1 Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE

2 Inspections and tests are intended to reduce or limit: Loss of life Loss of property Inspections and Tests

3 Inspections and tests are required by NFPA 72, National Fire Alarm and Signaling Code Adopted by other codes Required by law Inspections and Tests

4 Approved Authority Having Jurisdiction (AHJ) Code Listed Shall Should Definitions

5 Nothing in this Code shall prevent the use of systems, methods, devices, or appliances of equivalent or superior quality, strength, fire resistance, effectiveness, durability, and safety over those prescribed by this Code. Equivalency

6 As an alternate means of compliance, subject to the authority having jurisdiction, components and systems shall be permitted to be inspected and tested under a performance-based program. Performance Based Testing

7 Inspection, testing, and maintenance programs shall satisfy the requirements of this Code and conform to the equipment manufacturer s published instructions. Inspection, testing, and maintenance programs shall verify correct operation of the system. Equivalency

8 NFPA 72 requires inspection, testing, and maintenance personnel to be qualified and experienced. Examples include, but are not limited to the following: (continued on next slides) Qualifications

9 Personnel who are factory trained and certified for the specific type and brand of system being serviced Examples of Qualifications

10 Personnel who are certified by a nationally recognized certification organization acceptable to the authority having jurisdiction Examples of Qualifications

11 Personnel who are registered, licensed, or certified by a state or local authority to perform service on systems addressed within the scope of this Code Examples of Qualifications

12 Personnel who are employed and qualified by an organization listed by a nationally recognized testing laboratory for the servicing of systems within the scope of this Code Examples of Qualifications

13 Who is responsible to ensure that inspections, tests, and maintenance are carried out? The property owner, or The system owner, or The building owner, or Their designated representative Delegations must be in writing Must provide a copy for the AHJ when requested Responsibilities

14 Record (as-built) drawings Calculations Operations and Maintenance (OM) Manual Sequence of Operations Matrix of Operation Record of Completion NFPA 72 Previous Inspection and Test Report Required Documentation

15 Documentation

16 Questions?

17 Inspections do NOT involve any physical operation of the system components. Inspection: To look at carefully;; examine critically. A checklist is recommended Inspections

18 Things We Look for During Inspections Broken or damaged equipment Improperly located equipment Incorrect strobe ratings Incorrect heat detector rating Incorrect device/appliance spacing Poor wiring methods Missing equipment Building changes that affect operation Equipment blocked by building furnishings or other equipment Inspections

19 Inspections

20 Inspections

21 Inspections

22 Inspections

23 Inspections

24 Initial/Acceptance Re-Acceptance Periodic Types of Inspections

25 Conducted when system is installed. Involve a 100% inspection Used to verify code compliance and functionality Initial/Acceptance Inspections

26 Conducted when the system changes Addition of new devices or equipment Deletion of devices or equipment Inspect changes to system Re-Acceptance Inspections

27 Conducted even if the system does not change. NFPA 72 contains frequencies of inspection in Table Periodic Inspections

28 Questions?

29 Testing involves a physical manipulation of the component or equipment. Test: An examination or trial, as to prove the value or find out the nature of something. Use a checklist Use drawings Testing

30 Testing

31 Bulletin boards Signs Voice announcements Telephone calls Radios and pagers Text messages Occupant Notification

32 Occupant Notification

33 Fire Marshal/Chief/Engineer Building Inspector Wiring Inspector (Electrical) Representative of Owner/Occupant Representative of Insurance Carrier Supervising Station Notification of Testing

34 Record (as-built) drawings Operations and Maintenance (OM) Manual Sequence of Operations Matrix of Operation Record of Completion NFPA 72 Previous Test Report (if applicable) Required Documentation

35 Ladders Radios Smoke or listed aerosol per manufacturer s requirements Keys/special wrenches Hand tools Heat source NFPA 72 Manometer or Magnehelic Volt-Ohm Meter (VOM) Battery test meter Sound Pressure Level (SPL) meter Stopwatch Highlighters, pencils, and clipboard Required Tools and Equipment

36 When testing, avoid occupant/owner disruption. Walk test (silent) Test during off-hours Simulate tests only where necessary Types of Tests

37 Initial/Acceptance Re-Acceptance Periodic Types of Tests

38 Conducted when system is installed. Involve a 100% test Used to verify code compliance and correct operation Initial/Acceptance Tests

39 Everything MUST be Tested 100% Initial/Acceptance Tests

40 Conducted when the system changes Addition of new devices or equipment Deletion of devices or equipment Changes in software programming Re-Acceptance Tests

41 Site Specific Software changes Test all known changes, plus a functional test of 10% of initiating devices (up to 50) Basic Input/Output Software (BIOS) or firmware changes Test 10% of entire system At least one device or appliance on each circuit Re-Acceptance Tests

42 Periodic tests are conducted even if the system does not change. NFPA 72 contains frequencies of testing in Table Periodic Tests

43 Periodic Test Frequencies

44 NFPA 72 contains the methods of testing each component in Table Test Methods

45 Control Units (monitored vs. unmonitored) Control functions Fuses Interfaced equipment Lamps & LED Primary/secondary power supply Tests 45

46 Test battery charger annually 30 minute battery discharge test annually Load voltage battery test semiannually Other testing depending on battery type Tests 46

47 Verify signal receipt by operating the public emergency alarm reporting system box. Tests 47

48 Verify correct operation and identification of all annunciator functions Tests 48

49 Metallic conductors are tested only prior to initial tests: Measure stray voltage Measure voltage to ground Measure resistance to ground Measure resistance between conductors Measure loop resistance Tests 49

50 Using a heat source, test 2 or more RESTORABLE detectors on each circuit annually Test different RESTORABLE detectors each year DO NOT use open flames Tests 50

51 DO NOT test NON- RESTORABLE detectors with heat Electrically test contacts annually Replace all detectors after 15 years or test statistical sample (2 per 100) Tests 51

52 Other non-restorable heat detectors Line type Rate-of-Rise/Fixed Temperature Tests 52

53 Smoke Detector Functional Test Ensure smoke entry into sensing chamber and response Use aerosol or real smoke acceptable to manufacturer Tests 53

54 Aerosol smoke may contain oils. Use short puffs Keep a reasonable distance Too Close!!! 54

55 Tests Testing smoke detectors with a magnet is NOT considered a functional test. Use magnets for pre-testing. NFPA 72 requires smoke entry! 55

56 Smoke detector sensitivity Tests Calibrated test method Manufacturer s calibrated sensitivity test instrument Listed control unit arranged for the purpose Smoke detector/control unit arrangement whereby the detector causes a signal at the control unit when its sensitivity is outside its listed sensitivity range Other methods approved by the AHJ Tests 56

57 Calibrated test methods Tests 57

58 Manufacturer s calibrated test instrument Tests 58

59 Smoke detectors that report to the system controls when outside their listed and marked sensitivity range Use printer or buffer to record sensitivity of each device Tests 59

60 Sensitivity tests are conducted within one year after installation and every alternate year. May be extended to 5 years Good records are essential!!! Tests 60

61 Duct smoke detectors require the same functional and sensitivity tests as area smoke detectors Test sampling tube pressure using a manometer Tests 61

62 A manometer or Magnehelic are required for testing pressure difference across sampling tubes per the manufacturer s instructions. Tests

63 Waterflow switches must actuate within 90 seconds of flow equal to the flow from a single sprinkler head The device must not respond to surges and varying pressure Tests 63

64 Operate manual fire alarm boxes using manufacturer s recommended methods It may be necessary to remove glass rods/plates Keys/wrenches are required Tests 64

65 Pressure Type Waterflow Switches Operate switch Used on dry-pipe, preaction and deluge systems May be used on wetpipe systems Tests 65

66 Water tank level Water tank temperature Tests 66

67 Off-normal within 2 revolutions or 1/5 the travel distance of the valve Restoration-tonormal only when valve is open Tests 67

68 Consult NFPA 20, Standard for Stationary Fire Pumps Diesel Pumps Running Controller in other than automatic Failure to start Engine functions Electric Pumps Running Loss of power Loss of phase Phase reversal Tests 68

69 Radiant energy fire detectors Tests 69

70 Bells Horns Speakers Lights Textual Displays Combination Tests 70

71 Source Tests Meter 5 feet above floor 71

72 Public Mode Signaling 15 dba above average ambient SPL, or 5 dba above the maximum SPL lasting a minute or more Measure 5 feet above the floor Test annually Private Mode Signaling 10 dba above average ambient SPL, or 5 dba above the maximum SPL lasting a minute or more Measure 5 feet above the floor Test annually Tests 72

73 Sleeping Areas 15 dba above average ambient SPL, or 5 dba above the maximum SPL lasting a minute or more, or 75 dba, whichever is greater Test with barriers (doors, curtains, etc.) in place. Measure at the pillow Tests 73

74 Initial audible system tests Measure for conformity with NFPA 72 Periodic audible system tests Measure where building, system, or occupancy changes have occurred Tests

75 Areas likely to require intelligibility tests Places of worship Atria Transportation centers Covered malls Sporting venues Large assembly Tests 75

76 Required for ECS Not required in all areas Designer must designate Acoustically Distinguishable Spaces (ADS) Score of 0.50 on STI scale is required Tests 76

77 Verify correct rating of visible notification appliances (strobes) during the inspection Verify visible appliances operate Test annually Tests 77

78 DACT Follow manufacturer s instructions Verify connection to 2 separate means of communication, per NFPA 72 Verify line seizure capability Test loss of communications means and verify trouble signal is transmitted to supervising station within 4 minutes Tests 78

79 Elevator recall and shutdown HVAC shutdown Stair pressurization Smoke door releasing Door unlocking devices Damper control Smoke evacuation Tests 79

80 Test end-to-end when possible. Test by operating or simulating alarm signals when necessary Test at the same frequency as the initiating device that causes the function to occur (most are annual) Tests 80

81 Test Frequencies

82 Test Frequencies

83 Test Frequencies

84 Test Frequencies

85 Systems must be returned to service after testing is completed. Notify AHJ when any system is down for more than 4 hours. Fire watches may be required Verbally notify owner in writing of ANY deficiencies and follow up in writing within 24 hours Impairments and Deficiencies

86 Follow manufacturer s requirements Environment may warrant more frequent maintenance Maintenance

87 Field repairs to boards and other equipment is generally not permitted by the manufacturer. Only factory repairs are permitted. Maintenance

88 Most manufacturer warranties extend to 12 months Warranties usually start on the day of acceptance Warranties may be extended by contract Warranty

89 Some jurisdictions require maintenance contracts Systems that are not properly maintained will usually suffer from early failures Service Contracts

90 Record of Completion (NFPA 72) New systems Changes to system Record of Inspection, Test, and Maintenance (NFPA 72) All inspections and tests Records

91 Other records As-built (record) drawings Operations and Maintenance (OM) manuals Site specific software Building permit Records

92 For software-based systems, a copy of the site-specific software shall be provided to the system owner or owner s designated representative. A copy of the site-specific software shall be stored on-site in non-volatile, non-erasable, non-rewritable memory. The system owner shall be responsible for maintaining these records for the life of the system for examination by any authority having jurisdiction. Paper or electronic media shall be permitted. Records

93 Documentation

94 The owner must retain drawings and Record of Completion for the life of the system All other records must be retained for one year after the next test Keep at the FACU or in a separate enclosure labeled FIRE ALARM DOCUMENTS Records

95 System defects and malfunctions shall be corrected. If a defect or malfunction is not corrected at the conclusion of system inspection, testing, or maintenance, the system owner or the owner s designated representative shall be informed of the impairment in writing within 24 hours. Impairments

96 Be careful to avoid pitfalls that can cause liability. Consequences

97 Questions?

98 Thank You. Merton Bunker, PE Contact Information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax:

Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi Phone: Fax: Southaven Fire Department Fire Marshal s Office 8710 Northwest Drive Southaven, Mississippi 38671 Phone: 662-393-7466 Fax: 662-280-6521 Fire Alarm Maintenance Guide The City of Southaven enforces the 2012

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Fire Alarm System Inspection and Testing Report

Fire Alarm System Inspection and Testing Report Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local

More information

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION July 1, 2010 SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION Address: Permit #: Inspector: Date: Status: Inspector: Date: Status: A-Approved; AC-Approved

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities

NFPA Siemens Industry, Inc. All rights reserved. usa.siemens.com/infrastructure-cities Fire Alarm and Signaling Code Overview NFPA 72-2010 usa.siemens.com/infrastructure-cities Siemens Building Technologies, Inc. is a Registered Provider with The American Institute of Architects Continuing

More information

Unified Fire Authority - Fire Prevention Bureau

Unified Fire Authority - Fire Prevention Bureau Unified Fire Authority - Fire Prevention Bureau FIRE ALARM AND EMERGENCY COMMUNICATION SYSTEM RECORD OF COMPLETION To be completed by the system installation contractor at the time of system acceptance

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

INSPECTION AND TESTING FORM

INSPECTION AND TESTING FORM INSPECTION AND TESTING FORM Date: Time: SERVICE ORGANIZATION Name: Address: Representative: License No.: MONITORING ENTITY Contact: Monitoring Account Ref. No.: TYPE TRANSMISSION McCulloh Multiplex Digital

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

NFPA Changes

NFPA Changes Chapter 14, Inspection, Testing, and Maintenance Summary. Chapter 14 was Chapter 10 in NFPA 72-2007. The phrase fire alarm was deleted leaving the more generic term system. Technician qualification requirements

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

Smoke Detector Activation of any smoke detector shall start the alarm verification mode. Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Alarm System Plan Review 2009 International Fire Code and 2010 NFPA 72 Date of Review // BLD201 - Project Address: Project Name: _ Professional

More information

System Test Report CLEAN AGENT

System Test Report CLEAN AGENT City of Black Hawk Fire Department 196 Clear Creek Street PO Box 68 Black Hawk, CO 80422-068 Office 303-582-0426 Fax 303-582-2229 www.cityofblackhawk.org System Test Report CLEAN AGENT Occupancy Information

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS

SECTION 907 FIRE ALARM AND DETECTION SYSTEMS SECTION 907 FIRE ALARM AND DETECTION SYSTEMS 907.1 General. This section covers the application, installation, performance and maintenance of fire alarm systems and their components in new and existing

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES Report on Comments

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary 907.7 Acceptance tests and completion. Upon completion of the installation, the fire alarm system and all fire alarm components shall be tested in accordance with NFPA 72. A complete performance test of

More information

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability Fire Alarm Inspection, Testing, Maintenance Assuring the System s Operational Reliability What does AFAA-NE do? Education We supply the tools our members require to perform within the guidelines of our

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Anywhere, USA 30303 Tested to NFPA 72 Standards This Inspection was performed in accordance with applicable

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number: 109-B Concord Drive Casselberry, FL 32707 407.830.6500 DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72 Pg 1 of 4 Equity One 11180600 Owner/Representative: WO#: _Customer#: 1550 NE Miami Garden Dr

More information

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website.

COMMISSION ORDER. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No. 2016-316 Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM DIVISION 26 ELECTRICAL SECTION 26 81 11 PART 1 GENERAL 1.01 DESCRIPTION A. Furnish and install all equipment and accessories for a complete local, analog addressable, manually and automatically actuated,

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

Applying Performance-based Fire Alarm System Design Part 4

Applying Performance-based Fire Alarm System Design Part 4 Fire Alarm Notebook by Dean K. Wilson. P.E. Page 1 Applying Performance-based Fire Alarm System Design Part 4 by Dean K. Wilson, P.E. Over the course of the last four issues I have continued to discuss

More information

Are You Prepared? The impending impact of Code on Servicing Security Systems

Are You Prepared? The impending impact of Code on Servicing Security Systems Sam Docknevich, PSP, Security Service Portfolio Manager Are You Prepared? The impending impact of Code on Servicing Security Systems Siemens AG 2015 All rights reserved. usa.siemens.com/infrastructure-cities

More information

2019 COURSE CATALOG (rev )

2019 COURSE CATALOG (rev ) 2019 COURSE CATALOG (rev. 02.07.19) www.afaa.org CEUs Available for NICET, Engineers and Other! 3246 Noe-Bixby Road, Suite 101, Columbus, OH 43232 844-438-2322 Page 1 Page No. Seminar Name 3. A User s

More information

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces

MODULE 8. Tying the Systems Together: Emergency Control Functions and Interfaces MODULE 8 Tying the Systems Together: Emergency Control Functions and Interfaces 1 OVERVIEW OF MODULE 8 In this module we will: Describe all components, their arrangements and how the systems work Describe

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016

Minimum Standards for Engineers Practicing Fire Protection Engineering in the State of Oklahoma September 14, 2016 1. Introduction The intent of this document is to establish minimum standards for the practice of fire protection engineering within the State of Oklahoma as conducted by licensed professional engineers.

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Testing and Maintenance

More information

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge.

2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. 2. The Group F occupancy has have an a combined occupant load of 500 or more above or below the lowest level of exit discharge. Exception: Manual fire alarm boxes are not required where the building is

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

2018 NICET Code Transition Changes

2018 NICET Code Transition Changes 2018 NICET Code Transition Changes NICET will be transitioning to newer codes accepted in their exams in mid-october 2018, specifically: NFPA 72 2016 NFPA 70 2014 IBC 2015 NFPA 101 2015 Here are some changes

More information

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO Prepared For: Public Schools Facilities Authority State of New Mexico 2019 Galisteo, Suite

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

HIGH-RISE RETROFIT ORDINANCES - NO and NO

HIGH-RISE RETROFIT ORDINANCES - NO and NO INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: LAMC 91.8604 Effective: 9-06-90 DOCUMENT NO. P/BC 2002-054 Revised: 4-15-03 Previously Issued As: MGD 88 HIGH-RISE RETROFIT ORDINANCES - NO.

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

IN2 Digital, Addressable Fire-alarm System

IN2 Digital, Addressable Fire-alarm System Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Digital, Addressable Fire-alarm System Illinois Mathematics and Science Academy Follow this and additional works at: http://digitalcommons.imsa.edu/facility_in2_manuals

More information

Advanced Fire Alarm Systems Training Program Outline (5 Day)

Advanced Fire Alarm Systems Training Program Outline (5 Day) Advanced Fire Alarm Systems Training Program Outline (5 Day) Day 1 Prescriptive and Performance-Based Design Understand the methodology in accessing the threat of fire within a structure. Know the difference

More information

Fire Alarm Wiring. Circuit types, styles and limitations

Fire Alarm Wiring. Circuit types, styles and limitations Fire Alarm Wiring Circuit types, styles and limitations What we will cover Types Classes Notification Appliance Circuits (NAC) Initiating Device Circuits (IDC) Signaling Line Circuits (SLC) Class A, B,

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 DESCRIPTION SECTION 28 46 00 SPEC WRITER NOTES: 1. The A/E must obtain a copy of the VA ENGINEERING GUIDE FOR FIRE PROTECTION DESIGN which provides fire alarm system criteria that

More information

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 28 31 00 FIRE ALARM AND SMOKE DETECTION SYSTEMS A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A.

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015

CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 CAN/ULC-S1001, INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION & LIFE SAFETY SYSTEMS Simon Crosby, LEL, CET, CFPS October 21, 2015 Fire Commissioning in Canadian Codes and Standards BACKGROUND Why Commissioning?

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-28 31 13.00 40 (February 2017) ----------------------------------- Preparing Activity: NASA Superseding UFGS-28 31 13.00 40 (May 2013) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Fire Alarm Testing and Inspection Report

Fire Alarm Testing and Inspection Report Fire Alarm Testing and Inspection Report Property Name: Property Address: Property Manager: Contact: Phone Number: Central Station: Phone Number: PELICAN ISLE II 35 DOCKSIDE RD. NAPLES, FLORIDA 3110 BILL

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM SECTION 2 8 31 00 FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Request For Proposal apply to this Section.

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate www.fleenorsecurity.com 3 Morgan Court Johnson City, TN 37604 (423) 282-3755 Fire Alarm and Life Safety System Inspection Certificate For Sample Inspection Report 123 Main Street Johnson City, TN 37604

More information

MNEC NFPA 72 WHITE PAPER

MNEC NFPA 72 WHITE PAPER MNEC NFPA 72 WHITE PAPER In 2010, the National Fire Protection Assocation (NFPA), significantly changed their code # 72 (National Fire Alarm Code) and has forever improved the importance of communicating

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

FIRE DETECTION & ALARM SYSTEM BASICS

FIRE DETECTION & ALARM SYSTEM BASICS FIRE DETECTION & ALARM SYSTEM BASICS. 8 Fernwood Road Florham Park, New Jersey 07932 Siemens Building Technoloiges, Inc. ii Table of Contents Fire Detection and Alarm System Basics 1 General System Types

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system. SECTION 283111 - PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA

A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK. James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA A COMPARISON OF FIRE ALARM SYSTEM REQUIREMENTS IN THE US AND UK James R. Lugar Jr., P.E. Rolf Jensen & Associates, Inc. SFPE 2012 Savannah, GA Presentation Objective Compare fire alarm system design methods

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM SECTION 28 31 00 FIRE DETECTION AND ALARM SPEC WRITER NOTES: This specification addresses fire alarm systems installations of the following configurations/conditions: 1. A fully addressable fire alarm

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved

WESTIN HOTEL. Smoke Control System. Testing Procedures Manual. October 10, Copyright Impact Engineering, Inc All Rights Reserved IMPACT ENGINEERING, INC. WESTIN HOTEL Smoke Control System Testing Procedures Manual October 10, 2016 Copyright Impact Engineering, Inc. 2016 All Rights Reserved This manual is protected by the U.S. Copyright

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101

More information

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.

More information

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

FIRE ALARM SYSTEMS INFORMATION PACKET. Des Moines Fire Department Fire Prevention Bureau

FIRE ALARM SYSTEMS INFORMATION PACKET. Des Moines Fire Department Fire Prevention Bureau FIRE ALARM SYSTEMS INFORMATION PACKET Des Moines Fire Department February 2011 TABLE OF CONTENTS PURPOSE... 3 SCOPE... 3 ACRONYMS... 3 GUIDELINES... 3 I. INTRODUCTION... 3 A. APPLICABLE CODES AND STANDARDS.

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST OPTIONAL INFORMATION Name of School: Date of Inspection: Vocational Program/Course/Room: Signature of Inspector: ALARM SYSTEMS AND EVACUATION PLANS Guidelines: This checklist covers regulations issued

More information

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards

Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Addressing Sound Masking Requirements in the National Fire Alarm and Signaling Code and UL Standards Wayne D. Moore, P.E., CFPS, SET Vice President JENSEN HUGHES 117 Metro Center Boulevard, Suite 1002

More information

Page 1 of 40 First Correlating Revision No. 15-NFPA 72-2014 [ Global Input ] 10.5.4 Plans Examiners and Inspectors. 10.5.4.1 Fire alarm system and emergency communications system plans and specifications

More information

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS SECTION 280500 COMMON WORK RESULTS FOR SAFETY AND SECURITY PART 1 - GENERAL 1.1 RELATED SECTIONS A. All division 28 work shall, in addition to all division 1 specification sections, comply with all of

More information

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208)

Idaho Surveying & Rating Bureau, Inc South Cobalt Point Way Tel: (208) Meridian, Idaho FAX: (208) Idaho Surveying & Rating Bureau, Inc. 1871 South Cobalt Point Way Tel: (208) 343-5483 Meridian, Idaho 83642 FAX: (208) 895-8059 www.isrb.com e-mail info@isrb.com Joseph C. Harbacheck, CIC Secretary - General

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information