UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

Size: px
Start display at page:

Download "UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY"

Transcription

1 Revision No.: 3 Page 1 of 6 I. PURPOSE This procedure establishes guidelines for the weekly or monthly inspection and testing of all fire pumps within the University of Rochester by representatives of the University Fire Marshal s Office. This procedure is based on NFPA 25 Standard for the Inspection, Testing and Maintenance of Water-Based Fire Protection Systems, Chapter Eight. The purpose of inspection and testing shall be to verify the pump starts upon loss of pressure and the pump assembly is in operating condition and is free from physical damage. Any deficiency found will require immediate correction with the appropriate personnel working with Facility Operations to achieve said corrections. Fire pumps at buildings occupied by university employees, but are not owned by the university will be tested by the building owner or landlord and will not be the responsibility of EH&S. II. PERSONNEL AFFECTED Fire Safety Inspectors from the Department of Environmental Health and Safety, Fire Marshal s Office. Facilities and Services III. DEFINITIONS FSI NFPA Fire Safety Inspector National Fire Protection Association IV. RESPONSIBILITIES The FSI is responsible for the weekly or monthly inspection and testing of all fire pumps in buildings within their area of responsibility. Upon identification of any deficiencies, it is the responsibility of the FSI to issue work orders and work with the appropriate personnel to see that repairs and or replacements are made to all deficient materials. Facilities will be responsible for maintaining the fire pump at the recommended PM frequencies of the pump manufacturer. V. PROCEDURES 1. FSI shall contact University Communications Center (Public Safety) and advise them that they will be performing the weekly or monthly fire pump test and will be bypassing the associated fire alarm system(s) and they may receive trouble signals.

2 Revision No.: 3 Page 2 of 6 2. Every 7 days for vertical electrical pumps and every 30 days for horizontal electric pumps shall be run a minimum of 10 minutes and every 7 days the diesel pumps shall be run a minimum of 30 minutes. 3. The weekly/monthly fire pump testing will consist of a visual inspection before running the pump and observations while the pump is running. Where applicable, information shall be recorded on the Fire Pump Weekly Run Test Report. See Appendix I (electric) or Appendix II (diesel). 4. The weekly fire pump test shall be done without flowing water (churn) with all valves in their normal position. 5. Turn the jockey pump off. 6. This test shall be conducted by starting the pump automatically. To do this, open the drain cock located near the pump controller. Record the pump starting pressure. 7. Electric Pumps Observe the time for motor to accelerate to full speed and record the time controller is first step (for reduced voltage or reduced current starting). Diesel Pumps - Observe the time for engine to crank, time for the engine to reach running speed, periodically observe oil pressure gauge, speed indicator (if applicable), water and oil temperature indicators and record any abnormalities. 8. Check the pump packing glands to verify that a slight discharge of water is visible. Have facilities adjust gland nuts if necessary. 9. Observe water flow from the circulating relief valve. Adequate flow assures pump casing will not overheat. Diesel pump - observe flow from heat exchanger. 10. Check for excessive vibration, unusual noise, or other signs of malfunction. Discontinue the test if malfunctions are observed and call facilities customer service center x immediately for a safety work order to have repairs made immediately. If all appears normal continue with the test. 11. Record the system suction and discharge pressures. Record other system data as listed on the appropriate checklist. 12. Periodically verify that the pump and driver are not overheating during the test. 13. Shut down the pump manually. If the fire pump is equipped with a run timer let the run timer expire and record the time on the appropriate checklist. 14. Turn the jockey pump back on. Restore the fire pump controller to the automatic start position. 15. Notify Public Safety that the test is complete and that the alarm system should be put back to normal service. 16. Once test data is recorded, compare it to previous tests to determine if the pump is operating satisfactorily. Significant differences in operation should be analyzed as to the cause. Corrective actions should be completed as soon as possible and the pump retested.

3 Revision No.: 3 Page 3 of 6 VI. REFERENCES NFPA 25 standard for Inspection, Testing and Maintenance of Water-Based Fire Protection Systems. VII. APPENDICES/FORMS I. Electric Fire Pump Weekly/Monthly Test Sheet Blank Form II. Diesel Fire Pump Weekly Test Sheet Blank Form VIII. REVISION HISTORY Date Revision No. Description 4/24/09 New Establish policy/procedure for weekly inspection and testing of fire pumps. 3/19/10 1 Expanded policy to be more descriptive and added diesel requirements 3/15/13 2 Clarified steps in procedure and added new weekly diesel fire pump test sheet 4/10/14 3 Clarified steps in procedure and enhanced Appendix I and II to identify additional inspection points 1/3/18 4 Differentiate between vertical and horizontal pump testing frequencies per IFC2015.

4 Revision No.: 3 Page 4 of 6 Appendix I ELECTRIC FIRE PUMP LY/MONTHLY TEST Pump Location/Type: Pump Service: Valves open (Suction, Discharge, & By-pass) 2. Pump Start- MANUAL (on switch) 3. Pump start- AUTOMATIC (pressure drop) 4. Pump Stop- MANUAL (off switch) 5. Pump Stop- AUTOMATIC (timed stop if set) 6. Time controller is on first step (reduced voltage or reduced current starting) 7. Pump Start pressure 8. Suction Pressure 9. Discharge Pressure 10. Start Time 11. End Time 12. Pump run for at least 10 minutes 13. Pump packing showing slight discharge 14. Pump free from unusual vibration 15. Packings, bearings, casings not overheating 16. Circulating relief valve working

5 Revision No.: 3 Page 5 of Controller pilot light (power on) is illuminated 18. Transfer switch normal pilot light is illuminated 19. Isolation switch is closed (Standby emergency source) 20. Phase reversal pilot light if off or normal phase rotation pilot light is on 21. Facilities notified for deficiencies 22. Alarm received at fire alarm panel 23. Alarm received at Security 24. Test Acceptable COMMENTS: DATE INSPECTOR Appendix II DIESEL FIRE PUMP LY TEST Pump Location: Pump Service: Pump room heat is adequate (>40 o F) and ventilation louvers are free to operate 2. Fuel tank is 2/3 full 1. Oil Level Checked 2. Valves open (Suction, Discharge, & By-pass) 3. Pump Start- MANUAL (on switch) 4. Pump start- AUTOMATIC (pressure drop) 5. Pump Stop- MANUAL (off switch) 6. Pump Stop- AUTOMATIC (timed stop if set) 7. Pump Start pressure 8. Suction Pressure 9. Discharge Pressure

6 Revision No.: 3 Page 6 of Start Time 11. End Time 12. Pump run for at least 30 minutes 13. Pump packing showing slight discharge 14. Pump free from unusual vibration 15. Packings, bearings, casings not overheating 16. Heat Exchanger Cooling Water Discharge OK 17. Engine Speed Adequate 18. Engine Oil Pressure in Normal Range 19. Engine Water Temperature in Normal Range 20. Charging Rate in Normal Range 21. Battery Terminals Corrosion Free 2x. Battery electrolyte level is normal Controller power pilot light on illuminated Transfer switch normal pilot light illuminated Isolation switch is closed (Standby emergency source) Phase reversal pilot light if off or normal phase rotation pilot light is on 22. Facilities notified for deficiencies 23. Alarm received at fire alarm panel 24. Alarm received at Security 25. Test Acceptable DATE INSPECTOR COMMENTS:

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 1 Page 1 of 5 I. PURPOSE This procedure identifies how to conduct a sprinkler system main drain test for ACF sprinkler system. This test requires two FSU personnel to complete. One in the

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 4 Page 1 of 5 I. PURPOSE This procedure identifies how to conduct a sprinkler system main drain test for Strong Memorial Hospital. II. PERSONNEL AFFECTED Fire Safety Unit III. DEFINITIONS

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 3 Page 1 of 6 I. PURPOSE This policy establishes the steps required for performing the monthly fixed systems inspections and the semi-annual systems testing. Fixed systems include; wet chemical

More information

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire

More information

Facilities Management

Facilities Management Facilities Management Policy Number: 700.4 Title: Fire Protection & Life Safety Inspection Policy Implementation Date: August 1 st, 2008 Last Revised: September 14 th, 2017 Last Audited: August, 2017 Introduction

More information

FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION

FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION FIRE SAFETY SYSTEMS MAINTENANCE INFORMATION To be kept in school administration office Crown Copyright, Province of Nova Scotia 2004 Prepared by Nova Scotia Department of Education No part of this document

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 2 Page 1 of 5 I. PURPOSE This procedure establishes the steps to perform a fire drill for the URMC Surgical Center located at 180 Sawgrass Drive. II. PERSONNEL AFFECTED Fire Safety Specialist/Fire

More information

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps. Issued 2006/08/01 Section 13920 Packaged Fire Pumps and Controllers Page 1 of 7 PART 1 GENERAL 1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during

More information

Self Inspection Program

Self Inspection Program Self Inspection Program Munich Re Self Inspection Program Inspection and testing of fire protection systems Introduction Engineered fire protection systems are a vital factor in the reduction of potential

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 5 Page 1 of 6 I. PURPOSE This policy outlines the guidelines for posting a fire watch if the fire alarm and/or fire suppression system in any University building becomes inoperable and the

More information

Preventative Maintenance Tables

Preventative Maintenance Tables Preventative Maintenance Tables Table of Contents I. Table : Gas Fired Domestic Hot Water Heater II. III. IV. Table : Circulating Pump Table : Convectors Table 4: Grille and Diffusors V. Table 5: Unit

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 3 Page 1 of 10 I. PURPOSE This procedure establishes the steps required for off-site Business occupancy locations to perform the required annual fire drill and disaster drill reports as required

More information

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION FIRE PROTECTION PUMPS PART 1 - GENERAL SECTION 21 30 00 FIRE PROTECTION PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 01 00,

More information

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps

PHYSICAL FACILITIES Consultant s Handbook Specifications Division 21 Fire Suppression 3000 Fire Pumps Note: The A/E must choose all design values in brackets below before using in project specifications 1 General 1.1 Provide UL listed and FM approved fire pump complete with pump, driver, controller and

More information

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems Adam Olomon, P.E. Associate Consultant Fire & Life Safety and Fire Protection Introduction Adam Olomon Licensed Professional Engineer

More information

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required*

Revised March 2015 Fire Alarm Systems Verification. Schedule I(A) Services. *Manditory Site visit required* 1.0 Description of Services Required: Revised March 2015 Fire Alarm Systems Verification Schedule I(A) Services *Manditory Site visit required* Perform the annual fire alarm system and sprinkler system

More information

Diocese of Cleveland Facilities Services Corporation

Diocese of Cleveland Facilities Services Corporation Diocese of Cleveland Facilities Services Corporation BOILER MAINTENANCE and SERVICING SEASONAL MAINTENANCE - to be performed by trained boiler technician or boiler contractor only: 1. Disassemble the low

More information

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers, NFPA CODE TESTING & INSPECTION Requirements & Recommendations for Licensed Florida Hospitals, Ambulatory Surgery Centers, ICF/IID Healthcare, & In-patient Hospice Facilities per NFPA Life Safety Code 101

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

Liquefied Petroleum Gas Facility Written Fire Safety Analysis Liquefied Petroleum Gas Facility Written Fire Safety Analysis For Completed by Facility manager Received by Fire Department/Emergency Response representative Date Date INDEX Page Introduction 2 Conducting

More information

BERMAD Fire Protection

BERMAD Fire Protection Model: 400E-3M Bermad Electro-Pneumatically Controlled Deluge Valve with Easy Lock Manual Reset Installation Operation Maintenance Safety First BERMAD believes that the safety of personnel working with

More information

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property SEMIANNUAL FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

False Sense of Security???

False Sense of Security??? IS YOUR SPRINKLER SYSTEM GIVING YOU A FALSE SENSE OF SECURITY? Best Practices in Fire Safety An ASSE Virtual Symposium March 1 & 2, 2011 Walter S. Beattie CSP, CFPS, CSHM False Sense of Security??? Fire

More information

Liquefied Petroleum Gas Facility Written Fire Safety Analysis

Liquefied Petroleum Gas Facility Written Fire Safety Analysis Liquefied Petroleum Gas Facility Written Fire Safety Analysis For INDEX Page Introduction 2 Conducting the WFSA 2 WFSA CHECKLIST Section I Facility Information 3 Section II Facility Storage Container Information

More information

Prefunctional Checklist

Prefunctional Checklist Prefunctional Checklist This Prefunctional Checklist should be completed as part of startup and initial checkout of the equipment in preparation for Functional Performance testing. PC: 16231 ITEM: Generator

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

City of Duluth Festival Center 04/25

City of Duluth Festival Center 04/25 SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community. CNM WAY PROCESS CNM Process Name Fire Safety Program (04/10/2018 Revision) Overview of Fire Safety Program Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All

More information

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE Fire Department Core Values Protect lives, property, and the environment through preparedness, prevention,

More information

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!!

!!! Sample Written Program For Your Company. For BOILER SAFETY. Provided By:!!! Sample Written Program For Your Company For BOILER SAFETY Provided By: P.O. Box 2136 Slidell, LA 70458 Phone: 985-781-1444 Fax: 985-781-1446 Email: info@se-safety.com Purpose Boiler Safety Program The

More information

LEAK TEST FREQUENCY: a. CONTINUOUS b. DAILY/NIGHTLY c. WEEKLY. d. MONTHLY e. OTHER (Specify):

LEAK TEST FREQUENCY: a. CONTINUOUS b. DAILY/NIGHTLY c. WEEKLY. d. MONTHLY e. OTHER (Specify): UNDERGROUND STORAGE TANK MONITORING PLAN For use by Unidocs Member Agencies or where approved by your Local Jurisdiction Authority Cited: Title 23 CCR, Sections 2632(d)(1), 2634(d)(2), and 2641(h) TYPE

More information

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance

Model: 400E-5M. Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset. Installation Operation Maintenance Model: 400E-5M Bermad Hydraulically Controlled Anti-Columning Deluge Valve, with Easylock Manual Reset Installation Operation Maintenance Application Engineering Bermad 1. Safety First BERMAD believes

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE PUMP REVIEW Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved w/comments;

More information

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/

Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/ Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA 25 2017 & NFPA 13/72 2016 The purpose of this guide is to help you determine if the system will work as

More information

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input

Public Input No. 88-NFPA [ New Section after ] Statement of Problem and Substantiation for Public Input of 201 1/13/2014 12:51 PM Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating

More information

Prefunctional Checklist

Prefunctional Checklist This should be completed as part of startup and initial checkout of the equipment in preparation for Functional Performance testing. PC: 28 31 76 ITEM: Fire Alarm/Mass Notification System ID: (Use one

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS DIRECT FIRED HOT WATER BOILERS PARKER BOILER CO. GBI 201-5 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

SECTION INSPECTION AND TESTING OF WORK

SECTION INSPECTION AND TESTING OF WORK SECTION 01455 PART I - GENERAL 1.01 SECTION INCLUDES A. Project Inspections and Procedures B. Scheduling Inspectors Notification requirements 1.02 RELATED SECTIONS A. Section 01310 COORDINATION B. Section

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

Fire Protection System Impairment Procedure

Fire Protection System Impairment Procedure Fire Protection System Impairment Procedure June 2017 Fire Protection System Impairment Procedures Table of Contents I. Purpose II. III. IV. Fire Protection Systems Compliance and Responsibility Notification

More information

Slide 2 NFPA 25: 2017

Slide 2 NFPA 25: 2017 Slide 1 Changes for 2017 NFPA 25 Handbook Supplement 8 contains a table highlighting the significant technical changes to NFPA 25 for the 2017 edition, along with a brief comment regarding the reason for

More information

Life Safety Code Potpourri

Life Safety Code Potpourri Life Safety Code Potpourri JAMES P. LOVELAND P.E. MINNESOTA DEPARTMENT OF HEALTH Engineering Services Section FEDERAL MONITORING SURVEYS 2007 2008 2009 No. of FMSs 20 20 20 No. of Deficiencies 332 252

More information

Ammonia Detection System Codes and Design Specifications

Ammonia Detection System Codes and Design Specifications Ammonia Detection System Codes and Design Specifications January 15, 2018 Revision 6 Ammonia detection system codes and design specifications Following is a discussion of ammonia detection system design

More information

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY Revision No.: 6 Page 1 of 5 I. PURPOSE This procedure provides guidance to EH&S office staff to coordinate notifications of appropriate internal staff who will need to respond to an unannounced Joint Commission

More information

a) Establishment of emergency procedures to be followed at the time of an emergency;

a) Establishment of emergency procedures to be followed at the time of an emergency; 5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal

September 1, Sincerely, Mike Montgomery Fire Marshal. M.S. Montgomery Fire Marshal M.S. Montgomery Fire Marshal September 1, 2010 This document describes rules changes affecting the operation and fire safety in foster homes licensed and regulated by the Texas Department of Family and

More information

Fire Sprinkler Submittal Requirements and Acceptance Testing

Fire Sprinkler Submittal Requirements and Acceptance Testing Lubbock Fire Marshal s Office 1601 Mac Davis Lane Lubbock, Texas 79401 806-775-2646 Fax 806-775-3508 fireprevention@mylubbock.us Fire Sprinkler Submittal Requirements and Acceptance Testing To all Registered

More information

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location:

Global Property. QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Date of Inspection Location: Global Property QUARTERLY FIRE PROTECTION EQUIPMENT INSPECTION REPORT Plant: Date of Inspection Location: Inspected By: Reviewed By CONTROL VALVES (If Valves are Not Locked Open or Electronically Supervised

More information

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703 TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 DESCRIPTION These Sunline 2000 units are completely assembled, piped and wired at the factory to provide one-piece shipment and rigging.

More information

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and

More information

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING FLAME115 INFRARED HEATER SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. TROUBLESHOOTING GUIDE 5. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER

More information

CENTRAL STATE HOSPITAL PLAN PLANT OPERATIONS UTILITIES MANAGEMENT PLAN

CENTRAL STATE HOSPITAL PLAN PLANT OPERATIONS UTILITIES MANAGEMENT PLAN Page 1 of 11 CENTRAL STATE HOSPITAL PLAN SUBJECT: PLANT OPERATIONS UTILITIES MANAGEMENT PLAN ANNUAL REVIEW MONTH: RESPONSIBLE FOR REVIEW: March CSH Safety Officer LAST REVISION DATE: November 2003 I. SCOPE:

More information

SECTION GAS-FIRED RADIANT HEATERS

SECTION GAS-FIRED RADIANT HEATERS SECTION 23 55 23 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has

More information

Thermo 230 / 231 / 300 / 301 / Troubleshooting

Thermo 230 / 231 / 300 / 301 / Troubleshooting Thermo 230 / 231 / 300 / 301 / 350 5 Troubleshooting 5 Troubleshooting 5.1 General This section describes troubleshooting procedures for the heaters Thermo 230, 231, 300, 301 and 350. CAUTION Troubleshooting

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

APPENDIX H (DESIGN SUBMISSION CRITERIA)

APPENDIX H (DESIGN SUBMISSION CRITERIA) APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation

More information

OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue

OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE. John Percy, Public Education Officer Waterloo Fire Rescue OWNERS RESPONSIBILITIES & CASE STUDIES ONTARIO FIRE CODE John Percy, Public Education Officer Waterloo Fire Rescue AGENDA: Fire Protection and Prevention Act and Ontario Fire Code Role of Assistants to

More information

Safety Program. Eastern Electrical Testing Corporation 2 Skyline Drive Clarks Summit, PA (570)

Safety Program. Eastern Electrical Testing Corporation 2 Skyline Drive Clarks Summit, PA (570) Safety Program Eastern Electrical Testing Corporation 2 Skyline Drive Clarks Summit, PA 18411 (570) 586-4900 Eastern Electrical Testing Corporation Safety Program Table of Contents Safety Program... Section

More information

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST

CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST CITY OF LONG BEACH Department of Development Services BUILDING AND SAFETY BUREAU FIRE ALARM / ELECTRICAL FIRE PLAN REVIEW CHECKLIST DATE: PROJECT NO.: EXPIRATION DATE: STATUS: INFORMATION PROJECT ADDRESS:

More information

INSTALLATION AND SERVICE MANUAL FOR THE SERIES 1000-P FAN SERIES (PNEUMATIC CONTROL) SERIES 1000-H FAN SERIES (HYDRAULIC CONTROL) GEN 2

INSTALLATION AND SERVICE MANUAL FOR THE SERIES 1000-P FAN SERIES (PNEUMATIC CONTROL) SERIES 1000-H FAN SERIES (HYDRAULIC CONTROL) GEN 2 INSTALLATION AND SERVICE MANUAL FOR THE SERIES 1000-P FAN SERIES (PNEUMATIC CONTROL) SERIES 1000-H FAN SERIES (HYDRAULIC CONTROL) GEN 2 Publication No. 01906 Revision 0 Printed in Canada 1.1 INTRODUCTION

More information

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES

SECTION COMPRESSED-AIR EQUIPMENT FOR LABORATORY FACILITIES Page 226119-1 SECTION 226119 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

Understanding and Applying NFPA 25

Understanding and Applying NFPA 25 Understanding and Applying NFPA 25 Texas Edition Learning Objectives Describe the scope of NFPA 25. Distinguish between sprinkler system problems that fall within the scope of NFPA 25 and those that do

More information

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016)

2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) 2.07 Permit Application Checklist for Diesel Generators, Diesel Fire Pumps, and Fuel Tanks Serving Generators and Fire Pumps (2016) Reference: Documents referenced for this bulletin are as follows: San

More information

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS SECTION 236200 - PACKAGED COMPRESSOR AND CONDENSER UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions apply

More information

SECTION Fire Pumps

SECTION Fire Pumps SECTION 21 30 00 Fire Pumps PART 1 GENERAL 1.1 WORK INCLUDED A. Furnish, install and test a motor-driven fire pump, jockey pump, and controllers in the space provided and as shown in the contract drawings.

More information

Inspection, testing, and maintenance (ITM) Fixed fire protection and detection July 2016

Inspection, testing, and maintenance (ITM) Fixed fire protection and detection July 2016 July 2016 Author: Global Risk Engineering Technical Center Property Cover photo source: Rich Gallagher, Zurich Table of contents 1. Executive Summary... 1 1.1 Are systems in service?... 1 1.2 Are systems

More information

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH General This information is provided to clarify the requirements for a fire watch. A fire watch is the action of a person or persons

More information

Established /10/2015. Doran Pruisner Dan Wood

Established /10/2015. Doran Pruisner Dan Wood Established 1911 Doran Pruisner Dan Wood The International Fire Code, 2009 Edition shall apply to all occupancies except for those that are explicitly excluded by these provisions. 1 Buildings built between

More information

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO.

GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO. GENERAL BASIC INSTALLATION INSTRUCTIONS INDIRECT GAS FIRED WATER HEATERS PARKER BOILER CO. GBI 210 3C For a proper installation and in order to receive the best in operating life and efficiency from your

More information

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME

Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions

More information

ELEVATOR RESCUE PROCEDURE

ELEVATOR RESCUE PROCEDURE ELEVATOR RESCUE PROCEDURE Office of Environmental Health & Safety December 2013 Table of Contents I. Purpose:... 3 II. Scope:... 3 III. Responsibility:... 3 IV. Types of Emergencies:... 3 V. Definitions:...

More information

Manufacturing safety solutions

Manufacturing safety solutions Manufacturing safety solutions 4 th Quarter 2011 Inside this issue Manufacturing property conservation and protection Manufacturing property conservation and protection by Robert Mauerman Upcoming events

More information

MCCMH MCO Policy FIRE SAFETY IN RESIDENTIAL SETTINGS Date: 5/04/11. Definitions

MCCMH MCO Policy FIRE SAFETY IN RESIDENTIAL SETTINGS Date: 5/04/11. Definitions MCCMH MCO Policy 3-031 FIRE SAFETY IN RESIDENTIAL SETTINGS Date: 5/04/11 IV. Definitions A. Emergency Kit Bag A collection of items that are taken by group home staff, if possible, during each emergency/evacuation,

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

Page 1 of 198 Public Input No. 88-NFPA 20-2013 [ New Section after 3.3.38.10 ] Add New Defination 3.3.28.11 Multiple Stage Multiple Port Pump. A single driver pump with multiple impellers operating in

More information

Aldine Independent School District Aldine Westfield Road Houston, Texas Phone (281)

Aldine Independent School District Aldine Westfield Road Houston, Texas Phone (281) Aldine Independent School District 14910 Aldine Westfield Road Houston, Texas 77032 Phone (281) 985-6265 Created on August 2007 ALDINE INDEPENDENT SCHOOL DISTRICT BUILDINGS AND PROPERTIES 14910 Aldine-Westfield

More information

5.07 Air Replenishment Systems

5.07 Air Replenishment Systems 5.07 Air Replenishment Systems Reference: 2010 SFFC, Section 511.2 Definitions: CERTIFIED COMPRESSOR. A compressor used by a contractor for maintenance and testing of air replenishment systems that is

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

DIVISION FINNED WATER-TUBE WATER HEATERS

DIVISION FINNED WATER-TUBE WATER HEATERS DELTA LIMITED, TYPE WH - MODELS 399B-899B SUGGESTED SPECIFICATIONS Catalog No.: 3500.97B Effective: 04-01-17 Replaces: 11-15-08 DIVISION 23 52 33.13 FINNED WATER-TUBE WATER HEATERS - GENERAL 1.1 SUMMARY

More information

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES

INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES INTEGRATED LIFE SAFETY COMPLIANCE TESTING AND ITS PROCEDURES By: Mehrdad Ghods Integrated Engineering Student Sept. 06, 2002 University of British Columbia Vancouver, BC i PREFACE: The purpose of this

More information

Emis. Unit Description:

Emis. Unit Description: 1030459 88666 PERCHLOROETHYLENE DRY CLEANERS COMPLIANCE INSPECTION CHECKLIST INSPECTION TYPE: ANNUAL (INS1, INS2) COMPLAINT/DISCOVERY (CI) RE-INSPECTION (FUI) ARMS COMPLAINT NO: AIRS ID#:103 0459 Date:

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

SPECIFICATIONS Annual Fire Pump Testing and Inspection Department of Technology, Management and Budget Managed Facilities - Statewide

SPECIFICATIONS Annual Fire Pump Testing and Inspection Department of Technology, Management and Budget Managed Facilities - Statewide SPECIFICATIONS Annual Fire Pump Testing and Inspection Department of Technology, Management and Budget Managed Facilities - Statewide PURPOSE This RFP is to establish a three year quote for service to

More information

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton

P.C. Simonton & Associates, Inc. Consulting Engineers. Paul C. Simonton P.C. Simonton & Associates, Inc. Consulting Engineers 309 North Main Street 1050 Parkside Commons Post Office Box 649 Suite 101 Hinesville, Georgia 31310 Greensboro, Georgia 30642 Addendum No. One Date:

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Backflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code

Backflow Prevention for Fire Sprinkler Systems. State of Illinois Plumbing Code Backflow Prevention for Fire Sprinkler Systems State of Illinois Plumbing Code Backflow Prevention Fire safety systems connected to a public water supply will require a backflow prevention device between

More information

National Industrial Security Monitoring Station Evaluation

National Industrial Security Monitoring Station Evaluation National Industrial Security Monitoring Station Evaluation Listing Evaluation During the UL Listing evaluation we will examine your the monitoring facility, signal handling, means of record keeping, and

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT

More information

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials. B B11.0 DIVISION 08 - OPENINGS SECTION 08 17 00 INTEGRATED DOOR OPENING ASSEMBLIES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements. Add section numbers and

More information

Routine Outdoor Helium Compressor Maintenance Instructions

Routine Outdoor Helium Compressor Maintenance Instructions HAC 4500 Service Note 1201-022 Routine Outdoor Helium Compressor Maintenance Instructions Introduction Every month of operation the outdoor compressor of the HAC4500 will need to be thoroughly cleaned

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

Fire Alarm Testing and Inspection Report

Fire Alarm Testing and Inspection Report Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL

More information

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT

More information