INDIRECT GAS-FIRED AIR HEATER

Size: px
Start display at page:

Download "INDIRECT GAS-FIRED AIR HEATER"

Transcription

1 INDIRECT GAS-FIRED AIR EATER DG() SERIES INDOOR/OUTDOOR INSTALLATION MANUFACTURED BY

2 TABLE OF CONTENTS Description... Applications... Selection criteria... Installation guidelines... Selection table...7 Dimensions Models DG() 20 to... 8 Models DG() 7 to Models DG() 2 to Models DG() 20 to... Models DG() to Models DG() 2 to 2... Models DG() 0 to Roof curbs dimensions...8 Weight table...9 Options Remote control panel (optional)... 2 Gas piping... Characteristics...23 Typical specifications...2 Warranty...27 The features, illustrations and description in this document were, to our knowledge, accurate at the time they were approved for printing. We reserve the right to change or stop offering some features as well as stop producing a given model without prior notice and commitment on our part. 3

3 DESCRIPTION The DG() indirect gas-fired air heaters manufactured by BOUSQUET are certified for both indoor and outdoor installation and designed to serve as a heating system for make-up air or recirculated air. They operate with a minimum thermal efficiency of % and use natural or propane gas. The capacities available range from 200 to 00 MB (from 9 to kw) and from 000 to,000 SCFM (from 888 to 2,7 l/s) of air at temperature differences of F to 20 F (from C to C), which enables flexibility of use for multiple applications. The multiple pass heat exchanger comprises a primary drum and secondary tubes made of series L stainless steel requiring no thermal treatment to prevent the cracking of welded joints. In addition, series L stainless steel is known for its great resistance to corrosion and high temperatures, which increases the service life of the unit. The exchanger is equipped with access panels for the inspection and cleaning of the tubes. It is installed as to enable the thermal expansion that occurs during the heating cycles of the unit. The forced combustion air and high gas modulation burner with a 20: turndown ratio offers optimal heat transfer on all the surfaces of the exchanger while maintaining optimal combustion efficiency through the entire range of capacity. The heavy duty base frame of the unit is made of structural type U-shaped channels. The walls and roof are made of 8 gauges G galvanized steel panels with double folded longitudinal edges. The single wall units are insulated with a one-inch anti-bacterial Fiber Glass Duct Liner with Reinforced Coating. The exchanger section is double wall insulated with two inches high temperature Fiber Glass Blanket.lb/pi 3 density, and covered with a gauge G galvanized steel liner. The weatherproof control cabinet has one large access door to allow for the maintenance of the gas piping and electrical components. The exterior surfaces of the unit are treated with a phosphate cleaner-conditioner and covered with a synthetic Chromating Phosphate with anticorrosive primer. The finish is ensured with first quality high performance alkyd resin enamel. When required, a fresh air intake cowl, a mixing box with filters, motorized damper, or downturn or upward discharge plenum may be incorporated into the DG() unit. DG() heaters are C ETL US approved and are certified according to standards CAN/CGA3.2 and UL 79. APPLICATIONS Fresh air compensation with or without recirculation Apartment building corridors Schools ospitals Industries Industrial and commercial warm air heating systems Ventilation unit with cooling, re-circulation and/or economizer cycle

4 SELECTION CRITERIA. Capacity Required CFM External static pressure Required temperature rise Required final air temperature Type of gas 2. Type of installation Indoor Outdoor 3. Control location On the left-hand or right-hand side of the heater (when facing the airflow). Airflow configuration Direction of the airflow (vertical or horizontal) 00% fresh air 00% recirculated air Modulation (recirculated/fresh air). Temperature control Electronic controller with integral temperature sensor Electronic controller for a 0-0 VDC or -20 ma external signal. Remote controls (optional) Basic or deluxe control panel Room thermostat 7. Other options Low limit temperature sensor Air mixture temperature sensor Lighting Power outlets Switches Main power disconnect Gas piping according to FM standard Gas piping according to IRI standard

5 INSTALLATION GUIDELINES The installer of a heater such as the DG() must follow certain rules in order to comply with the codes governing gas equipment. ere are some recommendations: When gas pressure exceeds /2 psig (3.kPa), a high pressure regulator must be supplied and installed by the contractor. This regulator must have the same modulation capability as the burner (20: turndown). Allow for sufficient clearance around the unit to enable its installation and maintenance. For indoor installation, all purge and regulator vents must be individually piped to the exterior according to code CGA-B9 or other codes in effect; the chimney must satisfy the following requirements: have double walls be certified for positive pressure units (type PS) be certified ULC/UL; ensure that there is enough air for the combustion in the room where the heater is installed (refer to code in effect); ensure that the combustion air is clean and free of dust or corrosive material that could reduce the service life of the unit. For chimney and breeching dimensions, consult the manufacturer. For any other information related to the installation of the DG() air heaters, refer to the installation and service manual pertaining to these units.

6 SELECTION TABLE Using the selection table below, choose the DG() heater according to the required airflow and net heating capacity. Model DG() Burner capacity Net capacity Amperage 2 (A) Airflow 3 MB kw MB kw (7/3/) CFM l/s Notes:. Corresponding to the burner and gas piping nominal capacity 2. Amperage required for the burner motor and controls (fan motor not included). For other voltage, consult the manufacturer. 3. For a temperature rise of F to 20 F ( C to C) For less or more CFM, consult the manufacturer.. The DG() 20 and heaters are not certified C ETL in Canada. 7

7 MOTOR ORSEPOWER (P) Model DG() 20 DG() DG() 3 DG() 0 DG() DG() DG() Δ T ( F) Airflow CFM Fan (2) 2-2 (2) External static pressure in inches of water Notes:. Motor brake horsepower does not include the loss caused by pulley and belt friction (add %). 2. Fan with airfoil backward-inclined wheel 3. Internal static pressure includes the static pressure lost through the air intake, dampers, 2-inches filters (%) and heat exchanger. For other fan selections, consult the manufacturer. 8

8 MOTOR ORSEPOWER (kw) Model DG() 20 DG() DG() 3 DG() 0 DG() DG() DG() Δ T ( C) Airflow l/s Fan (2) 2-2 (2) External static pressure in Pa Notes:. Motor brake horsepower does not include the loss caused by pulley and belt friction (add %). 2. Fan with airfoil backward-inclined wheel 3. Internal static pressure includes the static pressure lost through the air intake, dampers, 2-inches filters (%) and heat exchanger. For other fan selections, consult the manufacturer. 9

9 MOTOR ORSEPOWER (P) Model DG() 7 DG() 8 DG() 00 DG() 2 DG() DG() 7 DG() 200 Δ T ( F) Airflow CFM Fan (2) 2-2 (2) - (2) - 2 (2) 2-2 (2) - (2) - 2 (2) - (2) 8-3 (2) - 2 (2) 8-3 (2) 8-8 (2) (2) 8-8 (2) 20- (2) (2) 20- (2) (2) (2) 20- (2) (2) External static pressure in inches of water Notes:. Motor brake horsepower does not include the loss caused by pulley and belt friction (add %). 2. Fan with airfoil backward-inclined wheel 3. Internal static pressure includes the static pressure lost through the air intake, dampers, 2-inches filters (%) and heat exchanger. For other fan selections, consult the manufacturer.

10 MOTOR ORSEPOWER (kw) Model DG() 7 DG() 8 DG() 00 DG() 2 DG() DG() 7 DG() 200 Δ T ( C) Airflow l/s Fan (2) 2-2 (2) - (2) - 2 (2) 2-2 (2) - (2) - 2 (2) - (2) 8-3 (2) - 2 (2) 8-3 (2) 8-8 (2) (2) 8-8 (2) 20- (2) (2) 20- (2) (2) (2) 20- (2) (2) External static pressure in Pa Notes:. Motor brake horsepower does not include the loss caused by pulley and belt friction (add %). 2. Fan with airfoil backward-inclined wheel 3. Internal static pressure includes the static pressure lost through the air intake, dampers, 2-inches filters (%) and heat exchanger. For other fan selections, consult the manufacturer.

11 Model DG() 2 DG() 0 DG() 3 DG() 00 DG() 0 Δ T( F) Airflow CFM Fan (2) (2) - (2) - 2 (2) -20 (2) 2-2 (2) (2) 2-20 (2) -2 (2) - 2 (2) 2-2 (2) - (2) - 2 (2) - (2) (2) MOTOR ORSEPOWER (P) External static pressure in inches of water Notes:. Motor brake horsepower does not include the loss caused by pulley and belt friction (add %). 2. Fan with airfoil backward-inclined wheel 3. Internal static pressure includes the static pressure lost through the air intake, dampers, 2-inches filters (%) and heat exchanger. For other fan selections, consult the manufacturer. 2

12 Model DG() 2 DG() 0 DG() 3 DG() 00 DG() 0 Δ T( C) Airflow l/s Fan (2) (2) - (2) - 2 (2) -20 (2) 2-2 (2) (2) 2-20 (2) -2 (2) - 2 (2) 2-2 (2) - (2) - 2 (2) - (2) (2) MOTOR ORSEPOWER (kw) External static pressure in Pa Notes:. Motor brake horsepower does not include the loss caused by pulley and belt friction (add %). 2. Fan with airfoil backward-inclined wheel 3. Internal static pressure includes the static pressure lost through the air intake, dampers, 2-inches filters (%) and heat exchanger. For other fan selections, consult the manufacturer. 3

13 DIMENSIONS Models DG() 20,, 3, 0, and S U V A PANEL Drain Ø3/8 (7) W K R C K Drain Ø3/8 (0) TO CONTROLS D T PANNEL OUTDOOR MODEL ONLY 3 (7) B E J ØL TO PIPING M Q P BB ( ) mm DIMENSIONS F Gas G N F Drain Ø3/8 (0) Filters in air intake () Filters in V filter section () A B BB C D E F G J K L M N P Q R S T U V W Ø GAS Ø VENT 2,3 Ø PURGE 3 inches (2) x2 (2) 20x2 (2) x2 (2) 20x2 DG() 20 mm (2) 0x3 (2) 8x3 (2) 0x3 (2) 8x3 inches (2) x2 (2) 20x2 (2) x2 (2) 20x2 8 8 DG() mm (2) 0x3 (2) 8x3 (2) 0x3 (2) 8x inches (2) x2 (2) 20x2 (2) x2 (2) 20x2 8 8 DG() 3 mm (2) 0x3 (2) 8x3 (2) 0x3 (2) 8x DG() 0 inches mm () x2 () 20x2 () 0x3 () 8x3 DG() inches mm () x2 () 20x2 () 0x3 () 8x3. With an inlet gas pressure of inches water column (3.kPa) 2. Indoor installation only 3. The purge (IRI option) and regulator vents must be piped separately to the outdoor.. Filter area is calculated for an air flow corresponding to a o F temperature rise (NOT o F).. The length and width of the curb are /2 inch smaller than those of the unit; the curb is 7 inches high.. The controls shown are on the left-hand side of the unit (controls on the right-hand side are also available). 7. For outdoor installation only. DG() inches mm () x2 () 20x2 () 0x3 () 8x / / / / / / / / / / / / /2 2 0-/ / /2 2 0-/ / /2 2 0-/ /

14 DIMENSIONS Models DG(), 7, 8 and 00 S U V A PANEL Drain Ø3/8 (7) W K R C Drain Ø3/8 (0) TO CONTROLS D T PANEL OUTDOOR MODEL ONLY 3 (7) E Ø L B J TO PIPING M Q P BB ( ) mm DIMENSIONS F G Gas Drain Ø3/8 (0) N F Filters in air intake () Filters in V filter section () A B BB C D E F G J K L M N P Q R S T U V W Ø GAS Ø VENT 2,3 Ø PURGE 3 inches () 20x2 (3) 20x20 () 20x2 (3) 20x20 DG() mm DG() 7 inches mm DG() 8 inches mm DG() 00 inches mm () 8x3 () 20x2 () 8x3 (3) 20x20 () 8x8 (3) 20x20 () 8x8 (3) 8x8 (3) 20x20 (3) 8x8 () 20x2 () 8x3 () 20x2 () 8x3 () 8x3 () 20x2 () 8x3 (3) 8x8 (3) 20x20 (3) 8x8 (2) 20x2 (2) 8x3 (2) 20x2 (2) 8x / / 3 7 / / / 3 7 / / /2 0 -/2 2 2-/ /2 / / /2 0 -/2 2 2-/ /2 / With an inlet gas pressure of inches of water column (3.kPa) 2. Indoor installation only 3. The purge (IRI option) and regulator vents must be piped separately to the outdoor.. Filter area is calculated for an air flow corresponding to a o F temperature rise (NOT o F).. The length and width of the curb are /2 inch smaller than those of the unit; the curb is 7 inches high.. The controls shown are on the left-hand side of the unit (controls on the right-hand side are also available). 7. For outdoor installation only.

15 DIMENSIONS Models DG() 2,, 7, 200 and 2 S U V A PANNEL Drain Ø3/8 (7) W K R C Drain Ø3/8 (0) TO CONTROLS D T PANEL OUTDOOR MODEL ONLY 3 (7) E Ø L B E TO PIPING Q BB M P J Gas F ( ) mm DIMENSIONS G Drain Ø3/8 (0) N F Filters in air intake () Filters in V filter section () A B BB C D E F G J K L M N P Q R S T U V W Ø GAS Ø VENT 2,3 Ø PURGE 3 inches () x20 (8) x2 () 20x2 () 20x / DG() 2 mm () 0x8 (8) 0x3 () 8x3 () 8x inches () x20 (8) x2 () 20x2 () 20x / DG() mm () 0x8 (8) 0x3 () 8x3 () 8x inches () x20 (8) x2 () 20x2 () 20x / DG() 7 mm () 0x8 (8) 0x3 () 8x3 () 8x inches (32) x20 (8) x2 (32) x20 (8) x DG() 200 mm (32) 0x8 (8) 0x3 (32) 0x8 (8) 0x inches (32) x20 (8) x2 (32) x20 (8) x DG() 2 mm (32) 0x8 (8) 0x3 (32) 0x8 (8) 0x / /2 / / /2 / / /2 / / /2 / / / With an inlet gas pressure of inches of water column (3.kPa) 2. Indoor installation only 3. The purge (IRI option) and regulator vents must be piped separately to the outdoor.. Filter area is calculated for an air flow corresponding to a o F temperature rise (NOT o F).. The length and width of the curb are /2 inch smaller than those of the unit; the curb is 7 inches high.. The controls shown are on the left-hand side of the unit (controls on the right-hand side are also available). 7. For outdoor installation only.

16 DIMENSIONS Models DG() 0, 3, 00 and 0 S U V AA A PANEL W K R C Drain Ø3/8 (0) Shipped in section DOOR TO CONTROL OUTDOOR MODEL ONLY D PANEL T 2 () E Ø L B E TO PIPING Q BB J M P ( ) mm DIMENSIONS Filters in air intake () Filters in V filter section () A AA B BB C D E F G J K L M N P Q R S T U V W Ø GAS Ø VENT 2,3 Ø PURGE 3 inches () x2 () x20 () x2 () x / /2 F DG() 0 mm () 0x3 () 0x8 () 0x3 () 0x inches () x2 () x20 () x2 () x DG() 3 mm () 0x3 () 0x8 () 0x3 () 0x With an inlet gas pressure of inches of water column (3.kPa) 2. Indoor installation only 3. The purge (IRI option) and regulator vents must be piped separately to the outdoor.. Lenght AA is for heaters with vertical discharge without turn plenum.. Filter area is calculated for an air flow corresponding to a o F temperature rise (NOT o F).. The length and width of the curb are /2 inch smaller than those of the unit; the curb is 7 inches high. 7. The controls shown are on the left-hand side of the unit (controls on the right-hand side are also available). 8. For outdoor installation only. G inches () 20x2 () 20x20 (3) 20x2 (7) 20x Gas Drain Ø3/8 (0) DG() / / / / -/ / / -/ mm () 8x3 () 8x8 (3) 8x3 (7) 8x N inches () 20x2 () 20x20 (3) 20x2 (7) 20x F DG() 0 mm () 8x3 () 8x8 (3) 8x3 (7) 8x

17 ROOF CURB TO PIPING UNIT (ELEVATION VIEW) DOWNTURN PLENUM OPTION ROOF CURB 7 (32) K R K D D F ( ) mm DIMENSIONS U V ROOF CURB (PLAN VIEW) I A AA W A AA C D F I K R U V W DG() 20,, 3 DG() 0,, INCES MM INCES MM 8 - -/2-3/ 3-3/ 3-3/ /2-3/ 3-3/ / -3/ / -3/ / / 7 INCES 8-73-/2-3/ 3-3/ DG(), 7 MM / 2 INCES - 77-/2 8-3/ 2-3/ DG() 8, 00 MM / / -3/ / -3/ / 7 3-3/ 883 DG() 2,, 7 INCES 7-97-/2 8-/ 3-3/ MM INCES /2-3/ -3/ DG() 200, 2 MM / -3/ / -3/ / -3/ / 37-3/ INCES 0 9-/2 8-3/ -3/ DG() 0, 3 MM / 2 INCES /2 8-3/ -3/ DG() 00 MM / / 83-3/ / 9-3/ / 73-3/ 873 INCES /2 8-3/ -3/ DG() 0 MM / -3/ / 9-3/ / 873 8

18 WEIGT TABLE MODEL DG() 20 DG() DG() 3 DG() 0 DG() DG() DG() DG() 7 DG() 8 DG() 00 DG() 2 DG() DG() 7 DG() 200 DG() 2 DG() 0 DG() 3 DG() 00 DG() 0 AIR INTAKE OOD Lb kg FRES AIR WIT RECIRCULATION Lb kg % FRES AIR Lb kg EXCANGER Lb kg PLENUM 2 Lb kg Notes:. This weight includes the V filter section. 2. Optional discharge plenum is used to turn the air flow for either up, down or side discharge. Up and down discharge are also available without the turn plenum. 9

19 OPTIONS Package with Dx Condensing Unit (up to 00 tons) Cooling or Recovery Coils Lighting fixture Annunciator S78A00 Mushroom air intake Display A03 20

20 REMOTE CONTROL PANEL (optional) Basic Panel (0 /2 w x /2 h) Stop/fan/burner selector switch Fan operation light Burner operation light Connecting terminal block Mid-Size Panel (0 /2 w x 0 /2 h) Basic panel Stop/fan/burner selector switch Fan operation light Burner operation light Connecting terminal block Temperature Selector (A3) Deluxe Panel ( 3/8 w x 7 /2 h) Standard equipment: Stop/start/fan selector switch Stop/start/burner selector switch Fan operation light Burner operation light Flame failure light Connecting terminal block Optional equipment: Low limit alarm light Clogged filter light igh gas pressure alarm light Low gas pressure alarm light Until purge cycle completed light Temperature selector (A3) Key lock Deluxe panel Note: Refer to the manufacturer for other arrangement or feature. 2

21 GAS PIPING COMPONENTS PILOT PIPING Manual shut-off valve Gas pressure regulator Automatic shut-off valve Manual ignition cock MAIN BURNER PIPING Pressure regulator Automatic quick-closing shut-off valve Automatic slow-opening and quick-closing shut-off valve Manual ignition cock /8-inch diameter test port Piping union Modulating valve supplied with burner DESCRIPTIONS OPTIONS Low gas pressure switch (required for: FM, IRI and pressure in excess of /2 psig) Normally open automatic vent valve (required for: IRI) igh gas pressure switch (required for: FM, IRI and pressure in excess of /2 psig)

22 CARACTERISTICS STANDARD CARACTERISTICS: C ETL US certified Natural gas GP Combustion forced draft burner eat exchanger with L stainless steel drum and tubes Gas piping for inlet gas pressure of inches of water column (3.kPa) Main power supply (7 volts/3 phases/ cycles) Single point connecting terminal block All the components required for the proper operation of the unit Flame rod detector Pre-purge period Galvanized steel (8 gauge) painted enamel -inch thick reinforced coated filler glass insulation Exchanger section: 2-inch thick ( mm) high temperature insulating material with a density of.lb/ft 3, with a gauge galvanized steel liner Access doors with screw-on knob handles Lifting lugs on both sides of the unit for easy handling and installation Access panel to the exchanger tubes (for cleaning purposes) Drain Burner automatic valve interlock Supply air temperature controller OPTIONAL CARACTERISTICS: Electric power supply (208, volts/3 phases/ cycles) igh gas pressure regulator (for pressure above inches of water column) MAXON burner Propane gas eat exchanger with 3L stainless steel drum and tubes Gas piping to FM or IRI requirement Ultra-violet flame detector Main power supply disconnect with or without fuses Terminal block to interface with a centralized building automation system Modulation controller with 0-0 VDC or -20 ma signal from a central building automation system Room thermostat Maintenance vestibule Maintenance platform Double wall construction (2, 3 or thick) 20-volt electrical outlet Waterproof lighting fixture Space for coils Coils (cooling, heat recovery,...) Note: Refer to manufacturer for any other options. 23

23 TYPICAL SPECIFICATIONS GENERAL Supply and install a Bousquet model DG() indirect gas-fired heater operating on natural gas for indoor (outdoor) installation. The manufacturer must be accredited by the CWB in compliance with standard CSA W7.. to meet the minimum standard applicable to all types of welds including the welds on a stainless steel heat exchanger. PERFORMANCE The heater will have the capacity to heat CFM of standard air from F to F, for a net heat output of MB at a minimum combustion efficiency of %. The fuel used will be natural gas at an inlet pressure of psig. UNIT CONSTRUCTION TThe heavy duty base frame of the unit shall be made of U-shaped channels. The walls and roof will be made of 8 gauges G galvanized steel panels with double folded longitudinal edges. PVC gaskets between each panel, with an external urethane based caulking shall be provided to ensure for unit water tightness. The single wall units will be insulated with a one-inch anti-bacterial Fiber Glass Duct Liner with Reinforced Coating. The exchanger section is double wall insulated with two inches high temperature Fiber Glass Blanket.lb/pi3 density, and covered with a gauge G galvanized steel liner. The weatherproof control cabinet shall have one large access do0r to allow for the maintenance of the gas piping and electric components. The exterior surfaces of the unit shall be treated with a phosphate cleaner-conditioner and coated with a Synthetic Chromating Phosphate with anti corrosion agent. The finish shall be ensured by first quality high performance alkyd resin enamel. For outdoor applications, all the controls and piping will be installed inside a weatherproof cabinet with access doors for easy maintenance. EAT EXCANGER The multiple pass heat exchanger shall be drum and tube type, with primary drum and secondary tubes entirely made of L stainless steel requiring no thermal treatment to prevent weld cracking and provide great resistance to corrosion and high temperatures, and increase service life of the unit. The exchanger will be equipped with bolted access panels for the inspection and cleaning of the tubes. 00 Series stainless steel, aluminized carbon steel heat exchangers are not acceptable. 2

24 BURNER AND GAS PIPING The burner will be of a forced draft type, factory-installed on the exchanger with all gas piping and control wiring required for the proper operation of the unit. The gas pilot piping will be equipped with an electronic spark ignitor, manual and automatic shut-off valves, pressure regulator, and manual cock. The gas piping of the burner will include a pressure regulator, automatic quick-closing shut-off valve, automatic slow-opening valve, manual ignition cock, test ports and modulating gas valve. The burner and gas piping assembly will have a modulating turndown ratio of at least 20:. Combustion air damper shall modulate with the gas control valve in order to maintain efficiency. eaters with constant speed draft inducer are not acceptable. FAN SECTION The fan section will be designed according to the Air Movement and Control Association standards. The fan and motor will be installed on a steel structure welded in compliance with the Canadian Welding Bureau standards and rest on anti-vibration isolators. An access door will be installed to enable the maintenance of the fan, motor, bearings, belts and pulleys. The motor will be open drip proof (ODP), thermally protected with superior efficiency; it will be installed on a base to enable belt alignment and tension. The fan will be a forward-curved blade type (FC), double width, double inlet (DWDI). FILTER AND DAMPER SECTION Dampers will be of standard construction, galvanized steel blades equipped with electric actuators and limit switch. The filters will be disposable, 2-inch thick, % efficient. An access door will allow for the inspection and changing of the filters BURNER CONTROL MODE (Select one of the following options): G for 00% outside air: Final air temperature is controlled by a 0-0 volts or -20 ma signal provided by other. G2 for 00% outside air: Final air temperature is controlled by a temperature controller and sensor supplied with the unit. G3 for Make-Up air and heating application, with recirculation: Final air temperature is controlled by two temperature controllers sensor and room thermostat supplied with the unit. One of the controllers will be ser for F supply air temperature; the other controller is ser for F supply air temperature; the room thermostat selects the F controller when room temperature is satisfied and the Fcontroller when heat is required. 2

25 AIR CONTROL MODE (Select one of the following options) V: Damper actuators and signal are provided by others. V2-A for 00% outside air: ON/O damper actuator supplied with the unit. V2-B for outside and return air: Modulating dampers actuators supplied with theunit, but controlled by others. V2-C for outside and return air: Modulating damper actuators supplied with theunit and internally controlled with a minimum fresh air potentiometer. REMOTE CONTROL PANEL A remote control panel will be supplied by the manufacturer to turn the unit on from a remote location. It will be outfitted with a stop/fan/burner selection switch and light indicating the operating status of the unit. CERTIFICATION All DG() heaters must be CETLUS approved and certified according to standards CAN/CGA3.2 and UL 79. 2

26 Printed in Canada - Rev (0/2007) MSA-DG, rue Nobel Sainte-Julie (Québec) J3E Z9 MANUFACTURED BY Toll free: Tel : 87- Fax : bousquet@bousquet.ca Web site :

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

Direct Fired Heater Model AD Specification

Direct Fired Heater Model AD Specification Direct Fired Heater Model AD Specification Description A Direct-fired gas heating and ventilating unit(s), as indicated on the drawings shall be furnished. Unit(s) shall be tested in accordance with ANSI

More information

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

Internal ridged board 1 x 1.5 foil face installation shall be installed on roof, walls and base of casing. A-D WITH MPU SPECIFICATION WRITTEN SPECIFICATION Description A Modular Packaged Heating, Cooling and ventilating unit(s), as indicated on the drawings shall be furnished. Direct Fired Gas Unit(s) shall

More information

Indirect Gas-Fired Make-Up Air

Indirect Gas-Fired Make-Up Air Indirect Gas-Fired Make-Up Air Model IG 800 to 7,000 cfm Up to 400,000 Btu/hr Multiple Furnace Control Options Optional Evaporative Cooling May 20041 Product Features Model IG Indirect Gas-Fired Make-Up

More information

TGIF-1. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You.

TGIF-1. Indirect Fired Heating Systems. Technical Guide for: IF Indoor Installations. IFW Outdoor Installations. Applied Air. Keeps You. TGIF- Indirect Fired Heating Systems Technical Guide for: IF Indoor Installations IFW Outdoor Installations Applied Air Keeps You Warm Indirect Fired Heating Systems Technical Guide In the business of

More information

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation

Industrial Space Heating Direct Gas-Fired Heating. Greenheat 50/50 Recirculation Industrial Space Heating Direct Gas-Fired Heating Greenheat 00% Outdoor Air Greenheat 50/50 Recirculation 80/0 Recirculation March 008 Product Overview Industrial Space Heating Greenheck s space heating

More information

May, 2004 Commercial & Industrial Applied Product Line Heating Ventilating Cooling Make-Up Air

May, 2004 Commercial & Industrial Applied Product Line Heating Ventilating Cooling Make-Up Air 75-137.5 May, 2004 Commercial & Industrial Applied Product Line Heating Ventilating Cooling Make-Up Air MODINE COMMERCIAL & INDUSTRIAL APPLIED PRODUCT LINE Modine has always been the industry standard

More information

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004

Engineering Bulletin. Gas Heat. for M-Series and T-Series Climate Changer Air Handlers CLCH-PRB010-EN. March 2004 Engineering Bulletin Gas Heat for M-Series and T-Series Climate Changer Air Handlers March 2004 CLCH-PRB010-EN Preface Gas heat can be a good heating option for any of the following applications: Climates

More information

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY Bousquet Technologies Inc. 2121, Nobel, Ste Julie, Quebec, Canada, J3E1Z9 SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL Oil-Fired air heater for industrial and commercial use. FOR YOUR SAFETY Do not

More information

Equipment Specifications

Equipment Specifications Equipment Specifications GAS/OIL HEATING ONLY INDIRECT-FIRED AIR HANDLER GUIDE SPECIFICATION PART 1 GENERAL [Gas][Oil][Gas/Oil Combo]-Fired Please note: Brackets indicate required choices to be made in

More information

FEATURES AND BENEFITS

FEATURES AND BENEFITS FEATURES AND BENEFITS Product Features and Benefits Full Product Line Offering Feature All models are 80% thermally efficient Blower performance up to 3.0 W.C. DX or chilled water section with factory

More information

Direct Gas-Fired Make-Up Air

Direct Gas-Fired Make-Up Air Direct Gas-Fired Make-Up Air Model TSU Heavy Duty, High Airflow Applications Manufacturing and Industrial Facilities Up to 64,000 cfm August 2012 Products Model TSU Direct Gas-Fired Make-Up Air Unit The

More information

Modular Heating & Ventilating Unit Model IGX-HV

Modular Heating & Ventilating Unit Model IGX-HV Modular Heating & Ventilating Unit Model IGX-HV Indirect Gas-Fired Heating Evaporative Chilled Water DX Cooling October 2008 Product Features Model IGX-HV Indirect Gas-Fired Heating and Ventilating Unit

More information

Warm. IFR Indirect Fired Gas Heating Systems. Applied Air. Keeps You

Warm. IFR Indirect Fired Gas Heating Systems. Applied Air. Keeps You TGIFR IFR Indirect Fired Gas Heating Systems Technical Guide for: Outdoor Rooftop Mounted Units To 46,000 CFM And 4,000 MBH Output Applied Air Keeps You Warm Indirect Fired Heating Systems Technical Guide

More information

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters. SECTION 15622 DIRECT GAS-FIRED BURNER & MANIFOLD SYSTEM PART 1: GENERAL 1.1 Section includes: A. Direct gas-fired heater modules B. Controls C. Equipment schedule 1.2 Related Sections A. Section 01655:

More information

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS SECTION 237339 - DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

Gas-Fired Indoor and Outdoor Duct Furnaces

Gas-Fired Indoor and Outdoor Duct Furnaces July, 2008 Gas-Fired Indoor and Outdoor Duct Furnaces INDOOR GRAVITY VENTED DFG, DBG, DCG INDOOR SEPARATED COMBUSTION DFS, DBS, DCS OUTDOOR GRAVITY AND POWER EXHAUSTED H Series table of contents A complete

More information

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating

Section (CSI ) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating Section 15700 (CSI 23 74 33) I-Series Drum & Tube (04/23/10) Indirect-Fired Heating & Ventilating Note: Optional items and/or items requiring a choice, will be shown between brackets and/or parentheses

More information

STR-Series Indirect-Fired Air Turnover Units

STR-Series Indirect-Fired Air Turnover Units STR-Series Indirect-Fired Air Turnover Units Equipment Specifi cations 1.800.589.3691 www.weather-rite.com GAS/OIL HEATING ONLY INDIRECT-FIRED AIR TURNOVER UNIT GUIDE SPECIFICATIONS PART 1 GENERAL [Gas][Oil][Gas/Oil

More information

Directflow SBDR/SBD SERIES

Directflow SBDR/SBD SERIES Bulletin SBDR/SBD-1 January 2015 Supersedes SBDR/SBD-1 Dated April 2014 Directflow SBDR/SBD SERIES DIRECT GAS-FIRED MAKE-UP AIR SYSTEMS Cooling Can Be Added A MODEL FOR EVERY APPLICATION SBD Direct Gas-Fired

More information

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL

ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL ELECTRIC AIR HEATER INSTALLATION AND SERVICE MANUAL BC(E) SERIES INDOOR / OUTDOOR MANUFACTURED BY GENERAL INFORMATION PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: TELEPHONE: INSTALLATION

More information

Directflow SBDR/SBD SERIES

Directflow SBDR/SBD SERIES Bulletin /SBD-1 June 2005 Supersedes SBD-1 Dated February 2005 and -1 Dated March 2001 Directflow /SBD SERIES DIRECT GAS-FIRED MAKE-UP AIR SYSTEMS Cooling Can Be Added A MODEL FOR EVERY APPLICATION SBD

More information

FORM NO. G REV. 2 Supersedes Form No. G Rev. 1 GAS FURNACES

FORM NO. G REV. 2 Supersedes Form No. G Rev. 1 GAS FURNACES FORM NO. G11-489 REV. 2 Supersedes Form No. G11-489 Rev. 1 GAS FURNACES RGPR- SERIES ECM Equipped Models with Input Rates from 50,000 to 125,000 BTU/HR 115 Volts, 60 Hz, Single Phase [15 to 37 kw] (U.S.

More information

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15732 - PACKAGED ROOFTOP AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 SECTION INCLUDES A. Package roof top unit. B. Heat exchanger. C. Refrigeration components. D. Unit operating controls. E. Roof

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC2 THRU NVC6 ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx WITH CONTROLINKS CONTROLS THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas

More information

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

PGF SERIES 7-1/2 Ton. Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT PGF SERIES 7-1/2 Ton C Belt Drive CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT SINGLE PACKAGE Combination gas heating and electric cooling, self contained for year-round comfort. Systems can be installed

More information

Submittal Data Performance Data Electrical Data

Submittal Data Performance Data Electrical Data ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:

More information

Direct Gas-Fired Make-Up Air Models DG and DGX

Direct Gas-Fired Make-Up Air Models DG and DGX Direct Gas-Fired Make-Up Air Models DG and DGX Commercial, Industrial and Kitchen Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Optional Cooling - Packaged DX (2.5

More information

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications

GAS FURNACES G20RE/ G20RXE EXISTING NEG ENGINEERING DATA EXISTING NEG. Typical Applications ENGINEERING DATA Typical Applications G20RE and G20RXE WhisperHeat DOWN-FLO GAS FURNACES *78.0% A.F.U.E. 50,000 to 150,000 Btuh Input Add-On Cooling 2 thru 5 Nominal Tons *Isolated Combustion System rating

More information

GAS FURNACES SILHOUETTE II PLUS 2 LXE TWO STAGE 80% A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES

GAS FURNACES SILHOUETTE II PLUS 2 LXE TWO STAGE 80% A.F.U.E. UPFLOW/HORIZONTAL GAS FURNACES FORM NO. G22-473 REV. 3 Supersedes Form No. G22-473 Rev. 2 GAS FURNACES UGPL- SERIES ECM Equipped Models with Input Rates from 50,000 to 125,000 BTU/HR [15 to 37 kw] (U.S. & Canadian Models) Annual Fuel

More information

GAS FURNACES SUPER QUIET 80 TWO STAGE 80% A.F.U.E. DOWNFLOW GAS FURNACES

GAS FURNACES SUPER QUIET 80 TWO STAGE 80% A.F.U.E. DOWNFLOW GAS FURNACES FORM NO. G11-490 GAS FURNACES RGLR- SERIES ECM Equipped Models with Input Rates from 75,000 to 125,000 BTU/HR 115 Volts, 60 Hz, Single-Phase [22 to 37 kw] (U.S. & Canadian Models) Annual Fuel Utilization

More information

Modular Supply Make-Up Air Unit

Modular Supply Make-Up Air Unit Modular Supply Make-Up Air Unit Model MSX Flexible Design Factory Assembled Heating Options Hot Water Steam Electric Cooling Options Evaporative Direct Expansion Chilled Water November 2009 Product Features

More information

GLOBAL FINISHING SOLUTIONS

GLOBAL FINISHING SOLUTIONS GLOBAL FINISHING SOLUTIONS > Eliminate problems with drafts, stale or contaminated air, and temperature stratification > Create balanced building pressure and maintain proper comfort levels > Introduce

More information

KIC Air Curtains. Technical Guide

KIC Air Curtains. Technical Guide TGKIC-3 KIC Air Curtains Technical Guide AIR PERFORMANCE AIR MOVEMENT AND CONTROL ASSOCIATION INTERNATIONAL, INC. King certifies that the air curtains shown herein are licensed to bear the AMCA seal. The

More information

13 GEP A L P - 1 A

13 GEP A L P - 1 A PRODUCT SPECIFICATIONS PACKAGED GAS / ELECTRIC 3GEP MERIT SERIES Residential - R-40A Bulletin No. 20602 December 202 Supersedes October 202 SEER - 3.00 AFUE - 80% 2 to 5 Tons Cooling Capacity - 22,800

More information

Field Start-Up Sheet Direct Fired Gas Equipment

Field Start-Up Sheet Direct Fired Gas Equipment Customer: Sales Representative: Model Number: Serial Number: Field Start-Up Sheet Direct Fired Gas Equipment ***Please Print*** INITIAL INSPECTION I. Installer Responsibilities 1. Remote Panel: All interconnecting

More information

SUBMITTAL SCHEDULE & DATA

SUBMITTAL SCHEDULE & DATA SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Date: 10/31/2016 Location: Engineer: Submitted by: Jeff Musto Architect: Contractor: Model

More information

RGE 13 A T - 1 A

RGE 13 A T - 1 A PRODUCT SPECIFICATIONS PACKAGED GAS / ELECTRIC 3GEP / RGE3 Rooftop Units 60HZ Bulletin No. 2063 December 202 Supersedes October 202 MODEL NUMBER IDENTIFICATION -PHASE MODELS SEER - 3.00 (3GEP Shown) AFUE

More information

62DA,DB,DC,DD,DE,DF07-38

62DA,DB,DC,DD,DE,DF07-38 62D-3SB 62DA,DB,DC,DD,DE,DF07-38 DEDICATED VERTICAL OR HORIZONTAL 100% OUTDOOR AIR UNIT PERFORMANCE DATA UNIT DIMENSION PRINTS ACCESSORY DIMENSION PRINTS Copyright 2011 Carrier Corporation Syracuse, New

More information

Combat. DF-Series Direct-Fired Heating, Cooling and Pressurization Systems. Equipment Specifications

Combat. DF-Series Direct-Fired Heating, Cooling and Pressurization Systems. Equipment Specifications Combat DF-Series Direct-Fired Heating, Cooling and Pressurization Systems Equipment Specifications 800.828.7450 www.rg-inc.com CANADA: 100% OUTSIDE AIR ONLY DIRECT-FIRED AIR HANDLERS GUIDE SPECIFICATION

More information

Product Data. S Unit may also be sidewall vented with an approved A S OVL units equipped with optional ECM 2.3 Variable

Product Data. S Unit may also be sidewall vented with an approved A S OVL units equipped with optional ECM 2.3 Variable LOW --- BOY OIL FURNACE INPUT CAPACITIES: 77,000 THRU 154,000 BTUH Product Data THE LATEST IN OIL FURNACE TECHNOLOGY A10232 The models OBL and OVL combine high efficiency and quiet operation with oil heating

More information

Direct Gas-Fired Make-Up Air Models DGK, DG and DGX

Direct Gas-Fired Make-Up Air Models DGK, DG and DGX Direct Gas-Fired Make-Up Air Models DGK, DG and DGX Kitchen and Industrial Applications 800-48,000 cfm 4 in. wg External Static Pressure Direct Gas-Fired Heating Packaged DX (3 to 16 tons), Split DX Cooling,

More information

A. Codes and Standards that are Standard at the University:

A. Codes and Standards that are Standard at the University: PART 1: GENERAL 1.01 Purpose: 1.02 References: 1.03 Requirements: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The

More information

SECTION ROOFTOP REPLACEMENT AIR UNITS

SECTION ROOFTOP REPLACEMENT AIR UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Specification Sections, apply to this Section. B. Related

More information

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART # INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #238-39387-00 THIS INSTRUCTION SUPPLEMENT IS ONLY INTENDED TO GIVE INSTALLATION INSTRUCTIONS AND INFORMATION RELATED TO THE INDUCED

More information

SKYPAK II, 3 Ton Series, gives you a

SKYPAK II, 3 Ton Series, gives you a SKYPAK II 3 ton Heating And Cooling self-contained Package SKYPAK II, 3 Ton Series, gives you a complete air-conditioning and heating system as an all in one package unit. Designed for convenient through-the-wall

More information

Counterflo CF BASIC COUNTERFLO HEATER RCF CURB MOUNTED ROOFTOP HEATER CFDF COUNTERFLO DUCT FURNACE INDIRECT-FIRED INDUSTRIAL HEATERS

Counterflo CF BASIC COUNTERFLO HEATER RCF CURB MOUNTED ROOFTOP HEATER CFDF COUNTERFLO DUCT FURNACE INDIRECT-FIRED INDUSTRIAL HEATERS Bulletin CF-1 May 2005 Supersedes CF-1 Dated February 1998 Counterflo INDIRECT-FIRED INDUSTRIAL HEATERS Self-contained, Automatic, Indirect-fired, Warm-air Heater C.S.A. APPROVED UNITS AVAILABLE Natural

More information

Contents INDEX. TDM Series Indirect Fired Heaters

Contents INDEX. TDM Series Indirect Fired Heaters Contents Typical Indoor Installations................... 000 Indoor Unit Dimensions (Vertical).............. 000 Indoor Unit Dimensions (Horizontal)............ 000 Outdoor Unit Dimensions.....................

More information

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU)

AIR HANDLERS. Central Station (CS3) Roof Mounted (RT) (Modular AL Frame AHU) AIR HANDLERS Central Station (CS3) (Modular AL Frame AHU) Roof Mounted (RT) CONTENTS 1. CS3 Modular Aluminium Frame AHU : Unit Types 2. Casing Structure 3. Blowers and Drives 4. Coils 5. Options and Accessory

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

GAS FURNACES. Communicating Furnace Thermostat. FORM NO. G Supersedes Form No. G RHC-TST550CMMS MID HIGH

GAS FURNACES. Communicating Furnace Thermostat. FORM NO. G Supersedes Form No. G RHC-TST550CMMS MID HIGH FORM NO. G11-508 Supersedes Form No. G11-508 GAS FURNACES RGLE- SERIES ECM Equipped Models with Input Rates from 75,000 to 125,000 BTU/HR 115 Volts, 60 Hz, Single-Phase [22 to 37 kw] (U.S. & Canadian Models)

More information

Rheem Prestige Series Two-Stage Downflow Gas Furnace equipped with the Comfort Control 2. System. RGLE- Series 80% A.F.U.E. Input Rates kbtu

Rheem Prestige Series Two-Stage Downflow Gas Furnace equipped with the Comfort Control 2. System. RGLE- Series 80% A.F.U.E. Input Rates kbtu THIS MODEL 80.0% 78% 82% 88% 97% Air Gas Furnaces Rheem Prestige Series Two-Stage Downflow Gas Furnace equipped with the Comfort Control 2 System RGLE- Series 80% A.F.U.E. Input Rates 75-125 kbtu ENER

More information

For More Information Click Here or Call General Supply M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS

For More Information Click Here or Call General Supply M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS TECHNICAL SPECIFICATIONS M7RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 95%+ AFUE Input 45,000 thru 7,000 Btuh The high efficiency downflow gas furnace is especially

More information

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS NOVEMBER 1, 2013 SECTION 15800 - AIR HANDLING EQUIPMENT 1.1 GENERAL A. All air handlers installed shall conform to the University of Rochester specification Guideline for Semi-Custom and Pre-Engineered Air Handling Units.

More information

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS SECTION 23 70 00 AIR HANDLING UNITS PART 1. GENERAL 1.1 Section includes air-handling units to 15,000 cfm and accessories. 1.2 Related Sections 1 : A. Division 01 - Brown University Standard for Narragansett

More information

8+* Bulletin No November 1997

8+* Bulletin No November 1997 ENGINEERING DATA VALUE 80Z UP-FLOW/HORIZONTAL GAS FURNACES *80.0 to 80.5% A.F.U.E. 45,000 to 20,000 Btuh (3.2 to 32.2 kw) Input Heating Capacity -/2 thru 6 Tons (3.5 thru 2. kw) Nominal Add-on Cooling

More information

Direct Fired Units w/ Packaged Cooling

Direct Fired Units w/ Packaged Cooling Direct Fired Units w/ Packaged Cooling Quick Select (Direct Fired BMA Type w/ Packaged Cooling).....S-1 Direct Fired BMA 109 ~ BMA 125 w/ Packaged Cooling....S-2 BMA Type w/ Packaged Cooling Typical Specifications.....S-9

More information

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004) High Plume Blowers Suggested Specification Section 15500 (Master Format 1996) Suggested Specification Section 23 38 16 (Master Format 2004) PART 1 GENERAL 1.01 WORK INCLUDED High Plume Laboratory Exhaust

More information

Product Data OBM/OVM. MULTIPOISE OIL FURNACE INPUT CAPACITIES 70,000 thru 154,000 BTUH THE LATEST IN OIL FURNACE TECHNOLOGY

Product Data OBM/OVM. MULTIPOISE OIL FURNACE INPUT CAPACITIES 70,000 thru 154,000 BTUH THE LATEST IN OIL FURNACE TECHNOLOGY MULTIPOISE OIL FURNACE INPUT CAPACITIES 70,000 thru 154,000 BTUH Product Data THE LATEST IN OIL FURNACE TECHNOLOGY A10311 The models OBM and OVM combine high efficiency and quiet operation with oil heating

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

PGB SERIES 3thru5Ton 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT

PGB SERIES 3thru5Ton 10 SEER CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT PGB SERIES 3thru5Ton 10 SEER C CONVERTIBLE SINGLE PACKAGE GAS/ELECTRIC UNIT SINGLE PACKAGE Combination gas heating and electric cooling, self contained for year-round comfort. Systems can be installed

More information

90 HIGH EFFICIENCY UPFLOW GAS FURNACES

90 HIGH EFFICIENCY UPFLOW GAS FURNACES FORM NO. GSC-497 REV. 2 Supersedes Form No. GSC-497 Rev. 1 GF901U SERIES Models with Input Rates 45,000, 60,000, 105,000 & 120,000 BTU/HR [13.19, 17.58, 30.77, & 35.17 kw] (All Models 90% A.F.U.E. or Above)

More information

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s) Furnish and install as shown on AERCO International plans and operation and maintenance manuals, with all applicable codes and authorities having local, state and federal jurisdiction, Benchmark Series

More information

RG7D 1-Stage Heat Series

RG7D 1-Stage Heat Series TECHNICAL SPECIFICATIONS RG7D 1-Stage Heat Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 9%+ AFUE Input 4,000 thru 7,000 Btuh The high efficiency downflow gas furnace

More information

Date: Project #: Engineer: Prepared By: Bid Date:

Date: Project #: Engineer: Prepared By: Bid Date: Brute NEOTHERM Date: Project #: Hydronic Boiler Hydronic Boiler Indoor Sizes 285-850 Submittal Data Engineer: Project Name: Prepared By: Location: Bid Date: Contractor: Standard Equipment Electronic PID

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

SIOUX STEEL COMPANY GRAIN CONDITIONING EQUIPMENT. Fans, Heaters & Controls

SIOUX STEEL COMPANY GRAIN CONDITIONING EQUIPMENT. Fans, Heaters & Controls SIOUX STEEL COMPANY GRAIN CONDITIONING EQUIPMENT Fans, Heaters & Controls 1 GRAIN CONDITIONING EQUIPMENT SIOUX STEEL COMPANY Innovative Solutions Manufactured By A Family-Owned Company With A ENGINEERING

More information

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat)

B24/C22/24 COILS BLOWER COIL UNITS ENGINEERING DATA. Bulletin # June 1994 Supersedes August B24 Blower Unit (With Optional Electric Heat) ENGINEERING DATA COILS BLOWER COIL UNITS B24/C22/24 B24 SERIES ADD-ON BLOWER UNITS UP-FLO DOWN-FLO HORIZONTAL WITH C22FC/CR22/CH22 & C24FC/CH24 COILS 1-1/2 Thru 5 Ton (5.3 thru 17.6 kw) Capacity 6,400

More information

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER PART 1 GENERAL 1.01 RELATED DOCUMENTS A. ANSI Z21.13 American National Standard for Gas-Fired Low Pressure Steam and Hot Water Boilers B. ASME Section

More information

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

M3RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace TECHNICAL SPECIFICATIONS M3RL Series High Efficiency / Direct Vent Condensing Downflow Gas Furnace Induced Draft - 90+ AFUE Input 60,000 & 80,000 Btuh The high efficiency downflow gas furnace is especially

More information

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS

CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS 7 Rosemex Products 97 VENTILATION CLIMATAIR PENTHOUSE AIR HANDLING SYSTEMS 2 INTRODUCTION Rosemex "Penthouse" units are essentially outdoor mechanical rooms. They group in one compact weather proof outdoor

More information

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters. Section 15 _ Energy Recovery Air Handling System Part 1: GENERAL 1.1 Section Includes: A. Energy Recovery Air Handler B. Controls (most by Others) C. Equipment Schedule 1.2 Related Sections: A. Section

More information

SECTION AIR DOORS

SECTION AIR DOORS SECTION 23 34 33 AIR DOORS Berner Series VSA air doors are designed for openings up to 12 ft for environmental separation and up to 10 ft for insect control. Berner Series VSB air doors are designed for

More information

Advance Release September 2009

Advance Release September 2009 Vertical Air Cooled DSV Series R 410A Model DSV096 DSV120 DSV144 DSV180 Nominal Cooling (Tons) 8 10 12 15 Refrigerant R 410A R 410A R 410A R 410A Cooling Performance Gross Cooling Capacity(Btu/h) 95,000*

More information

90 HIGH EFFICIENCY UPFLOW GAS FURNACES

90 HIGH EFFICIENCY UPFLOW GAS FURNACES FORM NO. GSC-534 GF901U SERIES Models with Input Rates 45, 60, 75, 90, 105 & 120 kbtu [13.19, 17.58, 21.9, 26.4, 30.77 & 35.17 kw] (All Models 90% A.F.U.E. or Above) 90 EFFICIENCY UPFLOW GAS FURNACES The

More information

BANANZA. B-Series Direct-Fired Heating, Cooling And Pressurization Systems. Equipment Specifications

BANANZA. B-Series Direct-Fired Heating, Cooling And Pressurization Systems. Equipment Specifications BANANZA B-Series Direct-Fired Heating, Cooling And Pressurization Systems Equipment Specifications 1.800.255.3416 www.bananza.com CANADA: 100% OUTSIDE AIR ONLY DIRECT-FIRED AIR HANDLER GUIDE SPECIFICATION

More information

XeteX, Inc. All Rights Reserved.

XeteX, Inc. All Rights Reserved. Model DXH Custom, packaged, roof mounted or indoor mounted unit with cooling (DX or Chilled Water) and an air-to-air aluminum flat plate exchanger designed to provide pre-cooling and reheat. The DXH is

More information

COMFORT CONTROL 90 PLUS WITH DUAL TWO-STAGE UPFLOW GAS FURNACES

COMFORT CONTROL 90 PLUS WITH DUAL TWO-STAGE UPFLOW GAS FURNACES FORM NO. GSC-493 REV. 3 Supersedes Form No. GSC-493 Rev. 2 GF902U*B SERIES Models with Input Rates of 45,000, 60,000, 75,000, 90,000 & 105,000 BTU/HR [13.19, 17.58, 22, 26.38 & 30.77 kw] 90 PLUS WITH DUAL

More information

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents

A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Boiler specifications A-8-01 Typical questions and answers on the boiler specifications on tender and boiler contract documents Burner General: Q. Burner and burner safeguards shall comply with the CGA

More information

VERTICAL FAN COIL UNITS

VERTICAL FAN COIL UNITS VERTICAL FAN COIL UNITS VERTICAL FAN COIL UNITS Model: CT & TCE 2 - Pipe 350 cfm to 1200 cfm capacity 4-row water coil 120v or 24v controls Electric heating coil (TCE Model) Fresh air connection from remote

More information

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges. Service Literature The LGH/LCH high and standard efficiency 5, 0, 5 and 50 ton (, 0.7, 58. and 75.9 kw) units, are configure to order units (CTO) with a wide selection of factory installed options. The

More information

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL

WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL PREPARED FOR: DATE: JOB NAME: WE ARE PLEASED TO PROVIDE THE ENCLOSED SUBMITTAL FOR YOUR REVIEW AND APPROVAL EQUIPMENT DETAILS ITEM TAG DESCRIPTION MODEL NUMBER 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 EQUIPMENT

More information

LARGE CAPACITY HEATERS

LARGE CAPACITY HEATERS 250 1,000 Capacities 7.5-12,850 150,000 CFM 200 MBH 250-7,500 MBH - - Tons APPLICATIONS Heating/Cooling/Makeup Air WAREHOUSES / FACTORIES SCHOOLS / UNIVERSITIES COMMERCIAL / RETAIL INDUSTRIAL GYMNASIUMS

More information

iq1001, Gen II Submittal Data

iq1001, Gen II Submittal Data , Gen II Submittal Data Date: Project Name: Bid Date: Fuel Type: Natural Gas Propane Project #: City State Zip: Engineer: Contractor: Factory Option: intouchbms KEY FEATURES Multiple Stainless (316L) Heat

More information

Installation Instructions

Installation Instructions Installation Instructions PAM3 SERIES PACKAGE AIR CONDITIONERS TABLE OF CONTENTS SAFETY LABELING AND SIGNAL WORDS... 2 UNIT DIMENSIONS... 3 SAFE INSTALLATION REQUIREMENTS... 3 LOCATING THE UNIT... 3 CLEARANCES...

More information

GAS FURNACES. RGRK- SERIES Models with Input Rates 120,000 BTU/HR [35.17 kw] (All Models 90% A.F.U.E. or Above)

GAS FURNACES. RGRK- SERIES Models with Input Rates 120,000 BTU/HR [35.17 kw] (All Models 90% A.F.U.E. or Above) FORM NO. G22-482 REV. 8 Supersedes Form No. G22-482 Rev. 7 GAS FURNACES RGRK- SERIES Models with Input Rates 120,000 BTU/HR [35.17 kw] (All Models 90% A.F.U.E. or Above) 90 PLUS WITH DUAL COMFORT CONTROL

More information

ENVIRO UNIT ENGINEERING MANUAL KES SERIES

ENVIRO UNIT ENGINEERING MANUAL KES SERIES ENVIRO UNIT ENGINEERING MANUAL KES SERIES The Cadexair INC. Enviro System (KES) and Recirculation System (KRS) have been designed and constructed specifically for a commercial kitchen exhaust. The units

More information

GAS FURNACES. ACHIEVER SERIES SUPER QUIET 80 80% A.F.U.E. DOWNFLOW GAS FURNACES w/ecm MOTOR

GAS FURNACES. ACHIEVER SERIES SUPER QUIET 80 80% A.F.U.E. DOWNFLOW GAS FURNACES w/ecm MOTOR FORM NO. G22-506 Supersedes Form No. G22-506 Rev. 1 GAS FURNACES RGLT- SERIES Models with Input Rates from 75,000 to 125,000 BTU/HR [22 to 37 kw] (U.S. & Canadian Models) Annual Fuel Utilization Efficiency

More information

48TF GAS HEATING/ ELECTRIC COOLING UNITS

48TF GAS HEATING/ ELECTRIC COOLING UNITS 48TF-4SB 48TF004-014 GAS HEATING/ ELECTRIC COOLING UNITS PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS Copyright 2005 Carrier Corporation Syracuse, New York 13221 Form

More information

ADF/ADFH 300 and 500

ADF/ADFH 300 and 500 MODEL ADF/ADFH DIRECT-FIRED SYSTEMS TECHNICAL DATA Four Sizes - 300, 500, 700, 1200 Horizontal Configuration with Full Curb Cap Base Horizontal or Vertical (down) Discharge Indoor/Outdoor Installation

More information

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS Single Package Rooftop Gas Heating/Electric Cooling Unit Two Stage Cooling Capacity Control with NOVATIONt Coil Sizes 08, 12, 14 with Puronr (R---410A) Refrigerant Submittal Data PERFORMANCE DATA CERTIFIED

More information

TECHNICAL SPECIFICATIONS

TECHNICAL SPECIFICATIONS TECHNICAL SPECIFICATIONS Model PGF1RA Series M1010 Product Line High Efficiency / Upflow / Horizontal Gas Furnace Induced Draft - 80+ AFUEurnace 2 10 YEAR WARRANTY WORRY-FREE PERFORMANCE 5 YEAR DEPENDABILITY

More information

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing

Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Installation & Service Instructions for Jackson & Church Flexaire Packaged Furnaces SDF-125 thru SDF-400 Gas Firing Important: To protect the unit and avoid damage to the heat exchanger, the blower speed

More information

Make-Up Air March 2012

Make-Up Air March 2012 Make-Up Air March 2012 Comfortable energy efficient kitchen ventilation starts here. At Larkin Industries, our goal is to manufacture well-designed kitchen ventilation systems with environmentally sustainable

More information

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units TECHNICAL SPECIFICATIONS R7DA Series 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units 5.4 ISMRE Commercial System 81% Steady State Efficiency Standard Features Fits Pre-Existing Curbs High-Efficiency Low

More information

A. Section Common Motor Requirements for HVAC Equipment: Fan motors.

A. Section Common Motor Requirements for HVAC Equipment: Fan motors. SECTION 235533 - FUEL-FIRED UNIT HEATERS PART 1 GENERAL 1.1 SECTION INCLUDES A. Gas fired unit heaters. B. Oil fired unit heaters. C. Tubular infrared heaters. 1.2 RELATED REQUIREMENTS A. Section 230513

More information

GAS FURNACES CLASSIC 90 PLUS HIGH EFFICIENCY UPFLOW GAS FURNACES

GAS FURNACES CLASSIC 90 PLUS HIGH EFFICIENCY UPFLOW GAS FURNACES FORM NO. G11-450 REV. 13 Supersedes Form No. G11-450 Rev. 12 GAS FURNACES /RGRB- SERIES Models with Input Rates from 45,000 to 120,000 BTU/HR [13.19 to 35.17 kw] (All Models 90% A.F.U.E. or Above) CLASSIC

More information

Rheem Classic Series Downflow/ Horizontal Gas Furnaces

Rheem Classic Series Downflow/ Horizontal Gas Furnaces Gas Furnaces Rheem Classic Series Downflow/ Horizontal Gas Furnaces RGTC- Series Up to 95% A.F.U.E. Input Rates from 45 to 105 kbtu [13.19 to 30.77 kw] A.F.U.E. (Annual Fuel Utilization Efficiency) calculated

More information

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA

NAVIEN AMERICA INC FITCH AVENUE IRVINE, CALIFORNIA, USA Navien America Inc. Specification Details for the Navien models: CR-210 CR-210A For Indoor Installation Only For Potable Water Heating and Space Heating NAVIEN AMERICA INC. 17855 FITCH AVENUE IRVINE, CALIFORNIA,

More information