1 GAZ - FIRED AIR HEATERS TECHNICAL NOTICE AND INSTRUCTIONS FOR MONTAGE ACGH 16/20/28/35/45/55/75/95 ACGC 20/28/35/45/55/75/95 ACGV 26/28/36/45/55/75/ BO3933 DTC AT FR 1

2 TABLE OF CONTENTS Section No. Sections Pages 1 GENERAL RECOMMENDATIONS Description of devices Operation Instruction for use Operating Safety Cut-off Guarantee 3 2 TECHNICAL SPECIFICATIONS OF AT GAS UNIT HEATERS Performance of ACGH helical gas unit heaters Performance of ACGV gas unit-destratificators Performance of ACGC centrifugal gas unit heaters 8-9 Assembly of the fan casing for ACGC 9 3 RETENTION OF UNIT HEATERS Adjustable rotation console for ACGH 16/20/26/28/35/36/45/ Rotation console for IPN, adjustable for ACGH 16/20/26/28/35/36/45/ Adjustable wall-mounted console for ACGH75/ Adjustable wall-mounted console for ACGC 11 4 ELECTRICAL WIRING Electrical schematic of unit heaters Electrical schematic of ACG75C centrifugal unit heaters Electrical schematic of modulating unit heaters and ACGV Basic connection schematic with pilot wire thermostat Basic connection schematic with individual thermostat 14 5 CONNECTION OF THE EVACUATION CONDUITS Evacuation conduit accessories for ACGH 20/28/ Evacuation conduit accessories for ACGH 45/55/75/ Connecting to the unit heater Connection of wall-mounted concentric cup - C12 for ACGH and ACGC Connection of roof mounted concentric cup - C32 - for ACGH and ACGC Connection of roof outlet - B22 for ACGH, ACGC and ACGV Connection of roof mounted concentric cup - C32 for ACGV 17 6 GAS CIRCUIT Changing gas Valve adjusting table first speed Adjusting table modulating valve 19 7 GAS CONNECTION Connection of unit heaters 20 8 COMMISSIONING THE GAS UNIT HEATERS Operating principle Bill of material 21 9 MAINTENANCE RECOMMENDATIONS FOR USER TROUBLE SHOOTING 23 NOTICE The range of products which is the subject of these instructions has successfully undergone numerous tests and inspections defined by the European Gas Directive : mechanical and electrical safety, reliability, combustion hygiene, etc. In addition to the technical requirements that it requires, the CE mark constitutes official recognition concerning the quality of design, manufacture and performance of this device. Its lifetime and its performance will be at optimum level if its use and its maintenance is carried out in accordance with the rules of the trade and the current requirements. 2

3 1-GENERAL RECOMMENDATIONS These devices can only be installed in rooms which are sufficiently ventilated, unless the device has a sealed connection. The correct operation of the unit heater depends on correct installation and commissioning. If these rules are not observed, the manufacturer will immediately be exempt from any liability. The installation and maintenance must be carried out in conformity with the regulation text and the current rules of the trade and by qualified personnel. DO NOT INSTAL THE GAS UNIT HEATER IN: - Rooms which have a risk of explosion, - Rooms containing chlorinated combination vapours, - Rooms with a high content of combustible dust, - Very humid rooms (electrical danger). - Domestic rooms. RECOMMENDATIONS FOR INSTALLATION : - Provide a minimum distance of 200 mm at the rear of the device fan side. - Provide sufficient clearance for opening the burner door. - The unit heater must be placed at a minimum of 200 mm from the ceiling and 2000 mm from the floor. After verifying that the assembly respects the requirements of these instructions, it is the responsibility of the installer: 1) to inform the user: -that he or she cannot carry out any modifications him or herself to the design of the devices and the manner in which the installation is executed ; The slightest modification (exchange, withdrawal...) of safety components or parts which influence the output of the device or combustion hygiene will automatically entail the withdrawal of the CE mark for the device. -that it is essential to carry out the required cleaning and maintenance operations. An annual preventive maintenance operation is obligatory. 2) to give the user these instructions AIRCALO, with the agreement of the organisation which has notified the CE marking, reserves the right to update these technical instructions. Only the instructions which accompany the product at its shipment can be considered as contractual; keep the instructions carefully near the device Description of the device Operation The ACG gas unit heater is a generator of independent hot air, operating with natural gas and propane; it is in conformity with the EEC European Directive 90/396 applicable to gas apparatus. It constitutes a "direct" heating gas system ; it is a device for the production and the emission of heat without an intermediate vehicular fluid. For the whole range described in these instructions, the combustion products are ejected out of the room using an extractor. The combustible air is taken from the ambient environment or from outside. These devices can be connected using a cup connection vertically or horizontally, or with a chimney outlet. ACG gas unit heaters operate using the various gases indicated on their manufacturer s plates in conformity with the European Directive Instructions for user - Please read the instructions in this manual carefully for the operation and maintenance of this device. - Have maintenance carried out at least once a year by qualified personnel. The frequency of the maintenance operations depends on the environment in which the device is installed. In particular, more regular inspection must be carried out in dusty locations. - Regularly verify that there is no damage to the device, to the chimney or to the gas conduit. - Regularly verify that the air openings in the building and around the device are not obstructed. - Verify that the hot air can circulate normally in the room, and therefore that there is no obstacle in front of the blowing outlet of the device, and that the grille is indeed open Operation When heat is required, the burner ignites using the ignition electrode then the pan starts to run, the hot air is then blown into the room. When the setting temperature is attained, the burner is extinguished. The fan continues to turn for about one minute, until it has eliminated the heat remaining in the heat exchanger. 3

4 1.4. Safety - If there is no flame, this is detected by an ionisation sensor and the gas vales are immediately closed. - The thermal protection of the heat exchanger is ensured by two thermostats. The first, which is automatically reset, protects against insufficient air flow (obstructions, fan failure). The second, which has to be manually reset, is set to a higher threshold than the first one. It protects the device against high excess heating due to an operating problem or unsuitable use. If the operation shows any difficulty whatsoever, please contact us. Make sure that the device can be supplied normally with combustion air at atmospheric pressure (any modification of the building after the installation of the device must be carried out taking this into account). Excessively low pressure inside the room can harm the correct functioning of the device by depriving it of the air necessary for combustion. The lowest temperature for device functioning is - 10 C Cut-off - To cut the device off during a short period, it is necessary only to cut off the thermostatic line (this means turning the thermostat to a minimum setting point or turning off the thermostat switch). - For a prolonged stoppage, switch off the thermostatic line, close the gas valve and cut off the electrical supply, taking care to wait for the fan to stop turning. Gas and electricity must only be cut off in case of emergency or for long stoppage periods Guarantee (An extract from the general sales condition, section GUARANTEE) : The devices must be installed by qualified professional personnel, in conformity with current regulations, with the rules of the trade and the instructions which are found in our assembly instructions. The devices are guaranteed 1 year against any manufacturing failure and 5 years for the heat exchangers as long as they are operated using the normal user instructions. The guarantee takes effect on the date of manufacture by our company and on condition that the guarantee form is returned completed and signed. We decline any responsibility and no guarantee will be applicable in case of negligence of the customer, of defective installation, or installation which is unsuitable or not in conformity with current standards. Only defects in manufacture or raw materials are concerned. The guarantee is limited to the replacement of parts which are found to be defective by identical parts; costs of labour, travel, transport and excess to the equipment are excluded. Any replacement which takes place during the guarantee period, even if it necessitates the immobilisation of the equipment, cannot in any circumstances extend the duration of the guarantee. No damages or interest can be claimed for direct or indirect prejudice. It is imperative that the installation, maintenance and any trouble shooting is carried out by qualified professional personnel. Any servicing must be carried out using the rules of the trade and therefore in accordance with current standards and the indications supplied by our company in this manual. The correct operation of the device depends on correct installation and commissioning. Non-respect of the rules will immediately cause our company to refuse any liability. The devices must only be equipped with the original smoke system and air intake. In case of use of accessories other than those proposed by our company, check that they are indeed compatible with the devices. Our company will not be responsible for any damage or prejudice resulting from improper use of the devices. The engineering studies office, the installer and the user are solely responsible for being aware of and respecting the legal provisions as well as the standards which are inherent in the design, location, installation, commissioning and maintenance. Damage due to the following causes cannot be taken into consideration or covered by our guarantee : - caused by external phenomena - caused by negligence on the part of the user - caused by non-respect of the settings in our technical manual - due to immediate or later damage caused by incorrect handling during transport, or incorrect manoeuvres - caused by the use of accessories other than the original ones - caused by defects in maintenance and monitoring. Whether this concerns the purchaser or any other person, our company cannot under any circumstances be held responsible for bodily injury or material damage of any type whatsoever, which could be caused by our products or which would be the direct or indirect consequence of the use of the said products. 4

5 2- TECHNICAL SPECIFICATIONS OF ACG UNIT HEATERS Axial Fan. ACGH Model The ACGH unit heaters are equipped with an axial fan. They are intended for direct blowing and are equipped, as standard, with a double deflection grille. 2-1 Performance of ACGH helical gas unit heaters TYPES ACG16H ACG20H ACG26H ACG28H ACG35H ACG36H ACG45H ACG55H ACG75H ACG95H Calorific output kw Usable power kw ,5 31, , ,4 84 Efficiency % > 91 >91 >91 > 91 > 91 >91 > 91 > 91 > 91 > 91 No of fans Rotation speed Rpm Air flow at 15 C Air flow at 50 C m 3 /h Delta T of air C Reach of air jet m Gas flow at 15 C Natural G20 20 mbar m 3 / h 1.88 m 3 / 2.22 m 3 / h 2.46 m 3 / 2.75 m 3 / h 3.06 m 3 / 2.96 m 3 / h 3.29 m 3 / 3.70 m 3 / h 4.11 m 3 / 3.81 m 3 / h 4.23 m 3 / 4.76 m 3 / h 5.28 m 3 / 5.82 m 3 / h 6.43 m 3 / 7.40 m 3 / h 8.22 m 3 / Smoke diameter mm / / / / / / 125 Air inlet mm Supply voltage Mono-phase 230 Volts / 50 Hz - IP42 Electrical power VA Weight kg Noise level (fan) dba m 3 / h 11.1 Overall dimensions of ACGH models Connection for 20/28/35 Smoke Air Gas Connection for 45/55/75/95 Smoke Air Gas 5 A B C Ø F Ø Air Ø G ACG16H / 125 1/2 ACG20H / 125 1/2 ACG26H / 125 1/2 ACG28H / 125 1/2 ACG35H / 125 1/2 ACG36H / 125 1/2 ACG45H /2 ACG55H /2 ACG75H /4 ACG95H /4

6 Vertical model ACGV ACGV destratificators are equipped with an axial fan. They are intended for direct vertical blowing and are equipped with a double deflection grille. They are specially suitable for direct blowing into corridors and offer the special feature of both heating and destratifying. 2-2 Performance of the ACGV gas destratificator TYPES ACG26V ACG28V ACG36V ACG45V ACG55V ACG75V ACG95V Calorific output kw Usable power kw , ,4 84 Efficiency % >91 >91 >91 > 91 > 91 > 91 > 91 No of fans Rotation speed Rpm Air flow at 15 C Air flow at 50 C m 3 /h Delta T of air C Reach of air jet m See page 7 Height of installation m 4/5 4/5 4/6 5/8 5/10 6/12 6/12 Gas flow at 15 C Natural G20 Groningue G25 Propane G31 20 mbar 25 mbar 37 mbar 2.75 m 3 / h 3.06 m 3 / h 2.03 kg/h 2.96 m 3 / h 3.29 m 3 / h 2.18 kg/h 3.81 m 3 / h 4.23 m 3 / h 2.81 kg/h 4.76 m 3 / h 5.28 m 3 / h 3.51 kg/h 5.82 m 3 / h 6.43 m 3 / h 4.30 kg/h 7.40 m 3 / h 8.22 m 3 / h 5.46 kg/h 10.0 m 3 / h 11.1 m 3 / h 7.40 kg/h Smoke diameter mm / / / 125 Air input diameter mm Supply voltage Monophase 230 Volts / 50 Hz - IP42 Electrical power VA Weight kg Sound level (fan) At 5 m in free field dba ACGV model operating principle Destratificators in the ACGV range incorporate two functions : Heating, operating identically to that of a gas unit heater. Destratification, the fan operating in accordance with the temperature of the ambient air. CAUTION : When determining the equipment to be used, supplement the destratification volume by non-heating destratificators (see photo opposite), to respect the minimum recommended rate of agitation*. 6

7 Overall dimensions of the ACGV models I I Types ACG26V ACG28V ACG36V ACG45V ACG55V ACG75V ACG95V A B C D E H I Ø F /125 80/125 80/ / 100 Ø Air Ø G (gas) 1/2 1/2 1/2 1/2 1/2 3/4 3/4 Installation height of ACGV models The ACGV models are retained at their upper part by four tightened M8 nuts. Blowing is vertical towards the ground and the installation height must not be lower or higher than that recommended. To get the best performance from the ACGV gas destratificators, we recommend you to respect the following heights. Types ACG26V ACG36V ACG55V ACG75V ACG95V L1 (min) m 0,45 0,45 0,45 0,50 0,60 L2 (min) m L3 (min) m H : Height (mini/ max) P : Max air reach m 4 / 5 4 / 6 5 / 8 6 / 12 6 / 12 m P = 16- H P = 20- H P = 25- H P = 28- H P = 30- H 7

8 Centrifugal model. ACGC ACGC unit heaters are equipped with a centrifugal fan and are supplied as standard with an air case (assembly p. 9). They are intended for blowing or taking air from a sheath network. Mixture dampers and a filter can be incorporated on the air case. 2-3 Performance of ACGC centrifugal gas unit heaters TYPES ACG20C ACG28C ACG35C ACG45C ACG55C ACG75C Calorific output kw Useable power kw Efficiency % > 91 > 91 > 91 > 91 > 91 > 91 Type of fan BD25/25 M6 BD28/28 M6 BD28/28 M6 BD33/33 M6 BD33/33 M6 BD33/33 M6 Motor electrical power kw - Hp / / / Motor rotation speed Rpm Motor coupling Speed MV GV PV MV Flow/pressure curve N Air flow at 15 C Air flow at 50 C m 3 /h Delta T of air C Pressure of available Pa ACG95C > 91 BD33/33 M6 2 (0.75-1) 750 PV Gas flow at 15 C Natural G20 Groningue G25 Propane G31 20 mbar 25 mbar 37 mbar 2.22 m 3 / h 2.46 m 3 / h 1.64 kg / h 2.96 m 3 / h 3.29 m 3 / h 2.18 kg / h 3.70 m 3 / h 4.11 m 3 / h 2.73 kg / h 4.76 m 3 / h 5.28 m 3 / h 3.51 kg / h 5.82 m 3 / h 6.43 m 3 / h 4.30 kg / h 7.40 m 3 / h 8.22 m 3 / h 5.46 kg / h m 3 / h 11.1 m 3 / h 7.4 kg / h Smoke diameter mm 80 / / / Air input diameter mm Supply voltage Mono-phase 230 Volts / 50 Hz - IP42 Electrical power VA Weight kg Assembly of the fan case for ACGC Preparation for assembly : Disassemble the side panels (1) and (2) of 2 the fan case A 3 Assembly of A and B : Assemble the fan case A on the thermal case B, using the 4 BTR M8 (3) screws 1 provided. B Caution : Position the fan supply electrical connector (5) at the supply cable end (7), See photo (I) above. Electrical connection : Connect the fan connector (5) with the thermal module connector (6), see photo (II) above. I II A Fan case B Thermal case Reinstall the side panels (1) and (2) using the hardware supplied. 8

9 Flow/pressure curves Pa * * 2 3* Pa M 3 /h ACG20C t 41 C t 36 C t 32 C t 29 C ACG28C t 42 C t 37 C t 34 C ACG35C t 36 C t 33 C t 31 C 7* M 3 /h ACG45C t 35 C t 33 C t 31 C t 30 C ACG55C t 37 C t 35 C t 33 C t 32 C ACG75C t 40 C t 38 C t 36 C t 35 C t 34 C * Flow/pressure curves with filter, consult us for this application. Maximum dimension of the ACGC models and optional accessories A A1 A2 A3 A4 B B1 H L L1 L2 L3 P Ø F Ø Air Ø AT / 125 1/2 AT / 125 1/2 AT / 125 1/2 AT /2 AT /2 AT /4 AT /4 9

10 3 MOUNTING OF UNIT HEATERS (See instructions supplied with the consoles) 3-1 Installation recommandations For good functionnning and the security of devices it s necessary to respect the munimum installation distances (see the schema below). 200 mini 700 mini 200 mini 200 mini 2000 mini 2000 mini 200 mini 200 mini 200 mini 3-2 Rotating console for IPN adjustable for ACGH 16/20/26/28/35/36/45/55 C Caution: make sure of the strength of the bracket ACG16 H ACG20H ACG26H ACG28H ACG35H ACG36H ACG45H ACG55H Connection B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 Dim A (mm) Dim B (mm) Dim C (mm) The CORAT kit is a wall fixing console for gas unit heaters ACGH 16/20/26/28/35/36/45/55. Assembly : See instructions supplied with the consoles. Attention: The CORAT kit can t be used with ACGH 75/95. 10

11 3-3 Wall mounted console for ACGH 16/20/26/28/35/36/45/55/75/95. Caution: make sure that the bracket is strong enough ACG75H ACG95H Connection B22 C32 B22 C32 Dim A (mm) Dim B (mm) Dim C (mm) Dim D (mm) The COAT kit is a wall-fixing console for gas unit heaters ACGH 16/20/26/28/35/36/45/55/75/95. Assembly: See instructions supplied with the consoles. 3-4 Wall-mounted console for ACGC 20/28/35/45/55/75. CAUTION : this console is not suitable for assembly with dampers or filter Caution: make sure that the bracket is strong enough ACG20C ACG28C ACG35C ACG45C ACG55C ACG75C Connection B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 B22 C32 Dim A (mm) Dim B (mm) Dim C (mm) Dim D (mm) The COAT kit is a wall-mounted console for gas unit heaters ACGC 20/28/35/45/55/75. Attention: COAT kit can t be used for ACGC 95. Assembly : See instructions supplied with the console. 11

12 4- ELECTRICAL WIRING 4-1 Electrical schematics of the gas heaters ACGH ACGC Phase/ brown Neutral/ blue Earth/ green- yellow Pilot/ black 4-2 Electrical schematics of centrifugal gas air heaters ACG75 Phase/ brown Neutral/ blue Earth/ green- yellow Pilot/ black 12

13 4-3 Electrical schematics for the 2 stages gas air heaters and ACGV Phase/ brown Neutral/ blue Earth/ green- yellow Pilot/ black TV RFP Limit Fan Reg Mod CC Blowing fan Pilot wire receiver Excess heat airstat with manual reset Fan triggering airstat Burner regulation airstat Burner modulator airstat (modulation option) Inspection box MVE PA SI EA MOD EVG TI Smoke extractor Burner air pressure switch Ionisation sensor Ignition electrode Gas modulating valve (2 speed option) Gas solenoid valve Isolation transformer Under normal operation, never stop the device by cutting off the electrical power. Wait for the fan to stop Pilot wire receiver card Burner connector Supply connector Fan connection Burner defect Burner reset 13

14 4-4 Basic connection schematic with pilot wire thermostat Connection of the unit heater :A : Neutral (blue) - B: Phase (brown) - D: pilot wire (black) - C: Earth ( green/ 1 - Switch off proximity items 2 - Unit heaters 4 Regulation and remote control panel 3 - Remote signalling module BSAT4P TFP1 TFP2TE TFP3 - ACG gas unit heaters are equipped as standard with a receiver for pilot wire, which enables using a single conductor to carry the functions of the ambient thermostat, the forced ventilation and remote resetting. - Several models of thermostat (4) are available. The use of these thermostats will provide you with supplementary functions such as remote resetting and forced ventilation. - The remote signalling module is not obligatory, in case of use, disconnect the connector supplied on the unit heater receiving card and replace it by the signalling module cable. Provide a sufficient length of cable for the number of devices on the line. The electrical connection of the devices must be in conformity with the regulations in force in the country concerned. Caution : 6 unit heaters maximum per TFP1 14

15 4-5 Basic connection schematic using individual thermostat REG110 REG111 REG112 Model : REG110 Individual controller without thermostat. On/off fan switch and remote resetting. Signalling indicator lamps : on, burner defect and excess heat. REG110 Model : REG111 Individual controller with an ambient thermostat with remote resetting. On/off fan switch and remote resetting. Signalling indicator lamps : on, burner defect REG111 REG112 Model : REG112 Individual controller without thermostat. Ambient thermostat with on/off fan switch and remote resetting. Clock programmable. Connecting the unit heater : A : Neutral (blue) - B: Phase (brown) - C: Earth ( green/yellow) ACG gas unit heaters are equipped as standard with a receiver which enables the AIRCALO regulator to be connected directly. Several models of individual thermostats are available: REG110, REG111, REG112, 1 Replace the four conductor supply cable with the three conductor cable supplied with the regulator. 2 Make a connection of individual thermostat REG according to the technical manual Individual control box supplied with the gas unit heaters. 3 Connect the 230 V AC power supply of the unit heater. 15

16 5 CONNECTING THE EVACUATION CONDUITS 5-1 Evacuation conduit accessories for ACG 20/28/35 1 Concentric telescopic extension 2 Concentric horizontal cup with finishing flap 3 Concentric roof cup Chimney outlet with moulding 5 Sealed length of 250/500/1000 mm 6 Concentric length of 500/1000 mm 7 Sealed elbow at 45 or Concentric elbow at 45 or 90 9 Flat flashing Tilted flashing with lead strip 5-2 Evacuation conduit accessories for ACG 45/55/75/95 2 Horizontal concentric cup with finishing flap 3 Concentric roof cup 4 Chimney outlet ( moulding not supplied ) Sealed length of 250/500/1000 mm 6 Concentric length of 500/1000 mm 7 Sealed elbow at Sealed elbow at 90 9 Flat flashing 10 Tilted flashing with lead strip Connecting to the unit heater Correct assembly Incorrect assembly α = 2 NO - Assembly of the smoke conduits must be carried out using a slope opposed to the device, α = 2 minimum. - The assembly of the conduits must be carried out so that no water can penetrate into the device, due to the electrical risk. For this purpose, please use a purge T-piece and a condensate recoverer, - Make sure not to damage the connector seals when assembling the conduits onto the device, check the sealing after assembly. - For greater lengths, it is essential to provide a condensate recoverer; this also applies to assemblies using cups. 16

17 5-4 Wall mounted concentric cup connection - C12 for ACGH and ACGC unit heaters ( I ) C12 - for ACGH and ACGC 20/28/35 The connections for fuel air inlet and evacuation of smoke are made horizontally at the outside of the building. The KC1280 kit consists of a terminal (1) and two rubber sliding clamps (2) which give a perfect finish. The connection is concentric with a diameter of 80/125 and connects directly onto the unit heater. Side (A) must be between 200 and 350 mm. A length (B) of 820 mm can only be obtained by using the cup. It is possible to shorten, extend or to deviate the cup outlet using accessories such as elbows, straight lengths of 0.5 m or 1 m or the telescopic extensions shown on page 15. CAUTION : The junctions between the tubes must be sealed and rigid. The total length of the circuit must not exceed 6 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. In the case of a greater length, please consult us. I II ( II ) C12 for ACGH and ACGC 45/55/75/95 The connections of the combustion air inlet and the smoke evacuation are to be horizontal, at the outside of the building. The KC12100 kit for ACG45 and KC12130 for ACG55/75/95 consists of two lengths of 250 mm (3) of a terminal (1) delivered with its bi-tubes/concentric transformer connector (4) and two wall mounted finishing plates (2). The diameters of the cups are 100/150 for model 45 and 130/200 for models 55/75/95. These kits are intended for a maximum wall thickness (A) of 270 mm for side B of 550 mm. It is possible to shorten, extend or to deviate the cup outlet using accessories such as elbows, straight lengths of 0.5 m or 1 m shown on page 15. CAUTION : The junctions between the tubes must be sealed and rigid. The total length of the circuit must not exceed 6 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. In case of greater lengths, please consult us. 5-5 Concentric roof cup connection - C32 for ACGH and ACGC unit heaters ( III ) C32 - for ACGH and ACGC 20/28/35 The connections for combustion air inlet and smoke evacuation are vertical through the roof to the outside of the building. The connection is concentric in diameter 80/125 and is connected directly onto the unit heater. The KC3280 kit consists of a roof terminal (1) and a concentric 90 elbow (2). Roof sealing will be carried out using a standard flashing or special flashing depending on the type of roof. The sliding moulding (7) supplied with the terminal enables the flashing to be covered for perfect sealing. The dimension (A) must be at least 250 mm. The terminal with its elbow enables a length (B) of 1195 mm to be obtained, dimension (C) 125 mm. It is possible to shorten, extend or to deviate the cup outlet using accessories such as elbows, straight lengths of 0.5 m or 1 m or telescopic extensions shown on page 15. CAUTION : The junctions between the tubes must be sealed and rigid. The total length of the circuit must not exceed 6 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. In the case of greater lengths, please consult us. III IV ( IV ) C32 - for ACGH and ACGC 45/55/75/95 Connections for the combustion air inlet and the smoke evaluation are made vertically through the roof to the outside of the building. Kit KC32100(ø 100/150 ) for ACG45-1 cup terminal (1) -2 x 90 elbows diameter 100 mm (2) -2 extensions length 250 mm (3) -1 transformation part (4) Kit KC32130 (ø 130/200 ) for ACG55/75/95-1 cup terminal (1) -2 x 90 elbows diameter 130 mm (2) -1 extension length 500 mm (3) -1 extension length 250 mm (3) -1 transformation part (4) It is possible to shorten, extend or to deviate the cup outlet using accessories such as elbows, straight lengths of 0.5 m or 1 m shown on page 15. CAUTION: The junctions between the tubes must be sealed and rigid. The total length of the circuit must not exceed 8 metres, taking into account the fact that an elbow of 90 or 45 corresponds to a length of 1 metre. In the case of greater lengths, please consult us. 17

18 5-6 Connection to outlet - B22 for ACGC, ACGH unit heaters and ACGV destratificator (V) B22 - for ACGH and ACGC 20/28/35/45/55/75/95 The combustion air is taken directly in the room and the evacuation of the smoke is made vertically through the roof. The kits KB2280 (ø80), KB22100 (ø100) and KB22130 (ø130) consists of: a T-piece with sealed plug (2), length one metre (1), and a roof terminal (3). The kit KB2280 is delivered with a sliding moulding (7). The minimum height of the roof outlet must be the same as the ridge of the roof. The kits for 20/28/35/45 provide for a dimension (B) of 2150 mm, dimension (C) 125 mm. For the 55/75/95 a dimension (B) of 2150 mm, dimension (C) 135 mm. It is possible to extend or deviate the roof outlet using accessories such as elbows and straight lengths of 0.5 m or 1 m shown on page 15. Provide sufficient ventilation. The required new air supply must be at least 100 m 3 /h per unit heater. CAUTION : The section of the smoke conduits must be at least equal to the outlet diameter. Smoke evacuation can only be vertical or at a maximum of 45. The total length of the circuit must not exceed 8 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. A double wall conduit must be provided if the part outside the building is over 2 metres. V VI (VI) B22 - for ACGV 28/35/55/75/95 The combustion air is taken directly in the room and smoke evacuation is made vertically through the roof. The kits KB2280V (ø 80) and KB22130V (ø 130) consists of a sealed elbow at 90 (1), a sealed length 0.5 m (2), a T-piece with sealed plug (3), two lengths of one metre (4) and a chimney cap (5). The kit KB2280V is supplied with a sliding moulding (6). The roof outlet must be as a minimum the same as the height of the roof ridge. Dimension (B) of kits KB2280V and KB22130V is 2150 mm, dimension (C) 630 mm for ACG28/35V and dimension (C) 750 mm for ACG55/75/95V. It is possible to extend or to deviate the roof outlet using accessories such as elbows and straight lengths of 0.5 m or 1 m shown on page 15. Provide sufficient ventilation. The required new air supply must be at least 100 m 3 /h per unit heater. CAUTION : The section of the smoke conduits must be at least equal to the outlet diameter. The smoke evacuation can only be vertical or at a maximum of 45. The total length of the circuit must not exceed 8 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. A double wall conduit must be provided if the part outside the building is over 2 metres. 5-7 Concentric roof cup connection - C32 for ACGV destratificator (VII) C32 - for ACGV 28/35 The connections for combustion air intake and smoke evacuation are made vertically through the roof at the outside of the building. The connection on the device is concentric at Ø 80/125. The kit KC3280V (ø 80/125) consists of a roof terminal (1) and a condensate recoverer (3). The roof sealing must be used using standard flashing or special flashing depending on the type of roof. The sliding moulding (5) supplied with terminal can be used to cover the flashing for perfect sealing. The exterior part must be at least 250 mm, dimension (A), the terminal provides for a total length of 1095 mm, dimension (B). It is possible to shorten, lengthen or to deviate the cup outlet using accessories such as elbows, straight lengths of 0.5 m or 1 m or the telescopic extensions shown on page 15. CAUTION : The junction between the tubes must be sealed and rigid. The total length of the circuit must not exceed 6 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. In the case of greater lengths, please consult us. 18 VII VIII (VIII) C32 - for ACGV 55/75/95 The connections for combustion air intake and smoke evaculation are made vertically through the roof to the outside of the building. The connection on the device uses bi-tubes Ø130 mm. The kit KC32130V (ø 130/200) consists of a roof terminal (1), of a condensate recoverer (2) and of a sealed length of 250 mm (3). Roof sealing is carried out using a standard flushing or special flashing depending on the type of roof. The fixed moulding mounted on the terminal can be used to cover the flashing (minimum dimension of 201 mm maximum dimension of 208 mm), for perfect sealing. The exterior part of the terminal 955 mm dimension (A), interior part 1060 mm dimension (B). It is possible to shorten, extend or to deviate the cup outlet using accessories such as elbows, straight lengths of 0.5 m or 1 m or telescopic extensions shown on page 15. CAUTION : The junction between the tubes must be sealed and rigid. The total length of the circuit must not exceed 8 metres, taking into account that an elbow of 90 or 45 corresponds to a length of 1 metre. In the case of greater lengths, please consult us.

19 6- GAS CIRCUIT 6-1 Changing gas The unit heaters are equipped with atmospheric gas torch burners, permitting the use of Natural gas G20, Natural gas G25 and Propane. The combustion ports are engineered so as to ensure very good stability of the flame without separation or return towards the injectors. THE SERVICE VISITS MUST BE CARRIED OUT BY A QUALIFIED PROFESSIONAL PERSON. Changing the gas is carried out in the following manner: 1- Disconnect the electrical supply connector and close the gas inlet. 2- Unscrew the gas line fixing nut (Item 1) on the gas valve and also the three screws (Item 2) which retain the injector ramp on the burner block. 3 Change the injectors (see adjustment table). 4 Screw in the new injectors (Item 3) changing the seals (Item 4) and making sure concerning sealing. The injectors must be installed dry. 5 Reassemble the ramp and connect the gas line to the gas valve, replacing the seal, make sure during assembly not to forget, or damage the seal. 6 Check for sealing after assembly. 7 Adjust the gas ramp pressure on the regulator CAUTION : This operation must be done with the gas and electricity supplies cut off. The adjustment of the gas pressure is made with the burner running Adjusting the gas pressure is done in the following manner: 1 Open the solenoid valve pressure regulating protection screw. 2- Unscrew the pressure test point, connect the pressure gauge (5) 2- Adjust the ramp pressure (6), in accordance with the adjusting table After adjustment, do not forget to put the protective screw back in place and to close the pressure test point. 5 6 Check for sealing after making the adjustment. 19

20 6-2 Valve adjustment table single speed Types Regulator pressure Adjustment for G20 Adjustment for G25 Adjustment for G31 Gas ramp injectors Washer extractor Regulator pressure Gas ramp injectors Washer extractor Regulator pressure Gas ramp injectors Washer extractor ACG16 9 mbar 4 x AL mbar 4 x AL mbar 4 x AL ACG20 9 mbar 5 x AL mbar 5 x AL mbar 5 x AL ACG mbar 6 x AL mbar 6 x AL mbar 6 x AL ACG28 9 mbar 5 x AL mbar 5 x AL mbar 5 x AL ACG35 9 mbar 6 x AL mbar 6 x AL mbar 6 x AL ACG mbar 8 x AL mbar 8 x AL mbar 8 x AL ACG45 9 mbar 8 x AL 2.20 none 12 mbar 8 x AL 2.20 none 25 mbar 8 x AL 1.30 none ACG55 9 mbar 10 x AL 2.20 none 12 mbar 10 x AL 2.20 none 25 mbar 10 x AL 1.30 none ACG75 9 mbar 12 x AL 2.20 none 12 mbar 12 x AL 2.20 none 25 mbar 12 x AL 1.30 none ACG95 9 mbar 16 x AL mbar 16 x AL mbar 16 x AL Gas solenoid valve 20/70 kw Gas solenoid valve 90 kw Regulator pressure adjustment Regulator pressure adjustment Gas Gas Pressure test point Pressure test point 6-3 Modulating valve adjustment table Adjustment for G20 Adjustment for G25 Adjustment for G31 Types Low speed ACG16 6 mbar ACG20 6 mbar ACG26 6 mbar ACG28 6 mbar ACG35 6 mbar ACG36 6 mbar ACG45 6 mbar ACG55 6 mbar ACG75 6 mbar ACG95 6 mbar Regulator pressure High speed 9 mbar 9 mbar 10.4 mbar 9 mbar 9 mbar 10.4 mbar 9 mbar 9 mbar 9 mbar 9 mbar Gas ramp injectors 4 x AL x AL x AL x AL x AL x AL x AL xAL xAL xAL 2.20 Extractor washer Low speed Regulator pressure High speed 40 7 mbar 12 mbar 40 7 mbar 12 mbar 40 7 mbar 13.8 mbar 27 7 mbar 12 mbar 30 7 mbar 12 mbar 40 7 mbar none none none Gas solenoid valve 20 to 75 kw 13.8 mbar 7 mbar 12 mbar 7 mbar 12 mbar 7 mbar 12 mbar 27 7 mbar 12 mbar 8 Gas ramp injectors 7 4 x AL x AL x AL x AL x AL x AL x AL xAL xAL xAL 2.20 Extractor washer Low speed Regulator pressure High speed Gas ramp injectors Extractor washer mbar 25 mbar 4 x AL mbar 25 mbar 5 x AL mbar 29 mbar 6 x AL mbar 25 mbar 5 x AL mbar 25 mbar 6 x AL mbar 29 mbar 8 x AL none 13 mbar 25 mbar 8 x AL 1.30 none none 13 mbar 25 mbar 10xAL 1.30 none none 13 mbar 25 mbar 12xAL 1.30 none mbar 25 mbar 16xAL Gas solenoid valve 90 kw 8 High speed Gas 7 Low speed 8 High speed 7 Low speed 20 Pressure test point

21 7- GAS CONNECTION A precise engineering study must be carried out on the diameters of the piping depending on the nature of the gas flow and the length of the piping. Make sure that the pressure drops in the piping do not exceed 5 % of the supply pressure. The gas connections must be carried out in conformity with the requirements concerning interior installations regardless of the type of gas. 7-1 Connection of unit heaters The unit heaters operate with a pressure of between 20 and 25 mbar for Natural gas and 37 mbar for the Propane versions. 1/ The gas supply network pressure corresponds to the entry pressure of the device: - in this case, connect each device with a dam valve item 1 and the gas filter item 2. 2/ The gas supply network pressure is higher than the intake pressure of the device: - in this case, connect each device with a dam valve item 1, a gas filter item 2 and a pressure regulator item 2, to reduce the supply pressure to the unit heater. CAUTION Any supply pressure which is higher than the maximum intake pressure tolerated by the gas solenoid valve will cause irreparable damage to that solenoid valve. To connect the unit heater to the gas network, use the union item 4 with the seal item 5 delivered with the device. Tighten the union onto the network before connecting it to the unit heater. Check that the gas supply circuit is correctly sealed upto the gas solenoid valve. (see schematic) Network Check the sealing up to the gas solenoid valve input 8- COMMISSIONING OF GAS UNIT HEATERS 8-1 Operating principle: 1- For the commissioning of the device, turn the regulation to demand. The inspection box tests the air pressure switch contact switch in its at rest position, and then triggers the smoke extractor. Its correct functioning is controlled by the differential air pressure switch which, if there is not enough air, will prevent the control box from following its cycle. 2- After pre-ventilation, the ignition electrode lights up and the gas solenoid valve allows the gas to pass to the injectors. 3- If the air/gas mixture is not ignited or is not detected by the ionisation sensor, the flame control box tries once more and then changes to safety position. 4- Once the burner is ignited, the blowing fan is triggered when the air temperature is higher than the fan airstat regulation value (35 C to 40 C). 5- In the case of a fan malfunctioning, the excess heat safety thermostat cuts off the unit heater burner if the temperature exceeds 90 C. CAUTION : Never stop the device before the fan has totally stopped. The lack of cooling can necessitate the excess heating airstat to be reset and can damage the heat exchanger over the long term. 21

22 8-2 Bill of material Detail of RFP card Detail of connections ACG 20 / 28 / ACG 45 / 55 / 75 / No. Description Spare parts part number ACG20 ACG28 ACG35 ACG45 ACG55 ACG75 ACG95 1 Smoke outlet ATE131 ATE131 ATE131 ATE004 PF329 PF329 PF329 2 Extractor washer ATE167 ATE168 ATE169 3 Air inlet ATE132 ATE132 ATE132 ATE004 PF329 PF329 PF329 4 Helicoidal fan for ACGH ATE223 ATE123 ATE192 ATE118 ATE119 ATE108 2 x ATE119 4 Centrifugal fan for ACGC ATE065 ATE061 ATE061 ATE063 ATE063 ATE194 5 Gas inlet ATE212 ATE212 ATE212 ATE212 ATE212 ATE213 ATE213 6 Gas tube GAZ0102 GAZ0102 GAZ0102 GAZ0102 GAZ0102 GAZ0102 GAZ Gas S/V with pressure regulator ( 1 Al. ) GAZ0011 9EL0070 Gas S/V with pressure regulator ( 2 Al. ) GAZ0007 PB509 8 Upstream gas pressure test point 9 Ramp pressure test point 10 Gas ramp 11 Ignition electrode ATE021 + ATE Ionisation sensor ATE022 + ATE024 ATE022 + ATE Inspectioni and safety box ATE318 ATE318 ATE318 ATE318 ATE318 ATE318 ATE Burner regulation airstat (65 C) ATE146 ATE146 ATE146 ATE146 ATE146 ATE146 ATE Fan airstat (30 to 35 C) ATE146 ATE146 ATE146 ATE146 ATE146 ATE146 ATE Excess heating airstat with reset (100 C) ATE147 ATE147 ATE147 ATE147 ATE147 ATE147 ATE Lack of air pressure switch ATE204 ATE204 ATE204 ATE204 ATE204 ATE204 ATE Smoke box SE0411 SE0420 SE0403 SE0430 SE0439 SE0448 SE Smoke extractor ATE002 ATE002 ATE013 ATE013 ATE013 ATE112 ATE Burner reset 22 Regulation connector 23 5A unit heater protecting fuse ATE201 ATE201 ATE201 ATE201 ATE201 ATE201 ATE Pilot wire receiver ATE248 ATE248 ATE248 ATE248 ATE248 ATE248 ATE Airstat 2 nd speed (25 to 30 C) ATE146 ATE146 ATE146 ATE146 ATE146 ATE146 ATE146 22

23 9-MAINTENANCE Correct and regular use and maintenance of the unit heater will determine rational and efficient operation, minimum consumption as well as long life. The maintenance must be done with the device cold, with the gas and electricity supplies cut off. These service visits must be carried out by a qualified professional person Parts Unit heater Maintenance operations Check the correct functioning of all the safety devices and verify that all the screws are correctly tightened. Heat exchanger, smoke extractor and venturi Get access to the heat exchanger by disassembling the burner and smoke boxes, clean it. Clean the extractor and the venturi via the rear smoke connection. Fan Clean with compressed air Smoke conduit Disassemble the conduit and sweep it out Blowing cases and grilles with adjustable vanes Clean using a duster Burner torches Disassemble the burner ramp, check their condition and clean them Injectors Clean the gas injectors Ionisation sensor and electrodes Check their condition, change them if necessary. Gas filter Disassemble the dirty cartridge and clean it with compressed air 10- RECOMMENDATIONS FOR THE USER Precautions to be respected : - Never obstruct the evacuation of the smoke and the intake of new air. - Never make any modifications to the adjustments which have been carried out by the qualified professional person. - Never spray any water onto the gas heater - Warn the after-sales technician when there is a change of gas, of gas pressure or a modification of the power supply voltage. You are strongly recommended to take out a maintenance contract: see with your installer. What should be done in case of problems? PROBLEMS Smell of gas REMEDIES - Close the external gas valve and the electrical supply then warn the maintenance technician. The burner stays in safety position (burner defect indicator lamp is lighted) - Press the reset button of the burner located on the thermostat control box. - If the problem persists, contact the after-sales technician. 23

24 11- TROUBLESHOOTING In case of problems, make sure that the conditions required prior to operating the unit heater are present. If the control box is in the safety position (with the burner defect indicator lamp lighted up), reset it. CAUTION : All electrical or mechanical operations must be carried out when the electrical supply is cut off and the gas supply is closed. Defect Cause Remedy The device does not start - Incorrect wiring - No voltage -The ambient thermostat is not triggered - The pilot wire receiver switch is not in the automatic position Excess heat safety airstat triggered. - Check the wiring - Verify the electrical supply - Increase the setting point of the ambient thermostat - Check the position of the receiver switch in the unit heater - Reset the airstat The burner preventilates continuously -Extractor defective -Air pressure switch disconnected -Air pressure switch defective - Replace the extractor - Reconnect the pressure air pipes - Replace the air pressure switch The ignition electrode is making sparks, the burner lights, the control box goes into safety position (burner defect indicator lamp lighted up) The device goes into safety position during operation (red light comes on) -Gas solenoid valve defective -Control box defective -Ionisation sensor out of adjustment or defective -Air in the piping -No gas -Gas supply interrupted - Replace it - Replace it - Adjust it or replace it - Bleed the piping - Check the pressure - Reset by pressing the red push button on the control box Cold air when starting -Incorrect adjustment of internal thermostat - Check the adjustment of the ventilation thermostat (adjustment 35 C) The device does not heat sufficiently -Incorrect placing of the thermostat -Incorrect adjustment of the thermostat -Insufficient gas pressure -Injectors are unsuitable - Modify its location - Check the thermostat - Check the gas supply pressure - Check that the injectors are correctly selected and replace them if necessary. The device never stops -The thermostat is set too high or is defective - Incorrect wiring - Lower the setting point or replace it - Check the wiring 24

GAS FIRED AIR HEATERS

GAS FIRED AIR HEATERS Installation and maintenance manual GAS FIRED AIR HEATERS FHAR..H/V/C DTC ARM 17-299 EN 1312BO3933 1 TABLE OF CONTENTS Section N Sections Pages 1 GENERAL INFORMATIONS 4 à 5 1.1 General recommendations

More information

Installation and maintenance manual INDIRECT GAS FIRED HEATER FOR LIVESTOCK ATL76H 1312BO3933 DTC ATL EN

Installation and maintenance manual INDIRECT GAS FIRED HEATER FOR LIVESTOCK ATL76H 1312BO3933 DTC ATL EN Installation and maintenance manual INDIRECT GAS FIRED HEATER FOR LIVESTOCK ATL76H 1312BO3933 DTC ATL 16-169 EN TABLE OF CONTENTS Section No. 1 GENERAL INFORMATION 1-1 General recommendations 1-2 Unit

More information

BENSON GAS UNIT HEATERS

BENSON GAS UNIT HEATERS BENSON GAS UNIT HEATERS Types VRA 065/090/110/140/170/220/285 Types VRC 065/090/110/140/170 Types VRE 090/110//170/220 49/AU/2840 0049 VARIANTE RANGE INSTALLATION AND SERVICE MANUAL Issue 2 0ctober 2003

More information

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL STREBEL GENEVA CE ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL INDEX TABLE 1 TECHNICAL DATA SECTION 1 SECTION 2 SECTION 3 SECTION 4 SECTION 5 SECTION 6 SECTION 7 SECTION 8 SECTION

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions Forced draught gas burner Code Model Type 3751982 GAS 3 519T80 291 (3) - 02/2010 DECLARATION Declaration of conformity in accordance with ISO / IEC 17050-1

More information

BENSON LINEAR RADIANT TUBE

BENSON LINEAR RADIANT TUBE BENSON LINEAR RADIANT TUBE Natural or Propane (Gas fired) I N S T A L L A T I O N C O M M I S S I O N I N G S E R V I C I N G U S E R I N S T R U C T I O N S September 2001 CONTENTS Page Compliance Notices

More information

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20-30-50-60-80-TC-001-EN Table of contents Information on the use of this manual... 1 Scope of delivery... 1 General safety...

More information

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS G 2000-S 25-35 - 45-55 60-70 - 100 (V13) 1 Index WARNINGS GAS FLOW RATE DIMSIONS SETTINGS PARAMETERS SERVICING THE URNER 3 8 13 OPERATING DESCRIPTION

More information

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING

FLAME115 INFRARED HEATER SERVICE MANUAL INDEX FIRE 115 WARNING FLAME115 INFRARED HEATER SERVICE MANUAL INDEX 1. CONTROLS AND COMPONENTS 2. FLAME CONTROL CYCLES 3. MAINTENANCE SCHEDULE 4. TROUBLESHOOTING GUIDE 5. REPAIR PROCEDURES 1. FAN MOTOR ASSEMBLY 2. FUEL FILTER

More information

GAS UNIT HEATERS ARM RANGE

GAS UNIT HEATERS ARM RANGE GAS UNIT HEATERS ARM RANGE ARM Simple and reliable heater Efficiency up to % Fleaxiheat Gas Unit Heaters - ARM series are suitable for indoor installation in industrial and commercial premises. Thanks

More information

Light oil burners. One stage operation

Light oil burners. One stage operation Installation, use and maintenance instructions Light oil burners One stage operation CODE MODEL TYPE 3505 RDB CF 38 50 T3 350050 RDBR CF 6 50 TR 35050 RDBR CF 33 50 TR 35050 RDBR CF 38 50 T3R 350650 RDBR

More information

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler

Conversion Instructions Logano G234X. Gas boiler. Please read carefully before installing and servicing. Gas boiler Gas boiler UPON COMPLETION OF THE INSTALLATION THE INSTALLER MUST INSTRUCT THE OWNER AND OPERATOR ON THE FUNCTIONALITY AND THE PROPER OPERATION OF THE BOILER AND THE HEATING SYSTEM. INSTALLER MUST REVIEW

More information

Installation and Operating Instructions. Models: T4-12LOW-9IS

Installation and Operating Instructions. Models: T4-12LOW-9IS Installation and Operating Instructions Models: T4-12LOW-9IS Dear Valued Customer, Thank you and congratulations on purchasing your new Parmco appliance. All Parmco products are made to the highest quality

More information

Proline GAS HOB Model TCG40IX Instruction Book

Proline GAS HOB Model TCG40IX Instruction Book Proline GAS HOB Model TCG40IX Instruction Book GB Operating and Installation Instructions Index Technical data and specifications...... 3 Installation...................... 3-6 Ventilation........................

More information

INSTALLATION AND MANINTENANCE INSTRUCTIONS

INSTALLATION AND MANINTENANCE INSTRUCTIONS INSTALLATION AND MANINTENANCE INSTRUCTIONS Appr. Nr. A 9503 T - 0085 AQ 0765 PEGASUS F2 T HIGH EFFICIENCY GAS-FIRED CAST-IRON BOILERS Models 51-68 - 85-102 2 Contents 1. General technical data 2. Dimensional

More information

LGB Gas fired boiler

LGB Gas fired boiler LGB Gas fired boiler Control Supplement LGB-5 Series 2 Propane gas CSD-1 Control System Part Number 550-110-682/0304 Please read this page first Hazard definitions To the installer... The following terms

More information

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25

OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 OPERATING & MAINTENANCE MANUAL INDUSTRIAL DIRECT FIRED DIESEL/KEROSENE HEATERS IC 25 NOT FOR DOMESTIC USE SPACE HEATING ONLY Made By: Spitwater Australia Pty Ltd 953 Metry St North Albury, NSW, Australia

More information

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP

AXIAL HEATER TROUBLE SHOOTING GUIDE. Models: AX24 N/PV, AX24 N/PV LT, AX24 LP AX26 N/PV, AX26 N/PV LT, AX26 LP AX28 N/PV, AX28 N/PV NT, AX28 LP AXIAL HEATER TROUBLE SHOOTING GUIDE Page 1 July 2009 Table of Contents Frequently Asked Questions... 3 Axial Heater CONTROL (Siemens LME69) Troubleshooting Chart... 4 Axial Heater BURNER Troubleshooting

More information

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

GAS AIR HEATER RANGE

GAS AIR HEATER RANGE GAS AIR HEATER RANGE ATH Horizontal gas air heater ATC Centrifugal gas air heater ATV Vertical gas air heater Address : Yahtec - 6 rue Pascal 7700 Meaux - France Phone number :+ (0) 60 4 4 86 Multiple

More information

Model No: Little Devil II (inc ss)

Model No: Little Devil II (inc ss) GAS HEATER Model No: Little Devil II (inc ss) PART NO: 6926020, 6926025 (SS) OPERATION & MAINTENANCE INSTRUCTIONS LS1213 INTRODUCTION Thank you for purchasing this CLARKE Gas Heater. Before attempting

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

DH-Direct Fired Poultry Farm Diesel Heater

DH-Direct Fired Poultry Farm Diesel Heater DH-Direct Fired Poultry Farm Diesel Heater Comparison of Diesel Heater to Gas Heater Diesel LPG Gas LPG Gas KW 43 70 120 Fuel consumption/hr 3 5.1 8.8 Heat output 37000 60000 100000 Cost of fuel/lit or

More information

BIX B-One 100 kw INSTALLATION GUIDE

BIX B-One 100 kw INSTALLATION GUIDE BIX B-One 100 kw INSTALLATION GUIDE Dear Customer, We thank you for choosing our product. The Bix B-One 100 Kw is a burner of advanced concept and technology, with a high reliability and construction quality.

More information

Forced draught gas burner

Forced draught gas burner Installation, use and maintenance instructions GB Forced draught gas burner One stage operation CODE MODEL TYPE 3751782 GAS 5 517T80 291 (4) - 07/2015 Declaration of conformity in accordance with ISO /

More information

Light oil / kerosene burner

Light oil / kerosene burner Installation, use and maintenance instructions Light oil / kerosene burner One stage operation CODE MODEL TYPE 374445 G5 444T50 290238 (5) - 05/20 TECHNICAL DATA Thermal power output 28 60 kw 2.3 5 kg/h

More information

... LCSA - LCSBD - LCSC Gas Fired Unit Heaters ...

... LCSA - LCSBD - LCSC Gas Fired Unit Heaters ... LCSA - LCSBD - LCSC Gas Fired Unit Heaters LCSA complete with horizontal and optional vertical louvres LCSA - LCSBD - LCSC... Gas Fired Unit Heaters... The new LCSA builds on the technical excellence of

More information

Installation & Maintenance Manual

Installation & Maintenance Manual Installation & Maintenance Manual MOL 200 S1L (B30A) Oil Burner 11/12 Tel: +44 (0) 1905 794331 Fax: +44 (0) 1905 794017 Email: info@nu-way.co.uk Web: www.nu-way.co.uk DESCRIPTION COMPONENTS 1. Shrouded

More information

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14

TermEfekt USER S MANUAL AIR HEATER. Model PGA 14 Przedsiębiorstwo Produkcyjno-Wdrożeniowe ARAJ sp. z o.o. 55-080 Kąty Wrocławskie, ul. Mireckiego 30 POLAND USER S MANUAL AIR HEATER TermEfekt Model PGA 14 Kąty Wrocławskie, 2004 Product identification

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500 Bio B10 E90-803-001-001-00 Rev 7-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X400 Bio B10 E90-803-001-001-03 Rev 13-1 - Contents Technical specifications Technical data... 3 Working field... 3 Dimensions... 4 Head and electrode settings...

More information

Light oil - kerosene burner

Light oil - kerosene burner Installation, use and maintenance instructions Light oil - kerosene burner One stage operation CODE MODEL TYPE 374374 G3B 437T 90 (4) - 05/0 TECHNICAL FEATURES TYPE 437T Thermal power output 9 35 kw.6

More information

FLCH4R Garage and Utility Electric Heater

FLCH4R Garage and Utility Electric Heater FLCH4R Garage and Utility Electric Heater Installation, Operation & Maintenance Instructions Model No. Volts Amps Watts BTU/HR Phase High Low High Low High Low Min Fuse Size* FLCH4R 208 17.3 8.66 3600

More information

W - WR - WD. Technical information W- WR - WD. Gas-fired convection heaters with fan

W - WR - WD. Technical information W- WR - WD. Gas-fired convection heaters with fan Gas-fired convection heaters with fan W - WR - WD Technical information A2B srl - Via d Ancona, 37-60027 Osimo (An) Tel. 071.723991 - Fax 071.7133153 - Web Site: www.accorroni.it - E-mail: a2b@a-2-b.it

More information

NXM2G Installation and Operating Manual

NXM2G Installation and Operating Manual NXM2G-1001 MARCH 26, 2014 NXM2G Installation and Operating Manual (-1 UL version shown) 40VG This manual must be affixed on or adjacent to the boiler or kept with boiler operating manual or other information.

More information

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance Installation Operation Commissioning Maintenance HOT AIR GENERATOR WITH GAS BURNER GGS NA11.45 A 06-2011 04-2011 CONTENTS 1. DESCRIPTION OF THE UNIT 2. INSTALLATION & CONNECTION 3. COMMISSIONING 4. CARE

More information

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN

READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AN READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING TO ASSEMBLE, INSTALL, OPERATE OR MAINTAIN THE PRODUCT DESCRIBED. PROTECT YOURSELF AND OTHERS BY OBSERVING ALL SAFETY INFORMATION. FAILURE

More information

Parts Available from

Parts Available from Montage und Bedienungsanleitung Manuel d entretien Installation, use and maintenance instructions Installatie-, gebruiks- en onderhoudsvoorschriften Oδηγίες εγκατάστασης, χρήσης και συντήρησης D F GB NL

More information

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only.

User Manual. 110 Cup (55 Cup Raw) Gas Rice Cooker. Model: 177GRCLP, 177GRCNAT 12/2018. Please read and keep these instructions. Indoor use only. 110 Cup (55 Cup Raw) Gas Rice Cooker Intertek 5010781 Conforms to ANSI STD Z83.11-2016 Model: 177GRCLP, 177GRCNAT 12/2018 FOR YOUR SAFETY Do not store or use gasoline or other flammable vapors or liquids

More information

Propane Heater REMKO PGM 30 REMKO PGM 60

Propane Heater REMKO PGM 30 REMKO PGM 60 Propane Heater REMKO PGM 30 REMKO PGM 60 Operation Technology Spare Parts Edition GB L07 REMKO strong as a bear. Operating instructions Make sure to read these instructions carefully before starting/using

More information

Oil burners Brûleurs fioul Stookoliebranders

Oil burners Brûleurs fioul Stookoliebranders Installation, use and maintenance instructions Manuel d entretien Installatie-, gebruiks- en onderhoudsvoorschriften GB F NL Oil burners Brûleurs fioul Stookoliebranders One stage operation Fonctionnement

More information

Use, Care, and Installation Guide

Use, Care, and Installation Guide Use, Care, and Installation Guide Model PSU-E30AS XP022421(1) 182766 Safety Notice... 2-3 List of Materials... 4 D ucting Calculation Sheet... 5 Mounting Height & Clearance... 6 Ducting Options... 7 Hood

More information

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS

JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS JUMBO INDIRECT FIRED DIESEL HEATER OPERATING INSTRUCTIONS Before using the heater, read and understand all instructions and follow them carefully. The manufacturer is not responsible for damages to goods

More information

ST 40 Oil Burner. Installation & Maintenance Manual

ST 40 Oil Burner. Installation & Maintenance Manual ST 40 Oil Burner Installation & Maintenance Manual 178 093 13 Thank you for choosing a Nu-way burner. As you would expect from a Company who has a pedigree of more than 75 years in the heating industry,

More information

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw GAS FIRED ATMOSPHERIC ELECTRONIC VERSION 51-102 kw GENERAL DESCRIPTION 900 D a3 1000 762 672 E 222 The PEGASUS F2 range of atmospheric natural gas-fired boilers are constructed of cast iron finned sections

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

UL U TR LTRASONIC S ONIC SCALE ALER PIEZO MINI

UL U TR LTRASONIC S ONIC SCALE ALER PIEZO MINI ULTRASONIC SCALER PIEZO MINI CONTENTS XI - SYMBOLS 1. INTRODUCTION 1 Alternating current Type BF device 2. WARNINGS 1 3. PRESENTATION 1 3.1 Presentation 1 3.2 Technical description 2! Warning, please refer

More information

Mod. ANBR9..G. CR DOC. NO. GAS-HEATED TILTING BRATT PAN. INSTRUCTIONS FOR INSTALLATION, ADJUSTMENT, USE AND MAINTENANCE...

Mod. ANBR9..G. CR DOC. NO. GAS-HEATED TILTING BRATT PAN. INSTRUCTIONS FOR INSTALLATION, ADJUSTMENT, USE AND MAINTENANCE... -HEATED TILTING BRATT PAN Mod. ANBR9..G. INSTRUCTIONS FOR INSTALLATION, ADJUSTMENT, USE AND MAINTENANCE...page 2-5 APPENDIX....pagina 6-7 Read the manual thoroughly and keep it in a safe place throughout

More information

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600

I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d. Model code: BORA600 I n s t r u c t i o n m a n u a l f o r b u i l t - i n h o o d Model code: BORA600 Contact Caple on 0844 8003830 or for spare parts www.4caple.co.uk 1 Y O U R A P P L I A N C E Thank you for buying your

More information

e Bath Fan with Light User s Guide

e Bath Fan with Light User s Guide e Bath Fan with Light User s Guide abfl100rnl, BFL125RNL Item Stock Number(s): BFL100RNL, BFL125RNL IMPORTANT INSTRUCTIONS - OPERATING MANUAL READ AND SAVE THESE INSTRUCTIONS READ CAREFULLY BEFORE ATTEMPTING

More information

51AKS I S O OWNER S MANUAL

51AKS I S O OWNER S MANUAL LLOYD'S REGISTER QUALITY ASSURANCE 51AKS I S O 9 00 1 OWNER S MANUAL This manual applies to the following models Stand-alone Split 51AKS 085--- 51AKS 010--- 51AKS 185--- 51AKS 013--- 51AKS 113--- 51AKS

More information

BG2000S PRE-MIX GAS BURNER

BG2000S PRE-MIX GAS BURNER BG000S PRE-MIX GAS BURNER INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 08707 707 77 FAX: 08707 707 767 E-MAIL:info@stokvisboilers.com

More information

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS INSTRUCTIONS FOR: INFRARED IP55 HEATER MODEL:- QZWP45N Thank you for purchasing a Consort Claudgen product. Manufactured to a high standard this product will, if used according to these instructions and

More information

MEC MEC C

MEC MEC C Gas-fired air heaters MEC 25 85 MEC 35 85 C Technical information MEC 25 85 - MEC 25 85 C GAS-FIRED AIR HEATERS MEC - MEC C SERIES Models 25-30 - 35-50 - 57-85 Technical information This manual is divided

More information

ART cm Island Curved Glass

ART cm Island Curved Glass ART28101 90cm Island Curved Glass [01] x 1 [02] x 1 [03] x 1 [04] x 1 [05] x 4 [06] x 1 [07] x 1 [08] x 1 [09] x 4 [10] x 4 [11] x 1 [12] x 4 (6x70mm) [13] x 4 (6.3x17x2mm) [14] x 8 (4x12x1mm) [15] x 4

More information

USER GUIDE ENGLISH TOPSTART Ref. TSWZ, TSWRS or TSG Between 0.5 and 3 kw

USER GUIDE ENGLISH TOPSTART Ref. TSWZ, TSWRS or TSG Between 0.5 and 3 kw The TopStart is a compact electric coolant heater with circulating pump for marine engines, generating sets and all types of vehicles located inside or outside (protected place only). TABLE OF CONTENTS

More information

GAS-FIRED AIR HEATERS MEC - MEC C SERIES Models Technical information

GAS-FIRED AIR HEATERS MEC - MEC C SERIES Models Technical information This manual is divided into three sections: GAS-FIRED AIR HEATERS MEC - MEC C SERIES Models 25-30 - 35-50 - 57-85 - SECTION 1 - GENERAL INFORMATION Technical information It contains all the information

More information

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM

MODEL HS115-3, HS115-4 & HS115-5 WIRING DIAGRAM ADDENDUM TJERNLUND PRODUCTS, INC. 1601 Ninth Street White Bear Lake, MN 55110-6794 PHONE (800) 255-4208 (651) 426-2993 FAX (651) 426-9547 Visit our web site www.tjernlund.com MODEL HS115-3, HS115-4 & HS115-5 WIRING

More information

Installation & Maintenance Instructions

Installation & Maintenance Instructions IMPORTANT INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS Saving energy and creating healthy, comfortable environments No. II-450 Date July, 2015 DRIVE-THRU UNIT 3 AIR CURTAIN SERIES DTU03 for outdoor use

More information

Operating instructions

Operating instructions Operating instructions Gas-fired condensing boiler Logano plus GB312 For the user Please read carefully before use 7 747 009 296-01/2007 EN Contents 1 For your safety..............................................

More information

1. GENERAL SAFETY RULES

1. GENERAL SAFETY RULES ID180 & ID290 Indirect-Fired Diesel/Oil Construction Heaters Sure Flame Products Lethbridge, Alberta, Canada Telephone: (403)328-5353 Fax: (403)328-9956 www.sureflame.ca July 12, 2006 Service and Maintenance

More information

en Direct oil-fired space heaters HD... Operator's manual

en Direct oil-fired space heaters HD... Operator's manual 0211670en 002 12.2007 Direct oil-fired space heaters HD... Operator's manual Table of contents 1. Foreword 5 2. Safety information 6 2.1 General recommendations... 6 2.2 Safety devices... 7 2.3 Labels...

More information

PowerVent. Installation manual (GB) English. Store this document in a safe place UK

PowerVent. Installation manual (GB) English. Store this document in a safe place UK PowerVent Installation manual (GB) Store this document in a safe place 959.034.03.UK GB Contents Blz Foreword 3 1. Introduction 3 2. CE declaration 4 3. SAFETY 4 3.1 General 4 3.2 Regulations 4 3.3 Precautions

More information

Installation Instructions Use and Care Guide Instructions d installation Mode d emploi et d entretien

Installation Instructions Use and Care Guide Instructions d installation Mode d emploi et d entretien Installation Instructions Use and Care Guide Instructions d installation Mode d emploi et d entretien AMCHD36SS/ AMCHD44SS/ INDEX WARNINGS AND REQUIREMENTS... 3 RECOMMENDATIONS AND SUGGESTIONS... 6 DIMENSIONS

More information

CG60/ 70/ 80/ 90/ 100 SS/BK

CG60/ 70/ 80/ 90/ 100 SS/BK CG60/ 70/ 80/ 90/ 100 SS/BK GB IE [01] x 1 [02] x 1 [03] x 1 [04] x 2 [05] x 1 [06] x 1 [07] x 1 [08] x 4 [09] x 4 [10] x 1 [11] x 6 1 : 1 [12] x 4 [13] x 6 (3.9 x 32mm) [14] x 4 (3.4 x 10mm) CG60/ 70/

More information

CINCINNATI, OH USA

CINCINNATI, OH USA INSTRUCTION MANUAL Part No. 89731 Revised October 1997 CINCINNATI, OH 45241-4807 USA GAS SAFETY PRECAUTIONS Instructions on what to do when a user smells gas can be obtained from the local gas supplier.

More information

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION INSTALLATION AND OPERATING INSTRUCTIONS FOR THE HARDY Fuel Oil Furnace Models D-140 & D-350 HARDY MANUFACTURING COMPANY, INC. 12345 ROAD 505 PHILADELPHIA, MS 39350 PHONE: (601) 656-5866 FAX: (601) 656-4559

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE Date revised: 11/10/08 2008-36 TSG-PRESTIGE Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL

More information

Service Manual Model 3163

Service Manual Model 3163 Service Manual Model 3163 Contents Important Safety Information.......... 1 Specifications.................. 2 General Information.............. 2 Direct Vent Requirements........... 2 Propane System................

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version

Duct heaters for ATEX/IECEx hazardous areas or in non-atex version for ATEX/IECEx hazardous areas or in non-atex version * Non contractual picture Warning It is imperative to read these instructions carefully before installing or maintaining the equipment. MI200EN 09/2017

More information

INSTRUCTION MANUAL FOR OIL BURNER MODELS

INSTRUCTION MANUAL FOR OIL BURNER MODELS INSTRUCTION MANUAL FOR OIL BURNER MODELS X500-2 Low voltage 12v dc Brushed motor E90-803-001-005-01 Rev 4-1 - Contents Technical specifications Technical data...3 Working field...3 Dimensions...4 Head

More information

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc Mikrofill Ethos Condensing combination boiler Maintenance Instructions 24cc IMPORTANT Benchmark Installation, Commissioning and Service Record Log Book is enclosed in your customer information pack. This

More information

TAHITI CONDENSING KR 55 - KR 85

TAHITI CONDENSING KR 55 - KR 85 IST 03 C 351-01 TAHITI CONDENSING KR 55 - KR 85 GB INSTALLATION USE AND MAINTENANCE Dear Customer, Thank you for choosing and buying one of our boilers. Please read these instructions carefully. They will

More information

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI Vivadens EN Wall-hung gas condensing boilers MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI User Guide 300015874-001-B Contents 1 Introduction...4 1.1 Used symbols...4 1.2 Abbreviations...4 1.3 General...4

More information

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N 238-44219-00 (Replaces pg. 2 in instruction manual.) CONGRATULATIONS! You have just purchased one of the finest water heaters on

More information

V SERIES HDR GAS RANGES

V SERIES HDR GAS RANGES SERVICE MANUAL ONE POWERFUL PACKAGE V SERIES HDR GAS RANGES TOPS Open Top Hot Top Griddle Top Work Surface BASES Standard Oven Convection Oven Cabinet Base - NOTICE - This manual is prepared for use by

More information

Columbia Boiler Company

Columbia Boiler Company EMG Series Boilers Available in Natural Gas & Propane Rev 12012 Columbia Boiler Company PO Box 1070 Pottstown, PA 19464 Tel (610) 473-8457 Fax (610) 367-6800 Website www.columbiaboiler.com Email cbcsales@ptd.net

More information

DIESEL/PARAFFIN HEATERS

DIESEL/PARAFFIN HEATERS DIESEL/PARAFFIN HEATERS MODEL NO: XR80, XR110, XR160, XR210 PART NO: 6931004, 6931006, 6931008, 6931012 OPERATION & MAINTENANCE INSTRUCTIONS LS0814 INTRODUCTION Thank you for purchasing this CLARKE product.

More information

Installation, Operating and Servicing Instructions

Installation, Operating and Servicing Instructions Installation, Operating and Servicing Instructions Opus 800 Gas Boiling Tops OG8003, OG8004 & OG8009 Please make a note of your product details for future use: Date Purchased: Model Number: Serial Number:

More information

breeze easytm model # F100-1W

breeze easytm model # F100-1W DewStop breeze easytm model # F100-1W Installation Guide Read and Save These Instructions LISTED Questions, Problems, Missing Parts? Please Call 1-360-876-2974 or E-Mail info@dewstop.com please retain

More information

GAS FIRED CONVECTION HEATERS WITH FAN GHIBLI SERIES Models Technical information

GAS FIRED CONVECTION HEATERS WITH FAN GHIBLI SERIES Models Technical information GAS FIRED CONVECTION HEATERS WITH FAN GHIBLI SERIES Models 4-5 - 6 This manual is divided into three sections: Technical information - SECTION 1 - GENERAL INFORMATION It contains all the information relevant

More information

1. Information before installation General terms of delivery, storage and transport

1. Information before installation General terms of delivery, storage and transport EN Read this manual carefully before installing, maintaining or repairing this device! The symbol indicates important information that must be taken into account in order to avoid risk of personal injury

More information

PowerVent. Installation manual (GB) English. Store this document in a safe place UK

PowerVent. Installation manual (GB) English. Store this document in a safe place UK PowerVent Installation manual (GB) Store this document in a safe place 959.078.00.UK GB Contents page Foreword 3 1. Introduction 3 2. CE declaration 4 3. SAFETY 4 3.1 General 4 3.2 Regulations 4 3.3 Precautions

More information

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS S150 & S300 CONSTRUCTION HEATERS Rev: 2.7.2 August 15, 2008 SERVICE AND MAINTENANCE MANUAL No. 934-6637 PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS A DIVISION OF HAUL-ALL EQUIPMENT LTD. 4115-18 Avenue

More information

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04 prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE 2004-28 TSG-SOLO-9/04 Table of Contents INTRODUCTION Page 1 SERVICING TIPS AND INSTRUCTIONS Page 3 CONTROL MODULE DISPLAY -

More information

CRU-S Series Stainless Steel Condensate Recovery Unit

CRU-S Series Stainless Steel Condensate Recovery Unit IM-UK-CRU-S UK Issue 1 CRU-S Series Stainless Steel Condensate Recovery Unit 1. Safety information 2. General product information 3. Installation 4. Commissioning 5. Storage, shutdown and equipment protection

More information

Air curtains. 114 MRX condensing gas air curtain. 118 MRA-H gas air curtain. 121 MRA-A ventilation only air curtain

Air curtains. 114 MRX condensing gas air curtain. 118 MRA-H gas air curtain. 121 MRA-A ventilation only air curtain Air curtains 114 MRX condensing gas air curtain 118 MRA-H gas air curtain 121 MRA-A ventilation only air curtain 122 SW / SE hot water / electrical air curtain 124 SWR / SER built-in hot water / electrical

More information

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No

JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No JANUS 3 CIRCULATOR WATER HEATER INSTALLATION, COMMISSIONING & SERVICING INSTRUCTIONS G.C. No 53 416 06 Publication No. ZZ 180/17 May 2000 These appliances are tested and certified by B G Technology for

More information

SAITEK srl. Serie. < Automatic burner control unit > Casalgrande (RE) ITALY Tel Fax

SAITEK srl. Serie. < Automatic burner control unit > Casalgrande (RE) ITALY Tel Fax Serie < Automatic burner control unit > MONO DOUBLE ELECTRODE FLAME DETECTION SAITEK srl www.saitek.it info@saitek.it Casalgrande (RE) ITALY Tel. +39 0522 848211 Fax +39 0522 849070 NOTE. AUTOMATIC BURNER

More information

Gas burner automatic safety control MMI / 811.1

Gas burner automatic safety control MMI / 811.1 Gas burner automatic safety control MMI 810.1 / 811.1 For 2-stage forced draught and combi oil/ gas burners Possible flame detectors: - Ionization probe - Infrared flicker detector INTRODUCTION 0708.21-01-e/04/99

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

s l it l on for Infrared Heaters

s l it l on for Infrared Heaters Installation and Instruction Manual for Infrared Heaters Contents Safety and operating instructions... 3 Scope of supply... Installation instructions... 4 5 Initial operation... 10 Cleaning instructions...

More information

FIREPLACE SIZES FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VACINITY OF THIS OR ANY OTHER APPLIANCE.

FIREPLACE SIZES FOR YOUR SAFETY DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VACINITY OF THIS OR ANY OTHER APPLIANCE. RGA 2-72 INSTALLATION AND OPERATION GUIDE FOR HARGROVE GAS LOGS PROPANE GAS ADEQUATE FIREPLACE VENTILATION IS REQUIRED FOR SAFETY. GAS LOGS MUST BE INSTALLED BY PERSONNEL QUALIFIED FOR INSTALLING GAS APPLIANCES.

More information

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000

SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual SH-2000 SH-2000, SH-2500, AB-3000 Bimetallic Steam Traps Installation and Operation Manual 65 SH-2500 SH-2000 AB-3000 Table of Contents General Safety Information.............. 2 Product Information..................3

More information

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2 I&M NUMBER: 316-42-15-1 Page: 1 _ Pre Installation Check to make sure that heater received is the same as that ordered. Elements may come in contact with each other during shipment. Minor adjustments to

More information

ENGLISH USER S GUIDE ThermoCar from 0,5 to 2 kw

ENGLISH USER S GUIDE ThermoCar from 0,5 to 2 kw The is a universal tank-style electric coolant heater to preheat engines. It is meant for either stationary (generating sets) or mobile applications (all types of vehicles). The choice of high-quality

More information