1 VAV Parameters 2017 products.koer.com Page 1 of 14
2 INTRODUCTION Learn how to setup various VAV parameters and configurations, PID calculation elements, EC motor voltages, wall type etc products.koer.com Page 2 of 14
3 Step 1 Enter Advanded Menu ONLY AUTHORIZED MAINTENANCE PERSONNEL SHOULD ENTER ADVANCED MENU AND MAKE CHANGES Picture 1. Press Menu Button Picture 2. Press Advanced to enter Advanced menu Picture 3. Enter Admin Password Menu appears Use the numbers to enter 4 digit factory preset pin. Number is being displayed in the blue ribbon Press DEL button to delete incorrect number Press OK to confirm input 2017 products.koer.com Page 3 of 14
4 Step 2 Enter Parameters Menu Picture 1. Press Parameter button to enter Parameter menu Picture 2. You entered Parameter menu Picture 2. Use Home button to return to Home Screen Picture 2. Use Up button to return to Advanced Menu Picture 2. Use Next and Prev button to navigate through various settings 2017 products.koer.com Page 4 of 14
5 Step 3 Control Sequence Go to Parameters 1 / 6 Menu Control sequence: The control sequence defines whether the controlled system is capable of heating, cooling or ventilating the zone. Select the desired control sequence by pressing the button next to Control sequence. The options are: Cooling - if the sensor temperature is higher then setpoint, Codis starts cooling the air. If the temeperature sensor is lower then the setpoint, Codis does not do anything Heating- if the sensor temperature is lower then setpoint, Codis starts heatingthe air. If the temeperature sensor is higherthen the setpoint, Codis does not do anything Cooling or Heating - using either manual button in Menu, or automatic changeover external RTD sensor or through CBMS device either is in cooling or heating mode Cooling and heating - device cools if sensor temperature is higher then setpoint and heats if sensor temperature is lower then setpoint 2017 products.koer.com Page 5 of 14
6 Ventilation - there is no temperature control, only control of humidity and air quality Press Save to confirm changes Step 4 Parameters 1 settings - Part I Cooling / Heating coil - If there are optional heat exchangers or modulating electric heaters, it is necessary to enable the analog output signal for the valve(s) through the Cooling / Heating Coil parameter Fan operating mode - A fan can be placed in series or in parallel with a VAV box. The Fan operating mode parameter is off by default. The parameter can be set to Series or Parallel depending on the configuration Series: If the fan is configured in series, the VAV damper actuator and fan are controlled according to temperature or air quality demand. The fan maximum and minimum speed can be adjusted in Parameters [5 / 5] Fan AQ PID and ECM voltage) 2017 products.koer.com Page 6 of 14
7 Parallel without heat exchanger: If the fan is configured in parallel, then the fan is used to recirculate warmer ceiling air. The parallel fan operates only when Heating is active and according to the 2017 products.koer.com Page 7 of 14
8 ambient temperature (the lower the ambient temperature, the higher the fan speed) Parallel with heat exchanger: VAV damper actuator will be controlled according to air quality demand. The fan and heat exchange valve will be controlled according to room air temperature Step 5 Parameters 1 settings - Part II Dehumdification: C35-VAV... can be configured to dehumidify a controlled zone with the dehumidification parameter. The options are: Enabled - The following system configuration is required to enable dehumidification: Control sequence is set to Cooling or Cooling and Heating ; or Cooling / Heating coil parameter is enabled; or The unit or system has a built in relative humidity sensor (optional) While operating in cooling mode, the valve of the heat exchanger will control relative humidity in line with each working modes humidity setpoints Disabled - Dehumidification will be disabled 2017 products.koer.com Page 8 of 14
9 Changeover signal: can be configured to be either Internal or external by CBMS input Occupied timer: The default duration for the occupancy timer is 60 minutes. To adjust the occupancy timer duration, enter screen 01/05 of the parameters menu and increase or decrease the number of minutes using the +/- buttons Press Save to confirm changes 2017 products.koer.com Page 9 of 14
10 Step 6 Parameters 02 settings Go to Parameters 2/6 menu VAV Voltage Output : To change analog output (AO1) voltage range from 0-10 V to 2 10 V and vice versa press the VAV voltage output button The Proportional-Integral- Derivative controller (PID controller) calculates a difference between measured values and set points. The PID controller minimizes the difference between those values by adjusting openness of the valves, damper actuator or fan speed. Adjust PID gains according to each project s specifications Tuning a PID controller involves setting values of Proportional band(p-band), Integral time(i-time) or Derivative time(d-time) parameter values. If two-term (PI) or one-term (P) control is needed adjust unnecessary values to zero VAV Temp. PID: is VAV temeperature PID for regulating temperature control Use + and - buttons to increase or decrease values Press value button to enter Keyboard to input PID value number Press Save to confirm changes 2017 products.koer.com Page 10 of 14
11 Step 7 Parameters 03 settings Go to Parameters 3/6 menu VAV Air Quality: PID controller for fine tuning CO2 control Valve : PID controller for fine tuning Valve opening control Use + and - buttons to increase or decrease values Press value button to enter Keyboard to input number Press Save to confirm changes Step 8 Parameters 04 settings Go to Parameters 4/6 menu Dehumdific. - PID controller for fine tuning Relative humidity control Fan Temp. - PID controller for fine tuning Fan temperature control Use + and - buttons to increase or decrease values Press value button to enter Keyboard to input number Press Save to confirm changes 2017 products.koer.com Page 11 of 14
12 Step 9 Parameters 05 settings VAV Air Quality: PID controller for fine tuning CO2 control ECM: The analog output signal for the EC motor can be configured with three parameters: ECM Min Off voltage: If this value is different from zero volts, adjust the ECM OFF voltage to value that will turn off the ECM fan. ECM MIN voltage: Defines the minimum signal value and the minimum speed of the fan (5 %). ECM MAX voltage: Defines the maximum signal value and the maximum speed of the fan (100 %). Use + and - buttons to increase or decrease values Press value button to enter Keyboard to input number Press Save to confirm changes 2017 products.koer.com Page 12 of 14
13 Step 10 Parameters 06 setting Wall type: choose between type of wall where device is mounted. Current options: Brick Drywall Press Save to keep changes Step 11 Parameters 5 settings Insert wisdom here. This document was last generated on :29:50 PM products.koer.com Page 13 of 14
VAV Thermostat Controller Specification and Installation Instructions. Model TRO24T4XYZ1
Model TRO24T4XYZ1 Description The TRO24T4XYZ1 is a combination controller and thermostat. The VAV Thermostat Controller is designed for simple and accurate control of any variable air volume box in a number
More informationcontrol sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals
control sequences Table 47: QST / EST Analog Electronic Control Strategies Control Package Number QST EST FS-A-5000 FSE-A-5000 FS-A-5001 FSE-A-5001 FS-A-5002 FSE-A-5002 FS-A-5003 FSE-A-5003 FS-A-5004 FSE-A-5004
More informationRegulation EASY CLIMA VERSION 1.6 TECHNICAL MANUAL
Regulation EASY CLIMA VERSION 1.6 TECHNICAL MANUAL WARNINGS SAFETY WARNINGS Read this manual carefully before installation and/or use of the equipment and keep it in an accessible place. The Manufacturer
More informationTEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application Application Note Building Technologies
TEC Controller Terminal Box Controller (VAV) - with Hot Water Reheat, Application 2023 Application Note 140-1052 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 6 Hardware Outputs...
More informationAirTrak. Digital Control System. User Manual. Touchscreen Systems
AirTrak Digital Control System User Manual Touchscreen Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 9 AIRTRAK DEFAULT SETTINGS... 9 Unit Operating Modes... 10 MRT Controls...
More informationTEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application Application Note
TEC Controller Terminal Box Controller (VAV) - Series Fan Powered with Hot Water Reheat, Application 2025 Application Note 140-1054 Building Technologies Table of Contents Overview... 4 Hardware Inputs...
More informationSiemens Thermostats. RDY2000BN Thermostat
Siemens Thermostats RDY2000BN Thermostat Answers for infrastructure and cities. Introducing the RDY2000BN BACnet Commercial Thermostat Bring more buildings and zones under control Reduce energy costs BACnet
More informationFan Coil Thermostat Controller Specification and Installation Instructions. Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication
Model TFHB24F3XYZ1 with External Humidity Sensor and BACnet Communication Description The TFHB24F3XYZ1 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications.
More informationZIP Economizer Method of Operation Sequence of Operation States Virgin State The ZIP Economizer comes shipped from the factory in this state. Setup Incomplete will be displayed. No control will occur until
More informationDOAS CM3500 Controller
DOAS CM3500 Controller Table of Contents Dehumidification Equipment Standard Limited Warranty 3 Installation 4 IAQ Controller Details 7 Alarms 27 Hardware Details 30 Specifications 33 Points List 37 Revision
More informationTEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application Application Note Building Technologies
TEC Controller Unit Conditioner - Two-Pipe Fan Coil Cooling or Heating, Application 2050 Application Note 140-1136 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware Outputs...
More informationTEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application Application Note Building Technologies
TEC Controller VAV 0-10V Fan Control with Hot Water Heat, Application 2236 Application Note 140-1228 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 10 Hardware Outputs... 10
More informationAdaptAire. Digital Control System. User Manual. Expert Systems
AdaptAire Digital Control System User Manual Expert Systems Rev. 10-29-15 1 2 Table of Contents OVERVIEW... 8 NETWORKING... 10 ADAPTAIRE DEFAULT SETTINGS... 10 UNIT OPERATING MODES... 11 MRT Controls:...
More informationFan Coil Thermostat Controller Specification and Installation Instructions. Model TFH24F3XYZ2 Stand-alone with Internal Humidity Sensor
Model TFH24FXYZ2 Stand-alone with Internal Humidity Sensor Description The TFH24FXYZ2 is a fully configurable controller designed specifically for 2 pipe and 4 pipe fan coil applications. No additional
More informationAdvanced Installation and Configuration Instructions
TP-WEM01-A Performance Series AC/HP Wi- Fi Thermostat Carrier Côr Thermostat Advanced Installation and Configuration Instructions Table of contents How to Use This Document... 3 Wiring Diagrams... 4 Installations
More informationUser s Manual ELITE PROGRAMMABLE THERMOSTAT WITH MENU DRIVEN DISPLAY
User s Manual ELITE PROGRAMMABLE THERMOSTAT WITH MENU DRIVEN DISPLAY Customizable programming options for every day, weekdays, weekends, or individual days. Smart recovery gradually adjusts indoor temperatures
More informationEXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov
3005925_2018-02-05.fm EXcon zone control Control for up to 4 individual zones EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov Tel. +45 65 66 12 34 Fax +45 65 66 11 10 exhausto@exhausto.dk www.exhausto.dk OJ-Air2
More informationONX908PIT-V1-S1-F1/B Modulating Digital Thermostat
ONX908PIT-V1-S1-F1/B Modulating Digital Thermostat Installation and operation instructions The ONX908PIT-V1-S1-F1 modulating digital thermostats are designed to provide Proportional-Integral (PI) modulating
More informationExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling
ExactLogic BACnet Communicating Thermostat EXL01627 Sequence Datasheet Fan Coil with Modulating Fan and Heat or Cool Floating Heating and Cooling DataSheet ev 1.12.304/4.0 June 14, 2016 Operating Sequence
More informationModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.
ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008 - 2 - Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page
More informationJob Name Control Systems Description Date
Job Name Control Systems Description Date Project Overview The project is a describe the building and its major HVAC systems (e.g. three-story office building, served by a rooftop unit VAV system ). In
More informationTC-9102 Applications
Application Note January 7, 2004 APPLICATION NOTE TC-9102 Applications Configuring TC-9102 Applications...3 Introduction... 3 Key Concepts... 4 TC-9102 Controller... 4 Control Modes...8 Procedure Overview...
More informationVT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors
VT8000 Series Replacement Procedure to Replace VT8000 Series Room Controller and Pair with ZigBee Pro Sensors Overview 2 This procedure shows how to replace VT8000 Room Controllers already installed, as
More informationBACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657
BACnet PTEC Controller VAV 0 to 10V Series Fan and 3- Stage Electric Heat, Application 6657 140-1158 Building Technologies Table of Contents Overview... 5 BACnet 14 Hardware Inputs... 14 Room Unit Identification...
More informationCommercial Touchscreen Thermostat
55,13M 1/27 Supersedes 12/25 Commercial Touchscreen Thermostat 25 Lennox Industries, Inc. Dallas, Texas, USA APPLICATION Page 1 INSTALLATION INSTRUCTIONS The Lennox Commercial Touchscreen Thermostat provides
More information0 C to 50 C ( 32 F to 122 F ) 0% to 95% R.H. non-condensing. 30 to 95% R.H. Dry contact across terminal BI1, BI2 & UI3 to Scom
Viconics VT7350 Series PIR Ready Fan-coil Controllers General The VT7350 series are PIR Ready low-voltage microprocessor-based fan-coil controllers. Models are available controlling single speed and multi-speed
More informationTri-Stack Smart System
Tri-Stack Smart System TM Notes & Warnings - The protection provided by this equipment may be impaired if it is not used in the manner specified herein. - Ensure all wiring meets applicable national and
More informationSEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT
SEQUENCE OF OPERATION GUIDELINE AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT Document: VAV-HTG rev1 Revision: 1.0 Rev. Date: July 22, 2011 NOTES: 1. THIS SEQUENCE
More informationSEQUENCE OF OPERATIONS
SEQUENCE OF OPERATIONS DDC CONTROLLER: Controller with integral LCD readout for changing set points and monitoring unit operation. Provided with required sensors and programming. Factory programmed, mounted,
More informationOVEN INDUSTRIES, INC.
OVEN INDUSTRIES, INC. OPERATING MANUAL Model 5C7-252 TEMPERATURE CONTROLLER With PLC Inputs Introduction Thank you for purchasing our controller. The Model 5C7-252 is an exceptionally versatile unit and
More informationRooftop Unit, Heat Pump and Indoor Air Quality Application Guide
Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT8600 Rooftop Unit Heat Pump and Indoor Air Quality Controllers 3 VT86X0U5X00B
More informationManual Supplement. Product/System Title: Static Pressure Controller. Contents of this manual supplement include:
Model Number: Product/System Title: 8635-ST Static Pressure Controller Contents of this manual supplement include: 1) Sequence of operation 2) Description of new software items 3) Deleted software menu
More informationVerasys System Operation Overview Technical Bulletin
Contents subject to change. Verasys System Operation Overview Technical Bulletin Code No. LIT-12012370 Issued January 2016 Refer to the QuickLIT Web site for the most up-to-date version of this document.
More informationI/O ZONE 560/583 USERS GUIDE
I/O ZONE 560/583 USERS GUIDE 641-224 641-242 641-237 1 Table of Contents Hot Gas Re-Heat Valve On/Off:... 15 THE ZONE CONTROLLER...4 Modulating Re-Heat Valve:... 16 SPECIFICATIONS...5 CONTROLLER COMPONENTS...6
More informationExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C
ExactLogic BACnet Communicating Thermostat EXL01625 Sequence Datasheet Fan Coil with Modulatating H/C and PO-PC H/C DataSheet ev 1.10.403/4.02 November 6, 2012 Operating Sequence Standard Occupied During
More information1 Air Handling Units In ICE
1 Air Handling Units In ICE From version 3.0, there is a library of common air handling units (AHU) in the distribution. A simulated building can have several AHUs. The following limitations apply: - every
More informationINDOOR CLIMATE OF A SINGLE ZONE
IDA Indoor Climate and Energy Basic Course INDOOR CLIMATE OF A SINGLE ZONE Guide Copyright EQUA Simulation AB February 2018 Purpose This is the first part of the IDA ICE basic course 1, where you get started
More informationNetworkable Fan Coil Controller Specification and Installation Instructions
Controller Models EFCB10T-OE1 (24Vac / 0 relays) EFCB12T-OE1 (240Vac / 0 relays) EFCB10TU4-OE1 (24Vac / 4 relays) EFCB12TU2-OE1 (240Vac / 2 relays) EFCB12TU4-OE1 (240Vac / 4 relays) TFL Series Thermostat
More informationExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet
ExactLogic BACnet Communicating Thermostat EXL01622 Sequence Datasheet DataSheet ev 1.2.008/4.1 July 30, 2013 Operating Sequence Standard Occupied During normal occupied operation the display will show
More informationUNT Applications. Using UNT Applications...3. Introduction Key Concepts UNT Controller Applications Fan Coil Units...
Application Note Issue Date 04/17/08 Supersedes 01/11/01 APPLICATION NOTE Using...3 Introduction... 3 Key Concepts... 4 UNT Controller Applications... 4 Fan Coil Units... 8 Unit Ventilators... 11 Rooftop
More informationUSER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel
USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel PU SENS 01 CONTENTS Safety requirements... 3 Purpose... 4 Technical data... 4 Overall dimensions [mm]... 4 Mounting and set-up... 5
More informationSpecification , July 2015
Technical Information PrecisionLine Controllers EDC21 / EDC22 / EDC23 EASYSET DIGITAL CONTROLLERS Specification 51-52-3-48, July 215 Introduction The EDC21, EDC22 and EDC23 controllers provide precise
More informationTEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application Application Note Building Technologies
TEC Controller Single Compressor Heat Pump with Reversing Valve Control, Application 2070 Application Note 140-1040 Building Technologies Table of Contents Overview... 4 Hardware Inputs... 5 Hardware
More informationReference Guide for Microprocessor Controller
Document 483586 Microprocessor Controller for Dedicated Outdoor Air System Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before
More informationSequence of operation
Sequence of operation IPS 4000 secondary variable speed control File No: 90.96 Date: february 21, 2013 Supersedes: new Date: new sequence of operation ips 4000 2 list of abbreviations: adj: Field Adjustable
More informationAdaptAire. Digital Control System. User Manual
AdaptAire Digital Control System User Manual Rev. 10-22-07 1 Table of Contents OVERVIEW... 6 NETWORKING... 7 ADAPTAIRE DEFAULT SETTINGS... 7 UNIT OPERATING MODES... 8 MDT Controls:... 8 UNIT OFF MODE...8
More information1 DOCUMENT REVISION CONTROL ELEMENTS... 9
CONTENTS Contents 1 DOCUMENT REVISION... 8 2 SOFTWARE VERSION... 8 3 BASIC DESCRIPTION... 8 4 CONTROL ELEMENTS... 9 4.1 BASIC DISPLAYS...10 4.2 CONTROL KEYS...11 4.2.1 Rotary button (Press / Turn)...11
More informationTEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application Application Note
TEC Controller Multiple Compressor Heat Pump with Reversing Valve & Mixed Air Control, Application 2273 Application Note 140-1045 Building Technologies Table of Contents Overview... 4 Hardware Inputs...
More informationHIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER
This manual must be left with owner and should be hung on or adjacent to the boiler for reference. US HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER MODELS CHS-85 through CHS-399 APPENDIX A CONTROLLER
More informationTstat9. Bacnet Thermostat
Tstat9 Bacnet Thermostat This full-featured thermostat is designed for cooling and heating systems in residential and commercial buildings.the thermostat can be configured for or use with air handlers,fan
More informationTempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications
Instruction Manual Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications Manual PCT-3000 Revision 9/2014 The PCT-3000 series control console incorporates
More informationTAP v2.10 Version Date: 6/12/13. Document Microprocessor Controller for Tempered Air Products
Document 475595 Microprocessor Controller for Tempered Air Products Reference Guide for the Microprocessor Controller Please read and save these instructions. Read carefully before attempting to operate
More informationModeling projects that require very tight space temperature control
Modeling projects that require very tight space temperature control Whereas space temperature controls for maintaining human thermal comfort typically have a deadband of several degrees between heating
More informationC37. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C37. User's Guide. Installer's Guide *VI7CE602* *087R8070* *087R8070* *VI7CE602*
User's Guide VI.7C.E6.02 2005.09 C37 *VI7CE602* *087R8070* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8070* *VI7CE602* Mixing controller with ON / OFF controlled
More informationC66. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C66. User's Guide. Installer's Guide. *vi7cc502* *087R8069* *087R8069* *vi7cc502*
User's Guide VI.7C.C5.02 2005.09 C66 *vi7cc502* *087R8069* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8069* *vi7cc502* Mixing controller with PI controlled
More information*IG1583EW* Aurora Touch UPC Kit Instruction Guide. Aurora Touch UPC Kit Instruction Guide
Aurora Touch UPC Kit Instruction Guide For use in single compressor water-to-air equipment utilizing fi rmware UPCSWASTD01-01 Aurora Touch UPC Kit Instruction Guide *IG1583EW* IG1583EW 08/14 Aurora Touch
More information1.0 Digital Controller
Form CP-AHU D19_D21_D22 (11-17) D303072-A Obsoletes Forms CP-Preeva-D21 (1-16) Doc No 303072, CP-Preeva-D19 (1-16) Doc No 303071 Applies to: Preeva, MAPS, MAPS II, RPB, RPBL & SSCBL Series For Air Handler
More informationCELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL
Operation Manual Celltrol II Bioreactor Control System Page 1 of 33 Table of Contents 1) Introduction... 3 1.1) Scope of Document... 3 1.2) Control System Overview... 3 1.3) Introduction to Celltrol II...
More informationSensor Control Panel
USER S MANUAL PU SENS 01 Sensor Control Panel V55-6EN-03(SENS).indd 1 18.08.2015 10:37:16 2 PU SENS 01 CONTENTS Safety Requirements 2 Main Technical Data 3 Control Panel Mounting 3 Control Panel Operation
More informationBACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller
BACnet Points for Single Compressor Water-to- Air Heat Pumps With Hot Gas Reheat Utilizing the FX10 Controller All volatile (Output) type points will revert to the uncommanded values after a power interruption.
More informationT600MEP-2 Programmable Economizer Thermostat
Installation Instructions Issue Date January 19, 2005 T600MEP-2 Programmable Economizer Thermostat Application The T600MEP-2 is a programmable thermostat for control of single- or two-stage unitary rooftop
More informationAireLogic. Digital Control System. User Manual
AireLogic Digital Control System User Manual Rev. 04-11-13 1 Table of Contents OVERVIEW... 6 NETWORKING... 8 AIRELOGIC DEFAULT SETTINGS... 8 UNIT OPERATING MODES... 9 MRT Controls:... 9 UNIT OFF MODE...
More informationECL Comfort 110, application 116
Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /
More informationOven Control System Operation - Ver 2.8
Version 2.8 - Pg:1 - Ver 2.8 This operation manual contains important information about your oven. All operators should review this manual before operating the oven. When you turn on the switch, the control
More informationB-40/B-41 Modulating Temperature Controller
INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N
More informationProduct Manual SZ1022/SZ1031/SZ1035/
Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed
More informationTEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072
TEC Controller Heating & Cooling Heat Pump with Internal Reversing Valve & Mixed Air Control, Application 2072 Application Note 140-1042 Building Technologies Table of Contents Overview... 4 Hardware
More informationInstallation Guide. ECL Comfort 210, application A Table of Contents
1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................
More informationSiemens RDY2000BN. Start Up Guide
Siemens RDY2000BN Start Up Guide Answers for infrastructure and cities. What this slide set is about This is a start up guide for the RDY2000BN BACnet Commercial Thermostat. This procedure show how to
More informationDHW / Setpoint Demand WWSD Modulation Boiler Output (x10,000 BTU/hr) External Input Signal Offset / Priority Override
Date Code - Data rochure oiler Control 265 D 265 10/03 The tekmar oiler Control 265 can control the supply water temperature on up to three modulating boilers based on outdoor temperature or setpoint requirements.
More informationT60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability
T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability Product Bulletin T601DFH-4, T602DFH-4, T603DFH-4, T604DFH-4, T605DFH-4, T601DFH-4+PIR, T602DFH-4+PIR,
More informationInstaller Manual KNX Touchscreen Thermostat
Installer Manual 02952 KNX Touchscreen Thermostat Index GENERAL FEATURES AND FUNCTIONALITY from page 5 ETS PARAMETERS AND COMMUNICATION OBJECTS from page 7 COMMUNICATION OBJECTS GENERAL FEATURES AND FUNCTIONALITY
More informationProduct Manual SZ1009
Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional
More informationRooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers
Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide VT8600 Series Room Controllers TABLE OF CONTENTS Overview 2 VT86X0U5X00B 2 heating / 2 Cooling for Rooftop unit and Indoor air quality 3
More informationReference Guide for Microprocessor Controller
Document 483232 Microprocessor Controller for Energy Recovery Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting
More informationSpartan Peripheral Devices. TE 256S Thermostat Applications
Spartan Peripheral Devices TE 256S Thermostat Applications Revision 1.0 TE 256S modulating Proportional plus Integral controller is specifically designed to control heating and cooling with 6 port modulating
More informationATC32U03 igate Communicating, Programmable Thermostat
ATC32U03 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 11/3/17 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature
More informationT7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS
Contents T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS OWNER S GUIDE Features... 2 Settings... 3 Programming... 5 63-2638 FEATURES Typically used in buildings (including: restaurants,
More informationATC32U01 igate Communicating, Programmable Thermostat
ATC32U01 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 7/2/12 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature
More informationWater Source Heat Pump Module Technical Guide
Factory Packaged Controls Tulsa Water Source Heat Pump Module WSHP WSHP Protection Module Module Orion No.: OE334-23-WPM-A NON-DIGITAL COMPRESSORS #1 THRU #4 +5V SUCT. +5V SUCTION PR. SENSOR PRES PRES
More informationMicroTech Self-Contained Air Conditioning System
Open Protocol Data Information Packet Version 2.3 Group: Controls Date: October 1999 MicroTech Self-Contained Air Conditioning System Open Protocol Data Communications t 2002 McQuay International - C O
More informationRetrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems
IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended
More informationRVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating
2 526 Heating Controller including dhw heating Series C RVL472 Multifunctional heating controller for use in residential and non-residential buildings Suited for: Heating zone control with or without room
More informationUser Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs
User Manual Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs Models 89800-03 and 89800-04 THE STANDARD IN PRECISION MEASUREMENT Table of Contents
More informationGuide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:
Date: 05/21/2001 Time: 02:57:44 PM Job Name: EarthWise VAV Terminal Units Full Spec Location: AnyTown, Earth Prepared by: Phone Number: Prepared for: Guide Spec Summary Option List SINGLE & DUAL DUCT UNIT
More informationGeneral The Dryer Programmer for Windows Computers
Published Manual Number: MQYDSB01 Specified Date: 20131120 As-of Date: 20131120 Access Date: 20131120 Depth: Detail Custom: n/a Applicability: YDS Language Code: ENG01, Purpose: publication, Format: 1colA
More informationApplication Guide siemens.com/thermostats
RDG/RDF room thermostats Application Guide siemens.com/thermostats Application overview 2-pipe el. heater or radiator 4-pipe with el. heater Chilled/ heated ceiling Chilled/heated ceiling with el. heater
More informationCLEVER CONTROL - Version: V6.0
CLEVER CONTROL - Version: V6.0 INSTALLATION AND FUNCTIONING MANUAL USER AND BASIC VERSION Please, read these instructions carefully before attempting installation Using a wrong tailor made RJ45 or RJ11
More informationER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller
PB_ER65-DRW_ 202 ER65-DRW Controller Heating Applications Product Bulletin The controller is a digital device for domestic or residential heating units. It covers water and air heating applications. All-in-one
More informationINSTALLATION & USER MANUAL
INSTALLATION & USER MANUAL HC Digital Automatic Humidistat (Y3760) CONTROLS 506808-01 3/2016 Supersedes 6/2011 picture goes here THIS MANUAL MUST BE LEFT WITH THE HOMEOWNER FOR FUTURE REFERENCE NOTICE
More informationComfortSense 7500 Commercial Thermostat. User Guide
ComfortSense 7500 Commercial Thermostat User Guide 507505-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...2 Home Screen Information...3 Operating Mode Selection...5
More informationNEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80
NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80 Carrier Software Systems Carrier Corporation Syracuse, New York rev October 10, 2013 Copyright 2013 Carrier Corporation, All Rights Reserved Page
More informationC62. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort C62. User's Guide. Installer's Guide *VIKME102* *087R8091* *087R8091* *VIKME102*
User's Guide VI.KM.E1.02 2005.09 C62 *VIKME102* *087R8091* www.danfoss.com ECL Comfort User's Guide ECL Comfort Installer's Guide www.danfoss.com *087R8091* *VIKME102* Double mixing controller C62 VI.KM.E1.02
More informationInstallation & Operation Manual
Boiler Control 275 Installation & Operation Manual Multi-Staging D 275 01/12 Replaces:03/09 The Boiler Control 275 is designed to stage up to four condensing or non-condensing, modulating or on-off boilers
More informationTempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications
Instruction Manual Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications Manual PCT30006, Revision 9/20/2016 The PCT30006 control enclosure incorporates
More informationHumidity Controller Specification and Installation Instructions. Model HRO20
Model Description The Humidity Controller is an advanced application to control relative humidity for general purpose applications. They are specially designed to control humidifiers and dehumidification
More informationReference Guide for Microprocessor Controller
Document 482641 Microprocessor Controller for Make-Up Air Products Reference Guide for Microprocessor Controller Please read and save these instructions for future reference. Read carefully before attempting
More informationCM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B
2 CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B CAUTION CAUTION - ONLY TRAINED, QUALIFIED PERSONNEL SHOULD INSTALL AND/OR SERVICE CLIMATEMASTER EQUIPMENT. SERIOUS
More informationMulti Boiler Guide. Kit #
Multi Boiler Guide Kit # 550002186 Technical Support @ 800-325-5479 Phone: (315) 797-1310 Fax: (866) 432-7329 e-mail: info@ecrinternational.com web site: www.ecrinternational.com Information and specifications
More informationNatural Ventilation Controller with 24vDC drive NVC-1204
Natural Ventilation Controller with 24vDC drive NVC-1204 BACnet Enabled C-036 08/11 FEATURES > 24V DC supply > Native BACnet communications > Master/Slave grouping (shared information) > 3 x 0-10V outputs
More information