FIRE ALARM SYSTEMS FOR PURPOSE-BUILT FLATS & APARTMENTS: A NEW APPROACH
|
|
- Justin Gibson
- 5 years ago
- Views:
Transcription
1 FIRE ALARM SYSTEMS FOR PURPOSE-BUILT FLATS & APARTMENTS: A NEW APPROACH
2 C-TEC HQ
3 Typical tower block
4 Andy Green Marketing Manager at C-TEC, a leading independent UK manufacturer of life safety electronic equipment 25 years experience in the fire alarm industry Used to live in a purpose built block of flats
5 What we will cover The origins of the Stay Put policy Overview of BS domestic fire detection & alarm systems Overview of BS commercial fire detection & alarm systems Does Stay Put still work Current NFCC (National Fire Chiefs Council) Guidance Can modern technology be used to complement or offer an alternative to Stay Put?
6 The Stay Put Policy A strategy in which a fire in a purpose-built block of flats is assumed to be confined to an individual compartmentalised dwelling unit Each dwelling unit is expected to have its own independent domestic fire alarm that notifies the occupant when there is a fire Occupants are expected to either put the fire out or leave the dwelling and notify the fire service so they can extinguish the fire before it spreads All escape routes and corridors are expected to be similarly protected and kept fire sterile
7 The Stay Put Policy
8 The Stay Put Policy
9 Why are there few communal fire systems in tower blocks? Dates back to 1948 and Chapter IV of CP3 guidance when only heat detectors, break glass points and bells existed. Communal systems at this time were considered undesirable due to:- Misuse and vandalism Unnecessary evacuations and the possible obstruction of fire fighting operations Cost of installation and ownership Fears over liability if a system was damaged
10 Design & Installation Standards
11 Overview of BS (Domestic Systems) Covers individual single dwelling units Does not give advice on signalling fires or faults to anywhere other than the dwelling Specifies different minimum Grades of system (A-F) for different types of dwellings. Defines Grades in such a way that a higher Grade is more acceptable than the minimum specified Grade for an application.
12 Categories of coverage of BS systems LD1 covers complete dwellings LD2 covers escape routes & designated areas LD3 covers escape routes only
13 Domestic Systems typically comprise: Grades F-D (Unmonitored Mains or Mains/Battery devices) Grades C-A (Monitored systems with separate controllers & batteries)
14 Overview of BS (Commercial Systems) Covers all non-domestic buildings including the communal parts of blocks of flats Includes 5 basic levels of protection (L1-5) with L1 being the entire building to L5 being an engineered approach L5 is the category normally assigned to the communal areas of apartments All devices to EN54
15 BS {2019 Draft} says: In the case of purpose-built flats, the degree of compartmentation between occupancies is normally sufficient to ensure that fire is contained in the dwelling of origin for a prolonged period. During this time, other occupants can remain in reasonable safety within their own dwellings. Accordingly, this part of BS 5839 does not provide recommendations for fire detection systems that incorporate detectors in the communal areas or ancillary accommodation (e.g. plant rooms) within purpose-built flats. BS (2017) says: virtually all premises need a fire alarm system BS covers the communal areas of blocks of flats. HOWEVER in Appendix A (which describes typical coverage for multiple scenarios) these areas are absent!
16 As a result Risk assessments follow the Stay Put strategy which often recommends communal areas are covered by a Cat L5 (Engineered) system The engineered solution tends to be: Do not put a communal fire detection & alarm system in the corridors & escape routes of the building Standards have been written to support a Stay Put strategy with no Plan B for when Stay Put fails No account has been taken of modern technology and what could be achieved using sophisticated cause & effects and system monitoring
17 IS STAY PUT SAFE?
18 What does stay put depend on? The integrity of the structure(s) cladding etc
19 What does stay put depend on? The integrity of the structure(s) cladding etc No deterioration in compartmentalisation
20 What does stay put depend on? The integrity of the structure(s) cladding etc No deterioration in compartmentalisation The fire services being informed promptly
21 What does stay put depend on? The integrity of the structure(s) cladding etc No deterioration in compartmentalisation The fire services being informed promptly Stairwells and corridors being kept clear
22 What does stay put depend on? The integrity of the structure(s) cladding etc No deterioration in compartmentalisation The fire services being informed promptly Stairwells and corridors being kept clear Fire service access being uncompromised
23 What does stay put depend on? The integrity of the structure(s) cladding etc No deterioration in compartmentalisation The fire services being informed promptly Stairwells and corridors being kept clear Fire service access being uncompromised Residents respecting and co-operating to maintain the integrity of the building/flats
24 Current National Fire Chiefs Council Guidance Guidance to support a temporary change to a simultaneous evacuation strategy in purpose built blocks of flats For buildings where Stay Put has been compromised Applies when a competent engineer assesses that the strategy is no longer effective due primarily (but not limited) to cladding issues Says a monitored automatic communal fire system to BS Cat L5 (i.e. an engineered solution) and/or waking watch should be provided until the issues are resolved
25 SO The objection to communal fire alarm systems that has run through most regulatory bodies has changed BUT Can you really be confident that the factors that led to the NFCC s guidance will not re-emerge? CONSIDER THIS How many apartment blocks do you know where stay put is compromised?
26
27 STAY PUT MADE SAFER
28 Interconnecting domestic & communal systems Rarely happens in purpose-built tower blocks due to the Stay Put policy and no associated commercial system being fitted The different physical modes of operation of domestic and commercial systems make it technically difficult (240VAC and 24VDC don t mix) No single organisation has needed to develop an interface between the two types of system There has been a digression of working practices and standards Consequently
29 240V I/O 24V Never the twain shall meet!
30 Using modern technology & NFCC Guidance as a building block for a Plan B solution
31 How could this be achieved?
32 How would a truly integrated system work?
33 Any faults in the dwelling are indicated in the dwelling and reported to the off-site monitoring centre.
34 Fire Level 1 Optical detector in kitchen triggered Alarm sounds in the dwelling and is reported to the off-site monitoring centre Occupant silences the alarm if safe to do so. When alarm clears system resets and is reported to the off site monitoring centre.
35 Fire Level 2 Heat detector in entrance triggered Alarm sounds in the dwelling and (if programmed) activates the alarms in nearby dwellings or floors. Occupant cannot silence the alarm. Alarm shows at the panel and is reported to the off-site monitoring centre.
36 Or the system can be setup to evacuate the entire building as per the NFCC s simultaneous evacuation strategy
37 Manual controls are also provided at the control panel to enable the Fire service to manually evacuate the building or floors
38
39
40
41 STAY PUT MADE SAFER
42 THANK YOU FOR YOUR ATTENTION Tel: +44 (0) STAND FS20
43 Advantages of C-TEC s Hush2 solution Can be completely stand alone or networked (i.e. connected to & monitored by a communal system) Same simple wiring as a Grade D system Controller fits on a double gang plate with integral rechargeable and replaceable battery (10 year life) Includes reachable onboard Hush and Test facilities Optional communal detectors/alarm devices
44 Advantages of C-TEC s Hush2 solution Sprinkler monitoring and cooker switch off available on the same monitored wiring scheme Multi-sensors can trigger a separate Fire Level 2 event to the communal panel for relevant action Comprehensive fault monitoring and logging of all domestic systems to a Cloud based system in real time Designed and manufactured in the UK
45 Advantages of C-TEC s Hush2 solution Reduced lifetime ownership costs: Lower upfront equipment cost than Grade D equivalent Equipment has a greater than 10 year lifespan Off-site monitoring means dwelling visits can be scheduled to suit the risk Using Fire Level 2 means reduced false alarms Monitoring of the domestic systems allows for reduced levels of surveillance and increased levels of reliability
46
47 What we have covered The origins of the Stay Put policy Overview of BS domestic fire detection & alarm systems Overview of BS commercial fire detection & alarm systems Does Stay Put still work? Current NFCC (National Fire Chiefs Council) Guidance Can modern technology be used to complement or offer an alternative to Stay Put?
48 THANK YOU FOR YOUR ATTENTION Tel: +44 (0)
49
50 QUESTIONS & ANSWERS
Fire Risk Assessment
Fire Risk Assessment George Wright House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General
More informationCladding Screening Test Result
Cladding Screening Test Result Submitting body Building address L&Q, One Kings Hall Mews, SE13 5JQ Flats 1-18, Burnell House, E20 1GY Organisation type: Contact details for test result Location of where
More informationFIRE SAFETY LOG BOOK
FIRE SAFETY LOG BOOK Regulatory Reform (Fire Safety) Order 2005 If you own, manage or operate a business, you will need to comply with fire safety law. The main law is the Regulatory Reform (Fire Safety)
More informationAVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard
Pocket guide to Fire Alarm Systems Design BS 5839-1 Standard AVAILABLE TO DOWNLOAD ON THE APOLLO APP The Regulatory Reform (Fire Safety) Order (FSO) became law on 1 October 2006 Legally you must comply!
More informationFire Alarm Control Panel. System Maintenance and Log Book
Fire Alarm Control Panel System Maintenance and Log Book Fire Alarm System Maintenance A fire alarm system must provide early and reliable warning of the outbreak of fire. To achieve this, the system remains
More informationLYHA Fire Safety Policy
LYHA Fire Safety Policy Introduction This Fire Safety Policy shows our approach to Fire Safety in the work place and in our homes. It identifies our approach to Fire Safety in: The workplace Flats with
More informationFire Risk Assessment
Fire Risk Assessment Trinity House HS.F.119 (rev02) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management systems... 1 4 General description
More informationWaking Watch / Common Fire Alarm. Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats
Waking Watch / Common Fire Alarm Guidance to support a temporary simultaneous evacuation strategy in a purpose-built block of flats Contents 1. Introduction... 3 2. Definitions... 5 3. Competence... 6
More informationDesign of Fire safety in Multi Occupancy Residential Accommodation
Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability
More informationB16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page Installation Guide
B16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 1 1.1 Installation Guide 2 SCREWDRIVER INTO S & PUSH COVER AWAY B16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page 2 2. ALARM REMOVAL LOCATE REMOVAL SLOT
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford
More informationFire Risk Assessment
Fire Risk Assessment Carr House HS.F.119 (rev03) delivering promises, improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management system... 1 4 General description
More informationFire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002
a guide to Fire Alarm Systems Design BS5839 Part1:2002 incorporating Amendment No.2 The Regulatory Reform (Fire Safety) Order (RRO) became law on 1 October 2006 Legally you must comply! What is the RRO?
More information3500 CONVENTIONAL FIRE ALARM CONTROL PANEL
3500 CONVENTIONAL FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:
More informationFire Risk Assessment
Fire Risk Assessment Manor House HS.F.119 (rev03) delivering promises improving lives Contents 1 Premises particulars... 1 2 General statement of policy... 1 3 Management systems... 1 4 General description
More information3.1 Introduction. 3.1 Introduction
DEPARTMENT OF ARCHITECTURE ABUBAKAR TAFAWA BALEWA UNIVERSITY, BAUCHI ARC 624: ADVANCED BUILDING SERVICES LESSON 3: FIRE DETECTION AND ALARM SYSTEMS IN BUILDINGS 3.1 Introduction 3.1 Introduction 3.2 Conventional
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:
More informationNOTTINGHAM CITY HOMES
APPENDIX 1 NOTTINGHAM CITY HOMES FIRE SAFETY POLICY 2013/14 Draft for Board Uncontrolled when printed Page 1 of 14 DOCUMENT CONTROL Identification and Approval Status Document Title: Nottingham City Homes
More informationSOUTH AFRICAN NATIONAL STANDARD
ISBN 978-0-626-26992-0 SOUTH AFRICAN NATIONAL STANDARD Fire detection and alarm systems for buildings System design, installation and servicing Published by SABS Standards Division 1 Dr Lategan Road Groenkloof
More informationUSER MANUAL & MAINTENANCE GUIDE OG OO
M+48. USER MANUAL & MAINTENANCE GUIDE OG OO What to do if the Fire Alarm Panel shows an Alarm (Red LED) Write down which LEDs are lit (either in the log book, or on a piece of paper for transferring to
More informationFire Safety Protocol
CORPORATE HEALTH AND SAFETY POLICY: Part 3 Arrangements Fire Safety Protocol Document Status: [ ] Guidance for Managers [] Protocol [ ] Procedures Version 0.1/ August 2013 DRAFT EALING NCIL Table of Contents
More informationFIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL GK FIRE & SECURITY LTD, UNIT 1 GREBE RD, PRIORSWOOD IND EST, TAUNTON, TA2 8PZ
BS5839-1 : 2013 FIRE ALARMS EMERGENCY LIGHTS NURSE CALL ACCESS CONTROL Forward It is recommended that this logbook be maintained by a relevant member of the premises management, to ensure that every entry
More informationTYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)
TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT) BRECON TOWERS BLACKBERRY LANE STOCKPORT SK5 8JW Date of this risk assessment review: 4th July 2017 Date of last risk assessment review: 8th May
More informationHi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety
Hi, welcome to the topic on Fire Detection and Alarm Systems. This topic forms one of the critical knowledge areas for prospective fire safety manager. As the appointed fire safety manager for a premise,
More informationLOG BOOK & CERTIFICATES
M+48 LOG BOOK & CERTIFICATES. FIRE ALARM SYSTEM SUMMARY: FIRE ZONE INFORMATION ZONE NO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41
More informationLogbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater
APPROVED BY: JBJ Precept EN Fire Detection/Alarm Panel & Precept EN Repeater Logbook PAGE 1 of 19 List of Contents 1. FIRE ALARM SYSTEM MAINTENANCE... 3 2. USER RESPONSIBILITIES... 3 2.1. RESPONSIBLE PERSON...
More informationConventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual
Conventional Fire System BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual Contents Contents 1. INTRODUCTION... 3 1.1 Purpose...3 1.2 Definitions....3 Premises Management...
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Tel: Person(s) consulted:
More informationThe Social Accountability International (SAI) Fire Safety Checklist
The Social Accountability International (SAI) Fire Safety Checklist Introduction The Social Accountability International (SAI) Fire Safety Checklist is a guidance tool prepared for SA8000 & BSCI Auditors
More informationLegal Requirements. There is no general legal requirement to install sprinklers. in places of work
01 A sprinkler system is a pipework distribution system charged with water, with a network of heatsensitive sprinkler heads supplied via a tank/reservoir or a water main. If the temperature rises above
More informationAlgo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM
Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT, ENGLAND +44 (0) 1282 717171 www.protec.co.uk
More informationFIRE SAFETY PLAN. Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA. May / Prepared by: Chris Pancoe
FIRE SAFETY PLAN Ceramics/Sculpture Building 47 Service Rd 1 S Winnipeg, MANITOBA May / 2017 Prepared by: Chris Pancoe TABLE OF CONTENTS Contents A. BUILDING AUDIT:... 3 BUILDING DESCRIPTION... 3 1. Level
More informationTHIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS.
THIS ORDINANCE ONLY AFFECTS EXISTING FIRE ALARM SYSTEMS. IF YOU RECEIVED A NOTICE BY MAIL AND YOU DO NOT CURRENTLY HAVE A FIRE ALARM INSTALLED IN YOUR BUILDING, YOU MAY DISREGARD THE NOTICE. Dear Building
More informationHealth, Safety and Wellbeing Management Arrangements. Core I Consider I Complex. Fire Safety. Health, Safety and Wellbeing Service
Health, Safety and Wellbeing Management Arrangements Core I Consider I Complex Fire Safety Health, Safety and Wellbeing Service 1. Success Indicators The following indicators will demonstrate success in
More informationREGULATORY REFORM (FIRE SAFETY) ORDER 2005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT
REGULATORY REFORM (FIRE SAFETY) ORDER 005 PERIODIC REVIEW OF FIRE RISK ASSESSMENT Responsible person (e.g. employer) or person having control of the premises: Address of premises: Graham Care Group Cornford
More informationPREMIER M PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES
8-24 ZONE CONVENTIONAL FIRE ALARM PANEL LOG BOOK & CERTIFICATES Approved Document No: GLT.MAN-113 It is recommended that this LOG BOOK be maintained by the responsible person(s) on site, who should ensure
More informationMINERVA MZX125 Digital Addressable Fire Detection System
DATASHEET MINERVA MZX125 Digital Addressable Fire Detection System The Minerva MZX125 is a highly featured digital addressable panel with a comprehensive but easy to operate user interface. The system
More informationUNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY
Revision No.: 11 Page 1 of 12 I. PURPOSE This procedure establishes a tool to help maintain a safe environment for all patients, visitors and staff by evaluating the loss of a life safety feature during
More informationThe EN54 Part 2 and 4 Fire System
Scope of work: To design, supply, install and commission a Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54 Part 2 and 4 Fire
More informationGrenfell Tower Inquiry
LFB00003103_0001 Grenfell Tower Inquiry Opening Statement of the London Fire Brigade Introduction 1. The devastating fire which occurred on the night of 14th June 2017 at Grenfell Tower caused unimaginable
More informationINTRUDER ALARM FOR BUSINESS SECURITY
INTRUDER ALARM FOR BUSINESS SECURITY WELCOME PACK THANK YOU FOR CHOOSING ADT Thank you for choosing us to help protect your business and employees. Please take the time to read your Welcome Pack carefully
More informationTX7110. Intelligent Heat Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.
TX7110 Intelligent Heat Detector Installation and Operation Manual Technology Copyright 2015, All right reserved. Product Safety To prevent severe injury and loss of life or property, read the instruction
More informationFIRE SAFETY IN SPECIALISED HOUSING GUIDANCE. Seamus Doyle Health & Safety Manager Pembrokeshire Housing Group
FIRE SAFETY IN SPECIALISED HOUSING GUIDANCE Seamus Doyle Health & Safety Manager Pembrokeshire Housing Group Why a new guide? Changing social care landscape (3/4 million residents) Impact of Fire Safety
More informationFalse Alarm Management. Graham Simons FIA Technical Manager
False Alarm Management Graham Simons FIA Technical Manager False Alarm Management Smoke alarms and smoke detectors sensitive to airborne particles and may not discriminate smoke & dust False alarms are
More information3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL
3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0) 1282 717273 Web:
More informationUSER MANUAL, MAINTENANCE GUIDE & LOG BOOK
ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Page 1 TABLE OF CONTENTS WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM (RED LED)... 4 WHAT TO DO IF
More informationFire precautions in dwellings
NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types
More informationRegulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation
FIRE RISK ASSESSMENT Retirement Housing (Independent Living) Developed in conjunction with Cambridge shire Fire and Rescue Service, Housing and Care 21 s primary authority (v3.november 2016) Regulatory
More informationFire risk management plan. MH/05/Revised/06/17
Fire risk management plan MH/05/Revised/06/17 1 1. Scope This policy applies to fire safety arrangements in all workplaces, common areas of residential premises and any other premises managed and/or owned
More informationGuidance Note FIA Application Guidance on BS :2015
Guidance Note FIA Application Guidance on BS 7273-4:2015 FIA Application Guidance on BS 7273-4:2015 1. INTRODUCTION... 3 2. OVERVIEW... 3 2.1. WHAT IS A DOOR RELEASE MECHANISM?...3 2.2. WHY INSTALL DOOR
More informationFIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA
93 FIRE DEPARTMENT - RULES FOR FIRE PROTECTION IN AUSTRIA INTRODUCTION 94 Legal requirements for the protection of firefighters Requirements of Building Act Fire Prevention Act Technical Guidelines OIB
More informationMINERVA MZX125. Digital Addressable Fire Detection System
A C C E S S C O N T R O L C C T V E A S R F I D F I R E P R O T E C T I O N I N T R U D E R A L A R M S DATA SHEET MINERVA MZX125 Digital Addressable Fire Detection System Features: Long term service and
More informationEmergency Response Team Plan. Shoal Island Office
Emergency Response Team Plan Shoal Island Office EMERGENCY RESPONSE TEAM LOCATION LIST ERT Team Leader Ed James (246-5452) Top Floor ERT Members Danny Anderson (246-5459) Main Floor ERT Members Ed Sinclair
More informationLoss Prevention Standards
Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building
More informationISLE OF WIGHT FIRE & RESCUE SERVICE
ISLE OF WIGHT FIRE & RESCUE SERVICE Record of Fire Safety Equipment Testing Fire Drills & Training CONTENTS 1. MEANS OF ESCAPE 2. FIRE WARNING AND AUTOMATIC FIRE DETECTION 3. FIRE EXTINGUISHERS AND HOSEREELS
More informationBS 5839 Part 6 : 2013 Changes. By Don Scott
BS 5839 Part 6 : 2013 Changes By Don Scott BS 5839 Part 6 : 2013 This new edition of the CoP is not a full revision but contains technical changes It is recognized that a full revision is required and
More informationUSER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Firmware Versions: PANEL 1.84 & LOOP CARD 3.70 MKII PROTOCOL ONE TO FOUR LOOPS ANALOGUE ADDRESSABLE FIRE ALARM PANEL USER MANUAL, MAINTENANCE GUIDE & LOG BOOK #Doc No. GLT-215-7-2 TABLE OF CONTENTS WHAT
More informationFIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures
FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures Building Name: Building Address: Plan Prepared By (please print): Date: Revision Date Comments Approval FIRE SAFETY MAINTENANCE
More informationFire Safety Logbook. FOLLOW the regulations. MANAGE fire risks. RECORD relevant checks
Fire Safety Logbook www.landlords.org.uk FOLLO the regulations RECORD relevant checks MANAGE fire risks Property Details Property Address: Post Code: Licence Holder/Manager: Contact Details Fire Detection
More informationPrincess Court Cornbrook Park Road Old Trafford Manchester M15 4FE
Princess Court Cornbrook Park Road Old Trafford Manchester M15 4FE Prepared by: Peter Golding Tech IOSH and Mark Alderson BSc Hons IEng MIFireE (IFE 0002248) Safety Management (UK) Ltd Holme Suite Clawthorpe
More informationDate Issued: December 14, 2017 Revision: 2.1
2.1 1. Introduction A is implemented to ensure the fire safety of building occupants or a building area when the Fire Alarm System or a Fire Protection System has been temporarily disabled due to malfunction,
More informationA Guide To BS Understanding the selection, spacing and siting of detectors
World Class Leaders in Fire Detection Since 1918 A Guide To BS5839-12017 Understanding the selection, spacing and siting of detectors Welcome to A Guide to BS5839 Part 1 : 2017 from HOCHIKI EUROPE (UK)
More informationEurope s Leading Manufacturer of Fire + Carbon Monoxide Alarms
Europe s Leading Manufacturer of Fire + Carbon Monoxide Alarms Need more info? Call us on +353 (0)61 471277 Ei Electronics e-mail: sales@eielectronics.ie web:www.eielectronics.com Ei Electronics, is an
More informationPREMISES FIRE SAFETY LOGBOOK
0844 740 3473 PREMISES FIRE SAFETY LOGBOOK PREMISES ADDRESS: LOG BOOK TO BE KEPT IN THIS LOCATION: AN INTRODUCTION TO YOUR LOG BOOK. The Regulatory Reform (Fire Safety) Order 2005 (FSO) requires that the
More information6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL
6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL Protec Fire Detection plc, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0) 1282 717171 Fax: +44 (0)
More informationCYNGOR SIR POWYS COUNTY COUNCIL
Appendix A CYNGOR SIR POWYS COUNTY COUNCIL Housing Services Fire Safety in Council Housing Policy Version For Portfolio Holder decision (10-01-2017) Reference POL LL Fire Safety Housing Services Fire Safety
More informationFIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS
A GUIDE ON FIRE SAFETY IN PURPOSE BUILT BLOCKS OF FLATS INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was commissioned to
More informationINTRUDER ALARM FOR BUSINESS SECURITY
INTRUDER ALARM FOR BUSINESS SECURITY WELCOME PACK THANK YOU FOR CHOOSING ADT Thank you for choosing us to help protect your business and employees. Please take the time to read your Welcome Pack carefully
More informationAMBASSADOR HOUSE. A guide on. Fire Safety in Purpose Built Blocks of Flats
AMBASSADOR HOUSE A guide on Fire Safety in Purpose Built Blocks of Flats INTRODUCTION Fire safety in blocks of flats is something that must be taken very seriously. The Local Government Group (LGG) was
More informationFire Precautions, Evacuation and Emergency Control Procedure Denmead Scouts HQ
Fire Precautions, Evacuation and Emergency Control Procedure Denmead Scouts HQ Document Details Originator: Craig Thompson February 2012 CONTENTS 1 Introduction 3 2 Scope 3 3 Roles and Responsibilities
More informationScimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:
Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: 01730 268 231. Fax: 01730 265 552 Scimitar user manual & log book SCIMITAR USER MANUAL Approved Document No. DFU7001001 Rev 2
More informationZP3 Operator & Maintenance Manual Version 1
ZP3 Operator & Maintenance Manual Version 1 Introduction Thank you for selecting Clymac Ltd. Clymac can provide maintenance for the system, emergency call out, telephone support and any modifications required
More informationFIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY
FIRE SAFETY POLICY & EMERGENCY EVACUATION POLICY Under the terms of the Regulatory Reform (Fire Safety) Order 2005, and subsequent regulations, Seaford College must ensure the safety from fire of all staff,
More informationNotice No. 7. Rules and Regulations for the Classification of Ships, July Issue date: March Working together for a safer world
Notice No. 7 Rules and Regulations for the Classification of Ships, July 2014 The status of this Rule set is amended as shown and is now to be read in conjunction with this and prior Notices. Any corrigenda
More informationa) Establishment of emergency procedures to be followed at the time of an emergency;
5.10 Fire Safety 5.10.1 Introduction The Corporation is responsible for carrying out the provisions of the Ontario Fire Code. This section outlines our responsibilities as well as inspections and testing
More informationStatutory Compliance Checklist
Date of Issue: April 2017 Statutory Compliance Checklist This document is for clergy and churchwardens to help them in the maintenance of their Churches. Refer to supplementary notes for further guidance.
More informationPRODUCT GUIDE & INFORMATION. Professional Fire & Carbon Monoxide Solutions
PRODUCT GUIDE & INFORMATION Professional Fire & Carbon Monoxide Solutions 1 Nearly 50 years experience of designing, manufacturing and supplying home safety products, makes BRK an industry leader. We believe
More informationINTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3
INTELLIGENT FIRE TECHNOLOGY Twinflex and Multipoint V3 User Guide (TO BE RETAINED BY USER) 26-0340 Issue 3 Rafiki Protection Limited Rafiki policy is one of continual improvement and the right to change
More informationYour specialist partner for total electrical compliance. Electrical Testing
Your specialist partner for total electrical compliance Electrical Testing "To achieve compliance with the legal requirements of the Electricity at Work Regulations 1989 requires proof that an electrical
More informationFIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016)
FIRE RISK ASSESSMENT Retirement Housing (Independent Living) (v3.november 2016) Regulatory Reform (Fire Safety) Order 2005 Category of Premises against the FSO 2005: Sleeping Accommodation The purpose
More informationFire Engineering in High Rise 15 November 2013
Fire Engineering in High Rise 15 November 2013 Neal Butterworth Arup UK www.arup.com Neal.Butterworth@arup.com Contents How do we protect against fire? How do we know this works? Why evacuate? What assumptions
More informationPAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00
PAT E N T System 88 COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00 Pg 1 of 12 CONTENTS 1. GENERAL 1.1 Introduction 2 1.2 System Description
More informationUSER MANUAL, MAINTENANCE GUIDE & LOG BOOK
INTELLIGENT 2 WIRE FIRE DETECTION SYSTEM WITH ID TECHNOLOGY USER MANUAL, MAINTENANCE GUIDE & LOG BOOK Approved Document No: GLT2-211-7-2 PAGE 0 TABLE OF CONTENTS WHAT TO DO IF THE FIRE ALARM PANEL SHOWS
More informationDigiplex LED Keypads User s Manual
KLEDEU03.fm Page -1 Friday, May 4, 2001 11:25 AM Digiplex LED Keypads User s Manual KLEDEU03.fm Page 0 Friday, May 4, 2001 11:25 AM KLEDEU03.fm Page 1 Friday, May 4, 2001 11:25 AM TABLE OF CONTENTS 1.0
More informationMECKLENBURG COUNTY FIRE MARSHAL S OFFICE
Effective Date: 11/01/02 Purpose: MECKLENBURG COUNTY To establish a set of guidelines for performance testing of all newly installed or upgraded fire alarm systems in order to ensure that all devices and
More informationF I R E S A F E T Y R E G I S T E R
F I R E S A F E T Y R E G I S T E R (Short Version) Cork County Fire Department www.corkcoco.ie April 2015 Introduction 1.1 Section 18(2) of the Fire Services Acts, 1981 and 2003 generally applies to all
More informationStandard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment
NFPA 720 2015 Summary Standard for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment TM, 7Oct14 CODE: Title, Standard, not Code Consistent with recent trend at NFPA, this document
More informationGuided Learning Hours (GLH) 8 Invigilated Assessment Hours (IA) 2 Total Qualification Time (TQT) 10
Qualification: Date Completed: 02 Feb 17 Unit: FIA AO Level 3 Fire Detection and Alarm Advanced Installer Development Group: FD&A Development Group Guided Learning Hours (GLH) 8 Invigilated Assessment
More informationUniclass L7535: N3253 EPIC L13:Y42. CI/SfB (57) X (K5) Residential Smoke Ventilation
Uniclass L7535: N3253 EPIC L13:Y42 CI/SfB (57) X (K5) Residential Smoke Ventilation Residential Smoke Ventilation SE Controls provides specialised products and services for natural smoke ventilation in
More informationBOOST8n. Technical Data Sheet. Domestic fire sprinkler pump system complying with and significantly surpassing BS
Technical Data Sheet BOOST8n Domestic fire sprinkler pump system complying with and significantly surpassing BS9251 2014 Industry leading fire sprinkler pump system with plc control and simple LCD screen
More informationDepartment of Physics/Block S11/Science Faculty NATIONAL UNIVERSITY OF SINGAPORE 2 ACTIONS TO BE TAKEN IN THE EVENT OF FIRE DURING OFFICE HOURS
Department of Physics/Block S11/Science Faculty NATIONAL UNIVERSITY OF SINGAPORE FIRE EMERGENCY PLAN AND RESPONSE (Applicable to S7, S12, S13 but with contents from pages 7-18 to change accordingly. All
More informationhighline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10
highline WINDOW CONTROLS INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM SVCS-1 * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10 CERTIFICATE OF COMPLIANCE SVCS-1 We the undersigned
More informationZERIO PLUS EDA-Z5008, Z5020 & Z5100
ZERIO PLUS EDA-Z5008, Z5020 & Z5100 USER MANUAL Revision 1.00 EDA-Z5008, Z5020 & Z5100 User Manual 0359 Electro Detectors Limited Electro House Edinburgh Way Harlow, Essex CM20 2EG, UK 14 0359 CPR 00226
More informationFIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre
FIRE SAFETY POLICY LEEDS METHODIST MISSION Oxford Place Centre P a g e 2 8 Version Draft 1 Name of responsible (ratifying) committee Leeds Methodist Mission Council Date ratified Document Manager (job
More informationFire Door Maintenance Guide.
Fire Door Maintenance Guide http://www.c-sgroup.co.uk/products/acrovyn-impact-resistant-doors/ Introduction Fire Doors are a critical safety feature of any building in which people work or visit, as they
More informationFIRE ALARMS. IN DWELLINGS By John Ware FIRE ALARMS
WM_Winter 05_part1_EW.qxd 17/11/05 6:55 am Page 1 1 IN DWELLINGS By John Ware IN THE UK around 80% of all fire deaths and injuries occur in dwellings, a total of 450 to 500 deaths and 14,000 injuries per
More informationFire safety management issues identified by fire risk assessments
Health and Safety Safety Team The University of Manchester Waterloo Place, 180 Oxford Road, Manchester Health and M13 Safety 9GP www.manchester.ac.uk To From Vice-Presidents/Deans, Heads of Schools and
More informationTHE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS
DERBY HOMES BOARD 24 NOVEMBER 2011 ITEM C5 THE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS Report of the Chief Executive 1. SUMMARY This report provides a brief overview
More informationOperating instructions SENTRI4 Control panel based Fire detection and alarm system
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 30 32 Zones Healthy 15:45 Fault Power Fault System Fault SenTRI 4 Fire System Designed to EN54 Pt 2 & 4 Operating instructions
More information- CONSTRUCTION FIRE SAFETY STANDARDS
SGG15 - CONSTRUCTION FIRE SAFETY STANDARDS 1) Construction Planning All construction sites shall plan and sequence their construction activities to ensure the early installation and operation of permanent
More information