1 4.e STATE OF MISSOURI County of Franklin ss. COMMISSION ORDER Commission Order No Third Quarter Term 2016 Tuesday,August,09,2016 Bid Notice IN THE MATTER OF ADVERTISING FOR SEALED BIDS FOR SMOKE DETECTOR INSPECTIONS WHEREAS, the Commission has determined that it is necessary to have all smoke detectors and related equipment tested and inspected on a semi-annual basis; and WHEREAS, the Commission has determined that it is in the best interest of to purchase such Inspections through the competitive bidding process. IT IS THEREFORE ORDERED that sealed bids for the services necessary to inspect smoke detectors are requested from interested bidders with notice to bidders to be published in the August 17, 24, and 31, 2016 editions of the Washington Missourian with said bids to be due and submitted no later than 10:00 AM on September 6, Bids should be submitted to the office of the Clerk, 400 East Locust, Room 201, Union, Missouri and in a sealed envelope marked with Smoke Detector Inspections and with opening date of September 6, 2016 plainly marked on envelope. IT IS FURTHER ORDERED that the Request for Bid and Notice to Bidders be displayed on the Franklin County website. IT IS FURTHER ORDERED that a site visit will be conducted on August 26, 2016 at 10:00 AM. IT IS FURTHER ORDERED that prospective bidders be notified that the Commission reserves the right to reject any and all bids. IT IS FURTHER ORDERED that a copy of this Order be provided to the Sheriff s Office, Attn: Capt. Dave Boehm. Presiding Commissioner Commissioner of 1 st District Commissioner of 2 nd District Updated: 8/8/2016 1:06 PM by Doris Meyer Page 1 Packet Pg. 53

2 4.e.a Security and Life Safety Monitoring and Inspections 1. Part 1 - General 1.2. References Codes-General All work and materials shall conform to all applicable federal, state and local codes and regulations governing the testing, inspecting and monitoring of each of the systems. If there is a conflict between the referenced standards, federal, state or local codes, and this specification, it is the bidder s responsibility to immediately bring the conflict to the attention of the County for resolution. National standards shall prevail unless local codes are more stringent. The bidder shall not attempt to resolve conflicts directly with the local authorities unless specifically authorized Quality Assurance Qualifications of Service Provider The service provider shall have a minimum of 5 years of experience in service of the equipment brand. The provider shall have successfully designed, installed, and monitored similar system fire detection and security on a previous project of comparable scope, size and complexity. The project shall be supervised by personnel certified by NICET as fire alarm Level IV technicians. The provider shall be responsible for providing qualified on site representative(s) for coordination of system testing and commissioning in accordance with these specifications Qualifications of Provider The contractor shall submit copies of all required Licenses and Bonds as required in the State having jurisdiction. The contractor shall employ on staff a minimum of one NICET level II technician or a professional engineer, registered in the State of the installation. Contractors unable to comply with the provisions of Qualification of Installers shall present proof of engaging the services of a subcontractor qualified to furnish the required services Project Conditions Responsibility Packet Pg. 54

3 4.e.a It shall be the contractor's responsibility to inspect the job site and become familiar with the conditions under which the work will be performed. All work may be conducted during normal working hours, 8:00 a.m. to 5:00 p.m., Monday through Friday Site Devices The following is a list of the Properties and an estimate of equipment for each. It is the responsibility of the contractor to verify site conditions, including device counts. Jail 1 Bruns Dr Union, MO Analog Control Panel 1 System Modules 1 Remote Annunciators Panel Battery 1 2 Signature Series Intelligent Detectors 94 3 Detector Bases 97 SuperDuct Signature Smoke Detector SuperDuct Sampling Tubes 7 SuperDuct Remote Test Stations 7 Signature Series Life Safety Modules Manual Pull Stations Input Modules 6 8 Output Modules 7 2 Signature Module Mounting Accessories Packet Pg. 55

4 4.e.a UIO Module Motherboards 2 SIGA-UIO6 Genesis Temporal Fire Horn-Strobes, Wall Mount, 84.4/79.4 dba, Multi-candela, 1 Gang 11 G1RF-HDVM 1.5. Inspections Test and Inspection - Fire A. Testing, general 1. The contractor shall perform all testing in occupied facilities at times of day that present the lowest impact and disruption to business and activities. Coordinate all testing in occupied buildings with the building owner s representative to assure that fire alarm system testing does not interrupt operations. 2. All equipment, instruments, tools and labor required to conduct the system tests shall be provided by the provider. At a minimum, the following equipment shall be made available for testing: a. Ladders and scaffolds as required to reach all installed equipment. b. Meters for reading voltage, current and resistance. c. Two-way communication devices d. Simulated smoke, heat-producing devices for heat detectors, extension poles for introducing smoke into detectors, as needed. e. Manufacturer s instruments to measure air flow through duct smoke detectors. f. Decibel meter. g. Status and diagnostic software and PC. B. All testing shall utilize a written test plan for testing the system components and operation in accordance with NFPA 72 and this specification. The contractor shall be responsible for the performance of the test plan, demonstrating the function of the system and verifying the correct operation of all system components, circuits, and system programming. C. The system test plan shall include but not be limited to the following: 1. Visually inspect all wiring. 2. Verify the absence of unwanted voltages between circuit conductors and ground. The tests shall be accomplished at the preliminary test with results available at the final acceptance test. 3. System wiring shall be tested to demonstrate correct system response for the following conditions: a. Open, shorted and grounded signal line circuits. Packet Pg. 56

5 4.e.a b. Open, shorted and grounded notification appliance circuits. D. System indications shall be demonstrated as follows: 1. Correct message content for each alarm input at all system displays. 2. Correct annunciator light for each alarm input at each graphic display. 3. Correct history logging for all system activity. 4. Correct sensitivity for all smoke detection devices. The use of system generated sensitivity reports is acceptable in meeting this requirement. a. Correct signals sent to the Central Monitoring Station. 5. Notification appliances shall be demonstrated as follows: a. All alarm notification appliances actuate as programmed b. Audibility and visibility at required levels. Measure sound levels at 5 ft. above finished floor with the room doors closed. c. For 24VDC NACS, measure and record the voltage at the most remote appliance on each notification appliance circuit, while operating. 6. System control functions shall be demonstrated as follows: a. In accordance with the system operation matrix. 7. System off premises reporting functions shall be demonstrated as follows: a. Correct information received for each alarm and trouble event 8. Secondary power supply (battery) capacity capabilities shall be demonstrated as follows: a. System battery voltages and charging currents shall be measured and recorded at the fire alarm control panels. b. System primary power shall be disconnected for 24 hours. At the end of that period, an alarm condition shall be created and the system shall perform as specified for a period of 5 minutes. c. System primary power shall be restored for forty-eight (48) hours. d. System battery voltages and charging currents shall again be measured and recorded at the fire alarm control panels. 9. The central monitoring station and/or fire department shall be notified before final test in accordance with local requirements. 10. Operate every installed device to verify proper operation and correct annunciation at control panel. 11. Open signaling line circuits and notification appliance circuits in at least 2 locations to verify presence of supervision. Test Reports Per the "Documentation" Section of the "Fundamentals of Fire Alarm Systems" Chapter in NFPA72 and the "Inspection and Testing Form" in the "Records" Section of the "Inspection, Testing and Maintenance" Chapter in shall be prepared by the Contractor along with Technician's name, certificate number and date. Inspection Frequency Packet Pg. 57

6 4.e.a The inspection of the smoke alarm system will be conducted on a semi-annual basis. The bid is requested to include hourly rate for repair labor in the event that issues are discovered. Site Visit A site visit will be conducted on at 10:00 o clock. Interested parties can contact Sheriff s Office, Capt. Dave Boehm at Packet Pg. 58

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire alarm and signaling systems at Sam Houston State University provide the highest level of life safety possible. This

More information

1.3 REFERENCE STANDARDS

1.3 REFERENCE STANDARDS SECTION 28 4600 FIRE DETECTION AND ALARM PART 1 -GENERAL 1.1 SECTION INCLUDES A. Fire alarm system design and installation, including all components, wiring, and conduit. B. Circuits from protected premises

More information

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING.

SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING. SUWANNEE RIVER WATER MANAGEMENT DISTRICT REQUEST FOR BID NO. 15/16-003AO FIRE ALARM SYSTEM INSTALLATION AND MONITORING Table of Contents Section Title Page 1 Introduction 2 2 Proposed Schedule 2 3 Instructions

More information

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax)

SANTA CLARA COUNTY Winchester Blvd., Los Gatos, CA (408) (408) (fax) FIRE DEPARTMENT SANTA CLARA COUNTY 14700 Winchester Blvd., Los Gatos, CA. 95032-1818 (408) 378-4010 (408) 378-9342 (fax) www.sccfd.org STANDARD DETAILS & SPECIFICATIONS Spec No C-4 Rev. Date 03/10/10 SUBJECT:

More information

Florida Building Code 2010

Florida Building Code 2010 Introduction Florida Building Code 2010 Chapter 9 Fire Protection Systems This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors are familiar with

More information

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course Florida Building Code 2010 Chapter 9 Fire Protection Systems Advanced Course 1 Introduction This course will cover specific sections of Chapter 9 that relate to fire alarm systems. While many contractors

More information

Functional Performance Test

Functional Performance Test Fire Alarm Control Panel & Fire Alarm Annunciator Panel Notify all building occupants that testing will be conducted. Fire alarm contractor shall have personnel with 2-way radios at the fire alarm control

More information

Bold items are particular to the City of Euless

Bold items are particular to the City of Euless EULESS FIRE DEPARTMENT FIRE MARSHAL S OFFICE INFORMATION LINE: Revised 8/2004 Fire Chief Lee Koontz Fire Marshal Paul Smith EFD-FMO 3-1 2003 International Fire & Building Code as Amended NFPA Standards

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline Moreno Valley Fire Department Guideline Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 8, 2017 Alarm & Signaling Systems PURPOSE Fire alarm and signaling systems are designed to

More information

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems

Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Automatic Fire Alarm Association Webinar On Inspection, Testing, And Maintenance Of Fire Alarm Systems Your Presenter: Merton Bunker, PE Inspections and tests are intended to reduce or limit: Loss of life

More information

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1

CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM. Bid # Addendum #1 CITY OF PORTSMOUTH Department of Public Works MUNICIPAL COMPLEX FIRE ALARM Bid #56-09 Addendum #1 This Addendum forms part of the original document marked Bid #56-09 MUNICIPAL COMPLEX FIRE ALARM. Device

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016 Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting Prepared Especially for : OSFM TEC 2016 Acceptance Testing 11-2008 Agenda Before you begin Completing the

More information

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2

More information

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

Rancho Cucamonga Fire Protection District Prevention Bureau Standard Rancho Cucamonga Fire Protection District Prevention Bureau Standard Title: Fire Alarm and Monitoring Systems Standard # 9-3 Effective: May 2002 Number of Pages: 7 Updated: December 2016 for consistency

More information

Full Service Central Station Fire Alarm Listing Evaluation

Full Service Central Station Fire Alarm Listing Evaluation Full Service Central Station Fire Alarm Listing Evaluation Listing Evaluation A UL Listing project includes: 1. Evaluating the central station facility for compliance with UL 827, Central-Station Alarm

More information

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,

More information

2019 COURSE CATALOG (rev )

2019 COURSE CATALOG (rev ) 2019 COURSE CATALOG (rev. 02.07.19) www.afaa.org CEUs Available for NICET, Engineers and Other! 3246 Noe-Bixby Road, Suite 101, Columbus, OH 43232 844-438-2322 Page 1 Page No. Seminar Name 3. A User s

More information

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications:

PART 1 GENERAL Quality Assurance A. Fire Alarm Contractor Qualifications: PART 1 GENERAL 1.01 Quality Assurance A. Fire Alarm Contractor Qualifications: 1 The Fire Alarm contractor shall be an Edwards Systems Technology (EST) designated representative and authorized to sell,

More information

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE

COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE COMMERCIAL (IBC) FIRE ALARM SUBMITTAL GUIDE SUPERVISION OF AUTOMATIC FIRE SPRINKLER SYSTEMS SUPERVISION OF ALTERNATIVE AUTOMATIC FIRE-EXTINGUISHING SYSTEMS FIRE ALARM AND DETECTION SYSTEMS The Fire Alarm

More information

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3 Technical Service Note Detection Systems, Inc. Fairport, New York 14450-9199 Technical Service (800) 374-7454 Sales: (800) 289-0096 and (585) 223-4060 Fax: (585) 223-9180 Concerns: Affects: Dated: June

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work

More information

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE PAGE 280800-1 SECTION 280800 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification

More information

Annual Fire Systems and Backflow Preventers Testing

Annual Fire Systems and Backflow Preventers Testing Facilities Management Request for Qualifications Annual Fire Systems and Backflow Preventers Testing At Various Facilities Proposals Due: 2:30 PM, Tuesday May 15, 2018 Deliver to: Attn: Sara Winger, Purchasing

More information

Austin Independent School District Police Department Policy and Procedure Manual

Austin Independent School District Police Department Policy and Procedure Manual Policy 8.07 Austin Independent School District Police Department Policy and Procedure Manual Life Safety Systems I. POLICY The proper operations of the AISD Life Safety Systems (LSS) are essential for

More information

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General

More information

El Reno Fire Department Fire Alarm Plan Review Worksheet

El Reno Fire Department Fire Alarm Plan Review Worksheet El Reno Fire Department Fire Alarm Plan Review Worksheet This Fire Alarm Plan Review Checklist is provided as a guide to assist with your Fire Alarm Plan Review Submittal requirements. Please contact us

More information

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS SECTION 21 22 00 CLEAN AGENT FIRE SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between // --- // if not applicable to the project. Also delete any other item or paragraph

More information

COUNTY OF ROCKLAND Department of General Services Purchasing Division

COUNTY OF ROCKLAND Department of General Services Purchasing Division Department of General Services Purchasing Division Title: Contract Period: Fire Extinguishers and Suppression Systems-Inspection, Testing, Maintenance, Repair and Recharging 3/1/18 through 2/28/19 with

More information

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE PAGE 283100-1 SECTION 283100 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

FIRE & LIFE SAFTEY STANDARD

FIRE & LIFE SAFTEY STANDARD Title: Effective Date: 01/01/14 Revised Date: 1/1/14 Code References: Title 16, Chapter 16.16 of the Roseville Municipal Code, NFPA 72 Note: This standard is a summary of Fire Department clarifications

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Fire Prevention Coffee Break Training. February 2017

Fire Prevention Coffee Break Training. February 2017 Fire Prevention Coffee Break Training February 2017 Agenda FDC s - Lund Standpipes - Phelan Fire Alarm Testing Phelan/Dooley Questions and Answers Open Forum Standpipe requirement Standpipes are required

More information

Fire Alarm System Fundamentals

Fire Alarm System Fundamentals Fire Alarm System Fundamentals Mircom is the largest and oldest privately owned fire alarm and life safety manufacturer in North America and 5th largest overall with 50 years of industry experience. Mircom

More information

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with a Cheetah Xi 50 addressable detection and control system.

More information

The 2013 National Fire Alarm and Signaling Code

The 2013 National Fire Alarm and Signaling Code ARE YOU A MEMBER OF AFAA? WHY SHOULD YOU BE A MEMBER BECAUSE YOUR BUSINESS IS IMPORTANT James Mongeau The 2013 National Fire Alarm and Signaling Code 1 NFPA 72 Organization Be*er organiza2on Easier to

More information

Brighton Area Fire Authority

Brighton Area Fire Authority 615 W. Grand River Ave. Brighton, MI 48116 o: 810-229-6640 f: 810-229-1619 January 14, 2019 Fire Alarm Contractors RE: Fire Alarm Credential & Submittal Requirements To Whom It May Concern: The following

More information

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE

MECKLENBURG COUNTY FIRE MARSHAL S OFFICE Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and

More information

SECTION FIRE ALARM SYSTEMS

SECTION FIRE ALARM SYSTEMS SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

SECTION FIRE DETECTION AND ALARM

SECTION FIRE DETECTION AND ALARM PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Section 15300 for requirements regarding fire protection systems. 1.2 SCOPE OF SECTION: This section contains the requirements for equipment and installation

More information

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.

THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS

Fort Rouge Leisure Centre Section HVAC Upgrades Phase 2 Page 1 of 5 Bid Opportunity No March 2013 FIRE ALARM SYSTEMS HVAC Upgrades Phase 2 Page 1 of 5 Part 1 General 1.1 SUMMARY.1 Section Includes:.1 Materials and installation for fire alarm systems upgrades..2 Audible signal devices..3 End-of-line devices..4 Sustainable

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: February 5, 2018 STANDARD INFORMATION Standard Number: NFPA 72 Standard Name: National Fire Alarm and Signaling Code Standard Edition and Issue Date: 2016 Edition

More information

Fire Alarm, Water Flow Alarm & Signaling Systems

Fire Alarm, Water Flow Alarm & Signaling Systems Orange County Fire Authority Community Risk Reduction 1 Fire Authority Road, Building A, Irvine, CA 92602 www.ocfa.org 714-573-6100 Fire Alarm, Water Flow Alarm & Signaling Systems Guideline D-03 Serving

More information

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 28 3111 DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Fire-alarm control unit. 2. Manual fire-alarm boxes. 3. System smoke detectors. 4. Heat detectors.

More information

Fire Alarm System Inspection and Testing Report

Fire Alarm System Inspection and Testing Report Fire Alarm System and ing Report Date of : Time of : 1. PROPERTY INFORMATION: Name of Property: Address: of property: Occupancy Type: Name of property representative: Address: Phone: Fax: E-mail: Local

More information

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017

Addendum # 2 Wicomico County Circuit Court Second Floor Renovations Date of Addendum: 2/6/2017 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 2 Wicomico County Circuit Court Second Floor

More information

You are required to READ ALL PAGES. of this application

You are required to READ ALL PAGES. of this application Fire/Smoke/Heat/CO Application Checklist You are required to READ ALL PAGES of this application NEW ROCHELLE FIRE DEPARTMENT 90 Beaufort Pl, New Rochelle, NY 10801 - (914) 654-2213 APPLICATION FOR FIRE/SMOKE/HEAT/CO

More information

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS

PROJ. NO SECTION PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS SECTION 26 92 50 PAGING, SPEAKERS AND HARD-WIRED CLOCK SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement

Second Revision No. 104-NFPA [ Section No ] Submitter Information Verification. Committee Statement of 1 9/22/2014 1:38 PM Second Revision No. 104-NFPA 72-2014 [ Section No. 3.3.3 ] 3.3.3 Accessible, Readily (Readily Accessible). Capable of being reached quickly for operation, renewal, or inspections

More information

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017

STUDY AND TEST MATERIAL FOR THE. FA2 and FA4 ASSESSMENTS. (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 STUDY AND TEST MATERIAL FOR THE FA2 and FA4 ASSESSMENTS (Fire Alarm On-Site and Business Cert. Holder) June 14, 2017 This document contains sample questions to help participants study for the FA2 and FA4

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 13852- PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this

More information

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10 Belleville, Ontario Page 1 of 10 1 GENERAL 1.1 GENERAL REQUIREMENTS.1 The General Conditions of CCDC2-2008, and the General requirements of Division 1, form part of this Section and must read in conjunction

More information

Changes in NFPA

Changes in NFPA Changes in NFPA 72-2002 2002 Oregon Fire Code Committee November 25, 2003 Michael B. Baker, SET Automatic Fire Alarm Association MikeBaker@afaa.org 2003 Michael B. Baker 1 Table of Contents 1. Administration

More information

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator

IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator IOWA STATE FIRE MARSHAL DIVISION Attn: Licensing Administrator 215 E Seventh Street; Des Moines, IA 50319 Email: sfmlicense@dps.state.ia.us APPLICATION CHECKLISTS (EFFECTIVE IMMEDIATELY) 1. DO NOT mail

More information

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance It is ordained by the Town Council of the Town of New Shoreham

More information

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 283111 A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: NFPA Technical Committee on Notification

More information

FIRE ALARM PRE-INSPECTION CHECKLIST 1. REFER TO CHAPTER 10 OF CURRENT STATE ADOPTED NFPA 72, FOR INSPECTION, TESTING AND MAINTENANCE PROCEDURES.

FIRE ALARM PRE-INSPECTION CHECKLIST 1. REFER TO CHAPTER 10 OF CURRENT STATE ADOPTED NFPA 72, FOR INSPECTION, TESTING AND MAINTENANCE PROCEDURES. FIRE ALARM PRE-INSPECTION CHECKLIST Prepared by: Representing: Date: 1. REFER TO CHAPTER 10 OF CURRENT STATE ADOPTED NFPA 72, FOR INSPECTION, TESTING AND MAINTENANCE PROCEDURES. 2. PROVIDE DRAWINGS IN

More information

Fire Alarm and Life Safety System Inspection Certificate

Fire Alarm and Life Safety System Inspection Certificate Fire Alarm and Life Safety System Inspection Certificate For Sample FireScan Healthcare 123 Main Street Anytown, State 55555 Tested to NFPA 72 Standards, 2007 Edition This Inspection was performed in accordance

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION SYSTEMS GENERAL 1.1 SUMMARY General 1. Work under this contract shall meet the requirements of Division 01, General Requirements, Conditions of Contract,

More information

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III SECTION 28 3111 - DIGITAL ADDRESSABLE FIRE ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS SPECIFICATION FOR A TOTAL FLOOD I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125

More information

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system. PART 1 GENERAL 1.01 Scope of Standard A. This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible.. This

More information

September 30, Dear Fire Suppression System Contractor/Designer:

September 30, Dear Fire Suppression System Contractor/Designer: CITY OF BOZEMAN FIRE DEPARTMENT P.O. Box 1230 Bozeman, Montana 59771-1230 Phone (406) 582-2350 CITY OF BOZEMAN BUILDING DEPARTMENT 20 E Olive St, STE 208 Bozeman, Montana 59715-4790 Phone (406) 582-2375

More information

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability

Fire Alarm Inspection, Testing, Maintenance. Assuring the System s Operational Reliability Fire Alarm Inspection, Testing, Maintenance Assuring the System s Operational Reliability What does AFAA-NE do? Education We supply the tools our members require to perform within the guidelines of our

More information

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood ECARO-25 TM clean agent fire suppression system utilizing HFC-125 as the fire extinguishing agent

More information

NOTICE TO CONTRACTORS

NOTICE TO CONTRACTORS NOTICE TO CONTRACTORS Notice is hereby given that sealed bids will be received by the City Council of the City of Reedley for furnishing all labor, materials, services, and equipment and performing all

More information

Date Issued: December 14, 2017 Revision: 2.1

Date Issued: December 14, 2017 Revision: 2.1 2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,

More information

Campus Wide Fire Alarm Repairs

Campus Wide Fire Alarm Repairs BID # 15-24 Campus Wide Fire Alarm Repairs SECTION "C" TECHNICAL SPECIFICATIONS OWNER Board of Trustees Middlesex County College 2600 Woodbridge Avenue P.O. Box 3050 Edison, New Jersey 08818-3050 PREPARED

More information

DONALD H. BERG, ARCHITECT

DONALD H. BERG, ARCHITECT DONALD H. BERG, ARCHITECT DVA PROJECT 632-CSI-402 PET/CT ROOM #A0-10 RENOVATION BASEMENT LEVEL, BUILDING 200 ARCHITECT S PROJECT No. 0917-02 ADDENDUM NO. 1 JUNE 25, 2018 Page 1 of 1 ARCHITECTURAL 1. Specifications:

More information

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA

AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES. Report on Comments Meeting, October 13-14, Richmond Marriott, Richmond, VA National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org AGENDA NFPA TECHNICAL COMMITTEE ON NOTIFICATION APPLIANCES Report on Comments

More information

ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions

ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico General Bid Conditions ROSWELL INDEPENDENT SCHOOL DISTRICT P.O. Box 1437 Roswell, New Mexico 88202-1437 General Bid Conditions BID # 19-06 Fire Sprinkler Systems Inspections, Testing and Maintenance SEALED BIDS will be opened

More information

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL SECTION 1 GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Total Flood Clean Agent Fire Suppression System utilizing FK-5-1-12 as the fire extinguishing agent and with a

More information

GE Security EST Fire & Life Safety. Sensible. EST2 Networkable Fire Alarm Control Panels with Voice Audio

GE Security EST Fire & Life Safety. Sensible. EST2 Networkable Fire Alarm Control Panels with Voice Audio GE Security EST Fire & Life Safety Sensible EST2 Networkable Fire Alarm Control Panels with Voice Audio We re not very good Before the remarkable EST2 life safety system, only large facilities could justify

More information

Control Relay Modules

Control Relay Modules TM INTERNATIONAL ANALOG ADDRESSABLE INPUT/OUTPUT DEVICES Control Relay Modules Model SIGA-CR, SIGA-MCR, SIGA-CRR, Features! Provides one no/nc contact (SIGA-CR/MCR) Form C dry relay contact can be used

More information

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001, INTEGRATED SYSTEMS TEST OF FIRE PROTECTION AND LIFE SAFETY

More information

NFPA Changes

NFPA Changes Chapter 21, Emergency Control Functions and Interfaces Summary. Chapter 21 is new. These requirements were formerly found in Chapter 6, Protected Premises Fire Alarm Systems. The term fire safety function

More information

Linear Heat Detection Engineering Specifications

Linear Heat Detection Engineering Specifications Linear Heat Detection Engineering Specifications July, 2007 SAFE Fire Detection Inc. 5915 Stockbridge Dr. Monroe, NC 28110 Phone: (704) 821-7920 Fax: (704) 821-4327 Website: www.safefiredetection.com E-mail:

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: FROM: Technical Committee on Notification Appliances

More information

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number: DATE OF SUBMISSION TO: Department of Licenses and Inspections Commercial and Industrial Fire Inspection Unit 990 Spring Garden Street, 3 rd Floor, Philadelphia, PA 19123 AP# CITY OF PHILADELPHIA FIRE ALARM

More information

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS

CAN/ULC-S INTEGRATED SYSTEMS TESTING OF FIRE PROTECTION AND LIFE SAFETY SYSTEMS 2013 Randal Brown & Associates Engineering Ltd. 1 RANDAL BROWN & ASSOCIATES ENGINEERING LTD. CONSULTING ENGINEERS LIFE SAFETY & FIRE PROTECTION 105 6 LANSING SQUARE TORONTO, ONTARIO CAN/ULC-S1001-11 INTEGRATED

More information

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS

MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS FIRE CODE BULLETIN December 2004 97 FCB 018 (R1) Page 1 of 5 BACKGROUND: MAINTENANCE OF FIRE PROTECTION DEVICES WITHIN RESIDENTIAL SUITES OF MULTI-FAMILY BUILDINGS Fire protection service companies are

More information

Chapter 4: Fire Protection Systems

Chapter 4: Fire Protection Systems Chapter 4: Fire Protection Systems Automatic Extinguishing Systems (Fire Sprinklers) One of the most important aspects of a storage warehouse inspection is ensuring that the automatic extinguishing system

More information

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics. A28.1 Standard of Practice - Fire Alarm Systems NOTE: Significant revisions or additions to the previous standards are highlighted in italics. OBJECTIVE OF STANDARD To provide compliant smart addressable

More information

OKLAHOMA STATE UNIVERSITY

OKLAHOMA STATE UNIVERSITY ENVIRONMENTAL HEALTH & SAFETY ADDRESSABLE FIRE ALARM SYSTEM STANDARD Revised 6/15 Revised: 6/15 Contact(s) Implementation Date Comments Gerald Petre, EHS June 2016 Review and Update Page 1 1.1 GENERAL

More information

PART IV DETAILED SPECIFICATION

PART IV DETAILED SPECIFICATION PART IV DETAILED SPECIFICATION PART IV DETAILED SPECIFICATIONS SECTION ONE: GENERAL 1.1 Scope A. This specification document provides the requirements for the installation, programming and configuration

More information

Division 28 - Electronic Safety and Security

Division 28 - Electronic Safety and Security Division 28 - Electronic Safety and Security 28 31 11 Fire Alarm Systems Fire alarm systems shall be installed in buildings when required by this section. 1. Purpose: The primary purpose of a fire alarm

More information

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning

CAN/ULC S Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning CAN/ULC S1001-11 Integrated Systems Testing of Fire Protection and Life Safety Systems and Fire Protection Commissioning Presentation To: Canadian Fire Alarm Association (CFAA) National Capital Region

More information

Sophisticated. io-series Intelligent fire alarm solutions for small buildings. An EDWARDS brand.

Sophisticated. io-series Intelligent fire alarm solutions for small buildings. An EDWARDS brand. Sophisticated. io-series Intelligent fire alarm solutions for small buildings See what s possible now. An EDWARDS brand. Big system performance for small building applications 99Supports Signature Series

More information

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning Page 1 of 6 PART 1 GENERAL 1.1 RELATED SECTIONS.1 Related Sections..1 The contractor is to ensure that all related work is co ordinated among all specification sections, as well as between Division 11,

More information

SECTION : FIRE ALARM & DETECTION SYSTEMS

SECTION : FIRE ALARM & DETECTION SYSTEMS SECTION 28 31 10: FIRE ALARM & DETECTION SYSTEMS 1. GENERAL A. This section applies to fire detection/alarm system and carbon monoxide system components and equipment installed during new construction

More information

The following information shall become and form part of the contract documents.

The following information shall become and form part of the contract documents. October 4, 206 To: Attention: Re: All Bidders All Bidders JCBE Gymnasium HVAC Upgrades BC#: 206433 Edmonds Project No.: BHM6090 All bidders, The following information shall become and form part of the

More information

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD PART 1 - GENERAL PURPOSE This Standard is intended to assure that fire detection/alarm systems at The University of Texas at Austin provide the highest level of fire safety possible. SCOPE This standard

More information