Menu operation via AKA 21 ADAP-KOOL. Controller for controlling evaporators AKC 114D, 115D and 116D. Software version 1.5x
|
|
- Alisha Washington
- 6 years ago
- Views:
Transcription
1 Menu operation via AKA 21 ADAP-KOOL Controller for controlling evaporators AKC 114D, 115D and 116D Software version 1.5x RC.1H.Z1.02 RC.1H.Z
2 System survey A refrigerating plant fitted with ADAP-KOOL refrigeration controls will mostly consist of several controllers where each controller will regulate its own refrigeration appliance/cold room. The system has been designed in such a way that contact can be made to each and every controller via a data communication system. One specific controller is selected, and it will now be possible to make settings and readouts for this unit. Operation The individual controllers can be operated in two ways: 1. With control panel type AKA 21. Use this document when operation takes place in this way. 2. With PC and system software type AKM. Use another document with literature number RC.1H.0-. Validity This menu operation was worked out in November 1998 and applies to AKC 114D, AKC 115D and AKC 116D with the following code numbers: 084B6029 and 084B6032 (AKC 114D) 084B6044 and 084B6048 (AKC 115D) 084B6045 and 084B6049 (AKC 116D) that are fitted with software version 1.5x. 2 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
3 Select a controller All controllers that are connected to the same network can be operated with the control panel. There may be as many as 125 controllers, and they are shown in groups of 16 on the display. 1 < 1 > 16 AEAAAAAAAAEEgg A A system is shown here which consists of more than 16 controllers. The meaning of the letters is, as follows: A: AKC controller E: Controller with active ERROR (on addresses 2, 11 and 12 in this example) g: Gateway (to addresses 13 and 14 in this example) G: Gateway with connected printer : A blank field indicates that there is no unit with this address. 1 < 4 > 16 AEAAAAAAAAEEgg A Select the unit that is to be operated by using the +/On or -/Off key, and push Enter. In this example you select the controller with address < 17 > 32 AAA If the system comprises more than 16 units or units with an address code higher than 16, you may change to the next group by pushing. Settings of a controller When a controller has been selected, you can make settings in it. This setting is performed, as follows: 5-50 to OFF / ON Shown in the upper right corner of the display is the setting with which the controller is operating. Below that value a new setting may be made. Use the three keys +/ON, -/OFF and Digit for setting the new value. This new value will not govern the regulation until you push the key Enter. ON ON Access to a controller The functions in the controller can be protected by means of an access code. Depending on the settings to be made, you may gain access in one of the following ways: User input: Gives access to: 1. Push F1 Display of alarms 2. Push F2 Reading of selected temperatures, change of temperature in the refrigeration appliance, start of defrost 3. Code 1 and then F1 Acknowledgement of alarms Code 1 and then F3 Setting of selected parameters 4. Code 2 Operation of all settings of the entire menu system (with system software type AKM there is access to additional functions). Pages 6 and 7 contain a description of how you gain access to the system via a code. AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/1998 3
4 Supporting text A supporting text is attached to the individual functions. When such a function is shown in the control panel s display, the supporting text can be obtained by pushing the key Help. The supporting text is intended as a help to users who no longer use these operating instructions. In the menus shown below functions with supporting texts are identified with the word Help next to the function. How to localise an error When an error appears in a system, it can be seen on the control panel s display which will show an E. If the control panel shows a text from a selected controller, the LED at the word Alarm will furthermore flash. 1 < 2 > 16 AEAAAAAAAAAAgg A AKC 116D Adr: 2 E Mon-11:27 High air temp When an error has occurred, first select the controller on which the error is registered. When the controller has been found, push F1, and the error message will appear. At the end of the document there is a list of all the error messages and a description of how to acknowledge an alarm. Functions of a controller When one controller has been selected from the total system, the following display will appear (the display is the first one shown when you have selected an address from the total system): e.g. AKC 116D Adr: 2 E Mon-11:27 From this position you can freely choose between several forms of operating levels: 1. Display of alarms - push F1 2. Display and setting of a few selected functions - push F2 3. Display and setting of several selected functions - push F3 The function may be protected with a code (code 1) 4. Display and setting of all allowed functions in the controller. The function may be protected with a code (code 2). Operation of the individual levels is shown below: 1. F1 When you push F1 the alarm messages from the controller in question appear. Only active alarms are shown. With a push on you can see whether there are more alarm messages, and if so, their texts. When an alarm has been localised and corrected, the alarm is acknowledged (removed from the system, so that it no longer appears). In large systems where a gateway is also connected this acknowledgement will take place automatically. In other systems it has to be done manually, cf. end of the document. Prior to the acknowledgement of the alarm, the keying of a code is required, see page 6. Leave the F1 function by pushing. 4 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
5 2. F2 When you push F2 a number of functions will appear where it is possible to read or set values. You can move to and from the individual functions by pushing or. On page 3 you can see how a setting is changed. Man. Def. Manual defrost is activated when ON OFF/ON (changes automatically to OFF) 7:03:02 CutOut C Setting of thermostat cut-out value MUST BE SET. Even if the thermostat function has not been 6:03:03 selected. (The value is used by the injection function). AlarmAir A Actual air temperature for the alarm function in section A 6:02:01 Ther.Air A Actual air temperature (section A) 6:02:02 Air Temp B Only AKC 115D/ Actual air temperature (section B) 6:02:03 AKC 116D Air Temp C Only AKC 116D Actual air temperature (section C) 6:02:04 S3 C (A) Air temperature at evaporator inlet (section A) 6:02:05 S4 C (A) Air temperature at evaporator outlet (section A) 6:02:06 RunTime A Actual thermostat cut-in time of section A 6:02:09 or duration of the latest finished cut-in RunTime B Only AKC 115D/ Actual thermostat cut-in time of section B 6:02:10 AKC 116D or duration of the latest finished cut-in RunTime C Actual thermostat cut-in time of section C 6:02:11 Only AKC 116D or duration of the latest finished cut-in Reg Cond. A Regulating condition 3:02:01 0: No cooling 6: Forced closing 1: Start 7: Regulation problems Reg Cond. B Only AKC 115D/ 2: Adaptive regulation 8: Emergency cooling (sensor failure) 4:02:01 AKC 116D 3: Start 9: Modulating thermostat regulation 4: Defrosting 10: Forced cutout(melt function) Reg Cond. C 5: Start after defrost 5:02:01 Only AKC 116D DefTime m Actual defrost cut-in time or duration of the latest finished 7:02:05 defrosting period. MDefTime m Average value of the latest 4 defrosting periods. 7:02:06 Leave the F2 function by pushing. AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/1998 5
6 3. F3 When you push F3, a number of functions will appear which are used when the system is serviced. If access code is used (code 1), key it as follows: - Push the key - Enter the code by using the three keys +, - and Digit (the code is mentioned later as code 1, and the factory setting is 40. If code 2 has been set at 0, access code 1 cannot be used). - Push Enter - Push F3 Move to and from the individual functions by pushing or. On page 3 you can see how a setting is changed. Main Switch Main switch: 1: Regulation -1 / 0 / 1 0: Controller stop 2:02:01-1: Service Diff. K Setting of thermostat differential :03:04 Dt Night K Night set back value :04:02 High Lim C High air temperature alarm limit (absolute value) When there is night setback operation, the alarm limit is raised 6:05:02 by the night setback value. Low Lim C Low air temperature alarm limit (absolute value) :05:05 S1 C (A) Refrigerant temperature at evaporator inlet. 3:02:05 S2-S1 K A Evaporator superheat measured with S1 and S2 sensors 3:02:02 AKV OD % A Actual valve opening degree 3:02:04 S1 C (B) Only AKC 115D/ Refrigerant temperature at evaporator inlet. 4:02:05 AKC 116D S2-S1 K B Evaporator superheat measured with S1 and S2 sensors 4:02:02 Only AKC 115D/ AKC 116D AKV OD % B Actual valve opening degree 4:02:04 Only AKC 115D/ AKC 116D S1 C (C) Refrigerant temperature at evaporator inlet. 5:02:05 Only AKC 116D S2-S1 K C Evaporator superheat measured with S1 and S2 sensors 5:02:02 Only AKC 116D AKV OD % C Actual valve opening degree 5:02:04 Only AKC 116D Def.Stop C Temperature value of defrost stop 0-60 (Temperature at the chosen sensor. See 7:04:04) 7:04:03 MaxDefTime Max. permissible defrost time in minutes (Security time on Temperature stop) 7:04:02 Leave the function by pushing. 6 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
7 4. Access to all functions The access to the functions may be protected with a code (code 2). If access code is used, key it as follows: - Push the key - Enter the code by using the three keys +, - and Digit - Push Enter - Push Move to and from the individual functions by pushing the four arrow keys. On page 3 you can see how a setting is changed. When you wish to leave the Access to all functions function, push Clear and then. List of functions on level 1: 1. Controller s access display and access to system information 2. Interruption of regulation and selection of language 3. Injection function for section A 4. Injection function for section B (AKC 115D/116D only) 5. Injection function for section C (AKC 116D only) 6. Thermostat function, night-setback function, alarm function, fan control and rail heat control 7. Defrost function 8. Forced control functions for service and initial setting Below and on the following pages the individual functions are shown together with a brief description: Level 1 Level 2 Level 3 Level 4 Description AKC 11xD Adr: xxx Mon hh:mm Controller access display If the code function is used, continue by pushing the "key" key. Enter Code Entry of access code 1 or access code 2 (cf. also 1:07 and 1:08) Continue by pushing "arrow left" 1:01 AKC 11xD Adr: xxx Access to system information Mon hh:mm If an E appears in the display, an error has been registered. 1 Code No. Reading of the controller s code no. and programme version. Prog. Ver. 1:02 Clock: Setting of controller clock (AKC clock) Mon hh:mm 1:03 Clock: Day. Setting of day (1 = Monday, 7 = Sunday) Mon(1) Sun(7) 1:03:01 Clock: Hour Setting of hours 1:03:02 Clock: Min. Setting of minutes 1:03:03 System Address Reading of the controller s system address Addr. yyy xxx yyy=network no. and xxx=address. 1:04 The system address can only be set via PC Alarm report to Reading of the alarm address (end receiver) the alarms are to be Addr. yyy xxx sent to. 1:05 The alarm address can only be set via PC. AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/1998 7
8 Main Function 2 Gateway Address Reading of the address on the nearst gateway which has to effect xxx alarms (see 1:05) 1:06 The address can only be set via PC Chg. Code1 Change of code 1. The code gives access to acknowledgement of active alarm by means of the F1 key. 1:07 Also access to the selected settings/readouts via the F3 key. (Factory setting = 40) (See also code 2) Chg. Code2 Change of code 2. The code gives access to the whole menu system. 1:08 (Factory setting = 0. Setting = 0 offers free access where neither code 1 not code 2 is required) Main function Alarm Message(s) In case of alarm, an E is shown on the display 2:01 (Error log becomes visible) See page 23, check of error log 2:01:01 Main Function Access to the main switch Settings 2:02 Main Switch Main switch: 1: Regulation -1 / 0 / 1 Help 0: Controller stop 2:02:01-1: Service Language Selection of language. Three languages have been entered 0-4 Help in the controller 2:02:02 Either: Or: 0: English 0: English 1: German 3: Danish 2: French 4: Spanish NB! This function must be set prior to any uploading to system software type AKM. When the language code has been changed, push "ENTER" and then "Clear". Injection (A) Section A Control 3 In case of alarm, an E is shown on the display Alarm message(s) (Error log becomes visible) 3:01 See page 23, check of error log Injection (A) Measurements 3:02 3:01:01 Read-out of measuring values related to section A Reg Cond. A Regulating condition 3:02:01 Help 0: No cooling 6: Forced closing 1: Start 7: Regulation problems 2: Adaptive regulation 8: Emergency cooling (sensor failure) 3: Start 9: Modulating thermostat regulation 4: Defrosting 10: Forced cutout(melt function) 5: Start after defrost S2-S1 K A Evaporator superheat measured with S1 and S2 sensors 3:02:02 SH Ref K A Actual superheat reference of the regulation 3:02:03 AKV OD % A Actual valve opening degree 3:02:04 S1 C (A) Refrigerant temperature at evaporator inlet. 3:02:05 S2 C (A) Refrigerant temperature at evaporator outlet. 3:02:06 8 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
9 Injection (A) Setting 3:03 Inj. Ctrl. A OFF / ON 3:03:01 Setting of expansion valve function section A Choose expansion valve function ON/OFF Injection (B) Only AKC 115D/116D Section B (only AKC 115D and AKC 116D) Control 4 Alarm message In case of alarm, an E is shown on the display 4:01 (Error log becomes visible) Injection (B) Measurements 4:02 Injection (B) Setting 4:03 4:01:01 See page 23, check of error log Read-out of measuring values related to section B Reg Cond. B Regulating condition 4:02:01 Help 0: No cooling 6: Forced closing 1: Start 7: Regulation problems 2: Adaptive regulation 8: Emergency cooling (sensor failure) 3: Start 9: Modulating thermostat regulation 4: Defrosting 10: Forced cutout(melt function) 5: Start after defrost S2-S1 K B Evaporator superheat measured with S1 and S2 sensors 4:02:02 SH Ref K B Actual superheat reference of the regulation 4:02:03 AKV OD % B Actual valve opening degree 4:02:04 S1 C (B) Refrigerant temperature at evaporator inlet. 4:02:05 S2 C (B) Refrigerant temperature at evaporator outlet. 4:02:06 Inj. Ctrl. B OFF / ON 4:03:01 Setting of expansion valve funciton section B Choose expansion valve function ON/OFF Injection (C) Only AKC 116D Section C (only AKC 116D) Control 5 Alarm message(s) In case of alarm, an E is shown on the display 5:01 (Error log becomes visible) Injection (C) Measurements 5:02 5:01:01 See page 23, check of error log Read-out of measuring values related to section C Reg Cond. C Regulating condition 5:02:01 Help 0: No cooling 6: Forced closing 1: Start 7: Regulation problems 2: Adaptive regulation 8: Emergency cooling (sensor failure) 3: Start 9: Modulating thermostat regulation 4: Defrosting 10: Forced cutout(melt function) 5: Start after defrost S2-S1 K C Evaporator superheat measured with S1 and S2 sensors 5:02:02 SH Ref K C Actual superheat reference of the regulation 5:02:03 AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/1998 9
10 Common Controller 6 Injection (C) Setting 5:03 AKV OD % C 5:02:04 S1 C (C) 5:02:05 S2 C (C) 5:02:06 Inj. Ctrl C OFF / ON 5:03:01 Actual valve opening degree Refrigerant temperature at evaporator inlet. Refrigerant temperature at evaporator outlet. Setting of expansion valve funciton section C Choose expansion valve function ON/OFF Functions common to sections A, B and C Alarm message(s) In case of alarm, an E is shown on the display 6:01 (Error log becomes visible) Thermostat Measurements 6:02 Thermostat Ctrl. Settings 6:03 6:01:01 See page 23, check of error log Read.out of measuring values related to thermostat function. AlarmAir A Actual air temperature for the alarm function in section A 6:02:01 Ther.Air A Actual air temperature (section A) 6:02:02 Air Temp B Only AKC 115D/ Actual air temperature (section B) 6:02:03 AKC 116D Air Temp C Only AKC 116D Actual air temperature (section C) 6:02:04 S3 C (A) Air temperature at evaporator inlet (section A) 6:02:05 S4 C (A) Air temperature at evaporator outlet (section A) 6:02:06 CutOut C Actual thermostat(s) cut-out value 6:02:07 CutIn C Actual thermostat(s) cut-in value 6:02:08 RunTime A Actual thermostat cut-in time of section A 6:02:09 or duration of the latest finished cut-in RunTime B Only AKC 115D/ Actual thermostat cut-in time of section B 6:02:10 AKC 116D or duration of the latest finished cut-in RunTime C Actual thermostat cut-in time of section C 6:02:11 Only AKC 116D or duration of the latest finished cut-in Settings for thermostat function Ther. Mode Definition of thermostat function 0-3 Help 0: No thermostat function 6:03:01 1: The thermostat function is atached to section A (cutout and cutin of sections B and C will come after section A) 2: There is one thermostat function in each function 3: Modulating thermostat regulation 10 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
11 Day/Night Ctrl. Settings 6:04 Ther. Sx Definition of thermostat sensor(s) 1-3 Help 1: S3A, S3/4B and S3/4C sensor(s) is used 6:03:02 2: S4A, S3/4B and S3/4C sensor(s) is used 3: Weighted value of S3A and S4A is used (setting = 3 may only be used, if "Ther. Mode" = 1) CutOut C Setting of thermostat cut-out value MUST BE SET. Even if the thermostat function has not been 6:03:03 selected. (The value is used by the injection function). Diff. K Setting of thermostat differential :03:04 Settings of day/night function Day/Night Choose day-/night operation function 0 3 Help 0: No night setback 6:04:01 1: Change between day and night operation according to signal on S6 input 2: Change between day and night operation according to internal time clock 3: Change between day and night operation according to the signal from the master controller (Signal via DANBUSS) Dt Night K Night set back value :04:02 Mo day h Time table for day and night operation on Mondays 0 24 End of night setback 6:04:03 At setting = 0 there is no night setback this day Mo night h Time table continued: 0 24 Start (of night setback) 6:04:04 At setting = 0 there is no displacement this day If day and night settings are identical, or if night is set before the function will be changed. See functional description Tu day h As above, Tuesdays :04:05 Tu night h As above, Tuesdays :04:06 We day h As above, Wednesdays :04:07 We night h As above, Wednesdays :04:08 Th day h As above, Thursdays :04:09 Th night h As above, Thursdays :04:10 Fr day h As above, Fridays :04:11 Fr night h As above, Fridays :04:12 AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
12 Air Temp. Alarm Settings 6:05 Sa day h :04:13 Sa night h :04:14 Su day h :04:15 Su night h :04:16 As above, Saturdays As above, Saturdays As above, Sundays As above, Sundays Settings for alarm function Alarm Mode Definition of alarm thermostat 0-3 Help 0: No alarm thermostat 6:05:01 1: S3A, S3/4B and S3/4C used as alarm sensors 2: S4A, S3/4B and S3/4C used as alarm sensors 3: (Only AKC 114D) Thermostat temperature in section A is used (see 6:02:02 TherAir A). High Lim C High air temperature alarm limit (absolute value) When there is night setback operation, the alarm limit is raised 6:05:02 by the night setback value. High1Del m Time delay of high air temperature alarm during pull-down Help This value will apply until the actual air temperature has dropped 6:05:03 below the "upper alarm limit". Thereafter shift to the time delay "High2Del m". High2Del m Time delay of high air temperature alarm during normal regulation Help 6:05:04 Low Lim C Low air temperature alarm limit (absolute value) :05:05 Low Del m Time delay for low air temperature alarm :05:06 Display Setting Settings for external temperature display type AKA 14 6:06 Fan Pulsing (CutOut Night) 6:07 Disp. ctrl. Choose read-out for display 0-3 Help 0: No display function 6:06:01 1: S3 read out 2: S4 read out 3: Ther.Air read out Offset K A Offset adjustment of display signal, display A :06:02 Offset K B Offset adjustment of display signal, display B :06:03 Offset K C Offset adjustment of display signal, display C :06:04 Setting of fan pulsing during night operation Fan On % Setting of the fans ON period in percent of the "FanCycl m" time (the function is only active in the cutout period during night 6:07:01 operation). FanCycl m Period time for total ON / OFF time :07:02 12 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
13 Railheat Pulsing (Day/Night) 6.08 Tc Signal Ctrl. Settings 6.09 Settings for railheat function RailOnDay % During day operation: Setting of rail heat ON period in percent of the "RailCycl m" time. 6:08:01 RailOnNgt % During night operation: Setting of rail heat ON period in percent of the "RailCycl m" time 6:08:02 RailCycl m Period time for total ON / OFF time :08:03 Setting of Tc Signal control Tc Ctrl. Tc regulation ON/OFF OFF ON 6:09:01 Tc On % Opening degree of the expansion valve, when Tc-outlet shall be cut-out. 6:09:02 (higher condensing pressure is required) TcOnDel.m Time delay before Tc outlet is cut-out :09:03 Tc Off % Opening degree of the expansion valve, when Tc-oulet is cut-in. 6:09:04 (lower condensing pressure allowed) TcOffDel.m Time delay before Tc outlet is cut-in :09:05 Output Ctrl. at Definition of controller outputs at forced control signal Forced Closing (when the "ON" inlet is cut-out (terminal 32-33)) 6:10 Output Ctrl. Output functions when there is forced control 1-3 Help 1: Fan outlet is ON 6:10:01 2: Fan outlet is OFF 3: All outlets are OFF and alarm thermostat function is stopped. ON-InpMode Definition of AKC-ON input (terminals 32-33) 0-1 0: Connection not used, as the regulation is controlled by the 6:10:02 gateway s override function 1: Connection must be made (when te voltage is interrupted the valve closes) Safety Function Settings for fan stop function Fan Stop by S5 6:11 FanStopS5 Fan stop function defines ON or OFF OFF/ON Help 6:11:01 FanStop C Temperature limit for fan stop (the fans are stopped when the S5A temperature is higher than this value. The fans will start again 6:11:02 when S5A is lower than "FanStop C" - 2K) Extended Ther. Extended settings for thermostat function Ctrl. Settings 6:12 S4 Day % S4 weighting by day S3 is automatically weighted. Must only be set if "Ther.Sx" = 3 6:12:01 S4 Night % S4 is weighting at night S3 is automatically weighted 6:12:02 S4MinLim C Only AKC 114D Setting of low S4 temperature alarm limit The function is only active, if weighting between S3 and S4 6:12:03 Help is used for the thermostat function AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
14 Defrost Control Extended Inject. Ctrl. Settings 6:13 Extended settings for injection function Glide K Temperature displacement for refrigerant is only set in systems with zeotropic refrigerants. 6:13:01 SH Max K Max. superheat reference value :13:02 SH Min K Min. superheat reference value :13:03 MOP Ctrl. Choose MOP function ON/OFF OFF/ON 6:13:04 MOP C MOP point value :13:05 TEV Define type of expansion valve OFF/ON OFF: AKV valves are used 6:13:06 ON: Connect a solenoid valve (TEV) to the AKV output. (Inj. Ctrl 3:03:01, 4:03:01 and 5:03:01 must be "Off") Defrost function 7:00 Alarm message(s) In case of alarm, an E is shown on the display 7:01 (Error log becomes visible) Defrost Measurements 7:02 Defrost Ctrl. Settings 7:03 7:01:01 See page 23, check of error log Read-out of measuring values related to defrost function Def. Cond. Defrost condition 7:02:01 Help 0: Defrost not started 4: Reserved delay 2 1: Pump down 5: Draining of evaporator 2: Extra delay 1 6: Delayed injection 3: Defrost 7: Delayed fan start S5 C (A) Defrost sensor temperature in section A 7:02:02 S5 C (B) Only AKC 115D/ Defrost sensor temperature in section B 7:02:03 AKC 116D S5 C (C) Only AKC 116D Defrost sensor temperature in section C 7:02:04 DefTime m Actual defrost cut-in time or duration of the latest finished 7:02:05 defrosting period. MDefTime m Average value of the latest 4 defrosting periods. 7:02:06 Help AccDefSkip Total number of skipped defrosts since start 7:02:07 AccNo.Def Total number of sustained defrosts since start 7:02:08 Def. Ctrl. OFF/ON 7:03:01 Man. Def. OFF/ON 7:03:02 Definition of defrosting method Choose defrost function ON/OFF Manual defrost is activated when ON (changes automatically to OFF) 14 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
15 DOD Ctrl. Choose defrost requirement ON/OFF OFF/ON 7:03:03 Fan run Choose fan operation during defrost ON/OFF OFF/ON 7:03:04 Defrost Stop. Definitions of defrost stop Temp(1)/Time(2) 7:04 Temp/Time 1: Temperature stop (time as security) 1-2 2: Stop on time 7:04:01 MaxDefTime Max. permissible defrost time in minutes (Security time on Temperature stop) 7:04:02 Def.Stop C Temperature value of defrost stop 0-60 (Temperature at the chosen sensor. See 7:04:04) 7:04:03 DefStop Sx Definition of sensor for defrost 1-5 Help 1: S1 4:S4 7:04:04 2: S2 5: S5 (Normal setting) 3: S3 Defrost Sequence Defrost sequence Settings 7:05 Inj.Del m Liquid injection delay time :05:01 FanOnDel m Max. permissible fan start delay after defrosting The delay time runs from the expiry of the delay time, if applicable, 7:05:02 for the liquid injection. Fan On C Temperature at which the fan starts after defrost Fans starts when all S5 temperatures are below the value. 7:05:03 Extended Program Help function for setting of defrost times Schedules The defrost periods are distributed evenly during a defined 7:06 period of time within a 24-hour period. No. Per Day Number of defrosts/24 hours 2-8 7:06:01 FirstDef Setting of time the 1st defrost begins 7:06:02 FirstDef Hour Setting of hours FirstDef Min. Setting of minutes LastDef Setting of time the last defrost begins 7:06:03 LastDef Hour Setting of hours LastDef Min. Setting of minutes Auto Set Transfer the values to the three subsequent defrost programmes. OFF/ON Help In pos. ON they are entered in "7:07", "7:08" and "7:09". 7:06:04 If the three defrost programmes are not to be identical, corrections subsequent must be made in the individual programmes. AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
16 Mon Sched. Choose defrost programme for Mondays 1-3 See also 7:07, 7:08 and 7:09 7:06:05 Tue Sched. Choose defrost programme for Tuesdays 1-3 See also 7:07, 7:08 and 7:09 7:06:06 Wed Sched. Choose defrost programme for Wednesdays 1-3 See also 7:07, 7:08 and 7:09 7:06:07 Thu Sched. Choose defrost programme for Thursdays 1-3 See also 7:07, 7:08 and 7:09 7:06:08 Fri Sched. Choose defrost programme for Fridays 1-3 See also 7:07, 7:08 and 7:09 7:06:09 Sat Sched. Choose defrost programme for Saturdays 1-3 See also 7:07, 7:08 and 7:09 7:06:10 Sun Sched. Choose defrost programme for Sundays 1-3 See also 7:07, 7:08 and 7:09 7:06:11 Schedule 1 Settings for defrost programme 1 Def. Start Times See 07:06 7:07 No. Per Day Number of defrosts/24 hours 0-8 7:07:01 Def1 Sc1 Setting of time the 1st defrost begins 7:07:02 Def1 Sc1 Hour Setting of hours 07:07:02:01 Def1 Sc1 Min. Setting of minutes 07:07:02:02 Def2 Sc1 Setting of time the 2nd defrost begins 7:07:03 Def2 Sc1 Hour Setting of hours 07:07:03:01 Def2 Sc1 Min. Setting of minutes 07:07:03:02 Def3 Sc1 Setting of time the 3rd defrost begins 7:07:04 Def3 Sc1 Hour Setting of hours 07:07:04:01 Def3 Sc1 Min. Setting of minutes 07:07:04:02 Def4 Sc1 Setting of time the 4th defrost begins 7:07:05 Def4 Sc1 Hour Setting of hours 07:07:05:01 Def4 Sc1 Min. Setting of minutes 07:07:05:02 16 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
17 Def5 Sc1 Setting of time the 5th defrost begins 7:07:06 Def5 Sc1 Hour Setting of hours 07:07:06:01 Def5 Sc1 Min. Setting of minutes 07:07:06:02 Def6 Sc1 Setting of time the 6th defrost begins 7:07:07 Def6 Sc1 Hour Setting of hours 07:07:07:01 Def6 Sc1 Min. Setting of minutes 07:07:07:02 Def7 Sc1 Setting of time the 7th defrost begins 7:07:08 Def7 Sc1 Hour Setting of hours 07:07:08:01 Def7 Sc1 Min. Setting of minutes 07:07:08:02 Def8 Sc1 Setting of time the 8th defrost begins 7:07:09 Def8 Sc1 Hour Setting of hours 07:07:09:01 Def8 Sc1 Min. Setting of minutes 07:07:09:02 Schedule 2 Settings for defrost programme 2 Def. Start Times See 07:06 7:08 No. Per Day Number of defrosts/24 hours 0-8 7:08:01 Def1 Sc2 Setting of time the 1st defrost begins 7:08:02 Def1 Sc2 Hour Setting of hours 07:08:02:01 Def1 Sc2 Min. Setting of minutes 07:08:02:02 Def2 Sc2 Setting of time the 2nd defrost begins 7:08:03 Def2 Sc2 Hour Setting of hours 07:08:03:01 Def2 Sc2 Min. Setting of minutes 07:08:03:02 AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
18 Def3 Sc2 7:08:04 Def4 Sc2 7:08:05 Def5 Sc2 7:08:06 Def6 Sc2 7:08:07 Def7 Sc2 7:08:08 Def8 Sc2 7:08:09 Def3 Sc2 Hour 07:08:04:01 Def3 Sc2 Min. 07:08:04:02 Def4 Sc2 Hour 07:08:05:01 Def4 Sc2 Min. 07:08:05:02 Def5 Sc2 Hour 07:08:06:01 Def5 Sc2 Min. 07:08:06:02 Def6 Sc2 Hour 07:08:07:01 Def6 Sc2 Min. 07:08:07:02 Def7 Sc2 Hour 07:08:08:01 Def7 Sc2 Min. 07:08:08:02 Def8 Sc2 Hour 07:08:09:01 Def8 Sc2 Min. 07:08:09:02 Setting of time the 3rd defrost begins Setting of hours Setting of minutes Setting of time the 4th defrost begins Setting of hours Setting of minutes Setting of time the 5th defrost begins Setting of hours Setting of minutes Setting of time the 6th defrost begins Setting of hours Setting of minutes Setting of time the 7th defrost begins Setting of hours Setting of minutes Setting of time the 8th defrost begins Setting of hours Setting of minutes 18 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
19 Schedule 3 Settings for defrost programme 3 Def. Start Times See 7:06 7:09 No. Per Day Number of defrosts/24 hours 0-8 7:09:01 Def1 Sc3 Setting of time the 1st defrost begins 7:09:02 Def1 Sc3 Hour Setting of hours 07:09:02:01 Def1 Sc3 Min. Setting of minutes 07:09:02:02 Def2 Sc3 Setting of time the 2nd defrost begins 7:09:03 Def2 Sc3 Hour Setting of hours 07:09:03:01 Def2 Sc3 Min. Setting of minutes 07:09:03:02 Def3 Sc3 Setting of time the 3rd defrost begins 7:09:04 Def3 Sc3 Hour Setting of hours 07:09:04:01 Def3 Sc3 Min. Setting of minutes 07:09:04:02 Def4 Sc3 Setting of time the 4th defrost begins 7:09:05 Def4 Sc3 Hour Setting of hours 07:09:05:01 Def4 Sc3 Min. Setting of minutes 07:09:05:02 Def5 Sc3 Setting of time the 5th defrost begins 7:09:06 Def5 Sc3 Hour Setting of hours 07:09:06:01 Def5 Sc3 Min. Setting of minutes 07:09:06:02 Def6 Sc3 Setting of time the 6th defrost begins 7:09:07 Def6 Sc3 Hour Setting of hours 07:09:07:01 Def6 Sc3 Min. Setting of minutes 07:09:07:02 AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
20 Def7 Sc3 7:09:08 Def8 Sc3 7:09:09 Def7 Sc3 Hour 07:09:08:01 Def7 Sc3 Min. 07:09:08:02 Def8 Sc3 Hour 07:09:09:01 Def8 Sc3 Min. 07:09:09:02 Setting of time the 7th defrost begins Setting of hours Setting of minutes Setting of time the 8th defrost begins Setting of hours Setting of minutes 20 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
21 Service mode 8 Service function Measurements of Measurements on inlets Input terminals 8:01 S1 C (A) Refrigerant temperature at evaporator inlet 8:01:01 S2 C (A) Refrigerant temperature at evaporator outlet 8:01:02 S3 C (A) Air temperature at evaporator inlet 8:01:03 S4 C (A) Air temperature at evaporator outlet 8:01:04 S5 C (A) Temperature at defrost sensor 8:01:05 S1 C (B) Only AKC 115D/ Refrigerant temperature at evaporator inlet 8:01:06 AKC 116D S2 C (B) Only AKC 115D/ Refrigerant temperature at evaporator outlet 8:01:07 AKC 116D S3/4 C (B) Only AKC 115D/ Air temperature at S3/4 sensor 8:01:08 AKC 116D S5 C (B) Only AKC 115D/ Temperature at defrost sensor 8:01:09 AKC 116D S1 C (C) Only AKC 116D Refrigerant temperature at evaporator inlet 8:01:10 S2 C (C) Only AKC 116D Refrigerant temperature at evaporator outlet 8:01:11 S3/4 C (C) Only AKC 116D Air temperature at S3/4 sensor 8:01:12 S5 C (C) Only AKC 116D Temperature at defrost sensor 8:01:13 NightCover Statement of S6 inlet 8:01:14 (terminal 60-61) Def. Start Statement of defrost start signal 8:01:15 (terminal 30-31) ON input Statement of forced closing input 8:01:16 (terminal 32-33) AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
22 Manual control Forced operation of outlets during service of Outputs "Main switch" must be set to be "-1" (see 2:02:01) 8:02 Man Ctrl. ON: Manual control is permitted when "Main Switch"= -1. OFF / ON NOTE: No monitoring 8:02:01 When manual setting is finished, setting must be changed to OFF. Fan Forced operation of fan outlet OFF / ON (terminal 10-11) 8:02:02 Railheat Forced operation of railheat outlet OFF / ON (terminal 12-13) 8:02:03 AKV OD % (A) Forced operation of expansion valve opening degree (terminal 14-15) 8:02:04 (Fans must be operating during forced control operation) Tc Signal Forced operation of Tc signal OFF / ON (terminal 16-17) 8:02:05 Compressor Forced operation of compressor outlet OFF / ON (terminal 18-19) 8:02:06 Alarm Forced opertion of alarm outlet (terminal 20-21) OFF / ON ON: Relay switch closed (no alarm) 8:02:07 OFF: Relay switch interrupted (alarm) Defrost A Forced operation of defrost outlet OFF / ON (terminal 22-23) 8:02:08 AKV OD % B Only AKC 115D/ Forced operation of expansion valve opening degree AKC 116D (terminal ) 8:02:09 (Fans must be operating during forced control operation) Defrost B Only AKC 115D/ Forced operation of defrost outlet OFF / ON AKC 116D (terminal ) 8:02:10 AKV OD % C Only AKC 116D Forced operation of expansion valve opening degree (terminal ) 8:02:11 (Fans must be operating during forced control operation) Defrost C Only AKC 116D Forced operation of defrost outlet OFF / ON (terminal ) 8:02:12 22 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
23 Error Log: The following display read-outs are only visible if there is an active error. A, B or C in brackets show in which regulation an active error i recorded. When the error is corrected, the error message can be removed by pressing ENTER. (If the code function has been selected, a code must also be entered). S1 Error ( ) S1 sensor error Check sensor connection / sensor resistance S2 Error ( ) S2 sensor error Check sensor connection / sensor resistance S3 Error ( ) S3 sensor error Check sensor connection / sensor resistance S4 Error ( ) S4 sensor error Check sensor connection / sensor resistance S5 Error ( ) S5 sensor error Check sensor connection / sensor resistance S3/4 Error ( ) S3/4 sensor error Check sensor connection / sensor resistance Wrong Ther. Sx Wrong selection of thermostat A weighted value of S3A and S4A has been selected for setting sensor thermostat operation, "Ther Sx" = 3, at the same time as one thermostat function, "Ther Mode" = 2 (3) has been selected. High Air Temp ( ) Too high air temperature Low Air Temp ( ) Too low air temperature Low S4 Temp. A Too low S4 temperature See "6:12" (AKC 114D only) Inject alarm ( ) Overfilled or empty evaporator Max. Def. period Max. defrosting period exceeded Defrosting finished according to time not as selected according exceeded ( ) to temperature Max. fan del time Max. fan delay exceeded When defrost has been completed, the fan start will be based on exceeded ( ) time, and not on temperature (7:05:03) 230 Volt on Wrong defrost demand Active defrost signal on terminal contrary to just finished Def. start input defrosting. Check clock settings Standby mode After power failure, timer must be set The Main switch is either set in the position "Controller stop" or "Service" (see 2:02:01). AKC 114D-116D Version 1.5x Menu operation RC.1H.Z2.02 Danfoss 11/
24 Communications/messages from AKA 21 Message not sent There is no contact between Chech the data communication system control panel and a controller Regulator message - ll - Chech the data communication system not received No node - ll - Chech the data communication system (There is no gateway on the data communication system) Initialisation error - ll - Chech the data communication system (There is a gateway on the data communication system) The message may be removed, if you disconnect AKA 21 briefly Message not Temporary communication Wait, or if it is a newly started system, check the setup of the data understood problem or wrong setup communication system Dansett supervising Pause function When you push a key, the display disappears. Supervising Lack of contact to a controller Chech the data communication system no answer AKC AKA 21 had been disconnected Wait. The message disappears on its own after three minutes. Occupied for a brief period Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alternations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respecitve companies. Danfoss and Danfoss logotype are trademarks of Danfoss A/S. All rights reserved. AC-RDT 24 Menu operation RC.1H.Z2.02 Danfoss 11/1998 AKC 114D-116D Version 1.5x
Controllers for controlling evaporators AKC 114, AKC 115, AKC 116 AKC 114D, AKC 115D, AKC 116D AKC 114A, AKC 115A, AKC 116A. Function description
Function description ADAP-KOOL Controllers for controlling evaporators AKC 114, AKC 115, AKC 116 AKC 114D, AKC 115D, AKC 116D AKC 114A, AKC 115A, AKC 116A RC.1H.U3.02 RC.1H.U4.02 11-1998 Contents Introduction...
More informationMenu operation via AKA 21 ADAP-KOOL. Compressor Pack Controller AKC 25H5. Software version 1.3x
Menu operation via AKA 21 ADAP-KOOL Compressor Pack Controller AKC 25H5 Software version 1.3x RC.1J.23.02 RC.1J.25.02 06-2000 System survey A refrigerating plant fitted with ADAP-KOOL refrigeration controls
More informationMenu operation via AKM ADAP-KOOL. Compressor Pack Controller AKC 25H5. Software version 1.3x
Menu operation via AKM ADAP-KOOL Compressor Pack Controller AKC 25H5 Software version 1.3x RC.1J.33.02 RC1J.35.02 06-2000 Menu list This menu function can be used together with system software type AKM.
More informationCapacity controller for water chiller AK-CH 650
Capacity controller for water chiller AK-CH 650 Menu operation via AKM Menu list This menu function can be used together with system software type AKM. The description is divided up into function groups
More informationController for controlling one evaporator EKC 414A1 REFRIGERATION AND AIR CONDITIONING. Manual
Controller for controlling one evaporator EKC 414A1 REFRIGERATION AND AIR CONDITIONING Manual Introduction Application The controller is a complete control unit for refrigeration appliances with integrated
More informationFunction description ADAP-KOOL. Controller for capacity regulation of brine installation AKC 25H7
Function description ADAP-KOOL Controller for capacity regulation of brine installation AKC 25H7 RC.1N.P1.02 RC.1N.P2.02 06-2001 Contents Introduction... 3 Application... 3 Systeminformation... 4 Operation...
More informationTemperature controller for limitation for the discharge gas temperature EKC 319A REFRIGERATION AND AIR CONDITIONING. Manual
Temperature controller for limitation for the discharge gas temperature EKC 319A REFRIGERATION AND AIR CONDITIONING Manual Introduction Application The controller limits the pressure gas temperature in
More informationCapacity controller EKC 331T REFRIGERATION AND AIR CONDITIONING. Manual
Capacity controller EKC 331T REFRIGERATION AND AIR CONDITIONING Manual Introduction Application The controller is used for capacity regulation of compressors or condensers in small refrigerating systems.
More informationController for appliance control AK-CC 550B. Manual
Controller for appliance control AK-CC 550B Manual Introduction Application Complete refrigeration appliance control with great flexibility to adapt to all types of refrigeration appliances and cold storage
More informationController for appliance control AK-CC 550A
User Guide Controller for appliance control AK-CC 550A ADAP-KOOL Refrigeration control systems Introduction Application Complete refrigeration appliance control with great flexibility to adapt to all types
More informationController for appliance control AK-CC 550. Manual
Controller for appliance control AK-CC 550 Manual Contents Introduction... 2 Operation... 4 Applications...12 Survey of functions...15 Operation...26 Menu survey...28 Connections...32 Data...34 Ordering...35
More informationBasic Plus2 Room Thermostats Floor Heating
MAKING MODERN LIVING POSSIBLE User Guide Basic Plus2 Room Thermostats Floor Heating www.heating.danfoss.com The English language is used for the original instructions. Other languages are a translation
More informationUser Guide. Controller for appliance control AK-CC 450
User Guide Controller for appliance control AK-CC 450 Contents Introduction... 2 Operation... 4 Applications...12 Survey of functions...15 Operation...26 Menu survey...28 Connections...32 Data...34 Ordering...35
More informationLiquid level controller EKC 347 REFRIGERATION AND AIR CONDITIONING. Manual
Liquid level controller EKC 347 REFRIGERATION AND AIR CONDITIONING Manual Introduction Application The controller is used for regulation of the refrigerant level in: Pump reservoirs Separators Intermediate
More informationController for appliance control AK-CC 450. Manual
Controller for appliance control AK-CC 450 Manual Contents Introduction... 2 Operation... 4 Applications...12 Survey of functions...15 Operation...26 Menu survey...28 Connections...32 Data...34 Ordering...35
More informationController for temperature control AK-CC 210
User Guide Controller for temperature control AK-CC 210 ADAP-KOOL Refrigeration control systems Contents Introduction... 2 Operation... 3 Applications... 6 Survey of functions... 8 Operation...18 Menu
More informationController for temperature control EKC 202D1
User Guide Controller for temperature control EKC 202D1 ADAP-KOOL Refrigeration control systems Introduction Application The controller is used for temperature control refrigeration appliances in supermarkets
More informationType UCG/UDG. English...1 Français...7 Español Up button. OK button. Down button
USER MANUAL Type UCG/UDG 57116D 06/12 (MBC) 1.10 2012 OJ Electronics A/S...1 Français...7 Español... 14 Type UCG/UDG Contents Introduction...1 First Time Settings...1 Ground Fault Circuit Interrupter (GFCI)...1
More informationController for temperature control - EKC 202A,B,C and EKC 302A,B
Controller for temperature control - EKC 202A,B,C and EKC 302A,B Manual Introduction Application The controller is used for temperature control refrigeration appliances and cold room in supermarkets Control
More informationController for evaporator control AK-CC 750
User Guide Controller for evaporator control AK-CC 750 ADAP-KOOL Refrigeration control systems Contents 1. Introduction...3 Application... 3 Principles... 4 2. Design of a controller...7 Module survey...
More informationController for Condensing unit Optyma Plus Evo 3 REFRIGERATION AND AIR CONDITIONING. Manual
Controller for Condensing unit Optyma Plus Evo 3 REFRIGERATION AND AIR CONDITIONING Manual Introduction Application Condensing unit control Advantages Condensing pressure control in relation to outside
More informationCapacity controller EKC 531D1 REFRIGERATION AND AIR CONDITIONING. Manual
Capacity controller EKC 531D1 REFRIGERATION AND AIR CONDITIONING Manual Introduction Application The controller is used for capacity regulation of compressors or condensers in small refrigerating systems.
More informationMAKING MODERN LIVING POSSIBLE. FP975 7-Day Electronic Programmer. User Guide. Danfoss Heating
MAKING MODERN LIVING POSSIBLE 7-Day Electronic Programmer Danfoss Heating User Guide For a large print version of these instructions please call Marketing on 0845 121 7400. Certification Mark Danfoss can
More informationRefrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING
Refrigeration and Air Conditioning Controls User s manual Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING Table of Contents Introduction p. 3 Configuring the host
More informationController for operation of evaporator on water chiller EKD 316
Controller for operation of evaporator on water chiller EKD 316 Manual Contents Introduction... 2 Operation... 3 Survey of functions... 4 Operation... 7 Menu survey... 7 Data... 9 Connections... 9 Ordering...
More informationThe full range of Evaporator Controls from ADAP-KOOL
MAKING MODERN LIVING POSSIBLE The full range of Evaporator Controls from ADAP-KOOL ADAP-KOOL case controllers offer highly efficient adaptive routines for each cabinet and cold room installation guaranteeing
More informationERV-24. Technician Settings & Operating Manual. Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135
ERV-24 Technician Settings & Operating Manual Protected by one or more of the following patents: US 5,547,017; 5,881,806; 6,431,268; CA 2,245,135 1 Introduction brief description General The ERV-24-HC11
More information- Data Brochure tekmarnet 4 Thermostat 542e
- Data Brochure tekmarnet 4 Thermostat 542e D 542e 03/08 1 Information Brochure Choose controls to match application 2 Application Brochure Design your mechanical applications 3 Rough In Wiring Rough-in
More informationEKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING. Manual
EKC 347 Liquid Level Controller REFRIGERATION AND AIR CONDITIONING Manual Contents Introduction...3 Valve compatibility...3 Features...3 Application examples...3 Ordering...3 Operating the EKC 347...4-5
More information- Brochure D 542. Introduction. Features. tekmarnet 4 Thermostat /05. 5 Data Brochure Control settings wiring instructions
- Brochure tekmarnet 4 Thermostat 542 D 542 06/05 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough In Wiring Rough-in 4 Wiring
More information3 Channel Multi-Purpose Programmer User Instructions
ES3247B 3 Channel Multi-Purpose Programmer User Instructions Thank you for choosing ESi Controls. All our products are tested in the UK so we are confident this product will reach you in perfect condition
More informationUser Guide. Color Touchscreen Programmable Residential Thermostat. ComfortSense Model: 13H /2015 Supersedes 7/2015
User Guide Color Touchscreen Programmable Residential Thermostat ComfortSense 7500 Model: 13H14 507503-01 10/2015 Supersedes 7/2015 TABLE OF CONTENTS Features... 2 Temperature Dial Indicator... 3 Home
More information4 Wiring Brochure Wiring and
- Brochure tekmarnet 4 Thermostat 544 D 544 06/05 1 Information Brochure Choose controls to match application Application Brochure Design your mechanical applications 2 3 Rough In Wiring Rough-in 4 Wiring
More informationUSER MANUAL Comfort System4 TM
67023D 07/16 (LOA) OCS4-10 / OSD4-1999 / OSA4-10 USER MANUAL Contents Introduction...1 Central Controller - Menu overview...2 First time settings Setup of the Comfort System4...3 Setup Central Controller...3
More informationInstructions AK-PC 520
Instructions AK-PC 520 084B8012 Identification Dimensions 084B8012 Principle NZ control PI or P control RI8NM102 04-2009 ENGLISH Connections P0/Pc: AKS 32R: 1 = Black = + 2 = Blue = - 3 = Brown = s Brine
More informationREMOTE CONTROL FOR CHILLER MYCHILLER
REMOTE CONTROL FOR CHILLER MYCHILLER GENERAL FEATURES... 3 MAIN FUNCTIONS AND EQUIPMENT:... 3 LCD DISPLAY... 4 KEYBOARD... 5 BOARD CONFIGURATION... 7 LIST OF MAIN PARAMETERS... 7 CONFIGURATION OF MAIN
More informationUSER'S OPERATING INSTRUCTIONS
SAT-2 Thermostat COOL FAN DRY HEAT AUTO SLEEP SWING AUTO ZONE SUN MON TUE WED THU FRI SAT HEATER ON OFF ERR UNIT USER'S OPERATING INSTRUCTIONS CONTENTS Page Introduction 3 Features Summary 3 Display 4
More informationDesigner TT Programme Set Up
Designer TT Programme Set Up After securely mounting the radiator as per the manufacturers installation instructions plug the radiator into a 13 amp socket outlet Turn the radiator ON by pressing the bottom
More informationT7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS
Contents T7350 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS OWNER S GUIDE Features... 2 Settings... 3 Programming... 5 63-2638 FEATURES Typically used in buildings (including: restaurants,
More informationOWNER S MANUAL. Part Number P
OWNER S MANUAL CPV230 Commercial Thermostat Part Number P374-2300 CONTENTS Page GENERAL...2 CONFIGURATION...3-12 Thermostat Display...3 Heat or Cool Indicator...4 Thermostat Front Panel Buttons...4 Thermostat
More informationCapacity controller AK-PC 651
User Guide Capacity controller AK-PC 651 ADAP-KOOL Refrigeration Control System Introduction Application The controller is used for capacity regulation of compressors and condensers in small refrigeration
More informationT7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS
T7351 Programmable Thermostat FOR CONVENTIONAL/HEAT PUMP SYSTEMS 63-2652 FEATURES Typically used in buildings (including: restaurants, shopping malls, office buildings and banks) under 55,000 square feet.
More informationOwner s Manual. Part Number 33CS250-01
33CS Commercial Programmable Thermostat IMPORTANT: Read entire instructions before programming the thermostat. Owner s Manual Part Number 33CS250-01 GENERAL Carrier s 7-day, commercial, programmable thermostats
More informationComfortSense 7500 Thermostat. User Guide
ComfortSense 7500 Thermostat User Guide 507503-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...3 Home Screen Information...3 Operating Mode Selection...6
More informationTB8220U Commercial Programmable Thermostat OWNER S GUIDE
TB8220U Commercial Programmable Thermostat OWNER S GUIDE 63-2643 Contents Features... 3 Main Screen Selections... 4 Programming Heating and Cooling Schedule... 6 Operating the Thermostat... 10 Replacing
More informationControl of the system, MLP RO pump station
Control of the system, MLP RO pump station Operating instructions TI071GB-02 /06.11.09/LJ 1/12 Table of contents Humidification pump Safety equipment Selecting RO type Choice of language Normal indications
More informationMAKING MODERN LIVING POSSIBLE. CP715Si. Electronic 2-Channel Common Timebase Programmer for Heating and Hot Water. User Guide.
MAKING MODERN LIVING POSSIBLE CP715Si Electronic 2-Channel Common Timebase Programmer for Heating and Hot Water Danfoss Heating User Guide CP715Si Electronic 2-Channel Common Timebase Programmer for Heating
More informationdanfoss Heating Solutions 5
4. Technical settings...22 4.1 Deactivating automatic daylight saving time...22 4.2 Adjusting to radiator/room...23 4.3 Deactivating intelligent control...23 4.4 Technical specifications...24 5. Safety
More information103E7. User Guide. 7-Day Electronic Timeswitch for Controlling Hot Water and Heating (Including Factory Replacement Units FRU) Danfoss Heating
103E7 7Day Electronic Timeswitch for Controlling Hot Water and Heating (Including Factory Replacement Units FRU) Danfoss Heating User Guide 103E7 7Day Electronic Timeswitch for Controlling Hot Water and
More informationDEVIreg Opti Electronic Timer Thermostat fulfilling Eco Design Directive
DEVIreg Opti Electronic Timer Thermostat fulfilling Eco Design Directive www.devi.com Table of Contents 1. Introduction..................................... 2 2. Technical Specifications.........................
More informationSafety & Installation Instructions
Model 8800 Universal Communicating Thermostat Safety & Installation Instructions READ AND SAVE THESE INSTRUCTIONS Table of contents Installation Installation location recommendations... 2 Thermostat mounting...
More informationProduct Manual SZ1009
Product Manual SZ1009 Conventional Heating & Cooling Thermostats with Heat Pump Mode Communicating Thermostats Description The SZ1009 is a microprocessor-based mable thermostats designed for conventional
More informationUser manual. CTS 602 by Nilan VPL 15 VPL 15 TOP. Version: 9.02, Software-version: 2.21
User manual CTS 602 by Nilan VPL 15 VPL 15 TOP Version: 9.02, 19-05-2014 Software-version: 2.21 Table of contents Table of contents... 2 Figure table... 2 Introduction... 3 Types of units... 4 Review of
More informationTPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating
TPOne-B Electronic Programmable Room Thermostat Danfoss Heating Installation Guide TPOne is an intelligent programmable heating control made easy. TPOne includes features which are designed to save energy.
More informationCapacity Controller AK-PC 351
User Guide Capacity Controller AK-PC 351 ADAP-KOOL Refrigeration Control System Introduction Application The controller is used for capacity regulation of compressors and condensers in small refrigeration
More informationComfortSense 7500 Commercial Thermostat. User Guide
ComfortSense 7500 Commercial Thermostat User Guide 507505-02 6/2018 Supersedes 5/2017 Table of Contents Features...2 Home Screen Temperature Indicator...2 Home Screen Information...3 Operating Mode Selection...5
More informationInstallation Guide. ECL Comfort 210, application A Table of Contents
1.0 Table of Contents 1.0 Table of Contents... 1 1.1 Important safety and product information..................... 2 2.0 Installation... 4 2.1 Before you start.....................................................
More informationDPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N
DPC-1 Programmable digital thermostat with communication Versión 2.0 Ref: N-27360 1108 Technical Information I S O 9 0 0 1 ER-0028/1991 Johnson Controls Manufacturing España, S.L. is participating in the
More informationOwner s Manual. Part Number 33CS250-FS and 33CS220-FS
Debonair 33CS Flush-Mounted Flatstat Commercial Programmable Thermostat IMPORTANT: Read entire instructions before programming the thermostat. Owner s Manual Part Number 33CS250-FS and 33CS220-FS GENERAL
More informationES3247B. 3 Channel Programmer. User and Installation Instructions
ES3247B 3 Channel Programmer User and Installation Instructions INDEX User Instructions What is a Channel Programmer? 1 Introduction to the 3 Channel Programmer 2 Quick Operating Guide 3 Programming the
More informationPlease read this manual carefully before installation and use.
Doylestown, PA 18902 USA Phone: 215-766 1487 - Fax: 215-766 1493 Email: support@scillc.com - www.scillc.com FMT-24-SUPER-PROG With freeze protection Owner s Manual Installation and Operating Instructions
More informationOptimize your HVAC/R application with the right Danfoss components
ADAP-KOOL Selection Guide Optimize your HVAC/R application with the right Danfoss components One- Stop-Shop for flexible control solutions Engineering Tomorrow s Food Retail Solutions Enterprise Manager
More informationParts Diagram. Up button. Down button. Right (fan) button. Left (system) button. RC/RH Jumper. Field programming pins
Table of Contents Parts Diagram........................................................... 1 Icon Descriptions......................................................... 2 Specifications...........................................................
More informationSubcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A
Installation & Service Manual S E C T I O N 26 Enviroguard III ENVIROGUARD III is a patented refrigerant control system that utilizes floating head technology (Nature s Cooling). The amount of liquid refrigerant
More informationTOUCHSCREEN. COMFORTSENSE Day Programmable Thermostat. 4 Heat / 2 Cool Universal Multi Stage MODEL NUMBER IDENTIFICATION L U FEATURES
P R O D U C T S P E C I F I C AT I O N S C O N T R O L S TOUCHSCREEN COMFORTSENSE 7000 7-Day Programmable Thermostat Bulletin No. 210515 June 2009 Supersedes February 2008 HOME SCHEDULE OPTIONS SET AT
More informationINSTRUCTIONS AK-CC 250A
INSTRUCTIONS AK-CC 250A t amb = 0 - +55 C 230 V a.c. 50/60 Hz 2.5 VA 10 V < U < 256 V DO1. Refrigeration * DO2. Defrost * DO3. Fan or refrigeration 2 * Coordinated defrost CE (250 V a.c.) 8 (6) A 8 (6)
More information1 DOCUMENT REVISION SOFTWARE VERSION BASIC DESCRIPTION BASIC OVERVIEW OF HYDRAULIC DIAGRAMS HYDRAULIC DIAGRAMS...
User Manual Contents 1 DOCUMENT REVISION... 4 2 SOFTWARE VERSION... 4 3 BASIC DESCRIPTION... 4 4 BASIC OVERVIEW OF HYDRAULIC DIAGRAMS... 5 4.1 BOILER NOT CONTROLLED BY THE CONTROLLER:... 5 4.2 BOILER CONTROLLED
More information/18 (JRK) MTD User Manual OJ Electronics A/S
67772 02/18 (JRK) MTD3-1999 User Manual Table of Contents Introduction.................................. 3 Menu Overview................................ 4 Icons....................................... 5
More informationModular Standard HP Chiller 1/4 screw compressor with Carel driver
Program for pco¹ pco 2 and pcoc Modular Standard HP Chiller 1/4 screw compressor with Carel driver Manual version 1.0 25 September 2003 Program code: FLSTDmMSDE Do we want you to save you time and money?
More informationETN-24-SUPER-PROG (US Program - Celsius)
Meitavtec Ltd (Contel group) Tel: 972 (3) 962 6462 Fax: 972 (3) 962 6620 www.meitavtec.com support@meitavtec.com ETN24SUPERPROG (US Program Celsius) Owner s Manual Installation and Operating Instructions
More informationRefrigeration and Air Conditioning Technical leaflet. Electronic controller EKC 201 and EKC 301
Refrigeration and Air Conditioning Technical leaflet Electronic controller EKC 201 and EKC 301 RC.5L.A1.02 RC.5L.A2.02 09-1998 Introduction EKC 201 and 301 are used for temperature control compressor control
More informationSafety. DANGER Indicates potentially fatal situations. WARNING Indicates possible danger to life and limb.
Edition 06.14 GB Operating and installation instructions Lago FB digital remote control Translation from the German 2014 Elster GmbH Safety Please read and keep in a safe place Please read through these
More informationOperation Manual NOVA LIVE S
Operation Manual NOVA LIVE S Models: NLS 1000, NLS 1500 and NLS 2000 IMPORTANT SAFEGUARDS Before use, please read and follow these instructions carefully, even if you feel you are familiar with the product.
More informationCTS 602 by Nilan. Compact P. Compact P Sun. Compact P Cool. Compact P Cool Sun. Version: 5.00, Software-version: 2.11
User manual CTS 602 by Nilan Compact P Compact P Sun Compact P Cool Compact P Cool Sun Version: 5.00, 13-06-2011 Software-version: 2.11 Contents Contents... 2 Figure table... 2 Introduction... 4 Types
More informationThe Information Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will
The formation Contained in this Document is Proprietary and should only be used for Service or Training of Authorized Blodgett Servicers who will be working on the Blodgett XR8 Oven. All other uses are
More informationEMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE
EMERSON BLUE Wireless Comfor t Inter face 1F98EZ-1621 HOMEOWNER USER GUIDE Emerson Blue Wireless Comfort Interface - Homeowner User Guide Message to Homeowners Congratulations on choosing the Emerson Blue
More informationECL Comfort 110, application 116
Operating Guide ECL Comfort 110, application 116 (valid as of software version 1.08) English version www.danfoss.com How to navigate? Adjust temperatures and values. Switch between menu lines. Select /
More informationSLV CONTROLLER 105N46XX SERIES
WITH MORE THAN 50 YEARS OF EXPERIENCE IN COMPRESSOR TECHNOLOGY AND HIGHLY COMMITTED EMPLOYEES, OUR FOCUS IS TO DEVELOP AND APPLY THE ADVANCED COMPRESSOR TECHNOLOGIES TO ACHIEVE STANDARD SETTING PERFORMANCE
More informationOWNERS MANUAL YEAR LIMITED WARRANTY READ ALL INSTRUCTIONS BEFORE PROCEEDING. Store this booklet for future reference
5100 Premier Series 7-Day Programmable 2-Heat / 2-Cool Heat /Cool Digital Thermostat OWNERS MANUAL Compatible with low voltage multi-stage heat / cool systems with up to two stages of heating and two stages
More informationPhone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.
Introduction The UL listed Phone-A-Stat (model # 7632 ) is designed and approved for the safe operation of remotely controlling four independent loads, such as a sprinkler system or a water heater via
More informationWeather compensated flow temperature control of heating and boiler systems
Instructions ECL Comfort 110 Application 130 Weather compensated flow temperature control of heating and boiler systems User guide, Installation & Maintenance DH-SMT/DK VI.KT.G3.02 Danfoss 06/2008 How
More informationRC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control
O M N I S T A T ELECTRONIC COMMUNICATING THERMOSTAT Installation Manual RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control Document Number 13I00-5 November, 1997 CONTENTS
More informationUSER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING 2 INSTALLATION
MODEL 5100 USER MANUAL Compatible with low voltage multi-stage heat/cool systems with up to two stages of heating and two stages of cooling. READ ALL INSTRUCTIONS BEFORE PROCEEDING 1 2 3 4 5 6 7 CONTENTS
More informationUser s Manual
997-060180-4e User s Manual 8403-060 Menu Driven Display 1120-445 I. CONTROLLER OPERATION ADJUSTING TEMPERATURE (Temporary Override when in Programmable mode) 1. Before you can adjust the temperature,
More information1F97-51 OPERATION GUIDE WHITE-RODGERS. Operator: Save this booklet for future use! 7-Day Programmable Electronic Digital Thermostat
OPERATION GUIDE 1F97-51 7-Day Programmable Electronic Digital Thermostat WHITE-RODGERS Operator: Save this booklet for future use! About Your New Thermostat... Your new White-Rodgers Digital Thermostat
More informationPanel Convector Heater User Instructions
Panel Convector Heater User Instructions LEVPH750TPR, LEVPH1250TPR, LEVPH1500TPR, LEVPH2200TPR IMPORTANT SAFEGUARDS Before use, please read and follow these instructions carefully, even if you feel you
More informationElegance. SMT-700 User manual. Ver
Elegance SMT-700 User manual Ver 3.0. 0807 Congratulations on the purchase of your new Thermostat! Your new air conditioning system thermostat has been built using the best components and design philosophy
More informationOperating your heating system with the Prefect PRE5701 Programable Thermostat
Operating your heating system with the Prefect PRE5701 Programable Thermostat 1 Your central heating system has been designed to provide a comfortable and flexible living environment, enabling you to have
More informationATC32U01 igate Communicating, Programmable Thermostat
ATC32U01 igate Communicating, Programmable Thermostat User Manual 97B0055N02 Rev.: 7/2/12 Table of Contents Section Title Page Menu Navigation Shortcuts 3 1.0 Operating Mode Selection 3 2.0 Temperature
More informationProgrammable Interactive User Manual
67504B 02/16 (ALA) DH E RT 102/BW Programmable Interactive User Manual www.schluter.com 1. Contents 2. Menu Overview..............3 3. Introduction................ 4 4. General Operation............5 4.1.Navigation
More informationMicroelectronic Programmable Thermostat Owner s Manual. 1 J.H Form Number
Microelectronic Programmable Thermostat Owner s Manual 1 J.H. 5-94 Form Number 69-0819 Table of Contents Programmed Recovery... 3 Programming Your Thermostat... 6 Programming... 6 Program Schedule... 7
More informationTechnical description. Atec.
www.thermia.com Thermia Värmepumpar is not liable or bound by warranty if these instructions are not adhered to during installation or service. The English language is used for the original instructions.
More informationTable of Contents. Product Image Table of Contents What is a Programmable Room Thermostat? Installation Procedure
1 Model: 1 Table of Contents Product Image Table of Contents What is a Programmable Room Thermostat? Installation Procedure 1 2 3-4 5-6 Mode Select Pairing the ProTouch iq Hub Pairing the ProTouch iq What
More informationIce Rink (Single and Dual Configurations) Custom Control Features
& M&M Refrigeration, Inc. Computer Control System Ice Rink (Single and Dual Configurations) Custom Control Features REVISION DATE DESCRIPTION - 4/20/05 Original release. A 09/21/98 Update Chiller Pump
More informationMAKING MODERN LIVING POSSIBLE. TP7001 Range Electronic 7 Day Programmable Room Thermostat. User Guide. Danfoss Heating
MAKING MODERN LIVING POSSIBLE TP7001 Range Electronic 7 Day Programmable Room Thermostat Danfoss Heating User Guide TP7001 Electronic 7 Day Programmable Room Thermostat For a large print version of these
More informationCOMF RT SYSTEM. T-32-TS Touchscreen Thermostat. User Manual
COM RT SYSTEM T-32-TS Touchscreen Thermostat User Manual TABLE O CONTENTS INTRODUCTION USINGTHETOUCHSCREEN DISPLAY TYPICAL DISPLAY SETTINGTHE DAY,TIME AND CALENDAR SETTING DAYLIGHT SAVINGTIME BASIC UNCTIONS
More informationMAKING MODERN LIVING POSSIBLE. User Guide. ECtemp 550. Electronic Intelligent Thermostat.
MAKING MODERN LIVING POSSIBLE User Guide ECtemp 550 Electronic Intelligent Thermostat www.eh.danfoss.com Table of Contents 1 Introduction............... 4 1.1 Safety Instructions........ 5 2 Settings.................
More informationProduct Manual SZ1022/SZ1031/SZ1035/
Product Manual SZ1022/SZ1031/SZ1035/ Conventional Heating & Cooling Thermostats Communicating Thermostats Description The SZ1022, SZ1031, and SZ1035, are microprocessorbased mable thermostats designed
More informationOperation manual. Daikin Altherma ground source heat pump EGSQH10S18AA9W. Operation manual Daikin Altherma ground source heat pump.
English Table of contents Table of contents About this document About the system. Components in a typical system layout... 3 Operation 3 3. Overview: Operation... 3 3. The user interface at a glance...
More informationMonitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING. Manual
Monitoring unit with alarm function and data collection AK-SM 350 REFRIGERATION AND AIR CONDITIONING Manual Introduction The AK-SM 350 is a combined data collection and monitoring unit for use in refrigeration
More information