Training Manual FT 51

Size: px
Start display at page:

Download "Training Manual FT 51"

Transcription

1 Training Manual FT 5 All the technical strengths, installation and maintenance: Panther Condens 2 KKO 25 KKO 25 KKV 30 KKO.

2 T echnical Training >>> Introduction... >>> Technical Specifications... Presentation of the range... Hydraulic description of Panther Condens combi... Hydraulic description of Panther Condens system... Hydraulic operation of Panther Condens... Technical characteristics... Control panel Panther Condens... Safety devices... Air/gas servo... The gas valve... Hydraulic unit... The heat exchanger... Software: general functions... Access to installer and After-Sales menus... Installation and After-Sales menu details... The Installation and After-Sales menus by theme... Appliance status... Gas valve setting... Change of gas type... >>> Installation... Heater location... Water and gas connections... Water and gas... Drain connections... Exhaust connections... Electrical connections... Flow rate / pressure curve available at boiler outlet (heating side)... Installation recommendations... Check-list for commissioning a heater... Service visit... >>> Maintenance... Service visit... Fault diagnosis help... Panther Condens combi circuit diagram... Panther Condens system circuit diagram... Measurements... hydraulic assembly... Combustion block assembly (all models)... >>> Accessories... Some accessories compatible with Panther Condens

3 T echnical Training >>> Introduction... This new range of boilers, constructed around a single and unique structure covers a wide range of powers and market segments. The performances have been improved: - optimum efficiency for heating and hot water production User comfort: - use of high performance accoustic insulation reduces noise further, - the pump has two automatic speeds to adapt to the demand without crating unnecessary nuisance, - the possibility of a tank controlled by a temperature sensor rather than a thermostat, with adjustment of the tank temperature directly from the boiler interface - a new room thermostat (Exacontrol) has been developed for simpler communication: information in full, in the local language, userfriendly menu, - a maintenance-free wireless outdoor sensor (powered by a solar cell) completes the room thermostat. The installation: - compact boiler dimensions - weight less than 40kg - installer functions (connection of the tank for system boilers to the fixing jig, a connector for the overheating safety device...) - compatible with all ebus controls, if used with new wireless room thermostat the new solar powered outdoor sensor can be used. - simple and rapid outlet connection to the drain, - packaging that is quick to open and easy to dispose of After-sales has not been forgotten: - simple access to internal components for ease of maintenance - simple access to comprehensive diagostic points with intuitive fault codes

4 >>> Technical Specification... Presentation of the range This new condensing wall hung boiler range is made up of Panther Condens, both combi and system boilers. All using pre-mix burner technology with a sealed case front. The different models: Panther Condens 2 KKO : system boilers, 3,9 to 2 kw in heating*, for DHW preparation 4, to 2,3 kw; Panther Condens 25 KKO : system boilers, 5,9 to 24,5 kw in heating*, for DHW preparation 6, to 30,6 kw; - Panther Condens 30 KKO : system boilers, 8,5 to 30,0 kw in heating*, for DHW preparation 8,7 to 35,7 kw; Panther Condens 25 KKV : combi boiler, 5, to 25,5 kw for hot water, 4,9 to 8, kw for heating* * at 80/60 C

5 >>> Technical Specification... Hydraulic description of Panther Condens combi (25 KKV) Pressure relief valve 2 Cold water filter 3 Filling system with non return valve 4 Cold water inlet flow sensor 5 Domestic hot water heat exchanger 6 Heating filter 7 Heating return temperature sensor 8 Condensate trap 9 Ignition and flame control electrode 0 Burner Primary heat exchanger 2 Thermal fuse 3 Air inlet / Flue outlet 4 Silencer 5 Expansion vessel 6 Fan 7 Gas valve 8 Igniter 9 Heating output temperature sensor 20 Air relief valve 2 Pump 22 3-way valve 23 Pressure sensor 24 Bypass 3 2 A B C D E F G Heating flow Pressure relief valve drain Hot water output Gas inlet Cold water inlet Heating return Condensate drain pipe - 5 -

6 >>> Technical Specification... Hydraulic operation of Panther Condens Hydraulic diagram in heating Hydraulic diagram in hot water - 6 -

7 >>> Technical Specification... Hydraulic description of Panther Condens system (2/25 KKO) Pressure relief valve 2 By-pass 3 Heating filter 4 Heating return temperature sensor 5 Condensate trap 6 Ignition and flame control electrode 7 Burner 8 Heat exchanger 9 Thermal fuse 0 Air inlet / Flue outlet Silencer 2 Expansion vessel 3 Fan 4 Gas valve 5 Igniter 6 Heating output temperature sensor 7 Air relief valve 8 Pump 9 3-way valve 20 Pressure sensor A B C D E F G Heating flow Pressure relief valve drain Hot water output Gas inlet Cold water inlet Heating return Condensate drain pipe - 7 -

8 >>> Technical Specification... Technical characteristics Boiler type C3, C33, C43, C53, C83 Description Units 2 KKO 25 KKV 25 KKO 30 KKV 30 KKO Gas category l 2H ll 2H3P ll 2H3P ll 2H3P ll 2H3P Heating Min. useable power at 80 C/60 C (P min.) kw Max. useable power at 80 C/60 C (P max.) kw Min. useable power at 50 C/30 C (P min.) kw Max. useable power at 50 C/30 C (P max.) kw P.C.I. efficiency at 80 C/60 C % P.C.I. efficiency at 50 C/30 C % Efficiency at part load (30%) on PCI at 40 C/30 C % Efficiency level according to the European Directive 92/42 - Condensation Minimum calorific rate (Q min.) kw Maximum calorific rate (Q max.) kw Minimum heating flow rate l/h Min. heating flow temperature C Max. heating flow temperature C Expansion tank, useable capacity l Expansion tank pre-inflation pressure bar Appliance maximum capacity at 75 C l Safety valve, maximum operating pressure (PMS) bar Sanitaire Min. useable power (P min.) kw 4. (*) (*) 6. - Max. useable power (P max.) kw 2.3 (*) (*) Min. calorific rate (Q min) kw 4. (*) (*) 6. - Maximum calorific rate (Q max.) kw 2.3 (*) (*) Min. domestic hot water temperature C Max. domestic hot water temperature C Specific flow rate (D) according to EN 3203 l/min Domestic hot water comfort according to EN ** - ** - Flow rate operating threshold l/min Cold water flow restrictor l/min Safety valve, maximum working pressure (PMW) bar Min. supply pressure bar Recommended supply pressure bar Pression d alimentation max. bar Electrique Tension d alimentation V/Hz Puissance maximale absorbée W Intensité A Fusible A Protection électrique IPX4D IPX4D IPX4D IPX4D IPX4D Classe électrique I I I I I 230V 50Hz 230V 50Hz 230V 50Hz 230V 50Hz 230V 50Hz * value measured during product certification. The theoretical value is.5 l/min

9 >>> Technical Specification... Technical characteristics Description Units 2 KKO 25 KKV 25 KKO 30 KKV 30 KKO Combustion Fresh air flow rate (03 mbar -0 C) m 3 /h Burnt gasses exhaust flow rate at Pmin. g/s Burnt gasses exhaust flow rate at Pmax. g/s Burnt gasses exhaust flow rate at Pmax., in hot water mode g/s Exhaust temperature at Pmin. 80 C/60 C C Exhaust temperature at Pmin. 50 C/30 C C Exhaust temperature at Pmax. 80 C/60 C C Exhaust temperature at Pmax. 50 C/30 C C Exhaust temperature in overheat C Exhaust temperature in hot water mode (hot water temperature 50 C) C Value of combustion products (measured at nominal calorific rate and with G20 reference gas, in heating): CO ppm mg/kwh CO2 % NOx weighted ppm mg/kwh Description Units 2 KKO 25 KKV 25 KKO 30 KKV 30 KKO Natural gas G 20 (*) Gas flow rate at maximum power hot water m 3 /h Gas flow rate at maximum power heating m 3 /h Gas flow rate at minimum power m 3 /h Gas supply pressure mbar Propane Gas G 3 (*) Gas flow rate at maximum power hot water kg/h Gas flow rate at maximum power heating kg/h Gas flow rate at minimum power kg/h Gas supply pressure mbar (*) ref. 5 C 03 mbar dry gas - 9 -

10 >>> Technical Specification... Control panel Panther Condens Domestic hot water circuit temperature control 2 Display 3 Reset button 4 Start/stop button 5 Heating circuit water temperature control 6 Working mode selection ECO 5 Temperature of the domestic hot water circuit 2 Fault symbols 3 Heating circuit pressure 4 Burner on indicator 5 Heating circuit temperature The symbol «ECO» appears when the exchanger pre-heating is deactivated. To activate or deactivate the pre-heating function, press + and - (DHW) at the same time : => pre-heating deactivated : «ECO» is displayed => pre-heating activated : «ECO» is not displayed - 0 -

11 >>> Technical Specification... Safety devices Flame control Temperature safety (ant-freezing / overheating) Thermal fuse 60 C Gas safety valve (EVS) Pump anti-block Water pressure sensor Non return valve on filling system Pressure relief valve (3 bar) 3-way valve anti-seize Safety Control device Values Action Safety devices locking the appliance and requiring a RESET in the case of a fault Overheating and Flow/return heating 97 C => max. temperature Fault displayed F20 temperature limiting NTC T increase more than 0 K/S. Fault displayed F24 ΔT (outlet - return) > 35 K Fault displayed F23 Thermal fuse 60 C Fault displayed F76 Flame control Ignition and ionisation electrode Up to 5 spark sequences separated by 7 seconds Fault F28 if no ignition Fault F29 if burner goes out Gas Gas safety valve 0V when shut down 24V then 6V in operation Air flow rate Gas servo-controlled by the air The gas flow rate is proportional to the air flow rate Display of various faults depending on origin Fault displayed F32 if fan fails Safety devices not requiring a RESET after the fault clears Antifreeze Flow NTC 7 C --> immediate heating Burner lit up to 35 C Pump anti-seize Internal control Activated for 30s if not activated for Activation without apparent demand 24 hours 3-way valve anti-seize Activated for 30s if not activated for 24 hours Activation without apparent demand Heating pressure Pressure sensor Triggered at 0.5 bar Display below 0.3 bar Reset at 0.3 bar display blinking between 0.3 and 0.5 bar Heating valve Opens at 3 bar Evacuation of excess pressure (display blinking below 2.5 bar) - -

12 >>> Technical Specification... Air/gas servo : Fan Venturi Burner Control unit Gas mechanism Modulating gas valve The heart of the automatic control is made up of: - a modulating valve controlled by a diaphragm - A governor - a venturi crossed by some of the air from combustion which initiates the gas flow. The air needed for combustion crosses the venturi, at the fan entrance. The partial vacuum created at the neck of the venturi is then transmitted to the gas valve. The gas valve regulator controls the flow of gas according to the airflow: when the fan speed decreases, the regulator reduces the gas flow rate by acting on the modulating valve. On the other hand when the speed of the fan increases, the regulator increases the gas flow rate

13 >>> Technical Specification... The gas valve : Safety valves (a) Gas high flow reducer (screw acting as diaphragm) Modulating gas valve operated by air flow: Gas inlet Modulating gas valve Mechanism in closed position: The gas safety valves (a) are closed. Gas does not flow. The pressure P0 of the gas under the modulating valve membrane and under the regulator membrane is identical. Gas valve at high flow rate: Safety valves (a) Channel For settings, refer to the Maintenance chapter. Gas inlet Channel 2 Channel 3 The 2 safety valves (a) are supplied at 24 V DC: they are thus open. The gas pressure arrives at the regulator valve via channel, and continues to the membrane of the modulating valve via channel 2. The fan operating at its maximum speed causes a reduction in pressure which is transmitted under the regulator membrane via channel 3. The regulator valve then closes and all the gas pressure is concentrated under the modulating valve membrane which now opens to its maximum. Gas valve in the modulation phase: Gas inlet Safety valves (a) Channel Channel 2 Channel 3 The fan speed decreases. The pressure under the regulator membrane tends to increase. The regulator valve gradually opens. An escape flow is established via channel 3 to the fan. This escape flow causes the pressure P2 to fall under the modulating valve membrane. The modulating valve closes to a greater or lesser extent depending on the size of the escape flow in channel

14 >>> Technical Specification... The relation between the fan speed and the usable heating power supplied by the boiler Vmin Vmax Panther Condens Theoretical fan speed Units 2 KKO 25 KKV 25 KKO 30 KKO Max. theoretical speed adjustable from: to: rpm This value is adjustable in the After-Sales menu, data item d Max. theoretical speed adjustable from: to: rpm This value is adjustable in the After-Sales menu, data item d These values are only for information : it can change on the time with the soft

15 >>> Technical Specification... Hydraulic unit of Panther Condens: Plate heat exchanger** Automatic air vent Heating pressure valve Screw giving access to the motor shaft for unblocking 2 speed pump Base plate (made from composite material) Cold water inlet flow sensor* * Not fitted to System version ** Replaced by a pipe support plate (for possible connection to an exchanger tank) 3-way valve motor* By-pass - 5 -

16 >>> Technical Specification... The heat exchanger: Is made up of flattened stainless steel tubes in a spiral. The heat transfer is carried out in two stages: - the first stage (A) uses 5 elements depending on the model (each element has 4 turns), in direct contact with the flame. - the second stage (B) (the cold stage) uses an element placed behind a deflector (C). This is heated by the flue products just before they are evacuated. This is where the condensing occurs. C - Deflector B - 2 nd exchange stage (condenser) Flue products Combustion air B - 2 nd exchange stage (condenser) Heat exchanger Burner A - st exchange stage Air inlet silencer: the silencer channels the air once it has entered the chamber thus avoiding airflow noise inside the equipment. Its venturi shape also aids the airflow. C - Deflector Gas valve Heating return Gas Condensation Heating flow Fan - 6 -

17 >>> Technical Specification... Regulation: general functions The burner can be lit following two different procedures depending on the prior condition of the unit: If the boiler has been switched off: On lighting after the electricity has been cut off (using the ON/OFF button or by disconnecting the cable), the boiler tests the circulation of water in the circuit. The procedure is as follows: - first a pre-flush of the pump depending on temperature - burner lights P = 90% of P. max and 3 seconds of stabilisation. - the outgoing temperature must rise by at least 5K. If not: - the burner then goes to max. power for 5 seconds. As soon as the 5K temperature rise is detected, the burner goes into normal operation. Otherwise the boiler cuts out indicating a fault (flashing display). Note: This is the same display as for lack of water pressure. DT < 5 C => P = 00% of P. max. for 5 seconds max. Pump pre-run Burner lights P = 90% of P. max 3 seconds DT 5 C => OK Normal operation DT 5 C => OK Normal operation This function is very useful to avoid overheating when the installation has not been fully bled (particularly at commissioning). DT < 5 C => Flashing display and made safe. If the boiler is already switched on: The principle is the same as case A, except the burner starts at about 60% of maximum power and looks for an increase of 2K instead of 5K. After the ignition phase, the regulator controls the burner in heating (reduction to Pmin) or hot water (the power is adjusted according to the need). Temperature regulation: After ignition, the burner then goes into reduced power for to 5 minutes: - minute if heating requirements are high - 5 minutes if the heating requirements are lower. After this period the power is released to be used as required. The reason for this forcing to minimum power is to favour condensation. The burner turns off at the setting +2K. (ot/min) VV TUV Note: it is recommended to use a modulating thermostat rather than a timeproportional one with this type of regulation to avoid interference

18 >>> Technical Specification... Regulation: Domestic hot water control: Regulation of tank heating (system boilers): There are 2 types of regulation allowed for a tank: either regulation by thermostat (ON/OFF contact) or regulation by NTC thermistor. In either case, the starting of the burner for a tank heating requests is preceded by a 30s pre-flush of the heating pump. This avoids the boiler being locked out in the case of too large a temperature difference between the tank and boiler temperatures. Tank equipped with a thermostat: - The closing of the thermostat conta, - the temperature of the primary circuit feeding the tank exchanger is 75 C (burner cut-off at 80 C). - the opening of the thermostat contact stops the burner and triggers a 30s pump post-flush. Tank equipped with an NTC thermistor: (NTC value: see table in accessories chapter) The tank temperature is set directly in the user menu, on the control panel (which is identical to the mixed version control panel). The thermistor allows continuous control of the tank temperature and consequent regulation of the primary circuit temperature. Tank heating start-up: when the tank temperature drops below the set temperature less 5K, the 3-way valve goes to the hot water position and the heating pump starts up. Heating stops when the NTC measures the setpoint in the tank. The pump carries out a 30s post-flush (3-way valve still in hot water position) and then stops. The regulation, in the case of a tank equipped with an NTC, is assisted by self-modification: the sensor measures the temperature 5 minutes after the burner shuts down. If the set point has been exceeded, a correction is applied to the next heating (the burner stops at a lower temperature to prevent a repetition of this temperature excess). The primary temperature depends on the setting to facilitate condensation: it is calculated at 5K below the hot water setting. In the case of scale in the tank, the primary temperature is pushed to the maximum. Regulation during hot water draw (mixed boiler): - demand detection: The burner is triggered in by a draw of.5l/min. It stops at. l/min. This hysteresis avoids having the burner in an unstable region (repetitive starts/stops). - temperature regulation: The primary regulation is performed by a calculation of the temperature setting on the primary circuit return. This calculation depends on the draw rate and the hot water temperature setting. The hot water setting is controlled by the temperature sensor in the primary return circuit (NTC5) in order to limit the influence of the cold water temperature on the hot water temperature. The presence of a solar tank is automatically detected by the solar thermistor being connected to the main circuit board (in position X32). There is no adjustment needed: the card records, at each draw, the time that it takes for the solar hot water to arrive at the boiler cold water inlet. It then applies this time to the following draw with an upper limit of 30 seconds. For example: at the first draw, the burner starts immediately but the hot water takes 0s to arrive at the boiler. On the next draw, the boiler will wait 0s before starting and record the new time the solar hot water takes. Thus the burner start-up time delay is constantly corrected for temperature variations in the solar tank

19 >>> Technical Specification... Regulation: Frost protection: The frost protection function is activated when the temperature falls below 2 C at the start of the heating circuit. The pump then runs for 0 minutes with the 3-way valve in the mixed position (central valve position to feed both the heating circuit and the plate heat exchanger): - If the temperature of the heating circuit falls below 7 C, the burner lights and remains alight until the temperature at the start of the heating circuit reaches 35 C. - If the temperature remains between 7 and 5 C, the burner lights after 30 minutes to raise the temperature to 35 C. - If the temperature exceeds 5 C, the pump runs for 30 minutes and then stops. T < 2 C 3-way in mixed position + pump ON for 0 mins T = 7 C 7 C < T < 5 C T > 5 C Burner ON T = 35 C Pump 30 minutes post-flush pump for 30 min then burner on up to 35 C pump OFF, 3-way in initial position Pump 30 minutes Protection against overheating and temperature limiting: The outlet / return thermistors protect the boiler against overheating by checking the maximum outlet temperature (97 C with the burner lit or 0 º C for 3 s with burner off). Complimentary conditions related to the flow rate in the installation: - check on the speed of temperature rise (0K/s max.) - checking the temperature difference outlet return: - if ΔT (outlet-return) > 30K => the burner is forced to minimum power for 0 minutes - if ΔT (outlet-return) > 35K => display of fault F23 initially volatile. If the fault repeats 5 times, the boiler shuts down and a reset becomes necessary. (Note: if the burner runs for at least 60 seconds, the counter is reset to zero) - 9 -

20 >>> Technical Specification... Access to installer and After-Sales menus : The display has hidden menus accessible by entering a code. This code is of interest to two groups of professionals: - The installer who needs to configure the appliance during installation => code 96 - The after-sales service who may need to change parts and then reconfigure them for the appliance => code 35 The installer menu gives access to a restricted list of data items whereas the After-Sales menu gives access to all the data items (installation + after-sales). To access installer or after-sales menu: Press the mode button () for about 7 seconds; the display layout will change. - Using the + or - button (2), display code 96 or Confirm with the mode button (). The display then shows line of the menu. To change a value: - Modify the value of the displayed data item using the + or button (3) on the boiler. - the change is automatically accepted after 3 seconds. To return to the normal display, press the mode button for 3 seconds. After 5 minutes of inaction, the display returns to normal operating mode. 2 3 Enter code 35 or 96 data value data VAL kw

21 >>> Technical Specification... Installation and After-Sales menu details: Code Parameter Units Description d.00 Maximum heating power kw PANTHER CONDENS 2 KKO 4 à 2 kw PANTHER CONDENS 25 KKV 5 à 8 kw PANTHER CONDENS 25 KKO / 30 KKV 6 à 25 kw Factory setting Parameter modifiable? d.0 Pump over-run time - heating min. Select a value between 2 and 60 minutes. 5 yes d.02 Anti-short cycle time delay after running in heating mode min. Prevents overly frequent burner start / stop in heating mode (this function does not apply to hot water mode). Select a value between 2 and 60 minutes. yes 20 yes This delay (called anti short-cycle) prevents an immediate restart in heating mode after the burner has been shut down by the temperature setting or by the TA. It depends on the temperature setting: - at 80 C, it if fixed (2 minutes). - at 20 C, it is adjustable from 2 to 60 minutes via data item d02 on the installer menu. Factory setting: 20 minutes. Temps (minutes) d02 = d02 = d02 = Température de consigne chauffage ( C) d.04 Tank temperature (if fitted with an NTC) (if a tank is installed) C Display of the tank water temperature (system models equipped with an NTC sensor). - read only d.09 Heating flow temperature setting (calculated value). C Display of the Heating flow temperature calculated by the TA ebus from the outside temperature and the slope chosen. read only d.0 Internal pump status. 0 = the pump is stopped = the pump is powered (it is running) read only The values with a green background are only accessible from the After-Sales menu (access code = 35) - 2 -

22 >>> Technical Specification... Code Parameter Units Description d. Auxiliary heating pump status (controlled by the option card) d.2 Unused d.3 Unused Heating request by an ON/OFF d.6 thermostat (connected to RT terminals of connector X7) d.7 Regulation type (outlet or return) C Lines d to d3 only appear if an option card is fitted and depend on the options selected. - 0 = the pump is stopped = The pump is requested 0 = contact open (no request) = contact closed (heating request in progress) NB : if the contact is shunted, the display is always. 0 = outlet = return Factory setting Parameter modifiable? read only - read only - yes Regulation on the return is useful for low inertia heated floor installations (without buffer tank): this type of regulation avoids burner shut-off when the temperature setting is reached too quickly. When regulation on the return is activated, the burner control is modified: The burner is forced to minimum power for 5 minutes then power regulation is authorised. Operating mode: d.8 Pump operation - 0 = With burner = Continuous with T.A. yes 2 = permanent in winter d.9 Pump speed - Operating mode: 0 = Burner lit; automatic speed in heating, max. in hot water, min. when the burner is off. = Min. speed in heating, max. in hot water 2 yes 2 = Automatic speed in heating, max. in hot water 3 = Max. speed in heating and hot water Operation of automatic speed: At each burner start in heating, the pump runs at reduced speed for at least 30 seconds. If the outlet/return temperature difference reaches 20K, the pump goes to max. speed until the burner shuts down (even if the temperature difference reduces). The same cycle occurs at the next ignition. d.20 Domestic Hot water max. temperature setting C The maximum recommended domestic hot water temperature is 60 C. Select a value between 50 C and 60 C. Note: The domestic Hot water temperature setting is adjustable by the user between 38 and 60 C. Factory setting = 55 C. d.2 d.22 The 2 following menus are displayed if an option card (not supplied) is installed on the appliance. Hot water preheating or tank reheating without NTC or thermostat request. Hot water request by thermostat, NTC or flow detector, without preheating request. d.23 Heating demand - d.25 Tank reheat or preheat request activated either by the interface (in hot water mode) or an e bus thermostat, or by a Timer (UK) = function authorised 0 = function not authorised 0: no dhw demand : dhw demand ( tap, tank ntc or tank switch) 0 = no heating demand = heating demand in progress The product configuration either does or does not allow tank reheating (timer in UK, Exacontrol 2009 with hot water programming): 0 = no authorisation for tank reheating = authorisation for tank reheating 60 yes - read only - read only - read only - read only The 2 following menus are displayed if an option card (not supplied) is installed on the appliance. Attributing a function to relay of the option card: = not applicable to this product d.27 Relay function - 2 = auxiliary heating pump 3 and 4 = not applicable to this product 5 = external gas valve 6 = = external error message yes The values with a green background are only accessible from the After-Sales menu (access code = 35)

23 >>> Technical Specification... Code Parameter Units Description d.28 Relay 2 function - Attributing a function to relay 2 of the option card: = not applicable to this product 2 = auxiliary heating pump 3 and 4 = not applicable to this product 5 = external gas valve 6 = external error message Factory setting Parameter modifiable? 2 yes d.33 Fan cut-off speed (calculated value) tr/min Multiply the value read by 00 to obtain r.p.m. - read only d.34 Real fan rotation speed tr/min. d.35 Position of 3-way valve (heating / DHW) Display of fan speed between 0 and 99. Multiply the displayed value by = domestic hot water 0 = heating 40 = centre position read only read only d.36 DHW flow rate l/min Flow rate measured by the hot water flow sensor read only The following menu is displayed if a solar system is connected to the appliance Displays the temperature measured by the sensor located d.39 Solar circuit inlet temperature C on the solar circuit inlet. - read only d.40 Heating flow temperature C Displays the heating output temperature. - read only d.4 Heating return temperature C Displays the heating return temperature. - read only Menus d.43, d.45 and d.47 only display if a wired outdoor thermostat is connected to terminal X7 of the main circuit board. Choice of heating curve depending on the outside d.43 Heating curve.2 yes temperature (see detail on following page) d.44 Ionisation check Coef. from 0 to 000 The lower this value (burner lit), the better the detection. However, this value depends on several parameters (gas quality, electrodes...) - read only d.45 Heating curve base C (See details, following page). Disappears for TA e-bus 20 yes d.47 Outdoor temperature C Displays the temperature measured by the outdoor sensor - read only d50 d5 Minimum speed correction. Maximum speed correction. tr/ min/0 tr/ min/0 Menus d50 and d5 are set at the factory The indicated value is multiplied by 0 and added to the theoretical minimum speed to give the minimum necessary speed. E.g.: d50 = 5 => Vmin = i.e. 350 rpm The indicated value is multiplied by 0 and subtracted from the theoretical maximum speed to give the maximum necessary speed. E.g.: d5 = - => Vmax = i.e. 690 rpm Depends on appliance Depends on appliance yes: 0 to 99 yes: - 99 to 0 The min. and max. speeds are different for each appliance. They depend on the manufacturing tolerances for each component. Therefore, it is not possible to give a standard setting. The factory setting is shown on the sticker on the silencer. This setting should only be re-entered if the main circuit board and option card are changed during after sales service. If only one card is changed, the new card copies the data from the other card. XXXX = Min. fan rotation speed 2 YYYY = Max. fan rotation speed Les lignes sur fond vert ne sont accessibles que par le menu SAV (code d accès = 35) 2 24 V

24 >>> Technical Specification... Installer Menu: The external sensor operation Setting is done using 2 parameters: - The sensor slope to be chosen on the curve below (): To know which slope to select, you need to know the local minimum temperature which was used for installation calculations. Choose the slope that gives the maximum heating setting at the local minimum temperature. See example below. Temperature setting Heating temperature ( C) With an e-bus thermostat (Exacontrol E...) the slope is set on the thermostat. This setting no longer appears in the boiler menu Outside temperature ( C) - Heating curve base correction (2): This parameter is used to correct the ambient temperature if the real temperature is different from the expected temperature. The factory setting (20 ) corresponds to an estimated ambient temperature. This value can be increased (up to 25 C) or reduced (down to 5 C). E.g.: desired temperature = 20 C, real temperature = 9 C => set to 2 C to offset the curve. Note: if the outside sensor is associated with a modulating thermostat, the curve base adjusts itself automatically With an e-bus thermostat (Exacontrol E...) the curve base adapts itself as needed. This setting no longer appears in the boiler menu Example: Either an installation equipped with radiators calculated according to the European standard NF EN 442 (Delta T between air and water = 50 degrees): the maximum heating temperature will then be 73 C (factory setting). Or a minimum local temperature of -6 C. In tracing on the diagram below the vertical from Text -6 C, then the horizontal to 73 C, we arrive at a slope of

25 >>> Technical Specification... Code Parameter Units Description d.62 Night-time offset (A different function to the thermostat comfort and eco period) C Reduces the heating output setting in accordance with the TA 24V status ex: if d62 is set at 20, Setting = 65 C if TA 24V on Setting = C = 45 C with TA 24V off 0 = function disabled Factory setting 0 Parameter modifiable? yes 0 to 30 C d64 Average burner ignition time S For these 2 values, an average calculated over the last 00 0 read only ignitions. d65 Max. burner ignition time S read only d.67 d68 d69 d.70 Time remaining until the end of the antishort cycle delay. Number of ignitions failed on the first attempt Number of ignitions failed on the second attempt Forcing of 3-way valve (AS version only) min. Displays time remaining until the end of the anti-short cycle delay. - read only - 0 read only - 0 read only - 0 = normal mode = do not use (blocking of the 3-way valve in the centre position) 2 = heating mode only 0 yes d.7 Max. Heating flow temperature setting. C Select a value between 50 and 80 C. (factory setting 75 C) 75 yes Note: The heating setting is adjustable via the user interface from 0 to 73 C. Factory setting = 60 C. This item allows limiting of the domestic hot water power (factory setting = max. setting). d.77 Domestic hot water power for AS boiler kw For F AS 25, the power is adjustable up to 25 kilowatts. However, given the circulator s performance, power is limited to a maximum of 20KW. For F AS 2, the power is adjustable up to 2 kw. d.80 Heating operating time d.8 Hot water operating time d.82 Number of burner ignitions in heating d.83 Number of burner ignitions in hot water 00h Blocks 00h Blocks 00 ign. blocks 00 ign. blocks Burner on operating time (00h block) = 00 hours Burner on operating time (00h block) = 00 hours P. max. of the model yes 0 read only 0 read only = 00 ignitions - read only = 00 ignitions - read only d.85 Minimum heating output kw This parameter increase the minimum output for the cases where the ignition is difficult. - yes d.90 Detection of an e-bus room thermostat - 0 = not detected = detected - read only d.93 Product code setting - Product code 2 yes Product codes: 2 KKO => 46 25KKO => KKV => KKO => 53 The values with a green background are only accessible from the After-Sales menu (access code = 35)

26 >>> Technical Specification... Code Parameter Units Description Factory setting Parameter modifiable? d.94 Reinitialise fault list - This function is used to clear the fault list on the appliance. 0 = no = reset fault list 0 yes d.95 Program versions C Gives the version of:. Main circuit board 2. Display card (Interface) - read only d.96 Return to factory settings - This function returns the parameters to the factory settings yes

27 >>> Technical Specification... The Installation and After-Sales menus by theme: Parameter Code read only Parameter Code read only Burner power Maximum heating output d.00 Domestic hot water power (AS boiler) d.77 Minimum output d.00 Regulation Regulation type (outlet or return) d.7 Heating curve d.43 Heating curve base d.45 Time delays Pump post flush time d.0 Anti short-cycle delay d.02 Anti short-cycle delay remaining d.67 x Temperature Tank temperature (if fitted with an NTC) d.04 x Heating flow temperature setting d.09 x Domestic Hot water max. temperature setting d.20 Solar circuit inlet temperature d.39 x Heating output temperature d.40 x Heating return temperature d.4 x Outside temperature d.47 x Max. Heating flow temperature setting. d.7 Pumps Heating pump status d.0 x Auxiliary pumps status d. x Pump operation d.8 Pump speed d.9 Checking of input requests Heating request by an ON/OFF thermostat d.6 x Hot water preheating or tank reheating without NTC or thermostat request. d.2 x Hot water request by thermostat, NTC or flow detector, without preheating request. d.22 x Heating demand d.23 x Tank reheating or preheating activated either by the interface or by an e-bus thermostat d.25 x Night-time offset d.62 ebus room thermostat detection d.90 x Fan Fan speed setting d.33 x Real fan rotation speed d.34 x Minimum speed correction d50 Maximum speed correction d5 Accessories Relay function d.27 Relay 2 function d.28 Statistics Average burner ignition time d64 x Number of ignitions failed on the first attempt d65 x Number of ignitions failed on the second attempt d68 x Heating operating time d69 x Hot water operating time d.80 x Hot water operating time d.8 x Number of burner ignitions in heating d.82 x Number of burner ignitions in hot water d.83 x Misc. Position of 3-way valve d.35 x Draw flow rate d.36 x Ionisation check d.44 x Heating demand d.23 x 3-way valve forcing (AS) d.70 Product code setting d.93 Reinitialise fault list d.94 Program versions d.95 x Return to factory settings d

28 >>> Technical Specification... Appliance status: This function can be used at any time to know what operating phase the appliance is in. To display this menu: Press the button of heating side ( ) for at least 3 seconds. The screen shows the appliance status S.xx. Press the mode button for at least 3 seconds to exit this menu. Status Heating mode S.00 No heating demand S.0 Fan pre-run S.02 Pump pre-run S.03 Ignition S.04 Burner lit S.05 Pump/fan post-run S.06 Fan post-run S.07 Pump post-run S.08 After-heating short cycle prevention delay Status Hot water mode S.0 Hot water demand S. Fan pre-sweep S.3 Ignition S.4 Burner lit S.5 Pump/fan post-run S.6 Fan post-run S.7 Pump post-run Status Hot water reheat (for system boilers connected to a tank) S.20 Pump pre-run S.2 Fan pre-run S.23 Ignition S.24 Burner lit S.25 Pump/fan post-run S.26 Fan post-run S.27 Pump post-run S.28 The heater locks out tank reheating after a reheat cycle (for minute) Status Specific messages S.30 Default condition, no heating or hot water demand. If an EBUS thermostat is connected to the heater, check that the shunt is present between connectors 3 and 4 of the heater main circuit board. S.3 Hot water only mode S.32 Test cycle: the extractor fan speed is outside tolerances when working S.34 Frost protection S.39 Heated floor contact open. S.4 Water pressure too high S.53 Wait cycle: difference in temperature between heating output and return too high. If T > 30, forced at Pmin S.54 Wait cycle: lack of water in the system / increase in temperature between heating output and return too high. S.96 Heating return temperature sensor test. S.97 Pressure test S.98 Water outlet and return temperature sensors test

29 >>> Technical Specification... Test modes: By activating the various test modes, you can access special functions on the appliance. Press the start/stop button to turn the appliance off. Hold down the mode and start/stop buttons for at least 5 seconds. The screen displays the first test mode P0. Press the or buttons of mode to select the desired test mode (P.0, P.02,...). Press mode to start the test mode. The test mode number «PX» and «On» flash on the screen. The test mode will stop automatically after 5 minutes. Once it ends, press the mode key for more than 5 seconds. Code n P.0 P.02 P.03 Parameter Force the burner to adjustable power in heating mode Force the burner to ignition pressure. Force the burner to power adjusted to d00 in heating mode P.05 Refill the appliance P.06 Air venting the installation P.07 Air venting the appliance Description The appliance operates at a power level adjustable from Pmin to 00% using the or buttons after a successful ignition. This function enables controls of the burner ignition. The appliance operates at adjusted maximum heating power. The 3-way valve is in the central position and the pump and the burner turn off for refilling the appliance. This function is activated for 5 minutes. --> The 3-way valve goes to the heating position. --> The pump operates in cycles of 5 seconds on / 5 seconds off. Ensure that the bleed valve is open. This function is activated for 5 minutes (4 minutes in DHW, minute in heating). --> The pump operates in cycles of 5 seconds on / 5 seconds off. Ensure that the bleed valve is open. This feature can be activated automatically when filling: if the pressure measured by the sensor passes from 0 to 0.5 b, the panel interprets this as a filling and activates the air venting device to prevent ignition of the burner when the exchanger is filled with air. In such a case, the pressure indication on the display will flash. However, if the transition from 0 to 0.5 bar is too fast (less than 5 seconds), the panel interprets this as a parasite and does not launch the function

30 >>> Technical Specification... Gas valve setting : 2 3 A combustion analyser is an essential tool for any work on the gas valve settings. Maximum power setting screw. 2 test point 3 Plug Gas valve setting: Service on the gas valve screw modifies the gas quantity for a given air flow rate (air/gas ratio). The direct result of this change is a change in the level of CO2 in the exhaust as the excess air varies. First remove the sealed panel. Remove the plug (3) from the test point (2) of the flue and connect a CO2 analyser. Here we are measuring on a vertical outlet duct. The same measurement on the elbow of a horizontal flue. Adjustment of the air/gas ratio is only done at peak power (refer to the test mode description in this chapter, after the description of the After-Sales menu). The recommended tool for this adjustment is a flat screwdriver or a 4mm spanner. The level of C02 required: Adjustment Model G20 G3 CO2 panel open F25 / F30 9 ± 0.2 % 0. ± 0.2 % CO2 panel closed F25 / F ± 0.3 % 0.3 ± 0.3 %

31 >>> Technical Specification... Change of gas type : Prepare the appliance as for a gas valve adjustment (see previous page), without running it (start/stop button on OFF). Preset the mechanism depending on the gas conversion to be performed. Change of gas type setting Model G20 G3 G3 G20 _ 25 KKV 2 turns 25 KKO 3 turns _ KKV 2 turns 25 KKO 3 turns Adjusting the maximum power Put the appliance into test mode P.0 : force burner to Pmax (00%). (Refer to the description of the test mode, in this chapter, after the description of the After-Sales menu). Wait for 5 minutes or so, until the CO2 reading has stabilized. Adjust the measured CO2 to the value given in the table below using the gas valve screw (). Change of gas type setting Model G20 G3 G3 G20 CO2 panel open F25 F30 0. ± 0.2 % 9 ± 0.2 % CO2 panel closed F25 F ± 0.3 % 9.2 ± 0.3 % Check the CO2 level in the combustion products. Stick the gas conversion label in its place () on the cover of the electric box. Indicate the type of gas connected on the sticker. 2 Return to service Replace the plug on the flue elbow. Replace the appliance sealed panel. Location of gas change sticker 2 Information plate - 3 -

32 >>> Installation... Heater location : side clearance: the panels are removed towards the front but a few mm are required at the side. However, it is not necessary to remove the side panels to maintain the appliance. 20 ØA + 5 min. ØA 20 min. 300 min. Attachment min. 20 min min. Boiler 2 Mounting bar 3 Template 4 Fixing jig

33 >>> Installation... Reminder of bathroom electrical protection zones 2 3 This range of boilers cannot be installed in zones 0, or 2. 3 m 2,25 m 2,25 m 0 0,60 m 2,40 m Water and gas connections: Heating return : 3/4 nuts 2 Cold water inlet : 3/4 nut 3 Gas : /2 nuts 4 Domestic hot water flow : 3/4 nut 5 Heating flow : 3/4 nuts 5 GAS

34 >>> Installation... Water and gas connections: Panther Condens KKO: Domestic hot water return : 3/4 nuts 2 Gas : /2 nuts 3 Domestic hot water flow : 3/4 nuts 4 Heating flow : 3/4 nuts 5 Heating return : 3/4 nuts 6 Tank 4 GAS

35 >>> Installation... Drain connections : Drain pipe 2 Condensate trap 2 Connect the condensate discharge hose () to a discharge circuit leading to the drain. Ensure that the condensates do not stagnate in the discharge circuit. Use PVC or other suitable materials to evacuate the non-neutralised condensates. Mild steel, galvanized steel and copper are not recommended, given the risk of corrosion. Observe the following installation precautions: - condensates must not be retained in the discharge pipe leading to the drain siphon - do not plunge the discharge pipe into the siphon s water tank OK The condensate trap is to be emptied periodically by flushing. The flushing is automatic by siphoning when the tank is full. For a correct functioning, the discharge pipe must not be submerged (in accordance with the above installation warnings). OK

36 >>> Installation... O P C E I I N M A 2000 D L H E B G F Repère Position of the exhaust end mm A Under a window 600 B Under an air vent 600 C Under a gutter 300 D Under a balcony 300 E From a nearby window 400 F From an adjacent air vent 600 G From vertical or horizontal drain pipes 600 Repère Position of the exhaust end mm H From a building corner 300 I From a building inside corner 000 L From the ground or another floor 800 M Between two outlets vertically 500 N Between two outlets horizontally 600 O From an adjacent air vent 600 P From a nearby roof window

37 >>> Installation... Exhaust connections: - If the exhaust is located within.80 of the ground, you must install an end protection kit. - The openings of a terminator for separate pipes must come out within a 50cm square. Horizontal exhaust system Ø 60/00 mm (type C3) Horizontal exhaust system Ø 80/25 mm (type C3) L L 63 Joint Each time an extra 90 elbow is needed (or 2 at 45 ), the length (L) must be reduced by m. Type Ø 60/00 Ø 80/25 Max length 0m 2m Vertical exhaust system Ø 60/00mm or Ø 80/25mm (type C33) Type Ø 60/00 Ø 80/25 Max length 0m 3m L Each time an extra 90 elbow is needed (or 2 at 45 ), the length (L) must be reduced by m

38 >>> Installation... Exhaust connections: Condensation flexible flue connection system (type C3S) This configuration allows reuse of an old flue or ventilation to install a sealed coiler duct. The length of the horizontal duct (L) is of the concentric type Ø 60/00. The length of the vertical duct (L2) is a flexible exhaust Ø 80mm. The air is drawn in through the flue duct. To prevent exhaust impurities being drawn in by the boiler air intake: Do not connect the appliance directly to a vertical outlet. Do not connect the appliance to a flue that was used for heating fuel products. L L2 D S Length of horizontal concentric duct Length of vertical duct Inside diameter of the flue Inside width of the flue S D S L L2 Type Max length (L +L2 S = 0 4,5m S 2 3m D = Ø30 8,m D Ø37 3m Each time an extra 90 is needed (or 2 at 45 ), the length (L) must be reduced by m. Exhaust system with collective duct Ø 60/00mm (type C43) - Make the connections to the collective duct using the accessories intended for this purpose. - A boiler connected to a type C4 installation must only be connected to flues with natural draw. - The flow of condensates from collective flue systems into the boiler is not allowed. L 4 Pressure balancer 2 Air supply duct 3 Collector duct 4 Boiler 5 Inspection hatch A Top floor B Ground floor L Max length Type Ø 60/00 Longueur max. 0m 3 2 A Each time an extra 90 elbow is needed (or 2 at 45 ), the length (L) must be reduced by m. B

39 >>> Installation... Exhaust connections : Double flow ventilation system 2 x Ø 80 mm (type C53) Any duct crossing a wall that exceeds the ambient temperature by more than 60 C must be thermally insulated at the site of this crossing. The insulation can be carried out using an appropriate insulating material with a thickness 0mm and a thermal conductivity 0,04 W/m.K (e.g.: glass wool). The terminals for combustion air intake and waste gas exhaust must not be installed on opposite walls of the building. Type Min length (L+L2) Max length (L+L2) 2 x Ø 80mm 2 x 0.5m 2 x 20m Each time an extra 90 is needed (or 2 at 45 ), the length (L) must be reduced by 2m. L L2 Double flow ventilation system 2 x Ø 80 mm for individual or collective flue (type C83) The flow of condensates from collective flue systems into the boiler is not allowed. Individual or collective flue The c83 exhaust connection is performed by piercing into an individual or collective flue (). The diameter of duct () is to be calculated depending on the total power of the appliances connected. Type Min length (L+L2) Max length (L+L2) 2 x Ø 80mm 2 x 0.5m 2 x 20m L L2 Each time an extra 90 is needed (or 2 at 45 ), the length (L) must be reduced by 2m

40 >>> Installation... Exhaust connections : Condensation flexible flue to pressurised chimney connection system (type B23P) In this configuration, the regulatory conditions relating to aeration must be complied with. This configuration allows reuse of an old flue or ventilation to install a sealed coiler duct. The length of the horizontal duct (L) is of the concentric type Ø 60/00. The length of the vertical duct (L2) is a flexible exhaust Ø 80mm. The fresh air is taken where the appliance is installed by way of a horizontal duct elbow (A). L L Length of horizontal concentric duct L2 Length of vertical duct A Horizontal duct elbow B Flexible duct elbow L2 Type Min length L Min length L2 Ø 60/00 0.5m - Ø 80 - m Max length L + L2 8 B Each time an extra 90 elbow is needed (or 2 at 45 ), the length (L + L2) must be reduced by m. A

41 >>> Installation... Electrical connections : Two hatches accessible from the electrical box cover can be used to connect various components. 2 5 Access for 24 V connection 2 24V connection terminals 3 230V connection terminals 4 Access for 230 V connection External accessories X7 X6 24 V BUS RT 24V BUS TANK 230 V T ext X V room thermostat connector Attention: do not connect 230V to this connector. In the case of an e-bus thermostat, leave the shunt in place on this connector. 2 E-bus room thermostat or e-bus wireless receiver connection 3 External temperature sensor connection 4 Heated floor overheat safety switch connector. Attention: In the absence of a heated floor overheat safety switch, these terminals must remain shunted (a shunt is already installed at the factory). 5 Exchanger tank with thermostat connection (for AS series versions). 6 Exchanger tank with temperature sensor connection (for AS series versions). 7 Connection to an e-bus roomstat : Exacontrol E In the case of an e-bus thermostat, leave the shunt in place on this connector. Exacontrol E 7 Exacontrol E 7 R X7 RT 24V BUS T ext Exacontrol E 7 R (2009) - 4 -

42 >>> Installation... Flow rate / pressure curve available at boiler outlet (heating side) : Panther Condens 2 KKO - 25 KKV A Pressure available between Heating flow and return (kpa) B Flow rate in the heating circuit (l/h) Speed min, bypass closed 2 Speed max, bypass closed 3 Speed max, bypass middle position 4 Speed max, bypass opened B Panther Condens 30 KKV - 25 KKO A Pressure available between Heating flow and return (kpa) B Flow rate in the heating circuit (l/h) Speed min, bypass closed 2 Speed max, bypass closed 3 Speed max, bypass middle position 4 Speed max, bypass opened Panther Condens 30 KKO A Pressure available between heating outlet and return (kpa) B Flow rate in the heating circuit (l/h) Speed min, bypass closed 2 Speed max, bypass closed 3 Speed max, bypass middle position 4 Speed max, bypass opened B B The flow rate in the installation can be modified with a bypass. Bypass screw

43 >>> Installation... Installation recommendations: Anti-corrosion and anti-sludge protection: To avoid any corrosion, it is recommended that you add a corrosion inhibitor to the heating circuit water. This inhibitor will prevent any electrical reactions between the different metals in the installation. As a consequence, it also prevents the formation of gasses that may be produced by chemical reactions. Water treatment is particularly important for plate heaters as the low temperature is favourable to bacterial growth. This can result in sludge that can block all or part of the circuit. For the dosage of these products, you must know the volume of water in the circuit. It is recommended that you make a note of this volume for future use. The inhibitors must be compatible with the materials used in the circuit. Bleeding the heating circuit: The boiler is equipped with an automatic bleed valve in the heating circuit. However, it may be useful to provide one or more additional bleed valves in the installation, particularly at the high points. This will make it possible to bleed the system more quickly. 2 Pump bleed valve plug 2 Pump 3 Pump shaft screw

44 >>> Installation... Check-list for commissioning a heater: Step Action Check - Before switching on. Check the electrical connections. 2 - Before pressurising 3 - Switch the appliance on, with no demand. 4 - Place the heating circuit under pressure. Check the expansion tank pre-inflation pressure. Deactivate heating and hot water using the control panel buttons. Un-stick the pump Open the taps on the fixing jig. Check that all heating circuit taps are open. Raise the pressure to 2 bar. (general power, connection of accessories, thermostat...) The tank may loose pressure, particularly if it has been stored for a long time. Water leaks. The air venting system must be activated (P07). The appliance is not available for 5 min. Warning: If the pressurisation lasts for less than 5 seconds (for example, by opening the connection plate valves when the installation is already pressurised), the automatic air venting function is not operable. Then it is advisable to start this sequence manually by means of the function P.07 (see section «test mode» in «Technical specification» chapter) before air venting the installation (next step). 5 - Bleed the air from the heating circuit. Reset the pressure after bleeding. Start test function P.06 (see test mode in Technical specification chapter). Open the heating and installation bleed valves. 6 - Bleed the domestic hot water circuit. Open the hot water taps on the installation to remove the air. 7 - Turn on the gas. Open the gas tap on the fixing jig. 8 - Boiler configuration at installation. 9 - Run the appliance in heating mode 0 - Run the appliance in domestic hot water mode - Explain the appliance to the end-user. Adjust the various parameters on the installation menu depending on the installation and the accessories. Set the heating flow rate through the bypass if necessary. Explain the main operations : ON/ OFF, RESET, filling the system, DHW and heating temperature adjustment, Take care that the end-user has his booklet. Carefully check for leaks with an electronic detector or soapy water. Check the value displayed on the After-Sales menu item d44 (ionisation quality). If this value drifts over time, it indicates a deterioration in flame detection. Check that the water circulates correctly and that the appliance shuts off correctly when reaching the temperature set. Check the exhaust circuit for leaks. Check that the heating flow rate is adequate. Check the hot water temperature. Ensure that it meets the user s requirements

45 >>> Maintenance... Service visit : List of recommended annual checks: Components Check Method Domestic hot water flow rate sensor Gas valve NTC Thermistors Flame detection (ionisation): Temperature regulation Pressure sensor Expansion tank Ignition of the burner for a domestic hot water flow rate of.5l/min Does the gas flow rate modulate correctly? Measure the resistance of each thermistor (2,500Ω at 20 C,,750Ω at 70 C) Ionisation quality Does the burner shut off at the end of regulation? Does the sensor stop the boiler if the pressure drops below 0.3 bar? Does the tank still contain gas? In the installer menu, line d36 indicates the domestic hot water flow rate. - Check that the burner properly ignites at the expected flow rate. - Check that the flow rate measured corresponds to reality. Draw off water at max. flow rate Reduce the draw rate until the burner goes off. Check that the gas flow rate follows. Disconnect the thermistors to measure the resistance. The ionisation quality can be checked with data item d44 of the After-Sales menu: Less than 300 with the burner lit = good detection Check that the burner shuts off when it approaches the setting (test to be performed in hot water mode at low flow rate) If possible, close the heating circuit isolation valves and drain the boiler until it shuts off. Check that the water pressure remains stable in operation. If not, check the tank pressure when empty. Also check: - combustion: measure the level of CO2 in the exhaust. Adjust the gas valve if necessary. - Check that there are no water leaks (at connections, safety valves, disconnect... ) - Check that there are no gas leaks (at connections, gas valve...) - the sealing of the exhaust ducts - the electrical ground connections Clean: - the burner: the burner gasket must be replaced each time it is removed - the main heat exchanger - the fan - the condensate tank () [remove (2), clean, rinse with water] - the heating filter (if necessary, clean the installation) - domestic hot water filter 2 The seals must be replaced each time they are removed

46 >>> Maintenance... Service visit: Additional operations during five-yearly visits. Components to clean: - heating valve (remove and rinse in water to remove any deposits) - Descale the plate heat exchanger The seals must be replaced each time they are removed. Check the fault history during the maintenance visit: It is important to check the fault history (see below) during the maintenance visit to see if any repetitive faults are occurring. Some faults do not display on the screen but are recorded in the log: - fault F22: lack of water pressure (the symbol appears, however, on the screen) - fault F49: voltage too low on the e-bus or short circuit on the e-bus connector Ionisation quality check: Check value d44 on the after-sales menu. If this value drifts from one maintenance to another, it indicates a deterioration in flame detection. (Note: This value is in a range of 0 to 000. The lower the value when the burner is lit, the better the detection. However, the value varies from one installation to another. Therefore, it is not possible to give a standard value. Fault history This menu displays the last 0 fault codes that have occurred on the appliance. To display the fault code history, press the and and mode buttons simultaneously for at least 3 seconds. The screen displays the first fault 0 F.xx. To display the other faults occurring on the appliance, press the button of mode. To erase the fault code history, refer to the Installer menu code 94. History Fault code 3 s 0 XX 02 XX... XX 09 XX 0 XX Data storage: The important data is stored on the main circuit board with a copy on the interface card. If one of these cards is changed during After Sales Service, the boiler data is automatically copied from the circuit remaining in place to the changed circuit. On the other hand, if you have to change both cards, it will be necessary to go through the entire After Sales menu and re-enter each data item

47 >>> Maintenance... Fault diagnosis help: Description Heating temperature sensor fault (NTC2,NTC5) DHW temperature sensor in the tank fault (NTC) Overheating fault (97 C measured by the Heating flow sensor) No water in the installation (< 0.3 bar) Maximum difference in temperature between heating output and return reached (35K). Water circulation fault (temperature rise greater than 0 K/s) Wrong flame detection. Fault code F00 F0 F0 F F3 F20 F22 F23 F24 F27 Cause Flow sensor (NTC2) disconnected Return sensor (NTC5) disconnected Flow sensor short-circuit (NTC2) Return sensor short-circuit (NTC5) Sensor short-circuit; or to the connector X6 is connected a jumper No water flow Leak in the installation Leak in the Pressure relief valve Expansion tank defective Water circulation problem Bad pump operation or low water Flame detection in spite of switched off gas valve. Ignition failure Flame failure during burner operation F28 F29 No or insufficient gas. Bad gas valve setting. Gas valve defective Igniter defective. Bad earth connection. ignition and flame control electrode defective. Air intake or exhaust fault. F32 Fan rotation speed incorrect EBUS voltage error F49 EBUS line fault Short circuit in EBUS connector Solution Check the sensor connections. Check the sensor cables check the sensor (characteristics in this chapter at Measurements ) Check that the pump is working correctly. Un-stick the pump. Check that the heating taps are open. Check the condition of the plate exchanger if the fault appears in hot water mode. Check the condition o the heating filter. Bleed the primary circuit. Refill and bleed the installation Check the expansion tank. Check that there are no leaks. Check the connections of the heater output and return sensors. Check the pump speed. See also solution for fault F20. See fault 20 or: Heating taps closed. Pump disconnected or stuck. Check the flame detection electrode Check the main circuit board. Check the igniter. Check the gas supply circuit (gas tap open). Check the gas valve. Check the adjustment of the gas valve. Check the igniter connection. Check the electrode condition (corrosion). Check the air intake and exhaust. Check the fan electrical connections Check the EBUS line voltage

48 >>> Maintenance... Fault diagnosis help: Description Fault code Cause Solution F6 Gas valve control fault Main circuit board fault F62 Gas valve closure fault Check all connections to the main circuit board F63 Main circuit board memory fault Check the electronic board. Rapid fluctuation of Heating flow or return F64 Check the product code. sensors. Reset the appliance. F65 Main circuit board temperature too high F67 Flame signal fault on the main circuit board Fluctuation of flame signal F68 See fault F28 See fault F28 User interface incompatible Check the product code. F70 Bad product code with main circuit board Check the card reference number. Heating flow temperature Heating flow sensor disconnected Check the sensor connections. F7 sensor fault or defective (no temperature change) Check that the sensor is clipped to the pipe. Permanent temperature Discrepancy between Heating flow and Check the temperature sensor connections difference between heater F72 return temperatures (permanent difference) Replace defective sensors. flow and return sensors Heating circuit pressure sensor fault Thermal fuse failure External accessory faults (not available when this document was printed) No water in the installation: no temperature increase with burner lit. Permanent temperature difference between heater flow and return sensors Heater flow and return sensors fault Disconnected contact of floor heating safety thermostat User interface fault (no display) F73 F74 F76 F77 Pressure sensor short-circuited or disconnected Pressure sensor electrical fault Thermal fuse disconnected. Thermal fuse defective External gas valve Condensate pump F83 Circuit not properly bled See fault F22 F84 F85 F86 - Flow and return temperature sensors inverted or disconnected. Temperature sensors faulty. Flow and return temperature sensors connected to the same pipe If there is connected a safety floor thermostat - the contact is open if not there is removed a jumper on contact X8 Interface card defective or bad connections. Check the sensor connections. Check the sensor Check the fuse and its connections. Check if the heat exchanger could have overheated. If necessary, replace it Check the accessory connections Check the temperature sensor connections Replace defective sensors. Check the temperature sensor connections Check if the safety floor thermostat is open. Check if there is on connector X8 a jumper present Check the main circuit board connection. Replace the interface card If no fault is displayed on the screen but : - The boiler does not start in heating mode => consult list of status codes in Technical specification chapter (this list indicates whether the panel receives a TA heating request, or whether the boiler is in a timer period, for example) => check the temperature readings of the different sensors => check the outdoorl sensor curve - The boiler does not start in hot water mode => consult list of status codes in Technical specification chapter => check the temperature readings of the different sensors

49 >>> Maintenance... INTERFACE FUS ON / OFF X2 X2 X3 X4 X5 X6 X7 X8 User interface Fuse Start/stop button General sensor connector: Cp Heating pressure sensor V3V 3-way valve Db Hot water flow rate detector 230V option card connector Not used on these models Pump (P) Not used on these models Optional tank connector Control accessories connector RT Connection for ON/OFF room thermostat E-bus Connection for modulating room thermostat (Exacontrol) Text Connector for a wired outside sensor Connector of floor heating safety thermostat X20 X2 X25 X30 X3 X32 X40 X5 X90 X0 General sensor connector: NTC2 Heating flow temperature sensor NTC5 Heating return temperature sensor K6 Heat exchanger thermal fuse Ve Fan EVS Gas valve safety valve Ignition and flame control electrode (AL) Not used on these models Exalink connector Not used on these models (UK timer) Solar connector Card 24V option connector User interface connector Not used on these models (factory use) Earth connector

50 >>> Maintenance... Panther Condens 25/30 KKV circuit diagram : X3 INTERFACE ON / OFF X5 X40 X32 X90 X30 X5 X7 X X FUS X2 X6 X8 RT e- bus T ext X X2 X3 X4 X0 X7 24 V Ebus NTC M N L 230 VAC P X X X Cp V3V Db K6 Ve EVS NTC2 NTC5 M AL

51 >>> Maintenance... Panther Condens 2/25/30 - KKO circuit diagram : X3 X40 X5 ON/OFF X32 X90 X30 X5 X7 X X FUS X2 X6 X X20 X X2 X3 X4 X0 NTC ON/OFF 24 V Ebus NTC M N L 230 VAC X X X M Cp V3V K6 Ve EVS NTC2 NTC5 AL - 5 -

52 >>> Maintenance... Measurements: Thermistor characteristics (NTC2 and 5) T C R (Ohms) V (Volts) , , , , , , , , , ,0 X X NTC5 2 NTC3 NTC2 Thermal fuse: The thermal fuse is single-use. It only triggers in the case of an abnormally high temperature in the heat exchanger(>60 C). Normal electrical resistance = 0 to 0 Ohms X K6 Heating pressure sensor: The pressure sensor is fed with 5VDC and it returns a voltage proportional to the circuit pressure. Pressure (bar) --> 0,3 0,5 0,7,0,3 Pins -3 of X2 (Volts) Pins -4 of X2 (Volts),3,4,5,7, Cp X

53 >>> Maintenance... Measurements: Gas valve: Resistance of servo safety valve = 5 ohms X EVS Operating phase: Ignition request Burner lit No request Electrical supply to gas valve: 24VDC at coil terminals (measurable between pins 9 and 8 of X20) The voltage is reduced to about 6V 0V In the event of a problem: If 0V: another fault is blocking the power to the gas valve. Check: - if a fault is displayed on the screen - check in the status list that the appliance is properly taking into account the request (list of statuses in technical specifications chapter) - if no fault detected, check the main circuit board If 24V: The servo safety valve is powered. Gas is therefore authorised. The fan (by its speed) controls the gas flow rate. Check: - the EVS coil resistance - the fan - blockage of the exhaust or air intake If 0V: see preceding case. Fan: 24Vdc between pins 6 and 7 of X20, in demand. Speed request (PWM) between 6 and 4 of X20. Speed feedback (S) between 6 and 3 of X20 X V PWM S 24Vdc Ve M

54 >>> Maintenance... Dismantling / reassembling Removal of the front Front panel 2 Front panel fastening screw Remove the 2 screws A. Pull the front panel down until it separates from the casing. Lift the front panel to release the upper couplings. C 24 V 230 V Access to the heating filter Domestic water exchanger attachment leg 2 Domestic water exchanger attachment screw 3 Gasket 4 Heating filter 5 Domestic water exchanger The heating filter improves the degassing of the heating circuit. A A B 2 Close the outgoing and incoming heating stop valves and drain the boiler. Remove the attachment screw (2) and leg (). Remove the domestic water exchanger (5). Remove the gasket (3). Remove the heating filter (4). Clean and replace. D E 3 4 B C 5 A 2 B A

55 >>> Maintenance... Dismantling / reassembling Access to the hot water filter The domestic water filter is directly attached to the flow sensor. To access this filter: Close the cold water input tap. Reduce the pressure by opening a hot water tap near the boiler. Remove the clip from the flow sensor. Pull the sensor forward to release it. Clean and replace

56 >>> Maintenance... Combustion block assembly (all models) : Gas valve connector 2 Ignition and flame control electrode holding screw 3 Ignition and flame control electrode connector 4 Ignition and flame control electrode holding screw 5 Ignition and flame control electrode gasket 6 Ignition and flame control electrode 7 Burner assembly mounting nut 8 Burner assembly mounting screw 9 Thermal fuse connector 0 Coil Heat exchanger 2 Burner gasket 3 Burner 4 Gas valve 5 Fan 6 Fan connector 7 Gas piping

57 >>> Accessoires... Some accessories compatible : Thermolink LUX: ebus 4 Wall support 2 Room thermostat 3 Circuit board present in the heating system 4 Wireless receiver connected to heating system 5 Wireless receiver connector 3 2 Thermolink LUX is a wireless modulating room thermostat. Its ambient temperature sensor allows precise temperature control. It can also adapt the curve of an exterior sensor to the building leakage, thus facilitating control. The receiver has a position inside the boiler casing. Its range is about 25m inside a building (00m outside). 5 Installer menu comments: (These comments relate to the block diagrams on the next two pages) () --> used to activate domestic hot water in the user menu: if OFF, the domestic hot water settings are not displayed. Programme: can be used to set up a weekly programme for the hot water function. This programming is basically provided for boilers with a tank and/or solar hot water production. (2) --> not applicable to boilers. (3) --> counting of free energy recovered when an installation has a heat pump or a solar system. Thermolink LUX will retrieve the information from the equipment via the e-bus connection (the equipment must therefore be compatible). (4) --> possibility of entering the After-Sales Service telephone number to be called in the case of a breakdown. This number will then be displayed on the screen. (5) --> this menu is used to associate the outside wireless sensor with the room thermostat. All the other thermostats in the Protherm range are compatible with Panther Condens : --> all ON / OFF or time-proportional thermostats --> all e-bus modulating thermostats in the Thermolink range

58 >>> Accessoires... Thermolink LUX: user menu. This menu is accessible by pressing the Menu button once. User Menu Heating Hot water ON / OFF Programme Temporary mods ON / OFF Temperature Programme Temporary mods. - activate (ON) - deactivate (OFF) - define (the times and ambient temperatures for each day of the week) - define a temporary modification (the temperature and the end time of the deviation) - deactivate the temporary modification - activate (ON) - deactivate (OFF) - Choice of hot water temperature, from 35 to 65 C - activate (ON) - deactivate (OFF) - define (the ON and OFF times for each day of the week). - define a temporary modification (the temperature and the end time of the deviation) - deactivate the temporary modification Absence Parameters - define an absence start and end time and date, the ambient temperature and whether the hot water is ON or OFF during the absence - deactivate the absence period- date (day, month, year) - time (hour, minutes) - language (choice of languages) - name of the appliance - lock keypad (activate / deactivate) note: to unlock: menu parameters lock keypad deactivate - screen (brightness / contrast) - reset (return to initial settings) - about (software version)

59 >>> Accessoires... Thermolink LUX: installer menu. This menu is accessible by pressing the Menu button for 7 seconds. A code is then requested. Enter 96 using the arrow buttons and then confirm with OK. Installer Menu Heating Max. ambient temp. Ambient temp. correction Set the maximum allowed ambient temperature Enter a correction if necessary ECS () Cooling (2) ON / OFF Maximum temperature Programme ON / OFF Programme - activate (ON) - deactivate (OFF) - Choice of maximum hot water temperature - activate (ON) - deactivate (OFF) - activate (ON) - deactivate (OFF) - activate (ON) - deactivate (OFF) Options External sensor adjustment - Outside temp. correction: correction from -5 to +5K in 0.5K steps - heating curve selection: 0.2 to 4.0 in steps of 0. Counters (3). Heat pump Solar - activate (ON) - deactivate (OFF) - activate (ON) - deactivate (OFF) - date (day, month, year) - time (hour, minutes) - language (choice of languages) - telephone (4) - about (software version) Wireless connection (), (2), (3), (4) and (5): see comments on previous page. Recognition (5) Test of wireless communication

60 >>> Accessoires... Wireless external sensor (ref ). This outside sensor operates with the Thermolink LUX. Its wireless communication with the thermostat receiver allows easy and rapid installation. It is equipped with a photovoltaic cell making it antonymous and maintenance-free. Its battery charges itself from just daylight, i.e. without receiving direct sunlight. In addition, it is delivered pre-charged. It s radio signal range is about 20m without obstructions. Its battery has a minimum autonomy of 30 days without solar top-up. Time interval between 2 communications with the base station: 5 minutes. Wired outdoor sensor (ref ). The boiler can accept a wired exterior sensor, to be wired to connector X7 of the main circuit board. In this case, the setting parameters for the sensor are found in the installer menu (d43 and d45). Outdoor temperature sensor characteristics : T C R (Ohms)

61 >>> Accessoires... Option card (ref ). The option card can manage: - a domestic hot water pump - an auxiliary heating pump - an external gas valve F.XX X3 INTERFACE ON / OFF X5 X40 X32 X40 B X90 OPT. X30 X5 X7 X X FUS X2 X2 A X6 X X X2 X3 X4 230 V ac - 6 -

WHE 2.24 / WHE 2.24 FF

WHE 2.24 / WHE 2.24 FF EN Wall-hung gas boilers WHE 2.24 WHE 2.24 FF User Guide 300011777-001-C . Contents 1 Introduction.............................................................................3 1.1 Symbols used...........................................................................................3

More information

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND Aqua Balance AquaBalance TM CONTROL MODULE QUICK START GUIDE 10 1 Domestic Hot Water temperature setpoint decreasing button 2 Domestic Hot Water temperature setpoint increasing button 3 Central Heating

More information

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production

Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production Divacondens D Plus Atmospheric condensation wall-mounted boilers, with instant domestic hot water production THE SIMPLEST SOLUTION FOR A CONDENSING BOILER DIVACONDENS D PLUS is the generator of condensation

More information

WALL-HUNG HIGH EFFICIENCY GAS BOILERS. Elegant, efficient and intelligent

WALL-HUNG HIGH EFFICIENCY GAS BOILERS. Elegant, efficient and intelligent CLAS HE WALL-HUNG HIGH EFFICIENCY GAS BOILERS Elegant, efficient and intelligent The high efficiency boiler that saves on energy and costs With specified intelligence, CLAS HE adapts to the householder's

More information

24-28 kw Conventional Combi Gas Boiler. Lawa / LawaPlus

24-28 kw Conventional Combi Gas Boiler. Lawa / LawaPlus 24-28 kw Conventional Combi Gas Boiler Lawa / LawaPlus Conventional Combi Gas Boilers Warmhaus wall-hung gas combi boilers Lawa and LawaPlus, with the advantage of its width as 288mm, are easily fit to

More information

1 VICTRIX ZEUS Superior kw I features

1 VICTRIX ZEUS Superior kw I features Wall-hung condensing VICTRIX ZEUS Superior kw I is the new range of wall-hung condensing boilers with 54 litre stainless steel storage tank available in two versions with nominal heat output of 26 kw and

More information

24/31-28/35-33/40 kw Premix System Condensing - ErP Combi Gas Boilers. Enerwa / EnerwaPlus.

24/31-28/35-33/40 kw Premix System Condensing - ErP Combi Gas Boilers. Enerwa / EnerwaPlus. 24/31-28/35-33/40 kw Premix System Condensing - ErP Combi Gas Boilers Enerwa / EnerwaPlus www.warmhaus.com Condensing-ErP Premix System Boilers 24/31-28/35-33/40 kw Warmhaus wall-hung gas combi boilers

More information

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power

VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 VICTRIX 115 Wall-hung condensing boilers for high power VICTRIX 90 is the new wall-hung condensing boiler for room heating only, set-up for independent functioning and for that in cascade mode

More information

RinNOVA. User manual and installation instructions

RinNOVA. User manual and installation instructions RinNOVA User manual and installation instructions Congratulations on your selection. WARNING Your modulating boiler is electronically adjusted and ignited. highly efficient sealed chamber with steel domestic

More information

DOMESTIC HOT WATER Follow operational sequence

DOMESTIC HOT WATER Follow operational sequence DOMESTIC HOT WATER Follow operational sequence Turn Winter/Summer selector to Summer position. The display is switch on. Go to section A Error 110 flashing Error 131 flashing Turn the selector to reset

More information

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C

WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) MODELS 34,8 kw (depotenziata) 50 C ALKON 50 C ALKON 70 C WALL HUNG GAS BOILER FOR C.H. AND PREDISPOSTION FOR INSTANTANEOUS D.H.W. PRODUCTION (with optional kit) OUTPUT RANGE from 50 to 560 kw (in battery) WORKING TEMPERATURE no limit on

More information

5 YEAR GUARANTEE. Inovia. High efficiency condensing combi and system boilers

5 YEAR GUARANTEE. Inovia. High efficiency condensing combi and system boilers * 5 YEAR GUARANTEE Inovia High efficiency condensing combi and system boilers WALL HUNG BOILERS Inovia INOVIA HIGH EFFICIENCY BOILER RANGE The Inovia range is the latest in intelligent gas boiler technology

More information

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19

OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER. Version DC19 OPERATION MANUAL RK-2006LPP AUGER FITTED SOLID FUEL BOILER TEMPERATURE CONTROLLER Version DC19 1. Application. Controller RK-2006LPP is designed for temperature control of solid fuel fired water boilers

More information

STM Department TRAINING MODULE. : instantaneous. Version 1.0, Jan 2006

STM Department TRAINING MODULE. : instantaneous. Version 1.0, Jan 2006 TRAINING MODULE Product group Group Project Name Sales designation Production unit : Wallhung boiler : instantaneous : MX2 COMFORT : : ST BRIEUC (France) Version 1.0, Jan 2006 - 2 - Update VERSION DATE

More information

C Tahiti. condensing

C Tahiti. condensing C 227-01 m a d e i n I ta ly Tahiti condensing Condensing, pre-mixed, wall-hung boilers KC 24 KC 28 - KC 32 indoor, instantaneous, combination boilers KR 24 KR 38 - KR 32 indoor, central heating only boilers

More information

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28 The competent brand for energy saving systems NEW Gas-combi boiler CGG-1K-24/28 Gas-combi boiler CGG-1K Technical data room sealed fannned flue model gas combi boiler for low temperature heating and d.h.w.

More information

VICTRIX Superior kw Export VICTRIX Superior kw X Export

VICTRIX Superior kw Export VICTRIX Superior kw X Export Wall-hung condensing VICTRIX Superior kw is the instantaneous sealed chamber wallhung boiler with power of 32 kw which, thanks to condensation technology, is characterised for its high efficiency and guarantees

More information

NIKE Star 24 3 E. Instantaneous wall-hung with open chamber boilers. NIKE Star 24 3 E

NIKE Star 24 3 E. Instantaneous wall-hung with open chamber boilers. NIKE Star 24 3 E Instantaneous wall-hung with open chamber boilers Small wall-mounted open chamber, conventional flue instant boiler. General features. is a wall-mounted, open combustion chamber, conventional flue generator

More information

HIGH OUTPUT. Skin design RANGE

HIGH OUTPUT. Skin design RANGE Light drop design HIGH OUTPUT Skin design RANGE Trim design 1 Product Introduction Product Presence Worlwide 2 Product Presentation Bosch Model Commercial Name: GWHC 27 3 Product Presentation Product Design

More information

RINNOVA COND. User manual and installation instructions

RINNOVA COND. User manual and installation instructions RINNOVA COND User manual and installation instructions Congratulations on your selection. WARNING Your modulating boiler is electronically adjusted and ignited. highly efficient; sealed chamber. Unlike

More information

24/31-28/35-33/40 kw Premix System Condensing Combi Gas Boilers. Priwa / PriwaPlus.

24/31-28/35-33/40 kw Premix System Condensing Combi Gas Boilers. Priwa / PriwaPlus. combi boilers panel radiators 24/31-28/35-33/40 kw Premix System Condensing Combi Gas Boilers Priwa / PriwaPlus www.warmhaus.com 1 Premix System Condensing Combi Gas Boilers 24/31-28/35-33/40 kw Warmhaus

More information

WALL-HUNG GAS CONDENSING BOILERS MCR-P 24/28 BIC. HOMOLOGATION B 23P - C 13x - C 33x - C 93x -C 53 - C 43x - C 83x *

WALL-HUNG GAS CONDENSING BOILERS MCR-P 24/28 BIC. HOMOLOGATION B 23P - C 13x - C 33x - C 93x -C 53 - C 43x - C 83x * VIVADENS MCR-P WALL-HUNG GAS CONDENSING BOILERS MCR-P 24: from 6.3 to 25.0 kw, for heating only MCR-P 24/BS 80 and MCR-P 24/BS 130: from 6.3 to 25.0 kw, for heating and domestic hot water production by

More information

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO

Great Britain en. Installation, user and service manual. Control panel HMI Gas 310/610 ECO PRO Great Britain en Installation, user and service manual Control panel HMI Gas 310/610 ECO PRO Dear Customer, Thank you very much for buying this appliance. Please read through the manual carefully before

More information

AVIO kw Export 1 FEATURES. Wall-mounted with storage tank

AVIO kw Export 1 FEATURES. Wall-mounted with storage tank 1 FEATURES Wall-mounted with storage tank Compact wall-mounted open chamber boiler with conventional flue and 45 litre stainless steel storage tank and nominal heat output of 23.7 kw (20,382 kcal/h). AVIO

More information

Bluehelix Tech Wall-hung premix condensing boilers, only heating or instant combi operation

Bluehelix Tech Wall-hung premix condensing boilers, only heating or instant combi operation Bluehelix Tech Wallhung premix condensing boilers, only heating or instant combi operation > EFFICIENT, RATIONAL & ROBUST CONSTRUCTION Ferroli s presence in wall hung boilers market has always been marked

More information

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40

USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 USER GUIDE VOGUE COMBI GEN2 C26 C32 C40 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

TAHITI CONDENSING KR 55 - KR 85

TAHITI CONDENSING KR 55 - KR 85 IST 03 C 351-01 TAHITI CONDENSING KR 55 - KR 85 GB INSTALLATION USE AND MAINTENANCE Dear Customer, Thank you for choosing and buying one of our boilers. Please read these instructions carefully. They will

More information

Rinnova Cond X. User manual and installation instructions

Rinnova Cond X. User manual and installation instructions Rinnova Cond X User manual and installation instructions Congratulations on your selection. WARNING Your modulating boiler is electronically adjusted and ignited. highly efficient; sealed chamber. Unlike

More information

SPECIFICATIONS - NIKE

SPECIFICATIONS - NIKE Wall-mounted instant boilers NIKE Mini kw Special is the ideal Immergas solution for modern building and wherever space is limited and has to be made the most of. Simple to use and easy to install, thanks

More information

HT V2 HT Split

HT V2 HT Split Scroll compressor Refrigerant R07C Aqu@Scop HT V Aqu@Scop HT Split High Temperature Air-to-Water Heat Pumps Models -, -7 and 8-9.0 to 7.9kW Aqu@Scop HT V / Aqu@Scop HT Split Installation examples - Single

More information

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM

INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM INSTALLATION AND OPERATING INSTRUCTIONS EVOLUTION EV HFM Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range of DOMUSA TEKNIK products you have chosen the Evolution EV HFM model. This

More information

24/31-28/35-32/40 kw Premix System Condensing Combi Gas Boilers. Priwa / PriwaPlus

24/31-28/35-32/40 kw Premix System Condensing Combi Gas Boilers. Priwa / PriwaPlus 24/31-28/35-32/40 kw Premix System Condensing Combi Gas Boilers Priwa / PriwaPlus 1 Premix System Condensing Combi Gas Boilers 24/31-28/35-32/40 kw Warmhaus wall-hung gas combi boilers Priwa and PriwaPlus,

More information

Service booklet for the Engineer for Gas Condensing Boilers

Service booklet for the Engineer for Gas Condensing Boilers Service booklet for the Engineer for Gas Condensing Boilers 6 720 610 577-00.10 ZWB 7-29 CC1 GC-Number: 47 108 05 ZB 7-28 CS1 GC-Number: 41 108 02 ZWB 7-27 HE combi GC-Number: 47 311 55 ZWB 7-25 HE combi

More information

WALL-HUNG HIGH EFFICIENCY GAS BOILERS

WALL-HUNG HIGH EFFICIENCY GAS BOILERS Heating Hot water Renewables GAS BOILERS E-COMBIevo E-SYSTEMevo CLAS HEevo CLAS HEevo system CLAS HE R WALL-HUNG HIGH EFFICIENCY GAS BOILERS Ariston a tradition that evolves For many years, we have entered

More information

5 YEAR ADVANCE PLUS WARRANTY. High efficiency condensing combi and system boilers

5 YEAR ADVANCE PLUS WARRANTY. High efficiency condensing combi and system boilers 5 YEAR WARRANTY ADVANCE PLUS High efficiency condensing combi and system boilers Android Apple WALL HUNG BOILERS Advance Plus ADVANCE PLUS HIGH EFFICIENCY BOILER RANGE The Advance Plus range is the latest

More information

Condensing, pre-mixed, wall-hung gas boilers with water tank

Condensing, pre-mixed, wall-hung gas boilers with water tank C 271-01 made in Italy Nias condensing Condensing, pre-mixed, wall-hung gas boilers with water tank Life-enhancing heat GB Condensing, pre-mixed, wall-hung boilers with water tank Nias CONDENSING HIGH

More information

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book

USER GUIDE. IMAX XTRA EL kW. For Installation Guide see reverse of book USER GUIDE IMAX XTRA EL 320-620kW For Installation Guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance

More information

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw

Superior. A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler. Outputs 120, 160, 200, 240, 280 kw Superior A Compact Floor Standing Gas Fired, High Efficiency Condensing Hot Water Boiler Outputs 120, 160, 200, 240, 280 kw 1 The Superior is a, pre-assembled floor standing, gas fired high efficiency

More information

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A... 70 80 99-00-O Residential Gas Condensing Boiler ZBR//8/35/4-3A... ZWB8/35/4-3A... 70 80 993 (03/03) CA/US Operating Instructions Contents Contents Key to symbols and safety instructions............................

More information

Technical Documentation

Technical Documentation Technical Documentation FEB-20E 09-2003 TECHNICAL DATA Model Category FEB-20E II 2H3P Type C 12,C 32,C 42,C 52 Maximum kw 23,8 Central Heating (C.H) Output Output kcal/h 20.468 Minimum kw 9,3 Output kcal/h

More information

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A cod. 6272262A GENERAL DATA Heating Data Heat Output Input (Adjustable) (Adjustable) Format 34i 11.2 34KW 45 145MJ/hr Format 34e 11.2 34KW 45 145MJ/hr General Specifications FORMAT 34i 34e Main burner injectors

More information

CONTENTS PRODUCT GAS TYPE CONVERSION ADJUSTMENTS FAULT & FAILURE. Product Notation Safety Systems Technical Data Main Components Operating Functions

CONTENTS PRODUCT GAS TYPE CONVERSION ADJUSTMENTS FAULT & FAILURE. Product Notation Safety Systems Technical Data Main Components Operating Functions 24 kw Open Flued Gas Combination Boiler (bithermic type) 24 kw Room Sealed Fan Assisted Gas Combination Boiler (bithermic type) 24 kw Room Sealed Fan Assisted Gas Combination Boiler (monothermic type)

More information

ALKON CARGO. A precise and fast delivery rate. A very high specific flow rate (20 litres per minute with Dt 25)

ALKON CARGO. A precise and fast delivery rate. A very high specific flow rate (20 litres per minute with Dt 25) ALKON CARGO ALKON CARGO model Max/min nominal output Heat input condensing Non-condensing η condensation at 30 part load 35 7,4 35,1 6,7 33,5 34,8 106,3 Efficiency class (directive 92/42) ALKON CARGO is

More information

INSTRUCTION FOR THE USER THC V E OIL BLU

INSTRUCTION FOR THE USER THC V E OIL BLU INSTRUCTION FOR THE THC V E OIL BLU CONTENTS General safety information 4 Precautions 4 Control panel 5 Mode selection 8 User levels 10 Start-up 12 Temporary shutdown 15 Preparing for extended periods

More information

ENERGY TOP. Condensing boiler solutions

ENERGY TOP. Condensing boiler solutions ENERGY TOP Condensing boiler solutions 1 ENERGY TOP > ENERGY TOP RANGE A wide array of flexible solutions both for centralised residential application and big commercial plants The increasing need for

More information

Quinta Pro Range. The New Remeha. Condensing Boilers REMEHA QUINTA PRO RANGE. High efficiency wall hung condensing boiler with ultra low NOx emission

Quinta Pro Range. The New Remeha. Condensing Boilers REMEHA QUINTA PRO RANGE. High efficiency wall hung condensing boiler with ultra low NOx emission The New Remeha Quinta Pro Range Condensing Boilers REMEHA QUINTA PRO RANGE HIGH EFFICIENCY 110% NCV AT 40/30 C FULLY MODULATING BOILER CONTROL PREMIX BURNER CLEAN COMBUSTION ULTRA LOW NOx BREEAM EXCELLENT

More information

Installation & User s Instructions

Installation & User s Instructions Installation & User s Instructions 8 080 shown Part No. 00 day Wired Digital Programmer & Room Sensor Part No. 080 day Wireless Digital Programmer & Room Sensor Part No. 00 hr Wireless Digital Programmer

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass HM model. With a suitable

More information

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber

User Manual RBS 24. for model CE series ENERGY. Wall mounted instantaneous combi boiler room sealed chamber User Manual for model RBS 24 series ENERGY Wall mounted instantaneous combi boiler room sealed chamber CE 0694 RBS 24 - SERIE ENERGY - RAD - ING - MAN.UT - 1407.1 - DIGITECH TR - MIAH6 - E04 Technical

More information

Quickheat 30 weather compensated boiler control

Quickheat 30 weather compensated boiler control Quickheat 0 weather compensated boiler control A compact and sophisticated heating controller The compact KM controller is designed for the control of fan assisted boilers with modulating burners. The

More information

USER GUIDE VOGUE MAX SYSTEM

USER GUIDE VOGUE MAX SYSTEM USER GUIDE VOGUE MAX SYSTEM 15 18 26 32 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not

More information

INSTALLATION AND OPERATING INSTRUCTIONS AVANTTIA

INSTALLATION AND OPERATING INSTRUCTIONS AVANTTIA INSTALLATION AND OPERATING INSTRUCTIONS AVANTTIA CGM-04/392 ER-0170/1996 Thank you for choosing a DOMUSA TEKNIK heating boiler. From the range of DOMUSA TEKNIK products you have chosen the Avanttia model.

More information

for Gas Condensing Boilers

for Gas Condensing Boilers Service booklet for the Engineer for Gas Condensing Boilers 6 720 611 400-00.1O ZWBR 7-30 R 30 HE plus combi GC-Number: 41 311 79 ZWBR 11-35 R 35 HE plus combi GC-Number: 41 311 80 ZWBR 11-40 R 40 HE plus

More information

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5 4 ±0.5 12.0 Servicing 12.2 Annual Servicing Inspection (Cont) Flame Sensing 5 ±1 10 ±1 Position Fig. 45 Spark Ignition 5. Remove the clip securing the gas feed pipe to the air/gas venturi. Disconnect the

More information

ir-range 8G /03.15 Changes reserved.

ir-range 8G /03.15 Changes reserved. U s e r m a n u a l ic-range is-range ir-range 8G.52.80.00/03.15 Changes reserved. Contents 1. Introduction...3 2. Safety...5 3. Boiler description...6 4. Display and functions...7 4.1 DHW and Heating

More information

BG2000S PRE-MIX GAS BURNER

BG2000S PRE-MIX GAS BURNER BG000S PRE-MIX GAS BURNER INSTALLATION OPERATION & MAINTENANCE DOCUMENTATION STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 08707 707 77 FAX: 08707 707 767 E-MAIL:info@stokvisboilers.com

More information

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en 8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................

More information

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book

USERS GUIDE. Esprit eco 24, 30. For installation guide see reverse of book USERS GUIDE Esprit eco 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification

More information

Air Comfort. Installation instructions (English) A

Air Comfort. Installation instructions (English) A Air Comfort Installation instructions (English) WWW.BRINKAIRFORLIFE.NL 614788-A This appliance may be used by children as of 8 years of age, persons of reduced mental or physical capacities and those of

More information

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE)

INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) INSTALLATION AND OPERATING INSTRUCTIONS BIOCLASS HM OD (FOR EXTERNAL USE) Thank you for choosing a DOMUSA TEKNIK heating boiler. Within the product range offered by DOMUSA TEKNIK you have chosen BioClass

More information

VICTRIX 50 1 SPECIFICATIONS. Wall mounted condensing boilers

VICTRIX 50 1 SPECIFICATIONS. Wall mounted condensing boilers Wall mounted condensing boilers VICTRIX 50 is the new wall-mounted central heating condensing boiler. It is pre-arranged for single and cascade operation (up to 3 appliances connected), with the advantage

More information

User Manual for model

User Manual for model User Manual for model RKA 24 /20 Wall mounted storage combi boiler premix condensing boiler CE 0694 Technical specification RADIANT BRUCIATORI S.p.A. Montelabbate RKA 24.20 - RAD - ING - MAN.UT - 1309.1

More information

Logic+ Combi

Logic+ Combi USER GUIDE Logic+ Combi 24 30 35 When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use

More information

MAINTENANCE AND SERVICE GUIDE

MAINTENANCE AND SERVICE GUIDE c MAINTENANCE AND SERVICE GUIDE Fanned Flue Condensing Central Heating System Boiler 24 and 30 Dimensions Outer case dimensions : - Width : 440 (minimum space required 450) - Height : 850 - Depth : 380

More information

wall-mounted boilers, water heaters and pool heaters floor standing boilers, water heaters and pool heaters

wall-mounted boilers, water heaters and pool heaters floor standing boilers, water heaters and pool heaters MADE IN ITALY THE EXPERT of stainless steel condensing heating systems ECO FRIENDLY wall-mounted boilers, water heaters and pool heaters floor standing boilers, water heaters and pool heaters AISI 6Ti

More information

User manual and Installation instructions

User manual and Installation instructions Wall hung, fanflue, roomsealed, high efficiency gas boiler User manual and Installation instructions ADVANCE Models G.C. Appl. No. ADVANCE 25C 47-583-43 COMBI BOILER ADVANCE 30C 47-583-44 COMBI BOILER

More information

ELECTRIC BOILERS FOR CENTRAL HEATING

ELECTRIC BOILERS FOR CENTRAL HEATING ELECTRIC BOILERS FOR CENTRAL HEATING TermoMax INSTRUCTIONS FOR INSTALLATION INSTRUCTIONS FOR INSTALLATION We reserve the right of alternations WE ARE NOT LIABLE FOR DAMAGES RESULTING FROM NON- OBSERVING

More information

MAX O GAZ. Condensing water heater TECHNICAL MANUAL

MAX O GAZ. Condensing water heater TECHNICAL MANUAL MAX O GAZ Condensing water heater TECHNICAL MANUAL 2 CONTENTS THE COMPONENTS OF THE MAX O GAZ.. 1 4 BALANCED FLUE AND CONVENTIONAL FLUE MAX O GAZ FEATURES. 3 6 INSTALLATION OF THE MAX O GAZ... 5 8 STANDARD

More information

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use GB122 Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C For trade use Please read thoroughly before attemting to diagnose fault 7217 4900 (03/2010) GB/IE List of contents

More information

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use GB122 7210 1300-12/2002 GB(EN) For trade use Servicing manual Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C Please read thoroughly before attempting to diagnose fault List of contents

More information

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance

HOT AIR GENERATOR WITH GAS BURNER NA11.45 A GGS. Installation Operation Commissioning Maintenance Installation Operation Commissioning Maintenance HOT AIR GENERATOR WITH GAS BURNER GGS NA11.45 A 06-2011 04-2011 CONTENTS 1. DESCRIPTION OF THE UNIT 2. INSTALLATION & CONNECTION 3. COMMISSIONING 4. CARE

More information

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000 M SERIES M116 / M45 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS Type : B23 Country BE CH ES FR GB IE IT LU NL PT Category I2E(R)B I2H I2H I2Esi I2H

More information

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions.

User Manual FLOWMAX-90. for model. Condensing water heater 85,000 BTU. Installation, operating, commissioning and maintenance instructions. User Manual for model FLOWMAX-90 Condensing water heater 85,000 BTU WARNING If the information in these instructions is not followed exactly, a fire or explosion may result, causing property damage, personal

More information

AGUAdens TM 100% residential condensing D.H.W. wall-mounted water heaters ( litres) AISI 316 D.H.W. WORKING PRESSURE TITANIUM CONDENSING

AGUAdens TM 100% residential condensing D.H.W. wall-mounted water heaters ( litres) AISI 316 D.H.W. WORKING PRESSURE TITANIUM CONDENSING MADE IN ITALY residential condensing D.H.W. up to 10 bar WORKING PRESSURE AISI 316 Ti TITANIUM D.H.W. 100% CONDENSING AGUAdens TM wall-mounted water heaters (16-22 -37 litres) AGUAdensTM INSTANTANEOUS

More information

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing

Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing Stokvis R600 LMS IP Water Heater Gas-Fired Floor Standing Condensing Water Heater Supplement STOKVIS ENERGY SYSTEMS 96R Walton Road East Molesey Surrey KT8 0DL Tel: 020 8783 3050 / 0870 7707747 Fax: 020

More information

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT

ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT ECONOFLAME R6000 GAS FIRED CONDENSING HOT WATER HEATER SUPPLEMENT DOC1066 GB STOKVIS ENERGY SYSTEMS 96R WALTON ROAD EAST MOLESEY SURREY KT8 0DL TEL: 08707 707 747 FAX: 08707 707 767 E-MAIL:info@stokvisboilers.com

More information

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI

MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI Vivadens EN Wall-hung gas condensing boilers MCR 24 MCR 24/28 MI MCR 30/35 MI MCR 34/39 MI User Guide 300015874-001-B Contents 1 Introduction...4 1.1 Used symbols...4 1.2 Abbreviations...4 1.3 General...4

More information

Q - Series Boiler. Troubleshooting Manual

Q - Series Boiler. Troubleshooting Manual Q - Series Boiler Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized

More information

The iqe Boiler Range. Combination and System T Boilers.

The iqe Boiler Range. Combination and System T Boilers. The iqe Boiler Range Combination and System T Boilers www.iqe.co.uk iqe - Max Technology Max Efficiency iqe is a select group of partners that have come together to create a unique product range of highly

More information

wall-mounted boilers, water heaters and pool heaters from 15 kw to 140 kw

wall-mounted boilers, water heaters and pool heaters from 15 kw to 140 kw MADE IN ITALY THE EXPERT of stainless steel condensing heating systems ECO FRIENDLY wallmounted boilers, water heaters and pool heaters from 15 kw to 140 kw floor standing boilers, water heaters and pool

More information

WALL-HUNG HIGH EFFICIENCY GAS COMBINATION BOILERS. Efficient, economical and easy

WALL-HUNG HIGH EFFICIENCY GAS COMBINATION BOILERS. Efficient, economical and easy E-COMBI WALL-HUNG HIGH EFFICIENCY GAS COMBINATION BOILERS Efficient, economical and easy Reliable, advanced Easy to install Easy installation, commissioning and servicing The E-COMBI range has been designed

More information

Sirius FS. Working towards a cleaner future

Sirius FS. Working towards a cleaner future Sirius FS Floor Standing Stainless Steel Condensing Boilers Single Boiler Applications: 50 to 160kW Modular Boiler Applications: up to 640kW Working towards a cleaner future heating specialists 1. Product

More information

Settings and Maintenance of the CombinAir

Settings and Maintenance of the CombinAir Atmos CombinAir Settings and Maintenance of the CombinAir Issue 13.8.10 Operation and commissioning: The control unit on the front of the CombinAir is used to adjust the settings during commissioning.

More information

Project Name: Location: Engineer: Contractor: I. GENERAL

Project Name: Location: Engineer: Contractor: I. GENERAL Part I - General Part II - Product Part III - Installation Project Name: Location: Engineer: Contractor: I. GENERAL I. PRODUCT Rep: Date: A. Supply and install modulating and condensing boiler(s) as specified

More information

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE Release January 2001 CONTENTS 1.0 GENERAL CHARACTERISTICS... 4 1.1 MAIN CHARACTERIS TICS... 4 2.0 USER INTERFACE (CODE C5121230)... 5 2.1 DISPLAY... 5 2.2 MEANING OF THE LEDS...

More information

Bluehelix Tech RRT Wall-hung condensing boiler with Ferroli Thermobalance heat cell

Bluehelix Tech RRT Wall-hung condensing boiler with Ferroli Thermobalance heat cell Bluehelix Tech RRT Wall-hung condensing boiler with Ferroli Thermobalance heat cell BLUEHELIX TECH RRT... EVOLUTION GOES ON The generator range comes with the well-tested AISI 304 stainless steel exchanger.

More information

System Installation. multi-zone heating

System Installation. multi-zone heating System Installation multi-zone heating Table of contents INTRODUCTION 1 Instructions guidance... 2 1.1 Product documentation...2 1.2 Associated documents...2 1.3 Explanation of symbols...2 1.4 Guarantee

More information

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc Mikrofill Ethos Condensing combination boiler Maintenance Instructions 24cc IMPORTANT Benchmark Installation, Commissioning and Service Record Log Book is enclosed in your customer information pack. This

More information

/2010 US/CA

/2010 US/CA 6 720 646 148-11/2010 US/CA (en) For the user User s Instructions Condensing gas boiler Logamax plus GB162-L.B. 80 kw/100 kw Please read thoroughly before operating This manual is available in the English

More information

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER

Combi C30 & C35. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER Combi C30 & C35 User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS COMBINATION BOILER When replacing any part on this appliance, use only spare parts that you can be assured confirm

More information

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. 1 MHG Heating Ltd ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual. Unit 4 Epsom Downs Metro Centre, Waterfield, Tadworth, Surrey, KT20 5LR Telephone 08456 448802 Fax 08456 448803

More information

80-140 80-180 95-260 70-360 65-400 65-500 Installation User and Service Manual TM your installer TM Warning Read this manual carefully before first using the water heater. Failure to read this manual and

More information

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017

i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book UIN A05 October 2017 24 1 2 23 3 4 5 20 6 I 19 7 18 8 9 15 14 11 13 12 i 24, i 30, i 35 combination boilers USER GUIDE For Installation Guide see reverse of book i 24 OFF MAX E STATUS BURNER RESET MIN PRE MIN MAX HEAT PREHEAT

More information

Seradens Super Seradens Super Plus

Seradens Super Seradens Super Plus Premix Full Condensing Combi Boilers Seradens Super Seradens Super Plus 20-28 - 36 kw THE FIRST CONDENSING TECHNOLOGY BOTH IN HEATING AND DOMESTIC HOT WATER IN TURKEY Smaller, more elegant and efficient

More information

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS G 2000-S 25-35 - 45-55 60-70 - 100 (V13) 1 Index WARNINGS GAS FLOW RATE DIMSIONS SETTINGS PARAMETERS SERVICING THE URNER 3 8 13 OPERATING DESCRIPTION

More information

System Installation HYBRID BACK-UP

System Installation HYBRID BACK-UP System Installation HYRID CK-UP TLE OF CONTTS INTRODUCTION 1 Instructions guidance... 2 1.1 Product documentation...2 1.2 ssociated documents...2 1.3 Explanation of symbols...2 1.4 Guarantee registration...2

More information

User Manual for model

User Manual for model User Manual for model RKA 24/8 RKA 24 RKA 28 RKA 34 Wall mounted storage combi boiler premix condensing boiler User instruction CE 0694 RKA 24.8_24_28_34 - RAD - ING - MAN.UT - 1104A - DIGITECH 2 - REGNO

More information

PELLET BURNER PV 350

PELLET BURNER PV 350 PELLET BURNER PV 350 INSTRUCTION MANUAL v1.1 1 PRODUCT DESCRIPTION...3 2 SAFETY RULES...3 3 WARNINGS...4 4 INSTALLATION INSTRUCTIONS...5 4.1 BOILER REQUIREMENTS...5 4.2 PELLET CONTAINER...6 4.3 INSTALLATION

More information

DIDACTIC MANUAL FAMILY: GROUP: MODELS: VERSIONS: PART NO.: AST 14 C 261/00. Wall-hung atmospheric boilers. Instantaneous type with Forced Draught

DIDACTIC MANUAL FAMILY: GROUP: MODELS: VERSIONS: PART NO.: AST 14 C 261/00. Wall-hung atmospheric boilers. Instantaneous type with Forced Draught DIDACTIC MANUAL FAMILY: Wall-hung atmospheric boilers GROUP: MODELS: VERSIONS: Instantaneous type with Forced Draught Delfis-Antea Mono-thermal Indoor and built-in installation PART NO.: AST 14 C 261/00

More information

Operating instructions

Operating instructions The energy you need Operating instructions Betacom 3 24c -A (H-GB) 30c -A (H-GB) GB, IE Contents Contents 1 Safety... 3 1.1 Action-related warnings... 3 1.2 Intended use... 3 1.3 General safety information...

More information