PRODUCT: SEL-SV-MCQ-O5- K6 VERSION TECHNICAL SHEET 1/5 SAC

Size: px
Start display at page:

Download "PRODUCT: SEL-SV-MCQ-O5- K6 VERSION TECHNICAL SHEET 1/5 SAC"

Transcription

1 PRODUCT: SEL-SV-MCQ-O5- K6 VERSION 3. TECHNICAL SHEET /5 SAC APPLICATION Flame presence signal sensor-transmitter recommended for single- or multiple-burner systems for industrial or commercial use of any kind of power, operating on gas, oil or any other fuel producing flame emitting or visible rays (yellow flame) either under continuous operation (switches burner on / off within a period of time longer than 24 hours). It is provided with sensor-transmitter fault self-diagnosis circuit at every 4 seconds operation (self-checking circuit). Item of ABNT NBR 233 Standard establishes as mandatory the use of sensor with fault self-diagnosis on burners from, Kcal power operating for 24 hours or longer without at least one shutdown. This product meets the requirements of ABNT 233 standard Sept./2 revision. It is provided with independent sensor sensitivity setting, which facilitates using it in multiple-burner applications, for discrimination of adjacent flames and signal transmitting circuit, which enables its application at distances up to,3 meters between the sensor and the flame detector relay or programmer. The device is provided with two sensors: one ultraviolet (8 nm to 26 nm) and another infrared (5 nm to nm) sensor. The MCQ system is composed of the flame presence detector relay, sensor SEL-SV-MCQ and programmer / monitor. Refer to the MCQ system functional diagram. In the MCQ system, detector relay is MCQ system s master unit; it establishes communication to all other set units, processes and performs the operations required for providing the flame control. It processes the ultraviolet and infrared radiation sensor signals and other parameters as well. The signals are programmed and monitored through the programming / monitoring unit MCQ. accessory and stored in (non-volatile) flash memory of the CHM-F- Through the accessory, it enables control and signaling operations via keyboard and alphanumeric LCD display as well as programming mode (U, I, U and I, U or I) and U and I set point. It also enables monitoring absolute and percent values of and, self-check, temperature on SEL-SV-MCQ, events in progress, the latest 6 events occurred in sequential order with date / time, their code, event date and time and parameters programmed. It further allows applying test programs for the output relays as well as their LEDs. Velho São Paulo SP Tel/Fax: (55 ) sheet when it deems it necessary Dec/2 /5

2 PRODUCT: SEL-SV-MCQ-O5- K6 VERSION 3. TECHNICAL SHEET 2/5 SAC TECHNICAL DATA Micro-processed with watchdog - failsafe Version: 3. NOTE: VERSION 3. WAS CREATED FROM THE NEED OF TECHNOLOGICAL UPDATE IDENTIFIED WITH CUSTOMERS. VERSION 3. OPERATES ONLY WITH THE SYSTEM MCQ PRODUCTS IN THE SAME VERSION OR IN SUPERIOR VERSION (RELAY / SENSOR / PROGRAMMER). EQUIPMENT FROM PREVIOUS VERSIONS MAY BE UPDATED TO VERSION 3., IN WHICH EVENT CUSTOMER MUST SHIP THE SET OF PRODUCTS COMPOSING THE MCQ SYSTEM TO SELCON ON MANDATORY BASIS. THE VERSION 3. IDENTIFICATION IS SHOWN ON THE OUTSIDE OF SEL-SV-MCQ SENSOR AND SYSTEM CHM-F RELAY CASING. - Supply voltage: 5 VAC + -5%; 5 / 6Hz ± 3% - Power consumption (max): 6 VA - Internal fuse: 25 ma, source protection, retarded, mounted on socket, model MST 2, Fusibras Ltda. make or similar. - Failsafe: provided with fault self-checking system with 4-second cycles - Sensor: photocells sensitive to ultraviolet and/or visible / infrared radiation - Signaling (switched on) - OP (Vm) Indicates sensor in operation. Blinking: indicates system fault - (Vd) Indicates presence of ultraviolet radiation flame - (Vm) Indicates presence of flame by infrared radiation - LCOM (Am) Indicates communication deficiency or fault - Operation: over communication channel RS 485 with relay and programmer -. - Sensitivity setting: through programmer / supervisor - Plain (4x4 mm) or convex (4x3 mm) lens, quartz crystal, resistant to combustion chamber pressure up to 5 psi ( kpa). - Ambient degree of protection: IP 66 - Connection to process: Collar with inner thread Rp (NBR 644), for connection to viewing tube - Electric connection: Three (3) ½ x 4 NPT inner thread holes for connection of flexible conduits - Wiring: 8 inner leads (7 ºC.33 mm² - 3 V) - Reduction tube (flame view): Provide tube (Fig 2) with diameter between./2 and 3, defined as function of its length and ability of emitting flame ultraviolet and/or infrared / visible radiation. - Maximum distance from sensor to flame presence detector relay :,3 meters - Weight: 3, grams - Operating ambient temperature: to 6 º C - Storage temperature: - 5 º C to 65 º C (dry heat) - Maximum operating relative ambient air humidity: 9% without condensation (NBR 529) - Casings: SAE 323 and SAE 359 cast aluminum alloy case - Painting: Epoxy powder, grey color - Identification tag: (stainless steel).5 mm thickness, 9 mm diameter, fastened by 2 screws. - Warranty: 2 months (see warranty certificate) Velho São Paulo SP Tel/Fax: (55 ) sheet when it deems it necessary Dec/2 2/5

3 PRODUCT: SEL-SV-MCQ-O5- K6 VERSION 3. TECHNICAL SHEET 3/5 SAC Dimensional Drawing (mm) 44,5 " Rp 29 ( NBR 644 ) 97 Thread depth 5mm Ø24 Connection to process 4,5 Ø2 ~85 INSTALLATION REFRACTORY REDUCTION TUBE ~9 3 x /2-4 NPT FIG NIPPLE SEL-SV-MCQ- 5-K6 P cam "Rp P ext Accessory: Articulate Connection ACS-CN-C(former SA-36-SE) Wiring diagrams COMBUSTION CHAMBER WALL FIG 2 Velho São Paulo SP Tel/Fax: (55 ) sheet when it deems it necessary Dec/2 PURGE AIR P ext > P cam See item: Precautions 3/5

4 PRODUCT: SEL-SV-MCQ-O5- K6 VERSION 3. TECHNICAL SHEET 4/5 SAC V SEL-SV-MCQ SELCON LTDA. PRODUTO: Indústria Brasileira MODO RESET ACK TST VRF RELE DHS HFL ON/OFF L2 F Rearm 5VAC Power Supply N (L) OBS.: PROVIDE SIMULTANEOUS ENERGIZING OF RELAY and SEL-SV-MCQ. CHM-F OUTPUT RELAY COIL? TRHTH TABLE OUTPUT RELAY CONTATS STATUS COMMENTS ACS-CN-C Q (K + K2) Flame Presence (control) (K3) Flame Presence (signaling) F2 F3 F4 F5 K2 K K3 (K4) Sistem Fail (control) K4 ACK DHS SELCON LTDA. PRODUTO: Indústria Brasileira TST HFL VRF MODO RESET RELE No Yes Yes (K+K2) No (K4) No (K+K2) No (K4) Yes (K+K2) Yes (K3) Yes (K4) Yes Yes (3/4) Open (K+K2) No (K4) No (3/4) Open (8/9) Open (3/4) Open (8/9) Closed (3/4) Closed (5/6) Closed (8/9) Closed (8/9) Open terminals 3/4 - V No Flame+ operanting, terminals 3/4 - V Whit or without flame+ failed terminals 3/4 - V LOGIC UNIT + CMS - CMS ACS-CB-3 FEMALE CONNECTOR ACS-CB-C427/457 = The status does not matter = Status OFF = Status ON NOTE: FOR EACH BURNER, PROVIDE AN MCQ SYSTEM; ECEPT PROGRAMMER, BECAUSE WITH ONE UNIT, "N" SYSTEM MAY BE PROGRAMMED/SUPERVISED (ONE AT A TIME) Vdc 4-2mA C (FLAME PRESENCE DETECTOR RELAY) CH Local Flame Signaling FIELD PANEL ACS-CV -CMS +CMS K/K2 K3 K4-4v L CH CONTROL USAGE. SIGNALING USAGE. : SYSTEM FAIL - CONTROL USAGE. : PROPORTIONAL SIGNAL FOR FLAME SIGNALING : ENERGIZED SIGNALING. F L(max) : SYSTEM FAIL - : PRESENCE OF ULTRAVIOLET - : PRESENCE OF INFRARED - : MAIMUM DISTANCE BETWEEN and SEL-SV-MCQ = L(max) < 3 m Mode - proportional to the ultraviolet rays focusing on ultraviolet sensor. Mode - proportional to the infrared rays focusing on infrared sensor. and Mode - proportional to the focusing rays with lower number of incident rays. or Mode - proportional to the focusing rays with higher number of incident rays. Site: A E Site: A E FIG 3 ORDERING CODE: SEL-SV-MCQ-O5- K6 Velho São Paulo SP Tel/Fax: (55 ) sheet when it deems it necessary Dec/2 4/5

5 PRODUCT: SEL-SV-MCQ-O5- K6 VERSION 3. TECHNICAL SHEET 5/5 SAC SEL-SV-MCQ - LENS O OPTIONAL ITEMS CONNECTION TO PROCESS DEGREE OF PROTECTION VIEWING TUBE ADAPTER - (d) d2 = 5 (d3) K6 d = 2 => plane OR => RP With fault selfchecking d3 = => none OR IP 66 d = 3 => convex d3 = => RP(M) / NPT(F) NOTE: Use this sensor with relay and programmer, which shall be specified separately. WARNING: Install the sensor upside down to prevent dirt buildup and keep the sensor face clean. Attention: Provide cooling air inlet and inspection tube cleaning as depicted on the figure above. Use θ < 4º C clean and dry air; flow rate: > 5 scfm; pressure > than the combustion chamber pressure in at least 3 mm water column. The sensor must see the flame, if possible, on the first 3% of the same, from the burner nozzle where higher visible radiation emission exists. Use the sensor only with programmers and/or detector relays made by Selcon. OTHER PRODUCTS AND ACCESSORIES: Flame relays: CHM SE, CHM P, CHM M, CHM M IIIMe (with base) and CHM F Automatic valve proving control: CHM T Ignition and flame monitoring programmers: PRG SE, PRG E, PRG Ie, PRG-Ie IIIMe (with base), PRG I, PRG M and PRG M IIIMe (with base) Flame optical sensors: SEL- SV Ionization flame sensors and ignition electrodes: SEL HT (standard) and SEL HT E (sensors and electrodes mounted under drawing or customer sample- special); Flame signal transmitter: ACS T (up to 5 meters between sensor and relay or programmer) Flame signal converter for 4-2 ma: ACS CV Ignition transformers: ACS TE (for supply in VAC or VCC) Timed ignition panel: ACS IT Portable ignitor: ACS IP (operates on batteries) Ignition panel (operates on batteries): ACS PN E Ignition panel and flame monitoring: PRG-Ie/O3 Cables: ACS - CB (ignition / sensing / communication / control) Touch-sensitive connector and protector for ignition cable: ACS CP Articulate connection ACS CN Ignition and monitoring panel: ACS PN (on request) Reform service for pilot burners: on request PRODUCTION DATA SUPERVISOR LINE Velho São Paulo SP Tel/Fax: (55 ) sheet when it deems it necessary Dec/2 5/5

PRODUCT: PRG-M-IIIMe---R- P2- TECHNICAL SHEET 1/9

PRODUCT: PRG-M-IIIMe---R- P2- TECHNICAL SHEET 1/9 PRODUCT: PRG-M-IIIMe---R- P2- TECHNICAL SHEET 1/9 APPLICATION PRG-M programmer is a flame safety piece of equipment for machines, equipment or systems with one or mullti-burners of any kind or power, with

More information

PRODUCT: CHM-F-MCQ-C VERSION TECHNICAL SHEET 1/5

PRODUCT: CHM-F-MCQ-C VERSION TECHNICAL SHEET 1/5 FLM PSNC DTCTION LY FO BUN PODUCT: -C VSION 3. TCHNICL SHT /5 SC 55 39-66 PPLICTION The relay is a flame safety equipment recommended for machines, equipments mono or multiburners systems, of any type

More information

UV Flame Supervision System

UV Flame Supervision System 7 783 UV Flame Supervision System DETACTOGYR LFE50 Series 02 ISO 9001 The LFE50 is a self-checking UV flame supervision system designed for use with continuously operating burners or for burners running

More information

Eclipse 90 UV Scanner Model A Version 1

Eclipse 90 UV Scanner Model A Version 1 85 Instruction Manual 10/14/010 Eclipse 90 UV Model 5600-90A Version 1 C US Introduction This sensor features a high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames that cycle on and

More information

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

UV Scanner. Model Specification. Introduction. 854 Instruction Manual 854 Instruction Manual 10/11/010 UV Model 5600-91 C US Introduction This sensor features a high temperature and high sensitivity ultraviolet (UV) tube for monitoring gas or oil flames in applications that

More information

Eclipse Self-Check UV Scanner

Eclipse Self-Check UV Scanner 856 Instruction Manual 10/18/2010 Eclipse Self-Check UV Model 5602-91 Version 1 Introduction The self-check UV is used for continuous gas or oil flames. A mechanical shutter in the scanner closes briefly

More information

RS /E-EV C01 SERIES

RS /E-EV C01 SERIES The well-known RS 300-800/E-EV BLU Burner Series, till now available up to 8 MW, has been upgraded with two new powerful burner models, the RS 1000-1200/E-EV C01 models that extend his max output up to

More information

Fireye FLAME SCANNERS

Fireye FLAME SCANNERS UV7A4 SC-107 APRIL 3, 2013 Fireye SCANNERS UV7SC UV7R4 UV Non Self-Checking Scanner Models: UV7A4, UV7R4 UV Self-Check Scanner Model: UV7SC DESCRIPTION The non self-check UV7A4, UV7R4 and self-check UV7SC

More information

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC APPROVED The UV1A3/6, UV2/UV2A6/UV2C, 45UV2, 45UV3, UV90-3/6/9 Scanners are used with the M-Series, M-Series II, MicroM, FlameWorx, MB-2 and D-Series controls as well as the Fireye FLAME-MONITOR TM, BurnerLogix

More information

MBCE-110/230UV Flame Sensor Module

MBCE-110/230UV Flame Sensor Module MBCE-1002 FEBRUARY 3, 2017 MBCE-110/230UV Flame Sensor Module DESCRIPTION The MBCE-110/230UV modules provide visual indication and electrical outputs that signal the user regarding flame presence in a

More information

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners Possible flame detectors: - Ionisation probe

More information

7800 SERIES RM7888A Relay Module

7800 SERIES RM7888A Relay Module 7800 SERIES RM7888A Relay Module SPECIFICATION DATA FEATURES APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically

More information

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage atmospheric gas burners Flame detection: - Ionisation probe - Infrared-flicker detector

More information

DESCRIPTION AND INSTALLATION

DESCRIPTION AND INSTALLATION SC-106 SEPTEMBER 3, 2013 DESCRIPTION AND INSTALLATION UV self-checking Scanner Models: 55UV5-1007, 55UV5-1009 For use only with designated Fireye controls For Infrared Photocell Scanners use SC103 For

More information

RS /E-EV C01 SERIES

RS /E-EV C01 SERIES The well-known RS 300-800/E-EV Burner Series, till now available up to 8 MW, has been upgraded with two new powerful burner models, the RS 1000-1200/E-EV models that extend his max output up to 12 MW and

More information

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS UV90 SC-102 MAY 2002 FIREYE SCANNERS UV1A UV8A UV non self-checking Scanner Models: UV1A3, UV1A6, UV8A, UV2, UV2A6, UV2C,45UV2, 45UV3, UV90-3. UV90-6, UV90-9 For UV self-check Scanners refer to SC-101

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit certified Qualitysystem ISO 9001 / EN 29001 Reg. Nr. 10529 Gas Burner Safety Control A Honeywell Company For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible

More information

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit A Honeywell Company Gas Burner Safety Control For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit Possible flame detectors: - Ionisation probe - Infrared flicker

More information

7800 SERIES RM7888A Relay Module

7800 SERIES RM7888A Relay Module 7800 SERIES RM7888A Relay Module FEATURES SPECIFICATION DATA APPLICATION The Honeywell RM7888A Relay Module is a microprocessor-based integrated burner control for industrial process semi-automatically

More information

FIREYE C9707A ALL FUEL SCANNER

FIREYE C9707A ALL FUEL SCANNER 65-8065 APRIL 11, 2013 FIREYE C9707A ALL FUEL SCANNER The C9707A All Fuel Scanner is used with the FIREYE R9107A Flame Controller to provide continuous monitoring of burner flames in industrial and utility

More information

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02 7 783 ISO 9001 DETACTOGYR Flame Safeguard Series 02 The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil

More information

LOW NOx MODULATING GAS BURNERS

LOW NOx MODULATING GAS BURNERS RS/E - RS/EV BLU SERIES LOW NOx MODULATING GAS BURNERS RS/E - RS/EV BLU SERIES RS 300/E BLU 500/1350 3800 kw RS 400/E BLU 800/1800 4500 kw RS 300/EV BLU 500/1350 3800 kw RS 400/EV BLU 800/1800 4500 kw

More information

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR 7 783 DETACTOGYR Flame Safeguard The... together with the QRA50M / QRA51M form a self-checking flame supervision system (DETACTOGYR ) designed for use with continuously operating oil or gas burners or

More information

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev.

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev. Flame scanner for fuel oil and coal flame (rev. A) Application: - Wall fired, corner fired and down-shot boilers - Oil, Orimulsion and pulverized coal burners PbS sensor to detect flame by infrared (IR)

More information

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE!

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE! DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE! Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious

More information

C7061C/F ULTRA VIOLET FLAME DETECTOR FEATURES APPLICATION PRODUCT HANDBOOK. Contents

C7061C/F ULTRA VIOLET FLAME DETECTOR FEATURES APPLICATION PRODUCT HANDBOOK. Contents C7061C/F ULTRA VIOLET FLAME DETECTOR PRODUCT HANDBOOK APPLICATION The C7061C/F are flame detectors for sensing the ultraviolet radiation generated by the combustion of gas, oil, or other fuels. Explosion-proof

More information

UV - flame detector dual fuel burners for intermittent burner operations

UV - flame detector dual fuel burners for intermittent burner operations KLC 11 1(formerly known as KLC 1001) Technical information UV - flame detector KLC 11 for oil -, gas- and dual fuel burners for intermittent burner operations 0085 Description The KLC 11 is a compact UV

More information

Distributed By: M&M Control Service, INC

Distributed By: M&M Control Service, INC Sales@mmcontrol.com APPROVED The information provided in this bulletin is directed to competent boiler and combustion service technicians who are experienced in the installation and operation of Fireye

More information

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module

7800 SERIES RM7840E,G,L,M; EC7840L Relay Module 7800 SERIES RM7840E,G,L,M; EC7840L Relay Module SPECIFICATION DATA Valve Proving features including: VPS test time When (Never, Before, After, Split or Both) FEATURES APPLICATION The Honeywell RM7840 is

More information

ABB. Measure IT Uvisor System Dual sensor flame scanner. UR460 Mod. UVIR /ER/EF/DV Flame Scanner Product Data Sheet (rev B)

ABB. Measure IT Uvisor System Dual sensor flame scanner. UR460 Mod. UVIR /ER/EF/DV Flame Scanner Product Data Sheet (rev B) Dual sensor flame scanner (rev B) Application: - Wall fired and corner fired boilers - Gas, oil and coal multi-fuel burners Combined PbS IR sensor and high sensitivity UV tube Continuous self-checking

More information

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control Oil Burner Safety Control A Honeywell Company DKO 974 N/976 N For 1- or 2-stage oil burners up to 30 kg/h throughput and intermittent operations with or without oil preheating Flame detection: - Photoresistor

More information

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS UV1A UV8A UV5 UV90L SC-108 June 14, 2017 FIREYE FLAME SCANNERS UV non self-checking Scanner Models: UV1AL-3, UV1AL-6, UV90L-1, UV90L-2, UV5-1. UV1AL 45UV3 DESCRIPTION The UV1AL, UV90L, and UV5 scanners

More information

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE!

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE! DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE! Read this manual before using this product. Failure to follow the instructions and safety precautions in this manual can result in serious

More information

North American Flame Detector Adapters 8832 through 8839 and Series R

North American Flame Detector Adapters 8832 through 8839 and Series R Combustion North American Flame Detector s 8832 through 8839 and Series R s simplify installation of flame detectors on North American burners. They also facilitate access to detectors for servicing. Most

More information

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ELECTRONIC FLAME SUPERVISION MULTI-BURNER MULTI-BURNER MODEL: SENS-A-FLAME II Revision: 0 7112 DESCRIPTION Model 7112 Sens-A-Flame II is a second generation solid-state programmable combustion safeguard for supervising multiple burner ovens, furnaces,

More information

INDUSTRIAL FLAME SCANNERS

INDUSTRIAL FLAME SCANNERS WINDOW 141 Flame Scanning System User's Manual WARNING DO NOT INSTALL, MAINTAIN OR OPERATE THIS EQUIPMENT WITHOUT FIRST READING, UNDERSTANDING, AND FOLLOWING INSTRUCTIONS IN THIS MANUAL. FAILURE TO FOLLOW

More information

7800 SERIES EC7885A/RM7885A Relay Module

7800 SERIES EC7885A/RM7885A Relay Module 7800 SERIES EC7885A/RM7885A Relay Module SPECIFICATION DATA 1. Torch-ignited main burner using the S445A Start-Stop Station, or any conventional knee or foot operated start-stop station. 2. Torch-ignited

More information

DESCRIPTION AND INSTALLATION

DESCRIPTION AND INSTALLATION SC-101 April 2001 DESCRIPTION AND INSTALLATION For 45UV5 UV self-checking Scanner Models: 45UV5-1005, 45UV5-1006, 45UV5-1007, 45UV5-1008, 45UV5-1009 and 45UV5-1105 For use only with designated Fireye controls

More information

Burner Company. Flame Safeguard Systems. Bulletin IG-1. Bulletin FS-1

Burner Company. Flame Safeguard Systems. Bulletin IG-1. Bulletin FS-1 Burner Company Flame Safeguard Systems Bulletin IG-1 Bulletin FS-1 Flame Safeguard Systems Flame Safeguard Model Identification (Example of a typical spec): FSG - E110/E300 - UV - NFPA/IRI/FM - W3 - FC

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA C706F APPLICATION C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

TYPE 85UVF/IRF Integrated Flame Scanner with Internal Flame Relay

TYPE 85UVF/IRF Integrated Flame Scanner with Internal Flame Relay CU-114 MARCH 14, 2014 TYPE 85UVF/IRF Integrated Flame Scanner with Internal Flame Relay exida FMEDA SIL3 SEE TABLE 1 ON PAGE 3 SEE TABLE 1 ON PAGE 3 DESCRIPTION APPLICATION The Fireye Phoenix type 85UVF/IRF

More information

Centro-Matic Automated Lubrication Systems System Controls

Centro-Matic Automated Lubrication Systems System Controls Selecting the right controls for your automated lubrication system is one of the last steps in the design process. Several different models may be chosen to control power-operated pumps, depending on the

More information

7800 SERIES EC7890A,B; RM7890A,B,C Relay Module

7800 SERIES EC7890A,B; RM7890A,B,C Relay Module 7800 SERIES EC7890A,B; RM7890A,B,C Relay Module SPECIFICATION DATA EC7890 APPLICATION RM7890 The Honeywell EC7890A,B/RM7890 is a microprocessor based integrated burner control for automatically fired gas,

More information

TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer

TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer CU-108 January 29, 2018 TYPE 105F1-1 Integrated Flame Scanner and Temperature Analyzer DESCRIPTION APPLICATION The Fireye Paragon, type 105F1-1 flame scanner is a microprocessor based flame analysis device

More information

Model 60200FR Gas Primary Control Data Sheet

Model 60200FR Gas Primary Control Data Sheet Programmable, Microprocessor Based Gas Burner Primary Controls On-Board LCD Screen Easy to Understand Icons for Inputs and Outputs Displays micro-amp Flame reading Display operational information Fault

More information

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660 Selectivity Adjustable by Means of - High Pass Frequency Filter - Gain - Threshold Different Adjustments for Different Conditions (e.g. According Fuel or Combustion Technology) Possible, to be Activated

More information

DESCRIPTION AND INSTALLATION

DESCRIPTION AND INSTALLATION SC-101 JUNE 26, 2013 DESCRIPTION AND INSTALLATION For 45UV5 UV self-checking Scanner Models: 45UV5-1005, -1005CEX, 45UV5-1006, 45UV5-1007, -1007CEX, 45UV5-1009, -1009CEX and 45UV5-1105 For use only with

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA C706F APPLICATION C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

FIREYE FLAME SCANNERS

FIREYE FLAME SCANNERS UV1A UV8A UV90 UV1A UV8A SC-102 MARCH 28, 2013 FIREYE FLAME SCANNERS UV non self-checking Scanner Models: UV1A3, UV1A6, UV8A, UV2, UV2A6, 45UV3, UV90-3. UV90-6, UV90-9 For UV self-check Scanners refer

More information

EUROBOX SERIES TYPES CM... SM... MM...

EUROBOX SERIES TYPES CM... SM... MM... EUROBOX SERIES TYPES CM... SM... MM... AUTOMATIC GAS BURNER CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN Application This range of electronic gas burner control systems

More information

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA) R SERIES 35-70 120 VAC Microprocessor-Based Direct Spark Ignition Control F-35-70 November 2015 FEATURES Safe start with DETECT-A-FLAME flame sensing technology Custom pre-purge and inter-purge timings

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector PRODUCT DATA FEATURES APPLICATION C706F C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 APRIL 13, 2012 MBCE-110/230FR Flame Sensor Module DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the user regarding flame presence in a combustion

More information

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector

C7061A,F Dynamic Self-Check Ultraviolet Flame Detector C706A,F Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA C706F APPLICATION C706A The C706A,F are dynamic self-checking flame detectors for sensing the ultraviolet radiation generated

More information

Sola Hydronic Control. An Eco-Friendly Solution.

Sola Hydronic Control. An Eco-Friendly Solution. Sola Hydronic Control An Eco-Friendly Solution. Honeywell s Sola Boiler Control saves you money and reduces your carbon footprint! Efficient Boiler Control Honeywell s Sola Boiler Control offers energy

More information

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules

7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules 7800 SERIES EC7895A,C; RM7895A,B,C,D and RM7896A,B,C,D Relay Modules SPECIFICATION DATA FEATURES APPLICATION The Honeywell EC7895/RM7895/RM7896 is a microprocessor based integrated burner control for automatically

More information

SIL3. C7961E,F Dynamic Self-Check Ultraviolet Flame Detector. Capable APPLICATION FEATURES PRODUCT DATA. Contents

SIL3. C7961E,F Dynamic Self-Check Ultraviolet Flame Detector. Capable APPLICATION FEATURES PRODUCT DATA. Contents C796E,F Dynamic Self-Check Ultraviolet Flame Detector PRODUCT DATA C796F C796E Detectors can be mounted horizontally, vertically or at any other angle providing the orientation arrow is pointing down.

More information

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors. Fire Sentry Corporation (FSC) 593 Apollo Street Tel.: 714-671-1100 Brea, California 92821 Fax: 714-671-5821 Multi-Spectral, Digital, Infrared Electro-Optical FSC Model No. s FS10-R and FS10-A Unitized,

More information

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071 SLATE UV Ampli-Check Flame Amplifier R8001S1071 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform.

More information

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY AUTOMATIC BURNER CONTROL SYSTEM The burner control unit Quad400 is suitable for the control of direct ignition burners up to 350 kw, pursuant to EN 746-2. Flame control by means of UV scanner or ionization

More information

Level gauges Series LS Level indicator, switch and transmitter for liquids

Level gauges Series LS Level indicator, switch and transmitter for liquids Level gauges Series LS Level indicator, switch and transmitter for liquids Simple construction Resistant under extreme temperature and pressure conditions No risk of leakage Measuring range: from 150 mm

More information

Power Flame Incorporated

Power Flame Incorporated Power Flame Incorporated SUGGESTED SPECIFICATION FOR MODEL NVC ULTRA LOW NOx GAS BURNERS SUB 9 PPM NOx THE POWER TO MANAGE ENERGY 2001 South 21st Street, Parsons, Kansas 67357 Telephone: 620-421-0480,

More information

M2500 Engine Controller Installation Manual

M2500 Engine Controller Installation Manual M2500 Engine Controller Installation Manual Revision: 23-04-2012 Page 1 Contents 1 Preface... 4 2 Installation... 5 3 Terminal Connections... 6 4 Inputs... 7 4.1 Power Supply... 7 4.2 Mode/ Control Inputs...

More information

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place 8.. Edition 08.0 D GB F NL I E DK S N P GR TR CZ PL RUS H www.docuthek.com Operating instructions UV sensor UVS 0 Translation from the German 008 009 Elster GmbH Contents UV sensor UVS 0......................

More information

7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules

7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules 7800 SERIES: EC7895A,C; RM7895A,B,C,D; RM7896A,B,C,D RM7897A,C and RM7898A Relay Modules SPECIFICATION DATA The RM7897A1002 offers selectable pilot operation, intermittent on terminal 8 or interrupted

More information

7800 SERIES EC7823/RM7823 Relay Module

7800 SERIES EC7823/RM7823 Relay Module 7800 SERIES EC7823/RM7823 Relay Module FEATURES SPECIFICATION DATA APPLICATION The Honeywell EC7823/RM7823 is a microprocessor based Flame Detector Relay that can be fitted with any 7800 SERIES amplifier

More information

B-40/B-41 Modulating Temperature Controller

B-40/B-41 Modulating Temperature Controller INSTALLATION & OPERATING INSTRUCTIONS B-40/B-41 Modulating Temperature Controller For Raytherm Boilers & Water Heaters H2 514-4001 WH2 2100-4001 Catalog No. 5000.70 Effective: 12-21-11 Replaces: NEW P/N

More information

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY >OLYL >H]LSLUN[O 4H[[LYZ SMOKELESS FLARE MONITOR Smokeless Flare Monitor (FM) Smokeless flares incinerate flammable hazardous

More information

1. Quick start-up guide

1. Quick start-up guide 1. Quick start-up guide This quick guide leads the way to install, start-up and configure necessary parameters in the normal cases. 1. PREPARING INSTALLATION Install fiber optic cable inside conduit. This

More information

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies Flame Rod Holder & Flame Rod Assemblies The small size of these devices enable their application to flame detection in installations where space is limited. The holder and flame rod assemblies facilitate

More information

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL IRIS IP65 IRIS UNISCAN APPLICATION MANUAL 01/08/05 DESCRIPTION TABLE OF CONTENTS PAGE IRIS - UNISCAN... 1 SPECIFICATION... 1 SUPPLY VOLTAGE: -... 1 OUTPUTS: -... 1 TRANSMISSION: -... 1 CABLE: -... 1 FLAME

More information

FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832

FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832 FLAME DETECTOR ADAPTERS 8832 through 8839 and Series R Bulletin 8832 February 2013 8835-R with C7061A U. V. Scanner s simplify installation of fl ame detectors on Fives North American burners. They also

More information

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features. CONsOlIDATOR 4 & 8 MulTI- C h ANNEl CONTROllERs ConsoliDator 4 Model PD940 ConsoliDator 4 Features Four 4-20 Four 4-20 Outputs ConsoliDator 8 Features Eight 4-20 Two 4-20 Outputs Common Features Four Pulse

More information

55UV5 SCANNER MODEL 1010

55UV5 SCANNER MODEL 1010 133-721 MAY 6, 2013 55UV5 SCANNER MODEL 1010 NEMA 4X, IP66 CLASS I, DIV 2, GROUPS A, B, C, D CLASS II, CLASS III, DIV 2, GROUPS F and G APPROVED This bulletin is directed to the licensed boiler service

More information

Model 3300 Technical Support and Installation Manual

Model 3300 Technical Support and Installation Manual Model 3300 Technical Support and Installation Manual Manual # T15011 Document Revision: A1 1. OVERVIEW 1 2. BASIC OPERATION 1 2.1 General 1 2.2 Field-of-View 2 2.3 Range 2 2.4 Environment 2 2.5 Configuration

More information

COMPACT FLAME CONTROLLER CFC 100

COMPACT FLAME CONTROLLER CFC 100 COMPACT FLAME CONTROLLER CFC 100 TECHNICAL DESCRIPTION EDITION: TB CFC100 EN REV. 1 2012-03-07 IMPORTANT: Please note, that all mounting and wiring as well as all changing or adjustment at the flame monitoring

More information

C7061A Dynamic Self-Check Ultraviolet Flame Detector

C7061A Dynamic Self-Check Ultraviolet Flame Detector C7061A Dynamic Self-Check Ultraviolet Flame Detector FEATURES PRODUCT DATA Oscillating shutter interrupts ultraviolet radiation reaching the UV sensor 12 times per minute to provide the UV sensor tube

More information

UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations

UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations KLC 10 Technical information UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations Description The KLC 10 is a compact UV flame detector, which has been developed

More information

Rota-Sonde DC4000-L. Laser pointer for easy alignment. Remote control of the sensitivity

Rota-Sonde DC4000-L. Laser pointer for easy alignment. Remote control of the sensitivity Scanning HOT METAL DETECTOR Rota-Sonde DC4000-L Two sensitivity ranges : 400 C and 230 C Laser pointer for easy alignment Remote control of the sensitivity Self-monitoring ISO 9001 Applications Benefits

More information

Flame Detector. Model: ZT-30P. User Guide. Document Ref: GLT Zeta Alarms Limited Morfa Road, Swansea, SA1 2EN, United Kingdom

Flame Detector. Model: ZT-30P. User Guide. Document Ref: GLT Zeta Alarms Limited Morfa Road, Swansea, SA1 2EN, United Kingdom Flame Detector Model: ZT-30P User Guide Document Ref: GLT-300-7-1 Zeta Alarms Limited 72 78 Morfa Road, Swansea, SA1 2EN, United Kingdom Phone: +441792 455 175 Fax: +441792 455 176 Website: www.zetaalarmsystems.com

More information

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVO-400 INDIRECT FIRED SPACE HEATERS OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) For FVO-400 INDIRECT FIRED SPACE HEATERS CERTIFIED FOR USE IN CANADA AND U.S.A. As per CSA B140.8 Portable Oil Fired Heaters / CSA B140.02003

More information

U2 Combination Viewing Head and Signal Processors

U2 Combination Viewing Head and Signal Processors U2 Combination Viewing Head and Signal Processors APPLICATION USER MANUAL Each sensor in the U2 has a different response which is suitable for certain applications. The UVTRON tube detector has a peak

More information

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh

AFUE up to 85.2% Heating Input 105,000 to 245,000 Btuh WATER HEATERS / BOILERS COWB3 Oil-Fired Hot Water Boiler PRODUCT SPECIFICATIONS Bulletin No. 0654 March 08 Supersedes September 05 AFUE up to 85.% Heating Input 05,000 to 45,000 Btuh MODEL NUMBER IDENTIFICATION

More information

Table of Contents. Part Number Index SANDYS INDUSTRIAL GLASS WHEELER A

Table of Contents. Part Number Index SANDYS INDUSTRIAL GLASS WHEELER A Table of Contents Part Number Index MANUFACTURER Page MANUFACTURER Page 1 1271A 1271B -211-B15 182EA 2 220736B 5 5/8X10RL 5/8X12RL 5/8X18RL 5/8X24RL 5/8X36RL 5/8X48HDRL 5/8X60RL 6 CONBRACO 6012 WHEELER

More information

Knürr RMS Compact II. Knürr RMS Compact II 2.81

Knürr RMS Compact II. Knürr RMS Compact II 2.81 Knürr RMS Compact II Knürr RMS Compact II 2.82 to 2.85 2.81 Knürr RMS Compact II Damage prevention with checks and controls System and network management requirements mean the systems ambient conditions

More information

Model D12-IR. Digital Gas Transmitter...

Model D12-IR. Digital Gas Transmitter... Model D12-IR Digital Gas Transmitter... ATI s Series D12 gas transmitter line now includes a versatile Infrared system that can be configured for LEL or select toxic gases. The D12-IR utilizes a compact

More information

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector) SMAC Controller Industrial Lubrication Systems Operation The SMAC Controller is a multi-purpose programmable controller used with industrial lubrication systems. Controller settings are saved whenever

More information

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001 SLATE Burner Control Module R8001B2001 INSTALLATION INSTRUCTIONS Scan for more information Application SLATE brings configurable safety and programmable logic together into one single platform. The platform

More information

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas HVAC Guideline Specifications WHISPER-JET: SET SERIES Two Stage Positive Pressure Gas-Fired Infrared Radiant Tube Type Heater Commercial/Industrial Applications Technical Summary Input Range: 80,000/60,000

More information

S55XB and S55XBE Series Viewing Heads

S55XB and S55XBE Series Viewing Heads S55XB and S55XBE Series Viewing Heads APPLICATION SPECIFICATION DATA The Honeywell S55xx product family comprises UV/IR viewing heads intended for flame scanning applications. These viewing heads must

More information

Indirect gas-fired air heater

Indirect gas-fired air heater Indirect gas-fired air heater SERIES HD INSTALLATION AND SERVICE MANUAL MANUFACTURED BY : BROTHERS LIMITED WARNING Improper installation, modification, adjustment or maintenance may cause damage, injury

More information

MBCE-110/230FR Flame Sensor Module

MBCE-110/230FR Flame Sensor Module MBCE-1001 FEBRAURY 6, 2017 MBCE-110/230FR Flame Sensor Module exida FMEDA SIL2 SEE NOTE 1 ON PAGE 4 DESCRIPTION The MBCE-110/230FR modules provide visual indication and electrical outputs that signal the

More information

DIESEL Engine Fire Pump Controllers Features

DIESEL Engine Fire Pump Controllers Features September 007 DIESEL Engine Fire Pump Controllers Features FD0 Diesel Engine Controllers 1-1 Printer / Recorder The industrial grade thermal printer is housed in a rugged steel enclosure within the controller.

More information

BC-R10 Series. Burner Controllers

BC-R10 Series. Burner Controllers No. CP-SS-1885E BC-R10 Series Burner Controllers Summary BC-R10 Series burner controllers are combustion safety controllers specifically designed for batch operation (systems which start and stop at least

More information

1.03 DELIVERY, STORAGE, AND HANDLING Heater will be stored to secure against damage and handled per manufacturer s recommendations.

1.03 DELIVERY, STORAGE, AND HANDLING Heater will be stored to secure against damage and handled per manufacturer s recommendations. HVAC Guideline Specifications supraschwank Packaged Luminous Infrared Radiant Gas Heater Combined Intensity (produces both Low and High Intensity radiant output) Commercial/Industrial Applications Size

More information

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B)

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B) Flame scanner for gas and oil burners (Rev. B) Application: - Wall fired boilers - Gas and oil burners High sensitive UV tube Continuous self-checking Rugged detector head for harsh environments: - Protection

More information

Interrupted Ignition Series Oil Primary Control

Interrupted Ignition Series Oil Primary Control Interrupted Ignition Series Oil Primary Control Application Guide & Installation Instruction for ICM1511*, ICM1512*, ICM151*, ICM1514* For more information on our complete range of American-made products

More information

C7012A,C,E,F,G Solid State Purple Peeper Ultraviolet Flame Detectors

C7012A,C,E,F,G Solid State Purple Peeper Ultraviolet Flame Detectors C70A,C,E,F,G Solid State Purple Peeper Ultraviolet Flame Detectors PRODUCT DATA APPLICATION The C70A,C,E,F,G Flame Detectors are solid-state electronic devices for sensing the ultraviolet radiation emitted

More information

DOMESTIC HOT WATER Follow operational sequence

DOMESTIC HOT WATER Follow operational sequence DOMESTIC HOT WATER Follow operational sequence Turn Winter/Summer selector to Summer position. The display is switch on. Go to section A Error 110 flashing Error 131 flashing Turn the selector to reset

More information

EUROBOX SERIES TYPES CM...N SM...N MM...N

EUROBOX SERIES TYPES CM...N SM...N MM...N EUROBOX SERIES TYPES CM...N SM...N MM...N AUTOMATIC CONTROL SYSTEMS FOR GAS BURNERS AND GAS BURNING APPLIANCES WITH OR WITHOUT FAN (MANUAL RESET) DESCRIPTION This series of electronic systems is suitable

More information