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd October 05, 2011 Eco-Sol Ltd Mr. Paul Allcock Cardiff House Cardiff Rd Barry, Vale of Glamorgan, CF63 2AW Great Britain Our Reference: Subject: R27181/11CA40094 Report of Surface Burning Characteristics

More information

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5 REPORT NUMBER: 3189147COQ-002 ORIGINAL ISSUE DATE: September 30, 2009 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Radial Engineering

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples

More information

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd November 29, 2010 Revised: January 10, 2013 Revised: January 18, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave Lee, Baie-D Urf QC H9X 3S3 Canada Our Reference: Subject: R26549/09CA56627 Report of Surface

More information

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC) February, 11 Revised February 28, 11 Jotun UAE Ltd (LLC) Mr. Richard Mann Al Quozind District Dubai, 3671 UAE Our Reference: Subject: SV18666/11CA24 Report of Surface Burning Characteristics Tests on Samples

More information

Acoustical Surfaces, Inc.

Acoustical Surfaces, Inc. S.T.O.P. February 21, 2013 Our Reference: Subject: SV19452/13CA09185 Report Of Surface Burning Characteristics Tests On Samples This is a Report summarizing the results of a test conducted under the Commercial

More information

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

ASTM E 662 Rate of Smoke Generation of Moniflex as manufactured by Isoflex AB UNCONTROLLED ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB" A Report To: Ciucevich 7200 Vermilion Ct. Wake Forest, NC 27587 USA Phone: (919) 570-291 E-mail:

More information

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc. December 6, 7 Jain (Americas) Inc. Ms. Sara B. Schopfer 1819 Walcutt Road Suite 1 Columbus, OH 43228 Our Reference: Subject: SV17122 / 7CA56359 Report Of Surface Burning Characteristics Tests On PVC Sheeting

More information

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198 ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" A Report To: Oxifree Global LLC 22955 State Highway 249, Suite 6 Tomball, TX 77375 USA Phone: (281) 251-7171 E-mail: ed.hall@oxifree.com

More information

Report of Surface Burning Characteristics Test on Acoustical Panel

Report of Surface Burning Characteristics Test on Acoustical Panel January 02, 2013 Ideacustik Christian Morales Torres Gerente General Av. Quito 3620 y Bolivia Guayaquil, Ecuador Our Reference: Subject: R27636 / 12CA68539 Report of Surface Burning Characteristics Test

More information

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source TEST REPORT Kolay 5mm 20mil Wear Layer LVT with Fiberglass Core Project

More information

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010 Contents: 1. ASTM E 84 (UL 723) Flame Spread Test Report 1 2. ASTM E 84 (UL 723) Flame Spread Test Report 2 3. ASTM E 84 (UL 723) Flame Spread Test Report 3 Updated April, 2010 4. Report of Surface Burning

More information

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA 1.0 INTRODUCTION This report presents the results of an investigation of the external fire resistance characteristics of the VELUX FCM Deck Mounted Skylight roof covering system in general accordance with

More information

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International January 3, 7 Mr. Danny French Contego International 334 Greyhound Pass West Carmel, IN 4632 Our Reference: Subject: R25382 / 6CA51291 Report Of Surface Burning Characteristics Tests On Fire Retardant Coating

More information

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6 Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)

More information

AMC/IEM SUBPART B. AC A, Section 7 is applicable when showing compliance with JAR 26.50(c).]

AMC/IEM SUBPART B. AC A, Section 7 is applicable when showing compliance with JAR 26.50(c).] SECTION 2 Subpart B JAR-26 [ACJ 26.50(c) Cabin crew seat location with respect to injury risk See JAR 26.50(c) AMC/IEM SUBPART B AC 25.785-1A, Section 7 is applicable when showing compliance with JAR 26.50(c).]

More information

CAN/ULC-S109 Flame Resistance of "Argo" Fabric

CAN/ULC-S109 Flame Resistance of Argo Fabric CAN/ULC-S109 Flame Resistance of "Argo" Fabric A Report To: Design/Craft Fabric Corporation 2230 Ridge Drive Glenview, IL 60025 USA Phone: Email: (847) 904-7000 x128 mboynton@design-craft.com Submitted

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC Mr. Seth Wentz Tile-diy LLC 1965 International Way Hebron, KY 41048 United States Our Reference: Subject: SV17262/08CA11093 Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy

More information

Heat and Smoke Release of a Ceiling-Installed Speaker

Heat and Smoke Release of a Ceiling-Installed Speaker WFCi Project #12051 Heat and Smoke Release of a Ceiling-Installed Speaker Indicative testing conducted in accordance with the test methodology described in UL 2043, Fire test for heat and visible smoke

More information

CAN/ULC-S109 Flame Resistance of "Xanadu" Material

CAN/ULC-S109 Flame Resistance of Xanadu Material CAN/ULC-S109 Flame Resistance of "Xanadu" Material A Report To: Design/Craft Fabric Corporation 2230 Ridge Dr. Glenview, IL 60025 USA Phone: (847) 904-7000 E-mail: mboynton@design-craft.com Attention:

More information

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss FIRE RETARDANT ARCHITECTURAL WOOD COATING ASTM E84 CLASS A FIRE SHIELD FS020 FIRE-SHIELD SEALER FS021 FIRE-SHIELD TOP COAT Available in different gloss www.duro-lak.com Easy to apply Water base sealer

More information

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process 2010 IMO FTP Code Revisions Parts 2, 5, 7, 8, 9 & 10 Presented by: Juan Manuel Flores, P.E. Date:

More information

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E 108-07a Rendered to: Trinity ERD Columbia, SC WFCi Project # 10135 & 11159 Testing Completed on: April

More information

NF X : Parts 1, 2, 3, 4 & 5

NF X : Parts 1, 2, 3, 4 & 5 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com NF X 10-702: Parts 1, 2, 3, 4 & 5 Fire test

More information

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

ASTM D Horizontal Burning Rate Determination of Marlon FS 1.5mm Clear Polycarbonate Sheet UNCONTROLLED ELECTRONIC COPY ASTM D 635-14 Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet A Report To: Brett Martin Ltd. 24 Roughfort Road Mallusk, Co. Antrim United

More information

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 EST. 1860 RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-800-913-9385 e-mail: info@fireretardantsinc.com

More information

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009 ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC #100-3191-1 TESTED: MARCH 27, 2009 April 2, 2009 Client: Attention: Cole Motorsports/CM Racing Products

More information

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

CAN/ULC-S102 Surface Burning Characteristics of ezobord 9 mm (Green) UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "ezobord 9 mm (Green)" A Report To: ivekter Inc. 1625 Drew Rd. Mississauga, Ontario L5S 1J5 Phone: 416-665-3571 Attention: E-mail:

More information

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13 Test Report No. AJHG1501000530FB Date: FEB.17, 2015 Page 1 of 13 ZHEJIANG TERASUN AIR DUCT CO., LTD MAREN VILLAGE, CHONGREN INDUSTRIAL ZONE, CHONGREN TOWN, SHENGZHOU CITY, ZHEJIANG PROVINCE, CHINA The

More information

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 21 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-8-913-9385 e-mail: info@fireretardantsinc.com

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility

More information

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50. Classification of reaction to fire performance in accordance with BS EN 13501-1: 2007 +A1: 2009 on Sandwich Panel, WP 50 Prepared for: Sandwich Panel Factory Jeddah Saudi Arabia 13 July 2011 0578 Page

More information

Test Report: ICL/H18/9039 Rev 1

Test Report: ICL/H18/9039 Rev 1 Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk

More information

Classification of Fire Performance of Wall and Ceiling Lining Materials

Classification of Fire Performance of Wall and Ceiling Lining Materials Classification of Fire Performance of Wall and Ceiling Lining Materials Using the Method of Kokkala, Thomas and Karlsson Reference: Kokkala, M.A. Thomas, P.H. and Karlsson, B. Rate of Heat Release and

More information

Flammability Test Results

Flammability Test Results Kmlex Aviation Inc. 265 Diab, Ville St-Laurent, Quebec, Canada, H4S 1E7 Tel: 514-626-1254, Fax: 514-784-131 Flammability Test Results FAR 25.853 / AWM 525.853 (a) Appendix F Part I, (a) 1, (i) 6 second

More information

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests

More information

BS EN : 2001 & IEC :2000

BS EN : 2001 & IEC :2000 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 60695-2-11: 2001 & IEC 60695-2-11:2000

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 REPORT 58 COMMERCENTRE DRIVE, LAKE FOREST, CA 963 Project No. G67677 Date: June 6, 4 REPORT NO. 67677LAX- TEST OF ONE FULL ON AT 9 BEAM ANGLE MODEL NO. RAZOR Q ZOOM RENDERED TO ELATION PROFESSIONAL 6 S.

More information

SOUTHWEST RESEARCH INSTITUTE

SOUTHWEST RESEARCH INSTITUTE SOUTHWEST RESEARCH INSTITUTE 6220 CULEBRA ROAD 78238-5166 P.O. DRAWER 28510 78228-0510 SAN ANTONIO, TEXAS, USA (210) 684-5111 WWW.SWRI.ORG CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part

More information

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441 Response-Time Comparisons of Ionization and Photoelectric/Heat Detectors 1. Introduction Despite

More information

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877. Return address: P.O. box 337, 7500 AH Enschede, TNO Centre for Textile Research Ariënsplein 3 7511 JX ENSCHEDE Forbo Flooring Attn. Mr. A. Tijhof Postbus 13 1560 AA Krommenie Report Sponsor : Contractor,

More information

BCTC CARPET TECHNICAL CENTRE

BCTC CARPET TECHNICAL CENTRE Wira House West Park Ring Road Leeds, LS16 6QL Tel: +44 (0)113 259 1999 Fax: +44 (0)113 278 0306 Web: http://www.bttg.co.uk/bctc Email: CSLeeds@bttg.co.uk 7 September 2010 Page 1 of 7 Client: Rectory Farm

More information

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 REPORT NUMBER: 101960325MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 TEST REPORT

More information

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

CAN/ULC-S102 Surface Burning Characteristics of 8 mm Fire Rated High Pressure Laminate Phenolic Panel ELECTRONIC DRAFT COPY CAN/ULC-S12 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel" A Report To: ABET Corporation 5 Paxman Road, Unit 1 Toronto, Ontario M9C 1B7

More information

IMO Resolution MSC 61(67): Annex 1: Part 2

IMO Resolution MSC 61(67): Annex 1: Part 2 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com IMO Resolution MSC 61(67): Annex 1: Part

More information

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY White Paper BACKGROUND: Safety is paramount in the home appliance industry. Due to the possibility of human mis-application, over-current, or short circuit

More information

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for: Classification of reaction to fire performance in accordance with EN 13501-1: 2007 +A1: 2009 on Superfoil SFNC Prepared for: Boulder Developments Ltd Black Horse Farm Main Street Norwell Nottinghamshire

More information

Flame Retardant Polyethylene Tubing

Flame Retardant Polyethylene Tubing Flame Retardant Polyethylene Tubing Classified Under U.L. 1820. Performance Pipe DRISCOPLEX 2600 Instube Flame Retardant (FR) Polyethylene Tubing For Pneumatic Instrument Controls PERFORMANCE PIPE is the

More information

Pneumatic Tubing POLYTUBING O.D. 5/32"

Pneumatic Tubing POLYTUBING O.D. 5/32 Pneumatic Tubing POLYTUBING O.D. 5/32" 1/4" 3/8" 1/2" PART NR COLOR COIL LENGTH MASTER PACK MASTER PACK WT. 1063636 TWIN TUBE 500' 1000' 16# 1063635 BLACK 500' 2000' 17# 1063641 BLUE 500' 2000' 17# 1063765

More information

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

CAN/ULC-S102.2 Surface Burning Characteristics of 16 mm Multiwall Polycarbonate ELECTRONIC DRAFT COPY CAN/ULC-S12.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate" A Report To: Polygal Plastics Industries, Ltd. Ramat Hashofet 19238 Israel Phone: 972-4-9596271 Email:

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

CAN/ULC-S102 Surface Burning Characteristics of Digitally Printed Aluminum Siding Coated Aluminum UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum A Report To: DiZal inc. 12 rue Bouvier, Suite 4 Québec, QC G2K K9 Phone:

More information

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal

More information

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor: IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2 Smoke & Toxicity Test WF Report Number: 166040 Date: 13 th August 2007 Test Sponsor: Fiba Tech Industries Ltd. 0249 Page 2 of 13 Bodycote warringtonfire

More information

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider. by NEENAH EnviroScape Mural pre-pasted printable wallcovering material EnviroScape Mural is a PVC free wall, window or hard surface scaping product that is pre-pasted with a water activated adhesive backing

More information

Materials Testing by Gregory Havel

Materials Testing by Gregory Havel Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics

More information

UL 94 Flammability Ratings: Introduction

UL 94 Flammability Ratings: Introduction UL 94 Flammability Ratings: Introduction UL intends this standard to serve as a preliminary indication of a plastics acceptability for use as part of a device or appliance with respect to its flammability.

More information

SOP SF SOP for LN2 Freezers

SOP SF SOP for LN2 Freezers Page 2 of 9 4. SCOPE 4.1. The SOP applies to personnel operating and maintaining the liquid nitrogen freezers owned or contracted for storage in the SSF. This SOP is applicable to all vapor phase and liquid

More information

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670.

Australian Standard. Fire detection, warning, control and intercom systems System design, installation and commissioning. Part 1: Fire AS 1670. AS 1670.1 2004 (Incorporating Amendment No. 1) AS 1670.1 2004 Australian Standard Fire detection, warning, control and intercom systems System design, installation and commissioning Part 1: Fire This Australian

More information

Review Fire Test Report

Review Fire Test Report Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Review Fire Test Report Determination of

More information

ISO 2685 INTERNATIONAL STANDARD. Aircraft Environmental test procedure for airborne equipment Resistance to fire in designated fire zones

ISO 2685 INTERNATIONAL STANDARD. Aircraft Environmental test procedure for airborne equipment Resistance to fire in designated fire zones INTERNATIONAL STANDARD ISO 2685 Second edition 1998-12-15 Aircraft Environmental test procedure for airborne equipment Resistance to fire in designated fire zones Aéronefs Méthode d'essai en environnement

More information

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798 July 22, 2009 Stewart Audio Inc Brian Mccormick Po Box 4058 Mountain View, CA 94040 Our Reference: Subject: File SV17764 / Project 09CA34798 UL Standard 2043, Third Edition "Fire for Heat and Visible Smoke

More information

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy BS 476: Part 7: 1997 on K-Flex IN Clad Foil Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, 36 20877 RONCELLO (MB) Italy 30 th October 2012 0578 Page 1 of 6 Prepared on behalf of BRE Global

More information

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1 Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com BS EN 13823: 2010 Reaction to Fire Tests

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center Eloma Genius T6-11 Gas Combination Oven Test Report FSTC Report # 501311112-R0 Application of ASTM Standard Test Method F2861-10 August 2012 Prepared by: Michael Karsz Denis

More information

Public Comment No. 1-NFPA [ Section No ]

Public Comment No. 1-NFPA [ Section No ] Page 1 of 7 Public Comment No. 1-NFPA 556-2014 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA, 19428-2959. ASTM D2859, Standard

More information

TEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Phone: (800) Fax: (800)

TEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Phone: (800) Fax: (800) TEST REPORT ON CENTRAL STATES MANUFACTURING, INC. S CENTRAL-SNAP PANELS (24 GA., 1.75" HIGH, 16" WIDE PANEL) AT 5' 0" 3' 9" PANEL SPANS IN ACCORDANCE WITH ASTM E1646-95(2011) & E1680-11 TESTED FOR: Central

More information

Department for Communities and Local Government Research Report:

Department for Communities and Local Government Research Report: Department for Communities and Local Government Research Report: BD 2890 Investigation of real fires - Electrical consumer unit fire experiments 293761 (E3V2) CPD/04/102/027 Prepared for: Brian Martin

More information

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6 Art3d LLC Test Report No. AJFS1809009217FF Date: OCT.17, 2018 Page 1 of 6 1600 N State Route 291 Unit 250, Sugar Creek, Missouri 64058 USA 中国认可国际互认检测 TESTING CNAS L4743 The following sample(s) was / were

More information

Hot Food Holding Cabinets Test for FWE HLC

Hot Food Holding Cabinets Test for FWE HLC Design & Engineering Services Hot Food Holding Cabinets Test for Report Prepared by: Design & Engineering Services Customer Service Business Unit Southern California Edison January 4, 2011 Acknowledgements

More information

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage RESEARCH TECHNICAL REPORT SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale

More information

PERFORMANCE REPORT. ARL Lab Number: Client: In-O-Vate Technologies Inc. 810 Saturn St. Jupiter, FL 33477

PERFORMANCE REPORT. ARL Lab Number: Client: In-O-Vate Technologies Inc. 810 Saturn St. Jupiter, FL 33477 PERFORMANCE REPORT ARL Lab Number: 50175 Client: In-O-Vate Technologies Inc. 810 Saturn St. Jupiter, FL 33477 Test Method: Miami-Dade County Protocol TAS 114, Appendix E (1995) Product: Dryer Vent L/N

More information

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630

REPORT COMMERCENTRE DRIVE, LAKE FOREST, CA 92630 REPORT 58 COMMERCENTRE DRIVE, LAKE FOREST, CA 963 Project No. G119188 Date: March 13, REPORT NO. 119188LAX-4 TEST OF ONE LED WASH MODEL NO. COLOUR CHORUS 4 RENDERED TO ELATION PROFESSIONAL 61 S. EASTERN

More information

NEBOSH International Technical Certificate in Oil and Gas Operational Safety

NEBOSH International Technical Certificate in Oil and Gas Operational Safety IOG1 - Element 4 - Fire protection and emergency response July 2012 NEBOSH International Technical Certificate in Oil and Gas Operational Safety Licence details RMS Publishing Victoria House, Lower High

More information

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation

More information

Electric radiator test

Electric radiator test Electric radiator test Final Report 56161/1 Carried out for Cornwall Heating Solutions Ltd & Bright Heating By Calum Maclean 27 June 2012 Electric radiator test Carried out for: Cornwall Heating Solutions

More information