KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

Size: px
Start display at page:

Download "KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE"

Transcription

1 KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

2 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information Safety notes Technical description Transport Mounting instructions Commissioning Installation and maintenance Scrapping Spare parts Air flow measurement Code key Declaration of conformity...17

3 GLEC-6 - Installation and maintenance 3 1 IMPORTANT INFORMATION Fläkt Woods GLEC-6 kitchen exhaust fan is tested by Fläkt Woods according to EN standard and the fan complies with health and safety of the EC Machinery Directive. All fans leave the factory after being subjected to testing. These instructions are intended for use by professional service staff. The installation, commissioning and operation of the fans must be carried out by professional staff, familiar with the safety regulations. Tools and protective equipment necessary for preventing accidents from occurring while installing and operating the fan must be used/worn in accordance with the local safety regulations. All personnel involved with the product must carefully study this operating manual and diligently comply with all orders and instructions. Fläkt Woods does not accept responsibility for any damage that can be attributed to nonobservance of these instructions. The warranty issued by the manufacturer will be forfeited if any changes to the product are made without the manufacturer s consent. 2 SAFETY NOTES This symbol is designed to point out all safety and danger related information regarding danger on the operating personnel s lives and health.

4 4 GLEC-6 - Installation and maintenance 3 TECHNICAL DESCRIPTION 3.1 CONSTRUCTION Motor 2. Motor bracket 3. Inlet connection 4. Standing skid 5. Impeller 6. Vibration damper 7. Lifting lug 8. Inlet cone 9. Outlet connection 10. Cleaning hatch 11. Front plate 12. Back plate 13. Speed controller 14. Mounting bracket for speed controller 3.2 SPECIFICATION The kitchen exhaust fan GLEC-6 is a radial fan with casing designed for use as an exhaust fan in high temperature use or as dual purpose fan in standard conditions. The fan has a split casing as standard for easier transport to the installation site. The fan is driven by 1x230 or 3x400 VAC 50 Hz, insulation class F/temperature rise class B permanent magnet motor. Motor is always equipped with speed controller. Fan type: GLEC radial box-fan Fire resistance class: F300(60), tested by Fläkt Woods Motor: 1x230 or 3x400 VAC, 50 Hz permanent magnet motor 3.3 FAN AND MOTOR RANGE Fan code Motor code Speed controller code Motor Drive Power (kw) Speed (r/min) Current (A) Voltage (V) Current (A) GLEC APEL FWD x230 VAC 50/60 Hz ±10% 3 GLEC APEL FWD x230 VAC 50/60 Hz ±10% 8.5 GLEC APEL FWD x VAC 50/60 Hz ±10% 4.2

5 GLEC-6 - Installation and maintenance DIMENSIONS Ø Outlet B C 44 Ø Inlet H D A L E W Fan size A B C D E H L W Ø Inlet Ø outlet Weight, kg

6 6 GLEC-6 - Installation and maintenance 4 TRANSPORT 4.1 TRANSPORT INSPECTION Check the fan immediately after you receive it and make sure that it has not been damaged during transport. If you discover any damage, get in touch with the transportation company without delay. Check the information on the fan rating plate. Proper procedures must be followed when transporting the pro duct! Faulty conditions in transporting may result in serious damage on the product. 4.2 TRANSPORT SAFETY The transport material is to be selected according to the packaging and the weight of the product. Loading must be carried out as instructed. 4.3 INTERMEDIATE STORAGE If the fan is to be stored before or in between uses, the following needs to be taken in account: - Original packaging is to be used. If the storage conditions require it, additional protection may be added - During long time storage indoor premises must be used. 4.4 LIFTING The fan has removable lifting lugs. Proper procedures must be followed when lifting the fan! For fan weights, see 3.4 Dimensions or name plate of fan.

7 GLEC-6 - Installation and maintenance 7 5 MOUNTING INSTRUCTIONS 5.1 INSTALLATION OF THE FAN The fan is secured to a base by M8 pin bolts and nuts (4 pcs) in mounting holes across antivibration mountings, included in delivery (see 3.1 Design, part 5). The base must be level and stable. The fan must only be mounted to a horizontal plane. The fan has three possible outlet directions (left/right/up), upwards as standard. Outlet direction can be changed by detaching the standing skids (see 3.1 Design, part 4) and placing them to desired side of fan casing (fixed with M8 bolts). Lower cleaning hatch handle must be removed DISMANTLING THE FAN If the final installation site is difficult to access, the fan has a split casing as standard for easier transport. If the fan has been in use and will be removed and dismantled, make sure that the fan is disconnected from mains (supply- and control cables detached) and ducting before beginning the dismantling work. 2. Detach the outlet connection by removing self-drilling screws. 3. Detach both cleaning hatches, fastened with M8 bolts. Mark the overlap between impeller&inlet cone. 1. Install support stands to back plate and standing skids with M8 bolt and self-drilling screw. Stands are delivered loose with the fan. Support stand Self-drilling screw M8 bolt Overlap between impeller and inlet cone 4. Remove M8 fixing bolts from the front plate end of the standing skids. Lift the fan up a little. Make sure that the fan can t fall down.

8 8 GLEC-6 - Installation and maintenance 5. Remove M8 socket cap fixing bolts from back plate and M8 fixing bolts from both side members. 7. Remove impeller locking screw and washer from the motor shaft end and pull the impeller out, if necessary use the extraction tool. 6. The front section can be lifted off now. 8. Detach the motor cable from speed controller. Remove M8 bolts from both sides of the motor bracket and lift the motor (with bracket still intact) away. Speed controller can be removed by detaching the mounting bracket screws (both sides of the bracket) and lifting it away with bracket still intact.

9 GLEC-6 - Installation and maintenance 9 If needed for easier motor and speed controller removal, the back plate can be laid face down by detaching the self-drilling screws from the standing skids, loosening standing skid M8 bolts and turning the standing skids 90 to side. Standing skids can also be completely removed. 11. Detach side members by removing the M8 bolts. Loosen standing skid bolt When disassembling the front section, it could be useful to mark part positions for easier reassembly. 9. Detach the cut-off by removing the M8 socket cap fixing bolts from front plate and M8 bolts from side member REASSEMBLING THE FAN Note that there is a glass fiber sealing installed between panels, side members and outlet connection. Remember to inspect the glass fiber sealing from defects and replace if necessary. Remember to check that the overlap is the same as measured before and the inlet cone is precisely aligned with the impeller! 1. Reassemble the front section in reverse order. Insert all bolts, but don t tighten them yet. 10. To detach the front plate, remove the M8 socket cap fixing bolts from front plate and M8 bolts from both side members.

10 10 GLEC-6 - Installation and maintenance 2. Reattach motor and speed controller with mounting brackets. Check that the motor height position is the same as it was. Tighten bolts and screws. 5. Lift the front section back, insert all bolts and check the gap and the overlap between inlet cone and impeller. Tighten all bolts while following that the gap and the overlap are staying stable. 3. Reattach standing skids, if they were removed. Lift the back plate up, turn the standing skids to original position and reattach the standing support screws. 4. Insert the impeller and tighten the end bolt.

11 GLEC-6 - Installation and maintenance Reattach the outlet connection. 5.2 OUTDOOR INSTALLATION If the fan is installed outdoors, all seams of outer side of the fan casing must be carefully sealed with fireproof sealing compound and rain cover (available as an accessory, see technical catalogue) for motor and speed controller must also be installed, see picture below. Rain cover 7. Reattach both hatches and remove support stands. Speed controller must be moved do fit under rain cover with motor, if needed. UV-shield for speed controller plastic parts (included in rain cover delivery). 5.3 FITTING THE ACCESSORIES Connections to duct system must always be done with flexible connections (available as an accessory, see technical cataloque). Providing necessary grounding for the accessories is within the constructor s field of responsibility. 5.4 SAFETY REGULATIONS The fan is equipped with speed controller, care should be taken that the speed controller is always in upright position, even if the outlet direction is changed. The fan must be always equipped with safety switch. If the fan is delivered without optional safety switch, the switch must be provided otherwise. Residual risk due to inappropriate behavior or malfunction during operation cannot be completely excluded. The system planner or constructor must prevent the emergence of any hazardous situations through suitable safety measures. Note that the impeller may rotate due the air flow in duct system, even if the fan is isolated from mains. Motor terminals may still be Live if the impeller is rotating, even when the main incoming supplied has been isolated. Ensure the impeller is kept stationary before opening and whilst the terminal box is open.

12 12 GLEC-6 - Installation and maintenance 5.5 ELECTRICAL CONNECTIONS All electrical connections must be wired by authorised personnel only. The necessary electrical and safety precautions must be taken into account. The fan must always be equipped with safety switch. Electrical connections shall be done as shown in drawing. Motor cable shall be shielded type. Shield should be grounded 360 at both ends of the cable. If the VSD will be mounted separate from the fan, the motor cable should be no longer than 5 meters. Basic circuit arrangements (not the delivery entities) below: GLEC AND GLEC GLEC

13 GLEC-6 - Installation and maintenance 13 6 COMMISSIONING 7 MAINTENANCE 6.1 SAFETY CHECKING Make sure, that the fan is isolated from mains. Open the cleaning hatch (see 3.1 Design, part 9) and rotate the shaft to check that the impeller can move freely. Make sure that there are no foreign objects in the fan or in the ducting. Also check that there is no unusual noise in the fan. Check that the installation work has been carried out in accordance with the relevant regulations. All necessary protective devices must be installed. Check, that all other regulations related to fire safety are followed. The fan may only be commissioned after all proper procedures have been followed and all necessary inspections have been carried out. 6.2 TEST RUN Briefly switch on the power supply to the motor to check whether the fan impeller rotates in the correct direction. If the impeller is rotating in the correct direction shown with the arrow, the fan may be switched on. Check that no abnormal mechanical sound and no surging occur. 7.1 WARRANTY A precondition of the warranty is that regular maintenance has been carried out. Defects under warranty must immediately be notified to the manufacturer or the importer. The warranty does not cover service work or indirect damages. 7.2 MAINTENANCE BEFORE MAINTENANCE Switch off the power supply to the fan from the safety isolating switch. Wait for the impeller to stop completely. Note that the impeller may rotate due the air flow in duct system, even if the fan is isolated from mains. Motor terminals may still be Live if the impeller is rotating, even when the main incoming supplied has been isolated. Ensure the impeller is kept stationary before opening and whilst the terminal box is open INSPECTION INTERVALS Inspection intervals can be defined by local authorities. If nothing else is mentioned, the fan shall be tested according to the intervals in table, but at least once a year. The annual inspection must be done by authorized personnel only. In order to assure safe operation we recommend to do the checking at regular intervals by specialized personnel or company and to document the results. FAN Pos. Description Commisioning 6 months 12 months 1 Fan is installed properly x x x 2 Flexible connections are OK x x x 3 Fan is visually OK x x x 4 There is no abnormal noise coming from fan x x x 5 Impeller and casing are clean x x x 6 MOTOR AND SPEED CONTROLLER Pos. Description Commisioning 6 months 12 months 1 Check bearing noise during test run x 2 Check proper rotation of impeller x x x 3 Visual control x x x 4 Check, that cabling is done in a proper way x 5 Speed controller is working as planned x x x 6

14 14 GLEC-6 - Installation and maintenance CHECKING THE MOTOR BEARINGS If the fan is used as a dual purpose fan, the motor bearings shall be checked twice a year. After hours it is recommended to change the motor. It is recommended to change the motor every three years CLEANING THE IMPELLER The maximum permissible vibration level measured from the motor bearing is 7,1 mm/s RMS. The impeller can be cleaned using a vacuum cleaner, compressed air or by brushing. If the impeller is coated with greasy dirt, it can be washed with a detergent or a solvent. The cleaning is done if necessary, but a control inspection should be done at least once a year. Badly tarnished impeller will result in lower efficiency of the fan and increases energy consumption. 7.3 FINAL INSPECTION Check that: - The overlap between the impeller and the inlet cone is same as before maintenance. - The inlet cone is aligned precisely with the impeller. - All screws and nuts have been tightened. - Glass fiber sealing is in good condition. - No foreign objects have been left in the fan or in the ducting. 7.4 FAULTS If any faults occur during inspection which cannot be repaired by maintenance personnel, please contact the service department at Fläkt Woods. Examples of faults can include the following issues: - foreign particles inside fan - corrosive media inside - too high vibrations - incorrect maintenance Possible problems generated: - bearing damage - corrosion damage - vibration generated damage CLEANING THE FAN CASING The inside of fan the casing can be cleaned same way as the impeller.

15 GLEC-6 - Installation and maintenance 15 8 SCRAPPING 9 SPARE PARTS Materials used in fan are listed below. Disposing of those materials should be done according to valid instructions. Component Material Standing skids Steel Vibration dampers (rubber) Rubber Fan casing Fan casing Steel Motor bracket Steel Noise isolation Stone wool Inlet cone Steel Impeller Impeller Steel Hub Steel Other Motor See manufacturers instructions Speed controller See manufacturers instructions Airflow measurement nipples PVC Accessories Safety switch PVC/steel Flexible connection PVC/steel Small amounts of other materials may occur. Use only genuine spare parts supplied/accepted by Fläkt Woods. If other spare parts are used, no warranty or EN-certification is valid SPARE PARTS - Motor - Speed controller - Impeller - Inlet cone

16 16 GLEC-6 - Installation and maintenance 10 AIR FLOW MEASUREMENT (OPTIONAL) The airflow sensor is used for measuring the airflow of the fan. The method is based on pressure differential. The pressure is measured at the specific point in the inlet cone and the reference pressure is measured upstream of the inlet cone. The air flow sensor is factory mounted in the inlet cone. 11 CODE KEY Kitchen exhaust fan Type (a) 6 = High temperature Size (bbb) 031, 040, 050 GLEC-a-bbb-c-ddd-0 Motor (c) 1 = 1-phase motor (sizes 031 and 040) 3 = 3-phase motor (size 050) Motor power (ddd) 055 = 0.55 kw (GLEC-6-031) 080 = 0.75 kw (GLEC-6-040) 220 = 2.20 kw (GLEC-6-050) Version (e) 0 The air flow is calculated from the equation: q v = A Dp m k q v = air flow (m 3 /s) k = k-factor (see name plate of each fan) Dp m = differential pressure reading (Pa)

17 GLEC-6 - Installation and maintenance DECLARATION OF CONFORMITY EC Declaration of Conformity Machinery Directive 2006/42/EC, Annex II, sub A Manufacturer: Fläkt Woods Oy Address: Kalevantie 39 FI Turku, Finland Name and address of the person authorised to compile the relevant technical documentation: Name: Heikki Stenberg Address: as above Confirms that: Kitchen exhaust fan GLEC-6 with accessories and EC/PM-motor is in accordance with the Machinery Directive (2006/42/EC) And that the machinery is in conformity with the provisions of the following other EC-Directives: 2014/35/EU Low Voltage Directive 2014/30/EU EMC-Directive 305/2011 EU / regulation, repealing Directive 89/106/EEC) And furthermore, declares that the following (parts/clauses of) European harmonised standards and Regulations have been applied: EN ISO :2010, 13857:2008, EN ,EN ,-2,-3. This Declaration of Conformity is valid only, if the installation is done in accordance with the Machinery Directive 2006/42/EC, where appropriate and that the original accessories are used. Turku, Heikki Stenberg R&D Manager

18 FG_DC_10087-GB_GLEC-6_TE_ _R0_300dpi Copyright 2017 FläktGroup GLEC-6 FläktGroup is the European market leader for smart and energy efficient Indoor Air and Critical Air solutions to support every application area. We offer our customers innovative technologies, high quality and outstanding performance supported by more than a century of accumulated industry experience. The widest product range in the market, and strong market presence in 65 countries worldwide, guarantee that we are always by your side, ready to deliver Excellence in Solutions. PRODUCT FUNCTIONS BY FLÄKTGROUP Air Treatment Air Movement Air Diffusion Air Distribution Air Filtration Air Management Air Conditioning & Heating Controls Service» Learn more on or contact one of our offices

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS Contents Page User instructions 3-5 General 3 Fan installation 3-4 Maintenance 3 Electrical installation 5 Troubleshooting 5 Technical description 6-8 General

More information

English CNA-CNB. Centrifugal fans Installation and maintenance

English CNA-CNB. Centrifugal fans Installation and maintenance 916505-0 English CNA-CNB Centrifugal fans Installation and maintenance 916505-0 GB Centrifugal fans types CNA, CNB, CNA-M and CNB-M installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2

More information

INSTALLATION FB T: +44 (0) F: +44 (0) E: W:

INSTALLATION FB T: +44 (0) F: +44 (0) E: W: INSTALLATION FB 1 Contents User instructions General Fan installation Maintenance Electrical installation Troubleshooting Technical description General Classification Technical specification Manufacturer

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original)

Montageanleitung RLO (Original) Mounting Instructions RLO (Translation of the original) Montageanleitung (Original) (Translation of the original) DE MA_ 1.0 06/2014 Taperlock Clamping-bush system _0 _1 Fixed hub Inlet nozzle with IMV 1. Revision index Revision Date MA_ 1.0 06/2014 2. Safety

More information

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80 EN OPERATING MANUAL OIL HEATER TRT-BA-IDE20-30-50-60-80-TC-001-EN Table of contents Information on the use of this manual... 1 Scope of delivery... 1 General safety...

More information

AXPR Wall Mounted Axial Panel Fans

AXPR Wall Mounted Axial Panel Fans Bulletin 78-January-03-06 AXPR Wall Mounted Axial Panel Fans INSTALLATION, OPERATION, AND MAINTENANCE MANUAL This publication contains the installation, operation and maintenance instructions for the AXPR

More information

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEC exhaust FAN» Technical CATALOUGE Technical catalouge Exhaust Fan GLEC 2 Contents Exhaust fan - GLEC... 3 Performance Data...4 Fan chart-explanation and definitions...

More information

TTV 4500 / TTV 4500 HP / TTV 7000

TTV 4500 / TTV 4500 HP / TTV 7000 TTV 4500 / TTV 4500 HP / TTV 7000 EN OPERATING MANUAL AXIAL FAN TRT-BA-TTV4500-4500HP-7000-TC-003-EN Table of contents The current version of the operating manual can be found at: Notes regarding the operating

More information

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN

PLENUM FAN EQLK PLENUM FAN, DIRECT-DRIVEN EQLK, DIRECT-DRIVEN INSTALLATION AND MAINTENANCE INSTRUCTIONS Contents Page Installation options...... 2 Checks to be made prior to commissioning...2 Electrical connections.....2 Measures before starting.....

More information

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS

PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN » INSTALLATION AND MAINTENANCE INSTRUCTIONS AIR COMFORT AIR TREATMENT 9933 GB 2016.05.25 PlEnum Fan CENTRIFLOW 3D (EQLP) PLENUM FAN, DIRECT-DRIVEN» INSTALLATION AND MAINTENANCE INSTRUCTIONS contents Page Installation options...... 2 Checks to be

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

XB-EFA-8L-BK & XB-EFA-8R-BK

XB-EFA-8L-BK & XB-EFA-8R-BK Supply & Extract Ventilation Unit with Heat Recovery The EMC Directive 2014/30/EU The Low Voltage Directive 2014/35/EU The information contained in this document provides details of installation, operation

More information

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315

USER S MANUAL. Centrifugal inline fan. VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125. VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315 USER S MANUAL VKMz 100 Q VKMz 100 VKMz 125 Q VKMz 125 VKMz 150 VKMz 160 VKMz 200 Q VKMz 200 VKMz 250 Q VKMz 250 VKMz 315 Q VKMz 315 Centrifugal inline fan VKMz CONTENTS Contents... 2 Safety requirements...

More information

SAFETY AND OPERATING MANUAL

SAFETY AND OPERATING MANUAL SAFETY AND OPERATING MANUAL Original instructions 2 General Safety Warnings WARNING! Read all safety warnings and all instructions. Failure to follow the warnings and instructions may result in electric

More information

Fire damper ETPR Instructions for Installation, Operation and Maintenance 10/2016

Fire damper ETPR Instructions for Installation, Operation and Maintenance 10/2016 Instructions for Installation, Operation and aintenance 10/2016 Installation Fire damper ETPR must be installed according to this installation manual, see pages 2-5. Operation and function testing According

More information

3 in 1 Garden Vacuum 9255 Instructions for Use

3 in 1 Garden Vacuum 9255 Instructions for Use Leaf Blower-Vac/Patio Cleaner Technical Specifications Model GY 8113 Rated voltage 230V Rated frequency 50Hz Rated power consumption 3000W Mains fuse(delayed action) 13A Speed 15000 rpm Max. blower air

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA

Operating Instruction Centrifugal fans without scroll (Translation of the Original) BA-RLE-AC /2014 RLE RLA Operating Instruction Centrifugal fans without scroll (Translation of the Original) EN RLE RLA Content 1. Important information 2. Safety notes 3.Technical description 4. Transport 5. Mounting / Installation

More information

Installation manual Mini Comfort 50 S/L 07/ V EN

Installation manual Mini Comfort 50 S/L 07/ V EN Installation manual Mini Comfort 50 S/L 07/2015 - V 1.1 - EN www.veneco-ventilation.be Veneco ventilation by Elek Trends Productions nv Blauwfazantjesstraat 4 B - 7700 Moeskroen Tel. +32 (0)56 48 15 90

More information

TFV 900 OPERATING MANUAL RADIAL FAN TRT-BA-TFV900-TC-001-EN

TFV 900 OPERATING MANUAL RADIAL FAN TRT-BA-TFV900-TC-001-EN TFV 900 EN OPERATING MANUAL RADIAL FAN TRT-BA-TFV900-TC-001-EN Table of contents Notes regarding the operating manual... 1 Safety... 2 Information about the device... 3 Transport and storage... 4 Start-up...

More information

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance

AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance 1.0 INTRODUCTION AXUS - SC Short Cased Axial Flow Fans Installation and Maintenance The Nuaire Short Cased Axial Fan range is produced in a range of sizes from 250mm to 1600mm diameter. Cases are manufactured

More information

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2

Cleaning unit for coolant. :_decftez`_>r_fr] Book No.: V2 Cleaning unit for coolant :_decftez`_>r_fr] Book No.: 1271526-02 V2 Alfa Laval Separation AB Separator Manuals, dept. SKEL S-147 80 Tumba, Sweden Telephone: +46 8 53 06 50 00 Telefax: +46 8 53 03 10 40

More information

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,

More information

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS

AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS AIR HEATING UNIT HEATMASTER ACJB INSTALLATION, OPERATION, MAINTENANCE AND SPARE PARTS 2 Air Heating unit ACJB - Technical manual CONTENTS OPERATION AND MAINTENANCE (FOR USER) System, functions, main components...3

More information

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2

CENTAFLEX Series A Assembly and operating instructions CF-AR M EN Rev. 2 Contents 1 General remarks... 5 2 Safety... 6 2.1 Safety remarks... 6 2.1.1 Signal words... 6 2.1.2 Pictograms... 7 2.2 Qualification of deployed personnel... 7 2.3 Intended application... 7 2.4 Application

More information

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL

CENTRIFUGAL FAN IN SCROLL CASING. Helix S-Vent OPERATION MANUAL CENTRIFUGAL FAN IN SCROLL CASING Helix S-Vent EN OPERATION MANUAL Helix / S-Vent www.blaubergventilatoren.de CONTENTS CONTENTS 3 Introduction 3 Use 3 Delivery set 4 Technical data 10 Safety requirements

More information

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL INLINE CENTRIFUGAL FAN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 4 Fan design 4 Delivery

More information

SINGLE-ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY VENTO V50-1 OPERATION MANUAL

SINGLE-ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY VENTO V50-1 OPERATION MANUAL SINGLE-ROOM REVERSIBLE UNIT WITH HEAT AND HUMIDITY RECOVERY VENTO V50-1 EN OPERATION MANUAL CONTENTS Introduction 3 General 3 Safety rules 3 Transportation and storage rules 3 Manufacturer's warranty 3

More information

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450

1. Description INSTRUCTION FOR AIR BLAST COOLER TYPE COOL 450 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Smoke extract fan SMHA HATCH

Smoke extract fan SMHA HATCH 12.11.2012 Contents Product overview... 3 Construction... 4 Specification... 5 Selection... 6 Installation... 7 Electrical connections... 8 Dimensions and weights... 9 Product code and accessories... 10

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RFEC/U/2017-1 (EN) (valid since 18.08.2017) ROOF FANS RF/EC...-... / RFV/EC...-... Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the

More information

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual UHIR Series Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater Owner s Manual This manual covers installation, maintenance and repair parts. Read carefully before attempting to

More information

Dry cooler Type XP120

Dry cooler Type XP120 61358 Directions for use 1 Declaration by the Manufacturer, Annex II B As defined by the EC Machinery Directive (MD) 98/37/EC, the Low Voltage Directive (LVD) 2006/95/EC and the EMC Directive 2004/108/EC.

More information

OPERATION AND MONTAGE MANUAL ROOF FANS

OPERATION AND MONTAGE MANUAL ROOF FANS NO RF/U/2017 (ENGLISH) (valid since 13.10.2017) ROOF FANS RF / RFV Venture Industries Sp. z o.o. is not responsible for any damage caused by improper use of the fan and reserves the right to modify this

More information

OPERATION MANUAL CENTRIFUGAL INLINE FAN WITH ELECTRONICALLY COMMUTATED MOTOR VKM EC SERIES. F88EN-02.indd :07:11

OPERATION MANUAL CENTRIFUGAL INLINE FAN WITH ELECTRONICALLY COMMUTATED MOTOR VKM EC SERIES. F88EN-02.indd :07:11 OPERATION MANUAL CENTRIFUGAL INLINE FAN WITH ELECTRONICALLY COMMUTATED MOTOR VKM EC SERIES F88EN-02.indd 1 04.09.2015 8:07:11 2 VKM ЕС CONTENT Introduction Use Structural designation key Delivery set Main

More information

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN.

OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. INSTALLATION, OPERATION & SERVICE MANUAL FOR COOLER TYPES OK, OKA, OKAF; ELD; ELDM; ELH; OKC; SC; SCA; SCAF; OK-LN; OKA-LN; OKAF-LN. 1. Introduction This manual is a guide for the installation, maintenance

More information

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material

1. Description INSTRUCTION FOR BLAST COOLER TYPE COOL 250. Material 1. Description General The cooler is used for cooling of water, oil or other liquid by use of air. The liquid is passing in the tubes where it transfere the energy to the air via the fins on the outside

More information

Monitored Pneumatic Valves On Series Ported Manifold

Monitored Pneumatic Valves On Series Ported Manifold Monitored Pneumatic Valves On Series Ported Manifold Patented Technology SUITABLE FOR RISK CATEGORY 4 APPLICATIONS As per EN 954-1 & AS4024.1 SIL 3 as per IEC 61508 Applications Include: Pneumatic Presses

More information

VETO CLEANER 500 FLUE GAS CLEANER

VETO CLEANER 500 FLUE GAS CLEANER As of serial number 3100 0001 VETO CLEANER 500 FLUE GAS CLEANER USER MANUAL SPARE PARTS LIST Manufacturer: ALA TALKKARI Veljekset Ala-Talkkari Oy FI-62130 HELLANMAA TEL. +358 6 433 6333 FAX +358 6 437

More information

USER S MANUAL. VKP Series INLINE FAN

USER S MANUAL. VKP Series INLINE FAN USER S MANUAL Series INLINE FAN 2 CONTENTS Safety requirements 3 Introduction 5 Use 5 Delivery set 5 Designation key 5 Technical data 5 Design and operating logic 8 Mounting and set-up 8 Connection to

More information

INSTRUCTION MANUAL. operates with ISO9001 certified quality system. TECSYSTEM S.r.l Corsico (MI) Tel.: Fax:

INSTRUCTION MANUAL. operates with ISO9001 certified quality system. TECSYSTEM S.r.l Corsico (MI) Tel.: Fax: INSTRUCTION MANUAL BAR 1200-1800-3600 1MN0080 Rev 0 operates with ISO9001 certified quality system TECSYSTEM S.r.l. 20094 Corsico (MI) Tel.: +39-024581861 Fax: +39-0248600783 http://www.tecsystem.it R.

More information

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE

STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE ISO 9001 : 2000 STORAGE, ERECTION, OPERATION AND MAINTENANCE MANUAL FOR CENTRIFUGAL FANS MODEL - MXE CUSTOMER : 1 CONTENTS 1 SAFETY... 5 1.1 General... 6 1.2 Description of symbols and pictograms... 6

More information

Waste water ejection unit

Waste water ejection unit Waste water ejection unit Over ground box SWH 500/50-80 SWH 500/50-80 Operation manual Table of contents: Page Declaration of conformity... 3 1. General... 4 1.1 Introduction... 4 1.2 Enquiries and orders...

More information

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS Installation & Operating Manual 3001806 03.02 USA CAN BESF Box Ventilator READ AND SAVE THESE INSTRUCTIONS 1200 Northmeadow Parkway, STE 180 Roswell, GA 30076 (770) 587-3238 (800) 255-2923 Fax (770) 587-4731

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

ST1. Mod. USE AND MAINTENANCE MANUAL

ST1. Mod. USE AND MAINTENANCE MANUAL Mod. USE AND MAINTENANCE MANUAL 2 Use and Maintenance Manual ---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

More information

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN

TTV 1500 / TTV 3000 OPERATING MANUAL CONVEYING FAN TRT-BA-TTV TC EN TTV 1500 / TTV 3000 EN OPERATING MANUAL CONVEYING FAN TRT-BA-TTV1500-3000-TC2016-26-004-EN Table of contents Notes regarding the operating manual... 2 You can download the current version of the operating

More information

MJC Cartridge Filter Unit Operation & Maintenance

MJC Cartridge Filter Unit Operation & Maintenance 1 of 19 Hodge Clemco Ltd MJC Cartridge Filter Unit Operation & Maintenance Owner s Manual Date of Issue: 19.07.04 TSSM536.1a Hodge Clemco Ltd Orgreave Drive Sheffield S13 9NR Tel: 0114 254 8811 Fax: 0114

More information

Topvex SR 09, 11, Topvex TR Compact Air Handling Units

Topvex SR 09, 11, Topvex TR Compact Air Handling Units Topvex SR 09, 11, Topvex TR 09-15 Compact Air Handling Units Installation instructions Document in original language 125593 A003 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves

More information

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60

HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 HG 675 X 60 HG 675 CX 60 HG 675 CN 60 HG 675 CW 60 1 2 1. : 93/68: 90/396: 2006/95/CE: 2004/108/CE: - 1935/2004:. 2002/95/CE: RoHS 2.,.,,,,...,. (,..)..,,.,. ( ),,, ;,,.,.....,.,,,,,,...,. (..),,.,..,.,,,,

More information

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) Our Expertise, Your Air-Moving Solution ISOLATED DIRECT DRIVE PLENUM FAN (IDDP) PART# 0601710001_rev_A INSTALLATION, OPERATION & MAINTENANCE MANUAL Please read and save these instructions for future reference.

More information

JASOPELS ROTATING FLESHING MACHINE 1-BEAM

JASOPELS ROTATING FLESHING MACHINE 1-BEAM USER MANUAL JASOPELS ROTATING FLESHING MACHINE 1-BEAM ITEM NO. 32200067 Our quality Your choice 2 www.jasopels.com TABLE OF CONTENTS About this document... 3 Declaration of Conformity... 6 Safety... 6

More information

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING

USER S MANUAL. VCU/VCUN Series CENTRIFUGAL FAN IN SCROLL CASING USER S MANUAL VCU/ Series CENTRIFUGAL FAN IN SCROLL CASING 2 CONTENTS Introduction Use Delivery set Designation key Technical data Safety requirements Design and operating logic Mounting and set-up Connection

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20 INSTALLATION, OPERATION AND MAINTENANCE Ariterm Hybrid 20 TABLE OF CONTENTS General...3 Installation... 4-5 Dimensions - with flue gas exhauster...6 Dimensions - without flue gas exhauster...7 Pipe installations...8

More information

½ Monitored Pneumatic Valve Patented Technology

½ Monitored Pneumatic Valve Patented Technology ½ Monitored Pneumatic Valve Patented Technology PBM4-S (Valve only air service equipment not included) SUITABLE FOR RISK CATEGORY 4 APPLICATIONS As per AS4024.1-Part 1502 & 1502 SIL 3 as per IEC 61508

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use

Operating Manual. Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN Safety instructions. 2 General description and use 1 Safety instructions 1.1 Proper use Model: 1400 Model: 1400-N RIFOmat Float-Controlled Condensate Traps, PN 100 Any improper use, intervention in the design and deviation from the design data automatically

More information

½ Monitored Pneumatic Valves On Series Ported Manifold

½ Monitored Pneumatic Valves On Series Ported Manifold ½ Monitored Pneumatic Valves On Series Ported Manifold Patented Technology SUITABLE FOR RISK CATEGORY 4 APPLICATIONS As per AS4024.1-Part 1502 & 1502 SIL 3 as per IEC 61508 & EN ISO 13849-1 Applications

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance. ESX-X Figure 1. ESX-X units. Removable top panel A D Control module located internally External Commissioning box Table 1. ESX-X Dimensions (mm) Spigot Weight Code A B C D dia (kg) ESX1-X 705 505 355 125

More information

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP

HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP HORIZONTAL MULTISTAGE CENTRIFUGAL PUMP WWPPCHLFT260 Instructions WWPPCHLFT260_Horizontal Multistage Centrifugal Pump_IB.indd 1 READ THIS MANUAL CAREFULL BEFORE INSTALL, START THE PUMP 1. Suction 2. Plug

More information

OPERATING MANUAL ORWAK March 2005 PUBL. NO Edition 4

OPERATING MANUAL ORWAK March 2005 PUBL. NO Edition 4 GB OPERATING MANUAL ORWAK 3400 March 2005 PUBL. NO 4869057-00 Edition 4 English TABLE OF CONTENTS Safety... 82 Operating instructions... 93 Technical specifications. 104 Dimensional drawing... 104 Transport...

More information

User Manual GV25 GV35 GV702. Company information: Original instructions GV12066 (1)

User Manual GV25 GV35 GV702. Company information:   Original instructions GV12066 (1) User Manual Original instructions GV25 GV35 GV702 Company information: www.vipercleaning.eu info-eu@vipercleaning.com GV12066 (1) 2012-04-10 USER MANUAL ENGLISH TABLE OF CONTENTS Introduction... 4 Manual

More information

INSTALLATION, OPERATION & MAINTENANCE MANUAL

INSTALLATION, OPERATION & MAINTENANCE MANUAL CENTRAL FANS COLASIT LTD Unit 12A, Palmers Road, East Moons Moat, Redditch. Worcs. B98 0RF Tel: 01527-517200 Fax: 01527-517195 Edition 04_13 INSTALLATION, OPERATION & MAINTENANCE MANUAL CIV Fan Range Valid

More information

Installation/Instruction Manual

Installation/Instruction Manual 1510876HC8902 Pressurized ventilators (for device cooling) Model Blade diameter (cm) Indoor or outdoor EF-20UYS-UL EF-25UAS-UL EF-30UBS-UL 20 25 30 Indoor Installation/Instruction Manual For customers

More information

Operating Instructions

Operating Instructions Operating Instructions Varioset Standard After-sales service For after-sales service please contact the Veit representative in your country. GmbH & Co. Justus - von - Liebig - Str. 15 D - 86899 Landsberg

More information

Novenco Air Handling Units

Novenco Air Handling Units Novenco Air Handling Units Climaster ZCF Guide 919432-0 GB Important This document is provided As is and is subject to change without notice. Novenco reserves this right due to continuous product development.

More information

Air Shower TECHNICAL DATA

Air Shower TECHNICAL DATA TECHNICAL DATA Table of Contents Introduction... 3 Unit setup and components... 3 Cleaning cycle... 4 Control system... 5 Size and dimensions... 6 Configuration of doors... 6 Technical data...8 Testing,

More information

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions

MNEFDD54 & MNBCDD54 GALVANIZED WALL FANS Installation, Operation, and Maintenance Instructions FARM PRODUCTS DIVISION MEMBER OF AMCA AMERICAN COOLAIR CORPORATION P.O. BOX 2300 JACKSONVILLE, FLORIDA 32203 PHONE (904) 389-3646 FAX (904) 387-3449 E-MAIL - fans@coolair.com MNEFDD54 & MNBCDD54 GALVANIZED

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

DanVex AD-200 Adsorption air dehumidifier. Operation manual

DanVex AD-200 Adsorption air dehumidifier. Operation manual DanVex AD-200 Adsorption air dehumidifier Operation manual CONTENT Safety instructions...3 Introduction...4 Purpose...4 Design...4 Operation principle...5 Dimensions and weight...5 Installation...6 Technical

More information

CE Unit is suitable for material transport. The transported gas may be up to 80 C.

CE Unit is suitable for material transport. The transported gas may be up to 80 C. The manual contains: 1 Safety regulations 1.1 Electrical 1.2 Crush risk 1.3 Hazardous dust 1.4 Suction injuries 1.5 Noise 1.6 Pneumatic 1.7 Other equipment 2 Machine Operation 3 Installation Directions

More information

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL TUBO-M/MZ AXIS-QA AXIS-Q TUBO-F AXIS-QR AXIS-F AXIS-QRA AXIS-QA G AXIAL FANS EN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements

More information

Operating instructions Plug Fans Direct driven with asynchronous or PM synchronous motor (Translation of the Original)

Operating instructions Plug Fans Direct driven with asynchronous or PM synchronous motor (Translation of the Original) Operating instructions Plug Fans Direct driven with asynchronous or PM synchronous motor (Translation of the Original) EN BA-CFD_RLM 9.4 09/2014 RLM E3 RLM 53 RLM 55 RLM E6 RLM G6 RLM 56 Contents 1. Important

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

Installation and operating instructions

Installation and operating instructions Installation and operating instructions Agrosec Optivol M11 408107 (en) ANTTI-TEOLLISUUS OY Koskentie 89 FI-25340 Kanunki, Salo Tel. +358 2 774 4700 Fax +358 2 774 4777 E-mail: antti@antti-teollisuus.fi

More information

SELF-PRIMING JET PUMPS

SELF-PRIMING JET PUMPS SS Anti-Rust SS Shaft Copper & Cold-rolled SELF-PRIMING JET PUMPS CONTENTS 1. Applications.... Model Description.... Technical Data... 4. Implementation Standards... 5. Safety Precautions... 6. Product

More information

Operating Instructions!

Operating Instructions! Operating Instructions! 3 4 Oscillation MO 16.2 / MO 40 Example 3 4 MO 16.2 The unit has to be strictly used according to the instruction manual. Keep the unit away from children and from persons not instructed

More information

57" Fiberglass Exhaust Fan with Cone

57 Fiberglass Exhaust Fan with Cone OPERATORS MANUAL Fiberglass Exhaust Fan IMPORTANT: READ AND SAVE THESE INSTRUCTIONS Read all instructions carefully before attempting to assemble, install, operate or service the product described. Failure

More information

SEMAK VITABLEND STICK BLENDER MODELS VB250, VB360, VB410 & VB510

SEMAK VITABLEND STICK BLENDER MODELS VB250, VB360, VB410 & VB510 SEMAK VITABLEND STICK BLENDER MODELS VB250, VB360, VB410 & VB510 OPERATION AND WARRANTY BOOKLET VB250 VB360 VB410 VB510 SEMAK AUSTRALIA: FACTORY 18, 87-91 HALLAM SOUTH ROAD, HALLAM VIC 3803 PH 03 9796

More information

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system INSTRUCTION MANUAL 1MN0110 REV. 0 operates with ISO9001 certified quality system TECSYSTEM S.r.l. 20094 Corsico (MI) Tel.: +39-024581861 Fax: +39-0248600783 http://www.tecsystem.it R. 1.1 25/08/16 ENGLISH

More information

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50 -30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554 Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation

More information

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use TOP INDOOR USE ONLY Introduction Units are rectangular in section and have circular/rectangular rigid spigots at each end. Four matching mounting feet are supplied with the unit. Full size access panels

More information

Directions for use. CPS/XPS - Condensor / Dry cooler

Directions for use. CPS/XPS - Condensor / Dry cooler 61221 Directions for use 1 2 Declaration by the Manufacturer, Annex II B As defined by the EC Machinery Directive (MD) 98/37/EC, the Low Voltage Directive (LVD) 2006/95/EC and the EMC Directive 2004/108/EC.

More information

Original instructions. Operation Manual & Cautions

Original instructions. Operation Manual & Cautions Original instructions Operation Manual & Cautions Thank you for purchasing the Mistresa from Showa Denki. This manual explains the specifications for the [Mistresa units from CRN Series]. Please read the

More information

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX. RG CPAP 24 V mit Powermodul 24V sensorless

Operating manual 1 SAFETY REGULATIONS AND INFORMATION. Original operating manual INDEX. RG CPAP 24 V mit Powermodul 24V sensorless Operating manual RG CPAP 24 V mit Powermodul 24V sensorless 1 SAFETY REGULATIONS AND INFORMATION Read the operating manual carefully before commencing work at the product. Pay attention to the following

More information

Impeller Stack Kit Dismantling and Reassembly CR(I/N) 1S 1 3 5

Impeller Stack Kit Dismantling and Reassembly CR(I/N) 1S 1 3 5 GRUNDFOS CR Series Impeller Stack Kit Dismantling and Reassembly CR(I/N) 1S 1 5 Grundfos Pumps Corporation 17100 W. 118th Terrace Olathe, Kansas 66062 Telephone: 91.227.00 Fax: 91.227.500 www.grundfos.com

More information

24 & 30 INCH DRUM FANS

24 & 30 INCH DRUM FANS 24 & 30 INCH DRUM FANS MODEL NO: CAM24 & CAM30 PART NO: 3231560 / 3231565 OPERATION & MAINTENANCE INSTRUCTIONS GC0414 INTRODUCTION Thank you for purchasing this CLARKE Drum Fan. Before attempting to use

More information

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC AQB09JJ6WC_IM_E_2585 2006.4.17 4:26 PM Page 17 INSTALLATION MANUAL Indoor Unit AQB09JJWC AQB12JJWC Outdoor Unit UQB09JJWC UQB12JJWC ENGLISH FRANÇAIS ESPAÑOL Split-type Air Conditioner (Cooling and Heating)

More information

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Smoke Master SMIA Compact pressurisation and smoke exhaust system Smoke Master SMIA Compact pressurisation and smoke exhaust system Fläkt Woods FIFLO EN 2009.09 2 All rights reserved. Contents System overview... 4 Design and operation... 5 Technical specification...

More information

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death.

Handling or using the product improperly and in disregard of the instructions with this mark might result in serious bodily injury or death. Please Read: Safety Precautions DC AC In order to ensure that this product is used safely, be sure that you read and understand the following precautions fully and use the product only as directed. Be

More information

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance EST-X Figure 1. EST-X unit. Removable top panel D Control module located internally External Commissioning box Table 1. EST-X Dimensions (mm) Weight Code A B C D dia. (kg) EST1-X 705 505 355 125 22 EST2-X

More information