Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI

Size: px
Start display at page:

Download "Technical Committee on Electrical Equipment Evaluation. ROC Meeting Agenda September 28-29, 2010 Providence, RI"

Transcription

1 Technical Committee on Electrical Equipment Evaluation ROC Meeting Agenda September 28-29, 2010 Providence, RI Item Call to Order Item Introductions Item Staff Remarks Item Approval of January 22, 2010 ROP Meeting Minutes Item Review of Task Group Assignments and Work Item Processing of Public and Committee Comments Item Old Business Item New Business Item Adjourn

2 Report on Comments June 2011 NFPA Log #1 EEE-AAA Technical Correlating Committee on National Electrical Code, The Technical Correlating Committee advises that Chapter Scope statements are the responsibility of the Technical Correlating Committee and the Technical Correlating Committee Accepts the actions of the Technical Committee. In addition, the Technical Correlating Committee directs that the Technical Committee consider the following actions within this proposal: 1) Review the entire document and revise it to comply with of the NFPA Style Manual which states that subdivisions shall contain at least two subdivisions. 2) In section 1.2, consider dividing the section into a purpose section and an application section to correlate with the NFPA 791 document. 3) Revise section 3.1, General, to include subsections and in accordance with the NFPA Style Manual, section ) In 3.3.1, the Technical Correlating Committee requests that the Technical Committee consider using the 2011 NEC definition of "Equipment. This is a direction from the Technical Correlating Committee on National Electrical Code in accordance with and of the Regulations Governing Committee Projects. 1

3 Report on Comments June 2011 NFPA Log #11 Chuck Mello, Underwriters Laboratories Revise the text from the ROP draft to read as follows. The This provisions of this standard shall address those requirements for the qualifications and competency of a body performing field evaluations on electrical products and assemblies with electrical components. These requirements shall be are based on ISO/IEC Guide 65 and ISO/IEC with adaptation for the unique characteristics of field evaluations. A field evaluation body (FEB) meeting the requirements of this standard shall be considered competent to perform field evaluations. These requirements shall apply to both the initial and continued competency of FEBs. The revised text provides better clarity to the user on the scope. The removal of the word those and changing the term qualifications to singular is to add clarity that this standard is the basis for qualification of third party testing bodies as a FEB. Section was revised to return this text to a statement of fact as opposed to establishing a requirement as permitted in the NFPA Manual of Style section This document is establishing the basis for the requirement and only used the ISO/IEC documents as a foundation. In the future there may be other standards that may be applied and this permits that expansion without limiting the technical committee to just these two documents. 2

4 Report on Comments June 2011 NFPA Log #12 Chuck Mello, Underwriters Laboratories Revise the text from the ROP Draft to read as follows: This standard shall provide the requirements for the competency of a FEB and for the recognition of an FEB by an authority having jurisdiction or other recognition body. in the application of evaluating the conformance of electrical equipment to the companion document. The revised text addresses the comments made during the balloting during the ROP process. In addition these revisions along with a companion comment to add a section 1.3 for application address the TCC comment number 2 to Proposal

5 Report on Comments June 2011 NFPA Log #22 Kenneth J. Rempe, Siemens Industry Inc Revise text to read as follows: This standard shall provide the requirements for the recognition of an FEB by an Authority Having Jurisdiction in the application of evaluating the conformance of electrical equipment to the companion document, NFPA 791, which will promote safety to life and property. The purpose of this document shall provide the requirements for applicants or third parties in applying for the services of an FEB, and any subsequent appeals, complaints and disputes on the evaluation report. The TCC recommended consideration of correlating the Purpose and Application of this document with the NFPA 791 document. In it is not clear if the author of [790-3] intended for the underlined text to be deleted from the original document, since it was not deleted. It has been added back for consideration by the Technical Committee has been added to the Purpose, since applicants and users of the Services of an FEB also have requirements and remedies afforded by this standard. Reference companion proposal for

6 Report on Comments June 2011 NFPA Log #26 Wendell Whistler, Intertek Testing Service This standard shall provide the requirements for the recognition of a Field Evaluation Body by an Authority Having Jurisdiction in the application of evaluating the conformance of electrical equipment to the companion document This words appear to only allow use of this document by the Authority Having Jurisdiction 5

7 Report on Comments June 2011 NFPA Log #23 Kenneth J. Rempe, Siemens Industry Inc Add text to read as follows: An organization or part of an organization that desires to be recognized as an FEB is subject to a standardized application and review by an Authority Having Jurisdiction. The requirements of this Standard will provide a more consistent application process to an Authority Having Jurisdiction, and improve the evaluation and recognition of FEB s that are competent to conduct Field Evaluations. Applicants who require Certification, Listing, or Evaluation of equipment, or systems before energizing will have an approved method to document the compliance to safety standards and final approval by the Authority Having Jurisdiction. The TCC recommended consideration of correlating the Purpose and Application of this document with the NFPA 791 document. The added text provides the intent to apply this Standard to Field Evaluation Bodies applications, review by Authorities Having Jurisdiction, and Applicants for services by the FEB. This provides a level of correlation to NFPA 791 as recommended by the TCC comment. Reference companion proposal for

8 Report on Comments June 2011 NFPA Log #13 Chuck Mello, Underwriters Laboratories Add the following text from the ROP Draft section 1.2 as new section 1.3. This standard shall be used by FEB s as the basis to seek recognition by an authority having jurisdiction or other recognition body in the application of evaluating the conformance of electrical equipment to the companion document. The text removed from section 1.2 of the ROP Draft was revised to provide complete sentences and for clarity. The revision resolves the TCC comment number 2 on Proposal

9 Report on Comments June 2011 NFPA Log #4 Chuck Mello, Vacouver, WA Revise text to read as follows: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA NFPA 791,, 2012 edition. Reserved The NFPA Manual of Style paragraph prohibits recommended practices from being referenced in a standard; therefore, NFPA 791 cannot be referenced in the body of the document as it is a recommended practice. This effectively deletes Section 2.2 since there are no NFPA documents now referenced in the main body of the document. The reference is deleted and the term reserved put in place in accordance with the NFPA Manual of Style paragraph The reference to NFPA 791 was moved to the Annex as A and Annex D.1.1 already has the necessary informational reference for NFPA 791 as provided in the ROP Draft. The changes to Clause to delete the reference to NFPA 791 and create the Annex statement are in a companion comment. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 8

10 Report on Comments June 2011 NFPA Log #24 Kenneth J. Rempe, Siemens Industry Inc Revise definition to read as follows: Any device, appliance, or machine that generates, conducts, or utilizes electrical energy. A general term, including material, fittings, devices, appliances, luminaires, apparatus, machinery, and the like used as a part of, or in connection with, an electrical installation. [ 2011] The TCC recommended consideration of this Definition from the 2011 NEC. The term Electrical is an adjective intended to describe or modify a specific kind of equipment. The terms equipment and electrical equipment are used many times in the NEC and NFPA 79, with only the definition as modified above in both documents. It seems appropriate to change this definition to Equipment as requested by the TCC. 9

11 Report on Comments June 2011 NFPA Log #14 Chuck Mello, Underwriters Laboratories Add the definition of Equipment to read as follows: A general term, including fittings, devices, appliances, luminaires, apparatus, machinery, and the like used as a part of, or in connection with, an electrical installation. The definitions following this would be renumbered accordingly. This comment does not alter the existing definition for electrical equipment as published in the ROP Draft. The addition of this definition in NFPA 790 will make it consistent with the companion document NFPA 791 that has a definition of electrical equipment developed by the Technical Committee and the standard definition equipment taken from the NEC. NFPA 790 uses both the term equipment individually and the phrase electrical equipment several times throughout the document. The definition of equipment provided in this comment is the definition from the 2008 NEC with the accepted change that will appear in the 2011 NEC. The change in the NEC is the deletion of the term material which is vague and generally speaking field evaluations cannot be completed on materials. The use of this definition aligns this document with the NEC. Acceptance of this comment may require moving to section 3.2 and renumbering all succeeding definitions. 10

12 Report on Comments June 2011 NFPA Log #5 Chuck Mello, Vacouver, WA Revise to read as follows: Equipment or materials to which has been attached a label, symbol, or other identifying mark of a FEB. Application of the label the the FEB indicates indicating the equipment or materials were evaluated and found to comply with requirements as described in an accompanying field evaluation report. The revised text corrects a typographical error with the term the used twice in a row. The revisions also put this definition into one single sentence statement which provides more clarity in the use of the term Field Labeled. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 11

13 Report on Comments June 2011 NFPA Log #3 EEE-AAA Technical Correlating Committee on National Electrical Code, The Technical Correlating Committee directs that the committee reconsider this definition with respect to the use of the term "adequate", and also reconsider the list of organizations included in the definition. This is a direction from the Technical Correlating Committee on National Electrical Code in accordance with and of the Regulations Governing Committee Projects. 12

14 Report on Comments June 2011 NFPA Log #25 Kenneth J. Rempe, Siemens Industry Inc Revise definition to read as follows: A document that specifies the safety requirements for specific equipment or class of equipment and is recognized by a regulatory authority in the United States or Canada, as applicable, as a safety standard providing an adequate designated level of safety; compatible with and maintained current with periodic revisions of applicable national codes and installation standards; and developed by a standards developing organization under a method providing for input and consideration of views of industry groups, experts, users, consumers, governmental authorities, and others having broad experience in the safety field involved; or currently designated as an American National Standards Institute (ANSI) safety-designated product standard or an ASTM International test standard used for evaluation of products or materials. The TCC directed the Technical Committee review the use of the term adequate in this definition. Replacing adequate with designated indicates that Standards provide prescriptive evaluation and test methods in order to comply with a specified purpose. 13

15 Report on Comments June 2011 NFPA Log #27 Wendell Whistler, Intertek Testing Service A document which specifies the safety requirements for specific equipment or class of equipment and is: Rrecognized by a regulatory authority in the United States or Canada, as applicable, as a safety standard providing an adequate level of safety, and Ccompatible with and maintained current with periodic revisions of applicable national codes and installation standards, and Ddeveloped by a standards developing organization under a method providing for input and consideration of views of industry groups, experts, users, consumers, governmental authorities, and others having broad experience in the safety field involved, or Ccurrently designated as an American National Standards Institute (ANSI) safety-designated product standard or an American Society for Testing and Materials (ASTM) test standard used for evaluation of products or materials. The term adequate is not easily defined and leaves a lot to interpretation and corrected the capitalized word in document 14

16 Report on Comments June 2011 NFPA Log #6 Chuck Mello, Vacouver, WA Revise to read as follows: Access shall not be conditional upon the size financial status of the applicant or membership of any association or group, nor shall the decision to issue a FEB Statement of Conformity be conditional upon the number of such certificates already issued. The revised text is to clarify what is meant by size. The intent is that service is to be provided equally and without regard to the applicant for a Field Evaluation being a large or small company. The term size is too vague and could be interpreted to mean attributes other than financial net worth as intended. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 15

17 Report on Comments June 2011 NFPA Log #2 EEE-AAA Technical Correlating Committee on National Electrical Code, It was the action of the Technical Correlating Committee that further consideration be given to the negative comment expressed in the voting. This is a direction from the Technical Correlating Committee on National Electrical Code in accordance with and of the Regulations Governing Committee Projects. 16

18 Report on Comments June 2011 NFPA Log #15 Chuck Mello, Underwriters Laboratories Continue to accept the proposal as written and published in the ROP Draft. With respect to the negative ballot item, the intent is for the FEB to be a legal business entity registered with a government organization such as a proprietorship, partnership, corporation or similar entity. For example a corporation with Articles of Incorporation in the State of Delaware. Corporations are only established in one location but the corporation is recognized outside the area where an FEB actually establishes an office or place of business to conduct operations. When establishing the business location, they would have to comply with the local State, Provincial, County, and/or City regulations for business licenses or tax requirement. The text removed could be construed that as part of recognition, the FEB would have to prove they were registered as a business in every locality that they provide service in without regard to if they have in fact established a business location or office in that locality. 17

19 Report on Comments June 2011 NFPA Log #16 Chuck Mello, Underwriters Laboratories Revise the text in 5.2.1(8) from the ROP Draft to read as follows: (8) Have a quality management system giving confidence in its ability to perform Field Evaluations This section establishes a requirement for a quality management system which is further defined and described in Section 5.5. In section 5.5, all the references are to a more generic management system and the term quality is not used there. There are other aspects to having a management system beyond quality and it would add clarity and consistency to this document by using only the term management system in Section 5.2 and

20 Report on Comments June 2011 NFPA Log #29 Wendell Whistler, Intertek Testing Service (2) Give advice or provide consultancy services for methods of dealing with matters which are barriers to the Field Evaluation requested except to identify and discuss with the Authority Having Jurisdiction the specific areas of the applicable product standard where a non conformance is identified As written it would preclude any discussion by the FEB with the Authority Having Jurisdiction 19

21 Report on Comments June 2011 NFPA Log #17 Chuck Mello, Underwriters Laboratories Delete section and renumber succeeding sections as needed. Where a FEB sub-contracts any part of the Field Evaluation, the work shall be placed with a subcontractor complying with the requirements in this document. The reference to this document is confusing since the entire document cannot be applied to a subcontractor. For example the appeals, complaints and disputes requirements in Section 7 would not apply to subcontractors since the FEB must perform activities in this area. Also, citation of this document permits a subcontractor to pass work on to another subcontractor, and then on to another subcontractor, etc. This does not seem to be the intention of this document. In the absence of specifying what requirements in the document apply, this clause should be deleted as it does not add anything to the requirements for being recognized as a FEB. 20

22 Report on Comments June 2011 NFPA Log #18 Chuck Mello, Underwriters Laboratories Revise the text of section from the ROP Draft to read as follows: The FEB shall record and retain details of its investigation of the competence and compliance of its subcontractors and maintain a register of all subcontractors. The document already specifies the characteristics of subcontractors that the FEB must investigate. Repeating those words here is only confusing. Also, the wording suggests that competence and compliance with subcontractor requirements are two separate things but directly contradicts that. 21

23 Report on Comments June 2011 NFPA Log #19 Chuck Mello, Underwriters Laboratories Revise the text of section from the ROP Draft to read as follows: In order to ensure field evaluation activities are carried out effectively and uniformly, the minimum relevant criteria for the competence of personnel involved in field evaluation activities shall be defined by the FEB. The revised text is to clarify and to distinguish from the more general requirement in As stated someone could interpret that competence requirements must be established and documented for the legal staff, the admin staff, the accounting staff etc. of the FEB when none of these individuals conduct a field evaluation nor need to have competence into the technical aspects of how to conduct a field evaluation. 22

24 Report on Comments June 2011 NFPA Log #28 Wendell Whistler, Intertek Testing Service a *A10.2 In specific situations where accessibility to a premisis is limited the AHJ may grant written authority to the FEB to apply a field label to the equipment at other than the final installation site such as the manufacturer s facility or other intermediate site Where access is limited due to security related issues or a remote location this is necessary 23

25 Report on Comments June 2011 NFPA Log #20 Chuck Mello, Underwriters Laboratories Revise Section 11.1 from the ROP Draft to read as follows: The FEB shall adopt reporting procedures that suit its needs, the needs of the applicant, and the needs of any other affected parties.. Personnel contributing to and responsible for the evaluation of conformance of a product shall provide the FEB with a report of findings as to the conformity with all the applicable requirements of the standard(s). The full report on the outcome of the evaluation shall be brought to the applicant s notice by the FEB, identifying any nonconformity that has to be corrected in order to comply with the applicable requirements of the standard(s).. The report shall further state what additional activities are required to complete the evaluation.. The format and content as defined in NFPA 791, shall be used. Field evaluation reports, as well as all information needed to understand and interpret them, shall be reported correctly, accurately, and clearly.. A process of checking completed reports shall be established to confirm that this requirement has been met. Renumber the Annex section to The revisions are to bring the text into the correct style of the NFPA Manual of Style Section that requires when there is one division in a chapter or section, there must be a second division. This action will require the renumbering of Annex item from the ROP Draft to

26 Report on Comments June 2011 NFPA Log #7 Chuck Mello, Vacouver, WA Revise to read as follows: The format and content as defined in NFPA 791, shall be used of the field evaluation technical report shall follow accepted industry guidelines. Add new appendix A as follows: A The report format and content as found in NFPA 791,, should be used for all field evaluation technical reports. The NFPA Manual of Style paragraph prohibits recommended practices from being referenced in a standard; therefore, NFPA 791 cannot be referenced in the body of the document as it is a recommended practice. This will also effectively delete Section 2.2. Clause was rewritten to establish the requirement and the reference to NFPA 791 moved to the Annex as A The change to section 2.2 is covered in a companion comment. Annex D.1.1 already has the necessary informational reference for NFPA 791 as provided in the ROP Draft. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 25

27 Report on Comments June 2011 NFPA Log #21 Chuck Mello, Underwriters Laboratories Revise the text of section 12.2 of the ROP Draft to read as follows: The decision to issue a statement of conformity shall be made by the FEB employee responsible for the completion of the inspection, testing, and evaluation process. The activities of testing and inspection have not been broken out as separate from evaluation heretofore in the document. Doing so here at the end is confusing especially since it seems obvious that testing and inspection are sub-activities within the more general evaluation process. 26

28 Report on Comments June 2011 NFPA Log #8 Chuck Mello, Vacouver, WA Revise to read as follows: The FEB shall not delegate authority for issuing or withdrawing a statement of conformity to an outside person or body, except as specified under the subcontracting procedures above in Section 5.4. Using the term above is too vague. References within the document should be to specific applicable sections. The revised text provides the direct section reference for this paragraph. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 27

29 Report on Comments June 2011 NFPA Log #9 Chuck Mello, Vacouver, WA Revise to read as follows: The FEB shall exercise proper control over the ownership, use and display of FEB Statements of Conformity. The title was not consistent with the text. In the title Statement of Conformity was singular but in the text the term Statements of Conformity was used. The text revision makes the title consistent with the text. The plural use is correct as a FEB will be issuing more than one Statement of Conformity and this clause is applicable to all of them. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 28

30 Report on Comments June 2011 NFPA Log #1 EEE-AAA Technical Correlating Committee on National Electrical Code, The Technical Correlating Committee advises that Chapter Scope statements are the responsibility of the Technical Correlating Committee and the Technical Correlating Committee Accepts the 791 Technical Committee actions. In addition, the Technical Correlating Committee directs that the Technical Committee consider the following actions within this proposal: 1) Review the entire document and revise it to comply with of the NFPA Manual of Style which states that subdivisions shall contain at least two subdivisions (example, should be followed by 1.1.2). 2) Revise section 2.1, General, to comply with of the NFPA Style Manual to remove mandatory requirements. 3) Revise section 3.1, General, to include subsections and in accordance with the NFPA Style Manual, section ) In 3.3.5, the Technical Correlating Committee requests that the Technical Committee consider using the 2011 NEC definition of "Equipment. This is a direction from the Technical Correlating Committee on National Electrical Code in accordance with and of the Regulations Governing Committee Projects. 1

31 Report on Comments June 2011 NFPA Log #15 EEE-AAA Chuck Mello, Vacouver, WA Add relocated text from as new section to read as follows: The purpose of the evaluation is to assist regulating authorities who make product and related installation approval decisions. The last sentence in of the NPFA 791 ROP Draft does not fit the style or set a recommendation for application of the document. Since it states a purpose this sentence fits into Section 1.2 as one of the purposes for the document. The deletion of the text for is completed in a companion comment. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 2

32 Report on Comments June 2011 NFPA Log #21 Chuck Mello, Vacouver, WA Add relocated text from as new section to read as follows: The purpose of the evaluation is to assist regulating authorities who make product and related installation approval decisions. The last sentence in of the NPFA 791 ROP Draft does not fit the style or set a recommendation for application of the document. Since it states a purpose this sentence fits into Section 1.2 as one of the purposes for the document. The deletion of the text for is completed in a companion comment. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 3

33 Report on Comments June 2011 NFPA Log #4 Chuck Mello, Vacouver, WA Delete the last sentence of in the ROP Draft and relocate to a new section so Section reads as follows: New or used electrical equipment not listed or labeled as a complete unit or assembly is considered to be unevaluated by a third party and will be subject to an evaluation as required by the AHJ. The purpose of the evaluation is to assist regulating authorities who make product and related installation approval decisions. The last sentence in of the NPFA 791 ROP Draft does not fit the style or set a recommendation for application of the document. Since it states a purpose this sentence fits into Section 1.2 as one of the purpose statements for the document. The addition of the text as new section is completed in a companion comment. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 4

34 Report on Comments June 2011 NFPA Log #3 Nancy W. Gunderson, Square D Company/Schneider Electric Revise text to read as follows: 3.3 [new] Clearance Distance. Shortest distance through air between two conductive parts Creepage Distance. Shortest distance along the surface of the insulating material between two conductive parts. Action on Proposal 791-9a removed the definition for creepage distance when section 4.2 was deleted in response to Proposal , and there was no longer a reference to the term. Accompanying comment requests to add creepage and clearance requirements into Construction Inspection which was section 6, and thus a definition, would be appropriate. Additionally, definition for clearance distance should be added to assist in distinguishing the terms. 5

35 Report on Comments June 2011 NFPA Log #22 Kenneth J. Rempe, Siemens Industry Inc Delete the following definition: Any device, appliance, or machine that generates, conducts, or utilizes electrical energy. The TCC recommended consideration of this Definition from the 2011 NEC. The term Electrical is an adjective intended to describe or modify a specific kind of equipment. Delete the Definition of and renumber remaining definitions. Definition in Equipment is the Definition of Equipment in the 2011 NEC, and is the same as proposed for NFPA 790 (paragraph 3.3.1). The terms equipment and electrical equipment are used many times in the NEC and NFPA 79, with only the definition in in both documents. 6

36 Report on Comments June 2011 NFPA Log #16 Chuck Mello, Underwriters Laboratories Replace the definition of Electrical Equipment from the ROP Draft to read as follows: A general term, including fittings, devices, appliances, luminaires, apparatus, machinery, and the like used as a part of, or in connection with, an electrical installation. This is the definition from the 2008 NEC with the accepted change that will appear in the 2011 NEC. The change in the NEC is the deletion of the term material which is vague and generally speaking field evaluations cannot be completed on materials. The use of this definition aligns this document with the NEC. Acceptance of this comment may require moving to Section 3.2 and renumbering all succeeding definitions. 7

37 Report on Comments June 2011 NFPA Log #17 Chuck Mello, Underwriters Laboratories Revise Section from the ROP Draft to read as follows: An identifier used A recognition issued by the United States Occupational Safety and Health Administration (Fed OSHA) of laboratories that perform testing per nationally recognized standards and certify products as stipulated in the. Federal OSHA does not use the term identifier when referring to Nationally Recognized Testing Laboratories. OSHA recognizes NRTLs with as suitable to provide testing and certification services to specified standards. The term identifier has a different application within OSHA and if OSHA were to use or adopt this document, this term could create confusion as to how it is intended to be applied in this document. 8

38 Report on Comments June 2011 NFPA Log #18 Chuck Mello, Underwriters Laboratories Revise the text of Section in the ROP Draft to read as follows: The following information should be provided for all inspections evaluations: Items 1 to 4 in the list below this section are not intended to be changed by action on this comment. The revised text is to be consistent with the use of the general term evaluation in both NFPA 790 and NFPA

39 Report on Comments June 2011 NFPA Log #9 Chuck Mello, Vacouver, WA Revise to read as follows: Evaluating used equipment involves should include additional considerations and preparation. Normal wear, intentional modification, and abnormal events that can cause mechanical and electrical changes that affect conformity should be considered. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because there are no recommendations stated. As published there are only explanatory materials which can only be in an Annex. The revised text provides the language necessary to provide this information as recommendations. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 10

40 Report on Comments June 2011 NFPA Log #5 Chuck Mello, Vacouver, WA Revise to read as follows: (1) Damaged Components. Inspection of Mmechanical components, such as enclosures, conduit, and fittings, and electrical devices should be completed to identify any that are visibly damaged or deformed which often render a product noncompliant andor require replacement. Those items known to be damaged should be reviewed with the evaluating body in advance when possible. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because only the last sentence has a recommendation stated. As published the first sentence only provide explanatory material which can only be in an Annex. The revised text provides the language necessary to provide this information as a recommendation. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 11

41 Report on Comments June 2011 NFPA Log #6 Chuck Mello, Vacouver, WA Revise to read as follows: (2) Equipment Not Suitable for Use. An assessment of Tthe environment surrounding equipment should be completed to observe often changes that have occurred over time. Changes to building construction, moving the equipment, and installing other equipment close by should be reviewed for any by can affect on compliance in the changed environment. Enclosure ratings, devices that penetrate enclosures, and the environment surrounding the equipment should be reviewed in advance when possible. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because only the last sentence has a recommendation stated. As published the first two sentences only provide explanatory material which can only be in an Annex. The revised text provides the language necessary to provide this information as recommendations. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 12

42 Report on Comments June 2011 NFPA Log #7 Chuck Mello, Vacouver, WA Revise to read as follows: (3) Absence of Drawings. Availability of technical drawing or schematics should be ensured in advance when possible. A lack of technical drawings or schematics may increase the complexity or greatly hinder an evaluation until and accurate drawings should be produced. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because the one sentence did not have a recommendation stated. The revised text provides the language necessary to provide this information as recommendations. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 13

43 Report on Comments June 2011 NFPA Log #8 Chuck Mello, Vacouver, WA Revise to read as follows: (4)* Absence of Manufacturer or Technical Support. Access to the original equipment manufacturers technical information or technical support should be ensured in advance where possible. Add new annex item as follows: A.4.2.2(4) Access to the original equipment manufacturer data simplifies the evaluation process. At times the manufacturer can supply information needed to determine conformance, which is not necessarily commonly known to others. Without the original manufacturer s support, extra time and testing could be necessary to complete an evaluation. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because the text did not have a recommendation stated. The revised text provides the language necessary to provide this information as recommendations. The original text was relocated to a new Annex items as A.4.2.2(4) so that information is captured for use. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 14

44 Report on Comments June 2011 NFPA Log #10 Chuck Mello, Vacouver, WA Revise to read as follows: The primary standard to be used should be a nationally recognized product safety standard written and maintained by a standards development organization that issues product safety standards such as Underwriters Laboratories, Factory Mutual Research Corporation, and Institute of Electrical and Electronic Engineers. These standards are generally adopted by the American National Standards Institute. Supplementary standards can include ones from manufacturing organizations such as the National Electrical Manufacturers Association or general safety bodies such as the National Fire Protection Association. Add new annex item as follows: A These primary standards are generally adopted by the American National Standards Institute. Supplementary standards can include ones from manufacturing organizations such as the National Electrical Manufacturers Association or general safety bodies such as the National Fire Protection Association. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because the second and third sentences in the text did not have a recommendation stated. The explanatory text was relocated to a new Annex item as A4.3.2 with an editorial change for clarity so that information is captured for use. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 15

45 Report on Comments June 2011 NFPA Log #11 Chuck Mello, Vacouver, WA Revise to read as follows: This chapter provides an overview of typical construction requirements that should be considered in the evaluation. The ROP Draft text does not comply with the NFPA Manual of Style Sections and because the sentence does not have a recommendation stated. The revised text now provides this information in the form of a recommendation. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 16

46 Report on Comments June 2011 NFPA Log #12 Chuck Mello, Vacouver, WA Revise to read as follows: (1) Correct color code or other identification used [Where color is used, the grounded (neutral) and grounding (equipment grounding and bonding) conductors have specified colors.] The ROP Draft text does not comply with the NFPA Manual of Style Sections and because the sentence in brackets does not have a recommendation stated. The revised text deletes this information since it is commonly published in the applicable product standards and the NEC. The revised text provides the necessary information to alert the user that there may be color coding requirements to consider. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 17

47 Report on Comments June 2011 NFPA Log #13 Chuck Mello, Vacouver, WA Revise to read as follows: The electrical testing program should follow the applicable standards as closely as practical considering the limits of a nonlaboratory setting and the need for the equipment to perform its needed function after the test. The following typical tests and measurements on complete units or subassemblies should be completed as specified in the applicable standard are often performed on complete units or subassemblies: (1) Insulation resistance test on power circuit with all sensitive electronic components such as line filters and Rf filters disconnected (2) Ground continuity of bonded parts to supply equipment grounding conductor termination point (3) Measurement of the input voltage while under maximum design load (4) Measurement of the input full load current while at the maximum design load normal operation (5) Temperature rise testing of terminals and heat producing devices (transformers, power supplies, coils, heaters) and components that could be affected by an elevated ambient caused by other heat producing components (6) Safety interlock circuit function testing (6) Safety interlock circuit function testing (7) Emergency stop The ROP Draft text does not comply with the NFPA Manual of Style Sections and because the second sentence does not have a recommendation stated. The revised text provides that each sentence includes a recommendation as required by the NFPA Manual of Style. This comment was the result of the work of a Technical Committee task group to address several items arising from the editorial review. The TG consisted of Tim McClintock, Ron Chilton and Chuck Mello and this comment was unanimously agreed to by the Task Group. 18

48 Report on Comments June 2011 NFPA Log #23 Wendell Whistler, Intertek Testing Service Ensuring the product can be installed in accordance with the electrical code including but not limited to the following: (1) Verifying presence of complete equipment nameplate(s). Nameplate is complete including the applicable information based on the standard and the NEC (2) Verifying that equipment construction provides for a compliant code installation. according to Provisions for mounting in accordance with the NEC (3) Verifying iinstallation instructions include sufficient detail (showing raceway entry points, supply conductor wiring methods, supply conductor types, field wiring torque values, and installer supplied overcurrent protection) (4) Verifying adequate wire bending space is provided for all field wiring terminals in accordance with the standard and the NEC. The AHJ is used to verifying information in accordance with the NEC and this is the gold standard used by the jurisdictions 19

49 Report on Comments June 2011 NFPA Log #24 Wendell Whistler, Intertek Testing Service Main Overcurrent Protection Device (OCPD). Main overcurrent protection supplied by the manufacturer or field installed should be verified as suitable for the loads involved, voltage, and interrupting rating. either supplied internally or specified by the installation instructions. Main overcurrent protection that is field installed and specified by the installation instructions should be verified as suitable for the loads involved, voltage, and interrupting rating. This would allow for field installed MAINS overcurrent devices to be evaluated as part of the equipment installation 20

50 Report on Comments June 2011 NFPA Log #25 Wendell Whistler, Intertek Testing Service (8) Separation of low voltage, Class 2 or Class 3 conductors circuit from power conductors The word conductor needed to be made plural 21

51 Report on Comments June 2011 NFPA Log #2 Nancy W. Gunderson, Square D Company/Schneider Electric Add new text to read as follows: 6.12 Distances between exposed energized parts. Inspect distances between exposed energized parts for adequate creepage and clearance distances for the voltage involved. Action on Proposal deleted Chapter 4 as most all was redundant to material in Chapter 6, Construction Inspection. However, the requirement to inspect the clearance and creepage distances was not in the chapter 6 material. Add new item to the Construction Inspection section to retain requirement to inspect the adequacy of basic spacings. 22

52 Report on Comments June 2011 NFPA Log #19 Chuck Mello, Underwriters Laboratories Revise the text numbering from the ROP Draft of Chapter 7 to read as follows: Each evaluation should result in a complete report detailing the results of the evaluation and a statement of conformity made from the results. Discrepancies and nonconformities that have to be resolved in order to comply with requirements should be promptly brought to the client s attention. Where successful correction of nonconformance occurs, the report should include detail of the corrective action. Discrepancies and nonconformities brought to the client s attention, per Section 7.1.1, should be brought to the AHJ s attention. A copy of the report, per Section 7.1, should also be provided to the AHJ. The title page should include the following items: (1) The identification of the company performing the evaluation (2) A general description of the equipment that was evaluated (3) The identity and location of the site where the evaluated equipment is or will be installed (4) The identity and location of the AHJ where the evaluated equipment is or will be installed (5) A report date (6) The project number or identifier (7) The identity of the person preparing the report, typically the evaluator The report contents should include a summary containing the following information: (1) The individual that initiated the project and company affiliation (2) The location of the preliminary inspection (3) The location of the final inspection and testing if different from the preliminary site location (4) Name(s) of the evaluator(s) (5) The date(s) of the preliminary inspection (6) The date of the final inspection, testing, evaluation, and application of the label (7) A summary statement of the findings (8) The name of the AHJ responsible for the final approval A statement or series of statements establishing specific conditions of acceptability to be adhered to in order to maintain the label as valid should be included. The complete citations of the primary and any contributing support standards used to complete the evaluation should be included. The citation should be complete that any subsequent audit can clearly identify the exact edition and revision of the standard(s) used. The equipment nameplate information should be documented for each manufactured unit that was evaluated as follows: (1) Product name (2) Product manufacturer s name (3) Model identification (4) Serial number for each unit evaluated (5) Electrical ratings (6) Mechanical ratings as applicable (7) FEB label serial number The detailed procedures used to inspect, test, and evaluate the product should be documented. The evaluation procedures should be separated into the major category areas as detailed in Chapters 6 and 7 with sufficient explanation for clear understanding to all parties involved including client, AHJ, and the end user. The evaluation section should include the following: 23

53 Report on Comments June 2011 NFPA 791 (1) A brief product description of the equipment function and its intended operation (2) Construction evaluation results found acceptable from Chapter 6 (3) Electrical testing results found acceptable from Chapter 7 (4) Discrepancies for each item found nonconforming including a description of the nonconformance, explanation of the hazards, the standards citation, the remedial action to resolve the nonconformance, and final resolution (5) Test instrumentation calibration information The following details should be included as appendices or attachments to the report: (1) Reference drawings used for the evaluation (2) Data sheet(s) documenting the test results from each of the electrical tests (3) The bill of material (critical components list) (4) Photographs of the discrepancies found, the resolution, and the overall equipment (5) Field notes, checklists, or other supporting data that would benefit the client The revised text provides for renumbering so the text in this Chapter is in compliance with Section of the NFPA Manual of Style. The text as published in the ROP Draft did not have a second section correlating with Section 7.1 as required. No technical changes were intended by this comment. It is noted that any correlating annex text may require reference paragraph number changes also. 24

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING

ELECTRIC and NEON SIGN STANDARDS. By Randy Wright RKW CONSULTING SEMINAR 301 Part 1: Changes in the 2005 NEC SEMINAR RULES: There are no Rules All Questions need to be asked Stop at any time for an explanation SEMINAR PARTS: ELECTRIC and NEON SIGN STANDARDS By Randy

More information

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action. M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Marshal Professional Qualifications Stacey Van Zandt DATE: July 13, 2010 SUBJECT: NFPA 1037 ROP TC Letter Ballot (F2011) The ROP letter ballot

More information

NFPA 791. Recommended Practice and Procedures for Unlabeled Electrical Equipment Evaluation Edition

NFPA 791. Recommended Practice and Procedures for Unlabeled Electrical Equipment Evaluation Edition NFPA 791 Recommended Practice and Procedures for Unlabeled Electrical Equipment Evaluation NFPA, 1 Batterymarch Park, Quincy, MA 02169-7471 An International Codes and Standards Organization Become a Member

More information

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev

FACT SHEET 2018 National Fuel Gas Code Summary List of Revisions rev This fact sheet provides an overview of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. These revisions are published

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Hot Work Operations

More information

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle)

M E M O R A N D U M. NFPA Technical Committee on Alternative Approaches to Life Safety. SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) M E M O R A N D U M TO: FROM: NFPA Technical Committee on Alternative Approaches to Life Safety Linda MacKay DATE: December 28, 2010 SUBJECT: NFPA 101A ROP TC Letter Ballot (A2012 Cycle) The ROP letter

More information

Please think twice about printing this matrix. You can it, along with your ballot to or

Please think twice about printing this matrix. You can  it, along with your ballot to or Page Line Clause E/G Organization Comment (rationale) ii Foreword E GWM Recommend inserting the following text between the first and second paragraphs, Fire Alarm Systems shall be installed in accordance

More information

ORDINANCE NO

ORDINANCE NO ORDINANCE NO. 2017-08-031 AN ORDINANCE OF THE CITY OF LANCASTER, TEXAS, REPEALING THE NATIONAL ELECTRICAL CODE 2014 EDITION IN ITS ENTIRETY AND REPLACING IT WITH THE ADOPTION OF THE NATIONAL ELECTRICAL

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU

Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU GNB-CPR AG Guidance from the Group of Notified Bodies for the Construction Products Regulation 305/2011/EU NB-CPR/AG/03/002r3 Issued: 24 May 2013 APPROVED GUIDANCE GNB-CPR AG position paper Guidance to

More information

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17

2018 National Fuel Gas Code Summary List of Revisions Updated: 7/27/17 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. 1.1.1.1 (B), (C), & (D)

More information

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Services and Fire Protection Equipment Linda MacKay DATE: November 10, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter Ballot Final Results The

More information

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot M E M O R A N D U M TO: FROM: NFPA Technical Committee on Building Service and Fire Protection Equipment Gregory Harrington, P.E., Staff Liaison DATE: October 1, 2009 SUBJECT: NFPA 5000 A2011 ROP Letter

More information

Electrical Tech Note 107

Electrical Tech Note 107 Electrical Tech Note 107 Biosystems & Agricultural Engineering Department Michigan State University Understanding the Construction Code Rules, Part 8 1 Based on the 2014 NEC and the 2015 MRC The State

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related

Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related Are Open Bottom Electrical Handholes a NEC Violation? Proposals to Change the 2002 NEC Traffic Signal and Roadway Lighting Related Introduction One of the proposals to change the 2002 NEC adds a provision

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

NECA. Standard for Electrical Safety in the Workplace

NECA. Standard for Electrical Safety in the Workplace 4/23/2018 N E R C e- A di st N rib ot ut Fo io r n NECA Significant Changes to the 2018 NFPA 70E Standard for Electrical Safety in the Workplace NFPA 70E Standard for Electrical Safety in the Workplace

More information

ANSI/NETA Standards Update

ANSI/NETA Standards Update Specifications and Standards Activity ANSI/NETA Standards Update NOW AVAILABALE!!!! NETA Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems The NETA Acceptance Testing

More information

RULEBOOK ON ELECTROMAGNETIC COMPATIBILITY

RULEBOOK ON ELECTROMAGNETIC COMPATIBILITY RULEBOOK ON ELECTROMAGNETIC COMPATIBILITY ("Official Gazette of RS, issue No. 13/2010) I INTRODUCTION Scope Article 1 This Rulebook stipulates the essential requirements that shall be met with regard to

More information

Committee on NFPA 85

Committee on NFPA 85 Committee on NFPA 85 M E M O R A N D U M TO: FROM: NFPA Technical Committee on Single Burner Boilers Patti Mucci, Technical Assistant II DATE: August 5, 2009 SUBJECT: NFPA ROP Letter Ballot The ROP letter

More information

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14

2015 National Fuel Gas Code Summary List of Revisions Updated: 04/24/14 The following list contains a summary of the significant revisions in the 2015 National Fuel Gas Code approved by the National Fuel Gas Code Committee, ANSI ASC Z223 and NFPA 54. PIPING Various Brass REVISED

More information

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems

National Fire Protection Association M E M O R A N D U M. Technical Committee on Testing and Maintenance of Fire Alarm and Signaling Systems National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Electrical Safety Requirements

Electrical Safety Requirements Electrical Safety Requirements Purpose This document defines the minimum required control measures to reduce the risk of injury or illness related to electricity. Scope Applicable to all Coca-Cola system

More information

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM

Committee Input No NFPA [ Global Input ] Submitter Information Verification. Committee Statement. 1 of /20/ :02 AM 1 of 213 10/20/2016 11:02 AM Committee Input No. 2505-NFPA 72-2016 [ Global Input ] Change the term visible to visual where appropriate Submitter Information Verification Submitter Full Name: SIG-NAS Organization:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Standpipes Elena

More information

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE

CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 RECOMMENDATION FOR USE CO-ORDINATION OF NOTIFIED BODIES PPE Regulation 2016/425 PPE-R/00.017 Version 2 RECOMMENDATION FOR USE Number of pages: 5 Approval stage : Approved on : Origin : Horizontal Committee, C2D Ad hoc group

More information

Electrical Hazards and NFPA-70E: Protecting Your Employees

Electrical Hazards and NFPA-70E: Protecting Your Employees Electrical Hazards and NFPA-70E: Protecting Your Employees Presented By Mark B. Haskins, MS, CSP Practical Safety Solutions, LLC At the CBIA Safety Health and Wellness Conference May 22, 2014 PRESENTATION

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

A Brief Orientation to the FAR

A Brief Orientation to the FAR APPENDIX 5 A Brief Orientation to the FAR The Federal Acquisition Regulation (FAR) is the primary acquisition regulation that governs federal government contracts. The FAR establishes uniform policies

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Are You Prepared? The impending impact of Code on Servicing Security Systems

Are You Prepared? The impending impact of Code on Servicing Security Systems Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems Siemens AG 2015 All rights reserved. usa.siemens.com/infrastructure-cities

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000- Log #12 BLD-BSF Final Action: (55.2 (New) ) NOTE: This proposal appeared as Comment 5000-168 (Log #86) which was held from the A11 ROC on Proposal 5000-239. Submitter: Technical Correlating Committee

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

BRL-K21030/02 5 August Certification of Alarm Communication. Certification Alarm Transmission Systems (ATS) Alarm Transmission Systems

BRL-K21030/02 5 August Certification of Alarm Communication. Certification Alarm Transmission Systems (ATS) Alarm Transmission Systems 5 August 2014 Certification of Alarm Communication Certification (ATS) Kiwa N.V. - 1-5 Augustus 2014 Preface This Evaluation Guideline (Certification Scheme) has been accepted by the Kiwa Board of Experts

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012

SAFETY CODES COUNCIL ORDER. BEFORE THE FIRE TECHNICAL COUNCIL On June 21, 2012 SAFETY CODES COUNCIL #1000, 10665 Jasper Avenue N.W., Edmonton, Alberta, Canada, T5J 389 Tel: 780-413-0099 I 1-888-413-0099 Fax: 780-424-5134 I 1-888-424-5134 www.safetycodes.ab.ca COUNCIL ORDER No. 0015423

More information

Page 1 of 15 Second Revision No. 8-NFPA 82-2013 [ Section No. 2.2 ] 2.2 NFPA Publications. National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471. NFPA 13, Standard for the Installation

More information

British Columbia Landscape Standard. Published by:

British Columbia Landscape Standard. Published by: British Columbia Landscape Standard Published by: British Columbia Society of Landscape Architects British Columbia Landscape and Nursery Association BC Landscape Standard 2012 The British Columbia Landscape

More information

Standard Development Timeline

Standard Development Timeline Standard Development Timeline The drafting team maintained this section while developing the standard. It will be removed when the standard becomes effective. Description of Current Draft This draft is

More information

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing

M E M O R A N D U M. NFPA Technical Committee on Wood and Cellulosic Materials Processing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Wood and Cellulosic

More information

Council Directive 93/68/EEC of 22 July 1993 amending Directives

Council Directive 93/68/EEC of 22 July 1993 amending Directives Council Directive 93/68/EEC of 22 July 1993 amending Directives 87/404/EEC (simple pressure vessels), 88/378/EEC (safety of toys), 89/106/EEC (construction products), 89/336/EEC (electromagnetic compatibility),

More information

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 1-NFPA [ Global Input ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input of 280 2/6/2015 12:06 PM Public Input No. 1-NFPA 58-2013 [ Global Input ] NOTE: This public input originates from Tentative Interim Amendment 58-14-1 (TIA 1079) issued by the Standards Council on August

More information

The Technical Committee on Commissioning and Integrated Testing

The Technical Committee on Commissioning and Integrated Testing National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org TO: FROM: The Technical Committee on Commissioning and Integrated Testing

More information

TECHNICAL COMMITTEE ON FIRE CODE

TECHNICAL COMMITTEE ON FIRE CODE TECHNICAL COMMITTEE ON FIRE CODE M E M O R A N D U M TO: FROM: Technical Committee on Fire Code (FCC-AAA) Gregory Harrington, P.E., Staff Liaison DATE: February 3, 2011 SUBJECT: NFPA 1124 Amended CP#2

More information

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Mercantile and Business Occupancies. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Mercantile and Business Occupancies

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: NEC Code-Making Panel 2 FROM: Kimberly Shea, Administrator,

More information

The New EMC Directive 2004/108/EC

The New EMC Directive 2004/108/EC The New EMC Directive 2004/108/EC In the process of this review I have tried to spell out in words what is often referred to as a section number while also keeping to location information as used in the

More information

7.3 Design and Development Design and development planning Design and development inputs Design and development outputs 7.3.

7.3 Design and Development Design and development planning Design and development inputs Design and development outputs 7.3. Rev. 1 03/05/2015 ANNEX A to the Yokogawa Corporation of America Quality Assurance Manual For Additional Requirements selectively applied to ATEX and IECEx certified products CONTENTS 1. Scope 2. Purpose

More information

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL RULES AND REGULATIONS CONCERNING 8 CCR 1507-57 BUILDING AND FIRE CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR LIMITED GAMING

More information

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition

National Fire Protection Association M E M O R A N D U M. NFPA Technical Committee on Construction and Demolition National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Construction

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: NEC Code-Making Panel 17 From: Kimberly Shea, Project Administrator

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Mercantile and

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

The New EMC Directive 2004/108/EC

The New EMC Directive 2004/108/EC The New EMC Directive 2004/108/EC In the process of the review I have tried to spell out in words what is often referred to as a section number. This helps reduce the need to flip pages as one reads this.

More information

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input

Public Input No. 16-NFPA [ Section No ] Additional Proposed Changes. Statement of Problem and Substantiation for Public Input Public Input No. 16-NFPA 211-2014 [ Section No. 2.3.1 ] 2.3.1 ASHRAE Publications. ASHRAE, Inc., 1791 Tullie Circle, NE, Atlanta, GA 30329-2305. ASHRAE Handbook: HVAC Systems and Equipment, 2008 2012.

More information

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification

Public Comment No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment. Submitter Information Verification Public Comment No. 2-NFPA 73-2014 [ Section No. 4.1.3 ] 4.1.3 Unused Openings. 4.1.3.1 Unused openings, other than those intended for the operation of equipment, those intended for mounting purposes, or

More information

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification Second Revision No. 2011-NFPA 101-2016 [ Section No. 14.2.2.2.4 ] 14.2.2.2.4* Classroom Door Locking to Prevent Unwanted Entry. Classroom doors shall be permitted to be locked to prevent unwanted entry

More information

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES INTERNATIONAL MARITIME ORGANIZATION E IMO SUB-COMMITTEE ON FIRE PROTECTION 46th session Agenda item 5 FP 46/5 30 November 2001 Original: ENGLISH UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED

More information

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES Report on Comments

More information

SECTION ISOLATED POWER SYSTEMS

SECTION ISOLATED POWER SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 20 11 ISOLATED POWER SYSTEMS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also, delete any other item or paragraph not applicable to

More information

NFPA 70E Edition Update

NFPA 70E Edition Update NFPA 70E- 2018 Edition Update Paul Colangelo- STSC, CHST, CET, CRIS National Director of Compliance Programs ClickSafety 1 ASSE Construction Practice Specialty Quarterly Meeting 11/17/2017 Agenda Overview

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60079-29-2 Edition 2.0 2015-03 Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen INTERNATIONAL

More information

SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21

SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21 SOMERSWORTH CODE FIRE PREVENTION AND LIFE SAFETY CHAPTER 21 ARTICLE I FIRE PREVENTION CODE 21-1. Statutory authority 21-2. Adoption of standards 21-3. Definitions 21-4. Exceptions to Fire Prevention Code

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

GASTEC QA. Approval Requirements 15. for the GASTEC QA product certificate for Steel pipes and sockets for the transport of gas. KE 15 January 2012

GASTEC QA. Approval Requirements 15. for the GASTEC QA product certificate for Steel pipes and sockets for the transport of gas. KE 15 January 2012 KE 15 January 2012 GASTEC QA Approval Requirements 15 for the GASTEC QA product certificate for Steel pipes and sockets for the transport of gas Foreword These GASTEC QA Approval requirements have been

More information

OPERATIONAL GUIDELINE. Office of the Fire Commissioner O.G.# Revision #1 TITLE: ISSUING ORDERS Page 1 of 8

OPERATIONAL GUIDELINE. Office of the Fire Commissioner O.G.# Revision #1 TITLE: ISSUING ORDERS Page 1 of 8 TITLE: ISSUING ORDERS Page 1 of 8 PURPOSE: SCOPE: POLICY: To ensure a consistent approach to the issuance of Province fire orders. All Local Assistants to the Fire Commissioner. All orders shall be dealt

More information

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety Div B 3.2.1.1.(4), (5) & (6) Exceptions in Determining Building Height BCBC1998-3.2.1.1.(4), (5) & (7) replace (harmonize with NBC) - NBC 2005 has significant revisions to provisions for mezzanines. These

More information

Record of Amendments. Version Date Amendment Section/page affected

Record of Amendments. Version Date Amendment Section/page affected Industry support for effective compliance BTHA Guidance - The Low Voltage Directive (LVD) Directive 2014/35/EU On the harmonisation of the laws of the Member States relating to the making available on

More information

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE EXTINGUISHERS TABLE OF CONTENTS RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-14 FIRE EXTINGUISHERS TABLE OF CONTENTS 0780-02-14-.01 Definitions 0780-02-14-.09 Restrictions 0780-02-14-.02 Standards

More information

Circuit Breakers JANUARY The electronic pdf version of this document found through is the officially binding version

Circuit Breakers JANUARY The electronic pdf version of this document found through   is the officially binding version STANDARD FOR CERTIFICATION No. 2.9 Approval Programmes Type Approval Programmes for EU recognised organisation Mutual Recognition (MR) No. MR-E001 Circuit Breakers JANUARY 2013 The electronic pdf version

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017 STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017 STANDARD INFORMATION Standard Number: UL 412 Standard Name: Refrigeration Unit Coolers Standard Edition and Issue Date: 5 th Edition Dated August 22,

More information

Circulation Report for SIG-TMS Comments Document # 72

Circulation Report for SIG-TMS Comments Document # 72 1 72-12 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 209 ) 72-13 Eligible To Vote:28 Affirmative: 24 : 0 Abstain: 0 : 4 3.3.x Deficiency (New) (Log # 234 ) 72-15

More information

Guidelines for designating and monitoring notified bodies in Norway

Guidelines for designating and monitoring notified bodies in Norway Guidelines for designating and monitoring notified bodies in Norway Version 13.12.2010 The Ministry of Trade and Industry has also prepared a Norwegian version of these guidelines. Questions may be directed

More information

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen IEC 60079-29-2 Edition 2.0 2015-03 REDLINE VERSION colour inside Explosive atmospheres Part 29-2: Gas detectors Selection, installation, use and maintenance of detectors for flammable gases and oxygen

More information

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot.

MEMORANDUM. According to the final ballot results, all ballot items received the necessary affirmative votes to pass ballot. National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Portable Fire Extinguishers

More information

MEMORANDUM. Subject: NFPA 1124 Proposed Tentative Interim Amendment (TIA) No. 1094

MEMORANDUM. Subject: NFPA 1124 Proposed Tentative Interim Amendment (TIA) No. 1094 National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Pyrotechnics Elena Carroll,

More information

Technical Assessment Guideline Applicable for the Kiwa KQ Certification Scheme:

Technical Assessment Guideline Applicable for the Kiwa KQ Certification Scheme: Technical Assessment Guideline Applicable for the Kiwa KQ Certification Scheme: Solar products and components Accreditation Kiwa Italia S.p.A. Via Treviso 32/34 31020 San Vendemiano (TV) Italia Tel: +39

More information

IMAS nd Edition Director, United Nations Mine Action Service (UNMAS), DC2 0650, United Nations, New York, NY 10017, USA

IMAS nd Edition Director, United Nations Mine Action Service (UNMAS), DC2 0650, United Nations, New York, NY 10017, USA 2 nd Edition 2003-01-01 Marking Mine and UXO hazards Director, United Nations Mine Action Service (UNMAS), DC2 0650, United Nations, New York, NY 10017, USA E-mail: mineaction@un.org Telephone: (1 212)

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Merchant Vessels

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60335-2-90 Edition 4.0 2015-08 Household and similar electrical appliances Safety Part 2-90: Particular requirements for commercial microwave ovens INTERNATIONAL ELECTROTECHNICAL

More information

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems BAFE Scheme: SP203-1 Version 5: May 2011 Fire Protection Industry Scheme, Reference SP203 Part 1 For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems British

More information

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS

home smoke candles alarms electrical burns smoking medical oxygen cooking FIREFIGHTING MATCHES & LIGHTERS SPRINKLERS FIREFIGHTING home smoke alarms REGULATIONS GOVERNING THE NFPA EDUCATIONAL MESSAGES DESK REFERENCE FOR THE FIRE SERVICE AND FIRE AND LIFE SAFETY EDUCATORS MATCHES & LIGHTERS medical oxygen cooking FIRE

More information

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017)

MEMORANDUM. Technical Committee on Board and Care Facilities. NFPA 101 Second Draft Technical Committee FINAL Ballot Results (A2017) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM TO: FROM: Technical Committee on Board and Care Facilities

More information

Requirements for ships carrying hydrogen and compressed natural gas vehicles

Requirements for ships carrying hydrogen and compressed natural gas vehicles Lloyd's Register briefing IMO FP 55 Summary report for clients Overview The 55 th session of the IMO Fire Protection Sub Committee (FP) was held from 25 th to 29 th July 2011, at the IMO headquarters in

More information

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN)

MEMORANDUM. NFPA Technical Committee on Fundamentals of Fire Alarm and Signaling Systems (SIG- FUN) National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org MEMORANDUM To: From: NFPA Technical Committee on Fundamentals of Fire

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

PQS Independent type-testing protocol

PQS Independent type-testing protocol PQS Independent type-testing protocol WHO/XXX Original: English Distribution: General TITLE: Integrated electronic maximum-minimum thermometer, with factory programmed alarms, for vaccine refrigerators

More information

1.0 Basic Principles and Practices of Propane Performance-Based Skills Assessment 2016

1.0 Basic Principles and Practices of Propane Performance-Based Skills Assessment 2016 1.0 Basic Principles and Practices of Propane Performance-Based Skills Assessment 2016 Section 1 Task 1 Task 2 Task 3 Task 4 Section 2 Task 1 Task 2 Task 3 Task 4 Section 3 Task 1 Task 2 Section 4 Task

More information

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System 1. GENERAL 1.1 INTENT OF SPECIFICATIONS A. This specification details the requirements for an engineered inert gas fire suppression system Model Kidde Nitrogen. These requirements, combined with good engineering

More information

Committee on NFPA 51A

Committee on NFPA 51A Committee on M E M O R A N D U M TO: FROM: NFPA Technical Committee on Industrial and Medical Gases Patti Mucci, Administrative Assistant DATE: May 6, 2010 SUBJECT: ROC Letter Ballot The ROC letter ballot

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing. 9/20/2016 2:27 PM Second Revision No. 5006-NFPA 101-2016 [ Section No. 3.3.56 ] 3.3.56 Delayed Action Closer. Self-closing device that incorporates a delay prior to the initiation of closing. Mechanical

More information

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN) 4 of 326 11/21/2013 1:03 PM First Revision No. 161-NFPA 72-2013 [ Section No. 3.3.11 ] 3.3.11 Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

More information

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations Contents Executive Summary... 1 Regulatory Requirements in the Gulf of Mexico for Hazardous Locations... 2 Referenced Codes and Standards... 2 Memorandum of Agreement... 2 Bureau of Ocean Energy Management

More information

NFPA Technical Committee on Fire Tests

NFPA Technical Committee on Fire Tests National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Fire Tests Tracy

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60730-2-13 Edition 3.0 2017-10 Automatic electrical controls INTERNATIONAL ELECTROTECHNICAL COMMISSION ICS 97.120 ISBN 978-2-8322-4900-0 Warning! Make sure that you obtained

More information