1 Arc Fault Detection Device (AFDD) is an innovative automated equipment for prevention of fires from arcing in electrical circuits and electrical installations
2 Ltd. ECOLIGHT LLC ECOLIGHT is an innovative Russian manufacturer of LED lighting fixtures under ECOLIGHT brand. Since 2015, the company has developed and launched a new Arc Fault Detection Device (AFDD). The latest development will reduce the number of fires due to faults of electrical mains by more than 2 times. The main advantages of ECOLIGHT products are high quality, reliability and affordability. 2
3 Fire statistics In 2016, there were 139,700 fires in Russia, which killed 8,760 people, injured 9,909 people, and caused property damage for 14,324 bln rub. According to FSRI of the Ministry of Emergency of Russia, fires from electrical equipment countrywide include: 26%, at the enterprises of certain ministries and authorities; Share of fires from electrical installations reaches 38%; In residential buildings - 32%; In private houses up to 70% of fires is caused by electrical installations. Causes of fires as exemplified by Germany (2016) Lightning strike Electrical energy Explosion Arson Hot works Human factor Open fire Self-ignition Overheating Other/unknown Statistics of causes of electricity mains failures as exemplified by Denmark for 2016 Operational failure Loose connection Ageing Material defects Damage by rodents Insulation fault Damages and moisture attack 3
4 Main causes of fires in electric systems and mechanisms 1. Arcing at big transition resistance (BTR) as the main current cause of fires in electrical mains. 2. Inflammation from parallel arcing. 4
5 Arc Fault Detection Device (AFDD) AFDD is in fact the third stage of development of electrical mains protection devices, following automatic circuit breakers and RCDs. It is installed in the distribution board on DIN-rail. It is equipped with AFDD-I control device designed to configure and verify functioning at the places of operation. AFDDs identify arc in the protected circuit and automatically disconnect it from the mains. 5
6 Standard equipment for protection of electrical circuits To protect electrical line the automatic circuit breakers are used for overcurrent protection (hereinafter ACB, see GOST R ), as well as circuit breakers operated by differential current (RCD, see GOST R IEC ). Reaction of electrical mains protection devices on various types of arcing Protection device Series (BTR poor contact) Type of arcing Parallel Phase - neutral Parallel Phase - ground Automatic Circuit breaker Doesn t detect at all May actuate too late (with a limited short-circuit current) May actuate too late (with a limited short-circuit current) RCD Doesn t detect at all Doesn t detect at all May not detect (under pulsed nature of arcing) AFDD Disconnects the mains Disconnects the mains Disconnects the mains 6
7 Licenses, patents Энергоэффективная продукция «ЭКОЛАЙТ» AFDDs were successfully tested and are recommended for use, which is certified by the following expert opinions: No.137/15 dated November 20, 2015, issued by FSBEI HPE MSCU Institute of Integrated Safety in Construction; No.35/ dated September 15, 2015, issued by FSBEI HPE State Fire- Fighting Service Academy of the Ministry of Emergency Situations of Russia AFDD has received a Certificate No. TC RU C-RU.ME68.B of compliance with the requirements of the Technical regulations of the Customs union TR CU 004/2011 Concerning the safety of low-voltage equipment and TR CU 020/2011 Electromagnetic compatibility of technical means. Patents: 7
8 Expected benefits from the services Comparison of technical and economic characteristics of AFDDs developed by LLC ECOLIGHT with the products of the main competitors Parameters Products Technical and economic characteristics of the product Siemens 5SM6 Schneider Electric A9FDD225 AFDD manufactured by ECOLIGHT company Rated maximum current, A Availability on the Russian market Delivery under the order, the delivery time is three (3) months Not supplied Start-up of mass production is planned for 2018 Approximate price
9 Comparison of technical and economic characteristics of major competitors Manufacturer Products Type execution Rated current, A Size on the DIN-rail, у.е. Cause indication triggering Testing (manual / automatic) Average price (without shipping and customs fees) Additional Functions / Note Ecolight AFDD-С1-63 Single 63 2 Continuous Automatic 65 EUR Overvoltage trip with adjustable value of V Availability of a means of monitoring the operation area Siemens (OEZ) Schneider Electic ABB Hager Eaton (Doepke, Schrack Technik) 5SM Modular 16 2 After restarting Automatic 93,58 EUR 5SM Modular 40 2 After restarting Automatic 109,44 EUR 5SM Modular 16 3 After restarting Automatic 98,87 EUR 5SM Modular 40 3 After restarting Automatic 113,23 EUR A9FDB610 Single 10 2 No Manual 93,05 EUR A9FDB616 Single 16 2 No Manual 90,28 EUR S-ARC1 B10 Single 10 2 After restarting S-ARC1 B16 Single 16 2 After restarting Manual +Automatic Manual +Automatic 112,22 EUR 113,15 EUR 1. Tching off at a voltage greater than 275V 2. AV connections by bundling with Siemens 5SY30 or 5SY60 MCB 1. Switching off at a voltage greater than 275V 2. AV connections by bundling with Siemens 5SY, 5SL MCB or RCD connection when bundled with Siemens 5SU RCBO 1. Integrated AB, type C 2. Trip at a voltage greater than 400V, tripping time of 200ms 1. Integrated AB, type B 2. Switching off at a voltage greater than 275V 3. With a negative result of the self-test, the device flashes red-green, but does not turn off, and must be checked by a manual test. This contradicts clause 8.17 of standard and without a constant visual control of the indication may lead to a lack of reaction to the arc breakdown ARC910D Single 10 2 No Manual 110,81 EUR 1. Switching off at a voltage greater than 275V, time of switching-off 200ms ARC916D Single 16 2 No Manual 104,29 EUR 2. Integrated AB, type B AFDD- 10/2/B/003-Li/A AFDD- 16/2/B/003-Li/A Single Single No No Automatic Automatic 125,1 EUR 119,69 EUR 1. Integrated AB, type B 2. Switching off at a voltage greater than 270V 3. Integrated RCD, current difference 0,03A 4. Overheating control 9
10 Project support In July 2017, the working group of the Expert Council of the Agency for Strategic Initiatives (ASI) reviewed and approved for support the business project "Development of production of automated spark protection devices (AFDD) for preventing fires in electrical networks and electrical installations". In November 2016, the State Budgetary Institution of Moscow, the Moscow City Innovation Agency, decided to include the products of ECOLIGHT Ltd. in the list of innovative, high-tech products and technologies. The AFDD project is a participant in the Skolkovo Innovation Center. 10
11 Benefits from introduction For citizens For city government Prevention of fires, which may cause serious physical and property damage Affordable price AFDD is an import substituting and competitive product in Russia Increase in jobs Increase in the tax base of Moscow 11
12 Contacts ECOLIGHT Ltd. Off. 721 A, bld. 17, Vereyskaya str., , Moscow
5SM6 AFD unit preventive, proven, standard-compliant
The 5SM6 AFD unit order now! 5SM6011-2 AFD unit (16 A) Miniature circuit breaker 1+N, 6 ka, 1 MW (16 A) MCB 1+N,1 MW 10 A 5SY6010-6 5SY6010-7 MCB 1+N, 1 MW 13 A 5SY6013-6 5SY6013-7 MCB 1+N, 1 MW 16 A 5SY6016-6
More informationA BITESIZED GUIDE TO AFDDs AND FIRE PROTECTION
A BITESIZED GUIDE TO AFDDs AND FIRE PROTECTION Bitesize III INTRODUCTION CONTENTS. INTRODUCTION DEFINING WHAT IS MEANT BY DANGER THE BASIC PRINCIPLES OF SAFETY - BS7671 TOO MANY FIRES FROM ELECTRICAL EQUIPMENT
More informationWelcome to Hager Presentation
Welcome to Hager Presentation Topics Intro to Hager Group Circuit Protection Enclosures Q&A IIEE Manila 4 th August 17 13.03.2009 2 Company presentation Who we are Hager Group is a leading provider of
More informationBringing power to life. GUIDE TO ARC FAULT DETECTION DEVICES (AFDD)
Bringing power to life. GUIDE TO ARC FAULT DETECTION DEVICES (AFDD) November 2017 COMPANIES INVOLVED IN THE PREPARATION OF THIS GUIDE Eaton Electric Limited 270 Bath Road, Slough, Berkshire SL1 4DX Tel:
More informationArc Fault Detection Devices. 18th Edition - We re ready
Arc Fault Detection Devices 18th Edition - We re ready ARC FAuLT DETECTION DEvICES & THE WIRING REGuLATIONS The 18th edition wiring regulations (BS7671) sets out requirements for electrical installations
More informationHow Arc Fault Detection Devices Minimize Electrical Fire Threats
How Arc Fault Detection Devices Minimize Electrical Fire Threats by Jean-Francois Rey, Pierre Dominique Socquet-Clerc, Simon Tian, and Zakaria Belhaja Executive summary Arc faults in low voltage electrical
More informationSiemens Hardware. Better to play it safe! SENTRON protection devices for modern electrical installations
The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the
More informationCERTIFICATE OF CONFORMITY No. TC RU С- DE.AB72.B.02315 Series RU No. 0492042 CERTIFICATION AUTHORITIES Certification authority of products of "Scientific and Technical Center "Techno-standard Limited Liability
More informationE DATA SHEET
ISO 9001 UK-VK SWITCHING UNIT UK-VK rev.10 UK-VK rev.11 UK-VK rev.1 UK-VK rev.13 UK-VK rev.14 UK-VK rev.15 4641.00 E DATA SHEET 1 MAIN SPECIFICATIONS 1.1 General 1.1.1 This datasheet is applicable to the
More informationArc Fault Detection Devices (AFDDs) Protecting People and Property
Arc Fault Detection Devices (AFDDs) Protecting People and Property Singapore Standard : CP5 Code of practice for electrical installations - Foreword 2 BS 7671 : the 18 th Edition report Short Brief 3 BS
More informationArc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance
Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides
More informationArc Fault Protection System D1000
Arc Fault Protection System D1000 Improve personnel safety Reduce damage Avoid costly repairs Minimize production downtime www.selco.com Segments & applications In all areas where electrical energy is
More informationGE Industrial Solutions. Residential Electronic Circuit Interrupters
GE Industrial Solutions Residential Electronic Circuit Interrupters Dual Function Circuit Interrupter (DFCI) Provides ground fault and arc fault circuit protection in one unit The 2014 National Electric
More informationD1000 Arc-fault Protection System
D1000 Arc-fault Protection System Improve personnel safety Reduce damage and minimize costly repairs Minimize production downtime www.selco.com D1000 Arc-Fault Protection system Efficient protection of
More informationwhole house safety Pocket Guide to Whole House Safety Siemens Energy & Automation, Inc Old Milton Parkway Alpharetta, GA 30005
Pocket Guide to Whole House Safety whole house SAFETY whole house Siemens Energy & Automation, Inc. 3333 Old Milton Parkway Alpharetta, GA 30005 1-800-964-4114 info.sea@siemens.com www.sea.siemens.com/afci
More informationArc Fault Protection ARCON ARCON. The Lightning Fast Airbag for Your Switchboard.
Arc Fault Protection ARCON ARCON The Lightning Fast Airbag for Your Switchboard. The continuous supply of electrical energy is an inherent requirement of today s society. The power outages in North America
More informationPocket Guide usa.siemens.com/afci
Whole House Safety Pocket Guide usa.siemens.com/afci Use electricity safely everywhere in your home. What causes arc faults? Arc faults can occur for many reasons and anywhere in a home s electrical system.
More informationBringing power to life. TECHNICAL BULLETIN RESIDUAL CURRENT DEVICE (RCD) SELECTION
Bringing power to life. TECHNICAL BULLETIN RESIDUAL CURRENT DEVICE (RCD) SELECTION November 2017 COMPANIES INVOLVED IN THE PREPARATION OF THIS TECHNICAL BULLETIN Eaton Electric Limited 270 Bath Road, Slough,
More informationPocket Guide to Whole House Safety. Whole house safety
Pocket Guide to Whole House Safety Whole house safety Use electricity safely everywhere in your home. Most of us take the safety of our home s electrical system for granted. And yet faulty electrical
More informationResidual Current Devices
Residual devices F200 Series UL 1053 Residual devices F200 Series Residual Current Devices Description The F200 Series residual devices offer a wide range of product for all of your fault protection needs.
More informationI N D I V I D U A L SWITCH G E A R
INDIVI DUAL SWITCH GEAR POWER HAS TO FLOW A. Horstmann Industrial Engineer, CEO The power supply is the neuralgic point in every production line and every large technical organism. If it doesn t work properly,
More informationREA 105 Arc Protection Module. Operator s Manual
REA 105 1MRS 751005-MUM Issued: 20.04.1998 Version: B2/26.5.2000 Checked: Approved: REA 105 We reserve the right to change data without prior notice. Contents: 1. General...4 1.1. Features...4 2. Safety...5
More informationA. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationMSSI Electrical introduction. 14 March 2016 Light and Building Markus Harlinghausen, CAPIEL Vice President
MSSI Electrical introduction 14 March 2016 Light and Building Markus Harlinghausen, CAPIEL Vice President CAPIEL is the European association of manufacturers of electrical switchgear and control gear Objective:
More informationFault Current Monitoring in Electrical Installations
Fault Current Monitoring in Electrical Installations Foundations, Applications and Methods of Measuring Residual Current in AC and DC Systems - With Residual Current Monitors (RCMs) according to IEC 62020
More information7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management
Reyrolle Protection Devices 7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management 7XG3120 - Arc Fault Monitor Relay The over-current caused by an arc is, due to its resistance, lower than the over-current
More informationElectrical Safety Through Design. Mersen EP formerly Ferraz Shawmut
Electrical Safety Through Design Mersen EP formerly Ferraz Shawmut Agenda Who is Mersen? Selective Coordination Code Requirements Coordination Made Easy Mitigating Arc Flash Energy on Transformer Secondary
More informationImprovement of HEMP Resilience of Automatic Fire Suppression System
Improvement of HEMP Resilience of Automatic Fire Suppression System Vladimir Gurevich Central Electric Laboratory, Israel Electric Corp., POB 10, Haifa 31000, Israel Abstract - Automatic fire suppression
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationIndex Arc Guard Systems. Arc Guard Systems. Arc Guard Systems Industrial Automation Supply - Tel:
Systems Index Systems - Systems Systems...1 -.16 General information Description...1 System description...2 Overview...3 Ordering details Arc monitor with detectors...4 Current sensing unit...5 Technical
More informationCat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE
Cat. N STOP & GO automatic resetting 87045 LIMOGES Cedex - FRANCE Telephone : + 33 5 55 06 87 87 Fax: + 33 5 55 06 88 88 Cat. N (s) : 4 062 88 / 4 062 89 CONTENTS PAGE 1. Description - Use... 1 2. Product
More informationMains Power Filter 970MF10 970MF20. Installation Instructions
Mains Power Filter Installation Instructions and Table of Contents 1.0 Warnings... 3 2.0 Introduction... 3 3.0 Quick Installation Overview... 3 4.0 Typical Installations... 3 5.0 Protection Concepts...
More informationUniversal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01
Gamma instabus Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG1 528-1DB01 Technical Product Information Universal Dimmer for switching or dimming of dimmable lamps Supports dimmable lamps including
More informationElectrical Energy department
Al-Balqa Applied University Power systems Protection course Dr Audih al-faoury Electrical Energy department 2018-2019 Department of Electrical Energy Engineering 1 Part 1 Power System protection Introduction
More informationSPECIFICITIES OF SUPERVISION OF OVERPRESSURIZED EQUIPMENT
FEDERAL ENVIRONMENTAL, INDUSTRIAL AND NUCLEAR SUPERVISION SERVICE OF RUSSIA SPECIFICITIES OF SUPERVISION OF OVERPRESSURIZED EQUIPMENT V. Chernyshev Deputy Head Department of State Construction Supervision
More information17 TH APRIL 2017 Switch Board Monitoring Protecting Switchboard. Courtesy of ABB. Paul Lee
17 TH APRIL Switch Board Monitoring Protecting Switchboard Courtesy of ABB. www.fengshengelectric.com.sg Paul Lee Agenda 1. Introduction 2. IEC 61439 3. Why Switchboard Monitoring 4. Switchboard Monitoring
More informationIconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW. Installation Instructions REGISTERED DESIGN
Iconic Series ControlLink Pushbutton 41EPBM-VW PDL356PBSS-VW Installation Instructions REGISTERED DESIGN Copyright Notice The concepts, products and designs described in this document are the subject of
More informationUnderstanding Your Options: AFCI Protection and the 2015 CE Code
Understanding Your Options: AFCI Protection and the 2015 CE Code November 25, 2014 Eaton 2008 Eaton Corporation. All rights reserved. Classifying An Arc Fault Operational Arcs - occur in a properly functioning
More informationDIRECTIVE NO: D-B
DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting
More informationNFEC FIRE SAFETY SEMINAR Krish Mysore
NFEC FIRE SAFETY SEMINAR 2018 Krish Mysore krish.mysore@schneider-electric.com Agenda 1 Electrical Fire Stats 2 Types of Electrical Fires 3 Electrical Risk Management 4 Electrical Health Check Assessment
More information3. RCCB (residual current operated circuit-breaker without integral overcurrent protection)
RESIDUAL CURRENT DEVICE (RCD) - Contents 1. Introduction 2. General 3. RCCB (residual current operated circuit-breaker without integral overcurrent 4. RCBO (residual current operated circuit-breaker with
More informationPar 16 with GU10 Socket
User manual Par 16 with GU10 Socket Table of contents 1. Safety instructions... 3 1.1. FOR SAFE AND EFFICIENT OPERATION... 3 2. Technical Data... 4 3. Description... 4 3.1. Introduction... 4 3.2. Safety
More informationInvestment Offer. I. General information about the project
Investment Offer I. General information about the project 1. Project name: "Development of the manufacture in order to develop new types of cable products and Ropes of wires " 2. Project branch: The Ministry
More informationABB Medium Voltage Days MEA 2016 Proactive safety ABB medium-voltage switchgear
ABB Medium Voltage Days MEA 2016 Proactive safety ABB medium-voltage switchgear Technical session Title of presentation Speaker name Speaker title Company name Location Martin Kropf Head of Local Product
More informationDEB71. Earth Leakage Monitoring Relay. Benefits. Description
Earth Leakage Monitoring Relay Benefits Adjustable trip level. Adjustable leakage threshold from 30mA to 5A or from 300mA to 30A. 2 outputs. Two relay outputs provide, besides the alarm signal an additional
More informationO KEY GROUP ANNOUNCES OPERATING RESULTS FOR Q3 AND 9M 2017
Press Release 27 Oct 2017 O KEY GROUP ANNOUNCES OPERATING RESULTS FOR Q3 AND 9M 2017 O KEY Group S.A. (LSE: OKEY, the Group ), one of the leading Russian food retailers, announces its unaudited operating
More informationDevelopment of standards for MV Switchgear for Arc Flash protection. ABB Group May 20, 2013 Slide 1
Development of standards for MV Switchgear for Arc Flash protection May 20, 2013 Slide 1 Development of standards for MV Switchgear for Arc Flash protection Bryan Johnson ABB South Africa Shaping the world
More informationContents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7
Practical Power System Protection for Engineers and Technicians Contents Preface ix Chapter 1 Need for protection 1 1.1 Need for protective apparatus 1 1.2 Basic requirements of protection 2 1.3 Basic
More informationIndependent, accredited testing station Member laboratory of STL and LOVAG
Independent, accredited testing station Member laboratory of STL and LOVAG TYPE TEST REPORT NO. 3096.2081034.859 GSAB Elektrotechnik GmbH Lindenstraße 23 99718 Greußen GERMANY GSAB Elektrotechnik GmbH
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60364-4-43 Second edition 2001-08 Electrical installations of buildings Part 4-43: Protection for safety This English-language version is derived from the original bilingual
More informationArc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk
Arc Flash Mitigation Solutions: A Proactive Approach To Arc Flash Risk Unrestricted Siemens Industry, Inc. 2015 All rights reserved. usa.siemens.com/arc-flash Everyone is concerned about the risk of Arc
More informationPOWER SYSTEM INCIDENT REPORT: TRIP OF DOUBLE CIRCUIT MACKAY- COLLINSVILLE TEE - PROSERPINE 132 KV LINES AND STRATHMORE SVC ON 29 DECEMBER 2010
POWER SYSTEM INCIDENT REPORT: TRIP OF DOUBLE CIRCUIT MACKAY- COLLINSVILLE TEE - PROSERPINE 132 KV LINES AND STRATHMORE ON 29 PREPARED BY: Electricity System Operations Planning and Performance FINAL Disclaimer
More informationWHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY
WHITE PAPER: ARC FAULT CIRCUIT INTERRUPTERS EXPANDING HOME SAFETY Expanding Home Safety Page 2 INTRODUCTION Smoke alarms, fire extinguishers, emergency escape ladders these are all proven methods for making
More informationDANFOSS OPTYMA PLUS INVERTER UNITS
Optyma Plus Inverter Condensing Units Danfoss Optyma Plus Inverter Units are designed with the unique benefits of stepless inverter scroll technology resulting in a 20-30% higher energy efficiency in a
More informationINSTRUCTION MANUAL EPH-121 CONTENTS
INSTRUCTION MANUAL EPH-121 CONTENTS SAFETY PRECAUTIONS 1 NAME OF COMPONENT PARTS 5 HOW TO ASSEMBLE THE FRAME 6 OPEN AND CLOSE THE PANELS 7 OPERATION 9 TIMER OPERATION 10 SHUTDOWN 11 ROUTINE MAINTENANCE
More informationMajor Fault Caused by Stator Winding Circuit Ring Failure
Case study Major Fault Caused by Stator Winding Circuit Ring Failure Joël Pedneault-Desroches, P. Eng. Presentation Outline Introduction Inspection report Chronology of events Repair Conclusion 2 Introduction
More informationData Bulletin. Determining the Cause of AFCI Tripping Class 760
Data Bulletin 0760DB0204 06/2002 Cedar Rapids, IA, USA Determining the Cause of AFCI Tripping Class 760 Retain for future use. INTRODUCTION DANGER HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION This document
More informationLOCAL STORM DATA SHEET
LOCAL STORM DETECTION > Storm detection: who is involved? > Regulations, storm phases and classification of detectors > ATSTORM local thunderstorm detector by measurement of electric field > STORM DETECTION:
More informationMeasurement of Safety Integrity of E/E/PES according to IEC61508
Measurement of Safety Integrity of E/E/PES according to IEC61508 Mr. Chen Zhenkang TUV Rheinland Singapore 18. May. 2018 Singapore World Metrology Day 2018 1 Agenda 1. TÜV Rheinland: a Certification Body
More informationDR J H BURGOYNE AND PARTNERS LLP FORENSIC SERVICES
DR J H BURGOYNE AND PARTNERS LLP FORENSIC SERVICES ROSEPARK CARE HOME Investigation of the cause of the Fire on 31 January 2004 POLICE CONTACTED BURGOYNES Initial contact, evening of Saturday 31 January
More informationINVESTMENT PROJECT. Implementation by: JV UKRINTERM COMPANY LIMITED
INVESTMENT PROJECT Organization of serial production of heat pumps, heat substations, advanced heating modules for modernization of heat supply systems of housing and communal services Implementation by:
More informationCombination Type AFCI
Combination Type AFCI Evolution of the Arc Fault Circuit Interrupter www.usa.siemens.com/afci 2 Alarming Statistics According to the U.S. Fire Administration (USFA), an estimated 67,800 fires, 485 deaths,
More informationAllianz Engineering Inspection Services Ltd. Electrical Services. Product Information
Allianz Engineering Inspection Services Ltd Electrical Services Product Information Electrical Testing and Inspection Services The Electricity at Work Regulations (EaWR) states that all electrical systems
More informationBU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24
INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24 1/8 More information than that reported in this
More informationWATER BATH MODEL TBS451PA OPERATION MANUAL
WATER BATH MODEL TBS451PA AC1120V OPERATION MANUAL No. TS45P-0601 Table of Contents Page 1. Safety instructions 1 2. Specifications 4 3. Wiring diagram & Parts 5 4. Before use 6 5. External views 9 6.
More informationCNS CENTRIFUGAL MULTISTAGE WATER DESCALING PUMPS BB4 TYPE API 610 ENGINEERING FLOW SOLUTIONS
CNS CENTRIFUGAL MULTISTAGE WATER DESCALING PUMPS BB4 TYPE API 610 ENGINEERING FLOW SOLUTIONS CNS Pumps For Water Descaling Description The CNS series pumps are centrifugal, multistage, horizontal, with
More informationPress Release. Short profile Beckhoff. Short profile February 2009 Page 1 of 6
Page 1 of 6 Short profile Beckhoff Beckhoff implements open automation systems based on PC Control technology. The product range covers Industrial PCs, I/O and Fieldbus Components, Drive Technology and
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62873-3-1 Edition 1.0 2016-09 Residual current operated circuit-breakers for household and similar use Part 3-1: Particular requirements for RCDs with screwless-type terminals
More informationRoom thermostat with Auto Timer, independent DHW
s 1 423 Room thermostat with Auto Timer, independent DHW for heating systems RDE100.1 DHW Room temperature control 2-position / TPI control with On/Off output for heating Optimum Start / Stop Comfort,
More informationThe complete residential solution
The complete residential solution Circuit Protection Resi MAX Clipsal.com/ResidentialProtection Contents What s new in final distribution residential...3 Resi MAX gives you the entire solution...4 Essential
More informationGB/T / IEC 62423:2009
Translated English of Chinese Standard: GB/T22794-2017 www.chinesestandard.net Buy True-PDF Auto-delivery. Sales@ChineseStandard.net GB NATIONAL STANDARD OF THE PEOPLE S REPUBLIC OF CHINA ICS 29.120;29.120.50
More information/ sicam SICAM Safety Full functionality for safety-critical applications Answers for infrastructure and cities.
www.siemens.com / sicam SICAM Safety Full functionality for safety-critical applications Answers for infrastructure and cities. More safety for your automation system Protect people and the environment
More informationPowerWave 2 Busway System
PowerWave 2 Busway System Guide Specifications (Revision 004, 11/17/2017) 1 GENERAL 1.1 Summary This specification covers the electrical characteristics and general requirements for a continuous opening,
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60364-4-44 Edition 1.1 2003-12 Edition 1:2001 consolidated with amendment 1:2003 Electrical installations of buildings Part 4-44: Protection for safety Protection against voltage
More informationRoom thermostat with Auto Timer, Option External Input
s 1 422 Room thermostat with Auto imer, Option External Input for heating systems RDE100.. Room temperature control 2-position control with On/Off output for heating Comfort, Economy, Auto timer and Protection
More informationEN Electrical Equipment of non-electric appliances for household and similiar purposes Safety requirements
EN 50165 Electrical Equipment of non-electric appliances for household and similiar purposes Safety requirements J. Stenger CLC/TC61/WG3 24. April 2002 1 History Gas-Appliance Directive 96/306/EEC Annex
More information1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection
Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication
More informationCeiling-Mounted Motion Detector. 752/CD, 752/CP, 752/CU and 752/Cx180. Installation Instructions
Ceiling-Mounted Motion Detector 752/CD, 752/CP, 752/CU and 752/Cx180 Installation Instructions Contents 1.0 Description...3 1.1 Contents of the Box...3 2.0 Safety...4 3.0 Coverage Patterns...4 3.1 PIR
More informationBATHROOM TRENDS - October 2017 INTERNATIONAL COMPARISON. Overview of bathroom trends in Houzz Inc.
2017 BATHROOM TRENDS - INTERNATIONAL COMPARISON October 2017 Overview of bathroom trends in 2016-17 Big Ideas LAST UPDATED MORE THAN 15 YEARS AGO In most surveyed countries,* at least half of bathrooms
More informationSIPROTEC Products and Solutions for Protection Systems
SIPROTEC Products and Solutions for Protection Systems Georg Korger, Head of Protection Technology, Energy Automation, Division Energy Management siemens.at/future-of-energy SIPROTEC Products and Solutions
More informationProject planning (original) EN. Functional safety. Inverter i550-cabinet kw
Project planning (original) EN Functional safety Inverter i550-cabinet 0.25... 45 kw This page intentionally left blank! Contents Contents Safety instructions 4 Basic safety measures 4 Residual hazards
More informationINTERNATIONAL STANDARD
IEC 61892-7 INTERNATIONAL STANDARD Edition 2.0 2007-11 Mobile and fixed offshore units Electrical installations Part 7: Hazardous areas INTERNATIONAL ELECTROTECHNICAL COMMISSION PRICE CODE XA ICS 47.020.60
More informationLABORATORY OVENS MODELS INCLUDE: TO-152G & TOH-152G TO-152F & TO-235F DEHYDRATING OVENS MODELS INCLUDE: TD-150F TD-330F TD-500F
0 LABORATORY OVENS MODELS INCLUDE: TO-152G & TOH-152G TO-152F & TO-235F DEHYDRATING OVENS MODELS INCLUDE: TD-150F TD-330F TD-500F WITH WEST 6100 CONTROL 1 IMPORTANT INFORMATION This manual contains operating
More informationMTRA-FSP Level Control Relay. Installation & Operation Manual
MTRA-FSP Level Control Relay Installation & Operation Manual This Manual is the support documentation for the installation, commissioning and operation of the MTRA-FSP Level Control Relay. Document Revision
More informationEngineering Procurement Construction Management
ADVANCED INTELLECTUAL INFRASTRUCTURE & INDUSTRY Engineering Procurement Construction Management AVATRi S&T LLC AVATRI S&T LLC Head office 1, build 1, office 206 str. Malaya Yushunskaya Moscow, Russia 117303
More informationPREVENTIVE PROTECTION PROTECCIÓN PREVENTIVA
PREVENTIVE PROTECTION PROTECCIÓN PREVENTIVA R PREVENTIVE PROTECTION ATSTORM v2 is a storm detector that measures the environmental electric field. It is fully automatic, without mobile parts, robust and
More informationCompetence Center in Electric Heating. February 2017
Competence Center in Electric Heating February 2017 Factsheet SST Group is the largest producer of electric heating cables and heat tracing solutions in Europe. Founded in 1991 1300 employees 4 own plants
More informationAutomation, Software und Informationstechnologie
Automation, Software und Informationstechnologie Report on the type approval of the Adjustable Frequency AC Drives PowerFlex 753 and 755 of Rockwell Automation Inc. Bericht-Nr.: 968/EZ 334.00/08 Datum:
More informationInterrupted Ignition Series Oil Primary Control
Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products
More informationCircuit Protector. GCP Series. Features. Electromagnetic Overcurrent Protection. Approvals. AC/DC Dual Voltage. Easily Identified ON/OFF Indicator
Circuit Protector GCP Series Features Electromagnetic Overcurrent Protection Overcurrent is prevented by an electromagnet, which is more appropriate and effective for circuit protection than the thermostatic
More informationELECTRICAL PANEL SAFETY ALERT I N S T I T U T E
ELECTRICAL PANEL SAFETY ALERT CONSUMER SAFETY I N S T I T U T E Dangerous Panels brochure.indd 1 9/29/08 11:41:48 AM The Electrical Panel The Heart of a Home s Electrical System The home s electrical system
More informationHeating and ventilation of the contemporary warehouse complexes
Heating and ventilation of the contemporary warehouse complexes Е. Shilkrot, Ph.D.,P.E., Head of the Laboratory A. Strongin, Ph.D.,P.E., Technical Director I. Agafonova, P.E., Head of the Designer Department
More informationRADIOCOMMUNICATIONS (EMC STANDARDS) NOTICE 2004 No. 2
RADIOCOMMUNICATIONS (EMC STANDARDS) NOTICE No. 2 Pursuant to regulation 32(1)(a), (b), (c), (d) and (j) of the Radiocommunications Regulations 2001, the Chief Executive, Ministry of Economic Development,
More informationIndustrial & Commercial Thermal BCU 580
Industrial & Commercial Thermal BCU 580 Burner control units For monitoring and controlling modulating or staged burners for multiple burner applications with a central air supply For directly ignited
More informationBasic Ex products / Zone 1, 21
Basic Ex products Basic Ex products / Zone 1, 21 Dear partners, Our products are intended for use in potentially explosive atmospheres of gases, vapors and dust in industries such as refineries, offshore
More informationBurner control units BCU 560, 565
Burner control units BCU 560, 565 roduct brochure GB 6 Edition 07.15 For monitoring and controlling modulating or staged burners for multiple burner applications with a central air supply For directly
More informationProduct Specifications 4 Breaker Main Disconnect Panel with Undervoltage Trip
NOVA Energy & Automation Product Specifications 4 Breaker Main Disconnect Panel with Undervoltage Trip Model NEAS-44125-G-UVR-C 03 January 2012 Product Description 1. Standard Applications The Nova 4 Breaker
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 62927 Edition 1.0 2017-07 colour inside Voltage sourced converter (VSC) valves for static synchronous compensator (STATCOM) Electrical testing INTERNATIONAL ELECTROTECHNICAL
More informationWiseBath WSB Shaking Water Bath Operation Manual (Version 1.4.0)
WiseBath WSB Shaking Water Bath Operation Manual (Version 1.4.0) written for Model WSB-18/-30/-45 Contents Page 1. Safety Instructions........ 3 2. Before Use...... 8 3. Introduction... 9 4. Package Contents...
More information2014 NEC for. Understanding the. AFCI protection AFCI code compliant safety. Eaton is a registered trademark.
2014 AFCI code compliant safety Understanding the 2014 NEC for AFCI protection Eaton is a registered trademark. All other trademarks are property of their respective owners. Eaton 1000 Eaton Boulevard
More information