Rev Installation Guide. Sondex Industrial and Marine Pumps

Size: px
Start display at page:

Download "Rev Installation Guide. Sondex Industrial and Marine Pumps"

Transcription

1 Rev Installation Guide Sondex Industrial and Marine Pumps

2 1. CONTENT 2. Applications... Page 2 3. Operation... Page 3 4. Maintenance... Page 4 5. Dis- and Reassembly... Page 5 6. Wear ring Clearances... Page 7 7. Part Description... Page 7 8. Problem Analysis... Page 8 9. EC Declaration of Conformity - Industrial Pumps... Page EC Declaration of Conformity - Marine Pumps... Page APPLICATIONS Receiving pump 1. Inspect for shipping damage. If a shortage or damage occurs, contact the carrier immediately. Location 1. Install vertical with motor up. 2. Pump should be accessible for inspection and repair work, head room must be provided for the use of hoist or tackle as necessary. 3. Lift pump by slinging through motor eye bolts and securing the motor support. 4. In no case should any part of motor be covered with insulation. Foundation 1. The pump must always be supported. 2. Pumps with smaller motors may be suspended in the piping, provided the piping is supported adjacent to the pump. 3. For pumps with larger motors the pumps should be attached to a support utilizing the tapped holes in the bottom of the pump casing. Note: Piping loads must not be applied to the pump. 4. Pump must be allowed to move with piping movement. Expansion of the piping must be taken into account when piping and suitable devices should be employed. Do not rigidly connect the pump to the floor. Note: provide vibrations isolations pads under floor mounted supports. Do not support unit by motor eye bolts. 2

3 3. OPERATION A. Before operating for the first time, check the following: 1. Is the motor correctly wired for voltage available? 2. Has the pump been primed? Pump should never be run dry. Extra effort may be required to get the air out of the seal chamber. CAUTION Make sure power supply to pump motor is locked out before touching motor shaft. 3. All rotating parts turn freely. B. Starting pump 1. Jog pump to check proper rotation. 2. Start pump with discharge valve closed. DANGER MAKE SURE SUCTION VALVE IS OPEN!! 3. When correct pressure has been reached, open discharge valve slowly. 4. Do not operate pump for prolonged periods with discharge valve closed, so as to avoid overheating and potential damaging loads. 5. Pump should be stopped if any of the following occur: a. No discharge. b. Insufficient discharge. c. Insufficient pressure d. Loss of suction e. Excessive power consumption. f. Vibration Check problem analysis further in the manual for help in troubleshooting. 3

4 4. MAINTENANCE A. Routine Inspections Routine inspections should be made on a regular basis. Inspections made while pump is running should reveal potential failures. 1. Inspect motor bearings for any sign of temperature rise. Temperature should not exceed 70 C. Temperature rise may indicate the early stages of bearing problems. 2. Listen for any unusual noise. a. Air trapped in pump. b. Hydraulic noise. c. Mechanical noise in motor and/or pump 3. Check suction gauge reading and confirm that it is normal. 4. Check discharge gauge reading and confirm that it is normal. a. If gauge readings are abnormal, find out why. Note: Suction and discharge gauges should read the same with pump stopped. B. Split Coupled Pumps The pump shaft is attached to the motor shaft with a coupling. The pump shaft does not contain bearings that need lubrication. C. Split Coupled Motors Some motors must be lubricated in accordance with the manufacturer s recommendations. Do not over lubricate the motor bearings as this could cause premature bearing failure. D. Mechanical Seal A mechanical seal is a very high-precision product and should be treated with extreme care before and during fitting. Replace the mechanical seal at minor and major pump rebuild or if leaking. If you need to replace your mechanical seal, please contact your local Sondex supplier and state the serial number of the pump. At you will find contact information to your local Sondex 4

5 5. DIS- AND REASSEMBLY A. General If the pump has been maintained and serviced properly, breakdowns which necessitate the pump being disassembled should not occur often. 1. If a problem occurs, the cause should be determined, if possible, before disassembling. (See Problem Analysis ). 2. If the pump is being disassembled, all parts must be carefully handled, avoid heavy blows and shocks. 3. All parts must be carefully cleaned and inspected for wear. Recondition or replace parts where necessary. B. Disassembly - Impeller Repair 1. Drain liquid from casing by removing drain plug. CAUTION Allow pump to cool and close suction, and discharge valves before working on pump!! 2. Remove seal flush line. 3. Remove bolts holding cover/motor adapter to casing. Pry cover/motor adapter and motor assembly from casing or use jack bolts. 4. Remove impeller bolt in a counterclockwise direction. Remove impeller and key. 5. All parts must be cleaned and inspected for wear. Replace parts where necessary. C. Disassembly - Seal Internal seal removal and replacement: Remove the seal cover and shaft coupling. Note: The shaft can drop if not properly supported in place, or the pump cover is on the pump casing. The seal rotating element can be drawn off the shaft. Note: Apply silicone grease on the outside of the shaft in the area between the seal and the end of the shaft. This will help you remove the seal through the opening between the pump shaft and motor shaft. The stationary seal element is to be removed from the seal cover. External seal removal and replacement: Loosen the two set screws on the seal rotating element. Remove the shaft coupling. Note: The shaft can drop if not properly supported in place or the pump cover is on the pump casing. Remove the seal rotating element. Note: Apply silicone grease on the of the shaft in the area between the seal and the end of the shaft. This will help you remove the seal through the opening between the pump shaft and the motor shaft. The stationary seal element is to be removed from the top of the cover/adapter after the snap ring is removed. 5

6 D. Reassembly - Impeller 1. Assemble impeller key and impeller on shaft. Refit with impeller washer on impeller bolt and tighten carefully. Be certain that the impeller rotates freely by hand. 2. Apply a few spots of gasket adhesive to gasket surface and press against adhesive. 3. Assemble cover-adapter complete with motor into casing. Ensure that gasket is seated correctly. Install hex-headed cap screws into casing tapings and tighten uniformly. 4. Reconnect seal flush line and drain plug. E. Reassembly - Seal Replacement Internal seal replacement: 1. Be certain that all parts to be replaced are free from burrs, with screw threads and connecting faces clear and free from damage. 2. Insert stationary element of seal into seal cover. Note: Do not touch the seal surfaces because this may result in leakage. Do not contaminate seal faces with fingerprints. 3. Lubricate the pump shaft end on the motor side with silicone grease. Do not use petroleum oil or grease. 4. Place spring retainer and spring to abut against retaining ring. Slide rotary seal on shaft until it contacts spring. 5. Make sure the seal cover O-ring is properly seated in groove of seal cover. Place the seal cover back onto the pump cover and bolt in place. Connect pump coupling to set shaft position. 6. Reconnect seal flush line to drain plug. External seal replacement: (Separate instructions are provided). 1. Be certain that all parts to be replaced are free from burrs, with screw threads and connecting faces clear and free from damage. 2. Insert stationary element of seal into seal cover. Note: Do not touch the seal surfaces, because this may result in leakage. Do not contaminate seal faces with fingerprints. Ensure the seal cover O-ring is properly seated in groove of the seal cover. Place the seal cover back onto the pump cover and bolt in place. 3. Install retaining ring in seal cover above stationary seal. 4. Lubricate the pump shaft end on the motor side with silicone grease. Do not use petroleum oil or grease. 5. Slide rotary seal on shaft. Connect pump coupling to set shaft position. 6. Slide rotating seal into final position and tighten the set screws, which will set proper seal position. 7. Remove the plastic seal retaining clamps. 8. Reconnect seal flush line to drain plug. 6

7 6. WEAR RING CLEARENCES Inspection Once a year it is recommended to disassemble the pump. All rotating parts must be checked and repaired, if necessary. Depending on the size and capacity of the pump, normal clearance between the impeller and casing wear ring is 0,45 to 0,50 mm. Wear ring diameter This applies to both upper and lower wear ring. Clearance Clearance (mm) 1,0 Max. clearance 0,9 0,8 0,7 0,6 0,5 0,4 Min. clearance 0,3 0,2 0, Wear ring diameter (mm) 500 The tolerance stated are average values, and must in each single case be compared with the needs for the necessary operation data. 7

8 A-A ( 1 : 2 ) 7. PART DESCRIPTION Item Part number Title Material Qty 14 F XX Mechanical seal 1 1 F XX Back plate Bronze / Cast iron PLUG 1/4 Steel, Mild 3 2 F XX Pump house Bronze / Cast iron 1 16 F XX Shaft for M90 to M280 Stainless steel 1 3 F XX Foot Cast iron 1 17 F XX Feather key Stainless steel 1 4 F XX Extension frame Cast iron Threaded bar Galvanized Steel XX00XX44 Unbraco screw A XX Washer Galvanized Steel 4/8 6 F O-ring Nitril/NBR XX00XX01 Hexagon screw Stainless steel 4 7 F XX Impeller Bronze XX Washer Galvanized Steel 2 Dimensions Designed by Date Approved by Date Rev. no. Revision Text 8 F XX Wear ring (1+1 or 1+1.1) Bronze without 2 tolerance: XX00XX01 Unbraco screw Galvanized Steel 4 DOFR XX00XX01 Hexagon screw Stainless steel XX00XX01 Unbraco screw Description: Galvanized Steel 2 ISO 2768-m 10 F XX Washer AISI F XX Adapter for Assembly M90 to M225 S-MP Cast iron 1 ISO projektion Motor M160L, 50Hz/18,5kW, 60Hz/ 21,5kW 11 F XX Cover forextension frame Bronze, Soft Tin 2 SONDEX XX Washer Impeller ø174 Galvanized Steel 4/ Slotted screw A2 6 26Jernet 8400XX Washer Rev. date Rev. bygalvanized Drawing no. Steel 3 Sheet Hex head self drilling Steel, Mild 4 F AML 1 /2 8

9 8. PROBLEM ANALYSIS A. No Discharge 1. Pump not primed. 2. Speed too low. 3. System head too high. 4. Suction lift higher than pump is designed. 5. Impeller completely clogged. 6. Incorrect direction of rotation. 7. Air leak in suction line. B. Insufficient Discharge Flow 1. Air leak in suction line. 2. Speed too low. 3. System head higher than anticipated 4. Insufficient NPSH: Suction lift too high. Check gauges, also check for clogged suction line or screen. 5. Impeller partially plugged. 6. Mechanical defects. a. Worn wear rings. b. Impeller damaged. c. Incorrect direction of rotation. F. Vibration 1. Air leak in suction line. 2. Air in system. 3. Impeller partially plugged. 4. Foundation not rigid. 5. Mechanical defects. a. Damaged impeller. b. Motor bearings worn. c. Rotor out of balance. d. Shaft bent. G. Motor Runs Hot 1. Speed too high. 2. Specific gravity of liquid too high. 3. Mechanical defects. a. Shaft bent. b. Rotating elements bind. c. Defective motor. d. Voltage lower than rating C. Insufficient Discharge Pressure 1. Speed too low. 2. System head less than anticipated. 3. Air in system. 4. Mechanical defects. a. Worn wear rings. b. Impeller damaged. c. Impeller diameter too small. d. Incorrect direction of rotation. D. Loss of Suction 1. Leak in suction line. 2. Suction lift too high. 3. Insufficient NPSH. 4. Air in the system. 5. Casing gasket defective. E. Excessive Power Consumption 1. Speed too high. 2. System head lower than rating. 3. Specific gravity of liquid too high. 4. Mechanical defects. a. Shaft bent. b. Rotating elements bind. c. Worn wear ring. 9

10 Overensstemmelseserklæring / EC declaration of conformity / Konformitätserklärung Producent / Manufacturer / Hersteller Sondex Pumps A/S Jernet 9 Tel: Sondex Pumps A/S Jernet 9 Repræsentant / Representative / Repräsentative Tel.: Fax info@sondex-pumps.dk V.A.T. No.: DK Bank: Sydbank Jernbanegade 14 Acc.No.: Swift: SYBKDK22 IBAN No.: DK Erklærer på eget ansvar, at følgende produkter / Declare under our sole responsibility that the products / Erklärt eigenverantwortlich, daß die Produkte Marinepumper / Marine pumps / Marine Pumpen Series: S-MP Som er omfattet af denne erklæring, er i overensstemmelse med følgende standarder / To which this declaration relates are in conformity with the following standards / Auf die sich diese Erklärung bezieht, den folgenden normativen Dokumenten entsprechen Maskindirektivet / Machinery directive / Maschinenrichtlinie EMC-Direktivet / EMC-Directive / EMV-Richtlinie Lavspændingsdirektivet / Low Voltage Directive / Niederspannungsrichtlinie 2006/42/EU Appendix II A EMC 2004/108/EU LVD 2006/95/EU Aage Søndergaard Nielsen Managing Director 10

11 Overensstemmelseserklæring / EC declaration of conformity / Konformitätserklärung Producent / Manufacturer / Hersteller Sondex Pumps A/S Jernet 9 Tel: Sondex Pumps A/S Jernet 9 Repræsentant / Representative / Repräsentative Tel.: Fax info@sondex-pumps.dk V.A.T. No.: DK Bank: Sydbank Jernbanegade 14 Acc.No.: Swift: SYBKDK22 IBAN No.: DK Erklærer på eget ansvar, at følgende produkter / Declare under our sole responsibility that the products / Erklärt eigenverantwortlich, daß die Produkte Industripumper / Industrial pumps / Industriepumpen Series: S-IP Som er omfattet af denne erklæring, er i overensstemmelse med følgende standarder / To which this declaration relates are in conformity with the following standards / Auf die sich diese Erklärung bezieht, den folgenden normativen Dokumenten entsprechen Maskindirektivet / Machinery directive / Maschinenrichtlinie EMC-Direktivet / EMC-Directive / EMV-Richtlinie Lavspændingsdirektivet / Low Voltage Directive / Niederspannungsrichtlinie 2006/42/EU Appendix II A EMC 2004/108/EU LVD 2006/95/EU Aage Søndergaard Nielsen Managing Director 11

12 Sondex Head Office Jernet 9 Denmark Tel Fax (1) Fax (2) info@sondex.dk Copyright 2013 Sondex A/S Sondex A/S can accept no responsibility for possible errors in catalogues, brochures and other printet materials. Sondex A/S reserves the right at any time to change the specifications without notice.

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions

AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions AC6 & AC8 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY PUMPS WITH MOTORS 1. No assembly required. Unpack the pump and motor and examine for any

More information

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3.

REF. NO Clamp Assembly 8 1 set Gasket (4 per set) S.S. Lock-washer 3/8 x 1/ Brass Impeller 3. 4.4 SUPPLY PUMPAK ASSEMBLY NOTE: This section applies only to systems, which include a supply pumpak. Only the H6, XA, and XC series systems contain a supply pumpak. If your system is a single zone, H6

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

569, 570, 571, 572 Series

569, 570, 571, 572 Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

568X, 587X, 588X Series

568X, 587X, 588X Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

LC Series - Light Commercial Pump Station Installation and Operation Manual

LC Series - Light Commercial Pump Station Installation and Operation Manual LC Series - Light Commercial Pump Station Installation and Operation Manual Please keep this manual with the pump station Content Rain Bird LC Series Overview... Safety Instruction... Operation... 3 Pump

More information

569, 570, 571, 572 Series

569, 570, 571, 572 Series Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions. Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

AC 4 & 5 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY ELECTRICAL CONNECTIONS INSTALLATION

AC 4 & 5 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY ELECTRICAL CONNECTIONS INSTALLATION AC 4 & 5 HORIZONTAL SERIES Sealed Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY PUMPS WITH MOTORS 1. No assembly required. Unpack the pump and motor and examine for any

More information

AC6/6H & AC8/8H Horizontal Metric Models

AC6/6H & AC8/8H Horizontal Metric Models AC6/6H & AC8/8H Horizontal Metric Models ASSEMBLY, INSTALLATION AND OPERATION MANUAL Part No. 108203 EU Declaration of Conformity Finish Thompson Inc. hereby declares that the following machine(s) fully

More information

Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95

Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B A-95 thru 394D-95, 399A-95 Specifications Information and Repair Parts Manual 316A-95, 316B-95, 393A-95, 393B-95 394A-95 thru 394D-95, 399A-95 Please read and save this Repair Parts Manual. Read this manual and the General Operating

More information

Warranty Details page 2. Pump Description & Technical page 3 Specifications. Transportation, Storage & Installation page 4. Pump Maintenance page 5

Warranty Details page 2. Pump Description & Technical page 3 Specifications. Transportation, Storage & Installation page 4. Pump Maintenance page 5 5 . Manual Contents Warranty Details page 2 Pump Description & Technical page 3 Specifications Transportation, Storage & Installation page 4 Pump Maintenance page 5 Wet end Dismantling page 6 Wet end Assembly

More information

SERVICE MANUAL. 300 Series Motorized 35650, 35651, 35652, 36750, 36751, and Model

SERVICE MANUAL. 300 Series Motorized 35650, 35651, 35652, 36750, 36751, and Model Section: MOYNO 500 PUMPS Page: 1 of 4 Date: March 1, 1998 SERVICE MANUAL MOYNO 500 PUMPS 300 Series Motorized 35650, 35651, 35652, 36750, 36751, and 36752 Model DESIGN FEATURES Housing: Cast iron/316 SS

More information

KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions

KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY Unpack pump from carton and check for shipping damage. WARNING: Magnetic field hazard. This pump

More information

OWNERS GUIDE TO INSTALLATION AND OPERATION

OWNERS GUIDE TO INSTALLATION AND OPERATION OWNERS GUIDE TO INSTALLATION AND OPERATION SPM SERIES HIGH POWER CENTRIFUGALS READ THESE INSTRUCTIONS CAREFULLY Read these installation instructions in detail before installing your pump. Be sure to check

More information

INSTALLATION & OPERATING INSTRUCTIONS

INSTALLATION & OPERATING INSTRUCTIONS INSTALLATION & OPERATING INSTRUCTIONS WARNING RISK OF ELECTRIC SHOCK. CONNECT ONLY TO A CIRCUIT PROTECTED BY A GROUND-FAULT CIRCUIT-INTERRUPTER. THE UNIT SHOULD BE INSTALLED BY A QUALIFIED SERVICE REPRESENTATIVE.

More information

SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½

SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½ SERIES 'HE' PLASTIC HORIZONTAL PUMP MODEL: H2 x1½ OPERATION AND SERVICE GUIDE O-820_R FEBRUARY 2013 Refer to Bulletin P-201 and Parts Lists: P-7200, P-7250. SAFETY PRECAUTIONS BEFORE STARTING PUMP 1. Read

More information

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW) The contents of this publication are based on the latest information available and the materials that are used at the time of printing.

More information

GP22/32 SERIES Sealed Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions

GP22/32 SERIES Sealed Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions GP22/32 SERIES Sealed Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY Unpack pump from carton and check for shipping damage. PUMPS WITH MOTOR No assembly required. Simply

More information

Types TMUB, TMUAH and. J Jockey Pumps

Types TMUB, TMUAH and. J Jockey Pumps Multistage Diffuser Pumps Types TMUB, TMUAH and J Jockey Pumps Instructions Installation Operation Maintenance Read this entire book before attempting to install, operate or repair these controls. Properly

More information

INSTRUCTION AND REPAIR MANUAL

INSTRUCTION AND REPAIR MANUAL SECTION 6 ITEM 390 DATED JANUARY 2003 SUPERSEDES SECTION 6 ITEM 390 DATED OCTOBER 2000 INSTRUCTION AND REPAIR MANUAL SERIES 390 6 The 390 Series is a superior commercial Multi-Stage Vertical In-Line Centrifugal

More information

MECHANICAL SEAL REPLACEMENT UNPACKING MAINTENANCE. Figure 1 & 2 - Mechanical Seal Replacement

MECHANICAL SEAL REPLACEMENT UNPACKING MAINTENANCE. Figure 1 & 2 - Mechanical Seal Replacement Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S12 S16 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD VALVES,

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

BELT DRIVEN STATIONARY AGITATOR

BELT DRIVEN STATIONARY AGITATOR BELT DRIVEN STATIONARY AGITATOR INSTRUCTION MANUAL www.usfarmsystems.com 2955 S. K Street Tulare, CA. 93274 (559)685-0340 (800)811-9462 Fax (559)685-9160 Revision Date 9/7/2017 TABLE OF CONTENTS How to

More information

"S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S2 S4 S5 SS6 SS7 S8

S SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S2 S4 S5 SS6 SS7 S8 Webster Pumps "S" SERIES IMMERSIBLE PUMP OWNER'S MANUAL INSTALLATION OPERATION PARTS Models S2 S4 S5 SS6 SS7 S8 PLEASE READ THE FOLLOWING INFORMATION PRIOR TO INSTALLING AND USING Webster PUMPS or HAYWARD

More information

High Output Vacuum/Pressure Pump

High Output Vacuum/Pressure Pump High Output Vacuum/Pressure Pump User Guide Catalogue Numbers: WP62 115 60 (115 V, 60 Hz) WP62 220 50 (230 V, 50 Hz, 1.1 A) WP62 100 60 (100 V, 50/60 Hz) Notice The information in this document is subject

More information

This label warns for risk of electrical shock when failing to observe.

This label warns for risk of electrical shock when failing to observe. MANUAL horizontal centrifugal pumps MB series ic drive SB series mechanical seal 1. Introduction 2. Safety precautions 3. Receipt 4. Installation / Operation and Maintenance 4.1 Installation 4.2 Operation

More information

Instruction and Maintenance Manual. Spiral Heat Exchanger

Instruction and Maintenance Manual. Spiral Heat Exchanger Instruction and Maintenance Manual Spiral Heat Exchanger 1. Content Description... Section 2 Introduction... Section 3 Important safety Precautions... Section 4 Generally... Section 5 Correct Installation...

More information

MECHANICAL SEAL REPLACEMENT UNPACKING MAINTENANCE. Figure 1 & 2 - Mechanical Seal Replacement

MECHANICAL SEAL REPLACEMENT UNPACKING MAINTENANCE. Figure 1 & 2 - Mechanical Seal Replacement Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions

KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions KC22/32 SERIES Sealless Non-Metallic Centrifugal Pumps Installation and Maintenance Instructions ASSEMBLY Unpack pump from carton and check for shipping damage. WARNING: Magnetic field hazard. This pump

More information

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H

SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H SELF-PRIMING CENTRIFUGAL PUMPS BMLS-M & BMLS-H INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS HP Phase Medium Head High Head 3 1 BMLS 300 M BMLS 300 H 3 3 BMLS 300 M3 BMLS 300 H3 5 1 BMLS 500 M BMLS

More information

1 1/8 Inch Centrifugal Pump Operation and Maintenance Guide

1 1/8 Inch Centrifugal Pump Operation and Maintenance Guide 1 1/8 Inch Centrifugal Pump Operation and Maintenance Guide Installation Location! The pump should be located as close as possible to the liquid source so that the suction line can be as short and direct

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Dust Extractor S13 READ ALL INSTRUCTIONS BEFORE USING Introduction Dear Customer, Thank you for choosing Ermator as your supplier. We hope that the Ermator S13 dust extractor will

More information

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS

INFRARED IP55 HEATER INSTRUCTIONS FOR: MODEL:- QZWP45N 1. SAFETY INSTRUCTIONS INSTRUCTIONS FOR: INFRARED IP55 HEATER MODEL:- QZWP45N Thank you for purchasing a Consort Claudgen product. Manufactured to a high standard this product will, if used according to these instructions and

More information

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance 1.0 INTRODUCTION AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance The Nuaire Short Cased Axial Fan range is produced in a range of sizes from 250mm to 1600mm diameter. Cases are manufactured

More information

TQ Series. Electronic Control Pump Instruction Manual. 50Hz. ISO 9001 Certified Walrus Pump Co., Ltd.

TQ Series. Electronic Control Pump Instruction Manual. 50Hz. ISO 9001 Certified Walrus Pump Co., Ltd. TQ Series Electronic Control Pump Instruction Manual 50Hz ISO 9001 Certified Walrus Pump Co., Ltd. EC Declaration of Conformity Manufacturer: Walrus Pump Co., Ltd. Address: No. 83-14, Dapiantou, Sanjhih

More information

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016 SECTION 23 21 23 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions and Division 01 Specification Sections, apply to this Section.

More information

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL TUBE AXIAL FANS BTA, WTA, HTA, DDA The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

SMF PUMP OWNER S MANUAL

SMF PUMP OWNER S MANUAL SMF PUMP OWNER S MANUAL IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING: Before installing this product, read and follow all warning notices and instructions

More information

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM 216279-000 rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM IDENTIFYING YOUR SYSTEM IOM216279-000 The HOTSTART heating system is designed to heat fluids for use in marine

More information

PENGUIN SERIES HSC PUMPS INTRODUCTION

PENGUIN SERIES HSC PUMPS INTRODUCTION PENGUIN Installation & Maintenance SERIES HSC PUMPS MODELS HSC-1/4 HSC-1/2 HSC-3/4 HSC-1 HSC-2 HSC-3 SEALS S - Single D - Double M - Single/Multi-Stage INTRODUCTION Penguin 316 stainless steel centrifugal

More information

E.2 series high efficiency circulator. Installation and operating instructions

E.2 series high efficiency circulator. Installation and operating instructions E.2 series high efficiency circulator Installation and operating instructions File No: 10.84 Date: august 16, 2012 Supersedes: 10.84 Date: july 20, 2010 contents 1.0 Operating limits 4 2.0 Electrical

More information

Mechanical Seal RG-4 stationary, double, liquid sealed

Mechanical Seal RG-4 stationary, double, liquid sealed Series SCK INSTALLATION AND OPERATING MANUAL Translation of the original manual Mechanical Seal RG-4 stationary, double, liquid sealed Keep for future use! This operating manual must be strictly observed

More information

CR A-F-A-E-HQQE 3x400/ HZ

CR A-F-A-E-HQQE 3x400/ HZ GRUNDFOS DATA BOOKLET CR45-12-2 A-F-A-E-HQQE 3x4/69 5 HZ Grundfos Pump 96122818 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/96122818/cr-45-12-2-a-f-a-e-hqqe.html

More information

KQ Series. Multistage Booster Pump System. Installation Manual. ISO 9001 Certified KQ200/400 KQ800

KQ Series. Multistage Booster Pump System. Installation Manual. ISO 9001 Certified KQ200/400 KQ800 KQ Series Multistage Booster Pump System Installation Manual KQ200/400 KQ800 ISO 9001 Certified Description The KQ series booster pump is an all-in-one compact and reliable automatic multistage centrifugal

More information

STAINLESS STEEL UNITS

STAINLESS STEEL UNITS Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL

ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL ECONO FLO 2.7HP VARIABLE SPEED PUMP OWNER S MANUAL IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS WARNING: Before installing this product, read and follow all warning

More information

OPERATION & MAINTENANCE MANUAL FOR VIL VERTICAL INLINE PUMPS TYPES CS, CC, RC, AND DS

OPERATION & MAINTENANCE MANUAL FOR VIL VERTICAL INLINE PUMPS TYPES CS, CC, RC, AND DS OPERATION & MAINTENANCE MANUAL FOR VIL VERTICAL INLINE PUMPS TYPES CS, CC, RC, AND DS PATTERSON PUMP COMPANY A GORMAN-RUPP COMPANY PO Box 790 2129 Ayersville Road Toccoa, Georgia 30577 Telephone: 706-886-2101

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. McDonnell & Miller Installation & Maintenance Instructions MM-607(B) Series FS7-4 Industrial Liquid Flow Switch (specified models only) Series FS7-4 OPERATION This control is an independently mounted water

More information

VERTICAL GLANDLESS PUMP

VERTICAL GLANDLESS PUMP VERTICAL GLANDLESS PUMP INSTALLATION, OPERATION AND MAINTENANCE MANUAL INDEX Sl.No CONTENTS Page No. 1 Introduction 02 2 Unpacking 04 3 Installation procedure for VGP (Pump dispatched without motor) 07

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

OPERATING INSTRUCTIONS

OPERATING INSTRUCTIONS OPERATING INSTRUCTIONS Dust Extractor T12600 READ ALL INSTRUCTIONS BEFORE USING Dear Customer. Thank you for choosing Ermator as your supplier. Introduction We hope that the Ermator dust extractor will

More information

Installation and operating instructions. E.2 Series high efficiency circulator

Installation and operating instructions. E.2 Series high efficiency circulator Installation and operating instructions E.2 Series high efficiency circulator File No: 10.84 Date: august 16, 2012 Supersedes: 10.84 Date: july 20, 2010 contents 1.0 Operating limits 4 2.0 Electrical

More information

Model Series. PumpAgents.com - buy pumps and parts online QUIET - FLUSH ELECTRIC TOILET. Model Series FEATURES SPECIFICATIONS INSTALLATION

Model Series. PumpAgents.com - buy pumps and parts online QUIET - FLUSH ELECTRIC TOILET. Model Series FEATURES SPECIFICATIONS INSTALLATION PumpAgents.com - Click here for Pricing/Ordering Model 37045-Series QUIET - FLUSH ELECTRIC TOILET FEATURES Very quiet flush cycle - like a household toilet Single button flush actuator - with dual function

More information

The Marine Throne. Model TMT S/37045/X-Series QUIET - FLUSH ELECTRIC TOILET. "all the comforts of home" FEATURES SPECIFICATIONS INSTALLATION

The Marine Throne. Model TMT S/37045/X-Series QUIET - FLUSH ELECTRIC TOILET. all the comforts of home FEATURES SPECIFICATIONS INSTALLATION The Marine Throne "all the comforts of home" Model TMT S/37045/X-Series QUIET - FLUSH ELECTRIC TOILET FEATURES Very quiet flush cycle - like a household toilet Single button flush actuator - with dual

More information

Hazardous Location Heaters. Thermostat INSTRUCTION MANUAL

Hazardous Location Heaters. Thermostat INSTRUCTION MANUAL Hazardous Location Heaters Thermostat INSTRUCTION MANUAL Rev. K 2018 nvent P/N 89115890 TABLE OF CONTENTS Warranty and Return Policy...2 Application...3 Control Accuracy...3 Technical Data...3 Design Data...3

More information

QUICK PRIME INSTALLATION AND SERVICE MANUAL

QUICK PRIME INSTALLATION AND SERVICE MANUAL QUICK PRIME INSTALLATION AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. Part #

More information

CR A-F-A-E-HQQE 3x400/ HZ

CR A-F-A-E-HQQE 3x400/ HZ GRUNDFOS DATA BOOKLET CR32--2 A-F-A-E-HQQE 3x/69 5 HZ Grundfos pump 9612212 Thank you for your interest in our products. Please contact us for more information, or visit our website https://www.lenntech.com/grundfos/crfam/9612212/cr-32--2-a-f-a-e-hqqe.html

More information

CONSTANT SUCTION UNIT

CONSTANT SUCTION UNIT CONSTANT SUCTION UNIT OPERATOR/MAINTENANCE M A N U A L Squire-Cogswell/Aeros Instruments Inc 1111 Lakeside Drive Gurnee, IL 60031-4099 1-800-662-5822/847-855-0800 Fax: 847-855-6218 www.aerosinstruments.com

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

QUICK PRIME INSTALLATION AND SERVICE MANUAL

QUICK PRIME INSTALLATION AND SERVICE MANUAL QUICK PRIME INSTALLATION AND SERVICE MANUAL NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. Part #

More information

CR5-9 A-FGJ-A-E-HQQE 1x220/240 50HZ

CR5-9 A-FGJ-A-E-HQQE 1x220/240 50HZ GRUNDFOS DATA BOOKLET CR5-9 A-FGJ-A-E-HQQE 1x2/24 5HZ Grundfos Pump 96537532 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/96537532/cr-5-9-a-fgj-a-e-hqqe.html

More information

Panel Fan Series Operators Manual (Galvanized and Polymer)

Panel Fan Series Operators Manual (Galvanized and Polymer) Panel Fan Series Operators Manual (Galvanized and Polymer) Galvanized Panel Fan with Three Wing Blade IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble,

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

DESCRIPTION MAINTENANCE INSTALLATION OF NEW SEAL REMOVAL OF OLD SHAFT SEAL

DESCRIPTION MAINTENANCE INSTALLATION OF NEW SEAL REMOVAL OF OLD SHAFT SEAL Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

! WARNING. Before using product, read and understand instructions.

! WARNING. Before using product, read and understand instructions. Installation & Maintenance Instructions MM-60C) Series FS4-3 General Purpose Liquid Flow Switch specified models only) Now with Stainless Steel Paddles OPERATION This control is an independently mounted

More information

CRN A-F-G-E-HQQE 3x400D 50 HZ

CRN A-F-G-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CRN45-2-2 A-F-G-E-HQQE 3x4D 5 HZ Grundfos Pump 96123118 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn45/96123118/crn-45-2-2-a-f-g-e-hqqe.html

More information

INSTALLATION & OPERATION MANUAL

INSTALLATION & OPERATION MANUAL 216300-000 rev2 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM FOR HAZARDOUS LOCATIONS MODEL OSE OSX (this page intentionally left blank) IDENTIFYING YOUR SYSTEM IOM216300-000 The HOTSTART

More information

CR64-1 A-F-A-E-HQQE 3x400D 50 HZ

CR64-1 A-F-A-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CR64-1 A-F-A-E-HQQE 3x4D 5 HZ Grundfos Pump 96123527 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/96123527/cr-64-1-a-f-a-e-hqqe.html

More information

CR A-F-A-V-HQQV 3x400D 50 HZ

CR A-F-A-V-HQQV 3x400D 50 HZ GRUNDFOS DATA BOOKLET CR9-1-1 A-F-A-V-HQQV 3x4D 5 HZ Grundfos Pump 9612486 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/9612486/cr-9-1-1-a-f-a-v-hqqv.html

More information

CR A-F-A-E-HQQE 3x400D 50 HZ

CR A-F-A-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CR64-2-2 A-F-A-E-HQQE 3x4D 5 HZ Grundfos Pump 96123528 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/96123528/cr-64-2-2-a-f-a-e-hqqe.html

More information

CR32-4 A-F-A-E-HQQE 3x400D 50 HZ

CR32-4 A-F-A-E-HQQE 3x400D 50 HZ GRUNDFOS DATA BOOKLET CR32-4 A-F-A-E-HQQE 3x4D 5 HZ Grundfos Pump 9612213 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crfam/9612213/cr-32-4-a-f-a-e-hqqe.html

More information

CombiBloc Close-coupled centrifugal pumps

CombiBloc Close-coupled centrifugal pumps CombiBloc Close-coupled centrifugal pumps CombiBloc CombiBloc is the premier solution for pumping clean thin liquids in a very cost-effective way. The pump is part of Johnson Pump s Combi-system, a modular

More information

SuperKlean Washdown Products

SuperKlean Washdown Products DURAREEL DR8 & DR8S INSTALLATION AND MAINTENANCE INSTRUCTIONS **DO NOT THROW AWAY AFTER INSTALLATION** **SAVE AND DISPLAY PROMINENTLY WHERE THIS EQUIPMENT IS USED** GENERAL WARNINGS High pressure and hot

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

Mechanical seals external, single or double, to DIN EN 12756

Mechanical seals external, single or double, to DIN EN 12756 INSTALLATION AND OPERATING MANUAL Translation of the original manual Series SCK Bearing pedestal group: 0 Mechanical seals external, single or Keep for future use! This operating manual must be strictly

More information

CRN90-1 A-F-G-V-HQQV 3x400D 50 HZ

CRN90-1 A-F-G-V-HQQV 3x400D 50 HZ GRUNDFOS DATA BOOKLET CRN9-1 A-F-G-V-HQQV 3x4D 5 HZ Grundfos Pump 96124237 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn9/96124237/crn-9-1-a-f-g-v-hqqv.html

More information

MARLOW PUMPS RECIRCULATION

MARLOW PUMPS RECIRCULATION End suction centrifugal pump line available in both close coupled and frame mounted configurations allow users to meet exactly most flow conditions on commercial pool and waterpark applications. Features

More information

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP

DS series STERLING PUMPS. Industrial End Suction Pumps ISO/DP DS series Industrial End Suction Pumps ISO/DP 5199 www.sterlingpumps.com.au DS series Capacities from: Heads from: 340 to 5,680 m3/h (1,500 to 25,000 USPGM) 21 to 106 metres (70 to 350 feet) Power range

More information

Multistage Centrifugal Pumps with Shaft Sealing Type HZ / HZA / HZAR

Multistage Centrifugal Pumps with Shaft Sealing Type HZ / HZA / HZAR Multistage Centrifugal Pumps with Shaft Sealing Type HZ / HZA / HZAR General DICKOW-pumps of series HZ/HZA are single- or multistage centrifugal pumps with shaft sealing. Application HZ/HZA-pumps are applied

More information

316 Stainless Steel Close- Coupled Self-Priming Flexible Impeller Pumps

316 Stainless Steel Close- Coupled Self-Priming Flexible Impeller Pumps Please read and save this Repair Parts Manual. Read this manual and the General Operating Instructions carefully before attempting to assemble, install, operate or maintain the product described. Protect

More information

CombiChem Centrifugal pumps. according to ISO 5199 and ISO 2858 / EN (DIN 24256)

CombiChem Centrifugal pumps. according to ISO 5199 and ISO 2858 / EN (DIN 24256) CombiChem Centrifugal pumps according to ISO 5199 and ISO 2858 / EN 22858 (DIN 225) CombiChem No limits to reliability! CombiChem is Johnson Pump s solution for liquid transport in the chemical industry.

More information

3020/3120 Series DEMING PUMPS. Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet

3020/3120 Series DEMING PUMPS. Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet 3020/3120 Series Frame-mounted and close-coupled Enclosded and semi-enclosed impeller Capacities to 4,000 GPM Heads to 780 feet A Crane Co. Company DEMING PUMPS Introducting Deming 3020/3120 Series End-Suction

More information

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,

More information

17 U.S. gallon portable low profile drain with electric pump

17 U.S. gallon portable low profile drain with electric pump Assembly and operation instructions 17 U.S. gallon portable low profile drain with electric pump Model 3669 Date of issue February 2018 Form number 404513 Version 2 Contents Safety...........................

More information

DNJ SERIES PUMPS END SUCTION CLOSE COUPLED

DNJ SERIES PUMPS END SUCTION CLOSE COUPLED DNJ SERIES PUMPS END SUCTION CLOSE COUPLED DNJ SERIES PUMPS These are close coupled with standard JM solids shaft ball bearing motors specially designed for pump applications in accordance with standards

More information

OWNERS GUIDE TO INSTALLATION AND OPERATION END SUCTION CENTRIFUGAL PUMPS

OWNERS GUIDE TO INSTALLATION AND OPERATION END SUCTION CENTRIFUGAL PUMPS OWNERS GUIDE TO INSTALLATION AND OPERATION END SUCTION CENTRIFUGAL PUMPS IL00 Figure - CJ0, EL0 Series IL0 Figure - CJ0, EL0 Series Drain Plug READ THESE INSTRUCTIONS CAREFULLY Read these installation

More information

CP-200 S&T. CP Warewash Pump Instruction & Operation Manual Speed & Time , Rev1.0, , Page 1 of 8

CP-200 S&T. CP Warewash Pump Instruction & Operation Manual Speed & Time , Rev1.0, , Page 1 of 8 CP-200 - Warewash Pump Instruction & Operation Manual Speed & Time 20-08606-01, Rev1.0, 20.07.2012, Page 1 of 8 Contents A) Description B) Site Survey and Installation Requirements C) Package Contents

More information

CR20-07 A-F-A-E-HQQE 3x400/ HZ

CR20-07 A-F-A-E-HQQE 3x400/ HZ GRUNDFOS DATA BOOKLET CR2-7 A-F-A-E-HQQE 3x4/69 5 HZ Grundfos pump 965513 Thank you for your interest in our products. Please contact us for more information, or visit our website https://www.lenntech.com/grundfos/crfam/965513/cr-2-7-a-f-a-e-hqqe.html

More information

Manual OW Caution:

Manual OW Caution: Caution: Warning: This manual should be fully read and understood before starting installation! Power supply 230 V 50/60 Hz! Run cooling unit always with correct oil level otherwise damage of pump may

More information

F-P, F-L, FT-P AND FT-L SERIES 2/3 JACKETED DIRECT STEAM TILTING & STATIONARY KETTLES PARTS AND SERVICE MANUAL

F-P, F-L, FT-P AND FT-L SERIES 2/3 JACKETED DIRECT STEAM TILTING & STATIONARY KETTLES PARTS AND SERVICE MANUAL F-P, F-L, FT-P AND FT-L SERIES 2/3 JACKETED DIRECT STEAM TILTING & STATIONARY KETTLES PARTS AND SERVICE MANUAL EFFECTIVE NOVEMBER 2, 2015 Superseding All Previous Parts Lists. The Company reserves the

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

sta-rite Call C and CC Series Installation/Operation/Parts For further operating, installation, or maintenance assistance:

sta-rite Call C and CC Series Installation/Operation/Parts For further operating, installation, or maintenance assistance: OWNER S MANUAL Centrifugal Pumps sta-rite C and CC Series 2791 0397 Installation/Operation/Parts For further operating, installation, or maintenance assistance: Call 1-888-782-7483 293 WRIGHT STREET, DELAVAN,

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

380 Series Multi-Stage Centrifugal Pumps

380 Series Multi-Stage Centrifugal Pumps 380 Series Multi-Stage Centrifugal Pumps Flows to: 2,500 GPM Heads to: 2100 Feet Temperatures to: 500+ F TDH - Feet 140 Years of Pump Manufacturing American-Marsh Pumps, one of the oldest pump lines in

More information