90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA,

Size: px
Start display at page:

Download "90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA,"

Transcription

1 90.1 and Designing High Performance Commercial Kitchen Ventilation Systems BY DON FISHER, P.ENG., RICH SWIERCZYNA, The energy intensity associated with operating commercial kitchen ventilation (CKV) systems is well recognized within the HVAC design community and food service industry. This operating cost burden has stimulated energy efficiency design concepts in recent years, including the application of demand-controlled kitchen ventilation (DCKV). 1 Over the past two and a half decades, ASHRAE Technical Committee 5.10, Kitchen Ventilation, developed and maintained a robust Handbook Chapter 2 while its affiliated Standing Standards Project Committee (SSPC) 154 has promulgated a ASHRAE Standard 154, Ventilation of Commercial Cooking Operations. This standard has been a catalyst and technical foundation for overhauling the kitchen ventilation section in the International Mechanical Code (IMC). 3 Effective 2010, ASHRAE Standard 90.1, Energy Standard for Buildings Except Low-Rise Residential Buildings, has embraced specific requirements for commercial kitchen ventilation. Subsequently, California Title 24 incorporated similar requirements commencing in Unfortunately, the industry effort to increase the energy efficiency of CKV systems has not had a corresponding impact on improving thermal comfort within kitchens. In striving to reduce energy consumption, engineers have had a long-standing tendency to minimize (or avoid) tempering makeup air, often compromising thermal comfort in the kitchen. Everyone (from employees to design professionals) has acknowledged that commercial kitchens represent a hot working environment, but documentation of sensible and radiant temperatures in commercial kitchens did not exist within the public domain. In response, ASHRAE funded a research project titled Thermal Comfort in Commercial Kitchens 5 that quantified the relatively extreme thermal conditions in 100 commercial kitchens (Figure 1). Don Fisher, P.Eng., is... Rich Swierczyna is... 54

2 Reprinting of this proof for distribution or posting on web sites is not permitted. Authors may request from the editor an electronic file of the published article to reprint or post on their website once the final version has been published. TECHNICAL FEATURE The goal of this article is to discuss the new standard 90.1 requirements in context with designing energy efficient CKV systems that strive to improve comfort conditions in kitchens. Complementary to this article is a publication by the Department of Energy, which also reviews the requirements in Standard 90.1 for kitchen exhaust. 6 Readers are invited to download PHOTO 1 Need caption. this publication as a complement to our perspective on high-performance CKV systems. And just what does high performance mean with respect to a CKV system? We believe that it means a system where the exhaust hood completely captures and contains cooking effluent, where the associated noise levels and energy costs are minimized, and where thermal comfort in the kitchen is consistent with good engineering practices and workplace standards. The format we have chosen for this article is to copy the appropriate sections in Standard 90.1 (shown in italics), followed by our interpretation and supporting industry information. In some cases, we also have paraphrased rational that was included in the foreword to the public review draft of this addendum as it no longer resides within the Standard Commercial Kitchen Exhaust Systems Replacement air introduced directly into the hood cavity of kitchen exhaust hoods shall not exceed 10% of the hood exhaust airflow rate. This first requirement ends the practice of specifying short-circuit hoods, where large percentages (up to 80%) of the replacement (makeup) air is introduced directly into the hood reservoir. Research conducted by the authors 7 confirmed the hypothesis that air introduced directly into the hood cavity competes directly with the thermal plume rising from the cooking equipment, thus requiring an exhaust rate that is higher than that needed to capture and contain (C&C) this thermal plume by itself. Laboratory tests under various configurations of appliances and hoods demonstrated that when the volume of short-circuit air exceeded 10% of the exhaust airflow, the hood would fail to capture and contain. From that point on, any increase in the quantity t o ( F) Zones: Cooking Dishwashing Preparation Casual Institutional QSR FIGURE 1 Average of operative temperature for kitchen type and kitchen zones with 95% confidence interval (100 kitchens). 5 of makeup air introduced into the hood reservoir required a proportional increase in the exhaust rate to maintain C&C. Anecdotally, this has been referred to as the bathtub effect, where the size of the drain [exhaust collar] must to be large enough to accommodate all water pouring into the tub [hood]; otherwise the tub overflows [spills]. While the 10% value from this research (stated earlier) coincides with the 10% maximum stated in , another reason to permit 10% of the replacement air requirement to be supplied directly into the hood cavity is to allow what can be described as high-velocity, low-flow air curtains. This is a design feature of some manufacturers that has been incorporated around the inside perimeter of hoods to enhance capture and containment by essentially extending the lower edge of the hood. As such hoods may be interpreted as a short-circuit design by the AHJ, the threshold limit of 10% clearly permits the specification of these hoods. NOVEMBER 2014 ashrae.org ASHRAE JOURNAL 55

3 Conditioned supply air delivered to any space with a kitchen hood shall not exceed the greater of: a) the supply flow required to meet the space heating or cooling load b) the hood exhaust flow minus the available transfer air from adjacent spaces. Available transfer air is that portion of outdoor ventilation air not required to satisfy other exhaust needs, such as restrooms, and not required to maintain pressurization of adjacent spaces. The rationale behind this requirement is to capitalize on available transfer air (that originated as outside air and has already been heated or cooled) as a contribution to the replacement air requirement of the exhaust hood, potentially reducing the size and energy consumption of the dedicated makeup air unit. In some cases, transfer ducts and/or fans may be incorporated within the design to meet this requirement. In other cases a dedicated MUA unit may be a more cost-effective option and the designer may need to argue that the transfer air was not available from a practical perspective. This is particularly true when the occupancy schedule of the adjacent space is not in sync with operation of the exhaust hood. Section applies to the design of all CKV systems, regardless of airflow capacity, while the following requirements apply only to CKV system design where the exhaust rate exceeds 5,000 cfm (2360 L/s) If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5,000 cfm then each hood shall have an exhaust rate that complies with Table If a single hood is installed over appliances with different duty ratings, then the maximum allowable flow rate in each section of the hood shall not exceed the Table values for the appliance duty ratings in that section of the hood. Refer to ASHRAE Standard for definitions of hood type, appliance duty, and net exhaust flow rate. The 5,000 cfm (2360 L/s) threshold was established to exempt smaller restaurants where the cost-effectiveness of the energy efficiency requirements could be challenged. The facility has a total kitchen hood exhaust airflow rate greater than 5,000 cfm statement replaced Individual kitchen exhaust hoods larger than 5,000 cfm. This prevented the addition of multiple hoods or hood sections individually operating beneath 5,000 cfm (2360 L/s) to avoid the energy saving methods and specifications required in and for larger capacity systems. TABLE : Maximum net exhaust flow rate, cfm per linear foot of hood length. (From Standard ) TYPE OF HOOD Wall-Mounted Canopy LIGHT DUTY MEDIUM DUTY HEAVY DUTY EXTRA HEAVY DUCT Single Island Double Island (Per Side) Eyebrow Not Allowed Not Allowed Backshelf Pass-Over Not Allowed Exception: a) At least 75% of all the replacement air is transfer air that would otherwise be exhausted. The exhaust airflow rates in Table are 30% below the minimum airflow rates in ASHRAE Standard Ventilation for Commercial Cooking Operations, for unlisted hoods. While the IMC still recognizes unlisted hoods, this airflow limitation in Standard 90.1 effectively outlaws unlisted hoods (for systems greater than 5,000 cfm [2360 L/s]). ASHRAE research has shown that hoods listed per UL Standard and tested per ASTM/ANSI F have exhaust rates that are at least 30% less than those of the unlisted hoods. The following discussion delves into this aspect, presenting third-party performance data for a number of hood designs. Certification bodies (CBs) list and label exhaust hoods that operate with commercial cooking appliances and a fire extinguishing system according to Standard UL 710 Exhaust Hoods for Commercial Cooking Equipment. 8 The Standard includes a construction section and performance section. The construction requirements ensure the hood s integrity during a fire and fan failure. The performance section ensures the hood s ability to capture and contain the cooking effluent and products of combustion under actual cooking conditions. However, in some cases, the cooking challenge may not be as challenging as some real-world conditions. As a result, the ASTM Kitchen Ventilation subcommittee of F26 Food Service Equipment took on a project to develop a test method 9 using enhanced flow visualization techniques to determine the capture and containment exhaust rate for different appliance lines and exhaust hood configurations. This test method was used as the foundation of past CKV research projects 7,10,11,12 as well as a basis for ongoing evaluation of high-performance hoods. 13 Figure 2 presents the results of third-party testing for eight different designs of 10-foot, listed wall-canopy 56

4 Reprinting of this proof for distribution or posting on web sites is not permitted. Authors may request from the editor an electronic file of the published article to reprint or post on their website once the final version has been published. TECHNICAL FEATURE hoods in comparison with a generic unlisted hood operating over a heavy-duty appliance line (two-vat fryer, under-fired boiler and convection oven) in accordance with ASTM In the first set of data the hoods are without side panels while in the second set the hoods have partial side panels. The generic unlisted hood did not include any of the performance enhancing features that the high-performance hoods incorporated (e.g., flow-enhancing flanges). Figure 2 shows that the capture and containment exhaust airflow rate for all eight of the high-performance hoods are at or below the maximum limit of 280 cfm per linear foot of hood (2,800 cfm total) set in Standard The variations in the C&C exhaust rates are due to the differences in individual hood designs. Note that the generic hood exceeded the maximum and that Manufacturer 8 s hood was at the limit for the condition without side panels (due to convective spill from the side of the hood). However, in both cases, the addition of side panels reduced the exhaust rate below the threshold. The bottom line is that many listed hoods will meet the Standard 90.1 exhaust rate requirements for wall-canopy hoods based on both UL 710 listings and ASTM F1704 performance testing. Note, however, that the UL 710 listing cfm numbers must be met in cases where the ASMT F1704 cfm values are lower. The same may not be said for the specification of single-island hoods operating over heavy-duty appliances, which are typically being used for exhibition cooking stations in modern food service facilities. The strong effluent plume that is generated by the heavy-duty appliances is very susceptible to cross drafts, reduced overhang and high-velocity makeup air introduction. As a result, the exhaust airflow rates required to capture and contain such thermal plumes increased significantly. ASHRAE RP-1480, Island Hood Energy Consumption and Energy Consumption Strategies, 12 explored the C&C exhaust airflow rates for single-island canopy hoods. One style of island canopy hood (10 ft by 4 ft [3 m by 1.2 m]) had the filter bank along the rear of the hood while the second style of hood (10 ft by 6 ft [3 m by 1.8 m]) had a V-bank down the center of the hood. The replacement air was supplied through 14 floor-mounted displacement diffusers to emulate transfer air from adjoining spaces and provide a low-velocity air supply, which has been proven to minimize the influence of replacement air on hood performance. The results are shown in Figure 3. Capture and Containment Exhaust Airflow Rate (cfm) 5,000 4,000 3,000 2,000 1,000 0 Combination-Duty Line-Broiler ASHRAE Standard cfm/ft Generic Hood Max Overhang Manufacturer 1 Manufacturer 2 Manufacturer 3 Manufacturer 4 Manufacturer 5 Manufacturer 6 Manufacturer 7 Manufacturer 8 Combination-Duty Line w/ Side Panels-Broiler FIGURE 2 Published manufacturers ASTM test data for the C&C exhaust airflow rates for a 10 ft (3 m) wall-mounted canopy hood over a heavy-duty appliance line. The difficulty in capture and containment is evident by the high exhaust airflow rates. While side panels mitigate some of the cross drafts and improve C&C performance, the data show that it is very difficult for singleisland canopy hoods to stay below the 420 cfm/ft (650 L/s m) limit imposed by Standard However, it is important to note that the data in Figure 3 is for generic, unlisted hoods. Unfortunately, not many manufacturers have used ASTM F1704 to report airflow rates for highperformance island hoods. Our message to the design engineer: Proceed with caution! If a kitchen/dining facility has a total kitchen hood exhaust airflow rate greater than 5,000 cfm then it shall have one of the following: a) At least 50% of all replacement air is transfer air that would otherwise be exhausted. b) Demand ventilation system(s) on at least 75% of the exhaust air. Such systems shall be capable of at least 50% reduction in exhaust and replacement air system airflow rates, including controls necessary to modulate airflow in response to appliance operation and to maintain full capture and containment of smoke, effluent and combustion products during cooking and idle. c) Listed energy recovery devices with a sensible heat recovery effectiveness of not less than 40% on at least 50% of the total exhaust airflow. NOVEMBER 2014 ashrae.org ASHRAE JOURNAL 57

5 Maximizing Transfer Air The replacement air required for commercial kitchen ventilation systems is always 100% of the exhaust air; what goes out must come in! A common design practice has been to supply at least 80% of replacement air using an independent makeup air unit (MAU) with the remaining 20% supplied by conditioned outdoor air from HVAC rooftop units (RTU) serving the kitchen and/ or by transfer air from adjacent spaces. This keeps the kitchen under a negative pressure (relative to the dining room) helping to prevent cooking odors from migrating into the dining area. However, in some climates the replacement air from an independent makeup air unit is not conditioned, which may create uncomfortable conditions (too cold and/or too hot) in the kitchen. In other climates, the makeup air is heated, which in many cases results in simultaneous heating (by the MAU) and cooling (by the RTU) of the kitchen during the shoulder seasons. Conventional design practice does not take full advantage of the relatively high rate of occupancy ventilation air per ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality, that is introduced into the dining room or other areas of the building adjacent to the kitchen. The first option under Section encourages using code-required outdoor air supplied to the dining room as replacement air, thus reducing (or eliminating) the fraction of replacement air from an independent makeup air unit. If this transfer air from the dining room (that otherwise would be exhausted or relieved by rooftop equipment) is 50% (or more) than the exhaust, the CKV design is in compliance with the Section requirement. Obviously, care should be taken to not introduce transfer air at high velocities within the kitchen, potentially cooling food that is staged near transfer windows. If less than 50% is available, it may still be used for the associated benefit, just not as a compliance option under Section And since occupancy ventilation air is conditioned in most cases, transferring it to the kitchen can improve comfort conditions. Several national restaurant chains have adopted this strategy and derive all replacement air for the CKV system from the HVAC system, realizing a positive benefit on thermal comfort in the kitchen. (Coincidently, none of these chains were included in the ASHRAE thermal comfort in commercial kitchens study.) In a case study by the authors (Figure 4), the design exhaust rate was Combination-Broiler Fryer, Broiler, Oven (F,B,O) w/side Panels Combination-Broiler (F,B,O) Heavy-Duty (3 Broilers) Heavy-Duty (3 Broilers) w/side Panels Heavy-Duty (3 Broilers) Minimum Overhang Single Island/Center V-Bank Single Island/Rear Filter ASHRAE Standard cfm/ft 0 2,000 4,000 6,000 8,000 10,000 Exhaust Airflow Rate (cfm) FIGURE 3 C&C Exhaust Airflow Rates for Single Island Canopy Hoods from ASHRAE RP-1480 Island Hood Energy Consumption and Energy Consumption Strategies. successfully reduced from 8,000 cfm to 6,000 cfm (3776 L/s to 2832 L/s) by incorporating best practices (54 in. [1.4 m] deep listed hood, increased overhang, pushing equipment tight to the wall and adding side panels 14 thus meeting the Standard 90.1 requirement with the 3,000 cfm (50%) transfer air Demand Controlled Kitchen Ventilation The second option in Section of the standard recognizes that demand-controlled kitchen ventilation (DCKV) controls are an important consideration for an energy efficient kitchen ventilation system. There are now more than a dozen manufacturers of DCKV systems supporting the authors hypothesis that DCKV is poised to move from best practice to standard practice within the design of commercial kitchens. 1 It is important to recognize that not all CKV systems can be operated at 50% of design flow when appliances are in an idle or ready-to-cook mode (regardless of the control system installed). This is due to the fact that some cooking appliances, such as under-fired charbroilers, exhibit a thermal plume under ready-to-cook conditions that is almost as aggressive as the plume generated by the cooking activity. But there is also the condition (of hood operation) when several appliances have been turned off (including the charbroiler) yet operation of the hood must be maintained (for one appliance remaining on or during the cool-down and 58

6 Reprinting of this proof for distribution or posting on web sites is not permitted. Authors may request from the editor an electronic file of the published article to reprint or post on their website once the final version has been published. TECHNICAL FEATURE cleanup periods). In such cases, it may be feasible to reduce the exhaust rate to the 50% level without repercussion. The question for the designer is which DCKV systems on the market can be responsive to this operating scenario and be in compliance with the Standard 90.1 requirement Energy Recovery The third option in Section recognizes listed air-to-air energy recovery equipment (also referred to a heat recovery ventilation or HRVs) as a compliance path for Thermodynamically, exhaust air heat recovery from kitchen ventilation is very attractive. In practice, however, this waste heat stream is challenged by the fact that the exhaust air is grease laden and subject to NFPA 96 jurisdiction, potentially requiring fire protection and/or wash down systems. Consequently, these systems are more expensive to install ($/cfm) than other HRV applications, challenging the ROI equation. There also is a conflict with Section of the IMC that does not permit HRVs in kitchen exhaust. However, there is now an exception stating that ERV equipment is not limited by this code section if such equipment recovers only sensible heat and utilizes only coil-type heat exchangers. This would allow loop or runaround coil type energy recovery systems for kitchen exhaust. One positive attribute of this HRV application is the typical unbalanced flow condition (i.e., more exhaust than supply air). This inherently increases the thermal effectiveness of the HRV. If applied in combination with a DCKV system, the effectiveness further increases under part-load (reduced airflow) conditions. The elevated exhaust air temperatures combined with the unbalanced flow condition makes heat exchanger frosting unlikely. (Heat exchanger frosting or freezing is an issue in cold climates and a defrost strategy often required.) The unbalanced flow conditions also make meeting the 40% effectiveness threshold very attainable with a runaround-coil style heat recovery system. The DOE article 6 states that DCKV will be a more economically attractive option than heat recovery for 90.1 compliance. We agree. However, the combination of a DCKV system with an HRV may completely eliminate the need for makeup air heating a definite attribute for a LEED building design and the future of CKV energy efficiency. We hope that further research and case studies RTU 3,000 cfm FIGURE 4 Illustration of transfer air used for Standard 90.1 compliance. will build a much needed knowledge base for the HRV potential in CKV design Performance Testing: An approved field test method shall be used to evaluate design air flow rates and demonstrate proper capture and containment performance of installed commercial kitchen exhaust systems. Where demand ventilation systems are utilized to meet , additional performance testing shall be required to demonstrate proper capture and containment at minimum airflow. This section is fundamental to the kitchen exhaust system commissioning and performance verification that protects public health and safety. Hood systems are a field assembly of various components including hoods, fans, replacement air systems, duct and distribution systems and require testing, once installed, to ensure specified system performance is met. This section requires verification of hood system performance and operation, and supports Standard 90.1 purpose and scope. The evaluation of design airflow rates can be determined by applying ASTM F2975 Standard Test Method for Measuring the Field Performance of Commercial Kitchen Ventilation Systems. 15 Protocols have been developed within the standard to measure velocities and apply correction factors to determine exhaust and makeup airflow rates. An approved field test method used to demonstrate capture and containment performance can be found in ASHRAE Standard Ventilation for Commercial Cooking Operations, Section 4.8.2, Type I Hood Capture and Containment Test. In that, it describes a field test where all the appliances under the hood are at operating temperatures, all sources of outdoor air providing makeup air for the hood are operating, and all sources for the MAU 3,000 cfm 6,000 cfm NOVEMBER 2014 ashrae.org ASHRAE JOURNAL 59

7 recirculated air providing conditioning for the space are operating. Capture and containment shall be verified visually by observing smoke or steam produced by actual cooking operation or by simulating cooking by using devices such as smoke candles or smoke puffers. Smoke bombs shall not be used. For a constant-volume system, this test is typically performed during heavy-load conditions. For a DCKV system, the system must be evaluated during heavy, medium and light-load cooking conditions. The worst-case scenario would be a sequence that progresses from no-load or light-load directly to heavy-load to evaluate the system response and its ability to capture and contain the cooking effluent by sufficiently ramping up the airflow rate. Summary The new requirements in Standard 90.1 limit the design exhaust rates for the different styles of hoods and appliance duties. It then requires one of three prescriptive paths, including 50% transfer air, DCKV on 75% of the exhaust or heat recovery on 50% of the exhaust. Facility, operation and economic constraints will dictate the path chosen. But in a perfect world (or maybe for a LEED project), why not incorporate all options. If the heat recovery from the exhaust was used to preheat domestic water in the summer, offsetting system fan energy, future CKV designs could approach net zero energy! Wow, from the most energy intensive system in a restaurant to net zero? We like to dream! But regardless of the limits to energy efficiency, ASHRAE through its technical committees and industry support has moved the North American CKV design world from the dark ages to the front-of-thepack. Furthermore, the inclusion of commercial kitchen ventilation within Standard 90.1 has caught the attention of the HVAC design community. We believe that the CKV system design has taken a positive step forward as a result of the Standard 90.1 initiative. Provided the designer understands the implications, limits and subtleties of the best practice options, one can cost-effectively increase the energy efficiency of CKV systems in concert with improving thermal comfort in the kitchen. References 1. Fisher, D., R. Swierczyna, A. Karas Future of demandcontrolled ventilation for commercial kitchens. ASHRAE Journal 55 (2) ASHRAE Handbook Fundamentals, Chap ICC International Mechanical Code. International Code Council, Washington, D.C. 4. California Energy Commission Building Energy Efficiency Standards, Title Stoops, J., et al Thermal comfort in commercial kitchens. ASHRAE Research Project Final Report. 6. DOE. ANSI/ASHRAE/IES Standard Kitchen Exhaust Brohard, G., D.R. Fisher PE, V.A. Smith PE, R.T. Swierczyna, P.A. Sobiski Makeup Air Effects on Kitchen Exhaust Hood Performance. 8. UL Standard for exhaust hoods for commercial cooking equipment. 6 th ed. Standard ASTM Standard F , Test Method For The Performance Of Commercial Kitchen Ventilation Systems. American Society for Testing and Materials. 10. Swierczyna, R., P. Sobiski, D. Fisher Revised Heat gain and capture and containment exhaust rates from typical commercial cooking appliances (RP-1362). Final Report. 11. Swierczyna, R., D. Fisher, P. Sobiski, T. Cole, M. Bramfitt Effect of appliance diversity and position on commercial hood performance (RP-1202). Final Report. 12. Swierczyna, R., P. Sobiski, D. Fisher, Island hood energy consumption and energy consumption strategies (RP-1480). Final Report. 13. FSTC Kitchen Hood Performance Reports. Fishnick.com. May FSTC CKV Design Guides. Fishnick.com. com/ventilation/designguides/ 15. ASTM Standard test method for measuring the field performance of commercial kitchen ventilation systems. Standard F American Society for Testing and Materials. 60

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives Design Considerations for Commercial Kitchen Ventilation By John A. Clark, P.E., Member ASHRAE Commercial kitchen ventilation (CKV) design must consider everything needed to be coordinated to form a system

More information

Demand-Controlled Ventilation For Commercial Kitchens

Demand-Controlled Ventilation For Commercial Kitchens Demand-Controlled Ventilation For Commercial Kitchens Tetra Images/Corbis By Derek Schrock, Member ASHRAE; Jimmy Sandusky, Associate Member ASHRAE; Andrey Livchak, Ph.D., Member ASHRAE Food service facilities

More information

Effective ventilation is necessary for the comfort

Effective ventilation is necessary for the comfort NEWS FROM THE NETWORK Understanding Kitchen Ventilation Clearing the Air and Eliminating the Myths by Tom Stroozas CFE, RCGC, CFSP GFEN Consulting Editor Effective ventilation is necessary for the comfort

More information

Demand-Controlled Ventilation for Commercial Kitchen Ventilation

Demand-Controlled Ventilation for Commercial Kitchen Ventilation Demand-Controlled Ventilation for Commercial Kitchen Ventilation Welcome. Today s webinar is being recorded and will be posted at: www.e3tnw.org www.conduitnw.org You may submit questions at any time during

More information

for commercial kitchen ventilation

for commercial kitchen ventilation Energy efficient solutionszag Energy efficient solutions for commercial kitchen ventilation Andrey Livchak, Dr., Halton Introduction Restaurants are among commercial buildings with the highest energy consumption

More information

Design Guide Improving Commercial Kitchen Ventilation System Performance

Design Guide Improving Commercial Kitchen Ventilation System Performance Design Guide Improving Commercial Kitchen Ventilation System Performance This design guide provides information about achieving and maintaining optimum performance and energy efficiency in commercial kitchen

More information

Demand Control Ventilation What, When and Where?

Demand Control Ventilation What, When and Where? Demand Control Ventilation What, When and Where? Presented by: Todd Bell Sr. Energy Analyst Fisher-Nickel Inc. Rich Swierczyna Sr. Engineer Fisher-Nickel Inc. The Food Service Technology Center (FSTC)

More information

Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry.

Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry. Commercial Kitchen Ventilation (CKV) Design and Recent Innovations and Developments in the Industry. Prepared by Dialectic, Inc. INTRODUCTION Commercial Kitchen Ventilation (CKV) Design and Recent Innovations

More information

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS

Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS Contents Chapters 4 & 5 of the 2012 Michigan Mechanical Code CHAPTER 4, MMC: VENTILATION CHAPTER 5, MMC: EXHAUST SYSTEMS 1 Ventilation and Exhaust 2 Seminar Introduction Seminar addresses key concepts

More information

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS (630) 620-5750 Fax: (630) 629-2374 www.villageoflombard.org COMMERCIAL HOOD & DUCT SYSTEM PLAN REVIEW REQUIREMENTS International

More information

Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1

Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1 January 31, 2013 Standing Standard Project Committee (SSPC) 189.1 Re: AHRI Comments on Proposed Addendum be to ASHRAE Standard 189.1 Dear Members of SSPC 189.1: These comments are submitted by the Air-Conditioning,

More information

Innovative Technologies [and Design Concepts] in Commercial Foodservice

Innovative Technologies [and Design Concepts] in Commercial Foodservice Innovative Technologies [and Design Concepts] in Commercial Foodservice Don Fisher, P. Eng. Fisher Consultants PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com Food Service Technology

More information

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK

FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK FOUNDATIONS OF MODERN KITCHEN VENTILATION (CKV) DESIGN HANDBOOK A Design Guide offering ideas and resources to focus on sustainable design for the modern CKV System. Optimize CKV applications, manage energy

More information

Adding More Fan Power Can Be a Good Thing

Adding More Fan Power Can Be a Good Thing This article was published in ASHE Journal, May 14. Copyright 14 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission of

More information

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY STAFF USE ONLY Thurston County Resource Stewardship 2000 Lakeridge Dr. S.W. Olympia, WA 98502 (360)786-5490 / (360)754-2939 (Fax) TDD Line (360) 754-2933 Email: permit@co.thurston.wa.us www.co.thurston.wa.us/permitting

More information

Don t Turn Active Beams Into Expensive Diffusers

Don t Turn Active Beams Into Expensive Diffusers This article was published in ASHRAE Journal, April 2012. Copyright 2012 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

REQUIREMENTS FOR HOOD PLANS

REQUIREMENTS FOR HOOD PLANS DEPARTMENT OF PUBLIC HEALTH Division of Environmental Health REQUIREMENTS FOR HOOD PLANS Submit one (1) set of plans drawn to scale of at least ¼-inch per foot. Plans shall conform to applicable California

More information

2015 ICC Commercial Cooking Systems

2015 ICC Commercial Cooking Systems 2015 ICC Commercial Cooking Systems Based on the: 2015 International Building Code (IBC ) 2015 International Mechanical Code (IMC ) 2015 International Fire Code (IFC ) 2015 International Fuel Gas Code

More information

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003 MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003 California Conference of Directors of Environmental Health I. Background Proper venting and capture of the gases, heat, grease,

More information

ASHRAE JOURNAL ON REHEAT

ASHRAE JOURNAL ON REHEAT Page: 1 of 7 ASHRAE JOURNAL ON REHEAT Dan Int-Hout Chief Engineer Page: 2 of 7 Overhead Heating: A lost art. March 2007 ASHRAE Journal Article Dan Int-Hout Chief Engineer, Krueger VAV terminals provide

More information

COMcheck Software Version Mechanical Compliance Certificate

COMcheck Software Version Mechanical Compliance Certificate COMcheck Software Version 3.8.2 Mechanical Compliance Certificate 90.1 (2007) Standard Section 1: Project Information Project Type: New Construction Project Title : Rudy's Star Motors Construction Site:

More information

2012 ICC Commercial Kitchen Hoods

2012 ICC Commercial Kitchen Hoods Welcome 2012 ICC Commercial Cooking Hoods Based on the: 2012 International Mechanical Code (IMC ) 2012 International Fire Code (IFC ) 2012 International Fuel Gas Code, (IFGC ) 2012 International Building

More information

Chapter One Commercial Kitchen Fires

Chapter One Commercial Kitchen Fires Table of Contents Table of Contents Chapter One Commercial Kitchen Fires COMMERCIAL KITCHEN FIRES... 2 The Commercial Kitchen Fire Problem... 2 Unreported Fires... 2 Cooking By-Products... 3 Grease Accumulation

More information

Notable Changes in the Mechanical Codes

Notable Changes in the Mechanical Codes Notable Changes in the Mechanical Codes July 2004 The following are some of the changes between the 1997 Uniform Mechanical Code and the 2003 International Mechanical Code(M) and the 2003 International

More information

BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT

BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT BETTER BUILDINGS BY DESIGN CONFERENCE 2008 Designing a Sustainable Commercial Kitchen FEBRUARY 13 BURLINGTON, VERMONT Don Fisher Manager PG&E Food Service Technology Center 925-866-5770 dfisher@fishnick.com

More information

Effects of Kitchen Ventilation on Residential Dwellings

Effects of Kitchen Ventilation on Residential Dwellings Effects of Kitchen Ventilation on Residential Dwellings Anthony C. Jellen Engineering i Projects Incorporated 1 Personal Background U.S.N. (1994 2000) BS B.S. in Civil Engineering (2005) PHRC employee

More information

Technical Report - AM15VL Series Ventless Dishmachines

Technical Report - AM15VL Series Ventless Dishmachines Warewash Engineering Troy, OH 45374-0001 Technical Report - AM15VL Series Ventless Dishmachines In this document: 1. Machine Operation 2. ICC Code Opinions 3. Customer Testing 4. Operational Test Report

More information

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016

Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Summary of BBS Proposed Ohio Mechanical Code Rule Changes October 2016 Ohio Administrative Code Rule Number OMC Section IMC origin Reason for proposed 4101:2-2-01 Air, Makeup 2015 Modified definition Air,

More information

Low Wall Back Shelf Exhaust Canopy

Low Wall Back Shelf Exhaust Canopy ITEM NO. 710 Powerline Road Suite H Deerfield Beach, FL 33442 (954) 570-9860 (800) 322-8730 FAX (954) 570-9865 Low Wall Back Shelf Exhaust Canopy Model LW APPLICATION Wall mounted canopy style ventilator

More information

Best Practices for Condensing Boilers

Best Practices for Condensing Boilers ASHRAE www.ashrae.org. Used with permission from ASHRAE Journal at www.cleaverbrooks.com. This article may not be copied nor distributed in either paper or digital form without ASHRAE s permission. For

More information

Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens

Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens XD 9011E ABGKSWBGHAE 10/16/2017 Fire Suppression Installation (R-102) for AVI Hoods & XLT Ovens CAUTION This appliance is for professional use by qualified personnel. This appliance must be installed by

More information

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item

Public Comment No. 23-NFPA [ Section No ] Statement of Problem and Substantiation for Public Comment Related Item Public Comment No. 23-NFPA 96-2015 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, 100 Barr Harbor Drive, P.O. Box C700, West Conshohocken, PA 19428-2959. ASTM E84, Standard Test Method

More information

IMC Significant Changes Summary Tier I

IMC Significant Changes Summary Tier I 2009-2015 IMC Significant Changes Summary Tier I 202 Environmental Air The definition of environmental air has been expanded through the addition of parking garage exhaust. 306.1 Access More than just

More information

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee

Gil Rossmiller. In the construction industry for over 30 years. ICC IRC Plumbing & Mechanical Code Development Committee Gil Rossmiller In the construction industry for over 30 years ICC IRC Plumbing & Mechanical Code Development Committee ICC- IECC Commercial Energy Code Development Committee Building Official Parker, Colorado

More information

MiniCore Ventilator (500, 1000) Series Engineering Guide

MiniCore Ventilator (500, 1000) Series Engineering Guide MiniCore Ventilator (500, 1000) Series Engineering Guide November 2017 V1.0 Johnson Controls, Inc. All rights reserved. TABLE OF CONTENTS Page Functionality and Benefits... 1 Unit Overview... 3 MiniCore

More information

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 230593 - TESTING, ADJUSTING, AND BALANCING FOR HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Balancing Air Systems: a. Constant-volume air systems. b. Variable-air-volume systems. 2.

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center CMA-180-VL-FL Electric Door-Type Heat Recovery Dishwashing Machine Test Report Application of ASTM Standard Test Method F1696-15 and F2474-09 May 2016 Prepared by: Edward

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center Hobart PW10eR Electric Pot and Pan Door-Type Dishwashing Machine Test Report Application of ASTM Standard Test Method F1696-15 & F2474-09 February 2016 Prepared by: Rich

More information

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems Volume 6, Issue 1 CARRIER edesign SUITE NEWS Modeling 100% OA Constant Volume Air Systems This article provides an overview of how to model a stand-alone constant air volume (CAV) 100% OA system in HAP.

More information

Kitchen Ventilation Hood Permit Application

Kitchen Ventilation Hood Permit Application TOWN OF BRIGHTON Office of the Fire Marshal 2300 Elmwood Avenue Rochester, New York 14618 (585) 784-5220 Office (585) 784-5207 Fax Kitchen Ventilation Hood Permit Application Plan Submittals and Installation

More information

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1 Table of Contents Page Number(s) Executive Summary 2 Project Background 3 Proposed Depth Alternatives 4 Proposed Depth Redesign 5-7 Justification of Proposed Depth Redesign 8 Proposed Breath Redesign 9

More information

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code

2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code 2015 & 2012 International Mechanical Code Significant Changes and the PA Uniform Construction Code Welcome! Shawn Strausbaugh Director PMG Technical Resources ICC Government Relations sstrausbaugh@iccsafe.org

More information

Do All DOAS Configurations Provide the Same Benefits?

Do All DOAS Configurations Provide the Same Benefits? TECHNIL FTURE This article was published in ASHE Journal, July 2014. Copyright 2014 ASHE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without

More information

Food Service Technology Center

Food Service Technology Center Food Service Technology Center CMA-180 / CMA-180-VL Dishwashing Machine Expanded Test Report FSTC Application of ASTM Standard Test Methods F1696-07 and F2474-09 January 2013 Prepared by: Denis Livchak

More information

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment

ISO INTERNATIONAL STANDARD. Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment INTERNATIONAL STANDARD ISO 15371 Second edition 2009-03-15 Ships and marine technology Fire-extinguishing systems for protection of galley cooking equipment Navires et technologie maritime Systèmes d'extinction

More information

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING

HONORABLE MENTION: COMMERCIAL BUILDINGS, EXISTING ASHRAE s BEST This article was published in ASHRAE Journal, November 2010. Copyright 2010 American Society of Heating, Refrigerating and -Conditioning Engineers, Inc. Reprinted here by permission from

More information

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE

PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE PROPOSED CODE CHANGES FOR REVIEW BY THE FIRE CODE ACTION COMMITTEE Developed by the Midwestern Regional Work Group CONTENTS Item 15 Limited area sprinkler systems Item 20 Scope of IFC Ch 7 Item 21 Fire-resistance-rated

More information

Residential ventilation concepts based on the idea of displacement airflow distribution

Residential ventilation concepts based on the idea of displacement airflow distribution A strategy for reducing energy demand Student: Aris Gkitzias (I.D:4180380) Mentors: Dr. Regina Bokel, Ir. John van der Vliet MSc graduation project Department of Building Technology, faculty of architecture

More information

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017

LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017 LEED for Homes V4 Provisional Alternative Compliance Paths for the Canadian market March, 2017 Note: These provisional ACPs may be used by registered LEED v4 Homes and Midrise projects until official ACPs

More information

COMcheck Software Version Review Mechanical Compliance Certificate

COMcheck Software Version Review Mechanical Compliance Certificate COMcheck Software Version 4.0.7.2 Review Mechanical Compliance Certificate Section 1: Project Information Energy Code: 2014 Oregon Energy Efficiency Specialty Code Project Title: Benton County Health Project

More information

H O B O K E N R E S I D E N T I A L

H O B O K E N R E S I D E N T I A L Proposal 1: Open Loop Geothermal for Water Source Packaged Terminal Heat Pumps and Heat Recovery Ventilation and Humidifier Heating and Cooling System Schematic Ventilation Schematic Proposal 1 System

More information

NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC

NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC NC Department of Insurance Office of the State Fire Marshal - Engineering Division 1202 Mail Service Center, Raleigh, NC 27699-1202 919-647-0000 Kitchen Exhaust Makeup Air Exceptions Code: 2012 Mechanical

More information

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate Section 1: Project Information Energy Code: 2009 IECC Project Type: New Construction COMcheck Software Version 4.0.2.8 Interior Lighting Compliance Certificate Construction Site: Owner/Agent: Designer/Contractor:

More information

CHAPTER 5: EXHAUST SYSTEMS

CHAPTER 5: EXHAUST SYSTEMS MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such

More information

Narrative Reports As Regulated by 780 CMR, Section 903.0

Narrative Reports As Regulated by 780 CMR, Section 903.0 EXHIBIT 20 Narrative Reports As Regulated by 780 CMR, Section 903.0 903.1.1 - FIRE PROTECTION CONSTRUCTION DOCUMENTS a. Basis (methodology) of design for the protection of the occupancy and hazard for

More information

Ventilation Guidelines

Ventilation Guidelines MinnEsota CoMMErCial KitChEn Ventilation Guidelines Ventilation Committee of the Inter- Agency Review Council Fourth Edition 1 Table of ConTenTs INTRODUCTION... 5 PREFACE... 6 Mission Statement of the

More information

The Current (2017) State of the Art for Air Leakage in Ductwork

The Current (2017) State of the Art for Air Leakage in Ductwork The Current (2017) State of the Art for Air Leakage in Ductwork Over the last ten years there has been a major shift in the way ASHRAE has approached air leakage in ductwork. This is reflected in the latest

More information

DemandAire. amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems. Demand Control Kitchen Ventilation System

DemandAire. amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems.  Demand Control Kitchen Ventilation System Demand Control Kitchen Ventilation System Standard 0. Compliant 08 Listed amaximize Energy Efficiency aincreased Kitchen Comfort acustomizable Systems www.streivor.com Standard and Code Requirements for

More information

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection:

Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: FIRE DEPARTMENT Kitchen Range Hood Fire Suppression System Acceptance Test Project Name: Project Address: Installer Name: Installer Address: Date of Inspection: DOCUMENTATION NO Plans have been reviewed

More information

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS

EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS ICC-ES Report PMG-1004 Reissued 08/2017 This report is subject to renewal 08/2018 EVALUATION SUBJECT: GILES RECIRCULATING (VENTLESS) HOODS DIVISION: 23 00 00 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)

More information

2006 Building Science Press All rights of reproduction in any form reserved.

2006 Building Science Press All rights of reproduction in any form reserved. building science.com 2006 Building Science Press All rights of reproduction in any form reserved. Building Science Digest 110 HVAC in Multifamily Buildings 2006-10-24 by Joseph Lstiburek Abstract: Are

More information

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE This article was published in ASHRAE Journal, March 20145 Copyright 2015 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Passivhaus school kitchens

Passivhaus school kitchens Passivhaus school kitchens Alan Clarke & Nick Grant, The Woodlands, Whitecroft, Lydney, GL15 4PL, UK 1 Introduction Schools in the UK provide a mid-day meal, usually cooked at the school. Accommodating

More information

NFPA 96, 2017 REVIEW SUMMARY

NFPA 96, 2017 REVIEW SUMMARY NFPA 96, 2017 REVIEW SUMMARY 1) NFPA 96 REVISION SUMMARY NFPA 96 Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations The 2017 edition adds a new normative annex on mobile

More information

Variable Ventilation for the Kitchen:

Variable Ventilation for the Kitchen: Variable Ventilation for the Kitchen: How It Works and Why It s Important for Your Restaurant YOUR ENERGY COSTS $ JAN FEB MAR MAP LEGEND lighting & signage control hvac & kitchen ventilation control energy

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

MD and Its Impact on Lab Facilities

MD and Its Impact on Lab Facilities MD 15128 and Its Impact on Lab Facilities RPIC / SLCan Sustainable Laboratories Regional Workshop September 5, 2013 Timothy Ma, P. Eng., M. Eng., PMP Senior Mechanical Engineer Mechanical and Laboratory

More information

Product Release Summary

Product Release Summary Product Release Summary 48/50HC with System March 2012 TC Benefits of EnergyX System Why Energy Recovery 1. Code requirements: ASHRAE 90.1-2004: Energy Recovery is required when design supply air capacity

More information

Displacement Ventilation

Displacement Ventilation Displacement Ventilation Displacement Ventilation Displacement Ventilation vs. Dilution Ventilation Characteristics Design Considerations Layout and Selection Product Overview Casino Case Study Dilution

More information

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION

INTELLINOX DEMAND CONTROL KITCHEN VENTILATION INTELLINOX DEMAND CONTROL KITCHEN VENTILATION COMMERCIAL KITCHEN VENTILATION EXPERTS FOR OVER 25 YEARS WHO WE ARE WE REALLY UNDERSTAND AIRFLOW IN YOUR KITCHEN Extensive experience with all kitchen hood

More information

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 15990 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the Specifier in correctly specifying Mechanical System Testing Adjusting

More information

MSYS 4490 AC Systems

MSYS 4490 AC Systems MSYS 4490 AC Systems Winter 2015 KITCHEN VENTILATION SYSTEMS By Satwinder Singh 12/02/2015 1 12/02/2015 2 By Satwinder Singh 1 12/02/2015 3 12/02/2015 4 By Satwinder Singh 2 Type I: Types of Hoods used

More information

Modular Active. Chilled. Beams

Modular Active. Chilled. Beams Modular Active Chilled Beams How Twa MAC Beams Work Primary air (100% outside air) is dehumidified to between 50-57 F dew point and is used to: control the latent requirements of the space, provide fresh

More information

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available. PART 1: GENERAL 1.01 General Requirements A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the

More information

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas

UFAD and Displacement Ventilation. Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and Displacement Ventilation Dan Int-Hout, FASHRAE Chief Engineer Krueger Richardson, Texas UFAD and DV Systems, Objectives: Understand Differences between: Well Mixed, Partially Stratified and Fully

More information

Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts

Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts Halton - Meeting the Kitchen Ventilation challenges of multiple venues in Hotels, Casinos and Resorts Form#: BR-011 Hotels, Casinos & Resorts Brochure Halton Foodservice specializes in indoor climate solutions

More information

DADANCO Technical Paper

DADANCO Technical Paper DADANCO Technical Paper 260 North Elm Street Westfield, MA 01085 Phone: (413) 564-5657 Fax: (413) 568-2969 March 2013 CLASSROOM SOLUTION USING ACTIVE CHILLED BEAMS (Note: This technical paper assumes the

More information

Intumescent Fire Dampers

Intumescent Fire Dampers Ph 1300 858 010 Intumescent Fire Dampers Fire resistant walls and floors in a building play an important part in containing the spread of fire and smoke. However, a building also needs to be well ventilated

More information

Cold Weather Operation Of Cooling Towers

Cold Weather Operation Of Cooling Towers This article was published in ASHRAE Journal, March 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 23 0594 - TESTING, ADJUSTING, AND BALANCING (TAB) PART 1 - GENERAL 1.1 SUMMARY A. This Section includes testing, adjusting and balancing HVAC systems to provide design conditions as indicated by

More information

Customer Advanced Technologies Program Technology Evaluation Report

Customer Advanced Technologies Program Technology Evaluation Report Customer Advanced Technologies Program Technology Evaluation Report Prepared by Dave Bisbee, CEM Energy Efficiency, Customer Research & Development Sacramento Municipal Utility District January 11, 2008

More information

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS Prepared for the: RPIC/SLCan Sustainable Labs Regional Workshop Presented by: THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY

More information

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300

CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 CALIFORNIA DEPARTMENT of FORESTRY and FIRE PROTECTION OFFICE OF THE STATE FIRE MARSHAL UL 300 FREQUENTLY ASKED QUESTIONS CONCERNING COMMERCIAL COOKING PROTECTION Published by FIRE ENGINEERING DIVISION

More information

Bill McCullough. Director ERV Products. Dallas, TX

Bill McCullough. Director ERV Products. Dallas, TX Bill McCullough Director ERV Products Dallas, TX TOPICS 1. ERV Definition & Benefit 2. Indoor Air Quality 3. Energy Efficiency 4. ERV Technology & Operation 5. Stand-Alone ERVs 6. Compact ERVs What is

More information

GEOTHERMAL DESIGN GUIDE

GEOTHERMAL DESIGN GUIDE GEOTHERMAL DESIGN GUIDE BENEFITS OF THE BULLDOG SYSTEM CGC Version CGC Group of Companies Incorporated 2018 CONTENTS INTRODUCTION... 2 CHALLENGES FACING CONVENTIONAL GSHP SYSTEMS... 3 FACTORS WHICH IMPACTS

More information

Demand Controlled Kitchen Ventilation (DCKV) [Strategy]

Demand Controlled Kitchen Ventilation (DCKV) [Strategy] [Strategy] BRIEF DESCRIPTION DCKV equipment automatically varies kitchen ventilation by monitoring cooking activity to increase the exhaust airflow and makeup air when needed. DCKV equipment monitors cooking

More information

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE T he advent of the small scroll or screw chiller, capable of producing condenser water as high as 140

More information

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems 233100 AIR DISTRIBUTION PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 230700 HVAC Insulation B. Section 237300 Air Handling C. Section 230900 Building Automation and Control System Guidelines D. Section

More information

Sanitation: Ware Washers, Water Heaters and the Plumbing of the Future

Sanitation: Ware Washers, Water Heaters and the Plumbing of the Future Food Service Technology Center Sanitation: Ware Washers, Water Heaters and the Plumbing of the Food Service Technology Center 1 Water Heating is a System Business As Usual Hot water systems in restaurants

More information

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC

2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC 2009 Washington State Non-Residential Energy Code Scott Rushing, PE, LEED AP - Rushing Company Lisa Rosenow, CSBA, LEED AP NEEC Mechanical Systems Agenda Changes in NREC Chapter 11 Changes in NREC Chapter

More information

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings

research highlight Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings research highlight October 2005 Technical Series 05-112 Assessment of Suite Compartmentalization and Depressurization in New High-Rise Residential Buildings INTRODUCTION The provision of airtight interior

More information

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions

IDL20e (2 way discharge) IDS60e (4 way discharge) Inffusers. UDI (vertical discharge) Frequently Asked Questions IDL20e (2 way discharge) IDS60e ( way discharge) Frequently Asked Questions UDI (vertical discharge) Inffusers INFFUSER FREQUENTLY ASKED QUESTIONS The following are frequently asked questions (FAQ s) on

More information

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET

COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET COMMERCIAL KITCHEN SUPPRESSION SYSTEMS INFORMATION PACKET Colorado Springs Fire Department Division of the Fire Marshal October 2013 Table of Contents PURPOSE... 3 SCOPE... 3 DEFINITIONS... 3 GUIDELINES...

More information

COMcheck Software Version Interior Lighting Compliance Certificate

COMcheck Software Version Interior Lighting Compliance Certificate Section 1: Project Information Energy Code: 2009 IECC Project Title: Berry Farms Animal Hospital Project Type: New Construction COMcheck Software Version 4.0.3.0 Interior Lighting Compliance Certificate

More information

EADQUARTERS. Technical Report One. Stephanie Kunkel Mechanical Option

EADQUARTERS. Technical Report One. Stephanie Kunkel   Mechanical Option EADQUARTERS 707 N. Calvert St. Technical Report One ASHRAE Standard 62.1 Ventilation ASHRAE Standard 90.1 Energy Design Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

Report on First Revisions with Statement June 2014 NFPA 101

Report on First Revisions with Statement June 2014 NFPA 101 101 FR6005 SAF-BCF (32.2.1.1.2) Recommendation: 32.2.1.1.2 Where there are sleeping accommodations for more than 16 residents are provided, the occupancy shall be classified as a large facility in accordance

More information

Benefits Offered by Passive Dehumidification Wheel Speed Control

Benefits Offered by Passive Dehumidification Wheel Speed Control Benefits Offered by Passive Dehumidification Wheel Speed Control White paper By John Fischer Benefits Offered by Passive Dehumidification Wheel Speed Control The most significant advantage of the Pinnacle

More information

SECTION COMMERCIAL-KITCHEN HOODS

SECTION COMMERCIAL-KITCHEN HOODS SECTION 23 38 13 COMMERCIAL-KITCHEN HOODS SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. 2. Delete other items or paragraphs in the section that are not applicable and renumber

More information