PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

Size: px
Start display at page:

Download "PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio"

Transcription

1 PERFORMANCE TEST REPORT Report No.: F Test Date: March 9 th & 10th, 2016 Rendered to: Metal Building Manufacturers Association Cleveland, Ohio ASSEMBLIES: Metal Roof Panels and Clay Roof Tiles with Type 1 Photovoltaic Module TEST METHOD: Fire Test Program Developed by MBMA Task Group Using UL 1703 Section 31 & ASTM E108 Procedures with Alternate Roof Covering Materials This report contains in its entirety: Cover Page: 1 page Report Body: 11 pages Photographs: 8 pages

2 Page 1 of Report Issued To: Metal Building Manufacturers Association 1300 Sumner Avenue Cleveland, Ohio Test Laboratory: Architectural Testing, Inc., an Intertek company ( Intertek-ATI ) York, Pennsylvania Project Summary: 3.1 Introduction: These fire testing standards aim to measure relative fire characteristics of roof coverings with photovoltaic modules and panels mounted above or on the roof covering under simulated fire scenarios which originate outside the building. Under controlled laboratory conditions, the behavioral response of materials, products or assemblies as affected by heat and flame are described. The performances of the roof covering systems are described only under specific conditions. Information is not provided by these tests that are applicable to any scenarios other than the specific conditions experienced during testing. Information is not provided by these tests that are applicable to actual fire situations because of the inherent differences between the classes as it pertains to fire source and fire application; no comparison between the classes exist. Results from tests are applicable to the specifics of the test and the aspect in which the tests were conducted, and are not applicable to similar materials or the results of those materials when used in concert with other materials. 3.2 Roof Assemblies: Metal Roof Panels and Clay Roof Tiles with Type 1 Photovoltaic Module 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimens tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. 3.4 Test Dates: March 9 th & 10 th, Test Sample Source: The roof assembly components used in testing were supplied by various members of the UL Non-Combustible Roof Group of the Metal Building Manufacturers Association. Members included S-5!, SolarCity, SunEdison, and Intertek-ATI.

3 Page 2 of Project Summary: (continued) 3.6 Test Method: 4.0 Test Details: UL , Standard for Safety Flat-Plate Photovoltaic Modules and Panels Section 31 Fire Tests with alternate roof coverings ASTM E108-07a / UL , Standard Methods for Fire Tests of Roof Class A and Class B procedures for Calibration, Spread of Flame, and Burning Brand 4.1 Specimen Description: Class A test decks for the Spread of Flame and Burning Brand tests were constructed of 2x4 lumber and 15/32 inch Type AC grade plywood with face and back veneers of Douglas Fir and finished with the components outlined below: 4.2 Spread of Flame: Baseline Tests Test Deck 40 inches wide by 8 feet long. Underlayment 15 lb. asphalt felt paper attached directly to the test deck with 5/16 in. staples on nominal 12 inch centers. Each layer overlapped the next layer by 2 inches. Roof Covering Class A three tab shingles were attached with 1-1/4 inch roofing nails Metal Panel Tests Test Deck 40 inches wide by 8 feet long. Underlayment One layer of GAF VersaShield was attached directly to the test deck with 5/16 inch staples on nominal 12 inch center spacing. Each layer overlapped the next layer by two inches. 30 lb. asphalt felt paper was installed directly above the VersaShield. Each layer of felt paper used a two inch overlap. Roof Covering Back section of deck comprised of steel 29 gauge galvalume metal roofing panels attached with #12 by 1 inch long metal roofing screws spaced 8 inches applied to the deck. Panels were installed directly under a Type 1 PV module. PV module measured 65 inches high by 39 inches wide by 2 inches thick. Module was mounted to the deck using S-5! hardware creating a 5 inch space between roof covering surface and bottom of the module. Front section of deck exposed to the flame plume was comprised of asphalt shingles and 15 lb. felt underlayment roof system (described in Section and specified in UL 1703) to create a fire scenario at the metal roof panel and PV module interface.

4 Page 3 of Test Details: Clay Tile Tests Test Deck 40 inches wide by 8 feet long. Underlayment 30 lb. asphalt felt paper was attached directly to the test deck with 5/16 in. staples on nominal 12 inch centers. Each layer overlapped the next layer by 2 inches. Clay Roof Tiles Two types of tiles were utilized in the test program: flat and barrel shaped. Back section of deck comprised of the clay roof tiles with a 3 in. head lap between courses and were installed with 1-1/4 in. roof nails. Tiles were installed directly under a Type 1 PV module. PV module measured 65 inches high by 39 inches wide by 2 inches thick. Module was mounted to the deck using SunEdison hardware creating a 5 inch space between roof covering surface and bottom of the module. Front section of deck exposed to the flame plume was comprised of asphalt shingles and 15 lb. felt underlayment roof system (described in Section and specified in UL 1703) to create a fire scenario at the metal roof panel and PV module interface. 4.3 Burning Brand: Test Deck 40 inches wide by 52 inches long with a 1/8 inch full length 40 inch horizontal joint at 22-1/2 inches and a 1/8 inch partial 22-1/2 inch vertical joint centered at 20 inches and located on the far side of the deck during exposure. Underlayment One layer of GAF VersaShield was attached directly to the test deck with 5/16 inch staples on nominal 12 inch center spacing. Each layer overlapped the next layer by two inches. 30 lb. asphalt felt paper was installed directly above the VersaShield. Each layer of felt paper used a two inch overlap. Metal Roof Panels Steel 29 gauge galvalume metal roofing panels attached with #12 by 1 inch long metal roofing screws spaced 8 inches applied to the deck. Panels were installed directly under a Type 1 PV module. PV module measured 65 inches high by 39 inches wide by 2 inches thick. Module was mounted to the deck using S-5! hardware creating a 5 inch space between roof covering surface and bottom of the module. Clay Roof Tiles Two types of tiles were utilized in the test program: flat and barrel shaped. Clay roof tiles with a 3 in. head lap between courses and were installed with 1-1/4 in. roof nails. Tiles were installed directly under a Type 1 PV module. PV module measured 65 inches high by 39 inches wide by 2 inches thick. Module was mounted to the deck using SunEdison hardware creating a 5 inch space between roof covering surface and bottom of the module. 4.4 Storage Information: Decks were stored in the fire laboratory prior to testing. Typical laboratory conditions are F and 40-65% relative humidity.

5 Page 4 of Test Details: (continued) 4.5 Moisture Content: Moisture content of the lumber and plywood were verified prior to testing. Plywood was less than 8% and the lumber was within 8-10%. 4.6 Equipment Calibration: A Fire Test Apparatus as described in ASTM E108 was used to generate 12 ± 0.5 mph air current and flame temperature of 1400 ±50 F. Air speed and flame temperature of the Fire Test Apparatus were calibrated prior to testing. A gas burner with flame temperature of 1630 ±50 F was used to ignite the brands for testing. See Section 5.1 for more information on equipment calibration. 4.7 Spread of Flame Procedure: After calibration of equipment, a test specimen described in Section was placed into the steel framed holder for testing at a 5:12 slope and refractory mortar applied at the leading edge of the deck. The fire test apparatus was turned on and the specimen was subjected to continuous flame and air current for duration of 10 minutes. This procedure was repeated for both test decks and observations were documented. 4.8 Burning Brand Procedure: Brands were oven conditioned at 105 to 120 F for a minimum of 24 hours prior to testing. Class A brands consisted of three layers of twelve 1 inch by 1 inch by 12 inch strips of Douglas Fir forming a grid of 12 inch square by 2-1/4 inch thick and weight verified to be within 2000 ±150 grams. The brand was ignited by exposing each 12 inch by 12 inch face for 30 seconds, each 2-1/4 inch by 12 inch face for 45 seconds, and the 12 inch by 12 inch faces again for 30 seconds into the gas burner. Total duration of ignition exposure was 5 minutes. Class B test brands consisted of a grid 6 inches square and approximately inches thick made of dry Douglas Fir lumber free of knots and pitch pockets. Use 18 nominal 1 by 1 by 6 inch strips, dressed on all four faces to 3 4 by 3 4 inches, and placed in three layers of six strips each with strips spaced 1 4 inch. The brands weight was verified to be within grams at the time of test. The brand was ignited by exposing each 6 by 6-inch face for 30 seconds, each by 6-inch face for 30 seconds, and each 6 by 6-inch face again for 30 seconds. After the brands were ignited, they were placed onto the test specimen described in Section of the E108 and Section of the UL 1703 at a 5:12 slope and secured in place with No. 18 soft iron wire. Class A brand were positioned with its upper edge 25.5 inches from the leading edge of the test deck and centered laterally with respect to the vertical joint in the test deck. The brand is to be placed so that the strips in both the upper and lower layers are parallel to the direction of air flow. Class B brand were positioned with its upper edge 24 inches from the leading edge of the test deck and centered laterally with respect to the vertical joint in the test deck. Brands were placed so that the strips in both the upper and lower layers are parallel to the direction of air flow. The testing apparatus without flame but only air current was turned on and the specimen was tested for 90 minutes or until the brand was completely consumed and the exposed and underside surfaces of the test deck did not exhibited signs of combustion. This procedure was repeated for all test decks and observations were documented.

6 Page 5 of Test Details: (continued) 4.9 List of Official Observers: Name Samuel Truthseeker Vincent Sagan Ryan Devine Dustin Haddock Scott Gingrich Ben Green Robert George Company SunEdison Metal Building Manufacturers Association SolarCity S-5! Attachment Solutions Intertek-ATI Intertek-ATI Intertek-ATI 5.0 Calibration: 5.1 Calibration Information: Date: Average Wind Speed: 12.5 mph Ambient Temperature: 64 F Average Flame temperature: 1392 F Date: Average Wind Speed: 11.8 mph Ambient Temperature: 61 F Average Flame temperature: 1395 F Date: Average Wind Speed: 11.9 mph Ambient Temperature: 67 F Average Flame temperature: 1395 F

7 Page 6 of Calibration: (continued) Base line Spread of Flame tests Test Flame Spread Deck #1 Deck #2 Deck #3 Average PV Offset Distance 46 inches 47 inches 48 inches 47 inches 35 inches 6.0 : Spread of Flame with Metal Roof Covering Specimen #1 00:01 Flame On Test Starts. 2:24 Ignition Ignition of the asphalt shingles. 3:57 1 foot Flame spread reaches 1 foot. 4:44 2 foot Flame spread reaches 2 feet. 6:07 3 foot Flame spread reaches 3 feet. 10:00 End End of test After Test No sustained surface flaming was observed passes 3 feet; PASS Spread of Flame with Metal Roof Covering Specimen #2 00:01 Flame On Test Starts. 1:37 Ignition Ignition of the asphalt shingles. 1:53 1 foot Flame spread reaches 1 foot. 3:04 2 foot Flame spread reaches 2 feet. 6:07 3 foot Flame spread reaches 3 feet. 10:00 End End of test After Test No sustained surface flaming was observed passes 3 feet; PASS

8 Page 7 of : (continued) Class A Burning Brand with Metal Roof Covering Specimen #3 00:01 Brand Placed Start of test. 2:04 Burn through Ignition on the underside of the PV module. 3:31 Smoke Smoke emits from the underside of deck at horizontal saw kerf. 6:15 Glass Breaks Brand burns thru PV module breaks glass and falls on roof deck. Brand 20:57 Brand is fully consumed. Consumed 29:00 End of Test End of test no signs of combustion. After Test No ignition of the product or underlayment was observed; PASS Class A Burning Brand with Metal Roof Covering Specimen #4 00:01 Brand Placed Start of test. 2:15 Burn through Ignition on the underside of the PV module. 4:12 Smoke Smoke emits from the underside of deck at horizontal saw kerf. 5:50 Glass Breaks Brand burns thru PV module breaks glass and falls on roof deck. 20:30 End of Test End of test no signs of combustion. After Test No ignition of the product or underlayment was observed; PASS. Class B Burning Brand with Metal Roof Covering Specimen #5 00:01 Brand Placed Start of test. 00:51 Smoke Smoke emits from the saw kerfs joint on underside of the deck. 17:04 Brand Brand consumed. 45:00 End Test No smoke or evidence of combustion - end test. After Test No sustained flaming on the underside of the deck was observed; PASS.

9 Page 8 of : (continued) Class B Burning Brand with Metal Roof Covering Specimen #6 00:01 Brand Placed Start of test. 00:48 Smoke Smoke emits from the saw kerfs joint on underside of the deck. 14:13 Brand Brand consumed. 21:36 End Test No smoke or evidence of combustion - end test. After Test No sustained flaming on the underside of the deck was observed; PASS. Spread of Flame with Clay Barrel Tile Specimen #7 00:01 Flame on Start of test. 01:25 Ignition Ignition of the asphalt shingles. 1:34 1 Foot Flame spread reaches 1 foot. 2:38 2 Feet Flame spread reaches 2 feet. 5:31 3 Feet Flame spread reaches 3 feet. 10:00 End Test End test. After Test No sustained surface flaming was observed passes 3 feet; PASS Spread of Flame with Clay Flat Tile Specimen #8 00:01 Flame on Start of test. 01:42 Ignition Ignition of the asphalt shingles. 1:45 1 Foot Flame spread reaches 1 foot. 2:53 2 Feet Flame spread reaches 2 feet. 3:55 3 Feet Flame spread reaches 3 feet. 10:00 End Test End test. After Test No sustained flaming on the underside of the deck was observed; PASS.

10 Page 9 of : (continued) Spread of Flame with Clay Flat Tile Specimen #9 00:01 Flame on Start of test. 1:34 Ignition Ignition of the asphalt shingles. 1:36 1 Foot Flame spread reaches 1 foot. 4:36 2 Feet Flame spread reaches 2 feet. 5:09 3 Feet Flame spread reaches 3 feet. 10:00 End Test End test. After Test No sustained flaming on the underside of the deck was observed; PASS. Class B Burning Brand with Clay Barrel Tile Specimen #10 00:01 Brand Placed Start of test. 00:54 Cracked tile Tile below mounted burning brand cracks. 14:02 Brand Brand consumed. 26:30 End Test No smoke or evidence of combustion - end test. After Test No sustained flaming on the underside of the deck was observed; PASS. Class B Burning Brand with Clay Flat Tile Specimen #11 00:01 Brand Placed Start of test. 00:45 Cracked tile Tile below mounted burning brand cracks. 13:53 Brand Brand consumed. 20:00 End Test No smoke or evidence of combustion - end test. After Test No sustained flaming on the underside of the deck was observed; PASS.

11 Page 10 of : (continued) Class A Burning Brand with Clay Flat Tile Specimen #12 00:01 Brand Placed Start of test. 2:24 Burn through Ignition on the underside of the PV module. 3:08 Dripping Dripping onto the roof deck from the underside of the PV module. 6:15 Glass Breaks Brand burns thru PV module breaks glass and falls on roof deck. 23:13 Brand Consumed Brand completely consumed. 27:00 End of Test End of test no signs of combustion. After Test No ignition of the product or underlayment was observed; PASS. Intertek-ATI will service this report for the entire test record retention period. Test records that are retained such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation will be retained by Intertek-ATI for the entire test record retention period. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: Scott Gingrich Senior Technician Fire Testing Matthew Freeborn Manager Fire Testing SDG:ddr Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Photographs (8)

12 Page 11 of 11 Revision Log Rev. # Date Page(s) Revision(s) 0 03/23/2016 N/A Original report issue This report produced from controlled document template ATI 00538, revised 05/06/15.

13 Appendix A Photographs

14 Test Report No.: F Photo No. 1 Spread of Flame Assembly with Metal Roof Covering Photo No. 2 Spread of Flame Assembly with Clay Flat Tile

15 Photo No. 3 Spread of Flame Assembly with Clay Barrel Tile Photo No. 4 Spread of Flame with Metal Roof Covering (During Test)

16 Photo No. 5 Spread of Flame with Clay Flat Tile (During Test) Photo No. 6 Spread of Flame with Clay Barrel Tile (During Test)

17 Photo No. 7 Class A Burning Brand Set-up on Metal Roof Covering (Pre-test) Photo No. 8 Class A Burning Brand on Metal Roof Covering (During Test)

18 Photo No. 9 Class B Burning Brand with Metal Roof Covering (During Test) Photo No. 10 Spread of Flame Burn Pattern with Metal Roof Covering (Post-test)

19 Photo No. 11 Class A Burning Brand with Metal Roof Covering (Post-test) Photo No. 12 Class A Burning Brand with Clay Flat Tile (Post-test)

20 Photo No. 13 Class B Burning Brand with Clay Flat Tile (Post-test) Photo No. 14 Class B Burning Brand with Metal Roof Covering (Post-test)

21 Photo No. 15 Class B Burning Brand with Metal Roof Covering Underdeck (Post-test)

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device

More information

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard

More information

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:

More information

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product PERFORMANCE TEST REPORT Rendered to: EVERBLOCK SYSTEMS, LLC PRODUCT: Modular Block Product Report No.: G1320.01-106-31 Report Date: 08/04/16 Test Record Retention Date: 07/29/20 130 Derry Court York, PA

More information

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E 108-07a Rendered to: Trinity ERD Columbia, SC WFCi Project # 10135 & 11159 Testing Completed on: April

More information

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL

BURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL BURNING BRAND PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR 022 0000 (Acrylic Dome) VELUX SUN TUNNEL ACCESSORY PRODUCTS: Tubular Skylight with ZTA 022 000090 9" Turrets

More information

SIGMADEK, LTD. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION

More information

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws

PERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws PERFORMANCE EVALUATION TEST REPORT Rendered to: GREENFIELD MANUFACTURING COMPANY PRODUCT: Hanger Screws Report No: Report Date: 01/12/11 Expiration Date: 12/28/14 Product: Hanger Screws PERFORMANCE EVALUATION

More information

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate PERFORMANCE TEST REPORT Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate Report No: C7626.1-16-31 Report Date: 5/8/13 Test Record Retention Date: 5/8/17 PERFORMANCE TEST REPORT

More information

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA

More information

FUNDERMAX GMBH FIRE TEST REPORT

FUNDERMAX GMBH FIRE TEST REPORT FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT

More information

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES

More information

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112

More information

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 REPORT NUMBER: 101960325MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 TEST REPORT

More information

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA

1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA 1.0 INTRODUCTION This report presents the results of an investigation of the external fire resistance characteristics of the VELUX FCM Deck Mounted Skylight roof covering system in general accordance with

More information

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1 REPORT NUMBER: 101145164COQ-005 ORIGINAL ISSUE DATE: April 25, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO udecor Inc.

More information

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC.

PERFORMANCE TEST REPORT. Rendered to: SOLATUBE INTERNATIONAL, INC. PERFORMANCE TEST REPORT Rendered to: SOLATUBE INTERNATIONAL, INC. Report No.: Test Date: 06/11/08 Report Date: 07/15/08 Record Retention End Date: 06/11/12 2524 E. Jensen Ave Fresno, CA 93706 phone: 559-233-8705

More information

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3 REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries

More information

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008 Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,

More information

Fire Performance of Translucent Systems

Fire Performance of Translucent Systems Fire Performance of Translucent Systems ASTM E-108 Burning Brand Test on Quadwall Class A Approved Light Transmitting Plastics Fire Test Performance Meets Building Code Requirements: Self-Ignition ASTM

More information

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy REPORT NUMBER: 100900037COQ-002 ORIGINAL ISSUE DATE: October 10, 2012 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, BC V3K 7C1 RENDERED TO Laminam S.P.A.

More information

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal

More information

Effect of Rack Mounted Photovoltaic Modules on the Fire Classification Rating of Roofing Assemblies

Effect of Rack Mounted Photovoltaic Modules on the Fire Classification Rating of Roofing Assemblies Effect of Rack Mounted Photovoltaic Modules on the Fire Classification Rating of Roofing Assemblies Project Number: 08CA39594, 09CA40917 File Number: IN15911, R26475 Date: September 30, 2009 Revised February

More information

Roof Coatings Manufacturers Association October 18, 2012

Roof Coatings Manufacturers Association October 18, 2012 Roof Coatings Manufacturers Association October 18, 2012 Examples of Addressing New Fire Challenges & Risks With Science Bob Backstrom Kevin Faltin UL and the UL logo are trademarks of UL LLC 2012 New

More information

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5 REPORT NUMBER: 3189147COQ-002 ORIGINAL ISSUE DATE: September 30, 2009 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Radial Engineering

More information

Materials Testing by Gregory Havel

Materials Testing by Gregory Havel Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics

More information

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source TEST REPORT Kolay 5mm 20mil Wear Layer LVT with Fiberglass Core Project

More information

Public Comment No. 2-NFPA [ Section No ]

Public Comment No. 2-NFPA [ Section No ] Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard

More information

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor

Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor www.astm.org ASTM D1230 Flammability of Apparel Textiles Scope: This test method covers the evaluation of the flammability

More information

SOUTHWEST RESEARCH INSTITUTE

SOUTHWEST RESEARCH INSTITUTE SOUTHWEST RESEARCH INSTITUTE 6220 CULEBRA ROAD 78238-5166 P.O. DRAWER 28510 78228-0510 SAN ANTONIO, TEXAS, USA (210) 684-5111 WWW.SWRI.ORG CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT

More information

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 21 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-8-913-9385 e-mail: info@fireretardantsinc.com

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT RAPPORT TECHNIQUE TECHNISCHER BERICHT CLC/TR 50670 December 2016 ICS 13.220.50; 27.160; 91.060.20 English Version External fire exposure to roofs in combination with photovoltaic (PV)

More information

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS

More information

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c 1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire

More information

We Identify and S.T.O.P. Your Noise Problems

We Identify and S.T.O.P. Your Noise Problems ASTM E-84 TESTING FOR MANUFACTURER, RENDERED TO: Acoustical Surfaces Inc. 123 Columbia Court North, Suite 201 Chaska, MN 55318 Noise S.T.O.P. Fabrisorb Acoustical Wall Panels TESTED: OCTOBER 3, 2002 October

More information

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss FIRE RETARDANT ARCHITECTURAL WOOD COATING ASTM E84 CLASS A FIRE SHIELD FS020 FIRE-SHIELD SEALER FS021 FIRE-SHIELD TOP COAT Available in different gloss www.duro-lak.com Easy to apply Water base sealer

More information

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS

FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS Report number FSP 1290A CSIRO job number LP46ASP3085 Date of issue 30 NOVEMBER 2007 Client EFFICIENCY MATRIX PTY LTD and YOUNGEN

More information

Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options

Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options 2016 NFPA Conference & Expo Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options Presented by: Joel Sipe Senior Managing Engineer Exponent Inc. Outline Project Background Fire

More information

Viewing a PV system fire test at Underwriters Laboratories STEVEN BUSHONG ASSOCIATE EDITOR

Viewing a PV system fire test at Underwriters Laboratories STEVEN BUSHONG ASSOCIATE EDITOR STEVEN BUSHONG ASSOCIATE EDITOR Viewing a PV system fire test at Underwriters Laboratories If a roof with installed PV modules is exposed to a fire, will the solar array help or hinder the flames? Until

More information

ENGINEERING EVALUATION

ENGINEERING EVALUATION ENGINEERING EVALUATION REPORT NUMBER: 100378137MID-002 ORIGINAL ISSUE DATE: April 26 th, 2011 REVISION AND DATE: Original EVALUATION CENTER Intertek 8431 Murphy Drive Middleton, WI 53562 RENDERED TO Hanchett

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd. May 22, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave. Lee Baie-D urf, QX 3S3 Canada Our Reference: Subject: R26549/13CA21763 Report Of Surface Burning Characteristics Tests On Samples As Submitted By

More information

Copyright 2018 American Wood Council 1

Copyright 2018 American Wood Council 1 Fire Tests in Support of Tall Mass Timber Buildings DES603 Sam Francis Senior Director, National Programs American Wood Council Jason Smart, P.E. Manager, Engineering Technology American Wood Council The

More information

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors February 2, 16 Rieke Office Interiors Mr. Todd Rieke Fox Ln. Elgin, IL 6123 Our Reference: SV3565 / 4787326412 Subject: Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By

More information

PERFORMANCE REPORT. ARL Lab Number: Client: In-O-Vate Technologies Inc. 810 Saturn St. Jupiter, FL 33477

PERFORMANCE REPORT. ARL Lab Number: Client: In-O-Vate Technologies Inc. 810 Saturn St. Jupiter, FL 33477 PERFORMANCE REPORT ARL Lab Number: 50175 Client: In-O-Vate Technologies Inc. 810 Saturn St. Jupiter, FL 33477 Test Method: Miami-Dade County Protocol TAS 114, Appendix E (1995) Product: Dryer Vent L/N

More information

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd November 29, 2010 Revised: January 10, 2013 Revised: January 18, 2013 Mr. Herbert Wheeler Railtech Ltd. 325 Ave Lee, Baie-D Urf QC H9X 3S3 Canada Our Reference: Subject: R26549/09CA56627 Report of Surface

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: FIRE RETARDANT WOOD TREATMENT REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: FIRE RETARDANT WOOD TREATMENT REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2666 Reissued 02/2018 This report is subject to renewal 02/2019. DIVISION: 06 00

More information

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009 ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC #100-3191-1 TESTED: MARCH 27, 2009 April 2, 2009 Client: Attention: Cole Motorsports/CM Racing Products

More information

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc. August 11, 2017 Contego International Inc. Mr. Danny French PO Box 49 Rochester, IN 46975-0049 Our Reference: R25382 / 4788022828 Subject: Report Of Surface Burning Characteristics Tests On Coated Louvered

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part

More information

TECHNICAL BULLETIN Weston Parkway, Cary, North Carolina, Telephone (919) FLAMMABILITY TESTING: A REVIEW BY COTTON INCORPORATED

TECHNICAL BULLETIN Weston Parkway, Cary, North Carolina, Telephone (919) FLAMMABILITY TESTING: A REVIEW BY COTTON INCORPORATED TECHNICAL BULLETIN 6399 Weston Parkway, Cary, North Carolina, 27513 Telephone (919) 678-2220 TRI 4004 FLAMMABILITY TESTING: A REVIEW BY COTTON INCORPORATED 2004 Cotton Incorporated. All rights reserved;

More information

STANDARD FOR FIRE RATED ROLLING DOOR ASSEMBLIES

STANDARD FOR FIRE RATED ROLLING DOOR ASSEMBLIES ANSI/DASMA 204-2004 AMERICAN NATIONAL STANDARD STANDARD FOR FIRE RATED ROLLING DOOR ASSEMBLIES Door & Access Systems Manufacturers Association, International Sponsor: 1300 Sumner Ave Cleveland, Ohio 44115-2851

More information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information UL 2360 Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction General Information UL 2360 - Test Methods for Determining the Combustibility

More information

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 158117 BS 476:

More information

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services

Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Peter Gordon Report number: FSP 1960 Date: 5 February 2019 Client:

More information

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol

More information

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES

FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES Report number FSP 1360 CSIRO job number SP3241 Date of issue 31 JULY 2009 Client SNAP FIRE SYSTEMS PTY LTD. Commercial-in-confidence

More information

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY White Paper BACKGROUND: Safety is paramount in the home appliance industry. Due to the possibility of human mis-application, over-current, or short circuit

More information

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY

GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY White Paper 23 May 2013 Rev A 503-32020 GLOW WIRE TESTING FOR THE APPLIANCE INDUSTRY Background Safety is paramount in the home appliance industry. Due to the possibility of human misapplication, over-current,

More information

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS SPANK 9901101 REPORT NO. 75157 Septemer 11, 00 Prepared For: Pollack 150 Varick Street New York, NY 10013 F-316-A 555 76TH STREET S.W., GRAND RAPIDS.

More information

Fire Risks and Safety Standards

Fire Risks and Safety Standards Fire Risks and Safety Standards Florian Reil TÜV Rheinland Group Renewable Energies 51105 Cologne, Germany Phone: + 49 221 806 27 94 Email: Florian.Reil@de.tuv.com Workshop BIPV The Increasing Role of

More information

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] 1.3 Application. 1.3.1 This standard shall apply to all systems for the movement of environmental air in structures that serve the following, except

More information

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd October 05, 2011 Eco-Sol Ltd Mr. Paul Allcock Cardiff House Cardiff Rd Barry, Vale of Glamorgan, CF63 2AW Great Britain Our Reference: Subject: R27181/11CA40094 Report of Surface Burning Characteristics

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center IR Energy Habanero HAB-M50 Gas Patio Heater Test Report Application of ASTM Standard Test Method FF2644-07 September 2014 Prepared by: Elan Frantz Trey Young Fisher-Nickel,

More information

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Contact person Date Reference Page Richard Johansson P (2) Fire Research issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa

More information

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International January 3, 7 Mr. Danny French Contego International 334 Greyhound Pass West Carmel, IN 4632 Our Reference: Subject: R25382 / 6CA51291 Report Of Surface Burning Characteristics Tests On Fire Retardant Coating

More information

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider. by NEENAH EnviroScape Mural pre-pasted printable wallcovering material EnviroScape Mural is a PVC free wall, window or hard surface scaping product that is pre-pasted with a water activated adhesive backing

More information

Heat and Smoke Release of a Ceiling-Installed Speaker

Heat and Smoke Release of a Ceiling-Installed Speaker WFCi Project #12051 Heat and Smoke Release of a Ceiling-Installed Speaker Indicative testing conducted in accordance with the test methodology described in UL 2043, Fire test for heat and visible smoke

More information

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process 2010 IMO FTP Code Revisions Parts 2, 5, 7, 8, 9 & 10 Presented by: Juan Manuel Flores, P.E. Date:

More information

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6 Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)

More information

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report

More information

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety

More information

Fire-resistance test on fire collars protecting a concrete slab penetrated by services

Fire-resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Chris Wojcik Report number: FSP 1735 Date: 8 September 2016 Client:

More information

Fire resistance test on fire collars protecting a concrete slab penetrated by services

Fire resistance test on fire collars protecting a concrete slab penetrated by services INFRASTRUCTURE TECHNOLOGIES Fire resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1601a Date: 11 April 2014 (This report

More information

CLT Adhesive Tests in Support of Mass Timber Buildings

CLT Adhesive Tests in Support of Mass Timber Buildings CLT Adhesive Tests in Support of Mass Timber Buildings DES604 Jason Smart, P.E. Manager, Engineering Technology American Wood Council Sam Francis, C.B.O. Senior Director, National Programs American Wood

More information

Report on Public Input June 2014 NFPA 101

Report on Public Input June 2014 NFPA 101 101 PI# 115 SAF-FUR (10.2.1.2) 10.2.1.2 Materials applied directly to the surface of walls and ceilings in a total thickness of less than 1 / 28 in. (0.9 mm) shall not be considered interior finish and

More information

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in INFRASTRUCTURE TECHNOLOGIES Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in accordance with AS/NZS 3837:1998 Fire Testing Report Author: Heherson Alarde Report Number:

More information

Second Revision No. 3-NFPA [ Section No. 2.3 ]

Second Revision No. 3-NFPA [ Section No. 2.3 ] Second Revision No. 3-NFPA 804-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ASME Publications. American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990. ASME Boiler

More information

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415

ASSESSMENT REVIEW. Review of Assessment Report WFRA C91415 ASSESSMENT REVIEW Review of Assessment Report WFRA C91415 Fire resistance performance of steel electrical wall boxes mounted in plasterboard partitions with modified mounting arrangements, box design and

More information

MODEL CF CEILING SUPPORTED CHIMNEY

MODEL CF CEILING SUPPORTED CHIMNEY Manufactured by Selkirk Canada Corp. - Hamilton, Ontario Installation Instructions for MODEL CF CEILING SUPPORTED CHIMNEY Round Top Storm Collar Flashing Attic Insulation Shield/Firestop Spacer Intermediate

More information

Southern California Gas Company Customer Programs Department

Southern California Gas Company Customer Programs Department Appliance Test Report SCGAT140220A Revision 0 Issued Date: March 2014 Duke 613Q-G1V Gas Convection Oven Performance Test Per ASTM F1496-13 Southern California Gas Company Customer Programs Department Food

More information

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern Hugh Hoagland Consulting, Inc. ArcWear.com 1566 Red Brush Road Newburgh, IN 47630 Phone: 502-314-7158 Fax: 603-457-5960 E-mail: hugh@arcwear.com Electric Arc Exposure Tests for Stern & Stern October 2002

More information

Installation Instructions

Installation Instructions Installation Instructions Type B Gas Vent Model E/R 3" 8" ECCO TYPE B GAS VENT AND ACCESSORIES ARE FOR USE ONLY WITH LISTED CATEGORY 1 GAS-FIRED APPLIANCES OR APPLIANCES LISTED FOR USE WITH TYPE B GAS

More information

GUARDIAN FIRE TESTING LABORATORIES, INC.

GUARDIAN FIRE TESTING LABORATORIES, INC. GUARDIAN FIRE TESTING LABORATORIES INC. Testing & Listing Field Labeling Page 1 of 5 Engineering & Product Certification Services Factory Inspections Guardian Fire Testing Laboratories, Inc. Phone: 716

More information

Acoustical Surfaces, Inc.

Acoustical Surfaces, Inc. S.T.O.P. February 21, 2013 Our Reference: Subject: SV19452/13CA09185 Report Of Surface Burning Characteristics Tests On Samples This is a Report summarizing the results of a test conducted under the Commercial

More information

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles

Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests. For Innovative Textiles Hugh Hoagland Consulting, Inc. Electric Arc Exposure Tests For Innovative Textiles Fabric system Outer Layer: 5.5 oz/yd² IUS Twill, 88% Cotton 12% Nylon, Style 341, Khaki. 6.6 oz/yd² Inner Layer: 6.5 oz/yd²

More information

Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants

Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants Research to Assist in the Development of Safety Standards and Building Codes for the Use of Flammable Refrigerants Karim Amrane, Ph.D. Senior Vice President Low GWP AREP Cooperative research & testing

More information

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS

BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS BUSHFIRE TEST ON GLAZED VERTICAL ELEMENTS Report number FSZ 1572 CSIRO job number SV3559 Date of issue 22 FEBRUARY 2013 Client BREEZWAY AUSTRALIA PTY LTD Commercial-in-confidence Copyright CSIRO 2013 Copying

More information

Asphalt(Shingle(Patterns( Identification(Guide( Heather(E.(Sommers(

Asphalt(Shingle(Patterns( Identification(Guide( Heather(E.(Sommers( ! IBHS(MEMBERS@ONLY(! Asphalt(Shingle(Patterns( Identification(Guide( Heather(E.(Sommers( Tanya(M.(Brown@Giammanco! Introduction This guide is intended to help claims adjusters and underwriters identify

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Worldwide Contacts www.tyco-fire.com RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description Pendent Sprinklers (TY2235)

More information

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798 July 22, 2009 Stewart Audio Inc Brian Mccormick Po Box 4058 Mountain View, CA 94040 Our Reference: Subject: File SV17764 / Project 09CA34798 UL Standard 2043, Third Edition "Fire for Heat and Visible Smoke

More information

FIRE TESTING OF LOW SLOPE ROOF ASSEMBLIES AN INTERNATIONAL REVIEW

FIRE TESTING OF LOW SLOPE ROOF ASSEMBLIES AN INTERNATIONAL REVIEW FIRE TESTING OF LOW SLOPE ROOF ASSEMBLIES AN INTERNATIONAL REVIEW Birgitte Messerschmidt Rockwool International A/S Denmark & John Scott Roxul Inc. Canada ABSTRACT Knowing the fire behaviour of roofs is

More information

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX IN A THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX William H. Greenwood and Ronald L. Akau Sandia National Laboratories PO Box 5800 Albuquerque, New

More information

Certificate of Compliance

Certificate of Compliance Certificate of Compliance This certificate is issued for the following: KS103SSF, KS103MSF, AND KS110CTF PANELS AS CLASS 1 INTERIOR WALL AND CEILING PANELS FOR INSTALLATION WITH NO HEIGHT RESTRICTION Prepared

More information

TABLE OF CONTENTS. 1.0 INTRODUCTION Scope References Test Specimen Description Summary 3

TABLE OF CONTENTS. 1.0 INTRODUCTION Scope References Test Specimen Description Summary 3 Page No. 2 TABLE OF CONTENTS Page No. 1.0 INTRODUCTION 3 1.1 Scope 3 1.2 References 3 1.3 Test Specimen Description 3 1.4 Summary 3 2.0 TEST PROCEDURES AND RESULTS 4 2.1 Wall-Mount Pull-Out Test 4 2.2

More information

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved. Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in

More information

TABLE OF CONTENTS. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction TEST PROGRAM 4

TABLE OF CONTENTS. Section Title Page 1.0 SUMMARY TEST SPECIMEN Materials and Construction TEST PROGRAM 4 TABLE OF CONTENTS Section Title Page 1.0 SUMMARY 1 2.0 TEST SPECIMEN 2 2.1 Materials and Construction 2 3.0 TEST PROGRAM 4 3.1 Test Sequence 4 3.2 Functional Test Procedures 5 3.3 Specimen Preconditioning

More information

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples

More information

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Worldwide Contacts www.tyco-fire.com Series EC-8 8.0 K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description Pendent Sprinklers are decorative glass bulb sprinklers

More information

Report of Surface Burning Characteristics Test on Acoustical Panel

Report of Surface Burning Characteristics Test on Acoustical Panel January 02, 2013 Ideacustik Christian Morales Torres Gerente General Av. Quito 3620 y Bolivia Guayaquil, Ecuador Our Reference: Subject: R27636 / 12CA68539 Report of Surface Burning Characteristics Test

More information