Fire damper ETPR Instructions for Installation, Operation and Maintenance 10/2016

Size: px
Start display at page:

Download "Fire damper ETPR Instructions for Installation, Operation and Maintenance 10/2016"

Transcription

1 Instructions for Installation, Operation and aintenance 10/2016 Installation Fire damper ETPR must be installed according to this installation manual, see pages 2-5. Operation and function testing According to CE marking, a fire damper must always be equipped with a tripping mechanism based on temperature. Fire dampers can be delivered equipped with either a fuse mechanism or an actuator. ETPR motorized fire dampers may additionally be linked to a smoke detection based tripping mechanism. A tripping system based on smoke detection is easy to install using FläktWoods FICO control and monitoring system. The FICO system can also be used for automatic function tests of fire dampers. The function testing for the motorized damper can be performed by cutting off the power supply by using the switch of the thermal trip connected to the motor. The spring will then close the damper. The function testing can also be done by means of the control and monitoring system FICO, either manually or automatically. The recommended automatic function testing interval for the motorized damper is 48 hours. The operation of the fuse mechanism is tested by pushing the red test button the spring will close the blade. Beware of the reset handle as it will rotate rapidly during test operation. To reset the mechanism, turn the handle until the mechanism clicks. aintenance The function testing interval is always determined separately for each building, but testing must be carried out at least twice a year according to product standard EN 15650:2010 (see example of check list beside). WARNING! Never put your hands inside the damper while it is closing. Clean the fire damper by means of a vacuum cleaner. Avoid chemical cleaning agents. Spare parts Actuator: see type specification on the actuator. Fuse part ETFF Fuse part replacement, see page 7. aintenance Check List: Fire damper reference Date of inspection Check actuator wiring for damage (where applicable) Check end-switch wiring for damage (where applicable) Check fire damper cleanliness and clean where necessary Check the condition of blades and seals, rectify and report where necessary Confirm the safety closure operation of the fire damper according to the manufacturer s instructions Confirm operation of damper to OPEN and CLOSE by use of the control system and physical observation of the fire damper, rectify and report where necessary Confirm operation of OPEN and CLOSED end-switches, rectify and report where necessary Confirm that the fire damper fullfills its function as a part of the control system (where applicable) Confirm that the fire damper is left in its normal working position NOTE! A fire damper is usually part of a system. As this is the case, the whole system should be checked as governed by the operation and maintenance requirements for the system.

2 Installation into building elements with fire classification EI 60 (Ø100 - Ø630) S ØD ØD 100 mm Figure 1 Figure mm S 120 mm/ 140 mm (Ø / Ø ) 200 mm Figure 3 Figure 4 Fläkt Woods 9938 EN All rights reserved.

3 Installation of fire damper into rigid building elements (walls and intermediate floors) with fire classification EI 60 and into floors with fire classification EI 90 (Fig. 1 and Fig. 4) 1. Installation opening in the rigid wall or intermediate floor must comply with the dimensions given in the table below. Size ØD (mm) Installation opening Ø (mm) The fire damper blade must be closed during installation. 3. Place the circular duct centrally in the opening. 4. Place the fire damper in the duct so, that the damper flange rests against the building element. Use screws of sufficient length (e.g. 6 x 40 mm), which are suited for rigid construction, to fasten the damper to the building element through the bendable brackets on the flange. The damper must be fastened at 4 brackets at the minimum. The blade shaft can be placed in any position. 5. Completely fill the gap between the duct and the building element using incombustible, rock based, fine-grained gypsum or concrete cast. Protect the damper whilst infilling. 6. Check the functioning of the fire damper and proper movement of the blade. Clean the damper, if necessary. Place plastic covers on the openings and keep them covered, until ducts are connected to the damper. 7. To reset the fuse mechanism: Turn the handle towards the OPEN position until the mechanism clicks and the blade locks into position. 8. anual function testing of the motorized fire damper can be performed with the tool delivered with the actuator. When connected to a power supply, function testing is done by using the switch of the thermal trip. NOTE! If you open the damper blade manually with the tool, be sure to release the damper back to the closed position before switching on power. 9. Connect ducts to the damper according to the instructions provided by the designer and the manufacturer. Use rivets of sufficient length (e.g. DIN Installation of fire damper into flexible building elements (gypsum board walls or similar) with fire classification EI 60 (Fig. 2 and Fig. 3) 1. Installation opening in the flexible wall must comply with the dimensions given in the table below. Size ØD (mm) Installation opening Ø (mm) The fire damper blade must be closed during installation. 3. Place the circular duct in the opening. 4. Fill the gap S between duct and wall opening on both sides by using fire-resistant mass. 5. Place the fire damper in the circular duct so, that the damper flange rests against building element. Use screws or anchors suited for gypsum board walls to fasten the damper to the building element through the bendable brackets on the flange. The damper must be fastened at 4 brackets at the minimum. The blade shaft can be placed in any position x10 or shorter) to lock fire damper to the duct. Note! Always check that damper blade can rotate freely and rivets/screws are out of the way. Access panel should be placed next to the fire damper to enable necessary cleaning and inspection. Suspend the ducts according to instructions from the manufacturer and ensure that the ductwork does not cause any load on the damper installation. 10. If the fire damper is used as an air transfer or air terminal device, it must be equipped with a protective grille. The distance between the grille and the damper blade in the open position must be at least 30 mm. In case of large fire dampers, an extension piece must be installed between the grille and the damper blade. A circular duct of suitable length can be used as an extension piece. 11. When dampers are to be mounted next to one another, the distance between the dampers should be 200 mm (Figure 4). Fläkt Woods 9938 EN All rights reserved.

4 Installation outside building elements with fire classification EI 60 (Ø100 - Ø630) mm ØD Figure 5 S 1 2 Figure mm ØD Figure 6 Fläkt Woods 9938 EN All rights reserved.

5 Installation of fire damper outside building elements with fire classification EI 60 (Fig. 5-7) 1. Install the duct in the usual manner so that it penetrates the building element, and seal the openings ( or S) using an approved method. 2. Connect damper to duct according to the instructions provided by the designer or manufacturer. Use rivets of sufficient length (e.g. DIN x10 or shorter) to lock fire damper to the duct. Note! Always check that damper blade can rotate freely and rivets/screws are out of the way. Access panel should be installed next to the damper to enable necessary cleaning and inspection. 3. Support the duct installation so that there is no extra load on the fire damper. In horizontal installation use hangers (1) and in vertical use shaft hangers (2) or other approved methods to stabilize the damper (Figures 5-7). 4. Insulate the duct between wall and fire damper flange as shown in figures 5-7, so that the fire classification EI 60 is met. 5. Check the functioning of the fire damper and proper moving of the blade. Clean the damper, if necessary. Place plastic covers on the openings and keep them covered, until ducts are connected to the damper. 6. To reset the fuse mechanism: Turn the handle towards the OPEN position until the mechanism clicks and the blade locks into position. 7. anual function testing of the motorized fire damper can be performed with the tool delivered with the actuator. When connected to a power supply, function testing is done by using the switch of the thermal trip. NOTE! If you open the damper blade manually with the tool, be sure to release the damper back to the closed position before switching on power. 8. The fixings used to secure the fire damper and ventilation duct must have a fire resisting capacity that is at least as high as the fire classification of the penetrated building element (the fire resistance rating of a class EI 60 element is R 60, etc.). 9. If the fire damper is used as an air transfer or air terminal device, it must be equipped with a protective grille. The distance between the grille and the damper blade in the open position must be at least 30 mm. In case of large fire dampers, an extension piece must be installed between the grille and the damper blade. Fläkt Woods 9938 EN All rights reserved.

6 Electrical wiring for motorized fire damper Only a trained electrician is allowed to perform the electrical wiring according to separate drawings and wiring diagrams. Wiring diagram for fire damper actuator is shown below. Power supply AC 230 V AC 24 V DC 24 V ~ T Status data of limit switches 1 2 S1 S2 S3 S4 S5 S6 < 5 < 80 Thermal trip Tf1 Tf2 Tf3 LED icroswitch wiring for fuse mechanism operated fire damper The microswitch does not affect fire damper triggering, it just indicates the position of the fire damper blade. The fire damper closes when the thermal trip activates. Status data from the microswitch can be provided from two microswitches (open/close). Proper functioning of the microswitch must be checked and proper indication verified. Electric specification: Operating temperature -25 C C I max = 0,1 A U max = 30 V (AC/DC) 5 Wiring diagram for microswitch Wiring digram shows the situation where damper blade is in closed position and microswitch (0 ) is activated Test button 2 Cover 3 Cable clamp 4 icroswitches (under cover) 5 Handle 2 3 Figure 8. Figure 9. Fläkt Woods 9938 EN All rights reserved.

7 Replacing fuse part ETFF Release the mechanism with the test button (1) close the fire damper. Figure Remove the fuse part mounting screw (6). Figure Holding the test button, pull out the complete fuse part (7). Figure Correctly install the new fuse part and fasten it with the screw (6). 5. Test the function of the product and reset the fire damper. Turn the handle towards the OPEN position until the mechanism clicks and the blade locks into OPEN position. To test the operation of the fuse mechanism, push the red test button (1) the spring should close the blade. Beware of the turning reset handle! 6 1 Figure Figure Figure 12. Fläkt Woods 9938 EN All rights reserved.

8 DECLARATION OF PERFORANCE No. 013CPR Product: Fire Damper ETPR 2. Intended use: Fire damper to be used in conjunction with fire separating elements to maintain fire compartmentation 3. anufacturer: Fläkt Woods Oy, Kalevantie 39, FI Turku, Finland Tel , 4. System of AVCP: System 1 5. Harmonized standard: SFS-EN 15650: Notified Body: SP Technical Research Institute of Sweden, Nr Performed determination the product type on the basis of type testing; initial inspection of the manufacturing plant and of factory production control; continuous surveillance, assessment and evaluation of the factory production control (FPC) under system 1 and issued: Certificate of constancy of performance CPR-SC Declared performance: Essential characteristics Nominal activation conditions/sensitivity: sensing element load bearing capacity sensing element response temperature Response delay (response time): closure time Operational reliability: cycling Fire resistance (300 Pa): Pass Pass Pass (50 cycles) Installation in flexible wall Installation in rigid wall Performance Installation in rigid floor Installation remote of wall/floor integrity E 90 E 120 E 120 E 60 insulation EI 60 EI 60 EI 60, EI 90 EI 60 smoke leakage EI 60 S, E 90 S EI 60 S, E 120 S EI 60 S, EI 90 S, EI 60 S E 120 S mechanical stability (under E) Pass Pass Pass Pass maintenance of the cross section (under E) Pass Pass Pass Pass Durability of response delay: sensing element response to temperature and load bearing capacity Pass Durability of operational reliability: Actuator cycles Pass open and closing cycle tests The performance of the product identified above is in conformity with the set of declared performance. This declaration of performance is issued, in accordance with Regulation (EU) No 305/2011, under the sole responsibility of the manufacturer identified above. Signed for and on behalf of the manufacturer by: Jari Hokkanen, R&D anager Turku Fläkt Woods Oy Kalevantie 39 FI Turku Tel Fax ETPR Installation 9938 GB

CE-marked ESAD - Smoke Control Duct System Installation instructions 08/2013

CE-marked ESAD - Smoke Control Duct System Installation instructions 08/2013 CE-marked ESAD - Smoke Control Duct System Installation instructions 08/2013 ESAD Smoke Control Duct System INSTALLATION INSTRUCTIONS 1.0 Installation of smoke control ducts, general quidelines Smoke Control

More information

VL120. Multi blade smoke evacuation damper 120' C-NT-V24-A 01/2016

VL120. Multi blade smoke evacuation damper 120'   C-NT-V24-A 01/2016 VL120 Multi blade smoke evacuation damper 120' en Rf-Technologies nv Lange Ambachtstraat 40 9860 Oosterzele Belgium Tel +32 9 362 31 71 Fax +32 9 362 33 07 info@rft.be www.rft.be C-NT-V24-A 01/2016 2 Table

More information

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking

Smoke Control Ducts and Dampers For Single Compartment Applications. Fulfilling new requirements for EN product standards for CE Marking Smoke Control Ducts and Dampers For Single Compartment Applications Fulfilling new requirements for EN product standards for CE Marking New Smoke Control Product Range Fläkt Woods Smoke Control Ducts and

More information

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D

CENTRIFLOW 3D. >> Installation and Maintenance. air comfort. CentriFlow 3D CENTRIFLOW 3D Plug fan GMEC >> Installation and Maintenance air comfort CentriFlow 3D 2 Plug Fan CentriFlow 3D GMEC Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU

Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKS-EU Type FKS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES Small rectangular fire damper for the isolation of duct penetrations

More information

Circular Fire Damper Cartridge

Circular Fire Damper Cartridge Clapets coupe-feu et Volets de désenfumage D.A.S. Organisme Certificateur AFNOR Certification - www.marque-nf.com SC Rf-Technologies nv - Lange Ambachtstraat - 9860 Oosterzele - Belgium - Tel +32 9 362

More information

Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU

Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FKRS-EU Type FKRS-EU COMPACT DIMENSIONS, IDEAL FOR RESTRICTED SPACES Small circular fire damper for the isolation of duct penetrations

More information

Fire dampers. For diverse applications

Fire dampers. For diverse applications . X X testregistrierung Fire dampers Type with fusible link for 72 C or 95 C CE compliant according to European regulations With TROXNETCOM as an option ATEX certification For diverse applications Rectangular

More information

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE 2 GLEC-6 - Installation and maintenance CONTENTS 1 Important information... 3 2 Safety notes... 3 3 Technical description...4 4 Transport... 6 5

More information

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans

GLEB. >> Installation and Maintenance. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEB KITCHEN exhaust FAN >> Installation and Maintenance Kitchen Exhaust Fan GLEB Installation and Maintenance Important Information, Safety notes, Technical Description

More information

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU Type FK-EU FOR DIVERSE APPLICATIONS Rectangular fire damper for the isolation of duct penetrations between fire compartments,

More information

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Prodotti > Protezione dal fuoco e dal fumo > Serranda tagliafuoco > Type FK-EU

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Prodotti > Protezione dal fuoco e dal fumo > Serranda tagliafuoco > Type FK-EU Type FK-EU FOR DIVERSE APPLICATIONS Rectangular fire damper for the isolation of duct penetrations between fire compartments, for a variety of installation situations, available in many different sizes

More information

Fire/Smoke damper EKO-SRBG2

Fire/Smoke damper EKO-SRBG2 Fire/Smoke damper EKO-SRBG2 Instructions for installation, operation and maintenance 2014-04 Instructions for installation, operation and maintenance EKO-SRBG2 Contents Handling the product...3 General

More information

BSK-RPR Fire Damper. Additional operating instructions according to

BSK-RPR Fire Damper. Additional operating instructions according to Additional operating instructions according to BSK-RPR Fire Damper Contents GENERAL CONDITIONS... 1 DESCRIPTION... 3... 4 EC Certificate of Conformity 0761 CPD 0245 Declaration of Performance 09-22-DoP-BSK-RPR-2013-07-01

More information

Bevent Rasch BSKC6. - Fire /06/17

Bevent Rasch BSKC6. - Fire /06/17 Bevent Rasch - Fire - BSKC6 19/06/17 Fire resistance class EI60/EI60S Sizes from 100 mm to 630 mm Prefitted safety actuator 24V or 230V Low weight Easy installation CE-marked building product according

More information

ESAR SMOKE CONTROL DAMPER» TECHNICAL CATALOGUE

ESAR SMOKE CONTROL DAMPER» TECHNICAL CATALOGUE FIRE SAFETY AIR TREATMENT FIRE DAMPERS ESAR SMOKE CONTROL DAMPER» TECHNICAL CATALOGUE 2 ESAR Smoke control damper Technical catalogue Circular smoke control damper ESAR is specially designed to use in

More information

Supply air unit VEKA Installation & Maintenance

Supply air unit VEKA Installation & Maintenance November 2008 Safety instructions Operating the air treatment unit and accessory components WARNING Before the air treatment unit is taken into service, any free connections must be provided with protective

More information

Smoke Master SMIA Compact pressurisation and smoke exhaust system

Smoke Master SMIA Compact pressurisation and smoke exhaust system Smoke Master SMIA Compact pressurisation and smoke exhaust system Fläkt Woods FIFLO EN 2009.09 2 All rights reserved. Contents System overview... 4 Design and operation... 5 Technical specification...

More information

BKA-EN Fire Damper. Additional operating instructions according to

BKA-EN Fire Damper. Additional operating instructions according to Additional operating instructions according to BKA-EN Fire Damper Contents GENERAL CONDITIONS... 1 DESCRIPTION... 3... 4 EC Certificate of Conformity 0761 CPD 0244 Declaration of Performance 09-19-DoP-BKA-EN-2013-07-01

More information

Smoke extract fan SMHA HATCH

Smoke extract fan SMHA HATCH 12.11.2012 Contents Product overview... 3 Construction... 4 Specification... 5 Selection... 6 Installation... 7 Electrical connections... 8 Dimensions and weights... 9 Product code and accessories... 10

More information

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59

SOUND-INSULATED FAN. Iso-K OPERATION MANUAL. Iso-K_v.1(2)-EN.indd :20:59 SOUND-INSULATED FAN OPERATION MANUAL _v.1(2)-en.indd 1 10.08.2015 15:20:59 CONTENT Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 3 Fan design 4 Delivery

More information

GLEB Kitchen exhaust fan

GLEB Kitchen exhaust fan GLEB Kitchen exhaust fan Installation and Maintenance??.1.2013 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

SMHA Hatch High temperature fan HT-fan Installation and Maintenance

SMHA Hatch High temperature fan HT-fan Installation and Maintenance High temperature fan HT-fan Installation and Maintenance 22.8.2012 Contents 1. Important information 2. Safety notes 3. Technical description 4. Transport 5. Mounting instructions 6. Commissioning 7. Maintenance

More information

Instructions for the BASIC BCRW Fan, Sizes General

Instructions for the BASIC BCRW Fan, Sizes General Instructions for the BASIC BCRW Fan, Sizes 004 027 1. General The BCRW is a direct-driven fan of axi-centrifugal design. This fan offers excellent power efficiency, low, uniform air flow, low sound generation

More information

Kezdőlap > Termékek > Tűz és füst elleni védelem > Füstmentesítő csappantyúk > Típus EK-EU. Típus EK-EU

Kezdőlap > Termékek > Tűz és füst elleni védelem > Füstmentesítő csappantyúk > Típus EK-EU. Típus EK-EU Kezdőlap > Termékek > Tűz és füst elleni védelem > Füstmentesítő csappantyúk > Típus EK-EU Típus EK-EU FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND AS AN ADDI TIONAL SUPPLY AIR INLET Rectangular smoke control

More information

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL

INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL INLINE СENTRIFUGAL FAN BOX BOX-R OPERATION MANUAL CONTENT 3 Introduction 3 General 3 Safety rules 3 Storage and transportation rules 3 Manufacturer s warranty 4 Fan design 4 Delivery set 5 Technical data

More information

DUCTGARD. Duct Mounting Smoke and Fire Control Dampers

DUCTGARD. Duct Mounting Smoke and Fire Control Dampers DUCTGARD Duct Mounting Smoke and Fire Control Dampers SFB (57.9) X UDC 697.9 Dampers 1 JAN 2015 Features - Certified to Current test standards BS EN 1366-2 - Fully tested and CE marked and compliant -

More information

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT 1. General The TBLZ-1-72-a optical smoke detector with built-in control unit is used for measuring

More information

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance

ECOSMART TWINFANS. (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use. Installation and Maintenance TOP ECOSMART TWINFANS (EST) 1 phase, Direct Drive, Run & Standby Fans for indoor use Installation and Maintenance The EMC Directive 2014/30/EU The Low Voltage directive 2014/35/EU INDOOR USE ONLY Introduction

More information

TEKNISK DOKUMENTATION VENTILATION BG BURCHARTH A/S

TEKNISK DOKUMENTATION VENTILATION BG BURCHARTH A/S Brandspjæld BFD-CS Rektangulært brandspjæld FIRE DAMPER Our Fire Damper (BFD-CS) with EN1366-2:1999 EIS120 certification and CE marklet. E Integrity: Integrity is the ability of a component of a fire damper

More information

ACN SMOKE INSTALLATION AND MAINTENANCE

ACN SMOKE INSTALLATION AND MAINTENANCE NovAx ACN SMOKE INSTALLATION AND MAINTENANCE 918149-0 English 918149-0 GB Installation and maintenance NovAx smoke exhaust fan type ACN smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport

More information

Part # Page Dampers Supported Directly From Structure 5. Dampers Supported From Ductwork Above 4

Part # Page Dampers Supported Directly From Structure 5. Dampers Supported From Ductwork Above 4 Part #453343 INSTALLATION INSTRUCTIONS DAMPERS AND LOUVERS CRD Series s These installation instructions apply to 3 hour rated ceiling radiation dampers mounted in a ceiling with supports from 1) a ceiling

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

Type EK-EU FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND AS AN ADDITIONAL SUPPLY AIR INLET, ALSO FOR NATURAL SMOKE AND HEAT EXHAUST SYSTEMS

Type EK-EU FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND AS AN ADDITIONAL SUPPLY AIR INLET, ALSO FOR NATURAL SMOKE AND HEAT EXHAUST SYSTEMS Home > PRODOTTI > Protezione dal fuoco e dal fumo > Serrande di estrazione fumo > Serie EK-EU Type EK-EU FOR MECHANICAL SMOKE EXTRACT SYSTEMS AND AS AN ADDITIONAL SUPPLY AIR INLET, ALSO FOR NATURAL SMOKE

More information

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to BS EN 16034: 2014 Permission to reproduce extracts from BS EN 16034 : 2014 is granted by BSI. DHF BEST PRACTICE

More information

Original instructions. Panther 6-15 kw

Original instructions. Panther 6-15 kw Original instructions 6-15 kw SE... 8 GB... 10 NL... 12 IT... 14 ES... 16 FI... 18 DE... 20 FR... 22 NO... 24 RU... 26 PL... 28 6/15 Fig 1. Bracket 100 ø7 520 90 ø6,5 ø14 450 510 Fig 2. Ceiling Wall 30

More information

SD119 Range of Conventional Smoke and Smoke/Heat Detectors (refer to attached appendix for details and conditions)

SD119 Range of Conventional Smoke and Smoke/Heat Detectors (refer to attached appendix for details and conditions) In compliance with Regulation 305/2011/EU of the European Parliament and of the Council of 9 March 2011 (the Construction Products Regulation), this certificate applies to the construction product(s).

More information

Fire damper DESIGN GENERAL FIRE CELL DIVISION DISTRIBUTION OF RESPONSIBILITIES FIRE PROTECTION DOCUMENTATION HAGAB FIRE DAMPER DESIGN

Fire damper DESIGN GENERAL FIRE CELL DIVISION DISTRIBUTION OF RESPONSIBILITIES FIRE PROTECTION DOCUMENTATION HAGAB FIRE DAMPER DESIGN Fire damper DESIGN GENERAL Chapter 5 of the BBR (National Board of Housing, Building and Planning's building regulations) specifies the functional requirements which form the basis for fire protection

More information

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION

GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES GENERAL INSTRUCTION GENERAL INSTRUCTION SAFETY DIRECTIVES INSTALLATION INSTRUCTION SAFETY DIRECTIVES Using the air handling unit... Free space for service and repair work... GENERAL INSTRUCTION Checking prior to commissioning...3

More information

CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE

CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE Page 1 of 4 CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE DoP Number: AS3002 AS3012 AS3052 1. Unique identification code of the product-type: AS3002 SIZE 1-6 OVERHEAD DOOR CLOSER SE

More information

F O C U S D O O R C L O S E R S

F O C U S D O O R C L O S E R S (3) - Door Closers.qxp_(3) - Door Closers Art 14/02/2014 16:14 Page 2 F O C U S D O O R C L O S E R S KD.915 With cover Successfully Tested to EN 1154 4 8 5 1 1 3 2 Adjustable 2 to 5 by Spring Closer opening

More information

AZN ATEX INSTALLATION AND MAINTENANCE

AZN ATEX INSTALLATION AND MAINTENANCE ZerAx AZN ATEX INSTALLATION AND MAINTENANCE 924714-0 English 924714-0 GB ZerAx axial flow fans type AZN ATEX Installation and maintenance 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Temperature

More information

EC Box Fan www.flaktwoods.com/oandm Safety, Installation, Operation and Maintenance Instructions CONTENTS Paragraphs Safety 1 Handling/Storage 2 Installation (Mechanical) 3 Fig. 1: Fig. 2: Tilt Mechanism

More information

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans

GLEC exhaust FAN. Air Comfort. Air movement. Duct & Box Fans Air Comfort Air movement Duct & Box Fans GLEC exhaust FAN» Technical CATALOUGE Technical catalouge Exhaust Fan GLEC 2 Contents Exhaust fan - GLEC... 3 Performance Data...4 Fan chart-explanation and definitions...

More information

WH45 DECLARATION OF PERFORMANCE (D.O.P.) PRESTATIEVERKLARING GEPATENTEERDE BRANDKLEP RONDE SERIE WH45

WH45 DECLARATION OF PERFORMANCE (D.O.P.) PRESTATIEVERKLARING GEPATENTEERDE BRANDKLEP RONDE SERIE WH45 WH45 DECLARATION OF PERFORMANCE (D.O.P.) PRESTATIEVERKLARING GEPATENTEERDE BRANDKLEP RONDE SERIE WH45 DoP_WH45Pn12rev3da25062018_NL pag 1/3 PRESTATIEVERKLARING DECLARATION OF PERFORMANCE n 12.3 (n 12 rev.3)

More information

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance

ECOSMART TWINFANS. (EST-X/R/B) 1 phase, Direct Drive, Run & Standby For External, Roof Mounted and Internal use Installation and Maintenance EST-X Figure 1. EST-X unit. Removable top panel D Control module located internally External Commissioning box Table 1. EST-X Dimensions (mm) Weight Code A B C D dia. (kg) EST1-X 705 505 355 125 22 EST2-X

More information

CE Unit is suitable for material transport. The transported gas may be up to 80 C.

CE Unit is suitable for material transport. The transported gas may be up to 80 C. The manual contains: 1 Safety regulations 1.1 Electrical 1.2 Crush risk 1.3 Hazardous dust 1.4 Suction injuries 1.5 Noise 1.6 Pneumatic 1.7 Other equipment 2 Machine Operation 3 Installation Directions

More information

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions

Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions Unity CV2GIP Decentralised Mechanical Extract Ventilation (dmev) Installation Instructions Commissioning Data: To be completed by the Commissioning Engineer. Refer to User / Homeowner Guide also supplied.

More information

Bevent Rasch RABC-VAV. - Fire /03/2018

Bevent Rasch RABC-VAV. - Fire /03/2018 Bevent Rasch - Fire - RABC-VAV 26/03/2018 Fire damper and VAV-damper combined RABC-VAV Fire resistance class E60 Sizes from 100 mm to 630 mm Prefitted safety actuator 24V Installation in ducts Available

More information

TopMaster Air Handling unit. Technical data

TopMaster Air Handling unit. Technical data Technical data Contents Page Description of the unit... 3 Design... 4 Technical data Size 030... 5 Size 0... 6 Accessories... 7 Controls... 9 Control functions... 10 Order codes... 11 Fläkt Woods 8180

More information

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA -

Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - TF N 530 Rev.2 2012-04-13 CONSTRUCTION SECTOR STANDARDIZATION GUIDANCE DOCUMENT Implementation of the Construction Products Regulation (CPR) in harmonized standards - Template for Annex ZA - 1 Drafting

More information

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20

INSTALLATION, OPERATION AND MAINTENANCE. Ariterm Hybrid 20 INSTALLATION, OPERATION AND MAINTENANCE Ariterm Hybrid 20 TABLE OF CONTENTS General...3 Installation... 4-5 Dimensions - with flue gas exhauster...6 Dimensions - without flue gas exhauster...7 Pipe installations...8

More information

Guidance Note No 21/1. CE Marking Windows and doorsets to BS EN 16034

Guidance Note No 21/1. CE Marking Windows and doorsets to BS EN 16034 Guidance Note No 21/1 CE Marking Windows and doorsets to BS EN 16034 Introduction CE Marking of construction products has been a legal requirement since July 2013. It is a European requirement for all

More information

Units for suspended ceilings

Units for suspended ceilings X X testregistrierung Units for suspended ceilings Type, hinged induced air grille, water connections Active chilled beam with two-way air discharge and horizontal heat exchanger, suitable for grid ceilings

More information

Installation and operating instructions

Installation and operating instructions Installation and operating instructions Agrosec Optivol M11 408107 (en) ANTTI-TEOLLISUUS OY Koskentie 89 FI-25340 Kanunki, Salo Tel. +358 2 774 4700 Fax +358 2 774 4777 E-mail: antti@antti-teollisuus.fi

More information

Smart Smart IR. Service instruction SALES DATE MANUFACTURED ON (DATE): APPROVAL MARK SOLD. model (check applicable) is recognized as serviceable

Smart Smart IR. Service instruction SALES DATE MANUFACTURED ON (DATE): APPROVAL MARK SOLD. model (check applicable) is recognized as serviceable Smart Smart IR model (check applicable) is recognized as serviceable Service instruction SALES DATE MANUFACTURED ON (DATE): SOLD APPROVAL MARK SMART-EN-04 BLAUBERG Company is happy to offer your attention

More information

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke

Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 918149-0 GB Installation and Maintenance Novax Smoke Exhaust Fan Type ACN Smoke 1. Application 2. Handling 2.1 Marking 2.2 Weight 2.3 Transport 3. Storage 4. Installation 4.1 Prior to attachment 4.2 Attachment

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

HEAT RECOVERY AIR HANDLING UNIT

HEAT RECOVERY AIR HANDLING UNIT HEAT RECOVERY AIR HANDLING UNIT OPERATION MANUAL KOMFORT_L v2(2)_en.indd 1 07.08.2015 15:0:44 CONTENTS Introduction General Safety regulations Transportation and storage regulations Manufacturer's warranty

More information

TopMaster Air Handling Unit

TopMaster Air Handling Unit TopMaster Air Handling Unit Contents Page Contents......................................2 Unit description................................3 Design........................................4 Technical Details

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

TopMaster Air Handling unit. Installation instructions

TopMaster Air Handling unit. Installation instructions Installation instructions Safety Instructions Operation of Air Handling units and accessories WARNING Installation may only be carried out by qualified personnel. Before taking the air handling unit into

More information

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use

INDOOR USE ONLY. Installation and Maintenance XTRACTOR. (ESX) 1 and 3 phase, Direct Drive, Fans for indoor use TOP INDOOR USE ONLY Introduction Units are rectangular in section and have circular/rectangular rigid spigots at each end. Four matching mounting feet are supplied with the unit. Full size access panels

More information

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance

Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 916503-0 GB Jet Fan Types AUC/ARC/AUR/ARR/AUO/ARO Installation and Maintenance 1. Main components 2. Application 3. Handling 3.1 Marking 3.2 Weight 3.3 Transport 4. Storage 1. Main components: Types ARC,

More information

SECTION AIR DUCT ACCESSORIES

SECTION AIR DUCT ACCESSORIES SECTION 23 33 00 AIR DUCT ACCESSORIES PART 1 - GENERAL 1.1 SUMMARY A. Section includes back-draft dampers, combination fire-and-smoke dampers, duct access doors, fire dampers, smoke dampers, volume control

More information

Topvex SF02-SF12 Air Handling Unit

Topvex SF02-SF12 Air Handling Unit Topvex SF02-SF12 Air Handling Unit Installation instructions Document in original language 130324 A004 GB Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their

More information

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance.

ECOSMART XTRACTOR. (ESX-X/R/B) 1 phase, Direct Drive For External, Roof Mounted and Internal use Installation and Maintenance. ESX-X Figure 1. ESX-X units. Removable top panel A D Control module located internally External Commissioning box Table 1. ESX-X Dimensions (mm) Spigot Weight Code A B C D dia (kg) ESX1-X 705 505 355 125

More information

LX-5 FIRE DAMPER. EI 120 (ve ho i o) S EN A1:2010. Damper tightness class: 4 EN 1751:2002. Casing tightness class: C. Fulfils requirements

LX-5 FIRE DAMPER. EI 120 (ve ho i o) S EN A1:2010. Damper tightness class: 4 EN 1751:2002. Casing tightness class: C. Fulfils requirements LX5 FIRE DAPER EI 120 (ve ho i o) EN +A1:20 Damper tightness class: 4 EN 1751:2002 Casing tightness class: C Fulfils requirements 88 EN 15650:20 GOLD EDAL TP 20 ARCH 20, 20 PATENT GRANT DECIION RELATING

More information

Declaration of performance ( DoP ) :

Declaration of performance ( DoP ) : Gueugnon Declaration of performance ( DoP ) : Gue.02.01 Stainless steel for construction purposes EU-regulation: 305/2011 Gueugnon site / 1.4404 / Cold-rolled 1. Product-type: 1.4404 / 1.4401 2. Construction

More information

Life Safety Dampers Selection and Application Manual

Life Safety Dampers Selection and Application Manual Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers August 2016 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER

More information

Installation instruction

Installation instruction Installation instruction C i40 www.contura.eu 82 CERTIFICATE Declaration of performance according to Regulation (EU) 305/2011 No. Ci40-CPR-130912-SE-2 PRODUCT Product type Type designation Manufacturing

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE Flooring Declaration of Performance Edition 01.07.2013 Identification no. Version no. 01 EN 1504-2: 2004 08 0921 EN 13813: 2002 DECLARATION OF PERFORMANCE Declaration of performance 1. Product Type Unique

More information

Fire protection unit

Fire protection unit Fire protection unit Model BAK-240 with general building supervisory approval Z-41.3-574 Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200

More information

CE Marking for Fire Resistant doors. The future EN Agustín Garzón Cabrerizo Technical Director Fire Resistance Lab.

CE Marking for Fire Resistant doors. The future EN Agustín Garzón Cabrerizo Technical Director Fire Resistance Lab. CE arking for Fire Resistant doors. The future EN 16034 Agustín Garzón Cabrerizo Technical Director Fire Resistance Lab. AFITI-LICOF 1 Overview Pedestrian doorsets, industrial, commercial, garage doors

More information

EDD61 & EDD91 Extractors

EDD61 & EDD91 Extractors EDD61 & EDD91 Extractors Installation, Use and Maintenance Customer Care Department The Group Ltd. Harby Road Langar Nottinghamshire NG13 9HY T : 01949 862 012 F : 01949 862 003 E : customer.care@cda.eu

More information

Ceiling diffusers. Type DLQL

Ceiling diffusers. Type DLQL X X testregistrierung Type Horizontal one-way air discharge Horizontal two-way air discharge Horizontal four-way air discharge Horizontal duct connection For horizontal one-way to four-way air discharge,

More information

Technical information. Remeha P200. Pressurized boiler. Heat output: kw

Technical information. Remeha P200. Pressurized boiler. Heat output: kw Technical information Remeha P200 R e m e h a P 2 0 0 Pressurized boiler Heat output: 59-256 kw Remeha P 200 CONTENTS Preface 3 1. Description of the unit 4 1.1 General 4 1.2 Burners 4 2. Construction

More information

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.

Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves. Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves Report No: 172158 Prepared for: Lindab Ventilation AB SE 26982 Båstad Järnvägsgatan

More information

Intumescent Fire Dampers

Intumescent Fire Dampers Ph 1300 858 010 Intumescent Fire Dampers Fire resistant walls and floors in a building play an important part in containing the spread of fire and smoke. However, a building also needs to be well ventilated

More information

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS

MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS MARINE APPLICATIONS MARINE» PRODUCTS AND SOLUTIONS FOR MARINE APPLICATIONS MEETING THE HIGHEST DEMANDS - EFFICIENT HVAC SOLUTIONS FOR ARCTICAL TO TROPICAL CONDITIONS AT FLÄKTGROUP WE WANT TO EXCEED the

More information

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL

INLINE CENTRIFUGAL FAN. Centro-M OPERATION MANUAL INLINE CENTRIFUGAL FAN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements 3 Manufacturer's warranty 4 Fan design 4 Delivery

More information

Cooper Lighting & Safety Limited Wheatley Hall Road, Doncaster, DN2 4NB, United Kingdom

Cooper Lighting & Safety Limited Wheatley Hall Road, Doncaster, DN2 4NB, United Kingdom In compliance with Regulation (EU) No 305/2011 of the European Parliament and of the Council of 9 March 2011 (the Construction Products Regulation or CPR), this certificate applies to the construction

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE Flooring Declaration of Performance Edition 01.07.2013 Identification no. Version no. 01 EN 1504-2: 2004 08 0921 EN 13813: 2002 DECLARATION OF PERFORMANCE Declaration of performance 1. Product Type Unique

More information

HULME MARTIN HEAT SEALERS

HULME MARTIN HEAT SEALERS HM Operating Instructions HM 7600 CDL HULME MARTIN HEAT SEALERS HULME MARTIN HEAT SEALERS www.hulmemartin.co.uk SAFETY INSTRUCTIONS HEAT SEALING EQUIPMENT A. Protection against hazards arising from the

More information

Installation instruction

Installation instruction Installation instruction Ci50 www.contura.eu 82 CERTIFICATE Declaration of performance according to Regulation (EU) 305/2011 No. Ci50-CPR-150821-SE-2 PRODUCT Product type Type designation Manufacturing

More information

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit

DC Heat Recovery Unit MVHR Wholehouse heat recovery unit DC Heat Recovery Unit MVHR Wholehouse heat recovery unit Stock Ref. N DC Heat Recovery Unit MVHR 443423 Installation, Maintenance & Users Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS.

More information

FSD-TD Series. Fire and Smoke Dampers B RITAI N. LPCB certificated fire dampers (LPS 1162)

FSD-TD Series. Fire and Smoke Dampers B RITAI N. LPCB certificated fire dampers (LPS 1162) Fire and Smoke Dampers LPCB certificated fire dampers (LPS 1162) ES classified fire dampers with reduced smoke leakage characteristics (BS EN 13501-3) Tested installation methods in differing supporting

More information

3480/RCH SERIES INSTALLATION INSTRUCTIONS

3480/RCH SERIES INSTALLATION INSTRUCTIONS 3480/RCH SERIES INSTALLATION INSTRUCTIONS NOTE: If plaster frame is required for installation order it as an option. ATTENTION: Read carefully before attempting to install or operate the heater. GENERAL

More information

Able to respond to smoke alarms for the protection of escape routes and areas with sleeping risk (ADB)

Able to respond to smoke alarms for the protection of escape routes and areas with sleeping risk (ADB) Fire and Smoke Dampers LPCB certificated fire dampers (LPS 1162) ES classified fire dampers with reduced smoke leakage characteristics (BS EN 13501-3) Tested installation methods in differing supporting

More information

Smoke Master SMPA Installation, operation and maintenance

Smoke Master SMPA Installation, operation and maintenance 19.11.2009 Contents Contents...2 Safety aspects...3 System overview...4 Installation...5 Installation of the fan unit...5 Electric installations...7 Stairwell smoke detectors...7 Relay unit for smoke detectors...7

More information

iq Star LYRA II chilled beam cassette

iq Star LYRA II chilled beam cassette iq Star LYRA II chilled beam cassette Key features Ventilation Heating and cooling Compact chilled beam Adjustable induction Flow Pattern Control Integrated control In option: Demand Controlled Ventilation,

More information

breeze easytm model # F100-1W

breeze easytm model # F100-1W DewStop breeze easytm model # F100-1W Installation Guide Read and Save These Instructions LISTED Questions, Problems, Missing Parts? Please Call 1-360-876-2974 or E-Mail info@dewstop.com please retain

More information

Original instructions AR

Original instructions AR Original instructions SE... 8 GB... 22 NO... 27 FR... DE... 6 ES... 4 NL... 46 IT... 5 RU... 56 Dimensions and connections AR20/AR25 M8 002/52 940/450 494 449 92 20 98 042/552 42 20 AR20/25A/E 40 275 DN5

More information

CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE

CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE Page 1 of 4 CONSTRUCTION PRODUCTS REGULATION 2011 DECLARATION OF PERFORMANCE DoP Number: HUK0022 1. Unique identification code of the product-type: AR880 Series Panic Bolt, AR882 Series Reversible Panic

More information

Cooling Strip Model SPB

Cooling Strip Model SPB Cooling Strip Model SPB Ferdinand Schad KG Steigstraße 25-27 D-78600 Kolbingen Telephone +49 (0) 74 63-980 - 0 Fax +49 (0) 74 63-980 - 200 info@schako.de www.schako.de Contents Description...3 Advantages...

More information

FIREPRO SoftSeal System

FIREPRO SoftSeal System PENETRATION AND AND LINEAR LINEAR JOINTS JOINTS APRIL JULY 2015 FIREPRO SoftSeal System www.rockwool.co.uk PENETRATION AND LINEAR JOINTS FIREPRO Range The ROCKWOOL FIREPRO SoftSeal system is part of this

More information

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL

AXIS-QA G TUBO-M/MZ AXIAL FANS. Axis / Tubo OPERATION MANUAL TUBO-M/MZ AXIS-QA AXIS-Q TUBO-F AXIS-QR AXIS-F AXIS-QRA AXIS-QA G AXIAL FANS EN OPERATION MANUAL www.blaubergventilatoren.de CONTENT 3 Introduction 3 General 3 Safety rules 3 Transport and storage requirements

More information

EUROPEAN TECHNICAL ASSESSMENT

EUROPEAN TECHNICAL ASSESSMENT EUROPEAN TECHNICAL ASSESSMENT ETA 16/0050 Version draft 01 Date of issue: 2016-03-18 UBAtc Assessment Operator: Belgian Construction Certification Association Rue d Arlon 53-1040 Brussels www.bcca.be -

More information

Smoke Master SMPA Compact pressurisation system

Smoke Master SMPA Compact pressurisation system Smoke Master SMPA Compact pressurisation system Fläkt Woods FILO E 2009.07 2 All rights reserved. Contents System overview...4 Design and operation...5 Technical specification...6 Electric and control

More information