1 Pilz Safety Lockout System (PSLS) An alternative isolation method for LOTO By Doug Sten, Safety Consultant, Pilz Automation Safety

2 Objectives Challenges with manual, mechanical isolation disconnects Challenges with using a contactor as an isolator Solution: UL 6420 Equipment Used for System Isolation and Rated as a Single Unit OSHA acceptance for LOTO via System Isolation Equipment Filing for Variances; Federal and State

3 Traditional mechanical isolation devices Larger sizes rated only 2,000 operations, most are rated at 8,000 operations Frequent use AC23a rating provides 20,000 operations 1 isolation cycle = 2 operations Over a 20 year mission life = 1.3 operations per day Changing out disconnects is expensive and inherently an unsafe job

4 Traditional mechanical Disconnects can fail unsafe isolation devices The operator is required to stand next to the door to throw the lever, putting him in harms way if there is a fault Phases may remain energized even when locked out

5 Traditional mechanical isolation devices Clearance of 36 in front of the disconnect enclosure is required Series connected disconnects for multiple access points can lead to false zero voltage verification because a disconnect upstream may be off Wet cleaning in food-grade environments are especially dangerous when high voltage disconnects are accessible After a power failure, a manual disconnect stays on leaving the potential for hazardous energy to be present when power is reapplied

6 Contactor as an energy isolation device A contactor system is optimal for high cycle rates but is not an isolating device, unless AC-23a rated as a unit Normal contactor endurance testing per IEC uses 6x rated current; AC23a requires 10x rated current and almost twice the cycle count Normal contactor testing per IEC for SSCR (Short Circuit Current Rating) type 2 coordination with the protection device (fuse, CB) allows the contacts to tack weld closed if it can be broken free easily

7 Contactor as an energy isolation device Common cause failure In a dual contactor arrangement both contactors can weld on same phase when subjected to a fault current This inhibits motion in a typical guard door interlock but does not isolate energy To meet ISO13849, dual channel requires the system must be tested for this common cause failure to qualify for safety of energy isolation

8 UL 6420: Controls/contactor as an isolation device Equipment Used for System Isolation and Rated as a Single Unit Electromechanical contactors remotely controlled and monitored to provide remote isolation status indication with a defined integrity level Used both as a means for removal of power for prevention of unexpected start-up of a stopped machine and as an isolator to provide protection from electric shock by ensuring the removal of electrical energy This equipment is intended for installation in accordance with the National Electrical Code, NFPA 70 and the Electrical Standard for Industrial Machinery, NFPA 79: 2012

9 UL 6420: Controls/contactor as an isolation device Equipment Used for System Isolation and Rated as a Single Unit Principally intended for industrial machine applications where, isolation of power is so frequently required that the mechanical life of a typical disconnecting means is unacceptably short or where there are multiple entry points on the machine where disconnection is required, or both. Note Multiple entry points are a function of access needs and the layout of the machine. In 2015, OSHA added the ANSI/UL 6420 for product approvals by a Nationally Recognized Testing Laboratory (NRTL). Reference: OSHA

10 Additional PSLS machine control interfaces UL 6420, 4.8.1: System isolation equipment can be configured to meet additional machine control interface applications such as: Safety related interface signal and feedback channels for Guard door locked status Release signal for guard locks Signal to and feedback from safety pneumatic control valve Signal from E-stop devices to and feedback from E-stop systems Run permissive to machine drive control system Zero speed signals from drive Signal to machine stop

11 Additional PSLS machine control interfaces UL 6420, 4.8.1: System isolation equipment can be configured to meet additional machine control interface applications such as: Information related interface channels Lockout switch positions (open or closed) Isolation system component status and troubleshooting aids Isolation system equipment status

12 Safety Lockout System Description A system to safely disconnect machines and facilities from electrical, hydraulic and pneumatic power, provide automatic zero energy verification in order to protect personnel and comply with industry standards to prevent unexpected start-up The power isolation is a control reliable design and uses dual channel circuitry in the disconnect path The concept is the same as a lockout tagout procedure with automatic verification (No light, No enter) UL 6420 System Isolation Equipment: the Pilz SLS system may be used as an isolation disconnect means for electrical servicing per NEC (A)(7) and NFPA section 5.5.4(3)

13 Characteristics The energy isolation systems are modular in design Large complex systems require Pilz integration and can consist of: Multiple electrical power SLS Panel Optional Interface Panel or Remote Interface Subpanel PSS4000 Safety PLC Panel RLS Remote Lockout Switch Optional Pneumatic Exhaust Dump Valve Interface Optional Hydraulic Exhaust Dump Valve Interface Long Distance connections via SafetyNET and fiber optics

14 Characteristics For simple disconnect replacement, OEM/User installed systems consist of Main electrical SLS Panel w/ PNOZmulti Controller Optional Marshalling Boxes for expansion Optional Pneumatic Exhaust Dump Valve Interface Optional Hydraulic Exhaust Dump Valve Interface

15 Design principle RLS 1 OFF ON Pilz SLS RLS 2 RLS 3 OFF OFF ON ON PSS or PNOZmulti Controller Redundant Isolation Contactors and Voltage Monitor Optional C-Stop(s) or E-Stop(s) P P Redundant Valve(s) and Dual PS Feedback

16 Multi system More Marshalling Panels 8 more RLS Optional Marshalling Panel 480Vac Line Power 8 Remote Lockout Stations per main panel Power and Control Panel Hydraulic Isolation Panel Isolated 480Vac Load Power SRP/CS Interface E-Stop, Interlock Interface and Dual Contact System Isolated Feedback Ethernet Communication for fault and system status Pneumatic Isolation Panel

17 Systems Wall mount systems: 60A, 100A, 200A Floor mount systems: 200A, 400A, 600A

18 Adding fluid power Pneumatic isolation will be added to the standard end of 2018 Hydraulic Isolation to be added in 2019 A plug-in pneumatic panel with inlet pressure switch and dual, calibrated zero pressure, factory tested, verification switches is provided for isolation to ISO Category 4, PL e

19 System isolation equipment Advantages Safe disconnect (isolation) of machine or zone hazardous energy Prevention of unintended start-up Zero energy verification and visual acknowledgement of the safe state (no need to suit up for zero voltage verification) Long lifetime, compared to traditional disconnect switches designed for high cycle frequency and 20 year mission life Remote operation removes operator from power switching elements Electrical and fluid power isolation with a single remote lockout station (just 1 lock)

20 System isolation equipment Advantages Economical placement of lockout points at each access promotes using proper procedures Flexible configuration for large and diverse machines and facilities Clearance of 36 in front of the Remote Lockout Station is not needed because it is 24VDC low current Removes the operator from hazards associated with wash down environments by removing the presence of 480VAC at the access point

21 NEC accepts PSLS The National Electrical Code (NFPA 70:2005) System isolation equipment: A redundant monitored, remotely operated contactor isolation system, packaged to provide the disconnection/isolation function, capable of verifiable operation from multiple remote locations, each having the capability of being padlocked in the off (open) position System Isolation Equipment shall be listed for disconnection purposes SIE shall be installed on the load side of the current protection and the related disconnecting means

22 NFPA 70E allows PSLS and PU3Z The 2018 edition of NFPA 70E Standard for Electrical Safety has added an exception specifically to allow SLS use of permanently mounted voltage monitor for verification of absence of voltage for electrical servicing. Prior to the exception one had to suit up in arc flash gear and use a hand held instrument. Now not just the SLS but any electrical panel can use the PNOZ PU3Z in a LOTO procedure for un-expected startup OR electrical servicing. From clause 120.5(7):

23 NFPA79 accepts PSLS NFPA The following devices shall be permitted to fulfill the isolating function: (1) Devices described in (2) A manual motor starter marked suitable for motor disconnect and compliance with UL 508 where located on the supply side of the last short circuit protection device (in the branch) (3) System isolation equipment that incorporates control lockout stations and is listed for disconnection purposes where located on the load side of the main supply circuit disconnecting means and over-current protection

24 ANSI Z LOTO and alternative measures 3.12 Energy Isolating Device. A means of preventing the transmission or release of energy. NOTE 4: System isolation equipment that incorporates control lockout stations and is listed for disconnection purposes where located on the load side of the main supply circuit disconnecting means and over-current protection can be energy isolating devices. See NFPA Other Means of Hazardous Energy Isolation. Remotely activated electro-mechanical lockout systems are an acceptable alternative to be used in selected applications such as long machines and inaccessible or inconvenient locations of primary isolation devices. The user shall install and operate such systems (e.g., remote low voltage lockout system, pneumatics systems) in accordance with the manufacturer s directions. See Annex B for further details. See NFPA 79.

25 ANSI Z Location. Energy isolating devices shall be accessible and, where practicable, be conveniently located to facilitate the application of isolating devices during necessary tasks. Energy isolating device should be located outside hazardous areas and at a convenient height from an adjacent walking area (i.e. not overhead or under machinery). If unable to position or install isolating device(s) at a convenient location, measures shall be taken to provide proper access to the devices. NOTE: As an example, a remote lockout or a system isolation equipment rated as a unit and listed for the purpose of isolating energy may be implemented as one such measure. See Annex B.

26 ANSI Z Annex B Remote Lockout Systems Justification to use a remote lockout system instead of a manual disconnect for service disconnect isolation purposes includes: When frequency of the task exceeds the capability of a manual disconnect When environment is not acceptable to place a manual disconnect Large complicated machinery involving many lockout devices making the lockout procedure too cumbersome Reduce to a single lock point directly at the access point To prevent machine operators from standing in front of large disconnect switches in case of short circuit fault

27 ANSI Z Annex B Remote Lockout Systems Justification to use a remote lockout system instead of a manual disconnect for service disconnect isolation purposes includes: Large disconnects can be physically hard to operate for some operators Required spaces not available (service access, electrical hazards, adequate ventilation, etc.) NOTE: Types of electrical lockout systems available include, but are not limited to remote low voltage system, and listed system isolation equipment.

28 PSLS in the US In 2015 OSHA accepted the standard into National Recognized testing Laboratory (NRTL) program as an acceptable standard a NRTL can certify product to and we are listed by UL By using UL6420 listed product the user meets NEC, NFPA79 and Z244.1 OSHA historically has moved slow in updating Prevention of unexpected startup which has not been updated since it was made law in OSHA currently has under review for an update

29 PSLS in the US OSHA deems electrical equipment acceptable for use if there is a standard for the product accepted and listed in the table in Our systems are proven in use since 1996 with no cases of a dangerous failure or OSHA citation for using it

30 OSHA 29 CFR Subpart S, Electrical , Definitions applicable to this subpar Acceptable. An installation or equipment is acceptable to the Assistant Secretary of Labor, and approved within the meaning of this Subpart S: (1) If it is accepted, or certified, or listed, or labeled, or otherwise determined to be safe by a nationally recognized testing laboratory recognized pursuant to Accepted. An installation is "accepted" if it has been inspected and found by a nationally recognized testing laboratory (e.g. UL) to conform to specified plans or to procedures of applicable codes.

31 Variance: Federal / State OSHA Variance is an alternative procedure of compliance with some part of a safety and health standard granted by OSHA. Employer may not be able to comply fully and on time with a new safety or health standard because of a shortage of personnel, materials, or equipment. Employer may prefer to use methods, equipment, or facilities that they believe protect workers as well as or better than OSHA standards. See Title 29 of the Code of Federal Regulations (CFR), Part 1905, Rules of Practice

32 Types of variances Temporary Variance - Allows employers a short term (limited time) relief - Employer must implement an effective compliance program as quickly as possible - The employer must demonstrate to OSHA that all available steps are being taken to safeguard workers. - Inability to afford compliance costs is not a valid reason

33 Types of variances Interim order - Permits an employer to continue operating under existing conditions while OSHA considers the employer s request employers - Must inform workers by giving a copy of the order to authorized employee representatives and posting a copy prominently in the workplace

34 Types of variances Permanent variance Grants an alternative means of compliance with the requirements of a standard to employers who can prove that their methods, conditions, practices, operations, or processes provide workplaces that are as safe and healthful as those that follow the OSHA standards - machine specific Employers must let workers know they have filed the application and that the workers have the right to request a hearing OSHA reviews the employer s evidence and, if appropriate, visits the workplace to confirm the facts provided in the application

35 Types of variances Permanent variance Final variance orders detail the employer s specific responsibilities and requirements and explain exactly how the employer s method varies from the OSHA requirement Application for a permanent variance, see 29 CFR Part Subpart B Visit OSHA s website at variances /apply.html

36 Thank You Doug Sten, Safety Consultant Pilz Automation Safety, L.P Commerce Blvd. Canton, MI Telephone: +1 (734)

NECA S System Approach to Electrical Safety for NFPA 70E

NECA S System Approach to Electrical Safety for NFPA 70E NECA S System Approach to Electrical Safety for NFPA 70E NECA s Systems Approach to NFPA 70E Easy to understand NFPA 70E employer requirements, Provides Supervisors with key on the job information, De-energize

More information

6/23/ National Electrical Contractors Association and Intec, Inc.

6/23/ National Electrical Contractors Association and Intec, Inc. 2012 National Electrical Contractors Association and Intec, Inc. 1 Palmer Hickman Director of Codes and Standards electrical training ALLIANCE Jim Dollard Safety IBEW 98 Objectives Explain why work should

More information

NECA S System Approach to Electrical Safety for NFPA 70E

NECA S System Approach to Electrical Safety for NFPA 70E NECA S System Approach to Electrical Safety for NFPA 70E NECA s Systems Approach to NFPA 70E Easy to understand NFPA 70E employer requirements, Provides Supervisors with key on the job information, De

More information

The Minor Servicing Exemption LOTO s Misunderstood Requirement

The Minor Servicing Exemption LOTO s Misunderstood Requirement The Minor Servicing Exemption LOTO s Misunderstood Requirement Carlos Gallegos Assistant Area Director - Response Team Aurora Area Office gallegos.carlos@dol.gov Goals Review LOTO application Define employee

More information

Occupational Safety Next Review Date: 12/20/17. Scope: University Wide Original Creation Date: 2009

Occupational Safety Next Review Date: 12/20/17. Scope: University Wide Original Creation Date: 2009 Stony Brook University EH&S Policy and Procedure Subject: 3-2 The Control of Hazardous Energy (Lockout Tagout) Published Date: 12/20/16 Occupational Safety Next Review Date: 12/20/17 Scope: University

More information

SUMMARY: Policy Title: Electrical Safety Work Practice Program. Policy Number: UNIV-EHS 430 Policy Approved: January 2014

SUMMARY: Policy Title: Electrical Safety Work Practice Program. Policy Number: UNIV-EHS 430 Policy Approved: January 2014 Policy Title: Electrical Safety Work Practice Program Policy Number: UNIV-EHS 430 Policy Approved: January 2014 Policies Superseded: FINA-730 Policy Management Area: Environmental Health and Safety Created/Revision(s):

More information

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove Jim Dungar, P.E. Principal Engineer Schneider Electric Engineering Services Jim.dungar@schneider-electric.com (920-766-8012)

More information

NFPA 70E Electrical Safety & Arc Flash Training

NFPA 70E Electrical Safety & Arc Flash Training NFPA 70E Electrical Safety & Arc Flash Training OSHA 1910.332(a) Training, 1910.332(a) Scope. The training requirements contained in this section apply to employees who face a risk of electric shock that

More information

IEEE Std IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations

IEEE Std IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations IEEE Std 45.5-2014 IEEE Recommended Practice for Electrical Installations on Shipboard Safety Considerations Presented by Dennis K. Neitzel, CPE, CESCP Director Emeritus Keeping People Safe from Electrical

More information

Electrical Hazards and NFPA-70E: Protecting Your Employees

Electrical Hazards and NFPA-70E: Protecting Your Employees Electrical Hazards and NFPA-70E: Protecting Your Employees Presented By Mark B. Haskins, MS, CSP Practical Safety Solutions, LLC At the CBIA Safety Health and Wellness Conference May 22, 2014 PRESENTATION

More information

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards

T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards T22 - Arc Flash Hazards and Arc Resistant Equipment- Understanding the Standards v2-5058-co900h Copyright 2016 Rockwell Automation, Inc. All Rights Reserved. 1 Agenda 1. Background 2. Related Electrical

More information

How many time has your company been asked by an owner or customer to work on equipment energized?

How many time has your company been asked by an owner or customer to work on equipment energized? How many time has your company been asked by an owner or customer to work on equipment energized? How many times has an electrician choose to not turn a circuit off because it was an inconvenience? How

More information

PROTECTING AGAINST ARC FLASH HAZARDS

PROTECTING AGAINST ARC FLASH HAZARDS PROTECTING AGAINST ARC FLASH HAZARDS Presented by: Andrew J. Fitzpatrick, P.E. Electricity Simply stated electricity is the flow of electrons Electricity is governed by laws: Ohms Law : V=IR Kirchoff s

More information

NFPA 70E Edition Update

NFPA 70E Edition Update NFPA 70E- 2018 Edition Update Paul Colangelo- STSC, CHST, CET, CRIS National Director of Compliance Programs ClickSafety 1 ASSE Construction Practice Specialty Quarterly Meeting 11/17/2017 Agenda Overview

More information

ENERGY CONTROL LOCKOUT/TAGOUT PROGRAM PLAN

ENERGY CONTROL LOCKOUT/TAGOUT PROGRAM PLAN ENERGY CONTROL LOCKOUT/TAGOUT PROGRAM PLAN Published by Environmental Health and Safety Last updated: 1/25/2017 Page 1 of 16 1. INTRODUCTION John Jay College Environmental Health and Safety (EHS) office

More information

VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage

VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted

More information

The safe way to verify the absence of voltage.

The safe way to verify the absence of voltage. VeriSafe Absence of Voltage Tester The safe way to verify the absence of voltage www.panduit.com/verisafe What is an Absence of Voltage Tester? Absence of Voltage Testers (AVTs) are permanently-mounted

More information

Your Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000

Your Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000 Your Global Automation Partner Minimizing Arc Flash Exposure in Industrial Applications White Paper - W1000 Industrial environments present multiple safety challenges, including fire hazards that require

More information

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 AGENDA Definition of Safety? Machinery Safety Standards Comparison of ISO 13849-1 and IEC 62061 Safety-related

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 This section specifies the furnishing, complete installation, and connection of automatic transfer switches. 1.2 RELATED WORK A. Section 14 21 00, ELECTRIC

More information

Electrical Safety Program.

Electrical Safety Program. University of North Carolina Wilmington Environmental Health & Safety Workplace Safety Electrical Safety Program GENERAL The UNCW Environmental Health & Safety Department (EH&S) is authorized by UNCW Policy

More information

F&S Control of Hazardous Energy Program

F&S Control of Hazardous Energy Program University of Illinois at Urbana-Champaign Facilities & Services Division of Safety and Compliance F&S Control of Hazardous Energy Program February 2013 Last updated by: j. neighbors Page 1 of 12 Last

More information

Lock Out/Tag Out: Control of Hazardous Energy (LOTO) Environmental Health &Safety / Risk Management

Lock Out/Tag Out: Control of Hazardous Energy (LOTO) Environmental Health &Safety / Risk Management Lock Out/Tag Out: Control of Hazardous Energy (LOTO) Environmental Health &Safety / Risk Management 229-4503 LOTO "Lockout/Tagout (LOTO)" refers to specific practices and procedures to safeguard employees

More information

SECTION SECURITY TESTING AND COMMISSIONING

SECTION SECURITY TESTING AND COMMISSIONING SECTION 280800 - SECURITY TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 WORK INCLUDES A. General Description: This specification section covers the provision of preliminary testing, acceptance testing,

More information

Safety Function: Single-beam Area Access Control (AAC)

Safety Function: Single-beam Area Access Control (AAC) Application Technique Safety Function: Single-beam Area Access Control (AAC) Products: Guardmaster Dual-input Safety Relay, Single-beam Area Access Control Sensors with E-stop Safety Rating: CAT. 4, PLe

More information

Electrical Safety Program

Electrical Safety Program Electrical Safety Program Developed by: The Office of Environmental Health and Safety June, 2010 Table of Contents Introduction 3 Scope..3 Definitions.3-5 CSU Electrical Shop...5 Responsibilities.5-6 Employees.....5

More information

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc.

9/7/2010. Chapter , The McGraw-Hill Companies, Inc. AND BONDING. 2010, The McGraw-Hill Companies, Inc. Chapter 1 GROUNDING AND BONDING 1 Proper grounding practices protect people from the hazards of electric shock and ensure the correct operation of overcurrent protection devices. Grounding is the intentional

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

Safe Maintenance Practices for Skilled Care Facilities

Safe Maintenance Practices for Skilled Care Facilities Safe Maintenance Practices for Skilled Care Facilities Part One: Lockout/Tagout Today s Presenter: Darrell G. Toenjes, ARM, CHSP, CWCP Healthcare Practice Leader Midwest Employers Casualty Company 25 years

More information

Contractor Safety. Workplace Safety & Environmental Division

Contractor Safety. Workplace Safety & Environmental Division Contractor Safety Workplace Safety & Environmental Division Click to edit Master title style This information is designed for tradespersons and persons supervising tradespersons who are performing work

More information

SEL Arc-Flash Solutions

SEL Arc-Flash Solutions SEL Arc-Flash Solutions Arc-Flash Protection at the Speed of Light Protect personnel and equipment. Detect arc-flash events and send a trip signal in as little as 2 ms to enhance safety and minimize equipment

More information

STANDARDS UPDATE NOTICE (SUN) ISSUED: March 28, 2018

STANDARDS UPDATE NOTICE (SUN) ISSUED: March 28, 2018 STANDARDS UPDATE NOTICE (SUN) ISSUED: March 28, 2018 STANDARD INFORMATION Standard Number: ANSI Z245.21 Standard Name: Stationary Compactors Safety Requirements for Manufacturing and Reconstruction Standard

More information

NECA. Standard for Electrical Safety in the Workplace

NECA. Standard for Electrical Safety in the Workplace 4/23/2018 N E R C e- A di st N rib ot ut Fo io r n NECA Significant Changes to the 2018 NFPA 70E Standard for Electrical Safety in the Workplace NFPA 70E Standard for Electrical Safety in the Workplace

More information

Arc Flash Analysis. Arc flash hazard analysis is required to determine the risk to personnel, warn them of the

Arc Flash Analysis. Arc flash hazard analysis is required to determine the risk to personnel, warn them of the GROUP Arc Flash Analysis Arc Flash Hazard Analysis : Arc flash hazard analysis is required to determine the risk to personnel, warn them of the hazards, and to instruct working personals as to what kind

More information

InstrumentationTools.com

InstrumentationTools.com Author: Instrumentation Tools Categories: Safety Systems S84 / IEC 61511 Standard for Safety Instrumented Systems IEC 61511 is a technical standard which sets out practices in the engineering of systems

More information

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC

NFPA 70E Arc Flash Considerations for MV Equipment. By: Dominik Pieniazek, P.E. HV Engineering, LLC NFPA 70E Arc Flash Considerations for MV Equipment By: Dominik Pieniazek, P.E. dominik@hv-eng.com HV Engineering, LLC http://sites.ieee.org/houston/ Full link for PDF copies of presentations: http://sites.ieee.org/houston/communities/ie

More information

National Electrical Code

National Electrical Code National Electrical Code 409.30 Disconnecting Means Disconnecting means that supply motor loads shall comply with Part IX of Article 30. 410.81 Control (A) Disconnection Luminaires (fixtures) or lamp installation

More information

Muskogee Public Schools. Lockout/Tagout. Program

Muskogee Public Schools. Lockout/Tagout. Program Muskogee Public Schools Lockout/Tagout Program May 15, 2014 1 MUSKOGEE PUBLIC SCHOOLS PROGRAM FOR THE CONTROL OF HAZARDOUS ENERGY Table of Contents I. Scope.3 II. Purpose..3 III. Definitions Applicable

More information

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 36 23 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between //--// if not applicable to project. Also, delete any other item or paragraph

More information

Machine Safeguarding and Lockout/Tagout Practices

Machine Safeguarding and Lockout/Tagout Practices Manufacturing Machine Safeguarding and Lockout/Tagout Practices On a daily basis, manufacturing employees may be asked to work with or interact with a wide variety of machinery and equipment. Some machines

More information

PGR-8800 TECHNICAL FAQ

PGR-8800 TECHNICAL FAQ PGR-8800 SOLAR ARC-FLASH PRODUCTS RELAY CATALOG TECHNICAL FAQ What are the typical applications / system voltages? The PGR-8800 can be used on electrical systems operating at any voltage (AC or DC) since

More information

NFPA 70E Standard for Electrical Safety in the Workplace. EEI Safety and Health Meeting May 2011

NFPA 70E Standard for Electrical Safety in the Workplace. EEI Safety and Health Meeting May 2011 NFPA 70E Standard for Electrical Safety in the Workplace EEI Safety and Health Meeting May 2011 NFPA Structure NFPA 70E Technical Committee reports to: NEC Technical Correlating Committee reports to: NFPA

More information

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation

Implementing an Energized Electrical Work Program. SESHA Hill Country Chapter. Brett Jay Davis, PE Zephyr Environmental Corporation Implementing an Energized Electrical Work Program SESHA Hill Country Chapter May 22, 2009 Brett Jay Davis, PE Zephyr Environmental Corporation bdavis@zephyrenv.com, 512 879-6628 Presentation Outline 1.

More information

Injury and Illness Prevention Program Quiz Answers

Injury and Illness Prevention Program Quiz Answers Injury and Illness Prevention Program Quiz Answers Name: 1. The company safety manager s responsibilities include a. Develop and implement rules of safe practices for each function within the company b.

More information

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100

2012 Edition. Tech Topics: Standards & Codes. Note 4, Issue 1. Points of Interest: Introduction. Background. Changes to Definitions in Article 100 Significant Changes to the NFPA 70E Standard 2012 Edition Tech Topics: Standards & Codes Note 4, Issue 1 Peter Walsh, PE Sr. Field Engineer Points of Interest: Arc-Rated (AR) vs. Flame-Resistant (FR) Training

More information

Digital EPIC 2 Safety manual

Digital EPIC 2 Safety manual Safety manual Before installation these instructions must be fully read and understood Table of contents Safety manual... 1 1. Introduction... 1 1.1 Terms and abbreviations... 2 1.2 Acronyms... 2 1.3 Product

More information

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland Scully Intellitrol Safety Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options TÜVRheinland Functional Safety Type Approved FS IEC 61508 Certified SIL 2 / SIL

More information

100 & 120 Series Pressure and Temperature Switches Safety Manual

100 & 120 Series Pressure and Temperature Switches Safety Manual 100 & 120 Series Pressure and Temperature Switches Safety Manual MECH-SM-01 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

ISIS SAFETY SYSTEM Installation guide

ISIS SAFETY SYSTEM Installation guide ISIS SAFETY SYSTEM Installation guide CAUTION This information is designed to help suitably qualified personnel install and operate Mechan Safety equipment. Before using this product, read this guide thoroughly

More information

THE BEST CHOICE FOR INDUSTRIAL MACHINE SAFEGUARDING. Machine Safety Solutions.

THE BEST CHOICE FOR INDUSTRIAL MACHINE SAFEGUARDING. Machine Safety Solutions. THE BEST CHOICE FOR INDUSTRIAL MACHINE SAFEGUARDING www.rockfordsystems.com Machine Safety Solutions INDUSTRIAL MACHINE SAFEGUARDING delivering turnkey machine safeguarding solutions for organizations

More information

2014 National Electrical Code & NFPA 70E/Arc Flash

2014 National Electrical Code & NFPA 70E/Arc Flash Gain an understanding of the 2014 NEC s latest additions, revisions and changes. Learn the precautions needed when working with and around electricity. People and property need to be safeguarded from the

More information

Options for Developing a Compliant PLC-based BMS

Options for Developing a Compliant PLC-based BMS Options for Developing a Compliant PLC-based BMS Jack Boone aesolutions Greenville, South Carolina, United States of America ABSTRACT Facilities are focusing on improving the reliability of their burner

More information

Electrical Safety Compliance: NFPA 70E

Electrical Safety Compliance: NFPA 70E Electrical Safety Compliance: NFPA 70E From Graybar and Schneider Electric Risks associated with shock and electrocution from inadvertent contact with energized parts have long been recognized as a threat

More information

Professional Seminar. The Electrically Safe Workplace. Understanding the NFPA 70E Electrical Safety Standard, 2012 Edition ...

Professional Seminar. The Electrically Safe Workplace. Understanding the NFPA 70E Electrical Safety Standard, 2012 Edition ... Professional Seminar The Electrically Safe Workplace Understanding the NFPA 70E Electrical Safety Standard, 2012 Edition Includes Complete Copy of NFPA 70E, 2012 Edition! Learn the Key Concepts of NFPA

More information

Setting the alarms in electrochemical sensor equipped toxic gas instruments

Setting the alarms in electrochemical sensor equipped toxic gas instruments : Setting the alarms in electrochemical sensor equipped toxic gas instruments out of the area before rather than after the concentration of toxic gas exceeds the hazardous condition threshold. Unfortunately,

More information

Safety requirements for voltage testing instruments

Safety requirements for voltage testing instruments MODEL POLICY Safety requirements for voltage testing instruments 1. FOREWORD 1.1. Approval 1.1.1. This standard is owned by. name of promulgating organization or department 1.1.2. Questions related to

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information

NFPA 70E Elevates Safety. with Heightened Risk Awareness

NFPA 70E Elevates Safety. with Heightened Risk Awareness NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness Next Page NFPA 70E 2015 Elevates Safety with Heightened Risk Awareness: Significant Changes Since 2012 Compel Updated Electrical Safety Training

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61784-3 INTERNATIONAL STANDARD Edition 1.0 2007-12 Industrial communication networks Profiles Part 3: Functional safety fieldbuses General rules and profile definitions INTERNATIONAL ELECTROTECHNICAL

More information

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations

Executive Summary. Shell Offshore Inc. BY: Keith M. Gonzales Sr., P.E. Regulatory Requirements for Hazardous Locations Contents Executive Summary... 1 Regulatory Requirements in the Gulf of Mexico for Hazardous Locations... 2 Referenced Codes and Standards... 2 Memorandum of Agreement... 2 Bureau of Ocean Energy Management

More information

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB 2CMT2016-005511 rev

More information

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY REVIEW DATE: 10/29/2002

MANUFACTURING TECHNICAL INSTRUCTIONS - SAFETY REVIEW DATE: 10/29/2002 1 of 15 AUTOMATION SAFEGUARDING REQUIREMENTS FOR DESIGN, CONSTRUCTION, MANUFACTURING AND INSTALLATION OF AUTOMATED SYSTEMS I. SCOPE AND PURPOSE A. Scope To provide guidelines for Design, construction,

More information

MACHINERY SAFEBOOK 5. Safety related control systems for machinery. Principles, standards and implementation. (Revision 5 of the Safebook series)

MACHINERY SAFEBOOK 5. Safety related control systems for machinery. Principles, standards and implementation. (Revision 5 of the Safebook series) Safety related control systems for machinery Principles, standards and implementation (Revision 5 of the Safebook series) MACHINERY SAFBOOK 5 Content Chapter 1 Regulations 2 EU Directives and Legislation,

More information

ESRB and ESRN Installation & Safety Instructions

ESRB and ESRN Installation & Safety Instructions B1784 ESRB and ESRN Installation & Safety Instructions IMPORTANT SAFEGUARDS When using electrical equipment, basic safety precautions should always be followed including the following: READ AND FOLLOW

More information

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators Rev 0, November 17 2015 Page 1 of 9 Table of Contents 1 INTRODUCTION 3 1.1 Terms and abbreviations 3 1.2 Acronyms 4 1.3

More information

Where Process Safety meets Machine Safety

Where Process Safety meets Machine Safety Where Process Safety meets Machine Safety A document to aid understanding between the end-user and machine builder for functional safety issues. by The 61508 Association Overriding key principle...it must

More information

Safety Control Modules for Emergency Stop Circuits FF-SRS5988 FF-SRS5935 FF-SRS5925 FF-SRS5934 FF-SRS5924 TYPICAL APPLICATIONS APPROVALS DIMENSIONS

Safety Control Modules for Emergency Stop Circuits FF-SRS5988 FF-SRS5935 FF-SRS5925 FF-SRS5934 FF-SRS5924 TYPICAL APPLICATIONS APPROVALS DIMENSIONS Safety Control Modules for Emergency Stop Circuits TYPICAL APPLICATIONS APPROVALS DIMENSIONS Single Channel Emergency Stop Module E-Stop circuits up to Category 2 (EN 954-) Sliding door protection Conveyors

More information

The plant meets the requirements of the current FSS 5 Checklist for Vessel Process Plants

The plant meets the requirements of the current FSS 5 Checklist for Vessel Process Plants FSS 5, Attachment 3: Safety list - Vessel Process Plants (powered devices, machines and facilities - not including industrial trucks) within Freudenberg Date: 2009-03-30 - Revision: 01 I. Nature of the

More information

Safety Instrumented Systems

Safety Instrumented Systems Safety Instrumented Systems What is a Safety Instrumented System? A Safety Instrumented System SIS is a new term used in standards like IEC 61511 or IEC 61508 for what used to be called Emergency Shutdown

More information

Control Panel 2.0 Installation Guide

Control Panel 2.0 Installation Guide Control Panel 2.0 Installation Guide Product Description The View Control Panel 2.0 houses the control components and power source that are responsible for the operation of a View Dynamic Glass system.

More information

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No User s Manual YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters Manual Change No. 16-045 Please use this manual change for the manuals listed below. 1. Applicable manuals, revised item, revised

More information

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems

Products Solutions Services CT287. Hazardous Area Classifications and Protection Systems Products Solutions Services CT287 Hazardous Area Classifications and Protection Systems Slide 1 Topics covered Types of Hazardous Area classifications with focus on North America Types of hazardous protection

More information

Safety Meeting Topic #37 NFPA 70E What is it?

Safety Meeting Topic #37 NFPA 70E What is it? Safety Meeting Topic #37 NFPA 70E What is it? The National Fire Protection Association (NFPA) 70E is the standard for Electrical Safety Requirements for Employee Workplaces and is a supplement to the NFPA70

More information

Electrical Safety for Facility Managers and Building Owners

Electrical Safety for Facility Managers and Building Owners CEU s Copy of Slides Evaluation Form Follow up information Disclaimer. This seminar was produced to help explain the importance and need for electrical safety specifically for Facility Managers. It does

More information

NFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions

NFPA 70E. Electrical Safety in the Workplace. KTR Associates. Joseph Deane, PE. Engineering Solutions NFPA 70E Electrical Safety in the Workplace KTR Associates Engineering Solutions Joseph Deane, PE Goal for Today Better understanding of NFPA 70E Raise the awareness of Electrical Hazards Why the sudden

More information

White Paper. NFPA 70E 2018 Edition Changes and Implications for. Personnel Performing Condition Based Maintenance. Abstract: iriss.

White Paper. NFPA 70E 2018 Edition Changes and Implications for. Personnel Performing Condition Based Maintenance. Abstract: iriss. NFPA 70E 2018 Edition Changes and Implications for Personnel Performing Condition Based Maintenance By Rudy Wodrich, P.Eng., MBA, CRL, L1 Thermographer, VP Engineering Services, IRISS Inc. Abstract: The

More information

Guide to Compliance with the Electrical Workplace Safety Standards in the United States

Guide to Compliance with the Electrical Workplace Safety Standards in the United States Guide to Compliance with the Electrical Workplace Safety Standards in the United States July 2011/1910DB1102 by Joseph H. Weigel, Product Manager Schneider Electric USA, Inc. Make the most of your energy

More information

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702

Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 Arc Flash Analysis: IEEE Method versus the NFPA 70E Tables July 2017 / 1910DB1702 by Reza Tajali, Schneider Electric Engineering Services Summary 1.0 Abstract 2.0 OSHA and NFPA Rules 3.0 Use of NFPA 70E

More information

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage. Product Bulletin The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification test to validate the

More information

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions

Easy to use, initiate test with the push of a button No additional tools required Provides visual alert to abnormal power conditions Product Bulletin VeriSafe Absence of Voltage The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification

More information

Lockout/ Tagout. (Control of. Hazardous Energy) WISHA. Washington Industrial Safety & Health Act. Chapter November 2009 Edition

Lockout/ Tagout. (Control of. Hazardous Energy) WISHA. Washington Industrial Safety & Health Act. Chapter November 2009 Edition WISHA Department of Labor & Industries Lockout/ Tagout (Control of Hazardous Energy) DO NOT OPERATE STEPS 1. 2. 3. Chapter 296-803 November 2009 Edition REVIEW REVIEW REVIEW Washington Industrial Safety

More information

AWL AIRCRAFT WARNING LIGHT LIOL-B TYPE OPERATION AND MAINTENANCE MANUAL

AWL AIRCRAFT WARNING LIGHT LIOL-B TYPE OPERATION AND MAINTENANCE MANUAL AWL AIRCRAFT WARNING LIGHT LIOL-B TYPE OPERATION AND MAINTENANCE MANUAL Page. 1 of 30 rev 2.00 INDEX: 1. LIOL-B Datasheet, ordering code, weight and dimensions 2. Overview 3. ICAO rules general concepts,

More information

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program. 15682 CENTRIFUGAL WATER CHILLERS ************************************************************************************************************* SPECIFIER: CSI MasterFormat 2004 number: 236416 An optional

More information

ISO INTERNATIONAL STANDARD. Safety requirements for industrial laundry machinery Part 1: Common requirements

ISO INTERNATIONAL STANDARD. Safety requirements for industrial laundry machinery Part 1: Common requirements INTERNATIONAL STANDARD ISO 10472-1 First edition 1997-12-15 Safety requirements for industrial laundry machinery Part 1: Common requirements Exigences de sécurité pour les machines de blanchisserie industrielle

More information

MACHINE GUARDING. Hazards of Unguarded Machines. Occupational Safety and Health Regulations (OSHA)

MACHINE GUARDING. Hazards of Unguarded Machines. Occupational Safety and Health Regulations (OSHA) MACHINE GUARDING Hazards of Unguarded Machines Workers are exposed to unguarded or inadequately guarded machines in many workplaces. According to OSHA, workers who operate and maintain machinery suffer

More information

Safety, Productivity and Risk Assessment Services For Industry

Safety, Productivity and Risk Assessment Services For Industry Butler Professional Services, LLC Ray Butler - President Safety, Productivity and Risk Assessment Services For Industry Site Audits Guarding Assessments Efficiency Studies Task/Hazard Risk Assessments

More information

Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip

Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip NOVA Energy & Automation Product Specifications 3 Breaker Main Disconnect Panel with Undervoltage Trip Model NEAS-XXXX-G-UVR 03 January 2012 Product Description 1. Standard Applications The Nova 3 Breaker

More information

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage.

Product Bulletin. VeriSafe Absence of Voltage Tester. The Safe Way to Verify the Absence of Voltage. Product Bulletin VeriSafe Absence of Voltage The Safe Way to Verify the Absence of Voltage. When servicing electrical equipment, workers must comply with safety regulations that require a voltage verification

More information

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT The interaction of fire protection systems can be extremely complex. The detection of a fire in a building by an automatic device

More information

Procedure for the Approval of New Fire Detection and Alarm Technologies

Procedure for the Approval of New Fire Detection and Alarm Technologies VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing

More information

SensaGuard TM Integrated Latch Installation Instructions

SensaGuard TM Integrated Latch Installation Instructions TM Integrated Latch Installation Instructions Certifications IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE Note: Refer to Technical Specifications for Certification information and ratings. 2 TM Installation

More information

PUMP CONTROL CENTER (PCC)

PUMP CONTROL CENTER (PCC) PART 1 SUMMARY A. In accordance with the plans and specifications, the Contractor shall provide and install a complete pre-fabricated, pre-tested ArcSafe Pump Control Center including all required equipment,

More information

Overview of Standards for CO Detection Products

Overview of Standards for CO Detection Products Overview of Standards for CO Detection Products Rev 1.1 1 General Overview... 3 2 Application and Installation Codes & Standards... 3 3 Product Standards... 4 4 Certified and Listed Products (Conforms

More information

Navigating the Safety Certification Process for LED Lighting Products Todd Straka, Director Lighting Services

Navigating the Safety Certification Process for LED Lighting Products Todd Straka, Director Lighting Services Navigating the Safety Certification Process for LED Lighting Products Todd Straka, Director Lighting Services www.intertek.com/lighting 1 Identifying Product Safety Requirements for Your Target Markets

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Design-In Health and Safety Guarding. Thermal April 2010

Design-In Health and Safety Guarding. Thermal April 2010 Design-In Health and Safety Guarding Thermal April 2010 8. Safeguarding 2 8.1. Fundamentals for Safeguarding 2 8.2. Guard Design 2 8.2.1. Point-of-Operation/Machine Guarding 2 8.2.2. Thermal Hazard Guarding

More information

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance

Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance Arc Flash Codes & Compliance: What You Need to Know to Deliver Both Protection and Performance An arc flash can cause serious injury or death to anyone in its path. The National Electrical Code provides

More information

Brian McCauley December 2017

Brian McCauley December 2017 Brian McCauley December 2017 ELECTRICAL SAFETY COMPLIANCE & NFPA 70E 2018 Agenda 1 Introduction Electrical Safety Basics Electrical Safety Statistics NFPA 70E 2018 Updates PPE Questions A Little bit of

More information

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE Digital Energy Power Quality INSTALLATION, OPERATION AND MAINTENANCE MANUAL GE TRANQUELL Enhanced Thermal Protection (ETP) Series Integrally Mounted Medium and High Exposure Surge Protective Devices

More information

SECTION PACKAGED HEAT TRANSFER SYSTEM

SECTION PACKAGED HEAT TRANSFER SYSTEM PACKAGED HEAT TRANSFER SYSTEM Page 1 of 6 SECTION PACKAGED HEAT TRANSFER SYSTEM 1 GENERAL 1.1 SUMMARY A. Packaged steam-to-water heat transfer system 1.2 REFERENCES A. ASHRAE American Society of Heating,

More information