Evaporative Cooling Technology Today

Size: px
Start display at page:

Download "Evaporative Cooling Technology Today"

Transcription

1 Evaporative Cooling Technology Today MARK IZARD, Monza (MI), Italy consultant E BAKAYA-KYAHURWA Department of Mechanical Engineering University of Botswana; Bag UB0061, Gaborone, Botswana bakayae@mopipi.ub.bw Abstract Water, because of its stability, heat transfer capabilities and seemingly inexhaustible supply, has been the prime sink used by nearly all industries for heat rejection. The Evaporative Cooling approach is basically a water saving technique where cooling water is continuously recirculated through the heat generating source and is cooled by evaporative heat rejection through the cooling tower. The cooling tower is the simplest and least expensive of all the evaporative cooling methods. The paper covers the nature and convenience of evaporative cooling as used in small, prefabricated cooling towers for HVAC applications and in large field erected units for industrial applications. Procedures for correct maintenance and cleaning in order to obtain maximum operating efficiency are addressed. The advantages and applications of wet dry hybrid units with particular reference to reducing water consumption are covered. The latest developments in heat exchange components are examined along with the relative merits of different forms and construction materials for the tower internals. The discussion that follows is about a wet-dry hybrid evaporative cooler, which in addition to the conventional tower has a coil that precools the hot water before it enters the wet section of the tower. Keywords: Cooling tower, Evaporative cooling, Wet-dry hybrid tower. INTRODUCTION Basic characteristics of an evaporative cooling tower An evaporative cooling tower is a machine of relatively simple conception and operation. The water to be cooled for a chiller, industrial process or refrigeration installation is pumped and distributed through spray nozzles over a fill pack or heat exchange surface through which passes an air current commonly generated by a fan. A small fraction of this water evaporates and the remainder is cooled thanks to the absorption of the latent heat of evaporation by the passing air, and falls under gravity into a basin (usually an integral part of the tower) from where it is pumped back to the heat load source. To avoid water entrainment the tower is fitted with droplet separators. Typical water evaporation rate is 1.8 m 3 /h for every kcal/h of heat rejected. A water quantity equal to that lost by evaporation must be bled-off from the tower inlet pipe (from the heat load): both these quantities are compensated by the make-up. In a circuit connected to an evaporative cooling tower the rate of water evaporation varies in proportion to the heat to be rejected at every instant. Moreover it is reduced as the outside ambient temperature goes down in the low season because the effect of the sensible heat exchange between the water to be cooled and the air current becomes significant. The water leaving temperature from the tower is determined by the wet-bulb temperature of the intake air and the design value (for a reasonable selection) will in any case be at least 3 C above the

2 design summer wet-bulb temperature. This is about 15 C below the outlet temperature obtainable from an aircooled unit of reasonable size. [Cooling tower maintenance manuals, EEC Machinery Directive]. For the correct application of any cooling tower it is advisable to consider at least the following items: Layout (for correct airflow without recirculation). Piping (for correct distribution, avoiding hold-up problems and cavitation). Freeze protection. Noise Levels and, where applicable. Capacity control. Ramifications of the standard cooling tower to suit the zone and application The first aspect to be considered in terms of a modern modification of the traditional cooling tower is the wetdry hybrid version execution. There are various options to examine: the most cost-effective solution for a particular installation depends substantially upon the importance of reducing water consumption. It is generally considered that the dry section of the cooling tower is primarily for plume control. In that case the cooling tower has the basic format shown in Fig. 2. Figure 1: Operating principle of an evaporative cooling tower It should be noted that the coils are mounted in a way which results in cross-flow heat exchange between the water descending inside the coil and the air flux: this is a poorer usage of the heat exchanger than complete counter-flow but is the standard set-up for ease of coil mounting. The cross-flow form of the tower wet/evaporative section is standard in the USA [ASHREA] whereas in Europe a counter-flow wet section which has the form of figure 1 is used. The dry section serves to provide warm, dryer air to be mixed with the very humid warm air from the evaporative cooling tower lower section. This is to reduce or eliminate plume formation when the discharge air comes in contact with cooler ambient air above the fan stacks [this "plume" is due to the condensation of water previously in vapour form].

3 Figure 2: [ASHREA] However in the context of industrial plant in hot climates where water consumption is a critical factor, it is instead appropriate to concentrate upon the quantity of pre-cooling of the entering warm water that can be achieved in the dry section, either at design conditions (summer dry bulb) or mid-season conditions. [Blackadder D.A. & Nedderman R.M. A Handbook of Unit Operations]. Subsequently the dry cooling should be maximised throughout the year. In the design stage the possibilities, according to the surrounding conditions and ambient temperatures should be carefully considered because "oversized" coils may be the appropriate option. I would not recommend the use of the open plastic fill-type heat exchangers for the dry section: they are an interesting idea for cooler climates where we need to reduce the cost of the heat exchanger support structure but the lower heat transfer by conduction through plastic plates and the lack of extended surface make them unsuitable for our objective of maximising dry cooling. Here is a practical selection example The end-user (a petro-chemical industry in Mexico) needs to cool 2725 m³/h of water from 47 C to 37 C with ambient air of 33 C/60% relative humidity (these conditions exist 20 days per annum): this corresponds to a design wet bulb temperature of 26 C. They indicate desirable design conditions of water cooled from 42 C to 32 C for ambient air at 28 C dry bulb with 65 % relative humidity (wet bulb = 23 C). The final design was based upon obtaining a dry pre-cooling of the given water flow rate from 42 C to 39 C using 16 finned coils, each 9 m long by 2 m high for air available at 28 C. These coils go then in pairs on 4 double air-intake counter-flow film fill cooling cells which evaporatively cool the flow from the combined coil outlets from 39 C to 32 C at 23 C design entering air wet bulb. What is interesting is that these coils can cool the same flow from 42 C to 36,3 C for an entering air temperature of 15 C (corresponding to the customer's winter season). This of course requires airside regulation in as much as we need full airflow on the coils and considerably diminished evaporative cooling capacity for the lower "wet" section of the tower. [Foster R.E. Air Conditioning with Evaporative Technology; March 1999] There is another interesting manner of approaching the question of maximising air-blast cooling capacity: the use of humidification panels, constructed from corrugated sheets of either resin-treated paper or fibre-treated PVC, over which water is distributed in excess and air is drawn in cross-flow format (to minimise airside pressure drop and risk of droplet entrainment). This system adiabatically cools and humidifies the inlet air which

4 follows the line of constant wet bulb temperature (very nearly parallel with the lines of adiabatic saturation in the air-water system which has similar values of diffusivity and thermal diffusivity): in this manner the air supplied to the dry cooling coils [Fig. 3] can be reduced in temperature typically by 5-6 C, with a consequent reduction in cooling water temperatures within the closed and protected finned-coils. [Personal Correspondence; Comfort Air, Zwolle Netherlands]. Figure 3: [ASHREA handbook Ch.37] As a natural extension from this examination of the best selection, usage and maintenance of evaporative cooling towers and having touched on evaporative cooling as a means of increase air-blast cooling capacity, there is a further development worthy of mention, being applicable as an economical HVAC system and particularly promising for hot countries with limited energy. In recent years, to provide some more economical and simpler "air-conditioning" for non-critical environments, a development has been made from standard adiabatic cooling, where some air cooled by the humidifying fill is cycled back to an air-air heat exchanger in order to pre-cool the outside air, before it enters the fill. This system basically permits us to cool a couple of degrees below the ambient air wet bulb temperature. Of course this type of system really provides "conditioned" air, which is too humid for normal "comfort", even if it is help for some spaces. A Dutch company has researched intensively and is now developing a commercial-scale-cooling unit derived from this technology, which brings further temperature reductions and a controlled humidity level. Although it is not possible to provide at this time the technical details (because of patents pending) it is possible to state that there will be commercial available a system suitable for "volume comfort cooling" in large commercial and industrial buildings and enclosed market areas. This system has the main advantages of: Significant reductions in energy consumption compared to normal "chiller-type" air conditioning. No refrigerant circuit and no compressor energy requirement. Relatively low cost and simple units for easy assembly even in areas with limited industrial facilities. Easy installation and service by ventilation personnel. There will also be the possibility of application on mobile units without additional power. The second important variable to consider in the design of the cooling tower is the fill-type. A whole section has been dedicated to "film" fills because of their greater heat exchange surface per unit volume. The starting point is to identify where the water is corrosive or scaling and/or dirty (charged with mud, algae etc.). It is necessary

5 to have values of ppm solids, ph, calcium hardness and total alkalinity. From these values are derived the Langlier saturation index which tells us whether the water is corrosive or scaling. In the case of the former, our concern must be with the support structures - the situation can be exacerbated by problems such as stresscorrosion cracking of steel in the presence of chloride ions. Scaling problems mean that we should be selecting the tower with a more open fill structure, best with vertical channels,.to facilitate inspection and cleaning and reduce risk of blockage. [Personal correspondence; Tower components USA]. Heavy scaling and/or high dirt levels require an effective splash fill with an optimised plastic grid system: smaller spans, inter-grid support to distribute loading and the ability to fit closely to the tower structural pillars are the key features [Tower Components Inc.]. Figure 4: Splash Grids during Installation Figure 5: Cell with Splash Fill in Operation [Photos courtesy of Tower Components Inc.] Using these more open or splash fills means selecting a larger unit with a greater initial investment: the saving comes in reduced maintenance and downtime. Synthetic fill pack & the advantages of pvc The use of plastic materials for cooling tower internals was born in the USA principally of the necessity to increase surface per unit volume and reduce both material and installation costs, providing also corrosion resistance.

6 Figure 6: [ASHREA] For example, in an evaporative cooling tower the employment of corrugated PVC sheets for all types of tower has enabled manufacturers to significantly reduce the cell dimensions thanks to a much greater specific exchange surface (for heat and mass transfer) per unit volume of cooling tower, compared to the old style fills made of wooden slats, grilles or indeed metal panels. In very large refinery towers and in the hyperbolic, natural draught towers of electrical power stations it was common practice for many years to employ a heat exchange surface made from asbestos-cement panels. Plastic packings have offered a cost effective alternative on a large scale all over both western and eastern Europe and allowed the end-users to dispose of that rather unhealthy asbestos material! Typically a synthetic/plastic fill is composed of high quality corrugated PVC sheets: these are assembled with the direction of the corrugations inverted every other sheet and glued together to form modules, typically 1200 x 300 x 300 mm or 1200 x 600 x 600 mm [although larger units can require modules of 1800 mm or 2400 mm length]. PVC is nowadays generally considered by tower manufacturers to be the most suitable synthetic material for the majority of cooling tower applications - for 3 reasons: It is intrinsically self-extinguishing. It has an optimum resistance to cycles of thermal "shock" (hot water brought on to cold fill pack when starting-up an industrial installation in the Winter). Best fill sheet efficiency because the adhesion of the water to make a nice, thin layer (which exchanges heat and mass with the passing air) on a synthetic sheet is best on PVC. When a cooling tower is put into service the friction of the water flowing over the fill sheets changes its surface in such a way that the adhesion (and hence the thermal performance) is maximised in about 6 weeks. Other plastic materials require about 10 times as long. [EUROFILL Literature Fill Media & Droplet Eliminators]. Additionally it is worth mentioning that for big cooling tower projects PVC fill can be supplied in loose sheets for easy and quick site assembly: this minimises transport and storage volume and costs. For some time during this past decade interest was shown in other plastic compounds considered possibly more "ecological" because potentially easier to recycle. Apart from the fact that used fill pack contains either biological matter, deposits or scale and must therefore be cleaned up before disposal, the PVC industry and more precisely the ECVM has invested in PVC recycling technology which will break down PVC waste into its constituent components. In the E.U. the first plants on PVC recycling are currently being brought on line.

7 The cooling tower is technologically simple equipment but once the right equipment supply for the application and surroundings has been effected there must also be a programmed and systematic approach to maintenance and servicing in order to ensure efficiency and avoid energy and water wastage. Advised servicing for cooling towers Type of servicing Start-up Shut-down Annual Inspection of the general condition of the unit Cleaning and removal of residues Cleaning and rinsing of pan Cleaning of filter Adjustment of water level Inspection of the heat exchange surface Inspection of the drift eliminators Inspection of the water distribution tubes Check and adjustment of bleed-off Check make-up valve Check for noise or vibrations Voltage and absorbed current control Lubricate bearings (where applicable) Check for unobstructed fan rotation Check for direction of fan rotation Drain pan and piping Inspection of galvanised components (where applicable) "Trouble-Shooting" Guide To Tower Internals Problem/Difficult Causes Remedies/Rectifying Action 1. Voltage reduction Check the voltage 2a. Incorrect angle of axial fan blades b. Loose belts on centrifugal fans (or speed- Adjust the blade angle Check belt tightness A. reducers Excessive absorbed 3. Overloading owing to excessive airflow-fill has current Regulate the water flow by means of B. Drift/carry-over of water outside the unit C. Loss of water from basins/ pans D. Lack of cooling and hence increase in temperatures owing to increased temperature range minimum water loading per m 2 of tower section the valve 4. Low ambient air temperature The motor is cooled proportionately and hence delivers more than nameplate power 1. Uneven operation of spray nozzles Adjust the nozzle orientation and eliminate any dirt 2. Blockage of the fill pack Eliminate any dirt in the top of the fill 3. Defective or displaced droplet eliminators Replace or realign the eliminators 4. Excessive circulating water flow (possibly owing to too high pumping head) Adjust the water flow-rate by means of the regulating valves. Check for absence of damage to the fill! 1. Float-valve not at correct level Adjust the make-up valve 2. Lack of equalising connections Equalise the basins of towers operating in parallel 1. Water flow below the design valve Regulated the flow by means of the valves 2. Irregular airflow or lack of air Check the direction of rotation of the fans and/or belt tension (broken belt possible) 3a. Recycling of humid discharge air Check the air descent velocity b. Intake of hot air from other sources Install deflectors 4a. Blocked spray nozzles (or even blocked Clean the nozzles and/or the tubes spray tubes) b. Scaling of joints Wash or replace the item 5. Scaling of the fill pack Clean or replace the material (washing with inhibited aqueous sulfamic acid is possible but long, complex and expensive)

8 Indications of Component Life Although it is naturally difficult to provide precise indications of the lifetime of the modular internals [which do depend upon air and water quality and general treatment of the unit], the following indications are worth considering: If the circulating water is scaling then the film fill pack may require replacement after 3 years. For small factory assembled units this is an acceptable maintenance work necessity. For very large units it represents a problem and is why splash fill should be seriously considered in these cases. Metallic drill eliminators should be examined with a view to possible replacement after 3-4 years: the solution of longer duration is modular PVC panels [fitted into a suitably resistant frame if they are on the summit/discharge of a forced-draught unit]. Tower fill replacements using plastic fill blocks A mm wave form is the most common type in the factory-assembled small cooling towers with fill heights of 300 mm to 1200 mm. Very occasionally a greater spacing is employed in smaller units. A 20 mm spacing is the standard fill for big cooling cells and field-erected units (cross-sections greater than 3-4 m by 3-4 m ) with fill height commonly mm. In large cells one may observe very strong jets of water from the spray nozzles: this can be due to dirt blocking some of the nozzle discharges, missing nozzles, poor water distribution or even the type of nozzle used. In this sort of case it is advisable to place a top half-layer or full layer of fill made with sheets of increased thickness (typically 500 macron). Towers with dirty or clogging water use even bigger openings [a 27 mm or even 50 mm wave-form] but it is important that this type of fill is covered by a top half-layer of 20 mm wave fill which ensures that the water sprayed is completely distributed over the main fill surface and does not descend freely down part of an opening. When repacking a tower it is important to: Check existing fill supports and hold-down channels for compatibility and positions compared to the new flu modules. Respect the original distance between the spray nozzles and the top of the fill. The "catch" here is that if we try to increase fill height (to obtain more thermal capacity) we. might reduce the space between the sprayers and the fill - water distribution can suffer and so tower performance decreases instead of increasing! Check temperature requirements: for high temperature applications ( > 60 C ) which represent 5-10 % of the installations a high temperature PVC is available (most commonly an ABS additive is employed to obtain the increased temperature limit). Modular plastic drift eliminators This type of eliminator is appreciated by maintenance contractors and end-users who have experienced the common corrosion problems associated with traditional metal-bladed eliminators in galvanised steel. The lightweight PVC eliminators are also better for towers with discharge ductwork, discharge hoods and air discharge sound attenuation because the panels are easier to remove, inspect and refit. [Johnson T. PowerGen Plastic Packings for Large Cooling Towers, - The Chemical Engineer, 1999]. Starting from preformed PVC sheets, these eliminators are prefabricated in handy blocks for ready insertion in the cooling tower and for easy removal for inspection of the water distribution. Thanks to their rectangular, modular form and to the ease of cutting, and exact coverage of the water distribution system can be made on site when renovating the tower.

9 Droplet eliminators Figure 7: [Photo courtesy of Eurofill Srl] Three model types can be identified: Panels comprising air passages with 2 changes in direction of airflow: these are used on axial fan, induceddraught towers. The panels are arranged in 2 series with the air direction changes oriented to bring the air towards the centre of the tower and the fan intake (for minimum pressure drop). Panels comprising air passages with 4 changes in direction of airflow (Fig. 7). These are more appropriate for forced-draught units where it is necessary to direct the hot, wet discharge air away from the air intake. Panels which employ a honeycomb structure of curved passages - these have a rather high-pressure drop. In hot climates or regions of strong sunshine the UV resistance of plastic eliminators on the top of forceddraught units is normally a concern to the end-user. It is normal to employ a strong, dark pigmentation of the PVC used tot tower fill and eliminators in order to provide UV resistance (as suggested in Cooling Tower Institute guidelines). High temperature PVC is best coloured white, using Titanium Dioxide, which provides increased UV resistance and of course more heat is reflected instead of absorbed. [Waste not want not; The Chemical Engineer 1999]. Air inlet louvres The PVC panel type of air inlet louvre is derived from a structure equivalent to half an eliminator panel, suitably reinforced, and is designed for induced-draught cooling towers on which it serves four purposes: Prevention of the suction of objects such as leaves from the surroundings into the tower. Elimination of water splash discharge from the pan. Smoothing of the entering airflow. Shading of the pan water and consequent discouragement of the possible growth of algae or other microorganisms. It represents a very efficient replacement from grilles and profile structures on small aria medium-sized towers and is quickly fitted using a simple support frame. CONCLUSION Summer heat can cause indoor conditions to become much hotter than desired. Evaporative cooling is one way to reduce temperatures inside buildings. As water evaporates, it absorbs energy from the surrounding

10 environment. A well-maintained ventilation system with evaporative cooling can reduce incoming air temperature by 5 to 10 C. Cooler indoor temperatures can improve the environment for plants and animals, plus significantly improve working conditions for employees. Evaporative cooling systems lower air temperature using mists, sprays, or wetted pads. Introducing water into ventilation air increases relative humidity while lowering the air temperature. For HVAC systems a new technology is presented which involves adiabatic humidification and cooling of air with supplementary heat exchange facilities to lower final air temperature and reduce relative humidity. This is the coolheart system from Comfort Air which has resulted in refrigerant tree air coolers with very low energy consumption. The main advantages of the system are: Significant reductions in energy consumption compared to normal air conditioning. No refrigerant circuit and no compressor energy required. Low cost, simple units for easy assembly even in areas with limited industrial facilities. Easy installation and service by ventilation personnel. Possibility of application on mobile units without additional power. Modifications of the standard cooling tower have been presented, the principle behind a wet-dry hybrid version has been shown and it is generally considered that the dry section of the cooling tower is primarily for plume control. The most cost-effective solution for a particular installation depends substantially upon the importance of reducing water consumption. In that case the cooling tower has the basic form shown in Fig. 2. The dry section provides warm, dryer air to be mixed with very humid warm air from the evaporative cooling tower lower section. This reduces or eliminates plume formation when the discharge air comes in contact with cooler ambient air above the fan. In the context of industrial plant in hot climates, where water consumption is a critical factor, it is appropriate to concentrate on the quantity of pre-cooling of the entering warm water that can be achieved in the dry section. Dry cooling should be maximised throughout the year. At the design stage the alternatives should be carefully considered, according to the prevailing ambient conditions and "oversized" coils may be the appropriate option. The authors do not recommend the use of open plastic fill-type heat exchangers for the dry section because of their lower heat transfer by conduction and lack of extended surface, which make them unsuitable for maximising dry cooling. These are an interesting idea for cooler climates where the need to reduce the cost of the heat exchanger support structure exists. REFERENCES 1. Cooling tower maintenance manuals drawn-up by the author in accordance with the requirements of the EEC Machinery Directive. 2. Blackadder D.A. & Nedderman R.M. A Handbook of Unit Operations Ch.6-- Academic Press. 3. Foster R.E. (New Mexico State University) Air Conditioning with Evaporative Technology: Economical and Environmental Advantages - Italian translation in Industria & Formazione - March Personal correspondence with Corafort Air b.v., Zwolle, The Netherlands. 5. Personal correspondence with Tower Components of New Jersey (USA). 6. ASHREA Handbook Ch EUROFILL Literature Fill Media & Droplet Eliminators. 8. Johnson T. -PowerGen Plastic Packings for Large Cooling Towers, - The Chemical Engineer Waste not want not - Contract News - The Chemical Engineer

Operation & Maintenance of Cooling Tower

Operation & Maintenance of Cooling Tower Operation & Maintenance of Cooling Tower 1 Contents Basic of Cooling Towers Types of Cooling Tower Preparation for Startup Startup Cooling Tower Caution During Operation Water Quality Maintenance & Control

More information

How about Savings in Time, Money, Energy and Longer Life?

How about Savings in Time, Money, Energy and Longer Life? Chapter 17: The Value of Maintaining Evaporative Cooling Equipment 97 The Value 17 of Maintaining Evaporative Cooling Equipment 1. Cooling Tower Maintenance and Upgrades... What s in it for You? How about

More information

Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs

Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs Alfa Laval Wet Surface Air Coolers (WSAC ) FAQs Q: How is the WSAC a closed-loop cooling system? A: The WSAC is a closed-loop cooling system because the process loop being cooled is inside the tube bundles

More information

EqUIPMENT LAYOUT MANUAL

EqUIPMENT LAYOUT MANUAL Bulletin 311-E Metric NEW! EqUIPMENT LAYOUT MANUAL For Cooling Towers, Evaporative Condensers, Closed Circuit Coolers Reduced Clearance Dimensions with EVAPCO Induced Draft Counterflow Products 3 Table

More information

What is Cooling S.Sen

What is Cooling S.Sen What is Cooling Tower @ S.Sen Gear Box Stack Shaft Fan Blade Motor Fill Theory of Cooling Towers Cooling towers fall into two main sub-divisions: natural draft and mechanical draft. Natural draft designs

More information

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers Equipment Layout Manual For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers for LIFE Equipment Layout Manual Table of Contents Introduction Introduction... 2 Induced Draft Counterflow Unit

More information

Closed Circuit Cooling Towers

Closed Circuit Cooling Towers VFL - C 35 Closed Circuit Cooling Towers Product Detail VFL Closed Circuit Cooling Tower... C36 Benefits... C38 Construction Details... C40 Custom Features and Options... C41 Accessories... C43 Engineering

More information

Fibreglass reinforced polyester (FRP) water collection basin with sloping base and smooth internal finish with rounded corners for easy cleaning.

Fibreglass reinforced polyester (FRP) water collection basin with sloping base and smooth internal finish with rounded corners for easy cleaning. 1 3 2 4 5 Closed Circuit Cooling Tower Factory Assembled - Modular Compact Design 1 IP56 Motor(s) directly coupled to low energy and high efficient fan(s) 2 Fibreglass reinforced polyester (FRP) sandwich

More information

Mr. GoodTower Service Center

Mr. GoodTower Service Center GTSC-E 0615 Mr. GoodTower Service Center Specialists in Replacement Parts and Maintenance of Evaporative Cooling Equipment Call now for a free inspection on your Evaporative Cooling equipment to: Extend

More information

lmprovin Industrial Refrigeration -!nergy Efficiency

lmprovin Industrial Refrigeration -!nergy Efficiency lmprovin Industrial Refrigeration -!nergy Efficiency R efvigeration systems consume a large portion of the total energy used in food processing and food storage industries. There are a number of simple

More information

Layout. Guidelines11. Chapter 11: Layout Introduction

Layout. Guidelines11. Chapter 11: Layout Introduction Guidelines11 Chapter 11: Layout 37 Layout 1. Introduction Open circuit cooling towers, closed circuit cooling towers and evaporative condensers all depend upon an adequate supply of fresh, ambient air

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

Appendix 13. Categories of Cooling and Heating systems

Appendix 13. Categories of Cooling and Heating systems EcoShopping - Energy efficient & Cost competitive retrofitting solutions for Shopping buildings Co-funded by the European Commission within the 7 th Framework Programme. Grant Agreement no: 609180. 2013-09-01

More information

Engineering Specifications for HXV Closed Circuit Hybrid Cooling Tower

Engineering Specifications for HXV Closed Circuit Hybrid Cooling Tower Engineering Specifications for HXV Closed Circuit Hybrid Cooling Tower 1.0 Closed Circuit Hybrid Cooling Tower 1.1 General: Furnish and install, as shown on the plans, factory-assembled closed circuit

More information

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction: Refrigeration Systems Theoretical hours: 2 Practical hours: 2 Units: 6 COOLING TOWERS First 10 minutes: review the last lecture. Then explain the new lecture, solve an example. Last 10 minutes review the

More information

How Much Energy is Really Being Wasted?

How Much Energy is Really Being Wasted? 310 2. CHILLER PLANT MEASURE 2.4.6 Avoid recirculation of air through the same or adjacent heat rejection units. RATINGS New Facilities Retrofit O&M A C The way a heat rejection unit is installed may cause

More information

MECHANICAL SERVICES 101. Ian White

MECHANICAL SERVICES 101. Ian White MECHANICAL SERVICES 101 Ian White Contents 1. Ventilation 2. Heat Gains & Losses 3. Heating Ventilation Air Conditioning (HVAC) Systems What are Building Services Building Services incorporate all aspects

More information

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way 1 CHAPTER I INTRODUCTION In the modern life, electronic equipments have made their way in to practically every part, which is from electronic gadgets to high power computers. Electronic components have

More information

Optimize Evaporative Cooler

Optimize Evaporative Cooler Frequently Asked Questions and Answers Contents regarding the Optimize Evaporative Cooler Technical 1 General Questions, Cooling Potential and Cooling Efficiency 2 Air velocity and pressure loss 3 Erection

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES UNIT OBJECTIVES 3/22/2012 SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

POWER TOWER SERIES Fiberglass Construction 45 to 540 Tons

POWER TOWER SERIES Fiberglass Construction 45 to 540 Tons Temperature Control Units Water & Oil 0-500 F Portable Chillers Air & Water-Cooled 0-70 F Central Chillers Air & Water-Cooled Packages & Modules 0-70 F Pump Tank Stations Chilled or Tower Water 00-00 gallons

More information

Evaporative Cooling. HEVAC Association. Humidity Group. an alternative and supplement to mechanical cooling

Evaporative Cooling. HEVAC Association. Humidity Group. an alternative and supplement to mechanical cooling Evaporative Cooling an alternative and supplement to mechanical cooling HEVAC Association Humidity Group 1. WHAT IS EVAPORATIVE COOLING? Evaporative Cooling is one of the oldest cooling systems known to

More information

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT

ETA ACCU 90% HIGHEST EFFICIENCY AIR HANDLING UNIT 90% EFFICIENCY HIGHEST EFFICIENCY AIR HANDLING UNIT Packaged energy recovery solutions for Green Buildings Integrated Accumulator, controls and DX Cooling System CLEAN AIR SINCE 1963 Euroclima is a company

More information

CTI Sponsored Educational Program

CTI Sponsored Educational Program Presented By: Kent Martens SPX Cooling Technologies, Inc. Slide No.: 1 CTI Mission Statement To advocate and promote the use of environmentally responsible Evaporative Heat Transfer Systems (EHTS) for

More information

VTL Open Cooling Towers... B98. Benefits... B100. Construction Details... B102. Custom Features and Options... B103. Accessories...

VTL Open Cooling Towers... B98. Benefits... B100. Construction Details... B102. Custom Features and Options... B103. Accessories... . - B 97 Product Detail... B98 Benefits... B100 Construction Details... B102 Custom Features and Options... B103 Accessories... B Engineering Data... B107 Structural Support... B111 Engineering Specifications...

More information

HVAC Water chiller selection and optimisation of operation

HVAC Water chiller selection and optimisation of operation HVAC Water chiller selection and optimisation of operation Introduction Water-chiller is a broad term describing an overall package that includes an electrical control panel, refrigeration plant, water

More information

The Industrial water cooling specialists WWW.TOTALPROCESSCOOLING.CO.UK CHILLERS TPC Chillers (Air Cooled Industrial Process Chillers, Oil Chillers and Packaged Chillers) with capacities from 1kW upwards

More information

Closed Circuit Cooling Towers

Closed Circuit Cooling Towers Closed Circuit Cooling Towers Overview Closed circuit cooling towers provide evaporative cooling for many types of systems, and the specific application will largely determine which BAC Closed Circuit

More information

Air Conditioning Inspections for Buildings Condensers

Air Conditioning Inspections for Buildings Condensers . Air Conditioning Inspections for Buildings Condensers PRESENTED BY NIRAJ MISTRY aircon@stroma.com Condensers Condensing Process Three main types: Air Cooled (using ambient air) Water Cooled (using mains,

More information

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING Sample Questions and Answers CHAPTER 5 EVAPORATORS 1. What is Evaporator? Classify the various types of evaporator. Evaporator

More information

Series 5000 Industrial Modular Cooling Tower. Series 5000 Cooling Tower. engineering Data

Series 5000 Industrial Modular Cooling Tower. Series 5000 Cooling Tower. engineering Data Series 5000 Industrial Modular Cooling Tower Table Of Contents B9 Series 5000 Cooling Tower B41 Structural Support B15 Construction Details B43 alternative Structural Support B17 Custom Features & Options

More information

SNOWCOOL SYSTEMS INDIA PVT LTD.

SNOWCOOL SYSTEMS INDIA PVT LTD. SNOWCOOL SYSTEMS INDIA PVT LTD. PRESENTS LARGEST RANGE OF AIR-COOLED FAN FLUID COOLERS CAPACITIES FLUID FLOW 2 CMH TO 20000 CMH HOT FLUID 35 C TO 195 C CONSTRUCTION VERTICAL OR FLAT BED MONO OR MULTI CELLS

More information

Evaporative Condensers

Evaporative Condensers VXC - E 13 Evaporative Condensers Product Detail VXC Evaporative Condensers... E14 Benefits... E16 Construction Details... E18 Custom Features and Options... E20 Accessories... E22 Engineering Data...

More information

What is a Closed circuit Cooling Tower (CCT)?

What is a Closed circuit Cooling Tower (CCT)? What is a Closed circuit Cooling Tower (CCT)? Closed circuit Cooling Towers are hybrids that pass the working fluids through a tube bundle, upon which clean water is sprayer and a faninduced draft applied.

More information

Hot-dip galvanising lines use cold rolled steel strip

Hot-dip galvanising lines use cold rolled steel strip Strip cleaning technology Hot dip galvanising lines require the base strip to be ultra clean to ensure the coatings adhere properly and perform well in service. Conventional high efficiency SMS DEMAG strip

More information

Cooling Towers. Energy-efficient solutions for open circuit, closed circuit and double-cell cooling towers.

Cooling Towers. Energy-efficient solutions for open circuit, closed circuit and double-cell cooling towers. ENGIE Refrigeration supplies the right cooling for every process: from efficient chillers and modular re-cooling systems to turnkey solutions such as refrigeration containers or modules. Efficiency, sustainability,

More information

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. HVAC Math The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb. Math F. to C. Conversion = (f-32)*(5/9) C. to F. Conversion = C * 9/5 +

More information

Refrigeration Systems and Accessories

Refrigeration Systems and Accessories As with the Chapter Review Tests and the Final Exam, the tests your understanding of the materials underlying the learning objectives. After you ve reviewed your answers to the Chapter Review Tests, try

More information

TOPAZ ADIABATIC COOLER

TOPAZ ADIABATIC COOLER TOPAZ ADIABATIC COOLER CONTENT Page Principle and operation 2 General description and benefits 3 TECHNICAL DOCUMENTATION Manufacturing details Options 4 6 Drawings and dimensions 7 On site lay out 8 Technical

More information

Evaporative Cooling products

Evaporative Cooling products user manual Evaporative Cooling products OPERATION - MAINTENANCE Z0582995_A ISSUED 06/2017 READ AND UNDERSTAND THIS MANUAL PRIOR TO OPERATING OR SERVICING THIS PRODUCT general information Note Recold

More information

Maintain. a TOWER of POWER. Part One How to. Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently

Maintain. a TOWER of POWER. Part One How to. Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently Part One How to Maintain a TOWER of POWER Don t let out of site, out of mind prevent you from keeping cooling towers running efficiently BY GLENN A. BABCOCK The cooling tower is often the forgotten component

More information

SNOWCOOL SYSTEMS INDIA PVT LTD.

SNOWCOOL SYSTEMS INDIA PVT LTD. SNOWCOOL SYSTEMS INDIA PVT LTD. PRESENTS LARGEST RANGE OF COOLING TOWERS CAPACITIES WATER FLOW 10 CMH TO 100000 CMH HOT WATER 35 C TO 85 C CONSTRUCTION FRP & RCC SINGLE & MULTIPLE CELLS CUBICAL & HYPERBOLIC

More information

Baltimore Aircoil RCF CLOSED CIRCUIT COOLING TOWERS. ...because temperature matters COUNTERFLOW INDUCED DRAFT

Baltimore Aircoil RCF CLOSED CIRCUIT COOLING TOWERS. ...because temperature matters COUNTERFLOW INDUCED DRAFT CLOSED CIRCUIT COOLING TOWERS COUNTERFLOW INDUCED DRAFT GENERAL DESCRIPTION: Commercial applications demand reliable, cost effective and energy efficient solutions. With an ever increasing focus on operational

More information

Service Step by Step Trouble-Shooting Check-List

Service Step by Step Trouble-Shooting Check-List WARNING: Only Data Aire trained technician or experience technicians should be working on Data Aire Equipment. Protect yourself at all times and work safe. Date: Dates at the job site: From: to Job#: Serial#:

More information

COMPANY PRESENTATION

COMPANY PRESENTATION Date: 16/01/07 Rev.: 0 edition: 1 Mod. 030 Page 1 of 8 1. GENERAL INFORMATION Company designation: M.I.T.A. S.r.l. Company offices & factory: I 27010 SIZIANO (PV) Via Antonio M. Fontana, 1 Legal address:

More information

Softcool evaporative cooling

Softcool evaporative cooling 2014US - 4.1 Softcool Softcool evaporative cooling Contents Page 2 3 6 7 Contents Softcool description Description of the design and function Use of rainwater Engineering information POLYBLOC USA - Lancaster,

More information

Open Cooling Tower. Equipment Layout Guide

Open Cooling Tower. Equipment Layout Guide Open Cooling Tower Forced Draft and Induced Draft Equipment Layout Guide COMPRESSED SYSTEM COMPONENTS INGERSOLL- TABLE OF CONTENTS Introduction.2 Forced Draft Unit Layout Single Units...3-5 Multiple Units

More information

Cold Weather Operation Of Cooling Towers

Cold Weather Operation Of Cooling Towers This article was published in ASHRAE Journal, March 2014. Copyright 2014 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Refrigeration air dryer

Refrigeration air dryer Principle of refrigeration air dryer Pneumatic circuit (System diagram) Warm wet water is precooled by compressed air chilled and dehumidified by air balancer (A) (precooler). Precooled compressed air

More information

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

12 In Row. Installation Manual. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc. MISSION CRITICAL Air Conditioning Systems 12 In Row Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents Table of Contents... 3 Site

More information

CONDAIR ME. In-duct evaporative humidifier and cooler Very low energy operation. Humidification and Evaporative Cooling

CONDAIR ME. In-duct evaporative humidifier and cooler Very low energy operation. Humidification and Evaporative Cooling CONDAIR ME In-duct evaporative humidifier and cooler Very low energy operation Humidification and Evaporative Cooling Evaporative module Mains or RO treated water is pumped to the top of the evaporative

More information

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING

MODULE 6 HUMIDIFICATION AND AIR CONDITIONING MODULE 6 HUMIDIFICATION AND AIR CONDITIONING LECTURE NO. 3 6.3 Humidification and dehumidification operations and design calculations Humidification operations: In this operation, water transfers from

More information

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION

TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION TECHNICAL BULLETIN SELECTING A COMPRESSED AIR DRYER INTRODUCTION Having an understanding of why water forms in your compressed air piping system will help you in evaluating the type of air drying system

More information

CONTENTS. B. System Design and Performance Requirements

CONTENTS. B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

LSFG-8 LOW SOUND & SLSFG-10 SUPER LOW SOUND TOWER FEATURES

LSFG-8 LOW SOUND & SLSFG-10 SUPER LOW SOUND TOWER FEATURES The Leaders in All-Fiberglass Cooling Towers REYMSA s success is the result of 35 years of experience in cooling towers. We have been putting ideas into action by researching and developing the latest

More information

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India

System-CoolAC. Bharatividyapeeth College of Engineering, Deekshant Bharti Scholar, New Delhi, India A Novel Design of Low Cost Domestic Cooling System-CoolAC Abhishek Gandhar Associate Prof., abhishek.gandhar@gmail.com Deekshant Bharti bravo9421@gmail.com Aditya Jain adityajn710@gmailcom Shiv Wadhwa

More information

SUPERCHILL Australia Pty Ltd

SUPERCHILL Australia Pty Ltd SUPERCHILL Australia Pty Ltd MODUPOL - Best Quality - Guaranteed Performance - Fibreglass Construction - Corrosion Proof - Compliance with AS3666 - All Applications - Made in Australia - Superchill is

More information

Optimal work climate with open doors. Industrial air curtains Model IndAC

Optimal work climate with open doors. Industrial air curtains Model IndAC Optimal work climate with open doors Industrial air curtains Model IndAC Industrial air curtain Optimal work climate During loading and unloading the door remains open, without the indoor climate being

More information

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers OM010 Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers The operating and maintenance instructions contained within this package are for ThermaFlex gasketed

More information

Series 6, Vertical Floor-Mount Units

Series 6, Vertical Floor-Mount Units MISSION CRITICAL Air Conditioning Systems Series 6, Vertical Floor-Mount Units Installation Manual ClimateWorx International Inc. 14 Chelsea Lane, Brampton, Ontario, Canada L6T 3Y4 2 Table of Contents

More information

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly.

All series is using Hitachi scroll compressor, low vibration and high efficiency. Internal thermostat embedded compressors, and it can react quickly. HITACHI proudly presents to our customers this wide range of split system air conditioners, from 4HP to 20 HP which is designed for high and medium outdoor temperature and comply with almost any types

More information

Drying principles and general considerations

Drying principles and general considerations Drying principles and general considerations Drying Mechanisms In the process of drying heat is necessary to evaporate moisture from the grain and a flow of air is needed to carry away the evaporated moisture.

More information

Products and Services

Products and Services Products and Services Evaporative Cooling HVAC Refrigeration Light to heavy industrial Chemical processing, refining Power generation MARLEY NC EVEREST CROSSFLOW COOLING TOWER NC Everest s preassembled

More information

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012 HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O INTRODUCTION HVAC systems or Heating, Ventilating and Air-Conditioning systems control the environment for people and equipment in our facilities.

More information

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier

Installation Guide. Dehumidification. Fresh Air Ventilation. Compact Size. Energy Efficient. RXID-AW90A Whole House Dehumidifier RXID-AW90A Whole House Dehumidifier with fresh air ventilation Installation Guide Dehumidification Fresh Air Ventilation Compact Size Energy Efficient The whole house dehumidifier integrates highcapacity

More information

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010 Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010 Calorifiers Heat Exchangers Pressurisation Units Sales Tel: 01457 835700 Sales Fax: 01457 832700 E-mail:

More information

NEWIN Centrifual Fan Forced Draft Cooling Tower Product Introduction

NEWIN Centrifual Fan Forced Draft Cooling Tower Product Introduction Product Introduction NCF series centrifugal fan forced draft cooling tower is a type of cooling tower designed to protect the environment from our years of cooling tower equipment design, production, operation,

More information

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made.

Press Release. How can the efficiency of the dryer section be increased? Dryer Section All Paper Grades. Heimbach wherever paper is made. Dryer Section All Paper Grades Press Release How can the efficiency of the T. Bock (Dipl.-Ing.), Manager Application & Technical Service, Heimbach GmbH & Co. KG, thomas.bock@heimbach.com I. Durniok (Dipl.-Ing.),

More information

WCD-1. Evaporative Cooling Modules. WCD Series. Alton. Keeps You. Cool

WCD-1. Evaporative Cooling Modules. WCD Series. Alton. Keeps You. Cool WCD-1 Evaporative Cooling Modules WCD Series Alton Keeps You Cool TURBOCELL WCD SERIES EVAPORATIVE COOLING MODULES THE LATEST IN COOLING TECHNOLOGY In many types of industries where efficient, low-cost

More information

DISTRIBUTION SYSTEMS. Water Piping and Pumps

DISTRIBUTION SYSTEMS. Water Piping and Pumps DISTRIBUTION SYSTEMS Water Piping and Pumps Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted

More information

NEW GENERATION INTELLIGENT CHILLER BOOSTER, ADIABATIC PRE-COOLING SYSTEM

NEW GENERATION INTELLIGENT CHILLER BOOSTER, ADIABATIC PRE-COOLING SYSTEM NEW GENERATION INTELLIGENT CHILLER BOOSTER, ADIABATIC PRE-COOLING SYSTEM H Y BRID COOLING Reduce chiller energy consumption by up to 37 % Increase chiller cooling capacity by up to 41% Achieve 100% protection

More information

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section. SECTION 15855 GAS FURNACE/DX COOLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of contract including General and Supplementary Conditions of Division 1 of Specification

More information

Evaporative Condensers

Evaporative Condensers J2 BAC offers evaporative condensers in six different styles to suit every industry application. CXV Models - CXV models deliver efficient performance in an easy-to-maintain package. BAC s combined flow

More information

The SMART COOLING adiabatic precooling panels will reduce up to 30% of your cooling systems energy consumption!

The SMART COOLING adiabatic precooling panels will reduce up to 30% of your cooling systems energy consumption! The SMART COOLING adiabatic precooling panels will reduce up to 0% of your cooling systems energy consumption! 1. System operation The SMART COOLING panel system increases the efficiency of the air-cooling

More information

Presenters. Brett Alexander. Mihir Kalyani. Troy Reineck

Presenters. Brett Alexander. Mihir Kalyani. Troy Reineck ow Brett Alexander Presenters Mihir Kalyani Troy Reineck Designing Your Water Treatment Program for Different Types of Heat Rejection Equipment Types of Heat Rejection Equipment Open Cooling Tower Closed

More information

Customers. The core of our innovation. Feeding&Conveying. Drying Dosing Temperature Control Refrigeration Granulation

Customers. The core of our innovation. Feeding&Conveying. Drying Dosing Temperature Control Refrigeration Granulation EN Customers. The core of our innovation Feeding&Conveying Drying Dosing Temperature Control Refrigeration Granulation Piovan Drying Technologies: Desiccant Bed Dryers Dried air is generated by means of

More information

Oxyvap Evaporative Cooling Applications

Oxyvap Evaporative Cooling Applications Oxyvap Evaporative Cooling Applications Oxycom Fresh Air BV March 9th, 2015 Abstract This paper shows two highly efficient applications of the Oxyvap direct evaporative cooling technology, developed by

More information

Chapter-8 Capacity Control of Refrigeration Systems

Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems Chapter-8 Capacity Control of Refrigeration Systems ၈.၁ Compressor Control Chiller Control and Chilled Water Plant Control Refrigeration system control

More information

R07. Answer any FIVE Questions All Questions carry equal marks *****

R07. Answer any FIVE Questions All Questions carry equal marks ***** Set No: 1 III B.Tech. II Semester Supplementary Examinations, April/May 2013 REFRIGERATION AND AIR CONDITIONING (Mechanical Engineering) Time: 3 Hours Max Marks: 80 Answer any FIVE Questions All Questions

More information

DIVISION 15 MECHANICAL

DIVISION 15 MECHANICAL DIVISION 15 MECHANICAL A. GENERAL DESIGN CONDITIONS 1. Design occupied spaces to maintain 72 F and a space dew point temperature not to exceed 55 F. 2. Design classroom and office space buildings with

More information

Performance Optimization of the Evaporative Condenser Design

Performance Optimization of the Evaporative Condenser Design Performance Optimization of the Evaporative Condenser Design Mit. C. Patel P.G.Student, Mech. Engg.Dept. Institute of Technology, Nirma University, Ahmadabad, Prof. B. A. Shah Mechanical Engineering Department

More information

Air Handling Units. Real HVACR people who understand your needs.

Air Handling Units. Real HVACR people who understand your needs. Air Handling Units Real HVACR people who understand your needs. Copyright HC Heat-Exchangers (PTY) Ltd. 1 Copyright HC Heat-Exchangers (PTY) Ltd. 2 About the HC AHU range HC Heat-Exchangers rich engineering

More information

EXCELSIOR SINHGAD COLLEGE OF ENGINEERING, PUNE PAPER PRESENTATION

EXCELSIOR SINHGAD COLLEGE OF ENGINEERING, PUNE PAPER PRESENTATION EXCELSIOR SINHGAD COLLEGE OF ENGINEERING, PUNE PAPER PRESENTATION ON SOLAR CHIMNEY BY MALAV R. MEHTA ANUJ K. SADANI (3 RD YEAR CMPS) (3 RD YEAR IT) GCOE AMRAVATI GCOE AMRAVATI E-MAIL:malav123_mehta@rediffmail.com

More information

Cooling Tower Designs

Cooling Tower Designs 2014 Service Technician Training Program Cooling Tower Designs Daniel S. Krack, CWT 2 Cooling Towers 1 Water Cooled Systems More Efficient than Air Cooled 40-60 % Higher COP than Air Cooled Lower Condensing

More information

SPRAY ADIABATIC SYSTEM HYBRID SPRAY SYSTEM (H.S.S.) - OPEN CIRCUIT. Compliant with VDI 2047 Part 2 +30% LOW. Under approval.

SPRAY ADIABATIC SYSTEM HYBRID SPRAY SYSTEM (H.S.S.) - OPEN CIRCUIT. Compliant with VDI 2047 Part 2 +30% LOW. Under approval. SPRAY ADIABATIC SYSTEM HYGENIC CERTIFICATION Compliant with VDI 2047 Part 2 RELATIVE HUMIDITY INCREASE +30% LOW Inlet air humidification system through water atomisation. A very thin water mist generated

More information

NEW GENERATION INTELLIGENT ADIABATIC PRE-COOLING SYSTEM

NEW GENERATION INTELLIGENT ADIABATIC PRE-COOLING SYSTEM NEW GENERATION INTELLIGENT ADIABATIC PRE-COOLING SYSTEM HYBRID COOLING Reduce chiller energy consumption by up to 37 % Increase chiller cooling capacity by up to 41% Achieve 100% protection for the condensers

More information

Tuning up ventilation systems

Tuning up ventilation systems MULTI-UNIT RESIDENTIAL BUILDINGS Tune-Ups for Energy and Water Efficiency This document is a tool to help reduce energy and water costs and improve comfort in a high-rise residential building through low-cost

More information

Armstrong Cool-Fog Systems

Armstrong Cool-Fog Systems Armstrong Cool-Fog Systems Armstrong International, Inc. is a leading supplier of hydropneumatic fogging systems used for both humidification and evaporative cooling. Its systems were first developed in

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Installation and maintenance manual. Open type cooling tower. Axial type. Series TAA

Installation and maintenance manual. Open type cooling tower. Axial type. Series TAA Installation and maintenance manual Open type cooling tower Axial type Series TAA W-Tech S.r.l. Via Cartiera 90/A - 40037 Sasso Marconi - (BO) Italy T: +39 051 6783010 F: +39 051 6784941 info@w-tech.it

More information

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark Introduction: Energy use is the single largest operating expense in commercial office

More information

AN ENVIRONMENT FRIENDLY COOLING OPTION

AN ENVIRONMENT FRIENDLY COOLING OPTION AN ENVIRONMENT FRIENDLY COOLING OPTION Manoj Arya* 1, Anoop Arya and S.P.S. Rajput 2 1. Deptt. of Mechanical Engg. M.A.N.I.T. Bhopal (INDIA) 2. Deptt. of Electrical Engg. M.A.N.I.T. Bhopal (INDIA) * Email:

More information

Eliminating Condensation and Resulting Corrosion. Sulphur Tail Gas and De-Gas Lines

Eliminating Condensation and Resulting Corrosion. Sulphur Tail Gas and De-Gas Lines Eliminating Condensation and Resulting Corrosion In Sulphur Tail Gas and De-Gas Lines By David R. Hornbaker, Controls Southeast, Inc. and Graham M. MacPherson, P.Eng., Millenia Resource Consulting Abstract

More information

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University

AND AIR-CONDITIONING. Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING Dr Ali Jawarneh Department of Mechanical Engineering Hashemite University 2 Objectives Differentiate between dry air and atmospheric air. Define and calculate

More information

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer

A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer A Design for True Performance and Energy Savings In Refrigerated Compressed Air Dryers The Digital Scroll Dryer Introduction By Timothy J. Fox, P.E. Hankison, an SPX Brand Canonsburg, Pennsylvania Refrigerated

More information

CROSSFLOW REPLACEMENT FILL KITS. Replacement Fill Kits Specifically Designed for All Types of Crossflow Cooling Towers (BAC, Marley, etc.

CROSSFLOW REPLACEMENT FILL KITS. Replacement Fill Kits Specifically Designed for All Types of Crossflow Cooling Towers (BAC, Marley, etc. CROSSFLOW REPLACEMENT FILL KITS Replacement Fill Kits Specifically Designed for All Types of Crossflow Cooling Towers (BAC, Marley, etc.) Hanging Verses Pack Hanging fill is installed in some manufacturers

More information

INSTANT CHILLER. Chester-Jensen Co., Inc. Unit Construction and Short Gas Flow

INSTANT CHILLER. Chester-Jensen Co., Inc. Unit Construction and Short Gas Flow Chester-Jensen Co., Inc. INSTANT CHILLER COOLANT RETURN FROM PROCESS Chilling water instantly and continuously to 33ºF presents no problem to the user of a Chester-Jensen Chiller. Other liquids, brine,

More information

Air-Handling System Cooling Options

Air-Handling System Cooling Options Air-Handling System Cooling Options High-Capacity, Economical Evaporative Cooling High-Efficiency, DX & CW Mechanical Cooling Pure and Simple Solutions AbsolutAire Air-Handling System Cooling Options Economical

More information

Vibration Of Cooling Tower Fans. Barry T. Cease Cease Industrial Consulting Vibration Institute 2015

Vibration Of Cooling Tower Fans. Barry T. Cease Cease Industrial Consulting Vibration Institute 2015 Vibration Of Cooling Tower Fans Barry T. Cease Cease Industrial Consulting Vibration Institute 2015 ceasevibration@icloud.com (843) 200-9705 1 WHAT IS A COOLING TOWER AND WHAT DOES IT DO? All cooling towers

More information

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS Chainarong Chaktranond *, and Peachrakha Doungsong Department of Mechanical Engineering, Faculty of Engineering,

More information