Keith Gillard London Luton Airport Operations Navigation House Airport Way Luton, Beds. Our ref: B.No Date:

Size: px
Start display at page:

Download "Keith Gillard London Luton Airport Operations Navigation House Airport Way Luton, Beds. Our ref: B.No Date:"

Transcription

1 Keith Gillard London Luton Airport Operations Navigation House Airport Way Luton, Beds. Our ref: B.No Metro House Blackfriars Road London SE1 8HA Fire risk assessment: Building 100, Proctor Way, Luton, Beds. The attached fire risk assessment identifies the following items as requiring attention for compliance with the relevant fire safety legislation. Should you wish us to quote please tick the appropriate boxes and either fax this form back to us on or alternatively contact us at the above address. Metro services required in the fire risk assessment: Please quote All of the items below Training courses (initial and 6 monthly refresher training) including fire extinguishers Provide additional Emergency Escape Lighting Units Provide Signs and Notices Signed: Name: Contact telephone number:

2 Fire Risk Assessment TUI Building 100 Proctor Way Luton Bedfordshire LU2 9LU Click Here and Insert Building Picture Assessment Date 9 th February 2012 Recommended Re-View Date February 2013 Assessor Bruce Batten Metro Safety Blackfriars Road London SE1 8HA Tel: Fax:

3 SUMMARY RISK RATING: NORMAL RISK Priority Rating Grade Guideline Time Frames Top Priority A* High risk items to be resolved, or work initiated within 24 hours. High Priority A Items that should be resolved, or work initiated within 7 days. Medium Priority B Issues that should be resolved, or work initiated within 3 months. Low Priority C Issues that should be resolved, or work initiated within a fixed time scale. NUMBER OF SIGNIFICANT FINDINGS BY PRIORITY RATING Section Grade No Section Grade No Ignition Sources Persons at Risk Fire Limitation Means of Escape Emergency Escape Lighting A* A* A A Signs & Notices B 1 B 4 C C A* A* A A Fire Fighting Equipment B 1 B 1 C C A* A* A A Fire Procedures/Training B 1 B 4 C C A* A* A A Testing & Maintenance B 2 B 3 C C A* A B 1 C Metro Safety SO : Building 100, Luton Airport Page 2

4 Table of contents Section One Significant Findings and Action Plan... 4 Fire Hazards... 4 Ignition Sources... 4 Persons at Risk... 4 Measures to Limit Fire Spread and Development... 5 Means of Escape... 5 Emergency Escape Lighting... 6 Signs & Notices... 6 Fire Fighting Equipment... 8 Fire Procedures and Training... 9 Testing and Maintenance Section Two - Premises Details Premises Description & Use Construction Contribution to Fire Risk Heating System Fire Hazards History of Fires Persons at Risk Fire Safety Provisions Fire Alarm System (Detection and Warning) Means of Escape Emergency Escape Lighting Signs and Notices Fire Fighting Equipment Fire Evacuation Procedures & Fire Safety Training Fireman s Switch Lifts Lightning Conductor Sprinkler System Dry/Wet Risers Smoke Extract/Smoke Vents Section Three - Fire Hazards Sources of Ignition Combustible Materials Persons at Risk Measures to Limit Fire Spread and Development Section Four - Fire Safety Provisions Fire Detection & Warning Means of Escape Fire Fighting Equipment Fire Procedures and Training Testing and Maintenance Section Five - General Information Scope of Survey Format Qualifications Re-views Why Assess Fire Risk? Legislation and Statutory Instruments Report Completion Enforcement Definitions Responsible Person Competent Person Relevant Person Young Person Technical Terms Used Means of Escape Section Six - Appendices Appendix 1: Fire Safety Routines Appendix 2: Fire Safety & Evacuation Recommendations Appendix 3: Portable Electric Appliance Test Guidelines Metro Safety SO : Building 100, Luton Airport Page 3

5 Section One Significant Findings and Action Plan The following action plan should be implemented by a designated responsible person. Fire Hazards Ignition Sources The storage in the store room at the end of the main corridor is too close to the light fittings. This storage should be reduced so that there is a 500mm clearance to the light fittings. Persons at Risk Contractors should be booked in and out of the premises at reception. A set of fire instructions appropriate to contractors should be kept at reception for them to read when booking in. Metro Safety SO : Building 100, Luton Airport Page 4

6 Measures to Limit Fire Spread and Development There is a fire separating wall between the warehouse and the office area. This has penetrating holes which should be infilled with fire resisting material. The door to the rear office area should be replaced with a fire resisting self-closing door fitted with smoke seals and intumescent strips. The fire door half way along the warehouse through the fire resisting wall should be fitted with intumescent strips, smoke seals and a selfclosing device. Both of these doors should be signed FIRE DOOR KEEP SHUT at eye level on both faces. Holes Complete Doors to be completed Fire door keep shut signs - complete Means of Escape The fire escape routes in the warehouse to the fire exits should be kept clear at all times. To aid this, these routes should be clearly marked on the warehouse floor. The fire exits along the rear side of the warehouse should be opened on a monthly basis. Some of these doors appear to be in a poor state of repair and may need replacing. Monthly checks to be introduced. All doors to be replaced with metal doors. Metro Safety SO : Building 100, Luton Airport Page 5

7 Emergency Escape Lighting Additional emergency escape lighting units should be provided in the following locations: To the rear external means of escape walkway. Order placed Signs & Notices Due to the storage in the warehouse, the fire exit signs are not visible. Therefore, high level signs should be provided above each of the fire exits from the warehouse. Fire action notices should be provided adjacent to all the break glass call points in the building. Metro Safety SO : Building 100, Luton Airport Page 6

8 Metro Safety SO : Building 100, Luton Airport Page 7

9 A Fire Exit Keep Clear notice should be provided on the external face of all the final exit doors from the building. There is a large step from the fire exits to the rear of the warehouse. There should be a suitable warning sign on the inside of the warehouse adjacent to each fire exit indicating CARE LARGE STEP DOWN. Fire Fighting Equipment The fire extinguisher at the fire point of the exit from the main office corridor is missing. This should be replaced by a 9 litre foam spray fire extinguisher. Metro Safety SO : Building 100, Luton Airport Page 8

10 Fire Procedures and Training Staff should be trained in fire safety on induction and then every 6 months. This should include the use and hazards of fire extinguishers, and it should be recorded in a logbook. A formal written emergency plan is not required but a suitable fire procedure should be formulated, issued to all staff, and a copy displayed on a staff notice board. This with suitable fire action notices at the fire alarm call points would be considered a suitable emergency plan for these premises. Method statements as well as fire risk assessments for all works carried out should be obtained from the contractors, in particular for any proposed hot work. Metro Safety SO : Building 100, Luton Airport Page 9

11 A fire drill should be carried out every 6 months and the result recorded in a log book. Testing and Maintenance Exit doors not in regular use should be opened monthly to ensure availability and ease of opening. A monthly visual check should be made of the fire fighting equipment to ensure that it is correctly located and available for immediate use. Metro Safety SO : Building 100, Luton Airport Page 10

12 The redundant fireman s switch should be removed. Metro Safety SO : Building 100, Luton Airport Page 11

13 Section Two - Premises Details Consultation on these premises was with Keith Gillard / Dave Brundell. Premises Description & Use The premise is a single storey detached building and is approximately 50m by 40m. It is primarily of traditional construction with concrete floors and is situated on an out of town estate The building is used as office and warehouse Construction Contribution to Fire Risk There were no apparent aspects of the premises construction that made a significant contribution to the fire risk. Heating System The heating system was oil powered hot air with the boiler located externally. Fire Hazards This is a no smoking building. There is a no significant arson risk. Housekeeping is good. The likelihood of fire within the premises is considered to be normal. History of Fires There were no reported recent fires in these premises. Persons at Risk The maximum number of relevant persons within the premises was estimated at 3 persons. At the time of the assessment no lone or remote working was reported as taking place in these premises. At the time of the assessment late working was reported as currently taking place in these premises. At the time of the assessment there were no persons working in the premises with significant disabilities (sight / hearing / movement / learning difficulties). All occupants are able to safely use the escape routes in the event of fire. Fire Safety Provisions Fire Alarm System (Detection and Warning) There was a fire alarm on site. This consisted of a control panel with battery back up located in entrance lobby with break glass call points and smoke detection throughout the office area with beam detection in the warehouse. The fire alarm is single stage with sirens as the warning signal. Means of Escape Means of escape from this building are fire exits situated at the front, side and rear of the building. Emergency Escape Lighting There was emergency escape lighting in the premises This consisted of self-contained units throughout. Signs and Notices Suitable and sufficient fire safety signage is not provided. The fire safety signage already provided is suitably located. Metro Safety SO : Building 100, Luton Airport Page 12

14 Fire Fighting Equipment There were fire extinguishers in the premises. The fire extinguishers are suitable and sufficient. There were no hose reels in the premises. Fire Evacuation Procedures & Fire Safety Training Appropriate fire drills and debriefs are not being carried out. The fire assembly point shown on the fire action notices is suitable. The Fire Assembly Point is outside building 99. Fireman s Switch There was a redundant fireman s switch on site. Lifts Lifts are not provided. There was no fire fighting lift / evacuation lift on site. Lightning Conductor There was no lightning conductor on site. Sprinkler System There was no sprinkler system on site. Dry/Wet Risers There were no dry risers on site. Smoke Extract/Smoke Vents There was no smoke /fume extract system in the premises. Metro Safety SO : Building 100, Luton Airport Page 13

15 Section Three - Fire Hazards Sources of Ignition Ignition sources Smokers Materials Naked Flames Electrical Heaters Gas Heaters Oil-Fired Heaters Hot Processes Cooking Engines or Boilers Machinery Faulty or Misused Electrical Equipment Lighting Hazards Hot Surfaces Blocked Equipment Ventilation Significant Friction Significant Static Electricity Significant Risk of Arson Risk Rating: Normal Yes No N/A Existing control measures Allowed outside only. Microwave and toaster in a tea area. Fire extinguisher provided. Heat detection provided. Stand alone oil fired hot air blower in warehouse. External oil powered boiler. Security checks. Card operated entrance security doors Metro Safety SO : Building 100, Luton Airport Page 14

16 Combustible Materials Combustibles Yes No N/A Existing control measures Flammable Liquids Flammable Gases Paper & Card Normal amounts for the business carried out. Plastics, Rubber & Foam Textiles Unacceptable Furniture Waste Materials Packaging Material Inappropriate Storage Risk Rating: Normal Persons at Risk Normal amounts for the business carried out. Rubbish removed weekly Daily emptying of waste bins. External waste skips 6/10 metres from the building. Normal amounts for the business carried out. Type of risk Yes No N/A Existing control measures Sleeping Accommodation Large Numbers of Relevant Persons. Unfamiliar Building Layout Long Escape Routes Lone or Remote Working Early/Late Automatic fire detection throughout the premises. Working Contractors Floor checked on evacuation. Signed in at reception. High Fire Risk Areas Persons with Special Needs Risk Rating: Normal Measures to Limit Fire Spread and Development Personal Emergency Evacuation Plan (PEEP) for staff (when applicable). Type of risk Yes No N/A Existing control measures Services, Ducts & Fire doors kept locked shut. Shafts Clear of all storage. Unsatisfactory Fire Resistance/ Stopping Inappropriate Wall Class O wall linings on escape routes. & Ceiling Linings Risk Rating: Normal Metro Safety SO : Building 100, Luton Airport Page 15

17 Section Four - Fire Safety Provisions Fire Detection & Warning Provisions Yes No N/A Existing control measures Adequate Fire Automatic fire detection throughout. Detection Adequate Fire Audible alarm throughout the building. Warning Vibrating pager issued as required. Backup Power Batteries incorporated within the fire alarm panel. Supply Staff Awareness Weekly tests. Adequate Fire Action Notices Management of Unwanted Fire Signals Appropriate detector(s) for the risk. All unwanted signals investigated by the manager and remedial action taken. Risk Rating: Normal Means of Escape Provisions Yes No N/A Existing control measures Suitable Time & Distance To Place of Safety Sufficient Exits & Suitably Located Suitable Size & Exit Type Satisfactory Disabled Egress Availability of Exit Routes Suitable Floor & Partition Layout Distances to exits are within recognised standards for the building use. (Both dead end and two way travel distances are satisfactory). Distances to exits are within recognised standards for the building use. Exit widths are sufficient for the anticipated occupancy figures in the sales floor and elsewhere and open in the direction of escape. Reasonable alternative means of escape provided for disabled occupants. Doors on exit routes are provided with emergency fastenings or are free from fastenings. Access rooms provided with smoke detection. Suitable Protection To Escape Route All fire doors to be self closing or locked shut. Smoke detection provided in corridor or rooms adjacent. Suitable Exit Signage Most routes adequately signposted. Adequate Fire Safety Signage Suitable Lighting Emergency escape lighting provided throughout escape routes, toilets and plant rooms. Effective normal lighting throughout. Escape Routes Clear of Obstructions Staff Awareness Risk Rating: High Metro Safety SO : Building 100, Luton Airport Page 16

18 Fire Fighting Equipment Provisions Yes No N/A Existing control measures Suitable & Sufficient Correctly As part of a fire point. Located Adequately Sign Red bodies. Posted Clearly visible. Adequate Staff Instruction & Training Risk Rating: Normal Fire Procedures and Training Provisions Yes No N/A Existing control measures Fire Emergency Plan Available Suitable & Sufficient Adequately Sign Posted Adequate Staff Instruction & Training Adequately Recorded Risk Rating: Normal Fire action notices and a suitable method of accounting for all staff/visitors at the assembly point. Metro Safety SO : Building 100, Luton Airport Page 17

19 Testing and Maintenance Provisions Yes No N/A Existing control measures Means of Escape Fire Detection & Warning Tests Sprinklers Tests Emergency Escape Lighting Tests Adequately Recorded Fire Detection & Warning Maintenance Emergency Escape Lighting Maintenance Fire Fighting Equipment Sprinkler Maintenance Adequately Recorded Portable Electrical Appliance Tests 5 yr Electrical Test Certificate Annual Inspection of Gas Heating Appliances Annual Inspection of Oil Fired Boiler Smoke Extract / Smoke Vents Adequately Recorded Risk Rating: Normal Sequential weekly tests. Monthly tests. Records held at head office. Carried out by Honeywell. Carried out by Honeywell. Annual service by Honeywell. Records held at head office. Records held at head office. Metro Safety SO : Building 100, Luton Airport Page 18

20 Section Five - General Information Scope of Survey An inspection of the fire safety provisions within this premises has been carried out and supplemented by an inspection of the occupants normal work practices and safety procedures. A fire risk assessment has then been undertaken on behalf of the occupier and this report prepared. Ceiling voids and inaccessible spaces were not checked for fire stopping or compartmentation, as this would involve invasive inspection. The report has been set out so as to provide practical solutions for compliance with the relevant fire safety legislation and associated technical codes and guides. Format The report is split into six sections. Section One Section Two Section Three Section Four Section Five Section Six Qualifications Significant findings and action plan Premises details Fire hazards Fire safety provisions General information Appendices Metro Safety undertakes assessments on actual and foreseeable eventualities as evident or likely, relating to any particular facility or premises. All assessments are valid and applicable at the time of the assessment. Metro Safety cannot be held liable for any subsequent changes to legislation, the premises, or their use that may alter the assessments. Metro Safety is not responsible for instigating the work specified in this risk assessment. It is the duty of the responsible person to action any significant findings and failure to do so may result in enforcement action by the enforcing authorities (Fire and Rescue Services). Re-views Fire risk assessments can become quickly out-dated, dependent on the nature of the property and the activities undertaken. It is important that reviews are undertaken regularly and whenever there are any significant changes in the people, plant, processes or premises. In general, the minimum recommended frequency for the review of a premise is annual. For a high-risk premises a 6 monthly review is likely to be more appropriate, until such time as the risk is reduced to normal. Why Assess Fire Risk? The Regulatory Reform Order (Fire Safety) 2005 requires this building to have a suitable and sufficient fire risk assessment undertaken and regularly reviewed. The significant findings of fire risk assessments must be in writing for all companies with five or more staff. Legislation and Statutory Instruments The following legislation where relating to fire safety has been taken into consideration for the purposes of the fire risk assessment of the common parts at the above building and was deemed to be applicable at the time of the assessment. You should be aware that only Acts of Parliament and Statutory Instruments have the force of law and that only courts can authoritatively interpret the law. The Regulatory Reform ( Fire Safety Order) 2005 The Housing Act 2004 The Building Regulations 2000 Metro Safety SO : Building 100, Luton Airport Page 19

21 The Health & Safety (Safety Signs and Signals) Regulations 1996 The Management of Health and Safety at Work Regulations 1999 The above legislation and details of fire safety publications can be obtained from: HSE Books Tel: or The Stationary Office on Tel: Report Completion Assessed By: Bruce Batten Checked By: Alan Wilson Responsible Person: Enforcement One of the following pieces of legislation will be relative to this report. The Regulatory Reform (Fire Safety) Order 2005 requires this premise to have a suitable and sufficient fire risk assessment undertaken and regularly reviewed. The Fire (Scotland) Act 2005 Fire Safety (NI) 2010 The local fire and rescue authority (the fire and rescue service) will be responsible for the enforcement of the above order. Eire. The Fire Services Act 1981 and 2003 Regulation 17 of the Management of the Health and Safety Regulations 2003 (For IOM) The Isle of Man Government Health & Safety at Work Inspectorate will be responsible for the enforcement of the above regulation. Definitions Responsible Person The person with overall control of the building; An employer with control of the workplace; Competent Person A competent person should have sufficient training, experience, knowledge and other qualities to properly implement the assessment and who know their limitations. Relevant Person Relevant persons within your buildings / curtilage for whom you are responsible are: employees; visitors; customers; public; residents; voluntary workers; contractors. Young Person Any employed person under the age of eighteen years. Note: There is a duty placed upon the Responsible Person to inform Relevant Persons and the guardians of Young Persons of the relevant significant findings of this Fire Risk Assessment. Metro Safety SO : Building 100, Luton Airport Page 20

22 Technical Terms Used Means of Escape Access Room: Means a room that forms the only escape route from an inner room. Accommodation Stair: A stair, additional to that or those required for escape purposes, provided for the convenience of occupants. Alternative Escape Routes: Escape routes sufficiently separated by either direction or space, or by fire-resisting construction, to ensure that one is still available should the other be affected by fire. Alternative Exit: One of two or more exits each of which is separated from the other; Automatic Release Mechanism: A device that will allow a door held open by it to close automatically in the event of each or any one of the following: a. Detection of smoke by automatic apparatus suitable in nature, quality and location; b. Operation of a hand operated switch fitted in a suitable position; c. Failure of electricity supply to the device, apparatus or switch; d. Operation of the fire alarm system; Automatic Self-Closing Device: A device, which is capable of closing the door from any angle and against any latch / lock fitted to the door. Note: Rising butt hinges do not meet the above criteria and are not acceptable. Dead-End: Area from which escape is possible in one direction only; Direct Distance: The shortest distance from any point within the floor area, measured within the external enclosures of the building, to the nearest storey exit ignoring walls, partitions and fittings, other than the enclosing walls/ partitions to protected stairways. Distance of Travel: Means the actual distance that a person needs to travel between any point in a building and the nearest storey exit. Doors, Fastenings: In general, doors on escape routes (whether or not the doors are fire doors), should either not be fitted with lock, latch or bolt fastenings, or they should only be fitted with simple fastenings that can be readily operated from the side approached by people making an escape. The operation of these fastenings should be readily apparent and without the use of a key and without having to manipulate more than one mechanism. This is not intended to prevent doors being fitted with hardware to allow them to be locked when the rooms are empty. There may also be situations such as hotel bedrooms where locks may be fitted that are operated from the outside by a key and from the inside by a knob or lever etc. In buildings where security on final exit doors is an important consideration, such as in some Assembly and Recreation or Shop and Commercial uses, panic bolts may be used. In non-residential buildings it may also be appropriate to accept on some final exit doors locks for security that are used only when the building is empty. In these cases the emphasis for the safe use of these locks must be placed on management procedures. Doors, Direction of Opening: The door of any doorway or exit should, if reasonably practicable, be hung to open in the direction of escape, and should always do so if the number of persons that might be expected to use the door at the time of a fire is more than 60. Note: With respect to industrial activities where there is a very high fire risk with potential for rapid fire growth, there will be a requirement for the door to open in the direction of escape for lower numbers than 60. Metro Safety SO : Building 100, Luton Airport Page 21

23 Doors, Revolving and Automatic: Revolving doors, automatic doors and turnstiles can obstruct the passage of persons escaping. Accordingly, they should not be placed across escape routes unless: a. They are to the required width and are automatic doors and either they are: i. Arranged to fail safely to outward opening from any position of opening, or ii. Provided with a monitored failsafe system for opening the doors if the mains supply fails or iii. They fail safely to the open position in the event of power failure; or b. Non-automatic swing doors of the required width should be provided immediately adjacent to the revolving or automatic door or turnstile. Emergency Lighting: Means that part of the lighting system, provided for use when the supply to the normal lighting fails ensures that the MEANS OF ESCAPE can be safely and effectively used at all material times; Escape Route, Lighting of: All escape routes should have adequate artificial lighting. Lighting to escape stairs should be on a separate circuit from that supplying any other part of the escape route. Standards for the installation of a system of escape lighting are given in BS 5266: Part 1 Emergency lighting Code of practice for the emergency lighting of premises other than cinemas and certain other specified premises used for entertainment and CP 1007 Maintained lighting for cinemas. Escape Route: Route forming that part of the means of escape from any point in a building to a final exit. Unprotected and Protected: The unprotected part of an escape route is that part which a person has to traverse before reaching either the safety of a final exit or the comparative safety of a protected escape route, i.e. a protected corridor or protected stairway. Unprotected escape routes should be limited in extent so that people do not have to travel excessive distances while exposed to the immediate danger of fire and smoke. Even with protected horizontal escape routes the distance to a final exit or protected stairway needs to be limited because the structure does not give protection indefinitely. Fire Door: A door or shutter, provided for the passage of persons, air or objects, which together with its frame and furniture as installed in a building, is intended (when closed) to resist the passage of fire and/or gaseous products of combustion, and is capable of meeting specified performance criteria to those ends. (It may have one or more leaves, and the term includes a cover or other form of protection to an opening in a fire-resisting wall or floor, or in a structure surrounding a protected shaft). All fire doors should have the appropriate performance under test to BS 476: Part 22, in terms of integrity for a period of minutes, e.g. FD30. A suffix (S) is added for doors where restricted smoke leakage/spread at ambient temperatures is needed. There is no current Standard for smoke control doors, although a standard test has been laid down in BS 476Part All fire doors should be fitted with an automatic positive action self-closing device except for fire doors to cupboards and to service ducts, which are normally kept locked shut. Final Exit: Means the termination of an escape route from a building giving direct access to a PLACE OF SAFETY such as a street, passageway, walkway or open space, and sited to ensure that persons can disperse safely from the vicinity of the building and the effects of fire. Fire Resistance: When planning fire precautions and MEANS OF ESCAPE in premises it is usual to have regard to the FIRE RESISTANCE of the elements of structure, e.g. walls, floors, doors etc. In some premises it may not always be possible to achieve the minimum standards set out. Therefore in such circumstances, compensating features are required such as a reduction in the DISTANCE OF TRAVEL or the provision of other fire safety installations. Fire / Smoke Stopping: This is a seal provided to close an imperfection of fit or design tolerance between elements or components to restrict fire, smoke and heat transference. Metro Safety SO : Building 100, Luton Airport Page 22

24 Inner Room: Means a room from which escape is possible only by passing through an ACCESS ROOM. Lifts, Evacuation: In general it is not appropriate to use lifts when there is a fire in the building because there is always the danger of people being trapped in a lift that has become immobilised as a result of the fire. However, in some circumstances a lift may be provided as part of a management plan for evacuating disabled persons. In such cases the lift installation needs to be appropriately sited and protected, and needs to contain a number of safety features that are intended to ensure that the lift remains usable for evacuation purposes during the fire. Guidance on the necessary measures is given in BS 5588: Part 8 Fire precautions in the design, construction and use of buildings, Code of practice for means of escape for disabled people. Means of Escape: This is the structural means whereby a safe route is provided for persons to travel from any point in a building to a PLACE OF SAFETY beyond the building without the need for outside assistance. Means of Escape, Criteria For: The basic principles for the design of means of escape are: a. There should be alternative means of escape from most situations; b. Where direct escape to a place of safety is not possible, it should be possible to reach a PLACE OF RELATIVE SAFETY, such as a protected stairway, which is on a route to an exit, within a reasonable travel distance. In such cases the means of escape will consist of two parts, the first being unprotected in accommodation and circulation areas, and the second in protected stairways (and in some circumstances protected corridors). The ultimate place of safety is the open air clear of the effects of the fire. However, in modern buildings, which are large and complex, reasonable safety may be reached within the building, provided suitable planning and protection measures are incorporated. Occupant Capacity: The occupant capacity of a room, storey, building or part of a building is: a. The maximum number of persons it is designed to hold; or b. The number calculated by dividing the area of room or storey(s) (m2) by a floor space factor (m2 per person). Note: area excludes stair enclosures, lifts, sanitary accommodation and any other fixed part of the building structure (but counters and display units etc should not be excluded). Place of Safety: Means a place beyond the building in which a person is no longer in danger from fire. Protected Corridor: This means a corridor which is protected by FIRE RESISTING construction from a fire in adjoining accommodation. Protected Lobby: This means a FIRE-RESISTING enclosure providing access to a PROTECTED STAIRWAY via two sets of FIRE RESISTING self-closing doors and into which no rooms open other than toilets or lifts. Protected Route: This means a route having an adequate degree of protection from fire, including walls (other than any part that is an external wall of a building), doors, partitions, ceilings and floors separating the route from the remainder of the building. Protected Stairways: Protected stairways are designed to provide virtually fire sterile areas that lead to places of safety outside the building. Once inside a protected stairway, a person can be considered to be safe from immediate danger from flame and smoke. They can then proceed to a place of safety at their own pace. To enable this to be done, flames, smoke and gases must be excluded from these escape routes, as far as is reasonably possible, by fire-resisting structures or by an appropriate smoke control system, or by a combination of both these methods. Metro Safety SO : Building 100, Luton Airport Page 23

25 Protected Stairways, Exits From: Every protected stairway should discharge: a. Directly to a final exit; or b. By way of a protected exit passageway to a final exit. Note: Doors may be situated in the enclosures to the passageway, and lobbies will be needed to these doorways if the main stairway is served by lobbies. Protected Stairways, Use Of Space Within: A protected stairway needs to be free of potential sources of fire. Consequently, facilities that may be incorporated in a protected stairway are limited to the following: a. Sanitary accommodation or washrooms, so long as the accommodation is not used as a cloakroom. A gas water heater or sanitary towel incinerator may be installed in the accommodation but not any other gas appliance; b. A lift well may be included in a protected stairway, if it is not a fire fighting stair; c. A reception desk or enquiry office area at ground or access level, if it is not in the only stair serving the building or part of the building. The reception or enquiry office area should not be more than 10m2 in area d. Cupboards enclosed with fire-resisting construction, if it is not in the only stair serving the building or part of the building. Responsible Person: A Responsible Person is the employer in relation to a workplace or a person who has control as occupier or otherwise in connection with the carrying on of a trade, business or other undertaking (for profit or not). The responsible person can also be the owner of the premises where the person in control does not have control in connection with the carrying on of a trade, business or other undertaking. In a multi tenanted building there will be Responsible Persons, who will be from each of the tenancies and the Landlord/Owner or their representative having control over the common parts and plant room areas. Room: This means an enclosed space within a building that is not used solely as a circulation space. (The term includes not only conventional rooms, but also cupboards that are not fittings, and large spaces such as warehouses, and auditoria. The term does not include voids such as ducts, ceiling voids and roof spaces). Storey Exit: Means an exit through which persons are no longer at immediate risk from the effect of fire and includes a FINAL EIT, an exit to a PROTECTED LOBBY or PROTECTED STAIRWAY (including an exit leading on to an external stairway), and an exit provided for MEANS OFESCAPE through a COMPARTMENT WALL via which a FINAL EIT can be reached. Note: A door in a compartment wall in an institutional building is considered as a storey exit for the purposes of B1, of the Building Regulations, if the building is planned for progressive horizontal evacuation. Width: The width of: a. A door (or doorway) is the clear width when the door is open; b. An escape route is the width at 1500mm above floor level when defined by walls or, elsewhere, the minimum width of passage available between any fixed obstructions; c. A stair is the clear width between the walls or balustrades. Notes: 1. Door hardware, handrails and strings that do not intrude more than 100mm into these widths may be ignored. 2. The rails used for guiding a stair lift may be ignored when considering the width of a stair. However, it is important that the chair or carriage can be parked in a position that does not cause an obstruction to either the stair or landing. Metro Safety SO : Building 100, Luton Airport Page 24

26 Section Six - Appendices Appendix 1: Fire Safety Routines Routine Frequency Record Daily Fire alarm indicator panel for normal condition (BS 5839) None or log book if fault Emergency escape lights (check for faults) (BS 5266) None or log book if fault Fire safety signs and fire extinguishers in position None or log book if fault Escape routes unobstructed None or log book if fault Fire resisting doors shut None or log book if fault Nightly Waste bins emptied etc. None or log book if fault Electric plugs removed and sockets not overloaded None or log book if fault Weekly Fire alarm test (actuation from different trigger devices) & any associated passive systems (Including doors held open/shut by electromagnets) (BS 5839) Log book Monthly Emergency escape lighting test including any auto start generator (simulated mains failure) (BS Log book 5266)) Fire fighting equipment (visual check) Log book Open exit doors not in daily use Log book Safety Inspection Log book Quarterly (3 monthly) Fire alarms (BS 5839) Log book Six monthly Fire evacuation drills Log book Annual Fire fighting equipment (BS 5306) Label Emergency escape lighting (Full discharge test)(bs 5266) Log book / Test Certificate Fire alarm (BS 5839) Log book / Test Certificate Five yearly Fire fighting equipment (discharge test-most types (BS 5306) Label Ten yearly Fire extinguishers (discharge test-carbon dioxide and some dry powder only (BS 5306) Label It is recommended that one person or organisation be nominated to be responsible for the maintenance of the fire precautions within the premises and the completion of all the records so as to ensure that the necessary entries are made into the logbook. Appendix 2: Fire Safety & Evacuation Recommendations Fire Safety and Evacuation Recommendations We would like to make the following fire safety recommendations for all staff to comply with in order to ensure their own safety: 1. All staff should be familiar with the location of the fire alarm call points on their floor. 2. Upon discovering a fire the fire alarm should be raised by operating the nearest call point. 3. Upon hearing the fire alarm, unless notice has been given otherwise, it is impossible to be sure that it is not a fire and the building should be evacuated promptly. 4. The premises should be confirmed as evacuated by the nominated fire wardens (or senior nominated personnel) so long as it is safe to do so. Toilet areas should be checked as the floors are cleared, with all doors being closed on leaving. 5. People must move quickly and calmly and not re-enter their premises, or the building, unless permission is given by the senior fire service officer present. 6. The person who discovers the fire should ensure that the fire service has been called. 7. Every member of staff should have been familiarised with their alternative emergency exit routes and have been walked all the way along them to the designated assembly point as part of their staff induction. 8. Everyone should know where the current designated assembly point is. Metro Safety SO : Building 100, Luton Airport Page 25

27 9. Lifts must never be used in the event of a fire (Unless known to be specifically designed for the use of persons unable to use the stairs in the event of fire) 10. When the fire service arrives each fire warden (or nominated senior person) should inform the senior fire service officer that their floor/premises is clear (or to building security who will then report directly to the fire service on their arrival). 11. Only once the fire alarm has been raised should fire extinguishers be used to attempt to extinguish the fire, but only if it is safe to do so, and only so long as this does not in any way endanger any person. If all staff are familiar with the above basic procedures then when there is an incident or a drill everything should go smoothly. Appendix 3: Portable Electric Appliance Test Guidelines The Health & Safety Executive recommends that in premises such as offices, regular visual inspections rather than testing may be sufficient to secure compliance with the requirements to maintain electrical equipment. This table can be used as a guide to the appropriate initial* form of testing. Significant hazards: Faults in appliances hence the need to undertake PAT tests; Misuse of appliances they should be suitable / sufficient for the intended activity. Equipment Environment User checks Formal visual inspection Combined inspection & testing Battery operated: No No No (<20v) Extra Low Voltage: No No No (<50vAC) e.g. telephone/desk lamps Information Technology: e.g. VDU and DSE No 2-4 years No - if double insulated Otherwise 5 years Copiers / Fax machines: Not hand held or rarely moved Double insulated equipment: Not hand held but moved regularly e.g. lamps / fans Double insulated equipment: Hand-held e.g. floor buffers Earthed equipment (Class 1): e.g. electric kettles, some floor cleaners Cables (leads) and plugs to the above units Extension leads (mains voltage) No 2-4 years No - if double insulated Otherwise 5 years No 2-4 years No Yes 6 months 1 year No Yes 6 months 1 year 1 2 years Yes 6 months 4 years depending upon what equipment / unit is attached 1 5 years depending upon what equipment / unit is attached *To be reviewed following experience of the faults found and of operating the maintenance system over a period of time. Metro Safety SO : Building 100, Luton Airport Page 26

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

FIRE RISK ASSESSMENT Self Assessment

FIRE RISK ASSESSMENT Self Assessment FIRE RISK ASSESSMENT Self Assessment Important! This fire risk assessment form is to be filled in by the responsible person within a business or organisation. As this is a free download for the use of

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk

Slight Harm Moderate Harm Extreme Harm Low Trivial Risk Tolerable Risk Moderate Risk Medium Tolerable Risk Moderate Risk Substantial Risk Fire Risk Assessment: ABC Sample House Sample Road SA1 3M2 C J Sparks Ltd 13 Alexandra Gardens Carshalton SM5 4LJ T: 02077577457 W: www.cjsparks.com E: sales@cjsparks.com Ref: 3077 Action Plan Number Action

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

Charlotte Building, 17 Gresse Street, London W1T 1QL

Charlotte Building, 17 Gresse Street, London W1T 1QL Charlotte Building, 17 Gresse Street, London W1T 1QL Fire Safety Management & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of

More information

Fire Safety Protocol

Fire Safety Protocol CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures 161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Premises Description Address Area Post Code Tel no. Num of Employees Normal Occupancy Max Allowed Use of Premises Building Length Building Breadth Area 0.00 M² Floors Storeys Below

More information

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA

Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Fire Risk Assessment Mechanics Institute Manchester Road Burnley BB11 1JA Assessment prepared by - Chris Caton MIFireE Pennine Fire & Safety Limited Pleasington Street Blackburn BB2 1UF info@penninefire.co.uk

More information

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be

EMLC Academy Trust. Fire Safety Policy 2017/19. Every child deserves to be the best they can be EMLC Academy Trust Fire Safety Policy 2017/19 Every child deserves to be the best they can be 1 Scope: EMLC Academy Trust & Academies within the Trust Version: 2 Filename: EMLC Academy Trust Fire Safety

More information

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014

Byker Various post codes. Your Homes Newcastle Health and Safety (fire) Officer Date of Fire Risk Assessment 18 th February nd October 2014 Type of Property Owner Address of Properties Responsible Person (s) consulted Multi- occupied housing referred to as the Byker Wall Ground floor and varying upper levels with open deck assess to all areas.

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment

More information

Fire Risk Assessment Guidance

Fire Risk Assessment Guidance Fire Risk Assessment Guidance This document is a guidance note to accompany the example fire risk assessment template. The example fire risk assessment template has been designed with small to medium domestic

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Fire Precautions (Workplace) Regulations Before beginning the risk assessment, check to see if your workplace has a Fire Certificate. If the workplace does have a Fire Certificate,

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT Full Property Name: St Augustine s Catholic Voluntary Academy Full Property Address: Opposite 93 PE9 1SR Date of Fire Risk Assessment: 6 th June 2017 Name of Fire Risk Assessor: Peter

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

Fire Risk Assessment Safety Checklist

Fire Risk Assessment Safety Checklist Fire Risk Assessment Safety Checklist This checklist has been prepared to help you comply with The Regulatory Reform Fire Safety Order 2005 What is the Regulatory Reform (Fire Safety) Order 2005? The Regulatory

More information

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes

Fire Risk Assessment. Guidance Notes. Location details. Risk Rating. Assessors. General notes Fire Assessment Location details Company Name Site address Site contact name Phone Guidance Notes looking at the workplace to identify potential A hazard is something that has the potential to cause harm;

More information

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing)

FIRE SAFETY LOG BOOK. (Record of Fire Safety Equipment Testing) FIRE SAFETY LOG BOOK (Record of Fire Safety Equipment Testing) Fire safety log book MARCH 2013 CONTENTS 1.0 PREMISES SPECIFIC INFORMATION 2.0 FIRE SAFETY EQUIPMENT TESTING 2.1 Escape Routes 2.2 Fire Warning

More information

5 Key Stages to Risk Assessment

5 Key Stages to Risk Assessment 5 Key Stages to Risk Assessment Stage 1: Identify Fire Hazards For a fire to start, three things are needed: A source of ignition Fuel Oxygen If any one of these is missing, a fire cannot start. Taking

More information

NOTTINGHAM CITY HOMES

NOTTINGHAM CITY HOMES APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes

More information

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9

Index. Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8. Fire Risk Assessments 9 Index Premises Information 2 About This Log Book 3 Service and Maintenance Requirements 4 8 Fire Risk Assessments 9 Fire Alarm Systems 10-20 Locations 10 Servicing 11 12 Activations 13 14 Weekly Checks

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

FIRE PROCEDURES 1. APPOINTMENTS

FIRE PROCEDURES 1. APPOINTMENTS 12b FIRE PROCEDURES 1. APPOINTMENTS Responsible Person In compliance with the Regulatory Reform (Fire Safety) Order 2005 (FSO), the School s Head, Mrs C Cameron is appointed as the Responsible Person for

More information

Wellsprings Primary School. Fire Emergency Evacuation Plan

Wellsprings Primary School. Fire Emergency Evacuation Plan Wellsprings Primary School Fire Emergency Evacuation Plan This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the plan is: To ensure the safety

More information

A basic guide to... Fire Safety for Scout Premises

A basic guide to... Fire Safety for Scout Premises A basic guide to... Fire Safety for Scout Premises A basic guide to Fire Safety for Scout Premises This Guide has been designed and produced by Chubb Fire to assist persons responsible for fire safety

More information

If there are more than ten people working other than on the ground floor,

If there are more than ten people working other than on the ground floor, Fire safety information sheet Introduction This information sheet is designed to give our safety representatives a basic understanding of fire safety and fire risk assessments under the current law. This

More information

UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT

UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT UNIVERSITY OF OXFORD FIRE RISK ASSESSMENT Building : Postal Address : Mathematical Institute, Andrew Wiles Building Radcliffe Observatory Quarter Woodstock Road Oxford OX2 6GG OUED Building Number: 550

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT Fire Risk Assessment Company ame Address of premises (premises being assessed) Sandwell Valley School and Sandwell Community Care Trust Training 150 Birmingham Road, West Bromwich, B70 6QT ame of Responsible

More information

DEF Fire Evacuation and Emergency Planning Criteria

DEF Fire Evacuation and Emergency Planning Criteria DEF Fire Evacuation and Emergency Planning Criteria This criteria should be used to devise individual DEF specific fire evacuation and emergency plans. It is the responsibility of the Clinic Team Leader

More information

LYHA Fire Safety Policy

LYHA Fire Safety Policy LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with

More information

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures

Fire Safety Management Plan. Qube 90, Whitfield Street, W1T 4EZ. Fire Safety Management Plan & Evacuation Procedures Fire Safety Management Plan & Evacuation Procedures Contents 1.0 Introduction 2.0 Means of Escape in Case of Fire 3.0 Means for Giving Warning in Case of Fire 4.0 Means for Fighting Fire 5. 0 Discovering

More information

H&S Forum. Fire Safety Policy Glascote Academy

H&S Forum. Fire Safety Policy Glascote Academy Fierte Multi Academy Trust Health and Safety Policy Handbook Reference Number HR 103 Issue 6 Approved By H&S Forum Date September 2016 To be reviewed September2017 Policy Title Fire Safety Policy Glascote

More information

Fire Safety Policy Date: 0

Fire Safety Policy Date: 0 Fire Safety Policy Date: 0 Policy Preparation & Introduction This document format has been produced by Firesafe Solutions (UK) Ltd to aid managers, tenants and others responsible for fire safety in their

More information

PREMISES FIRE SAFETY LOGBOOK

PREMISES FIRE SAFETY LOGBOOK 0844 740 3473 PREMISES FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. The Regulatory Reform (Fire Safety) Order 2005 (FSO) requires that the

More information

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent

More information

Fire Safety Risk Assessment Large Premises

Fire Safety Risk Assessment Large Premises Fire Safety Risk Assessment Large Premises Premises Name: Person Completing this Assessment: Date of Assessment: Date of Next Review: (Recommended Annually) Fire Safety Risk Assessment (Large Premises)

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT Wyclif Independent Christian School Premises Middle School, St. Johns Hall, Machen Fire Safety Risk Assessment for Wyclif Christian School Introduction Regulatory Reform Order

More information

FIRE SAFETY POLICY Revised March 2013

FIRE SAFETY POLICY Revised March 2013 FIRE SAFETY POLICY Revised March 2013 CONTENTS Page No 1.0 Statement of Intent 1 2.0 Fire Safety Accountability Structure 2 3.0 Roles and Responsibilities 3 4.0 Fire Safety Management 7 5.0 Fire Risk Assessment

More information

THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS

THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS THE FIRE SAFETY GUIDE FOR BUSINESS OWNERS 0800 2211 8034 Table of Contents Part 1: Introduction Part 2: Who is Responsible? Part 3: What is Required? Fire Risk Assessments Appointment of Competent Persons

More information

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer

KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY. Last Review Date 30 June Next review date 30 August Health and Safety Officer KRISHNAMURTI FOUNDATION TRUST FIRE SAFETY POLICY Last Review Date 30 June 2015 Policy endorsed by Policy is maintained by ISI reference Trustees Co-Principals/Directors A9, B6, B9 Next review date 30 August

More information

Fire safety procedure

Fire safety procedure Fire safety procedure Review date: October 2020 Responsible (s): Health and Safety Applicable to Staff: Accessible to Students: Accessible to general public: (including clients) Yes Yes Yes 1 Contents

More information

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy

Fire Safety Policy 29/09/2017. Holme Grange School Whole School Policy Including EYFS. Fire Safety Policy Holme Grange School Whole School Policy Including EYFS Fire Safety Policy This document details the school s policy on fire safety in operation at Holme Grange School. The document is split into a number

More information

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job

More information

Following a near miss (after a fire or where evidence suggests that a fire could have occurred).

Following a near miss (after a fire or where evidence suggests that a fire could have occurred). Contents: This is your Fire Risk Assessment Revision of this risk assessment Scope of assessment and methodology Executive Summary Risk Rating Assessment Overview The Responsible Person/Duty Holder Persons

More information

NOT PROTECTIVELY MARKED. Fire Legislation

NOT PROTECTIVELY MARKED. Fire Legislation Fire Legislation Contents Policy Statement... 2 Legislation... 2 Fire Extinguisher Usage... 2 Fire Evacuation Procedure... 3... 4 Line Managers/Supervisors... 4 Business Support Officer... 5 Driver/Handy

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description

More information

Annemount School Fire Safety Policy This Policy is for the whole school including the EYFS

Annemount School Fire Safety Policy This Policy is for the whole school including the EYFS Annemount School Fire Safety Policy This Policy is for the whole school including the EYFS Procedures Due concern is taken that the Regulatory Reform (Fire Safety) Order 2005 is complied with. The School

More information

Fire Procedures. April 2016

Fire Procedures. April 2016 Estates Department Fire Procedures April 2016 Author Robert Hardman Estates Manager Last Policy Review Date 1/04/16 Next policy Review Date 1/04/17 Reviewed by The Laurus Trust School Fire Procedures Contents

More information

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome

Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome Health & Safety Policy HSP 03 Fire Safety Version Status Date Title of Reviewer Purpose/Outcome 1.0 Draft 07.03.2016 David Maine 1 st Draft for consultation/review 1.1 Approved 22.12.2016 David Maine 1

More information

FIRE RISK ASSESSMENT

FIRE RISK ASSESSMENT FIRE RISK ASSESSMENT ESTABLISHMENT: Address: WAVERLEY SCHOOL 105 The Ride Enfield EN37DL Assessor: (print) Responsible Person: G WILLIAMS Signature G Williams GAIL WEIR (Head Teacher) Date: Review date

More information

FIRE POLICY ST.GEORGES AND OUR LADY QUEEN OF PEACE PARISHES OF WORCESTER INTRODUCTION. Fire is one of the most common workplace hazards.

FIRE POLICY ST.GEORGES AND OUR LADY QUEEN OF PEACE PARISHES OF WORCESTER INTRODUCTION. Fire is one of the most common workplace hazards. FIRE POLICY ST.GEORGES AND OUR LADY QUEEN OF PEACE PARISHES OF WORCESTER INTRODUCTION Fire is one of the most common workplace hazards. The RR (Fire Safety) Order 2005 requires responsible persons to carry

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

Element C3.5 Means of Escape

Element C3.5 Means of Escape .5 Means of Escape RRFSO Article 14 Legal Factors Responsible person must ensure routes to emergency exits and exits themselves are kept clear at all times Exits must directly lead to place of safety Safe

More information

Allfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person:

Allfire Site No. a division of Allsaved Ltd. Fire Safety Log Book. Premises Address: Responsible Person: Site No. a division of Allsaved Ltd. Fire Safety Log Book Premises Address: Responsible Person: Introduction An Introduction to Your Fire Safety Log Book The Regulatory Reform (Fire Safety) Order 2005

More information

Fire Risk Management Policy. UK September 2017

Fire Risk Management Policy. UK September 2017 UK September 2017 5 & 7 Diamond Court, Opal Drive, Eastlake Park, Fox Milne, Milton Keynes MK15 0DU, T: 01908 396250, F: 01908 396251, www.cognitaschools.co.uk Registered in England Cognita Limited No

More information

Regulatory Reform (Fire Safety) Order A short guide to making your premises safe from fire

Regulatory Reform (Fire Safety) Order A short guide to making your premises safe from fire Regulatory Reform (Fire Safety) Order 2005 making your premises safe from fire Introduction This booklet provides simple and practical advice to people responsible for fire safety in small and medium-sized

More information

Fire Safety. A TUC guide for trade union activists

Fire Safety. A TUC guide for trade union activists Fire Safety A TUC guide for trade union activists Contents Section one Introduction 3 Section two The law 4 Section three Fire risk assesment 5 Section four Policies and procedures 6 Section five Enforcement

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Department The Cockpit Risk Assessment number PM/06/2015 Date. 17 th June 2015 Review due date 17 th June 2016 Activity: Fire safety risk assessment Location: The Cockpit Name of Assessors:

More information

Fire Safety and Fire Risk Management Procedures, Fire Safety Systems Testing Instructions and Log Sheets

Fire Safety and Fire Risk Management Procedures, Fire Safety Systems Testing Instructions and Log Sheets Fire Safety and Fire Risk Management Procedures, Fire Safety Systems Testing Instructions and Log Sheets Approved By Head of OHES Effective Date June 2017 Date Approved June 2017 Status Live Policy Owner

More information

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY

HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY HEALTH & SAFETY MANAGEMENT ARRANGEMENTS FOR FIRE SAFETY INTRODUCTION Cwmni CYNNAL recognises its duty of care to employees and all reasonable steps will be taken to secure the health and safety of employees.

More information

Fire Safety Policy 2018/19

Fire Safety Policy 2018/19 Fire Safety Policy 2018/19 Reviewed: March 2016 Next Review: March 2019 1. Policy Statement The School is committed to ensuring, so far as is reasonably practicable, the health, safety and welfare of all

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE EMERGENCY PLAN This Emergency Plan has been developed following fire risk assessments of the relevant building. The purpose of the Plan is to ensure the

More information

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service

Health, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in

More information

ISLE OF WIGHT FIRE & RESCUE SERVICE

ISLE OF WIGHT FIRE & RESCUE SERVICE ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS

More information

St Edward s Oxford FIRE SAFETY POLICY

St Edward s Oxford FIRE SAFETY POLICY FIRE SAFETY POLICY 1 CONTENTS Section Page No.(s) 1. Policy Statement 3-5 2. Organisation and Responsibilities 6 3. Responsibilities of Responsible Person 7-8 4. Responsibilities of Senior Management 9

More information

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x

Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Fire Safety Audit: Part B - Questionnaire (Questionnaire Devised By Mr.R.R.Nair) Yes No x Name & Address of the Society IDENTIFY PEOPLE AT RISK 01 Have you identified who is at risk? 02 Have you identified

More information

Fire Risk Assessment (FRA) Checklist

Fire Risk Assessment (FRA) Checklist Fire Risk Assessment (FRA) Checklist Assessed by: Job Title: Department/Location: Date Document Downloaded: Date of Assessment: Duty Holder Name: FRA. Description / Comments FHRA. 1. MANAGEMENT, PLANNING

More information

The Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report

The Regulatory Reform (Fire Safety) Order Fire Risk Assessment Report 42 Haslucks Croft, Shirley, Solihull, B90 2EQ (t) 0121 249 1281 (m) 07814 203 977 www.veritas-consulting.co.uk The Regulatory Reform (Fire Safety) Order 2005 Fire Risk Assessment Report Client The Company

More information

Fire Policy and Procedures. Cañada Blanch Spanish School

Fire Policy and Procedures. Cañada Blanch Spanish School Fire Policy and Procedures Cañada Blanch Spanish School SUMMARY 1. Introduction (p. 3) 2. Roles and responsibilities (p. 3) -- Headteacher -- Fire Team -- All staff -- Contractors 3. Fire procedures (p.

More information

FIRE SAFETY RISK ASSESSMENT

FIRE SAFETY RISK ASSESSMENT FIRE SAFETY RISK ASSESSMENT Wyclif Independent Christian School Premises Ebenezer Chapel,Wyndham Street, Machen Fire Safety Risk Assessment for Small Premises Introduction Regulatory Reform Order The Regulatory

More information

Arbour House. Fire Policy and Procedures

Arbour House. Fire Policy and Procedures Arbour House Fire Policy and Procedures Policy Review Date: May 2017 Introduction Arbour House School endeavours to ensure that risks from fire are identified and that arrangements are in place to control

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA

More information

Fire Safety Awareness Workbook

Fire Safety Awareness Workbook Fire Safety Awareness Workbook For All Staff Please ensure you read the workbook thoroughly and complete the assessment at the end Version 2. Introduction Fire safety training is a mandatory element of

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

Kings Fire Safety Policy

Kings Fire Safety Policy Kings Fire Safety Policy All Kings policies will be ratified by the Board of Directors and signed by the Chairperson. Each policy will be co-signed by the principal of each school. Review dates will be

More information

Project: Location: Date Prepared: Last Reviewed:

Project: Location: Date Prepared: Last Reviewed: Project: Location: Date Prepared: Last Reviewed: Contents Premises Essential Information 4 Definitions & Acronyms 5 Introduction 5 Building Description and Safety Systems 7 General Strategy, Responsibilities

More information

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007)

FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: DSFRS Log book Version 1.0 (October 2007) FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. This Fire Safety Log book has been prepared to assist the responsible person in coordinating

More information

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019 Fire Safety Policy (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January 2018 Next Review: January 2019 Person Responsible: School Business Manager 1 P age 1. INTRODUCTION a) King Fahad

More information

Health and Safety Services. Safety Guide 5. Fire drills

Health and Safety Services. Safety Guide 5. Fire drills Health and Safety Services Safety Guide 5 Fire drills Fire drills Contents Summary...iii 1. Scope...1 2. Responsibilities...1 2.1. Duties on managers... 1 2.2. Duties of all building occupants... 1 2.3.

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY

FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY FIRE SAFETY & EMERGENCY EVACUATION STRATEGY AND POLICY Under the terms of the Box Hill School must ensure the safety from fire of all staff, pupils, contractors and visitors. In order to do this the school

More information

To seek Cabinet approval of the Council s Fire Safety Policy. It is proposed that Cabinet approves the Fire Safety Policy.

To seek Cabinet approval of the Council s Fire Safety Policy. It is proposed that Cabinet approves the Fire Safety Policy. NORTH AYRSHIRE COUNCIL Cabinet 1 May 2018 Title: Purpose: Recommendation: Fire Safety Policy To seek Cabinet approval of the Council s Fire Safety Policy. It is proposed that Cabinet approves the Fire

More information

FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY

FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY FIRE PREVENTION, PROCEDURES AND RISK ASSESSMENT POLICY PART 1: FIRE SAFETY INTRODUCTION Our priority is to minimise the risk to life and to reduce injury by maintaining the physical fire safety of the

More information

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May

More information

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING

UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK. Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING UCL ESTATES Fire Safety UNIVERSITY COLLEGE LONDON PREMISES FIRE SAFETY HANDBOOK Regulatory Reform (Fire Safety) Order 2005 DARWIN BUILDING University College London Gower Street, London WC1E 6BT Contents

More information

FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY

FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY Under the terms of the Regulatory Reform (Fire Safety) Order 2005, and subsequent regulations, Seaford College must ensure the safety from fire of all staff,

More information

Fire Risk Assessment Case Study

Fire Risk Assessment Case Study Appendix B Fire Risk Assessment Case Study The purpose of this case study is to illustrate one practical approach to conducting a fire risk assessment. The checklist and proformas used in this case study

More information

- CONSTRUCTION FIRE SAFETY STANDARDS

- CONSTRUCTION FIRE SAFETY STANDARDS SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Hot Work Permits All construction sites shall implement a system of Hot Work Permits for all work activities that generate heat, sparks or flames. All of the

More information