Chapter 4: Fire Protection Systems
|
|
- Cory Bradford
- 5 years ago
- Views:
Transcription
1 Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system is operating properly and continues to provide protection based on the current needs of the processes involved. As an inspector, you will follow the system from the pipes leaving the ground to the last sprinkler head. Along the way, you will visualize all of the components. Are they present and operating properly? Nothing is obstructing the delivery of water in the event of fire and that all required, periodic maintenance and testing has been performed. Spare sprinkler head box Fire alarm flow switch AES (Automatic Extinguishing System) service label Sprinkler calculation plate Riser control valve Tamper switch wiring tied to alarm system 2008 LACFC Group S-1: An automatic sprinkler system shall be provided throughout all buildings containing a Group S-1 occupancy where one of the following conditions exists: 1. A Group S-1 fire area exceeds 12,000 square feet; 2. A Group S-1 fire area is located more than three stories above grade plane; or 3. The combined area of all Group S-1 fire areas on all floors, including any mezzanines, exceeds 24,000 square feet. 4-1
2 2008 LACFC Sprinkler system monitoring and alarms: All valves controlling the water supply for automatic sprinkler systems, pumps, tanks, water levels and temperatures, critical air pressures, and water-flow switches on all sprinkler systems shall be electrically supervised. (EXCEPTIONS) Control valve supervisory signal device In this image the valves are monitored by a fire alarm. These tamper switches are an indicating type. When the yellow dial/ paddle is positioned inline, the valve is open. Vol 7-C1-S7 All control valves shall be locked in the open position, with a non-case-hardened lock Control valve Control Valve Supervisory Signal-Initiating Device. Each sprinkler riser shall have a readily visible, accessible above grade exterior indicating control valve 2002 NFPA Two separate and distinct signals shall be initiated: one indicating movement of the valve from its normal position (off-normal) and the other indicating restoration of the valve to its normal position If the indicator was positioned horizontal in this situation the valve would be shut. The valves are installed to allow servicing to portions of the sprinkler system without shutting down the entire system. When the valve is shut the fire alarm signals a supervisory alarm. 4-2 Indicator in the open position at this time NFPA The off-normal signal shall be initiated during the first two revolutions of the hand wheel or during one-fifth of the travel distance of the valve control apparatus from its normal position.
3 Riser water flow alarm switch A water flow switch is installed in the fire sprinkler riser, when the sprinkler system activates, the water movement in the riser pushes the paddle upwards and activates the alarm. Water flow pushes the paddle upwards, activating the water flow alarm NFPA * Testing the water-flow alarms on wet pipe systems shall be accomplished by opening the inspector s test connection. (Not the main drain valve.) 2008 LACFC Alarms: Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Alarm devices shall be provided on the exterior of the building in an approved location. A single approved audible/visual sprinkler flow alarm shall be provided in the interior of the building in a normally occupied location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. This cut out of pipe (cookie/coupon) is left there to show the inspectors a hole was cut out to fit the flow switch paddle in the riser. 4-3 The water flow switch sends a signal to the FACP. The fire alarm will sound and the outside water gong shall ring within 90 secs per NFPA 72, NFPA 13, states an audible alarm shall sound on premises within 5 minutes of water flow.
4 2002 NFPA The inspection, testing, and maintenance of fire alarm systems, their initiating devices, and notification appliances shall comply with the requirements of this chapter. Missing sign indicating call 911 if bell is ringing NFPA * Initiation of the alarm signal shall occur within 90 seconds of waterflow at the alarm-initiating device when flow occurs that is equal to or greater than that from a single sprinkler of the smallest orifice size installed in the system. Water flow alarm (outside ringer, water motor-gong) indicates water is flowing from this riser. This alarm is not intended to be an evacuation alarm. The primary purpose is the notification of people outside the building that water is flowing. It also serves as an alerting device for the incoming firefighters as to which system is activated LACFC Inspection, testing and maintenance: Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. Both images below show problems with the water flow switch the image on the left is having electrical wiring issues and the flow switch on the right has been removed. Damaged/inoperable flow switch wiring Missing flow switch. 4-4
5 2002 NFPA * Gauges. Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced NFPA Pressure gauges shall be installed above and below each alarm check valve or system riser check valve where such devices are present NFPA The required pressure gauges shall be listed and shall have a maximum limit not less than twice the normal system working pressure at the point where installed NFPA * A supply of at least six spare sprinklers (never fewer than six) shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced NFPA The sprinklers shall correspond to the types and temperature ratings of the sprinklers in the property NFPA A special sprinkler wrench shall be provided and kept in the cabinet to be used in the removal and installation of sprinklers. One sprinkler wrench shall be provided for each type of sprinkler installed. 4-5
6 2008 LACFC Records: Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request. Example of currently accepted label AES service tag. Sprinkler calculation plate Accurate, up-to-date records are required to document the history of the system inspection, testing and maintenance. Record keeping is not intended simply to prove to the fire inspector that the required inspections, testing and maintenance are being performed, but also to assist the owner or his agent in performing these functions. A well -kept log helps an owner or technician determine how the system is performing over time. California CCR, Title 19 Article 6 When service or testing and maintenance is performed, the initial date of service or testing and maintenance, the printed name and signature of the person performing or supervising the servicing shall be placed on the tag or label. A hole shall be clearly punched in the appropriate boxes. No person shall remove a tag or label from or place a tag or label on an automatic fire extinguishing system except when service or testing and maintenance is performed. No person shall deface, modify, or alter any tag or label attached to or required to be attached to any automatic fire extinguishing system. The label or tag conforming to this section shall be securely attached to each automatic fire extinguishing system at the time of service or testing and maintenance. The label or tag approved by the Office of the State Fire Marshal shall be affixed to a system only after all deficiencies have been corrected. 4-6
7 2002 NFPA : Sprinklers shall not show signs of leakage; shall be free of corrosion, foreign materials, paint, and physical damage; and shall be installed in the proper orientation (e.g., upright, pendent, or sidewall). In this image the sprinkler head has been painted. This sprinkler head shall be replaced NFPA : Any sprinkler shall be replaced that has signs of leakage; is painted, corroded, damaged, or loaded; or in the improper orientation NFPA : Where sprinklers have been in service for 50 years, they shall be replaced or representative samples from one or more sample areas shall be tested. Test procedures shall be repeated at 10-year intervals. This image the drywall has been installed over the sprinkler head. Repair or replace sprinkler head. 4-7
8 2008 LACFC NFPA 13 sprinkler systems: Where the provisions of this code require that a building or portion thereof be equipped throughout with an automatic sprinkler system in accordance with this section, sprinklers shall be installed throughout in accordance with NFPA 13 except as provided in Section If you notice an interior structure with a ceiling, note if there is any piping leading to the room. In this case, there is none. This image is an example of unpermitted construction the occupants built a showroom in the warehouse and did not submit plans or obtain approval for the construction LACFC Installation: Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. This image shows the inside of the showroom. Notice the lack of sprinkler protection in the ceiling. 4-8
9 Vol. 7-C1-S-7 When sprinkler protection is required in a structure, sprinklers shall be provided throughout 100% of the structure. No piping indicates not sprinklered. The images on this page are common violations. This warehouse bathroom was constructed without permits and without sprinklers. Vol. 7-C1-S-7 Sprinkler protection shall be installed in any area where an obstruction from the overhead protection, exceeding four feet by four feet is created (length and width) for standard sprinklers. It is important to open every door while doing an inspection. in this image we see a storage closet under the stairs. This is a sprinklered building and this area should be sprinklered. 4-9
10 2008 LACFC Obstructed locations: Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet in width. Not less than a 3-foot clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. Should the simulator be sprinklered? In the example shown here, the plane (simulator) is used for training. Many different types of training are conducted here. From emergency water landings to flight attendant food service, with a fully functioning galley. The simulator is wider than 4 feet and the building is sprinklered. In the images below, these trailers have been parked under a sprinklered area of the building. Because the trailers are permanently parked, used as storage rooms and being attached to the building, should they be sprinklered? If unable to answer yourself, further research or consultation with either building and safety or your chain of command is needed. Sealed to building and apparently permanent Note, no piping 4-10
11 2008 LACFC Systems out of service: Where a required fire protection system is out of service, the fire department and the fire code official shall be notified immediately and, where required by the fire code official, the building shall either be evacuated or approved standby personnel shall be provided for all occupants left unprotected until the fire protection system has been returned to service. When utilized, standby personnel shall be provided with at least one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires. Paddle on valve indicating closed In this example the fire sprinkler system was taken out of service for repair without informing the fire department. The inspector found the system out of service while on an annual inspection LACFC Impairment coordinator: The building owner shall assign an impairment coordinator to comply with the requirements of this section. In the absence of a specific designee, the owner shall be considered the impairment coordinator LACFC Preplanned impairment programs: Preplanned impairments shall be authorized by the impairment coordinator. Before authorization is given, a designated individual shall be responsible for verifying that all of the following procedures have been implemented: 1. The extent and expected duration of the impairment have been determined. 2. The areas or buildings involved have been inspected and the increased risks determined. 3. Recommendations have been submitted to management or building owner/manager. 4. The fire department has been notified. 5. The insurance carrier, the alarm company, building owner/manager, and other authorities having jurisdiction have been notified. 6. The supervisors in the areas to be affected have been notified. 7. A tag impairment system has been implemented. 8. Necessary tools and materials have been assembled on the impairment site. These procedures must be followed whenever systems are purposely impaired, such as for routine sprinkler system alarm testing. 4-11
12 FIRE WATCH This Department shall set forth the requirements of a fire watch when a building or premises presents a hazard to life or property as a result of a fire or emergency, or when it is determined that any fire protection equipment or system is inoperable, defective, or has been taken out of service, or when determined by the Chief LACFC Tag required: A tag shall be used to indicate that a system, or portion thereof, has been removed from service. Fire Watch: The assignment of a qualified person or persons having the sole responsibility for the continuous patrol of a building or premises for the purpose of detecting fires and transmitting an immediate alarm to the building occupants and Fire Department. When any fire protection system is taken out of service it must be clearly identified with a visible tag that indicates the conditions of the impairment. Proper notification of responsible parties eliminates the chance of false alarms, reduces disruption of normal business activities and encourages quick resumption of normal operations. 4-12
13 2008 LACFC Protection against interruption of service: The fire pump, driver, and controller shall be protected in accordance with NFPA 20 against possible interruption of service through damage caused by explosion, fire, flood, earthquake, rodents, insects, windstorm, freezing, vandalism and other adverse conditions. Fire pump 2008 LACFC Testing and maintenance: Fire pumps shall be inspected, tested and maintained in accordance with the requirements of this section and Title 19 California Code of Regulations, Chapter LACFC Valve supervision: Where provided, the fire pump suction, discharge and bypass valves, and the isolation valves on the backflow prevention device or assembly shall be supervised open by one of the following methods. 1. Central-station, proprietary or remote-station signaling service. 2. Local signaling service that will cause the sounding of an audible signal at a constantly attended location. 3. Locking valves open. 4. Sealing of valves and approved weekly recorded inspection where valves are located within fenced enclosures under the control of the owner LACFC Pump room environmental conditions: Tests of pump room environmental conditions, including heating, ventilation and illumination shall be made to ensure proper manual or automatic operation of the associated equipment. Fire pump room 2002 NFPA * Records of inspections, tests, and maintenance of the system and its components shall be made available to the authority having jurisdiction upon request. Remove flammable and combustible liquids. In this example the occupants were storing flammable and combustible liquids in the pump room. 4-13
14 Fire Alarm/Monitoring 2008 LACFC General: This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing buildings and structures. The requirements of Section are applicable to new buildings and structures. The requirements of Section are applicable to existing buildings and structures. Alarm information needed during an emergency Alarm monitoring company name and number. Green light ONLY Electrical circuit number and location. Vol7-C1-S7 Reg#7 Automatic sprinkler systems shall be supervised by a listed/ approved central, proprietary, or remote station, or a local alarm when approved by the Chief, which will give an audible signal at a constantly attended location when the number of sprinklers is 100 or more. (New Fire Code changes this from 100 heads to 20 heads) LACFC Construction documents: Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Construction documents should be found at the control panel. These documents will assist the engine company in locating the problem. Check the date on battery batteries. Batteries should be replaced per specifications found on the battery. The installation date should be written on the battery. 4-14
15 During the inspection the control panel annunciator should read system normal with green light(s) only. The purpose of fire alarm systems shall be primarily to provide notification of fire alarm, supervisory, and trouble conditions; to alert the occupants; to summon aid; and to control fire safety functions. You may find an annunciator panel at the main entrance and a Fire Alarm Control Panel (FACP), usually in a utility room on the premises NFPA * The authority having jurisdiction shall be notified prior to installation or alteration of equipment or wiring. At the authority having jurisdiction s request, complete information regarding the system or system alterations, including specifications, shop drawings, battery calculations, and notification appliance circuit voltage drop calculations shall be submitted for approval NFPA * All required annunciation means shall be readily accessible to responding personnel and shall be located as required by the authority having jurisdiction to facilitate an efficient response to the fire situation LACFC Obstruction of fire alarm equipment: Fire alarm initiating devices, alarm notification appliances and annunciators shall not be concealed from view, obstructed or impaired in any manner. Doors leading to fire alarm control panels shall have signage 4-15
Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS
901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
More informationModule 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements
Module 3 Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements 1 WATER-BASED SUPPRESSION SYSTEMS-PART TWO This module covers: 1. Ohio Building Code requirements and when and why
More informationMAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS
MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS Introduction When properly installed and maintained, automatic fire sprinkler systems have proven to be the most effective means for protecting life and
More informationChapter 2: Identification, water and access
Chapter 2: Identification, water and access As you are approaching the occupancy to be inspected, take note of building and fire protection services. Put yourself in the shoes of a first arriving company
More informationFlorida Building Code Chapter 9 Fire Protection Systems Advanced Course
Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors
More information2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.
2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is
More informationFlorida Building Code 2010
Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with
More informationMoreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline
Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to
More informationBlack Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment
Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment February 2017 Alberta Fire Code safety equipment maintenance requirements: The Black Diamond Fire Department has
More informationFire Pump Supervision - Part 3 by Dean K. Wilson, P.E.
Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Fire Pump Supervision - Part 3 by Dean K. Wilson, P.E. Question: As the Authority Having Jurisdiction in my suburban community in the northeastern United
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationOXNARD FIRE DEPARTMENT Fire Watch Guidelines
OXNARD FIRE DEPARTMENT Fire Watch Guidelines What is a Fire Watch? A Fire Watch is a temporary measure intended to ensure continuous and systematic surveillance of an activity, building or portion thereof
More informationSECTION 907 FIRE ALARM AND DETECTION SYSTEMS
SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing
More informationWinnipeg Fire Department Fire Prevention Branch
Winnipeg Fire Department Fire Prevention Branch Manitoba Fire Code Life-Safety Equipment Maintenance Requirements The Fire Prevention Branch of the Winnipeg Fire Department has prepared this document of
More informationOxnard Fire Department 360 W. Second Street Oxnard, CA (805) Fax (805)
Oxnard Fire Department 360 W. Second Street Oxnard, CA 93030 (805) 385-7722 Fax (805) 385-8009 FIVE YEAR CERTIFICATION REPORT Service and maintenance report for automatic fire extinguishing systems, including
More informationFIRE & LIFE SAFTEY STANDARD
Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications
More informationNew Construction Fire Inspection Process
New Construction Fire Inspection Process This document is intended to provide the Owner, Designer, and/or Contractor of new construction with an outline of required fire inspections and with the specific
More informationFire System Impairment Policy
Fire System Impairment Policy Purpose: To establish procedures to be followed, when a fire protection or suppression system is taken out of service, due to construction, alteration, power outage, repair,
More informationUpdate all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.
More informationSystem Test Report CLEAN AGENT
City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information
More informationSANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)
FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationGUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard
GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS High-Hazard This document shall apply to all Group H, High-Hazard occupancies. GENERAL Scope Reporting of emergencies, coordination with emergency response
More informationSubject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees
Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees Purpose: To establish procedures to be followed when a fire
More informationFIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION
CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION SECTION FC 1401 GENERAL 1401.1 Scope. This chapter shall govern fire safety measures during the construction, alteration, or demolition
More informationNirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection
Factory Name Address Fire Safety Follow up INTIMATE APPARELS LTD Karnaphuli EPZ, Plot no. 91-93, rth Patenga Date 05/20/2014 Date Report Received 11-August/15 Date of 1 st Follow-up 08-vember/15 Date of
More informationAgency for Health Care Administration
Page 1 of 100 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS CFR Type Memo Tag FED - KA100 - General Requirements - Other
More informationTHIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.
THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building
More informationAUTOMATIC FIRE SPRINKLER SYSTEMS
MCKINNEY FIRE DEPARTMENT FIRE MARSHAL S OFFICE AUTOMATIC FIRE SPRINKLER SYSTEMS These guidelines are to be followed when a business, facility or organization installs an automatic fire sprinkler system
More informationUniversity Design Standard Fire Alarm Systems
1.0 Overview University Design Standard Fire Alarm Systems This document provides Virginia Tech s standards for the design and installation of fire alarm systems and equipment in new construction, retrofit
More informationFull Service Central Station Fire Alarm Listing Evaluation
Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm
More informationInspection of Fire Sprinkler Systems. NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems
Inspection of Fire Sprinkler Systems NFPA 25, Inspection, Testing & Maintenance of Water Based Fire Protection Systems Objective To familiarize Facility Managers with the process of routine inspection
More informationCedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch
Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH General This information is provided to clarify the requirements for a fire watch. A fire watch is the action of a person or persons
More informationAgency for Health Care Administration
Page 1 of 51 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS CFR Type Memo Tag FED - K0130 - MISCELLANEOUS Title MISCELLANEOUS OTHER LSC DEFICIENCY NOT ON 2786 FED - K9999 - FINAL OBSERVATIONS Title
More informationSECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM
SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division
More informationInspection and Testing of Water-Based Systems
Inspection and Testing of Water-Based Systems Standard Model/Computer-Based Testing Level II Content Outline The candidate for NICET certification at Level II in the Inspection and Testing of Water- Based
More informationALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST
OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued
More informationHIGH-RISE RETROFIT ORDINANCES - NO and NO
INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.
More informationService Requirements SEMI- ANNUAL ANNUALLY OTHER REF. REQUIREMENT
58 Fire protection equipment requires care and maintenance at scheduled intervals to assure it will operate properly and safely when needed. Only personnel who are trained and qualified to maintain the
More informationI. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018
Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018 Prepared by: EH&S The probability of casualties and major structural damage increases when fire
More informationSPRINKLER SYSTEM DRY WET
Seattle Fire Department Confidence Test Report (use one form per sys.) 206-386-1448 Confidence Testing Officer 206-615-1068 (fax) 206-233-7219 Red Tag Hotline SPRINKLER SYSTEM DRY WET Status Given CONFIDENCE
More informationUC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION
SECTION: UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION INITIATOR: DALE SAUNDERS REVISION DATE: September 2015 1. Program Description 2. Scope 3. Definitions
More informationPublic Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance
Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance It is ordained by the Town Council of the Town of New Shoreham
More informationRancho Cucamonga Fire Protection District Prevention Bureau Standard
Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency
More information1301: Fire protection systems. (A) Section 901 General
ACTION: Final DATE: 12/04/2017 11:44 AM 1301:7-7-09 Fire protection systems. (A) Section 901 General (1) 901.1 Scope. The provisions of this rule shall specify where fire protection systems are required
More information1301: Fire protection systems.
ACTION: Original DATE: 10/18/2018 11:42 AM 1301:7-7-09 Fire protection systems. (A) Section 901 General (1) 901.1 Scope. The provisions of this rule shall specify where fire protection systems are required
More informationAgency for Health Care Administration
Page 1 of 92 FED - K0000 - INITIAL COMMENTS Title INITIAL COMMENTS Type Memo Tag FED - K9999 - FINAL OBSERVATIONS Title FINAL OBSERVATIONS Type Memo Tag FED - KA100 - General Requirements - Other Title
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD LICENSED CARE FACILITIES SCOPE: This standard provides requirements for licensed care facilities known as for the Elderly with seven
More informationAnnual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System
Annual Report of Inspection, Testing & Maintenance of Automatic Sprinkler System Building/Business Name: Address of Property: Inspector Name: Joe Price THE CORNERSTONE 1425 NE 7TH AVENUE PORTLAND OR Date
More informationFIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures
FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE
More informationPRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING
SUMMARY PROVER'S PLAN OF CORRECTION K 000 INITIAL COMMENTS K 000 A Life Safety Code Survey was conducted by the State Fire Marshal beginning on May 9th, 2017 and ending on May 10th, 2017. Adair Acute Care
More informationFunctional Performance Test
Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control
More informationAPPENDIX H (DESIGN SUBMISSION CRITERIA)
APPENDIX H (DESIGN SUBMISSION CRITERIA) FIRE ALARM SYSTEM As per ACCORD standard Part 5, section 5.7 Fire Alarm System Design to be verified by ACCORD Chief Safety Inspector. Testing of the installation
More informationDEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS
Section 400.000 Suppression Systems The purpose of this guide is to assist the Incident Commander (IC), Fire Officers and Firefighters with the planning of effective operations for supporting water-based
More informationAUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations)
AUTOMATIC FIRE SPRINKLER SYSTEM STANDARDS Development Standard #4.1 (Commercial Installations) This standard applies to the design and installation of automatic fire sprinkler systems in conjunction with
More information1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.
PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This
More informationTable of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME
Table of Contents CHAPTER 10 ADMINISTRATIVE RULES FOR CERTIFICATION OF CHILD CARE FACILITIES FIRE STANDARDS FOR FAMILY CHILD CARE HOME Section No. Subject Page No. 1 Authority and Purpose 10-1 2 Definitions
More informationCITY OF PASADENA FIRE DEPARTMENT
Page 1 of 8 CITY OF PASADENA FIRE DEPARTMENT INSTALLATION OF COMMERCIAL SPRINKLERS (Revised 12/10/2014) SCOPE: This standard applies to the design and installation of automatic fire sprinkler systems in
More informationIowa State Fire Marshal
Iowa State Fire Marshal LIFE SAFETY CODE REQUIREMENTS LONG TERM CARE Kyle R. Gorsh, Special Agent in Charge Iowa Department of Public Safety State Fire Marshal Division 2012 LSC & Applicable Standards
More informationGENERAL AREAS OF INSPECTION
This information is intended to assist you in preparation for the annual high-rise inspection. This is not a complete list and the Inspector may identify other conditions or issues in the building that
More informationUnderstanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training
Understanding, Applying and Enforcing NFPA 25 James D. Lake NFSA Director of Training When Sprinklers Are Ineffective Water did not reach fire 8% 7% 7% 5% 44% Not enough water released Damaged Component
More informationWritten Fire Safety Plans
Written Fire Safety Plans 2012 LSC KATHARINE ACHOR SEPTEMBER 2016 NFPA Standard: 2012 NFPA 101, 19.1.1.3.1 All health care facilities shall be designed, constructed, maintained, and operated to minimize
More informationQuick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA & NFPA 13/
Quick Guide for Fire Sprinkler Inspection Requirements Key Deficiencies with NFPA References NFPA 25 2017 & NFPA 13/72 2016 The purpose of this guide is to help you determine if the system will work as
More informationHCD DSA OSHPD 1 2 1/AC AC SS SS/CC
CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 30 ELEVATORS AND CONVEYING SYSTEMS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency
More informationSTATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL
STATE OF MARYLAND DEPARTMENT OF STATE POLICE OFFICE OF THE STATE FIRE MARSHAL Larry Hogan Governor Boyd K. Rutherford Lt. Governor 1201 Reisterstown Road Pikesville, MD 21208 410-653-8980 Fax 410-653-8988
More informationDERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM
DERRY FIRE DEPARTMENT LISTED AGENT CERTIFICATION PROGRAM THIS COURSE IS FOR AGENTS WISHING TO DISABLE TRANSMITTING SIGNALS IN ORDER TO PERFORM MAINTENANCE TESTING AND DRILLS. OBJECTIVE The objective of
More informationSANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST
July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST FIRE AND LIFE SAFETY SYSTEMS FOR STRUCTURES FIVE OR MORE STORIES IN HEIGHT AND LESS THAN 75 FEET IN HEIGHT FROM THE POINT
More informationNova Scotia Fire Dispatch Minimum Standards (2017)
Fire Service Association of Nova Scotia Nova Scotia Fire Dispatch Minimum Standards (2017) July 14, 2017 Scope This document sets out the minimum standards to which fire dispatch operations are expected
More informationFire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment):
Fire Safety Plan (Single-Stage Fire Alarm System) (Small Establishment): Fire Safety Plan Single-Stage Fire Alarm System for: (Business Name) (Business Address) Submission Date - Submitted by - Signature
More informationMount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION
Mount Laurel Fire Department, Office of The Fire Marshal FIRE WATCH NOTIFICATION (Please Print or Type) PREMISE DATE TIME ADDRESS RESPONSIBLE PERSON PHONE ORDERED BY RECEIVED BY CIRCUIT INTERVALS FIRE
More informationChanges in NFPA
Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration
More informationNew Facilities. Minimum Requirements
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 Item Reference Violation General Requirements NFPA 1124-7.1.1 Retail sales of consumer fireworks in both new and existing buildings, structures, and
More informationC. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.
SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this
More information2010 FIRE CODE OF NEW YORK STATE
2010 FIRE CODE OF NEW YORK STATE CHAPTER 14 FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION SECTION 1401 GENERAL 1401.1 Scope. This chapter shall apply to structures in the course of construction, alteration,
More informationRequired vs. Non-required Fire Protection Systems. Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer
Required vs. Non-required Fire Protection Systems Dan Austin Chief Fire Code Consultant/State Fire Protection Engineer What are we going to cover? What makes a system required? What to do when a non-required
More informationAutomatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems
Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life
More informationMontgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040
Montgomery County Government Building and Codes Department 350 Pageant Lane, Suite 309 Clarksville, TN 37040 SPRINKLER SHOP DRAWINGS 2007 NFPA 13 and 2007 NFPA 24 Project: Listed items require sprinkler
More informationHOW COMMERCIAL FIRE PROTECTION SPRINKLER SYSTEMS REALLY OPERATE
A Guide for Fire Sprinkler Maintenance and Operation Commercial fire protection sprinkler systems have been saving lives and reducing property damage for more than a century. New England s textile mills
More informationSECTION FIRE ALARM SYSTEMS
SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationRocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO
Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO 80303 303-494-3735 Contractor s Checklist and Installation Guide TABLE OF CONTENTS Fire Protection Narrative........... 3
More informationGLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE
GLENDALE FIRE DEPARTMENT FIRE MARSHAL S OFFICE To: From: Subject: Whom It May Concern Carl Ray Austerman, Fire Marshal Contractor s Guide Welcome to the Glendale Fire Department s Contractors Guide. This
More informationESCONDIDO FIRE DEPT TRAINING MANUAL Section Engine Module Page 1 of 8 Annual Sprinkler System Inspection Revised
Engine Module Page 1 of 8 ANNUAL INSPECTOR S TEST Note: In 2014 the Escondido Fire Department discontinued performing an Inspector s Test on sprinkler systems electing to inspect the system as outlined
More informationrpsa FIRE PROTECTION ENGINEERS
FIRE PROTECTION ENGINEERS R.P. SCHIFILITI ASSOCIATES, INC. P.O. Box 297 Reading, Massachusetts 01867-0497 USA 781.944.9300 Fax / Data 781.942.7500 Telephone Elevator Fire Safety: Elevator Recall and Elevator
More informationA Building Manager s Guide to Maintaining Fire Code Compliance
A Building Manager s Guide to Maintaining Fire Code Compliance Know your role in conducting fire protection system inspections : Fire Alarm Codes and Standards Maintaining your compliance with fire code
More information1.3 REFERENCE STANDARDS
SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises
More informationFIRE SERVICE FEATURES
CHAPTER 5 FIRE SERVICE FEATURES SECTION 501 GENERAL 501.1 Scope. Fire service features for buildings, structures and premises shall comply with this chapter. 501.2 Permits. A permit shall be required as
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 5 Page 1 of 6 I. PURPOSE This policy outlines the guidelines for posting a fire watch if the fire alarm and/or fire suppression system in any University building becomes inoperable and the
More informationRULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS
RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER 0780-02-07 FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS TABLE OF CONTENTS 0780-02-07-.01 Definitions 0780-02-07-.08 Installation,
More informationSECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD
PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard
More informationFire Safety Plan FOR. Business/Property Name: Address: Phone Number: Occupancy Classification. Approved by Fire Inspector: Date:
Fire Safety Plan FOR Business/Property Name: Address: Phone Number: Occupancy Classification Approved by Fire Inspector: Date: Table of Contents Part 1 Building Resources Audit Page 3 Part 2 Human Resources
More informationa) Establishment of emergency procedures to be followed at the time of an emergency;
5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing
More informationFIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
SANTA MONICA FIRE DEPARTMENT Fire Prevention Division 333 Olympic Drive 2 nd Floor Santa Monica, CA 90401 310-458-8915 / Fax 310-395-3395 FIVE YEAR AUTOMATIC FIRE EXTINGUISHING SYSTEMS CERTIFICATION REPORT
More informationResidential Based Care Facility Guidelines
Moreno Valley Fire Department Fire Prevention Bureau Residential Based Care Facility Guidelines Approved and Authorized By: Randall Metz, Fire Marshal Issued: January 1, 2011 Residential Based Care Facilities
More informationUNIVERSITY. Facilities Management
EAST TENNESSEE STATE UNIVERSITY Facilities Management Policy Number: 700.10 Title: Fire Protection Impairment Program Implementation Date: April, 2008 Last Revised: August 4th, 2014 Introduction The probability
More informationSouthaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax:
Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi 38671 Phone: 662-393-7466 Fax: 662-280-6521 Fire Alarm Maintenance Guide The City of Southaven enforces the 2012
More informationBold items are particular to the City of Euless
EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards
More informationPART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:
PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,
More informationFire Sprinkler System Design and Installation Requirements
Fire Sprinkler System Design and Installation Requirements The Park City Fire Service District (PCFD) and Park City Municipal Corporation (PCMC) have made the following amendments to the State of Utah
More informationMONTECITO FIRE PROTECTION DISTRICT
Section 5a MONTECITO FIRE PROTECTION DISTRICT FIRE PROTECTION PLAN Residential Automatic Fire Sprinkler System Installations I Automatic Fire Sprinkler System Standards 1. Definition and Standard: An automatic
More information1301: Fire protection systems. Section 901 General
ACTION: Revised DATE: 10/26/2017 4:58 PM 1301:7-7-09 Fire protection systems. (A) Section 901 General (1) 901.1 Scope. The provisions of this rule shall specify where fire protection systems are required
More information