Instruction Manual. Satellite Switched, Power Monitoring Unit. RS2 Series
|
|
- Eustacia Hillary Brooks
- 5 years ago
- Views:
Transcription
1 Instruction Manual Satellite Switched, Power Monitoring Unit RS2 Series Geist Yolande Ave., Lincoln, NE F:
2 Contents Contents... 2 Specifications... 3 Overview 3 Environmental 3 Electrical 3 Receptacle Ratings 3 EMC Verification 3 Installation... 5 Guidelines 5 Mounting 5 Web Interface... 7 Overview 7 Sensors Page 7 Logging Page 8 Display Page 9 Alarms Page 10 Sensors Overview 12 Internal Sensors 12 Data Logging and Display 12 Service and Maintenance 12 More Technical Support 12 Table of Figures Revision History GM Revision Date: 12/22/2014
3 Specifications Overview The RS2 Series expands the power of your Geist R-Series RSMINI, RSE, RSO, RCX, RSM, RCM, or RCU units (firmware version 3.00 and higher ONLY) with the addition of 2 outlets with remote switching and monitoring. RS2 Series units use the host unit s built in web server to display power monitoring data and give users control for installations needing switching of either one or two outlets. No software other than a web browser is required for operation and several data formats are available. RS2 Series units monitor Voltage, Current, Real and Apparent Power, and also provide a calculated Power Factor. The measurements are per unit, so both outlets are measured as one circuit. A single, Ethernet equipped host can connect multiple units within a cabinet or row by tethering units. Optional external sensors can monitor other environment factors. Note: On boot-up the RS2 will only turn on Outlet 1. After the RS2 has completed boot-up (about 5 seconds) Outlet 2 will turn on. This is to prevent a large inrush current if the RS2 is supplying power to certain devices. Environmental Temperature Operating: 10 C (50 F) min 45 C (104 F) max Storage: -25 C (-13 F) min 65 C (149 F) max Humidity Operating: 5% min 95% max (non-condensing) Storage: 5% min 95% max (non-condensing) Elevation Electrical Operating: 0 m (0 ft) min 2000 m (6561 ft) max Storage: 0 m (0 ft) min m (50000 ft) max See nameplate for unit ratings. Receptacle Ratings NEMA 5-15R 125 Volts, 15 Amp IEC-320 C13 125/250 Volt, 15 Amp (North America) or 10 Amp (Global) 1 IEC-320 C19 125/250 Volt, 20 Amp (North America) or 16 Amp (Global) EMC Verification This Class A device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. 1 Given ratings are per receptacle bank GM Revision Date: 12/22/2014
4 This Class A digital apparatus complies with Canadian ICES-003. Cet appareil numérique de la classe A est conforme à la norme NMB-003 du Canada. Warning: Changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user s authority to operate this equipment. GM Revision Date: 12/22/2014
5 Installation Guidelines Each host unit can support up to 16 attached sensors including RS2 units. Each host can support up to 600 feet of aggregate sensor cable length connecting the RS2 units, and other sensors, to the host. RS2 units are ONLY supported by Geist R-Series units with firmware version 3.00 or higher. If the RS2 is installed in a cabinet the ambient temperature of the rack should be no greater than 45C. Install the RS2 such that the amount of airflow required for safe operation of equipment is not compromised. Mount the RS2 so that a hazardous condition is not achieved due to uneven mechanical loading. Follow nameplate ratings when connecting equipment to the branch circuit. Take into consideration the effect that overloading of the circuits might have on over-current protection and supply wiring. The RS2 relies on the building installation for protection from over-current conditions. A Listed circuit breaker is required within the building installation. The circuit breaker should be sized according to the RS2 s nameplate ratings and local/national electrical codes. Reliable earth grounding of rack-mount equipment should be maintained. Particular attention should be given to supply connections other than direct connections to the branch circuit. The RS2 must be connected to an earthed socket-outlet. For pluggable equipment, install the RS2 so that the input plug or appliance coupler may be disconnected for service. Sequential power-up of devices powered by the RS2 is recommended to avoid high inrush current. Caution: Disconnect all power cords before servicing. Mounting The RS2 is made to be mounted to any flat surface using four (4) screws, as shown in Figure 2. The mounting holes are 1/4 diameter, so screws should be selected to fit and strong enough to securely hold the RS2 in place. The mounting hole dimensions are shown in Figure 1. Figure 1: RS2 Mounting-Hole Dimensions GM Revision Date: 12/22/2014
6 Figure 2: Mounting the RS2 GM Revision Date: 12/22/2014
7 Web Interface Overview The RS2 must be attached to a host unit via RJ-12 patch cable in order to view the RS2 on a network. The host unit is accessible via a standard, unencrypted HTTP connection as well as an encrypted HTTPS (SSL) connection. The following web pages change or contain added content after the RS2 Series unit is connected: Sensors Page The front page, Sensors, gives both instantaneous and historical views of the host unit s data. Real time readings are provided for all power strip and sensor data next to historical graphs. Each attached RS2 Series units will show a remote sensor section on the host unit s Sensors page. All power monitoring information will be shown here. Figure 3: Sensors Page - Remote Sensor GM Revision Date: 12/22/2014
8 Logging Page The host unit s Logging page allows the user to access the historical data of the RS2 by selecting the desired readings and time range to be graphed. This is done the same way the sensor readings are graphed on the host unit. A new section will be shown for each RS2 added to the host unit. Figure 4: Logging Page GM Revision Date: 12/22/2014
9 Display Page The host unit s Display page allows the user to assign friendly names to the RS2 unit. This friendly name is shown as the name of the RS2 on the host unit s other pages. This feature is helpful to distinguish one RS2 from another RS2 or from another sensor when attached to the same host device. Figure 5: Display Page GM Revision Date: 12/22/2014
10 Alarms Page The host unit s Alarms page allows the user to establish alarm conditions for each sensor reading. Alarm conditions can be established with either high or low trip thresholds. To set an alarm, select the alarm type from the dropdown menu. Then select whether the alarm will trip above or below the threshold. Finally, set the threshold limit in the text box. If a notification is required, select the amount of time the alarm must be tripped before sending the notification and how often to repeat the notification. Then check the boxes for the desired notification types. Alarm notification options differ with each host but include a buzzer, and SNMP Trap. The RS2 adds the option of switching each outlet off or on when an alarm is tripped. Select the outlet that is desired to be switched and then go to the Control page to select the action to be taken. When an alarm is triggered the outlet will perform the selected action. Note: To enable alarm switching the user must read and accept the disclaimer located on the Config page s Admin tab. Figure 6: Alarms Page GM Revision Date: 12/22/2014
11 Control Page The host unit s Control pages will become active after the RS2 is attached, if they are not already. The Control pages include an Actions tab and a Settings tab. The Settings tab gives the user the ability reset the kilowatt hours or to change the friendly names of the outlets on the RS2. The Actions tab contains the controls for the switching capabilities of the RS2. There are six options for switching the outlet: Manual off Turns off outlet. Manual on Turns on outlet. Alarm trips off Sets outlet to be turned off when alarm trips. Outlet will be on whenever the alarm is untripped. Alarm trips off, latching Sets outlet to be turned off when alarm trips. The outlet stays off until the Release to ON control button is pressed, even if the alarm is cleared. Alarm trips on Sets outlet to be turned on when alarm trips. Outlet will be off whenever the alarm is untripped. Alarm trips on, latching Sets outlet to be turned on when alarm trips. The outlet stays on until the Release to OFF control button is pressed, even if the alarm is cleared. Figure 7: Control Actions Page Figure 8: Control Settings Page GM Revision Date: 12/22/2014
12 Sensors Overview The RS2 updates its measurements every 5 seconds. Like all external sensors, the RS2 s measurements are read by the host every 10 to 30 seconds, depending on the number of other sensors connected. Sensor data collected by the RS2 gives useful trend analysis data, and allows users to view changes and draw useful conclusions about what is happening over time in the monitored environment. Internal Sensors The RS2 contains the following onboard sensors: Volts: Measures instantaneous RMS voltage. Volts(Peak): Measures the highest reported voltage since the last time the data was updated, typically every 5 seconds. Amps: Measures instantaneous RMS current. Amps(Peak): Measures the highest reported current since the last time the data on the screen was updated, typically every 5 seconds. Real Power: Average of instantaneous voltage and current over the last 1.5 seconds. Apparent Power: The product of instantaneous RMS Voltage and RMS Current. This is the value used by circuit breakers. Power Factor: The ratio of Real Power to Apparent Power. Data Logging and Display All data collected by the RS2 can be graphed by the host unit. The host unit s Logging page allows the user to select graphed content to be logged. Selected sensor values are logged by the host unit at a rate of one point per minute and are shown on the Sensors page. Host units with LCD displays can optionally show sensor measurements there as well. The number of selected sensors determines the maximum data logging time span. This period is calculated and displayed on the Logging page. The oldest data will be deleted when the onboard memory fills up in order to make room for new data. All RS2 sensor values are shown on the RS2 s onboard display. Service and Maintenance No service or maintenance is required. Do not attempt to open the RS2 or you may void the warranty. No serviceable parts inside. It is recommended that power be removed from the unit before installing or removing any equipment. More Technical Support (800) support@geistglobal.com Or contact your distributor. GM Revision Date: 12/22/2014
13 Table of Figures Figure 1: RS2 Mounting-Hole Dimensions... 5 Figure 2: Mounting the RS Figure 3: Sensors Page - Remote Sensor... 7 Figure 4: Logging Page... 8 Figure 5: Display Page... 9 Figure 6: Alarms Page Figure 7: Control Actions Page Figure 8: Control Settings Page GM Revision Date: 12/22/2014
14 Revision History Revision Date Notes Approved By 1.0 3/22/2011 Initial Version CDG, AK, BP 1.1 8/16/2011 Alarms outlet control features added CDG 1.2 6/5/2012 Logo and Website Update CDG GM Revision Date: 12/22/2014
Instruction Manual Environmental Monitoring Unit with Output Relay
Instruction Manual Environmental Monitoring Unit with Output Relay Watchdog 100 Series Firmware Version 3 Geist. 1821 Yolande Ave., Lincoln, NE 68521 800.432.3219 402.474.3400 F: 402.474.4369 www.geistglobal.com
More informationHP Power Distribution Unit with Power Monitoring (Models S124 and S132) User Guide
HP Power Distribution Unit with Power Monitoring (Models S124 and S132) User Guide March 2006 (First Edition) Part Number 413611-001 Copyright 2006 Hewlett-Packard Development Company, L.P. The information
More informationIFS Fiber Module Installation & Operation Instructions
DECT000 DECT00 DECT00 DECR000 DECR00 DECR00 IFS Fiber Module Installation & Operation Instructions P/N 00 REV B ISS 0AUG DECT00 CHANNEL LNK ACT TX RX 00FX CONTACT CLOSED WHEN ON CONTACT TO ETHERNET TRANSMITTER
More informationIon Gateway Cellular Gateway and Wireless Sensors
Page 1 of 9 Account & Network Setup If this is your first time using the Ion Gateway online system site you will need to create a new account. If you have already created an account you can skip to the
More informationTLM-1 TOWER LIGHT MONITOR V3.0. INSTALLATION and OPERATING INSTRUCTIONS
TLM-1 TOWER LIGHT MONITOR V3.0 INSTALLATION and OPERATING INSTRUCTIONS SYSTEM OVERVIEW The TLM-1 Tower Light Monitor is a microprocessor-based system designed to monitor the status of incandescent tower
More informationKONICA MINOLTA GP-502 OPERATION MANUAL
KONICA MINOLTA GP-502 OPERATION MANUAL Rev 1.0 February 2012 Table of Contents 1. Safety 2. Overview 2.1 Features & Benefits of GP-502 2.2 Ellipse Binding Elements 2.3 User Interface & Feature Locations
More informationGeneral. General. Input. (1) 16 AMP Circuit Breaker. Communication. (1) RJ45 for Ethernet. Current Meter. Operation. Nominal Input Voltage 230V
Managed PDU: is built -in network interface that allows an administrator to access the PDU from a remote interface to turn on or off outlets, the more important is POM can monitor every outlet power consumption
More informationPWM. Solar Charge controller with Ethernet. Solar Smart PWM 20Amp. Hardware Description : Release : 19 June 2014
Solar Charge controller with Ethernet Release : 19 June 2014 Hardware Version : Version 1 Firmware version 1 PC Application Software : Version 1.0.0.0 Hardware Description : The Solar Smart regulator was
More informationRACK MONITORING SYSTEM - RAMOS Ultra
CONTEG DATA SHEET version: 9-05-0 COMPLEMENTARY SYSTEMS RACK MONITORING SYSTEM marketing@dafnia.com www.dafnia.com ABU DHABI UAE +97 55575 DUBAI JAFZA +97 4 5995 +97 4 8840 MUSCAT DOHA OMAN +968 4 75005
More informationIndigoVision Alarm Panel. User Guide
IndigoVision Alarm Panel User Guide THIS MANUAL WAS CREATED ON 2/21/2017. DOCUMENT ID: IU-AP-MAN002-4 Legal considerations LAWS THAT CAN VARY FROM COUNTRY TO COUNTRY MAY PROHIBIT CAMERA SURVEILLANCE. PLEASE
More informationInstallation Instructions
Installation Instructions S E C U R I T Y S Y S T E M Please refer to the System Installation Manual for information on limitations regarding product use and function and information on the limitations
More informationSEE DISCLAIMER ON REVERSE
BOLTEK CORPORATION Lightning Detection GSM-1 Text Message Notification for EFM-100C Electric Field Monitor User Guide SEE DISCLAIMER ON REVERSE BOLTEK LIGHTNING DETECTION GSM-1 Text Message Alert Dialer
More informationBatt-Safe Battery String Monitoring System
Batt-Safe Battery String Monitoring System Technical White Paper October 2010 Introduction Battery monitoring systems are categorized as either cell monitors or string monitors. Battery cell monitors provide
More informationECO PDU PE7214/PE7216/PE7324/PE7328
ECO PDU PE7214/PE7216/PE7324/PE7328 As part of its NRGence line, ATEN has developed a new generation of green energy power distribution units (eco PDUs) to effectively increase the efficiency of data center
More informationS541.RF 4G Product Guide
S541.RF 4G Product Guide Table of Contents Table of Contents... Page 1 Overview and General Concept... Page 2 Application... Page 2 Features... Page 3 Specifications... Page 3 Network Topology... Page
More informationSKU# LC54225 Please retain these instructions for future reference. Adult assembly required.
Thank you for purchasing a Chuggington Brewster s Big City Adventure Playset! 1 CONTEN T TO SURFACE - 1 RIGHT CURVE ASCENDING - 1 FLAGS - 2 BT BUMPER - 1 SINGLE RISER - 18 CARGO DESTINATION - 1 T SWITCH
More informationIFS Fiber Module Installation & Operation Instructions
VT9930WDM VT9930WDM-R3 VR9930WDM VR9930WDM-R3 IFS Fiber Module Installation & Operation Instructions P/N 1062791 REV B ISS 01JUL11 VT/VR9930WDM RS - 232 DATA 1 2 3 4 5 6 7 8 20 Data Input Data Output Ground
More informationClock Radio AJ3112/37 Register your product and get support at www.philips.com/welcome 1 2 1 @! 0 9 3 4 876 5 ^ % $ # IMPORTANT SAFETY INSTRUCTIONS Clean only with dry cloth. Where the MAINS plug or
More informationfield SENSE EC-FS2-001-A
field SENSE EC-FS2-001-A www.fieldsense.com introduction The FieldSENSE 2.0 is the next generation in Personal RF Monitors specifically designed for protecting personnel working near broadcast and telecommunications
More informationPowercom Ltd Powercom Building A, Ramat Hakovesh Israel Tel: +972 (9) Fax: +972 (9)
Powercom Ltd Powercom Building A, Ramat Hakovesh Israel 44930 Tel: +972 (9) 790 7900 Fax: +972 (9) 744 4738 info@powercom.co.il Industry Trends & Drivers Operational Efficiencies Changing Demand Regulation/
More informationVT1101M VT1102M IFS Fiber Module Installation & Operation Instructions
VT1101M VT1102M IFS Fiber Module Installation & Operation Instructions P/N 1062814 REV B ISS 01JUL11 Video source Coax cable VT1101M VIDEO TX ifs 3 +9-12VDC 2 GRD 1 Contact input Black with white stripe
More informationTruVision IR Turret Camera TVT-2202/TVT-4202 Installation Guide
TruVision IR Turret Camera TVT-2202/TVT-4202 Installation Guide P/N 1072921 REV A ISS 10FEB15 Contents Product overview 2 Camera description 3 Installation 4 Programming 6 Specifications 7 Setup menu
More informationPet Immune SAW PIR Motion Sensor
PET Immune SAW PIR Motion Sensors Installation Sheet Description This is the Installation Sheet for SAW PIR and PET Immune Motion Sensors. See Table 1. Table 1: Motion Sensors 60-807-95R 60-807-01-95R
More informationIFS Fiber Module Installation & Operation Instructions
VAT1200 VAT1200-R3 VAR1200 VAR1200-R3 IFS Fiber Module Installation & Operation Instructions P/N 1062830 REV B ISS 01JUL11 NOTE: For an unbalanced audio input connection tie pin 1 to pin 2 and utilize
More informationIFS Fiber Module Installation & Operation Instructions
VT6010 VT6010-R3 VR6010 VR6010-R3 IFS Fiber Module Installation & Operation Instructions P/N 1062796 REV B ISS 01JUL11 4 BNC Cables (Input from cameras) VT6010A 4 CHANNEL VIDEO TRANSMITTER 1-2 - VIDEO
More informationIFS Fiber Module Installation & Operation Instructions
DT00 DT00-R DT0 DT0-R IFS Fiber Module Installation & Operation Instructions DR00 DR00-R DR00 DR00-R P/N 0 REV B ISS 0AUG DT00 CONTACT WHEN ON CHANNEL CONTACT TRANSMITTER ifs International Fiber Systems
More informationKWX N4 PDU. Intelligent, Rack Mounted, Power Distribution Units. The most innovative PDU on the market KWX-N16A10C3-H4F MONITORED & SWITCHABLE PDU
PDUeX as standard where others don t!! The most innovative PDU on the market Monitor Each Sockets Current Control each outlets on/off Sequential power on/off User can define the sequence of order in which
More informationLORAIN CIP 4890/48120 DC Power System
DC Power for Business-Critical Continuity Key Features Compact flexibility provides rectifiers, distribution, and controller in one shelf Constant power delivers more current at lower voltages to meet
More informationQUICK START GUIDE. Lono, LLC 686 East 110 South, Suite 102 American Fork, UT 84003
QUICK START GUIDE Lono, LLC 686 East 110 South, Suite 102 American Fork, UT 84003 Welcome. This guide will help you install your Lono controller. For additional information, check out our installation
More informationDigijock Home Security
Digijock Home Security User Manual Congratulations on your purchase! The Digijock Home Security is a wireless alarm system that will protect your home or your small business from fire and burglary. Consisting
More information2 x screws. 2 x wall plugs
INSIDE THE BOX 2 x screws Main display 2 x wall plugs Wall mount RH RH Y1 Y1 RC O/B AUX RC Y2 O/B G AUX W1 Y2 G W1 C C W2 W2 Wire labels Adapter plate 4 x AA Batteries GETTING STARTED The ZEN thermostat
More informationIFS Fiber Module Installation & Operation Instructions
D1300 D1300-R3 D2300 D2300WDM D2300CP D2300SHR IFS Fiber Module Installation & Operation Instructions P/N 1062852 REV ISS 01AUG11 D1300 / D2300 / D2300SHR 2 - Wire RS485 Connection 4 3 2 1 No Connection
More informationTP WEM01 A Carrierr Côr Thermostat AC/HP Wi-Fir Thermostat Performance Series. Installation Guide
TP WEM01 A Carrierr Côr Thermostat AC/HP Wi-Fir Thermostat Performance Series Installation Guide INTRODUCTION Welcome and from all of us at Carrier, thank you for purchasing your new Côr thermostat: the
More informationEnvironmental Monitoring and Alarming
Environmental Monitoring and Alarming About Geist Geist designs and manufactures industry leading technology and software for powering, monitoring, cooling and managing critical data center infrastructure.
More informationIntrinsically Safe Digital Float Monitor Instruction Manual
Intrinsically Safe Digital Float Monitor Instruction Manual Model # DT-IS-GPS Series Document # 040256C0001 Revision # A Dated 06/21/2010 Notice The information contained in this document is current as
More informationSensorHawk 4 PoE. For more information please visit us at or call us at 1 (800)
A high-speed, accurate and intelligent monitoring device. The Poe is a completely embedded host with a proprietary Linux like OS which includes TCP/IP stack, a built-in web-server and full Email and SNMP
More informationADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE
K3179V2 2/11 Rev. A ADEMCO 4208SNF V-Plex Universal Class A Module INSTALLATION AND SETUP GUIDE FEATURES The ADEMCO 4208SNF Universal Class A Module can be used in either of two different applications.
More informationsafety & regulatory information
safety & regulatory information Document Part Number: 338610-001 Sixth Edition June 2006 This guide provides safety and regulatory information that is compliant with U.S., Canadian, and International regulations.
More informationIFS Fiber Module Installation & Operation Instructions
VAT7420 VAT7420-R3 VAT7430 VAT7430-HP VAT7450 VAT7450-R3 VAT7450-HP IFS Fiber Module Installation & Operation Instructions VAR7420 VAR7420-R3 VAR7430 VAR7430-R3 VAR7450 VAR7450-R3 P/N 1062829 REV B ISS
More informationInstallation and Operation Manual Low Power (LP) DC Power System
Installation and Operation Manual Low Power (LP) DC Power System LPS Power Enclosure LPB Battery Enclosure 2051259 R3 Information in this document is subject to change without notice and does not represent
More informationUser Manual. Power Distribution Unit. Version: 1.0
User Manual Power Distribution Unit Version: 1.0 Table Of Contents 1. Introduction... 1 1-1 Package Contents... 1 1-2 Safety... 1 1-3 Disposing of PDU... 1 1-4 Function... 1 1-5 Overview... 2 2. Installation...
More informationICT180S-12I INTELLIGENT MODEL (SERIES 2)
The Power of Reliability ICT180S-12I INTELLIGENT MODEL (SERIES 2) INSTRUCTION MANUAL TABLE OF CONTENTS Warnings Page 2 Product Description Page 3 Installation Page 4 LCD/Select Button Operation Page 7
More informationADT. Pulse 2017ADT LLC
ADT Pulse Interactive Solutions DBC835 Wirelesss HD Doorbell Cameraa Quick Installation Guide Property of ADT, LLC. Information accurate as of published date and is provided as is without warranty of any
More informationEvolve 5.5 cu. ft. Medical-grade Undercounter Refrigerator
Evolve 5.5 cu. ft. Medical-grade Undercounter Refrigerator Quick Start Guide Product Features Quiet Operation Temperature Uniformity SilverPoint Enabled Local and Remote Alarms Stable Temperature Control
More informationLORAIN CSP DC Power System
DC Power for Business-Critical Continuity Key Features Compact flexibility provides more space for revenue generating equipment Constant power delivers more current at lower voltages to meet load or recharge
More informationMETEOROLOGICAL INSTRUMENTS
METEOROLOGICAL INSTRUMENTS INSTRUCTIONS WIND TRACKER MODEL 06206 R.M. YOUNG COMPANY 2801 AERO PARK DRIVE, TRAVERSE CITY, MICHIGAN 49686, USA TEL: (231) 946-3980 FAX: (231) 946-4772 WEB: www.youngusa.com
More informationKWX- N1 N2 N3 N4 Remote Monitored PDU
KWX- N1 N2 N3 N4 Remote Monitored PDU KWX-N series is our remote monitored PDU that supports multitask and multiuser access. The software supports various TCP/IP protocols, Including: HTTP, HTTPS, SSL,
More informationConcord 5 TouchScreen Installation Sheet
Concord 5 TouchScreen Installation Sheet Safety information IMPORTANT SAFETY INFORMATION. READ ENCLOSED WARNINGS AND SAFETY INFORMATION. WARNING! Disconnect panel power before servicing. CAUTION: Use static
More informationCisco TelePresence MCU 4200 Series safety and compliance information
Cisco TelePresence MCU 4200 Series safety and compliance information On this page: Safety information symbols Operating guidelines Safety warnings Technical specifications Compliance information WEEE information
More informationDominion PX. Intelligent Rack Power Distribution. Dominion PX Series. Broadest portfolio of smart PDUs to enable energy management in the data center
Dominion PX Intelligent Rack Power Distribution Dominion PX Series Intelligent PDUs and inline meters that give you more control of power and cooling in the data center. Remote power monitoring and metering
More informationUsing ANM Mobile CHAPTER
CHAPTER 19 Date: 3/22/13 This chapter describes Cisco ANM Mobile, which allows you to access your ANM server or ANM Virtual Appliance and manage your devices using a mobile device such as an iphone or
More informationRACK MONITORING SYSTEM RAMOS Ultra
version: 7-05-03 CONTEG DATASHEET COMPLEMENTARY SYSTEMS RACK MONITORING SYSTEM CONTEG, spol. s r.o. Czech Republic Headquarters: Na Vítězné pláni 79/4 40 00 Prague 4 Tel.: +40 6 9 8 Fax: +40 6 9 9 Production
More informationInnovative Circuit Technology Ltd.
Innovative Circuit Technology Ltd. Dual Bus Distribution Panel Series INSTRUCTION MANUAL 855-314-000 Models: ICT200DF-12IRC ICT200DB-12IRC WARNING Risk of serious personal injury or damage to equipment
More informationRC300 IntelliFire Plus Multifunction Remote Control Installation & Operating Instructions
RC300 IntelliFire Plus Multifunction Remote Control Installation & Operating Instructions Hearth & Home Technologies disclaims any responsibility for, and the warranty will be voided by, the following
More informationBased on years of Industry experience it s ready to run right out of the box, simply assign the IP address and connect to the embedded web server.
v.100.00x A high-speed, accurate and intelligent monitoring device. The is a completely embedded host with a proprietary Linux like OS which includes TCP/IP stack, a built-in web-server and full Email
More informationThermoControl 0 C - 10 C - 20 C - 30 C
ThermoControl Product and Quality Reliability Alarm Functions & Documentation Global Monitoring 0 C - 10 C - 20 C - 30 C Global monitoring: global temperature measurement and real-time monitoring using
More informationDisclaimer. Trademarks. Copyright. Warranty
1 Disclaimer Trademarks Copyright Control4 makes no representations or warranties with respect to any Control4 hardware, software, or the contents or use of this publication, and specifically disclaims
More informationPerformance Thermal Binder
Performance Thermal Binder TM Helios 60 E F S Please read these instructions before use. Lire ces instructions avant utilisation. Lea estas instrucciones antes de usar la máquina. INDEX LAMINATOR CONTROLS
More informationLC-151 Dual-Tech Motion Sensor (Single PIR & Microwave) with adjustable Pet Immunity INSTALLATION INSTRUCTIONS & USER MANUAL P/N: ver.
LC-151 Dual-Tech Motion Sensor (Single PIR & Microwave) with adjustable Pet Immunity INSTALLATION INSTRUCTIONS & USER MANUAL P/N: 7131720 ver.b 1 1 General... 3 2 Features... 3 3 Assembly description...
More informationIon Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm
Ion Endeavor Controller Digital Level Control with Alternation Page 1 of 8 General Overview The Ion Endeavor is a pump controller that senses a water level of up to 72", has a configurable water level/pump
More informationecobee 3 Quick Start Guide Installation Guide DRAFT
ecobee 3 Quick Start Guide Installation Guide DRAFT 1 what s in the box? ecobee3 thermostat remote sensor (and stand) power extender kit ecobee 3 Installation Guide 2 optional trim plate installation materials
More informationGalaxy Pulsar Plus Digital Battery Plant Controller
Galaxy Pulsar Plus Digital Battery Plant Controller Features Supports up to 60 Power Modules rectifiers and converters Supports dual voltage plants, with rectifiers and converters Auto-sensing dual voltage
More informationIntelliDoX Operator Manual
IntelliDoX Operator Manual OPERATOR MANUAL TABLE OF CONTENTS Table of Contents Table of Contents...1 About this Publication...3 Important Safety Information: Read First...4 Getting Started...5 About the
More informationKnürr RMS Compact II. Knürr RMS Compact II 2.81
Knürr RMS Compact II Knürr RMS Compact II 2.82 to 2.85 2.81 Knürr RMS Compact II Damage prevention with checks and controls System and network management requirements mean the systems ambient conditions
More informationIMPORTANT SAFETY INFORMATION! WARNING ALWAYS keep electric cords, home furnishings, drapes, clothing, papers, or other combustibles at least 3 feet (0
Electric Fireplace Factory Model: EF-30D CONSUMER SAFETY INFORMATION Read this manual before installing and operating this appliance Failure to follow these instructions may result in electric shock, fire
More information23-IN Electric Logset
23-IN Electric Logset ASSEMBLY, CARE & USE INSTRUCTIONS MODEL # ELCG240-INF Questions, problems, missing parts? Before returning to your retailer, call our customer service department at 1-855-571-1044
More informationT M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power
T M User Manual MarinaGuard Ground Fault Monitoring Panel For Marina Shore Power NAE1095810 / 03.2013 T M Bender Inc. USA: 700 Fox Chase Coatesville, PA 19320 Toll-Free: 800-356-4266 Phone: 610-383-9200
More informationMonitoring Solutions
GSM Systems Monitor: Temperature, Humidity, Power, Water, Smoke, Carbon Monoxide and More September 2016 Table of Contents GSM Systems... 3 Argon 100 GSM... 3 Ares 12 & 14 GSM... 4 Poseidon2 4002... 5
More informationPour & Float Froggy TM
US User s Manual Pour & Float Froggy TM 2012 VTech Printed in China 91-002702-007 Introduction Thank you for purchasing the VTech Pour & Float Froggy TM! The Pour & Float Froggy TM is full of surprises!
More informationGigaCore 12. Gigabit Ethernet Switch for the entertainment industry. Quick Start Guide. V2.1.0 Rev5. English
GigaCore 12 Gigabit Ethernet Switch for the entertainment industry Quick Start Guide V2.1.0 Rev5 English Table of Content Safety Instructions 3 Compliance information 4 Warranty information 5 Registration
More information3M Benchtop Air Ionizer 963E. User s Guide
3M Benchtop Air Ionizer 963E User s Guide 1 Table of Contents Section Page Safety Information...3 1. Description...4 2. Performance...4 3. Power Requirements...4 4. Installation...4 5. Operation...5 6.
More informationDATAssure. Laboratory wireless alarm & monitoring system
DATAssure Laboratory wireless alarm & monitoring system Wireless alarm & monitoring system A new monitoring generation The DATAssure wireless monitoring system is used across a broad range of market sectors
More information[ [ ADMIN PANEL USER GUIDE
[ [ ADMIN PANEL USER GUIDE ADMIN PANEL USER GUIDE 2 Contents Logging In & Systems Overview 3 System Details 5 Analytics 6 View Alarms 8 Manage Alarms 9 Create Alarms 10 Device Reporting Alarm 11 Monthly
More informationC-Bus Four Channel General Input Unit Installation Instructions
C-Bus Four Channel General Input Unit Installation Instructions 5504GI Series REGISTERED DESIGN REGISTERED PATENT Table of Contents Section...Page 1.0 Product Range... 3 2.0 Description... 3 3.0 Capabilities...
More informationProliphix Thermostat Installation Guide. Release 2.0
Proliphix Thermostat Installation Guide Release 2.0 July 2006 Beta Draft Confidential Technical Support When contacting Proliphix for technical assistance, please have the following information available:
More informationCode Alert Series 30 Software User Guide
Code Alert Series 30 Software User Guide 2018 RF Technologies, Inc. All specifications subject to change without notice. All Rights Reserved. No Part of this work may be reproduced or copied in any form
More informationAdded password for IP setup page : Password must be in IP format!
NETWORK POWER MONITOR Release : 21 August 2014 Hardware Version : Version 7 Firmware version 1.00 PC Application Software : Version (latest)...2 Added password for IP setup page : Password must be in IP
More informationMILLA ELECTRIC FIREPLACE
MILLA ELECTRIC FIREPLACE MODEL NO. 064-3177-0 ASSEMBLY INSTRUCTIONS Toll-free: 1-888-670-6684 IMPORTANT: Please read this manual carefully before beginning assembly of this product. Keep this manual for
More informationPlease Keep This Manual For Future Reference REV.01
ELCG347 ELCG240 1-855-571-1044 Please Keep This Manual For Future Reference REV.01 IMPORTANT INFORMATION When using electrical appliances, basic precautions should always be followed to reduce the risk
More informationIFS Fiber Module Installation & Operation
T1000 T1000-R3 T1020 T1020-R3 T1025 T1025-R3 R1000 R1000-R3 R1030 R1030-R3 R2000 R2000-R3 R2020 R2020-R3 R2025 R2025-R3 R2010WDM R2010WDM-R3 R2010WDMB R2010WDMB-R3 IFS Fiber Module Installation & Operation
More informationDC-RMCU1 DC-Powered Remote Monitoring and Control Unit Owners Guide
DC-RMCU1 DC-Powered Remote Monitoring and Control Unit Owners Guide (These instructions are intended for use by a technician familiar with electronic products) Remote Monitoring and Control Unit Web Ready
More informationOperating Manual. Gasgard 100 Control System. Order No.: /00. MSAsafety.com
Operating Manual Gasgard 100 Control System Order No.: 10153908/00 MSAsafety.com Warning! THIS MANUAL MT BE CAREFULLY READ BY ALL INDIVIDUALS WHO HAVE OR WILL HAVE THE RESPONSIBILITY FOR ING OR SERVICING
More informationDT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions
DT8050A DUAL TEC Motion Sensor with Anti-Mask - Installation Instructions QUICK LINKS Mounting Location Guidelines Open the Sensor Mount the Sensor Sensor Components and Settings Wire the Sensor Wiring
More informationSYSTEM OVERVIEW. Environmental Monitoring. Simplified.
SYSTEM OVERVIEW Environmental Monitoring. Simplified. Uptime Devices designs Environmental Monitoring products for businesses of all sizes. APPLICATIONS Data Centers Cold Storage Power Plants Manufacturing
More informationOutdoor Temperature Sensor
Didactum`s IP-based monitoring devices have many uses: Monitoring of wiring closets and server room environments Remote monitoring of technical rooms in branch offices Monitoring of power supply systems
More informationTypical applications include the vibration detector. Detection of vibrations and shocks
Didactum`s IP-based monitoring devices have many uses: Monitoring of wiring closets and server room environments Remote monitoring of technical rooms in branch offices Monitoring of power supply systems
More informationShockLink. Important Product Information.
EN ShockLink Important Product Information www.laerdal.com English ShockLink Important Information Warnings and Cautions A Warning states a condition, hazard, or unsafe practice that can result in serious
More informationRaytec Avigilon Integration User Guide Integrating Raytec Network Illuminators with Avigilon Control Center Document Revision 2.0
Raytec Avigilon Integration User Guide Integrating Raytec Network Illuminators with Avigilon Control Center Document Revision 2.0 Table of Contents 1 INTRODUCTION... 3 1.1 OVERVIEW... 3 1.2 SOFTWARE COMPONENTS...
More informationBROADBAND MODEL WITH REMOTE POWER CONTROL (SERIES 2) ICT180S-12BRC (FOR POSITIVE GROUND SYSTEMS) ICT180S-12BRCP (FOR NEGATIVE GROUND SYSTEMS)
The Power of Reliability BROADBAND MODEL WITH REMOTE POWER CONTROL (SERIES 2) ICT180S-12BRC (FOR POSITIVE GROUND SYSTEMS) ICT180S-12BRCP (FOR NEGATIVE GROUND SYSTEMS) INSTRUCTION MANUAL TABLE OF CONTENTS
More informationPipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual
MANUAL Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual Model FPT 130 Single Point Freeze Protection Heat Trace Control Table of Contents SCFP-CO-F130 Overview... 3 Installation...
More informationKT-100 Door Controller
WARNING: This manual contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer. The entire manual should be carefully
More informationO2LPR67 Full HD Bullet IP LPR Camera
CAUTION CAUTION RISK OF ELECTRIC SHOCK NOT OPEN RISK OF DO ELECTRIC SHOCK DO NOT OPEN CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK DO NOT REMOVE COVER (OR BACK) NO USER-SERVICEABLE PARTS INSIDE REFER
More informationModel SWH-4000 Multi-Technology Mullion 125 KHz and MHz (Flex) Reader Installation Guide. Version A0 Part Number UM-104 September 2005
Model SWH-4000 Multi-Technology Mullion 125 KHz and 13.56 MHz (Flex) Reader Installation Guide Version A0 Part Number UM-104 September 2005 1 CONTENTS Introduction................................................
More informationYale Real Living Key Free Push Button Deadbolt B1L Installation and Programming Instructions
Yale Real Living Key Free Push Button Deadbolt B1L Installation and Programming Instructions Before you begin DOWNLOAD THE BILT APP for step-by-step installation instructions & to register your product
More informationMODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT
TRACON MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT TABLE OF CONTENTS GPT 130 Overview... 2 Installation... 3 Power Source and Load Connection... 4 Temperature Sensor Installation... 5 Panel
More informationCombined CAN Sensor Unit Temperature, Humidity and Smoke
Combined CAN Sensor Unit Temperature, Humidity and Smoke Didactum`s IP-based monitoring devices have many uses: Monitoring of wiring closets and server room environments Remote monitoring of technical
More informationCODE ALERT Enterprise Software User Guide
CODE ALERT Enterprise Software User Guide 2018 RF Technologies, Inc. All specifications subject to change without notice. All Rights Reserved. No Part of this work may be reproduced or copied in any form
More informationSingle Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual
We manage heat MANUAL Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual 1850 N Sheridan Street South Bend, Indiana 46628 (574) 233-1202 or (800) 234-4239
More informationNGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions
NGC-UIT-ORD User interface terminal for Raychem NGC systems Installation Instructions Description The NGC-UIT-ORD is a panel mounted display used in conjunction with other approved Raychem control and
More informationQuick start guide. SB3014-WM DECT 6.0 expansion wireless mic for use with AT&T model SB3014
Quick start guide SB3014-WM DECT 6.0 expansion wireless mic for use with AT&T model SB3014 Congratulations on purchasing this AT&T product. For customer support or product information, visit our website
More information