1 BSHM ARCHITECTS, INC. 15 Central Square, Suite 300 Youngstown, Ohio January 22, 2015 ADDENDUM NO. 4 to Drawings and Specifications for URSULINE MOTHERHOUSE HEALTHCARE RENOVATIONS 4250 Shields Road Canfield, Ohio To all Bidders: This Addendum supplements and amends the original drawings and Specifications, it shall be taken into account in preparing proposals and shall become a part of the Contract Documents. GENERAL 1. The cost of the Plumbing Work will be submitted as an add to the bid for the rest of the project work no later than Tuesday, January 27, 2015 at 2:00 pm. This bid will be delivered to the Ursuline Motherhouse. 2. TABLE OF CONTENTS: SPECIFICATIONS Add the following sections: PLUMBING PUMPS DOMESTIC HOT WATER HEATING EQUIPMENT 3. SECTION GENERAL DUTY VALVES FOR PLUMBING: Replace previous Section with the revised Section which is attached. 4. SECTION PLUMBING PUMPS: Add Section Plumbing Pumps. 5. SECTION DOMESTIC HOT WATER HEATING EQUIPMENT: Add Section Domestic Hot Water Heating Equipment ADDENDUM NO. 4 Page 1

2 DRAWINGS 6. COVER SHEET: Drawing Index: Add Sheet P First Floor Ceiling Plan - Plumbing (water). 7. SHEET P-202: Replace the previous Sheet P-202 with the revised Sheet P-202 which is attached. 8. SHEET P-203: Add Sheet P First Floor Ceiling Plan - Plumbing (water). END OF ADDENDUM enclosures: Specifications: GENERAL DUTY VALVES FOR PLUMBING PLUMBING PUMPS DOMESTIC HOT WATER HEATING EQUIPMENT Drawings: P-202 P ADDENDUM NO. 4 Page 2

3 SECTION GENERAL DUTY VALVES FOR PLUMBING PART I - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification Sections, apply to this Section SCOPE A. The valves for the various plumbing systems shall be as hereinafter described in this section. PART II - PRODUCTS 2.01 VALVES GENERAL USE A. The water supply system shall be fitted with valves at points specified or indicated on the Drawings. Provide minimum ¾ hose end drain ball valves with vacuum breakers and threaded caps with chains at all low points of the water system to provide for drainage. Drain valves with caps and chains shall be the Nibco No. T/S HC, bronze, full port, or approved equivalent. Valves shall conform to MSS SP-110. B. All shut-off valves in water lines, 2-1/2 and smaller, except balancing valves, shall be ball type as specified. Larger valves, except balancing valves, shall be gate type as specified. C. All valves for general use shall be Nibco Inc., Milwaukee, Apollo, or Watts. D. All valves shall be designated for a minimum 125 pounds per square inch (S.W.P.), 200 pounds per square inch (W.O.G.). E. Bronze or brass valves, including check valves and balancing valves, shall be made to be dezincification resistant, with metal components in the waterway, or not containing more than 15% zinc in their chemical makeup. Other than balancing valves herein specified, brass shutoff valves of any type will not be acceptable. F. The name or trademark of the manufacturer and the guaranteed working pressure shall be cast or stamped on the body. G. Shutoff Valves: Valves 2-1/2 and smaller shall be ball type, the Nibco No. T/S , or approved equivalent. Valves shall conform to MSS SP-110. The Nibco "Nib-Seal" insulated ball valve, 2-1/2" and smaller, will be acceptable. Valves 3 and larger shall be gate type, the Nibco No. T or F-617-0, or approved equivalent. Valves shall be iron body, bronze mounted, outside screw and yoke, solid wedge, flanged or threaded, Class 125. Valves shall conform to MSS SP The Apollo Series 77C-200-AO full port bronze ball valve, 2 and smaller, with 2 tube extensions and conforming to MSS SP-110, or approved equivalent, will be acceptable for installation with the press tubing assembly system GENERAL DUTY VALVES FOR PLUMBING

4 2. The Nibco No. PF Series bronze ball valve with female press ends, 2 and smaller, will be acceptable for installation with the press tubing assembly, with silicon bronze stem, and plated brass ball. The Nibco Nib-Seal PF NS insulated ball valve will be acceptable. Valve shall conform to MSS SP Ball valves for the PermaLynx System shall be the Victaulic Nvent PermaLynx PL200 Series, or approved equivalent. Valves shall be 2 and smaller. 4. Furnish and install lockable water valves for equipment installations where specified or indicated on the drawing details, Nibco, or approved equivalent. H. Check Valves: Valves in water lines shall be of the horizontal swing check type. Valves with brass discs shall be regrinding type. Valves 3" and smaller shall be Nibco S-413/T-413, or approved equivalent. Valves shall conform to MSS SP-80. Valves 4" and larger shall have iron bodies, bronze mounted, Nibco Figure F-918/T-918, or approved equivalent. Valves shall conform to MSS SP- 71, Type Check valves for the PermaLynx System shall either be the horizontal swing check type as specified with adapters, or the Victaulic Nvent PermaLynx PL500 Series, or approved equivalent. Valves shall be 2 and smaller. I. Backflow Preventers 2" and Smaller (except as herein specified): Reduced pressure zone type, bronze body, Watts Series 909QT-S, with 909-AG air gap fitting piped to nearest drain, Wilkins, or Apollo. Quarter turn, full port ball valves and strainer, with bronze body ball test cocks. A stainless steel backflow preventer will be acceptable. J. Dual Check Valves ¼ thru 3/8 (vending, tea, coffee, or ice machine): Installation shall be of 316 stainless steel body, corrosion-resistant, internal rubber components, for continuous pressure, the Watts Series No. SD-2/SD-3, Wilkins, or Apollo. Valve shall be certified to ANSI/NSF Standard 18, Manual Food and Beverage Dispensing Equipment. Model SD-3 includes an atmospheric port requiring extension of relief piping, and shall be utilized wherever possible. The Watts Model 9BD acceptable. Provide strainer ahead of either installation. K. Double Check Backflow Preventer ½ Size: All bronze body, the Watts Series 7, Wilkins, or Apollo, with plastic check modules, silicone discs, Buna-N seals, and stainless steel springs, suitable for continuous pressure. A Watts Series Cu7 copper-body dual check valve, or equivalent, will be acceptable. Provide strainer ahead. L. Other Backflow Preventers ½ and Smaller: All bronze body, reduced pressure zone type, the Watts No. 009QT-S, with 909-AG air gap fitting piped to nearest drain, Wilkins, or Apollo. Quarter turn, full port ball valves, with bronze body ball test cocks, with tee handle shutoffs, and strainer. A stainless steel backflow preventer will be acceptable. M. Vacuum Breakers: Where specified, noted, or required, vacuum breakers shall be rough bronze, non-removable, the Watts No. 8A, Wilkins, or Chicago Faucet. Watts No. 8AC, or equivalent for chrome vacuum breakers. N. Silent Check Valves 2 and Smaller: Mueller Steam Specialty Model 303 AP, Titan, Nibco, or Apco. Designed to prevent backflow, surge, and water hammer. Body/cap shall include C.I. ASTM A126-B/C.S ASTM A216-WCB. Gasket assembly shall be non-asbestos. Seal, EPDM; stem, 420 stainless steel; disc, brass GENERAL DUTY VALVES FOR PLUMBING

5 ASTM B16; and spring, 302 stainless steel. Working pressure, WOG rating of 200 PSI at 150 degrees F. Suitable for horizontal or vertical flow, threaded. 100% hydrostatically tested. O. Unions: Wrot copper, ground joints, and solder ends, Nibco, or approved equivalent. P. Dishwasher Dual Check Backflow Preventer: All bronze body, Watts Series 7, with plastic check modules, silicone discs, Buna-N seals, and stainless steel springs. A Watts Series Cu7 copper-body check valve, or equivalent, will be acceptable. Provide strainer ahead. Wilkins or Apollo shall be approved equals. Q. Balancing Stations (B.S.): Each balancing station shall consist of a check valve, balancing cock and a thermometer. The Contractor shall balance the various hot water piping systems to maintain no more than 3 degrees temperature differential between all loops. R. Water Heater Thermostatic Temperature Control Valves Water heater thermostatic temperature control valves shall be the Symmons TempControl #5-1000A-NI-W-NW, Leonard, or Lawler, thermostatic controller, rough brass or rough chrome, complete with all components, check stops, volume control shutoff valve, bi-metal mercury-free dial thermometer, wall mounted. Furnish a spare cartridge or main thermostatic control device for each valve to the Owner. S. Relief Valves Relief valves shall be ASME, pressure relief type or combination temperature/pressure relief type, as manufactured by Watts, Kunkle, or Apollo. Extend each relief valve outlet to nearest funnel/floor drain or safe waste PRESSURE REDUCING VALVES A. Pressure reducing valves of 4" size shall be the Watts Series 127 W-WR, iron body, flanged, with No. 223 bronze auxiliary valve installed for low flows, complete with all piping, equalizing lines, needle valve, valves, and gauges, per manufacturer's recommendations, or approved equivalent. B. Pressure reducing valves of 3 size shall be the Watts Series N223F-WR, iron body, flanged, with No. 223 bronze auxiliary valve as described in the preceding paragraph, or approved equivalent. C. Pressure reducing valves of sizes 2-1/2" and smaller shall be of bronze construction, the Watts Series 223 or N223B as required, or approved equivalent. D. Furnish and install a strainer ahead of each pressure reducing valve, of type specified. Reducing valve with integral strainer will be acceptable. E. Comparable pressure reducing valves as manufactured by Apollo, Spirax-Sarco, Watson McDaniel, or equivalent, will be acceptable. F. Provide a pressure gauge on inlet and outlet of each pressure reducing valve POINT-OF-USE MIXING VALVES GENERAL DUTY VALVES FOR PLUMBING

6 A. Individual thermostatic point-of-use mixing valves shall be provided at each sink, lavatory, bank of fixtures, or other appliance requiring hot water. Mixing valves shall be the Symmons Industries MAXLINE Series 5-210, 5-225, or 5-230, Leonard, or Lawler. Valve shall be of brass and bronze body construction, rough chrome or polished chrome finish, minimum flow rate,.5 GPM; brass and stainless steel flow control components, vandal-resistant temperature handle adjustment, integral checks/strainers, and wall mounting bracket. Temperature range, Series 5-210, 85 degrees F. to 160 degrees F; Series and 5-230, 120 degrees F. to 180 degrees F; control of temperature +/- 7 degrees F., Series 5-210; 60 degrees F to 140 degrees F for Series and Fail-safe design. Mixing valve shall conform to ASSE For other locations, set outlet temperatures of mixers as shown or as otherwise directed by the Owner. 2. Furnish and install shutoff valves on inlet and outlet lines of each mixer. 3. Refer to the mixing valve schedule shown on the drawings STOPS A. Each plumbing fixture furnished under this Contract and each piece of special equipment furnished under other contracts or by the Owner shall, unless otherwise shown or specified, be provided with compression stop valves on the water supply lines. On copper or PEX lines, ball valves shall be installed on branch water lines to equipment. Stops shall be finished brass, chrome-plated where exposed and shall be provided with stop control as shown or specified RELIEF VALVES A. Relief valves shall be ASME, pressure relief type or combination temperature/pressure relief type, as manufactured by Watts, Kunkle, or Apollo. Extend each relief valve outlet to nearest funnel/floor drain or safe waste BUTTERFLY VALVES A. Nibco N200 Series, Watts, DeZurik, or approved equivalent, lug style, cast iron, ASTM A126CL.B, bronze body bushing, EPDM rubber liner, aluminum bronze disc, stainless steel one-piece stem, bi-directional flow, and bronze shaft bushing. Valve shall include bubble tight shutoff. Butterfly valves shall meet or exceed requirements of MSS-SP67. PART III EXECUTION 3.01 INSTALLATION A. All valves must be accessible. B. Provide a shutoff valve at the base of up fed water risers and at the top of down fed water risers with a minimum ¾ hose end ball drain valve with vacuum breaker and threaded cap with chain at the base of all water risers, of types specified. C. Each piece of equipment that may have to be removed from the system for repair shall be connected by union or flange, and provided with isolation valves GENERAL DUTY VALVES FOR PLUMBING

7 D. Upon installation, all testable backflow preventers provided by the Plumbing Contractor shall be tested under the Plumbing Contract, in accordance with manufacturer s installation standards, or in accordance with local authorities or utility company having jurisdiction over the installations. All testing shall be completed by persons certified in this type of work. All costs, fees, or charges required for testing shall be included in the Contract price. END OF SECTION GENERAL DUTY VALVES FOR PLUMBING

8 SECTION PLUMBING PUMPS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification Sections, apply to this Section SCOPE A. The pumps shall each be as hereinafter described in this section, of sizes and capacities as noted on the Drawings, and as herein specified. B. The pumps shall each be installed in accordance with the prevailing local plumbing codes. C. All pumps must be accessible. PART 2 - PRODUCTS 2.01 RECIRCULATING PUMPS A. Circulating pumps shall be of all bronze construction or stainless steel construction, lubricated, the Bell and Gossett Booster Series, Taco, or Armstrong. Circulating pump providing circulation between heater and storage tank shall be the B & G Series, or equivalent, furnished by the heater manufacturer for installation under the Plumbing Contract. Provide an aquastat to control each pump operation. Refer to the schedule shown on drawings for capacities and electrical characteristics. B. Power wiring will be furnished and installed under the Electrical Contract. Manual motor starters shall be furnished under the Plumbing Contract and delivered to the Electrical Contractor for installation. All control wiring required to operate aquastats and pumps shall be included under this Contract, of type specified. PART 3 - EXECUTION 3.01 INSTALLATION A. Install each pump in accordance with manufacturer's written recommendations and installation instructions. B. For each recirculating pump, furnish and install a ball shutoff valve and strainer on inlet piping to the pump, with a balancing cock on outlet piping. Furnish and install a check valve where shown. END OF SECTION PLUMBING PUMPS

9 SECTION DOMESTIC HOT WATER HEATING EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification Sections, apply to this Section SCOPE A. Furnish and install a domestic natural gas-fired water heater/storage tank unit, complete with expansion tank equipment and associated accessories, as shown on the Drawings and as herein specified CODE COMPLIANCE A. Water heater shall be installed in accordance with and shall meet or exceed the energy efficiency requirements set forth by applicable portions of The International Energy Conservation Code, and all applicable state, federal, and local codes having jurisdiction. PART 2 - PRODUCTS 2.01 WATER HEATER AND STORAGE TANK (NATURAL GAS) A. Natural gas water heater shall be State Sandblaster model #SBD81 199NE or equal, with a storage capacity of 81 gallons, an input rating of 199,000 BTUs per hour, a recovery rating of 263 GPH at 100ºF rise and a maximum hydrostatic working pressure of 160 psi. The water heater shall be protected against overheating caused by the buildup of scale, film and other sediment by a self-cleaning device, positioned inside the tank so that it directs the flow of inlet water to keep precipitated solids in suspension so that they are removed from the water heater on that or successive draws. Glass-lined water heater shall also be protected against electrolytic corrosion by multiple factory-installed anode rods. In addition, the water heater shall: 1. Be equipped with an integrated control system consisting of a 180ºF adjustable thermostat with upper and lower sensing bulbs. 2. Be equipped with intermittent electronic ignition, a manual reset gas shutoff device, a gas pressure regulator, factory-installed CSA Certified and ASME Rated T&P Relief valve and 2-3/4" x 3-3/4" tank inspection port. 3. Be design-certified by Underwriters Laboratories under Volume III tests for commercial water heaters for delivery of 180º water. 4. Be design-certified by UL (Underwriters Laboratories) to current edition of ANSI Z CSA 4.3 standards governing storage-type water heaters. 5. Meet the thermal efficiency and standby loss requirements of the U.S. Department of Energy and Current Edition of ASHRAE/IESNA Have a 3-year limited warranty as outlined by manufacturer DOMESTIC HOT WATER HEATING EQUIPMENT

10 B. Storage tank shall be a State glass-lined storage tank model #PVG 0120 O0VTA125. Tank shall be 51-3/4 x 28 and have a nominal capacity of 120 gallons. Tank shall have threaded openings. Interior of tank shall be glass-lined with an alkaline borosilicate composition which has been fused to the steel by firing at a temperature of 1600 F. Glass coating shall be continuous over the entire inner surface of the tank. Outer jacket shall have a baked enamel finish. Foam insulation to meet R12.5 minimum thermal insulation requirements of the Department of Energy and current edition of ASHRAE/IESNA Cathodic protection shall be provided. Tank shall have a working pressure of 150 psi EXPANSION TANKS A. Furnish and install an Amtrol Expansion Tank model ST-20VC for the hot water system. Watts DETA Series, Wessels Company or approved equivalent, of required capacity. Tank shall be pre-charged, field adjustable, carbon steel, with FDA approved bladder, stainless steel system connection, and charging valve. Tank must be constructed in accordance with Section VIII of the ASME Boiler and Pressure Vessel Code, with prime painted exterior. Insulate expansion tank as specified. Expansion tank shall be furnished with an ASME pressure relief valve as designated by the Ohio Department of Labor and Industry regulations. Valve inlet to tank RELIEF VALVES A. Refer to Section PART 3 - EXECUTION 3.01 INSTALLATION A. Furnish and install thermometers and pressure gauges at locations shown or specified for the water heating piping and equipment, of types specified. Refer to Section END OF SECTION DOMESTIC HOT WATER HEATING EQUIPMENT

11 b s h m OFFICE PHARMACY 249 STOR. 257 ALL SEASONS PORCH 256 ROOM a r c h i t e c t s, i n c. ROOM TRASH 255 NURSE STATION 251 GATHERING 246 STOR. 250 PANTRY 244 PASS. 245 MATTHEW R. SOTOSKY E LINENS/LAUNDRY 243 PASSAGE central square suite 300 youngstown, ohio (fax) 236 DINING 248 ELEV ROOM ROOM KITCHEN 247 DN 231 STAFF 235 PASS SHOWER 209 PASSAGE 226 EXERCISE 202 EXISTING CHAPEL NO WORK IN THIS AREA TUB STAIR 203 PASS. 208 ROOM TREATMENT 207 ROOM ROOM ROOM ROOM ROOM JAN 225 HEALTH CARE RENOVATIONS 4250 SHIELDS ROAD, CANFIELD, OH DN URSULINE SISTERS OF YOUNGSTOWN Commission Drawn EXISTING CHAPEL, OFFICES, LIVING QUARTERS, CAFETERIA, ETC. - NO WORK rmh Checked cjm Sheet Title INFIRMARY RENOVATION PHASE 5 AREA OF WORK Revisions January 16, 2015 January 22, 2015 Cad Number Date ENGINEERING 1044 N. Meridian Rd., Suite B Youngstown, OH ph:(330) fax:(330) CJL Project # December 17, 2014

12 b s h m a r c h i t e c t s, i n c. 15 central square suite 300 youngstown, ohio (fax) MATTHEW R. SOTOSKY E URSULINE SISTERS OF YOUNGSTOWN HEALTH CARE RENOVATIONS 4250 SHIELDS ROAD, CANFIELD, OH EXISTING CHAPEL, OFFICES, LIVING QUARTERS, CAFETERIA, ETC. - NO WORK Commission Drawn rmh Sheet Title Checked cjm INFIRMARY RENOVATION - PHASE 5 AREA OF WORK Revisions January 16, 2015 January 22, 2015 Cad Number ENGINEERING 1044 N. Meridian Rd., Suite B Youngstown, OH Date December 17, 2014 ph:(330) fax:(330) CJL Project #

SECTION DOMESTIC WATER PIPING SPECIALTIES

SECTION DOMESTIC WATER PIPING SPECIALTIES SECTION 22 11 19 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

A. This Section includes the following domestic water piping specialties:

A. This Section includes the following domestic water piping specialties: SECTION 221119 DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Codes and Standards: A. Plumbing Code Compliance: Comply with applicable portions of National Standard Plumbing Code pertaining to selection and installation of Plumbing materials

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

SECTION SECTION DESIGN REQUIREMENTS

SECTION SECTION DESIGN REQUIREMENTS SECTION 26 09 SECTION 23 05 23 DESIGN REQUIREMENTS GENERAL DUTY VALVES GENERAL INFORMATION 1.1 This section applies to valves for hydronic and steam systems. DESIGN REQUIREMENTS 2.1 Design Criteria a.

More information

VALVES SECTION 15100

VALVES SECTION 15100 VALVES SECTION 15100 PART 1 GENERAL 1.1 DESCRIPTION A. The requirements of this SECTION apply to all Work of this DIVISION where applicable. The valves, materials, and methods herein are generally common

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.01 SECTION INCLUDES A. Water heaters. B. Packaged water heating systems. C. Domestic water heat exchangers. D. Water storage tanks. E. Water softeners. F. Reverse osmosis equipment. G.

More information

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES DIVISION 21 FIRE SUPPRESSION PART 1 GENERAL 1.01 DESCRIPTION A. Provide UL listed, FM approved listed fire protection specialties or accessories as required by either the equipment manufacturer or the

More information

University of Delaware

University of Delaware SECTION 23 21 23_HYDRONIC PIPING SYSTEMS ABOVE GRADE PART 1 GENERAL 1.1 SUMMARY University Contact: Energy & Engineering Group (302) 831-1744 This standard includes hydronic piping requirements for both

More information

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops,

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops, SECTION 23 21 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant. SECTION 218800 - FIRE PROTECTION 1. GENERAL A. Provisions of Division 1, GENERAL REQUIREMENTS, and Section 230000, MECHANICAL GENERAL CONDITIONS, and Section 230050, SEISMIC PROTECTION are a part of this

More information

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008 SECTION 15181 - HYDRONIC SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Air separators B. Expansion tanks C. Pump accessories 1.2 RELATED SECTIONS A. Section - Plumbing Piping Specialties B. Section

More information

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 22 3300 - ELECTRIC, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler SECTION 15181 - HYDRONIC SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler B. Expansion tanks C. Pump accessories 1.2 RELATED SECTIONS

More information

FIRE SUPPRESSION SPRINKLER SYSTEM

FIRE SUPPRESSION SPRINKLER SYSTEM PART 1 GENERAL 1.01 DESCRIPTION A. The provisions of the General Requirements, Supplementary Requirements, and Division 1 apply to the plumbing work specified in this Division. B. The requirements of this

More information

HYDRONIC SPECIALTIES TACO AC(F)-PAX 05/15/2008

HYDRONIC SPECIALTIES TACO AC(F)-PAX 05/15/2008 SECTION 15181 - HYDRONIC SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Air separators B. Expansion tanks C. Pump accessories 1.2 RELATED SECTIONS A. Section - Plumbing Piping Specialties B. Section

More information

SECTION WATER HEATERS

SECTION WATER HEATERS SECTION 15457 WATER HEATERS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: A complete hot water generating system with necessary accessories as indicated on Construction Documents, as specified, and

More information

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS 230500 HVAC BASIC MATERIAL AND METHODS PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230000 Basic HVAC Requirements B. Section 230523 Valves C. Section 230510 Chilled

More information

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL

University of Houston Master Construction Specifications Insert Project Name SECTION DOMESTIC WATER HEATERS PART 1 - GENERAL SECTION 22 14 00 DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section 23 00 10,

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

Design and Construction Standards SECTION PLUMBING EQUIPMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT SECTION 15450 PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES: A. Water heaters. B. Packaged water heating systems. C. Water storage tanks. D. Water softeners. E. Pumps. F. Circulators. 1.2 REFERENCES

More information

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings. SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.

More information

ADDENDUM NO. 3 March 19, 2018

ADDENDUM NO. 3 March 19, 2018 ADDENDUM NO. 3 March 19, 2018 PROJECT: MT. VIEW ELEMENTARY CASSIA SCHOOL DISTRICT NO 151 BURLEY, IDAHO The following addenda apply to the Project Manual and / or Drawings for this project and shall be

More information

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS

D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS D-8 OUTLINE SPECIFICATION FOR HTHW HEAT EXCHANGERS GENERAL: This document provides performance requirements and guideline information for Heat Exchanger equipment for Colorado College only, and is not

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS SECTION 22 36 01 ELECTRIC PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

TECHNICAL. Series 18. Pump Packages

TECHNICAL. Series 18. Pump Packages TECHNICAL S Y S T E M S Series 18 Pump Packages Series 18 Pump Packages Standard Features Close-coupled, end-suction, centrifugal pumps Mounted and wired pump starters Hand-Off-Auto switch for each pump

More information

SECTION DOMESTIC WATER HEATERS

SECTION DOMESTIC WATER HEATERS SECTION 223500 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION METERS AND GAGES FOR PLUMBING PIPING

SECTION METERS AND GAGES FOR PLUMBING PIPING SECTION 220519 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

. ECTION METERS AND GAGES

. ECTION METERS AND GAGES . ECTION 230519 - METERS AND GAGES PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 00 thru 01 Specification

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION PLUMBING - EQUIPMENT

2016 CDM Smith All Rights Reserved July 2016 SECTION PLUMBING - EQUIPMENT PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 22 30 00 PLUMBING - EQUIPMENT A. Furnish all labor and materials required and install the following Plumbing Equipment complete as specified herein and as shown

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO

ACADEMIC SUCCESS CENTER THE COLLEGE AT BROCKPORT STATE UNIVERSITY OF NEW YORK PROJECT NO SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

OKLAHOMA STATE UNIVERSITY - BUILDING DESIGN STANDARDS

OKLAHOMA STATE UNIVERSITY - BUILDING DESIGN STANDARDS Page 1 PART 1 GENERAL 1.1 SUMMARY A. Work of this section includes providing basic mechanical materials including, but not limited to, the following: 1. Valves. 2. Pipe expansion joints. 3. Supports and

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14

Essex County College - West Essex Campus Addition And Renovations dlb # / 11-14 SECTION 210523 - GENERAL-DUTY VALVES FOR WATER-BASED FIRE-SUPPRESSION PIPING PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary

More information

DOMESTIC WATER PACKAGED BOOSTER PUMPS

DOMESTIC WATER PACKAGED BOOSTER PUMPS DIVISION 22 PLUMBING 22 11 16 DOMESTIC WATER PIPING 22 11 19 DOMESTIC WATER PIPING SPECIALTIES 1. To facilitate landscape and other maintenance operations, exterior hose bibs shall be provided at 150 foot

More information

SECTION FUEL-FIRED DOMESTIC WATER HEATERS

SECTION FUEL-FIRED DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8

West District Library Section Campeau Drive, Ottawa SPRINKLER SYSTEMS City of Ottawa Project No. CR Page 1 of 8 City of Ottawa Project No. CR006230 Page 1 of 8 PART 1 - GENERAL 1.1 Reference Standards.1 Conform to the following:.1 Provincial and municipal building and fire regulations as approved by Provincial Fire

More information

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 FUEL-FIRED, DOMESTIC WATER HEATERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

4. Provide brass valve tags marked for the service. See pertinent service specification for valve type.

4. Provide brass valve tags marked for the service. See pertinent service specification for valve type. Section includes various guidelines for valves, instrumentation for process systems, meters, thermometers, and gauges. This design guideline is written to the designer of record (DOR). This guideline is

More information

Engineering Specifications

Engineering Specifications BRONZE BALL VALVES Model 2970 and Model 2970.10 PART 1: GENERAL 1.1 SUMMARY A. General duty press end type bronze ball valve 1.2 DEFINITIONS A. The following are standard abbreviations for valves: 1. WOG:

More information

SECTION ELECTRIC WATER HEATERS

SECTION ELECTRIC WATER HEATERS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION FIRE-SUPPRESSION STANDPIPES PART 1 - GENERAL 1.1 DESCRIPTION Fire-suppression wet and manual dry standpipes. 1.2 SCOPE OF WORK SECTION 21 12 00 A. Design, installation and testing shall be in accordance with NFPA 14 except for specified

More information

UNIVERSITY OF MISSOURI Building Hydronic Piping and Pump Systems 2017 Q3

UNIVERSITY OF MISSOURI Building Hydronic Piping and Pump Systems 2017 Q3 GENERAL: Hydronic systems included in this document are chilled water, heating hot water, dual temperature and glycol based systems. DESIGN GUIDELINES: Design General 1. Where campus steam is available,

More information

Indirect Fired Water Heater

Indirect Fired Water Heater Indirect Fired Water Heater 35-119 Gallon Capacities Features Heavy Duty Construction Hydrastone cement lining provides long tank life Copper-silicon tappings cannot rust or corrode High impact composite

More information

WAL-RICH CORPORATION SINCE 1950

WAL-RICH CORPORATION SINCE 1950 STEAM SPECIALTIES ANGLE STEAM RADIATOR VALVES 0408102 1/2 1 10 0408104 3/4 1 6 0408002 1" 1 4 0408004 1 1/4" 1 2 0408006 1 1/2 1 2 - Brass - Imported STRAIGHT STEAM RADIATOR GATE VALVES 0409002 1" 1 4

More information

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC). SECTION 15555 HORIZONTAL FIRE TUBE BOILERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15510 - Piping (HVAC). 2. 15540 - Pumping Equipment (HVAC). 1.02 SUBMITTALS A. Submit properly identified

More information

Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW

Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW MODEL V Process Water Heater For Industrial Applications All Voltages, Single or Three Phase Up To 88 KW Features Industrial Grade Construction Stainless steel pressure vessel provides maximum service

More information

Series 20 Dual Check Backflow Preventers

Series 20 Dual Check Backflow Preventers Series 20 Dual Check Backflow Preventers Excellence Matters Specify It! A Division of Watts Regulator Company 427 North Market Blvd Suite #9 Sacramento, CA 9584 Phone: 96-928-02 Fax: 96-928-9 www.amesfirewater.com

More information

PROVIDES TEPID WATER FOR EMERGENCY SHOWER

PROVIDES TEPID WATER FOR EMERGENCY SHOWER PROVIDES TEPID WATER FOR EMERGENCY SHOWER Model EMV FEATURES Heavy Duty Construction Hydrastone cement lining provides tank longevity Copper-silicon alloy tappings cannot rust or corrode High impact composite

More information

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY SECTION 22 11 23.13 DOMESTIC WATER PRESSURE BOOSTING PART 1 - GENERAL 1.1 SUMMARY A. Where utility water pressure cannot adequately meet the pressure requirements of the domestic water systems and where

More information

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES

SECTION STEAM AND STEAM CONDENSATE SPECIALTIES SECTION 23 22 18 STEAM AND STEAM CONDENSATE SPECIALTIES PART 1 - GENERAL 1.1 SECTION INCLUDES A. Steam Traps. B. Flash Tanks. C. Condensate Return Units. D. Pressure Reducing Valves. E. Safety Valves.

More information

SECTION HYDRONIC PIPING AND SPECIALTIES

SECTION HYDRONIC PIPING AND SPECIALTIES SECTION 15511 HYDRONIC PIPING AND SPECIALTIES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Pipe Materials. 2. Fittings. 3. Specialty Items. 4. Glycol Antifreeze Protection. 5. Process Cooling B.

More information

DESIGN GUIDELINES AND TECHNICAL STANDARDS

DESIGN GUIDELINES AND TECHNICAL STANDARDS DESIGN GUIDELINES AND TECHNICAL STANDARDS Date of Issuance: January 1, 2014 DIVISION 22 PLUMBING SECTION 22 1118 DOMESTIC WATER DISTRIBUTION SYSTEM 1. General: This section outlines general requirements

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL Division 23 - HVAC 090070 Switzerland Beallsville K-12 Section 23 21 13 HYDRONIC PIPING SECTION 23 21 13 HYDRONIC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and General Provisions of the

More information

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions 4201 Lien Rd Madison, WI 53704 TS-140F Revised 09-10 Owner s Manual Therma-Stor III Heat Recovery System Installation, Operation & Service Instructions Read and Save These Instructions Table Of Contents

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

WATERSTONE ASSISTED LIVING AND MEMORY CARE

WATERSTONE ASSISTED LIVING AND MEMORY CARE DOMESTIC WATER PIPING SPECIALTIES BATON ROUGE, LOUISIANA SECTION 22 11 19 SECTION 22 11 19 - DOMESTIC WATER PIPING SPECIALTIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system.

COHASSET, MA March 6, The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. 23 00 00 HEATING, VENTILATING & AIR-CONDITIONING The following is the HVAC outline specifications, which defines the scope of work of the HVAC system. PART 1 GENERAL 1.1 CODES A. All work installed under

More information

Packaged Semi-Instantaneous Steam Fired Water Heater

Packaged Semi-Instantaneous Steam Fired Water Heater MODEL STX Packaged Semi-Instantaneous Steam Fired Water Heater Shell and Tube Style Heater Features Reliable Only high grade materials used in construction to ensure long operating life Heat exchange pressure

More information

Semi-Instantaneous Indirect Fired Water Heater

Semi-Instantaneous Indirect Fired Water Heater MODEL BWX Semi-Instantaneous Indirect Fired Water Heater Use Boiler Water Or HTHW To Heat Domestic Water Features Reliable Only high grade materials used in construction to ensure long operating life Hydrastone

More information

BRADLEY HALO EMERGENCY PLUMBING FIXTURES

BRADLEY HALO EMERGENCY PLUMBING FIXTURES BRADLEY HALO EMERGENCY PLUMBING FIXTURES Bradley Halo Emergency Plumbing Fixtures are a new generation in safety equipment, featuring separate supply and waste piping to eye/face wash, ergonomic hand activation

More information

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 SECTION 232116 - HYDRONIC PIPING SPECIALTIES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - Systems and Equipment. Page 238239-1 SECTION 238239 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

SECTION DOMESTIC WATER AND DRAINAGE PIPING SPECIALTIES

SECTION DOMESTIC WATER AND DRAINAGE PIPING SPECIALTIES PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Specification Sections, apply to this Section. B. Related Sections

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

SECTION HEATING BOILERS

SECTION HEATING BOILERS SECTION 23 52 00 HEATING BOILERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes boilers, controls and boiler trim, steam and condensate connections, hot water connections, fuel burning system and connections,

More information

A. General provisions and other plumbing systems are specified in other Sections of Division 22.

A. General provisions and other plumbing systems are specified in other Sections of Division 22. PART 1: GENERAL 1.01 DESCRIPTION: A. General provisions and other plumbing systems are specified in other Sections of Division 22. B. This Section covers plumbing water systems and equipment. C. See Section

More information

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model BWXP OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER Electric Heater Company Base Model "BWXP" HUBBELL ELECTRIC HEATER COMPANY P.O. BOX 288 STRATFORD, CT 06615 PHONE: (203)

More information

A. This Section includes the following emergency plumbing fixtures:

A. This Section includes the following emergency plumbing fixtures: Page 224500-1 SECTION 224500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES SECTION 15300 FIRE PROTECTION PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. Dartmouth College is currently insured by Factory Mutual. References to the owner s insurance company in this specification

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards Date Description of Change Pages / Sections Modified ID 6/15/16 Entire document - mgl44 PART 1 - INTRODUCTION 1.1 PURPOSE A. This section is intended to define the general installation and minimum product

More information

Packaged Steam Fired Water Heater

Packaged Steam Fired Water Heater MODEL ST Packaged Steam Fired Water Heater Utilizes Steam To Heat Domestic Water, Semi-Instantaneous or Storage Type Heaters Features Reliable Packaged System Only high grade materials used in construction

More information

PROJECT NAME: DPW Idaho State University Liberal Arts Building Chiller Replacement

PROJECT NAME: DPW Idaho State University Liberal Arts Building Chiller Replacement ADDENDUM NO.2 April 6, 2018 PROJECT NAME: DPW 18 223 Idaho State University Liberal Arts Building Chiller Replacement The data included hereinafter is issued by the Engineer (Engineered Systems Associates,

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

DIVISION 23 HVAC Hydronic Piping Systems

DIVISION 23 HVAC Hydronic Piping Systems General Information Programming/ Design Bidding/ Preconstruction Installation/ Construction Closeout/ Warranty QA/QC Checklist Construction Services DIVISION 23 HVAC 23 21 13 Hydronic Piping Systems 01

More information

Internal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR

Internal Use Only INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS IAPMO GUIDE CRITERIA FOR ELECTRICAL OR HIGH-DENSITY MAGNETIC ANTI-SCALE OR WATER CONDITIONING APPLIANCE IGC 91-2009 1. PURPOSE 1.1 The purpose

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

ASME Packaged Electric Water Heater

ASME Packaged Electric Water Heater MODEL SH & H ASME Packaged Electric Water Heater 15-1600 KW - All Voltages & Phases, 80-5000 Gallon Capacity Features Reliable Packaged System Only high grade materials used in construction to ensure long

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21 Division 21: FIRE SUPRESSION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM Table of Contents 1 Division 21 SECTION 21 1313 WET-PIPE SPRINKLER PROTECTION SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A.

More information

Revitalize Building Mechanical Systems (4619)

Revitalize Building Mechanical Systems (4619) SECTION 235216 FIRE-TUBE CONDENSING BOILERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

STORAGE TANK INSTALLATION and OPERATION MANUAL

STORAGE TANK INSTALLATION and OPERATION MANUAL LST-I-O 100161529_2000014416 Rev F STORAGE TANK INSTALLATION and OPERATION MANUAL LOW LEAD CONTENT The information contained in this manual is intended for use by qualified professional installers, or

More information

Owner s Manual Therma-Stor II Heat Recovery System

Owner s Manual Therma-Stor II Heat Recovery System PO Box 8680 Madison, WI 53708 TS-138C Revised 8/08 Owner s Manual Therma-Stor II Heat Recovery System Installation, Operation & Service Instructions Read and Save These Instructions Table Of Contents 1.

More information

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section PART 1 - GENERAL 1.00 GENERAL PROVISIONS A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section 1.01 DESCRIPTION OF WORK A. Work Included: Provide

More information

SECTION METERS AND GAGES FOR HVAC PIPING

SECTION METERS AND GAGES FOR HVAC PIPING SECTION 23 0519 METERS AND GAGES FOR HVAC PIPING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Thermometers. 2. Gages. 3. Test plugs. 4. Thermowells. 1.2 SUBMITTALS A. Product Data: For each type

More information

BRADLEY CORPORATION DOMESTIC WATER PIPING SPECIALTIES Page 1 of 9

BRADLEY CORPORATION DOMESTIC WATER PIPING SPECIALTIES Page 1 of 9 BRADLEY THERMOSTATIC MIXING VALVES Bradley Corporation, a leader in the manufacture of fixtures and plumbing products, produces four lines of thermostatic mixing valves (TMVs). Bradley Navigator High-Low

More information

Gas Station & C Store SECTION CWM Job No

Gas Station & C Store SECTION CWM Job No SECTION 21 1300 - PART 1 - GENERAL 1.1 WORK INCLUDED A. Provide labor, materials, equipment and services to perform operations required for the complete installation and related Work as required in Contract

More information

Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures.

Valve Pressure and Temperature Ratings: Not less than indicated and as required for system pressures and temperatures. SECTION 220523 - VALVES PART 1 - GENERAL 1.1 SUMMARY This Section includes the following general-duty valves: 1. Copper-alloy ball valves. 1.2 SUBMITTALS Product Data: For each type of valve indicated.

More information

DIVISION 21 - FIRE SUPPRESSION

DIVISION 21 - FIRE SUPPRESSION DIVISION 21 - FIRE SUPPRESSION DESIGN CRITERIA It is the policy of UC Davis to install fire sprinkler systems in all new construction/facilities. If the building is classified as a pole barn, shed, carport,

More information