FMO Fire and Building
|
|
- Martha Pope
- 6 years ago
- Views:
Transcription
1 FMO Fire and Building Inspection Reference Manual 2003 Code Edition, version Prince William County Fire Marshal s Office 5 County Complex Court, Suite 160 Prince William, Virginia
2 FIRE MARSHAL S OFFICE FIRE PROTECTION AND BUILDING PERMIT ASSOCIATED INSPECTIONS Effective February 14, 2007, the following guideline is in place regarding all fire protection (FPP), building (BLD), and fire lane plan (FLP) permit inspections conducted by the Prince William County Fire Marshal s Office. Fire Alarm Systems The inspections shown below are required for all fire alarm system installations under permit. If there an emergency power generator present and the fire alarm system is wired to the generator as power back up, the fire alarm battery test (74) is not required. However, the system must be tested utilizing the generator power source prior to the fire alarm final inspection (81). The fire alarm battery test is also not required when replacement of a fire alarm device is done of like kind equipment. 73- Fire alarm test 74- Fire alarm battery test 81- Alarm final Note: Where the fire alarm is connected to a fire suppression system, elevator with fire department recall, and/or a mechanical system to shut down circulation fans, the inspection/test must be coordinated with the appropriate trade(s). This coordination is necessary to permit the testing of the connection between the fire alarm and the devices on the affected systems. Failure to have representatives of the other trade(s) present will result in an automatic rejection of the inspection/test. Underground Fire Main The inspections/tests shown below are required for all underground fire main installations under permit. Regardless of who does the work, the underground fire main must be inspected/tested from the point it leaves the street main to the point that it is connected to the sprinkler/standpipe system. If the installation is broken into two permits, the underground flush (61) can be done one time as long as the entire length of underground main is being flushed. The underground final (82) is an administrative action done by the Fire Marshal at the time of completion of all other required tests/inspections (59, 60, 61). 59- Visual inspection 60-Underground hydrostatic test 61-Underground flush 82-Underground final (administrative approval) Page 1 of 6
3 Automatic Systems Wet Pipe System The inspections/tests shown below are required for all wet pipe sprinkler system installations under permit. Some of the inspections/tests are only required when the particular piping/appurtenance is present. If there is a breezeway loop present, the following inspections are mandatory: 84-Breezeway Loop hydrostatic test 85-Breezeway Loop visual inspection 86-Breezeway Loop flush If the sprinkler system is a NFPA 13R system, the following flow test is required: 87-Four-head flow 13R If the sprinkler system is a NFPA 13D system, the following flow test is required: 89- Two- head flow 13D If the system has an anti-freeze loop or component the following inspection is required: 90- antifreeze If there is a standpipe included as part of the sprinkler system, the following inspections/tests are required: 67-Standpipe hydrostatic test (if equipped with standpipes and not tested with remainder of sprinkler system) 68-Standpipe flow test (if equipped with standpipes) If there is a fire pump present and is required to supply the sprinkler system with adequate pressure and volume of water, the following test is required: 72-Fire pump test (if so equipped) ALL wet pipe sprinkler system installations/modifications under permit are required to have the following tests/inspections. There is an exception to the hydrostatic test for 1) the addition or relocation of less than five heads, 2) the addition of ten or less new fittings, 3) the addition of twenty feet or less of pipe (pipe nipples shall not be counted as pipe length), or 4) any combination of these items. In addition, in order to gain approval on a wet sprinkler final inspection, any underground fire main piping supplying the system must have final approval as well as the fire alarm system monitoring the sprinkler system must have had a fire alarm test (73) and be capable of monitoring the Page 2 of 6
4 sprinkler system. (The monitoring system, if required, must be in-service and able to call an approved and listed monitoring company.) If there is an anti-freeze system being employed to protect an area subject to freezing, a visual inspection/test of the antifreeze protection temperature must be performed and is part of the visual inspection of the sprinkler system (83). 62-static test 83-Visual inspection 66-Wet sprinkler final Dry Pipe System ALL dry pipe sprinkler system installations/modifications under permit are required to have the following tests/inspections. There is an exception to the hydrostatic test for 1) the addition or relocation of less than five heads, 2) the addition of ten or less new fittings, 3) the addition of twenty feet or less of pipe (pipe nipples shall not be counted as pipe length), or 4) any combination of these items. In addition, in order to gain approval on a dry pipe sprinkler final inspection, any underground fire main piping supplying the system must have final approval as well as the fire alarm system monitoring the sprinkler system must have had a fire alarm test (73) and be capable of monitoring the sprinkler system. (The monitoring system, if required, must be in-service and able to call an approved and listed monitoring company). 83-Visual inspection 62-static test 65-Air test 64-Trip test 88-Dry pipe sprinkler final Clean Agent and Hood Systems Clean agent and hood systems installations under permit are required to have the following tests, as appropriate. These systems must be connected to and sound the building fire alarm system, upon initiation, where a fire alarm system is present. 69-Clean agent test 70-Hood system test Fire Marshal s Office Final Inspection for Shell Buildings (146-FMO final inspection Shell) Effective February 14, 2007, all shell building trade inspection permits must have a partial approval (PAP) or approved (APP) status prior to the FMO final inspection-shell (146) inspection being scheduled and/or approved. This includes the fire protection Page 3 of 6
5 permits (FPP) and fire lane plan permits (FLP) for the shell. Fire Marshal s Office Final Inspection for Tenants (149-FMO Final Inspection- Tenant) Effective February 14, 2007, all tenant building and trade inspection permits must have a partial approval (PAP) or approved (APP) status prior to the FMO final inspection- Tenant (149) inspection being scheduled and/or approved. This includes any trade or fire protection permits (FPP) and/or fire lane plan permits (FLP) pertaining to any shell permits that the tenant space may be associated with. Page 4 of 6
6 Fire Marshal s Office Fire Protection Systems Inspection flow chart (3/13/07) Fire Alarm System Automatic System Standpipe System Underground Fire Main Wet System 73 Fire Alarm 74 Battery Test*** 81 Fire Alarm Final Dry System 83- Visual 62 Test 65 Air Test 64 Trip Test 84 Bzy LP hydro 85 Bzy LP visual 86 Bzy LP flush 88 Dry System Final YES 90 antifreeze 87 4 head flow 13R 66 Wet Final Breezeway Loop? 83 Visual *62 Test NO 70 Hood system 89 2 head flow 13D Standpipe Flow 72 Fire pump 69 Clean agent test 59 Visual 60 U/G 61 U/G Flush 82 U/G final 146- FMO Final Shell ** 148 Stocking (Optional) 149 FMO Final Tenant Page 5 of 6
7 General Notes: For an 88 or 66, the U/G fire main must have had an Underground Fire Main Final (82) with all of the required Underground Fire Main inspections approved if there was an underground fire line involved. An Underground Fire Main Final (82) must have a Underground Fire Main Visual (59), Underground Fire Main hydro (60), and Underground Fire Main Flush (61) to get a final. The flush may come from another permit in the case of a split permit for the street valve to 5 feet outside the building and 5 feet outside the building to the sprinkler flange (spool). An Dry System final (88) or a Wet final (66) must have final approval of all sprinkler components and a fire alarm test (73) to get a final. For inspections, ALL fire protection systems must have been approved and finalled. An FMO final inspection- tenant (149) cannot be scheduled until the FMO finalshell (146) inspection for the shell (if applicable) has a status of provisional approval (PAP) or approved (APP). * only required if 1) five heads or more, 2) ten or more fittings, 3) twenty or more feet of pipe, or 4) any combination of the three. **For an optional Stocking/storage inspection (148), the fire protection systems (sprinkler, standpipe, and fire alarm) must be finalled. Other systems may not be required to be final until the 149 inspection. Shells cannot have Stocking/storage inspection 148 inspections done as stocking of a shell is not permitted. **If stocking is not needed, the inspections proceed directly to FMO final- tenant (149). ***A fire alarm battery test may or may not be required on an existing system depending upon the scope or work being done. Page 6 of 6
Expectations (continued)
Expectations (continued) The work is ready to be inspected. If a problem develops where the work is not ready for inspection, call the FMO and cancel the inspection as soon as you are aware there is a
More informationCODE COMPLIANCE MANUAL
5 County Complex Court Suite 160 Prince William, VA 22192 Phone: 703-792-6360 www.pwcgov.org/fire CODE COMPLIANCE MANUAL Supplemental Information intended for Architects, Engineers, Designers, and Installers
More informationFire Protection Systems Plan Review
Fire Protection Systems Plan Review and Inspections Prince William County Fire Marshal s Office December 15, 2005 Fire Marshal s Office Organizational Chart Kevin McGee Assistant Chief- Fire Marshal Warren
More informationSACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET
SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET 1 SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT
More informationD. The work addressed in this section consists of a fire protection system, which may include coordination with one or more of the following:
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of Sam Houston State University for the design and construction of standpipe systems to include combination standpipe
More informationBurnsville Fire Department 100 Civic Center Pky, Burnsville, MN Fire Marshal: FAX:
Burnsville Fire Department 100 Civic Center Pky, Burnsville, MN 55337 Fire Marshal: 952-895-4579 FAX: 952-895-4512 2018 FIRE SUPPRESSION PERMIT APPLICATION PERMIT Wet System Dry System Cooking Hood Clean
More informationFire Sprinkler Submittal Requirements and Acceptance Testing
Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Sprinkler Submittal Requirements and Acceptance Testing To all Registered
More informationPLAN REVIEW FEES. Sprinkler Systems. NUMBER OF Without With SPRINKLERS Inspections Inspections
The Mt. Pleasant Fire Department requires all contractors to submit plans for review of all sprinkler systems, fire detection and alarm systems, and gas suppression or dry chemical systems. The Fire Department
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationDesign & Construction Standards, Revised January
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for the design and construction of standpipe systems to include combination standpipe
More informationSkilled Healthcare Documentation Requirements Life Safety and Fire Protection
DATE OF EVALUATION: FACILITY NAME: FACILITY ADDRESS: ADMINISTRATOR: MAINTENANCE DIRECTOR: All required documentation must be written and saved for at least 2 years and some documentation may be required
More informationPLAN REVIEW CHECKLIST
PLAN REVIEW CHECKLIST Date Documents Submitted: Log No.: File No.: Property Information Building Name: Building Address: Owner s Name: Owner s Address: Owner s Phone: Fax: E-mail: System Designer/Contractor
More informationWEST VIRGINIA UNIVERSITY
WEST VIRGINIA UNIVERSITY Environmental Health and Safety (SOP) WV State Fire Marshal (SFM) Project Plans Review Process & Procedures West Virginia University Environmental Health & Safety Page 1 of 10
More informationType of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:
DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM
More informationInternational Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures
International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures Please note this is not an all-inclusive list. The type and complexity of your project
More informationMINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review
MINOOKA FIRE PROTECTION DISTRICT Fire Prevention Bureau Fire Inspector Rodney Bradberry Plan Review Minooka Fire Protection District Maintaining Your Fire Safety Systems Fire continues to be a major threat
More informationDivision 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21
Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.
More informationFIRE SPRINKLER SHOP DRAWING SUBMITTAL REQUIREMENTS
Department of Fire Rescue & Emergency Services Fire Marshal s Office Dania Beach District 103 West Dania Beach Blvd. Dania Beach, Florida 33004 Office: (954)342-4262 Fax: (954)342-4265 FIRE SPRINKLER SHOP
More informationEXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5
UNIT PRICING IS A "NOT TO EXCEED" PRICE EXHIBIT D ATTACHMENT G - UNIT PRICING DMS-14/15-039B - SIMPLEXGRINNELL, LP FIRE SPRINKLER SYSTEM INSPECTIONS YEARS 1-5 Unit Pricing to perform all required Test
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationFIRE DEPARTMENT SYSTEM PERMIT APPLICATION
Permit No:_ FIRE DEPARTMENT SYSTEM PERMIT APPLICATION Thank you for submitting plans for the installation or modification of a required fire protection or detection system. Typical review of system plans
More informationENGINEERING/PLAN REVIEW - FEE SCHEDULE Exhibit A
CCCFPD ORDINANCE 2018 21 Date of Adoption July 10, 2018 ENGINEERING/PLAN REVIEW - FEE SCHEDULE Exhibit A Page 1 of 11 Review Number 1.1 1.2 PLAN REVIEW Preliminary Plan Review - Consultations - Meetings
More informationFIRE SUPPRESSION SYSTEM REVIEW APPLICATION 1. NEW PLAN REVIEW RESUBMITTAL
STATE OF LOUISIANA 10/09/2015 DEPARTMENT OF PUBLIC SAFETY - OFFICE OF STATE FIRE MARSHAL CODE ENFORCEMENT AND BUILDING SAFETY 8181 INDEPENDENCE BLVD., BATON ROUGE, LA 70806 800-256-5452 225-925-4920 FAX:
More informationFire Sprinkler Plan Submittal Form
Contents Fire Sprinkler Plan Submittal Form... 2 Standpipe Plan Review Submittals... 4 Fire Pump Plan Submittal Requirements... 6 Fire Alarm Plan Submittal Form... 8 Kitchen Hood Wet Chemical Submittal...10
More informationCLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau
CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau 575 E. Flamingo Road, Las Vegas, NV 89119 (702) 455-7316 FAX (702) 455-7347 Permit Type: 105.7.13 Control Number: A.0 Effective Date: 11/15/11 TITLE:
More informationA. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:
SECTION 21 13 13 WET-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationSTATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT
STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device
More informationFIRE ALARM APPLICATION CITY OF MADISON HEIGHTS
FIRE ALARM APPLICATION CITY OF MADISON HEIGHTS www.madison-heights.org COMMUNITY DEVELOPMENT DEPARTMENT BUILDING DIVISION 300 W. THIRTEEN MILE RD. MADISON HEIGHTS, MICHIGAN 48071 (248) 583-0831 FAX (248)
More informationFIRE INSPECTION CHECKLIST
Applicable Base Codes FIRE INSPECTION CHECKLIST Florida Fire Prevention Code, 5th Edition NFPA 1, Uniform Fire Code, Florida 2012 Edition NFPA 101, Life Safety Code, Florida 2012 Edition NFPA 13, 2010
More informationUniversity of Houston Master Construction Specifications Insert Project Name SECTION DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL
SECTION 21 13 16 DRY-PIPE FIRE SPRINKLER SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
More informationRevision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.
SECTION 211300 FIRE SUPPRESSION SYSTEMS 1.0 All new and renovated buildings shall be provided with automatic sprinklers throughout and fire standpipe systems. The design and installation of these systems
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD INSTALLATION OF COMMERCIAL FIRE SPRINKLER SYSTEMS STANDARD #C-001 EFFECTIVE 03-25-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationGlobal Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationWestern Michigan University Facilities Management Engineering Division
Western Michigan University Facilities Management Engineering Division Design Guidelines for Facilities Construction: DESIGN GUIDELINE DG21-1 Fire Suppression Systems & Equipment I. GENERAL... 1 A. General
More informationSECTION (13900) - FIRE SUPPRESSION SYSTEMS
PART 1 GENERAL 1.01 SUMMARY SECTION 21 10 00 (13900) - FIRE SUPPRESSION SYSTEMS A. Section Includes: 1. Pipe and Fittings. 2. Sprinklers. B. Related Documents: 1. Marriott s Fire Protection and Life Safety
More informationConstruction and Development Guide
Construction and Development Guide **Based on the 2014 Indiana Fire Prevention Code and relevant NFPA Codes and Standards ** Copyright 2018 Clay Fire CRRD 1 P a g e Table of Contents Map of Jurisdiction...
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationGLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE
GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: Contractors From: Charles Jenkins, Fire Marshal Subject: Contractor s Guide This guide is provided by the Fire Marshal as a service to the construction
More informationSECTION WATER BASED FIRE SUPPRESSION SYSTEMS
PART 1: GENERAL 1.01 Scope of Standard A. This standard provides general guidance concerning the specific preferences of Texas State University-San Marcos for automatic fire sprinkler and standpipe systems.
More informationThis regulation outlines procedures to be followed for fire drills and all school event decorations.
SUPPORT SERVICES September 14, 2016 SUPPORT SERVICES Fire Safety I. Purpose The purpose of this regulation is to establish guidelines for promoting fire safety awareness, practices, and policies to ensure
More informationA. This section includes design and performance information for fire protection and suppression systems.
SECTION 21 00 10: FIRE PROTECTION SYSTEM DESIGN 1. SUMMARY A. This section includes design and performance information for fire protection and suppression systems. 2. GENERAL A. All fire protection materials
More information2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7
WET SPRINKLER Monthly Wet Sprinkler 2-SUPPRESSION REQUIREMENTS - CODE REQUIRED INSPECTIONS TEST Page 1 of 7 VISUALS [per NFPA 25-1998 ed] 1. Gauge (Ck for Condition, Normal Pressure) [per 2-2.4.1] 2. Valves
More informationNarrative Reports As Regulated by 780 CMR, Section 903.0
EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for
More informationDIVISION 21 FIRE SUPPRESSION
Table of Contents 21 00 00 FIRE SUPPRESSION...2 A. REFERENCE ABBREVIATIONS... 2 B. GENERAL... 2 C. DESIGN REQUIREMENTS... 2 D. DOCUMENTATION... 2 21 08 00 FIRE SUPPRESSION COMMISSIONING...2 A. PIPE CLEANING...
More informationDIVISION 21 - FIRE SUPPRESSION
DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,
More informationFire Suppression Introduction Contact Information
Contact Information Jeffrey Mayers Fire Safety Engineering Manager Georgia State Fire Marshal s Office 404-617-8515 E-mail: jmayers@sfm.ga.gov 1 Goal of This Seminar: Hierarchy of Codes List reference
More informationFire Protection Essentials QA/QC Plan Sample
Fire Protection Essentials QA/QC Plan Sample Good for smaller projects and bid qualifications Has All the Essential Elements of a well-founded Quality Control Plan Contact: FirstTimeQuality 410-451-8006
More informationAnnual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System
Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date
More informationGlobal Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:
Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised
More informationPART II: New Construction Inspections and Acceptance Testing Procedures
Stafford County Fire Marshal s Office Handbook for Building/Fire Code Policies and Guidelines PART II: New Construction Inspections and Acceptance Testing Procedures Phone: 540-658-8648 Fax: 540-658-9128
More informationFire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector
NOTICE OF PROPOSED RULE DEVELOPMENT DEPARTMENT OF FINANCIAL SERVICES DIVISION OF STATE FIRE MARSHAL RULE CHAPTER: 69A-46, F.A.C. RULE: 69A-46.0165, F.A.C. RULE CHAPTER TITLE: Fire Protection System Contractors
More informationDESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES
SECTION 21 13 00 - FIRE SUPRESSION SPRINKLER SYSTEMS SCOPE OF WORK This standard provides general guidance concerning the specific preferences of The University of South Alabama for automatic fire sprinkler
More informationTo expedite the plan review and inspection processes, please refer to the information below.
Guidelines: The goal of the Denison Fire Department is to assist its customers in understanding our submittal, plan review and inspection process and policies, as they pertain to new construction. Familiarity
More informationFIRE SPRINKLER SYSTEMS POLICY
FIRE SPRINKLER SYSTEMS POLICY Revised 1/1/17 DESIGN AND SUBMITTAL REQUIREMENTS All new and existing fire sprinkler systems within the jurisdiction of the City Fire Department shall meet all of the applicable
More information2. Welding Materials and Procedures shall conform to the ASME Code.
PART 1 GENERAL 1.01 Scope of Standard A. The design guidelines contained herein include the requirements for systems, materials, fittings and valves utilized for fire protection systems at Sam Houston
More informationFIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
More informationFACILITY PROFILE CALIFORNIA ASSOCIATION OF HEALTH FACILITIES DISASTER PLANNING GUIDE
This facility profile is a document that provides a general overview and listing of relevant information pertaining to operational and property characteristics. This information should be shared with local
More informationCOBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM
SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International
More information2016/2017 Fee Schedule
Corporate Office 2420 Alft Lane Elgin, IL 60124 P: 847.697.1300 F: 847.697.1310 www.firesafetyfsci.com Specializing in Fire, Building, and Life Safety 2016/2017 Fee Schedule Regional Office 23650 Woodward
More informationDESIGN AND CONSTRUCTION STANDARDS SPECIFICATION GUIDELINES
SECTION 21 30 00 FIRE PUMPS GENERAL This standard provides general requirements of The University of South Alabama in Mobile Alabama for fire pumps. This document is not intended to serve as a guide specification.
More informationSECTION Fire Pumps
SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.
More information1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors)
1 Exam Prep NFPA 14 Stand Pipe Systems Questions and Answers (Plumbing Contractors) 1. What is the minimum diameter for a non-hydraulically calculated Class III fire standpipe that is part of a combined
More informationAPPLICATION FOR INSTALLATION OF SPRINKLER SYSTEM.,. :" ROCHESTER, NH FIRE DEPARTMENT FIRE PREVENTION DIVISION
--= =--'" APPLICATION FOR INSTALLATION OF SPRINKLER SYSTEM.,. :"..~S" ".".,.,, " ROCHESTER, NH FIRE DEPARTMENT....~...... FIRE PREVENTION DIVISION 37 Wakefield Street.. Rochester, New Hampshire 03867"
More informationFIRE SPRINKLER SYSTEMS POLICY
FIRE SPRINKLER SYSTEMS POLICY VERSION 1.012/2015 FIRE SPRINKLER SYSTEMS Design and Submittal requirements All new and existing fire sprinkler systems within the jurisdiction of the City of San Mateo Fire
More informationFIRE SUPPRESSION SPRINKLER SYSTEM
PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this
More informationDESIGN & CONSTRUCTION GUIDELINES
ADMINISTRATIVE SERVICES 4202 E. FOWLER AVENUE, FPC110 PHONE: (813) 974-2625 FACILITIES PLANNING & CONSTRUCTION TAMPA, FLORIDA 33620-7550 WEBSITE: USF.EDU/FPC DESIGN & CONSTRUCTION GUIDELINES DIVISION 21
More informationFire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit
NOTICE OF PROPOSED RULE DEPARTMENT OF FINANCIAL SERVICES DIVISION OF STATE FIRE MARSHAL RULE CHAPTER: RULE CHAPTER TITLE: 69A-46, F.A.C. Fire Protection System Contractors and Systems RULE: RULE TITLE:
More informationDIVISION 21 FIRE SUPPRESSION FIRE SUPRESSION
DIVISION 21 FIRE SUPPRESSION 21 00 00 FIRE SUPRESSION 21 01 00 Operation and Maintenance of Fire Suppression 21 01 10 Operation and Maintenance of Water Based Fire Suppression Systems 21 01 20 Operation
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More information2012 OBC Changes. Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014
2012 OBC Changes Summary of key changes to Life Safety and Fire Protection Systems for CFAA January 22, 2014 2012 OBC New Sentence 3.2.4.2(6) Buildings interconnected by walkways permitted in Articles
More informationBox-in-Box Cold Storage Fire Protection Options
Box-in-Box Cold Storage Fire Protection Options FireAustralia TYCO Model ESFR-17 Dry Type Pendent Sprinkler Jeffrey Barkley Tyco Fire Protection Products Objective Common Box-inBox Cold Storage Challenges
More informationDIVISION 21 - FIRE SUPPRESSION
DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationNASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION
BUILDING PERMIT# Revised 6/30/15 AP# PERMIT # Cost $ Check# Receipt# NASSAU COUNTY FIRE PROTECTION PERMIT APPLICATION 5 TH EDITION (2014) OF THE FLORIDA BUILDING CODE IS IN EFFECT THE 2012 FLORIDA FIRE
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationPLAN REVIEW SUBMITTAL GUIDE
PLAN REVIEW SUBMITTAL GUIDE Plans, specifications and other construction documentation for the initial plan review should be as complete as possible at the time of submittal. Use this convenient guide
More informationSECTION WET PIPE FIRE PROTECTION SPRINKLER SYSTEM
SECTION 213100 WET PIPE FIRE PROTECTION SPRINKLER SYSTEM PART 1 - GENERAL 1.01 GENERAL REQUIREMENTS A. The requirements of the General Conditions and Supplementary Conditions apply to all work herein.
More informationFIRE DEPARTMENT DESCRIPTION OF SERVICE UNIT FEE I. INSPECTION FEE
I. INSPECTION FEE *1 A. HIGH-RISE INSPECTION. Each Floor $ 262.00 Commercial. B. HOTELS, MOTELS, RESIDENTIAL OCCUPANCIES 1 Hotels, Motels, Apartments and Condominimums 3-10 Units Each Building $ 204.00
More informationFIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY
FIRE INSPECTORS GUIDELINES FOR PLAN REVIEWS AND INSPECTIONS OF NEW CONSTRUCTION / ADDITIONS AND CHANGE OF OCCUPANCY PLAN REVIEWS SITE PLANS: 1) Access to buildings (Volume V NC Building Code sections 602.6.1
More informationEL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD
EL DORADO COUNTY REGIONAL FIRE PROTECTION STANDARD Installation of Residential Fire Sprinkler Systems STANDARD #C-002 EFFECTIVE 03-19-2009 PURPOSE: To ensure that sprinkler plans submitted for review contain
More informationBCCO TRAINING FOR CONTRACTORS
BCCO TRAINING FOR CONTRACTORS Printed or Saved Mygov Virtual Inspections PERMITS 2 APPLYING FOR PERMITS Please visit our Website at buildingcodecompliance.ocps.net for valuable information regarding the
More informationRecommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region
Recommended Amendments to the 2015 International Existing Building Code North Central Texas Council of Governments Region The following sections, paragraphs, and sentences of the 2015 International Existing
More informationSheetz Inc. Fire Protection Service Guidelines
Sheetz Inc. Fire Protection Service Guidelines Overview The following are guidelines for Sheetz Fire Protection Services for the 2016/2018 contract year. Each key area is listed below with the appropriate
More informationFreezing of Water-Based Fire Protection Systems
Risk Solutions Freezing of Water-Based Fire Protection Systems Freezing of water in fire protection piping can seriously compromise a property s fire protection. This report provides information on methods
More informationCarrollton Fire Rescue
Carrollton Fire Rescue Fire Prevention Division Guide for Construction 2016 edition 2 Carrollton Fire Rescue Prevention Division Table of Contents Fire Prevention Division... 3 General Guidelines... 4
More informationBackflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code
Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code Backflow Prevention Fire safety systems connected to a public water supply will require a backflow prevention device between
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationExisting Fire Protection Systems Description
21 0510 Existing Fire Protection Systems Description The existing system descriptions below are based on the best information available as of September 30, 2016. The designer shall verify on site all existing
More informationSecond Revision No. 20-NFPA [ Section No. 1.4 ] Supplemental Information. Submitter Information Verification. Committee Statement
Second Revision No. 20-NFPA 14-2015 [ Section No. 1.4 ] 1.4* Equivalency. Nothing in this standard is intended to prevent the use of systems, methods, or devices of equivalent or superior quality, strength,
More informationANTIFREEZE AND AUTOMATIC FIRE SPRINKLERS UPDATE. Presented by: Jerry Schultz The FPI Consortium, Inc. July 28, 2017
ANTIFREEZE AND AUTOMATIC FIRE SPRINKLERS UPDATE Presented by: Jerry Schultz The FPI Consortium, Inc. July 28, 2017 History What happened? NFPA Response Current Status OUTLINE HISTORY 1940 Non-Freezing
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationFIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.
15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.
More informationChapter 2: Definitions
FLORIDA BUILDING CODE Existing Buildings 6 TH Edition (2017) Code Changes based on the document provided by DBPR - 2014 and 6th Edition (2017) Florida Building Code Comparison JUMP TO CHAPTER (click chapter
More informationFire Sprinkler System Design and Installation Requirements
Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah
More informationWHEA FSE inspections.
WHEA FSE inspections www.jfahern.com FEC.02.03.05 Features of Fire Safety Buildings are protected from fire by a series of detection, notification and suppression devices Each feature of fire safety must
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationCOMPLIANCE ALTERNATIVES
CHAPTER 12 COMPLIANCE ALTERNATIVES SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter are intended to maintain or increase the current degree of public safety, health, and general welfare
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More informationPERFORMANCE COMPLIANCE METHODS
CHAPTER 13 PERFORMANCE COMPLIANCE METHODS SECTION 1301 GENERAL 1301.1 Scope. The provisions of this chapter shall apply to the alteration, repair, addition and change of occupancy of existing structures,
More informationFire System Impairment Policy
Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,
More information