1 Sheet 1 of 40 HINDUSTAN PETROLEUM CORPORATION LIMITED MUMBAI REFINERY DHT PROJECT ENGINEERING DESIGN BASIS ELECTRICAL DOCUMENT NO: 44LK /E.02/0001/A4 Rev No. Issue Date Pages Rev Description Prepared By Checked By Approved By A Issued for Approval MSJ VDV RBD B Issued for Engineering MSJ VDV VDV C Revised after incorporating HPCL comments & Issued for FEED Approved by HPCL & Issued for Implementation MSJ VDV VDV MSJ VDV VDV

2 CONTENTS LIST LIST OF ENCLOSURES NO. OF SHEETS ENCLOSED (YES / NO) A EXISTING DATA 2 YES B GENERAL INFORMATION 4 YES C RECEIVING SWITCHYARD 3 YES D STANDBY / CAPTIVE POWER GENERATION 1 YES E H. T. SWITCHGEAR 1 YES F MAIN / DISTRIBUTION TRANSFORMER 1 YES G POWER CONTROL CENTRE (PCC) 2 YES H MOTOR CONTROL CENTRE (MCC/PMCC) 2 YES I H.T. MOTORS 1 YES J L.T. MOTORS 1 YES K CABLES & ACCESSORIES 1 YES L DISTRIBUTION BOARDS (MLDB, MPDB, LDB, SLDB, PDB) 1 YES M CONTROL STATIONS 1 YES N LIGHT FITTINGS 1 YES O BATTERY & BATTERY CHARGER 1 YES P CAPACITORS 1 YES Q PUBLIC ADDRESS SYSTEM 1 YES R TELEPHONE SYSTEM 1 YES S ELECTRICAL INSTALLATION 1 YES T EARTHING 1 YES U UPS 1 YES V FIRE ALARM SYSTEM 1 YES W VARIABLE SPEED DRIVES 1 YES ANNEXURE I (SCHEME FOR VSDs UP TO 75 KW RATING) 1 YES DesignBasis_44LK5100_Rev0.doc Page 2 of 40

3 EXISTING DATA 1.0 HOOK UP WITH EXISTING SWITCHGEAR IS REQUIRED? REQUIRED 2.0 DETAILS OF EXISTING HV / MV SWITCHGEAR 2.1 VOLTAGE LEVEL & FREQUENCY 22 KV / 6.6 KV, 50HZ 2.2 FAULT LEVEL & BUSBAR RATING OF EXISTING HV/MV SWITCHGEAR PANELS. 2.3 SPARE HV/MV BREAKER PANELS AVAILABLE FOR USE. 2.4 SPARE BREAKER PANEL CONTAINS REQUIRED BREAKER, CT S, PT S, RELAYS, METERING ETC MVA for 3 sec. FOR 22 KV 350 MVA for 3 sec. FOR 6.6 KV * * 2.5 SPACE AVAILABILITY FOR EXPANSION. * 3.0 DETAILS OF EXISTING LV SWITCHGEAR 3.1 FAULT LEVEL & BUSBAR RATING OF EXISTING LV SWITCHGEAR PANELS. 50 KA FOR 1 SEC FOR 415V 3.2 SPARE LV BREAKER PANELS AVAILABLE FOR USE. * 3.3 SPARE BREAKER PANEL CONTAINS REQUIRED BREAKER, CT S, PT S, RELAYS, METERING ETC. * 3.4 SPACE AVAILABILITY FOR EXPANSION. * 4.0 DETAILS OF EXISTING FIRE ALARM SYSTEM * 4.1 HOOK UP WITH EXISTING FIRE ALARM PANEL REQUIRED? 4.2 MAKE & MODEL OF EXISTING FIRE ALARM PANEL. 4.3 TYPE OF EXISTING FIRE ALARM PANEL. 4.4 SPARE CARD AVAILABLE IN EXISTING FIRE ALARM PANEL FOR HOOK UP OF NEW DETECTORS? 5.0 DETAILS OF EXISTING TELEPHONE SYSTEM * 5.1 NEW TELEPHONES TO BE CONNECTED TO EXISTING EPABX? 5.2 MAKE & MODEL OF EXISTING EPABX. 6.0 CABLE LAYING ** 6.1 NEW CABLE TRAYS TO BE LAID ON EXISTING PIPE RACK? DesignBasis_44LK5100_Rev0.doc Page 3 of 40

4 6.2 MAXIMUM LOAD, WHICH THE EXISTING PIPE RACK CAN TAKE? 6.3 EXISTING CABLE TRAYS TO BE USED FOR LAYING OF NEW CABLES? 6.4 SPACE AVAILABLE ON EXISTING CABLE TRAYS IN CASE EXISTING CABLE TRAYS ARE TO BE USED. NOTE: * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 4 of 40

5 GENERAL NFORMATION 1.0 SITE CONDITIONS 1.1 ALTITUDE: Above MSL 6.71 Meters 1.2 AMBIENT TEMP MAXIMUM: 40 o C MINIMUM: 12 o C 1.3 RECOMMENDED DESIGN TEMP. FOR ELECTRICAL EQUIPMENT S (IS 9676) 45 o C 1.4 SOIL RESISTIVITY Later (After Soil Resistivity test). 1.5 SESIMIC ZONE (IS-1893 Part-1) Zone-III 1.6 RELATIVE HUMIDITY 95% 1.7 SITE ENVIRONMENT Tropicalized, Marine, with presence of corrosive fumes. 2.0 ELECTRICAL DETAILS OF INCOMING SUPPLY 2.1 VOLTAGE & FREQUENCY AT POINT OF SUPPLY 110 KV 2.2 FAULT LEVEL (Sym) AT POINT OF SUPPLY (DESIGNED & ACTUAL) DESIGNED - ** / * ACTUAL - ** / * 2.3 NEUTRAL EARTHING AT SUPPLY END SOLIDLY EARTHED 2.4 FLUCTUATION VOLTAGE ± 10% FREQUENCY ± 5% COMBINED ± 10% 2.5 MINIMUM LOAD POWER FACTOR STIPULATED BY SUPPLY AUTHORITY PARALLEL OPERATION OF INCOMERS Momentary Paralleling At 6.6 kv and 415 V. 3.0 DETAILS OF ELECTRICAL DISTRIBUTION SYSTEM 3.1 PRIMARY DISTRIBUTION VOLTAGE LEVEL: VOLTAGE: 6.6 kv FREQUENCY: 50 Hz PRIMARY DISTRIBUTION SYSTEM NEUTRAL EARTHING: Resistance Earthing (Thru NGR) 3.2 INTERMEDIATE DISTRIBUTION VOLTAGE LEVEL VOLTAGE 6.6 kv DesignBasis_44LK5100_Rev0.doc Page 5 of 40

6 GENERAL NFORMATION INTERMEDIATE DISTRIBUTION SYSTEM NEUTRAL EARTHING Resistance Earthing (Thru NGR) EARTH FAULT CURRENT LIMITED TO: 100 A 4.0 LT. POWER DISTRIBUTION SYSTEM 4.1 VOLTAGE 415 V A.C 3 Phase. 4.2 NEUTRAL EARTHING Solidly Earthed 4.3 VOLTAGE AND FREQUENCY VARIATION: A.C SYSTEM a) VOLTAGE: ± 10 % b) FREQUENCY: ± 5 % c) COMBINED VOLTAGE AND FREQUENCY ± 10 % D.C SYSTEM (At system output terminals) a) Electrical control, lighting etc. ± 1 % at Charger terminals ± 10 % at Battery terminals (Limits during charging/discharging cycle) b) Instrumentation power supplies: ± 1 % at Charger terminals ± 10 % at Battery terminals (Limits during charging/discharging cycle) 5.0 VOLTAGE FOR LIGHTING DISTRIBUTION 5.1 NORMAL LIGHTING a) VOLTAGE b) FREQUENCY c) SOURCE 5.2 EMERGENCY LIGHTING a) VOLTAGE b) SOURCE c) APPROX. % 5.3 CRITICAL LIGHTING a) VOLTAGE b) SOURCE c) LOCATIONS 240 V A.C 1 Phase 50 Hz Existing power supply available from TEC 240 V A.C 1 Phase Emergency PCC. 15% 220 V D.C Battery Back-Up Light fittings / Battery Charger (SEE NOTE 1) Escape Routes, Substations, Control rooms, Near Incomers of 6.6 kv Swgr & 415V PCC 5.4 LIGHTING TRANSFORMER /S TO BE PROVIDED Yes / No (415 V / 415 V) DesignBasis_44LK5100_Rev0.doc Page 6 of 40

7 GENERAL NFORMATION 6.0 CONTROL SUPPLY FOR ELECTRICAL SYSTEM 6.1 HIGH TENSION CIRCUIT BREAKERS a) SPRING CHARGING MOTORS 110 V DC b) CLOSING CIRCUITS 110 V DC c) TRIP CIRCUITS 110 V DC d) ALARM 110 V DC e) INDICATION 110 V DC f) RELAY AUX. SUPPLY 110 V DC g) HEATERS IN PANELS 240 V A.C 1 Phase h) CONTROL CIRCUIT 110 V DC 6.2 LOW TENSION CIRCUIT BREAKERS (PCC / PMCC) a) SPRING CHARGING MOTORS 110 V DC b) CLOSING CIRCUIT 110 V DC c) TRIP CIRCUIT 110 V DC d) ALARM 110 V DC e) INDICATION 110 V DC f) RELAY AUX. SUPPLY 110 V DC g) HEATERS IN PANEL 240 V A.C 1 Phase h) CONTROL CIRCUIT 110 V DC DesignBasis_44LK5100_Rev0.doc Page 7 of 40

8 GENERAL NFORMATION 6.3 LOW TENSION MOTORS CONTROLLED BY CONTACTORS (MCC) a) COIL CIRCUIT VOLTAGE 240 V A.C 1 Phase (Refer Note 2) b) INDICATIONS 240 V A.C 1 Phase c) ALARM 240 V A.C 1 Phase d) SPACE HEATER CIRCUIT 240 V A.C 1 Phase 7.0 POWER SUPPLY TO LOCAL CONTROL PANELS FOR PACKAGE UNITS 415 V A.C, 50 Hz, 3 Phase. (Any other power supply required shall be derived within the panel by package vendor) 8.0 SOURCE OF SUPPLY FOR CRITICAL LOADS UPS 9.0 PAINTING FOR ELECTRICAL EQUIPMENT S & STRUCTURES 9.1 OUTDOOR EQUIPMENT EPOXY BASED POWDER COATED 9.2 INDOOR EQUIPMENT EPOXY BASED POWDER COATED 9.3 CABLE TRAY & STRUCTURAL STEEL-MATERIAL OF CONSTRUCTION CABLE TRAY SUPPORTS SHALL BE EPOXY PAINTED, PREFABRICATED FRP/GI TRAYS (SEE NOTE 3) 9.4 SHADE 632 OF IS: GENERAL 10.1 CORPORATE STANDARD TO BE FOLLOWED 10.2 STANDARDS OTHER THAN 'IS' IF TO BE FOLLOWED Jacobs Standards to be followed alongwith IS, OISD, NFPA. IEC, (IEEE wherever IEC does not deal) TIE UP WITH EXISTING SYSTEM IF APPLICABLE YES 11.0 TYPE OF ELECTRICAL EQUIPMENT S TO BE USED IN HAZARDOUS AREAS DesignBasis_44LK5100_Rev0.doc Page 8 of 40

9 GENERAL NFORMATION a) ZONE 0 As defined in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A4 b) ZONE 1 c) ZONE ACCURACY CLASS OF METERS a) REVENUE METERS CL. 0.5 b) kw METER CL. 0.5 c) AMMETER CL. 1 d) FIELD AMMETERS CL MOTORS Up to & including 160 kw 415 V A.C, 50 Hz, 3 Phase 14.0 CABLE-COLOUR CODES POWER RESPECTIVE PHASE NEUTRAL POWER CONTROL, METERING SAFETY SWITCHES / EMERGENCY EARTH Above 160 kw & 6 MW 6.6 kv A.C, 50Hz, 3 Phase. ** RED / YELLOW / BLUE BLACK GREY ORANGE GREEN / YELLOW WITH GREEN STRIPES 15.0 INDICATION LAMP- LED TYPE OFF ON FAULT STATUS PHASE 16.0 PUSH BUTTON START STOP RESET INCREASE / DECREASE GREEN RED AMBER / YELLOW WHITE RED,YELLOW, BLUE GREEN RED YELLOW / WHITE BLACK NOTES : 1) SEPARATE BATTERY & CHARGER SHALL BE PROVIDED FOR CRITICAL LIGHTING. 2) FOR MOTORS <= 55 KW (WHICH ARE HAVING DOL STARTER) THE CONTROL SUPPLY FOR MOTOR FEEDERS SHALL BE 110V DC WHEREVER THE LENGTH OF CABLES IS MORE THAN 500 MTRS. 3) CABLE TRAYS INSIDE SUBSTATION BUILDINGS SHALL BE PREFABRICATED GI AND CABLE TRAYS OUTSIDE SUBSTATION BUILDINGS SHALL BE PREFABRICATED FRP. DesignBasis_44LK5100_Rev0.doc Page 9 of 40

10 GENERAL NFORMATION 4) PAINTING FOR OUTDOOR EQUIPMENTS SHALL BE WITH SHADE NO 632 AS PER IS:5 AND FOR INDOOR EQUIPMENTS SHALL BE SHADE NO 631 AS PER IS:5. 5) IN CASE OF 4 CORE LIGHTING CABLES THE COLOUR CODE SHALL BE RED & YELLOW FOR PHASE, BLACK FOR NEUTRAL AND GREEN FOR EARTHING. ONE NO CORE SHALL BE SPARE. * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 10 of 40

11 RECEIVING GIS 1.0 EQUIPMENT S TO BE INSTALLED BY ELECTRIC AUTHORITY 1.1 LIST OF EQUIPMENT S TO BE SUPPLIED BY ELECTRIC AUTHORITY CT / PT/ TVM 1.2 INSTALLATION (OUTDOOR / INDOOR) INDOOR 1.3 REQUIREMENT OF ROOM FOR INSTALLING CIRCUIT BREAKER / RELAY PANEL / METERING PANEL 1.4 AREA REQUIRED FOR RECEIVING YARD TO ACCOMMODATE EQUIPMENT S SUPPLIED BY ELECTRIC AUTHORITY 1.5 INCASE METERING EQUIPMENT TO BE SUPPLIED BY CLIENT, DETAILS OF THE SAME ** / * ** / * NA 2.0 INCOMING LINE 1. WITH CABLES 2. OVERHEAD LINES SINGLE CIRCUIT DOUBLE CIRCUIT 2.1 IN CASE OF DOUBLE CIRCUIT a) OPERATION b) BUS COUPLER c) NO. OF OUTGOING BAYS IN GIS d) PROVISION FOR FUTURE IN GIS 3.0 GIS DESIGN PARTICULARS * * INDEPENDENT / PARALLEL ISOLATOR / CIRCUIT BREAKER ** ** ** New GIS shall be identical in all respects to the existing one. Additionally pressure gauges along with pressure switches should be available. 1. NOMINAL SYSTEM VOLTAGE 110 KV 2. HIGHEST SYSTEM VOLTAGE 123 KV 3. SYM. FAULT LEVEL AT NOMINAL VOLTAGE ** / * MVA 4. BASIC INSULATION LEVEL 650 KVP 5. AUXILIARY POWER CONTROL LIGHTING 6. CREEPAGE DISTANCE 6.1 FOR ENCLOSED INSULATORS 6.2 FOR EXPOSED INSULATORS 415 V AC 110 V DC 240 V AC 12 mm / kv 31 mm / kv DesignBasis_44LK5100_Rev0.doc Page 11 of 40

12 RECEIVING GIS 7. MINIMUM CLEARANCES i) PHASE TO PHASE ii) MINIMUM CLEARANCES BETWEEN POLES TO EARTH ** 8. BUS BAR ARRANGEMENT DOUBLE BUS ARRANGEMENT 9. BUS BAR TYPE NA 10. MATERIAL COPPER 11. ENCLOSURE CONFIGURATION 1-PHASE / 3-PHASE ** / * 12. TYPE OF MATERIAL FOR ENCLOSURE NON CORROSIVE ALUMINIUM 13. DEGREE OF PROTECTION FOR GIS IP 4X 14. MAXIMUM DESIGN PRESSURE OF ENCLOSURE ** 15. INTERNAL FAULT AND PRESSURE LIMITING DEVICES 16. OPERATING MECHANISM 16.1 DISCONNECT AND GROUNDING SWITCHES 16.2 CIRCUIT BREAKER 16.3 OFF CIRCUIT ISOLATOR 17. SEALING END BOX FOR UNDERGROUND CABLE TERMINATION REQUIRED COMMON / SEPARATE MOTORISED MOTORISED MOTORISED REQUIRED 18. TYPE OF CABLE (XLPE) XLPE 19. SF6-TO-OIL TRANSFORMER TERMINATION REQUIRED 20. GAS INSULATED SURGE ARRESTERS REQUIRED 21. TIE UP WITH EXISTING GIS REQUIRED 4.0 GROUNDING SYSTEM IEEE 80 & IEEE GROUNDING MATERIAL COPPER 4.2 ALLOWABLE GROUND INSULATION ** 4.3 MAGNITUDE OF FAULT CURRENT 40 KA 4.4 DURATION 1.0 sec. for grounding material size & 0.6 sec for step / touch potential calculations 4.5 CONNECTION WITH EXISTING GROUNDING SYSTEM OF GIS REQUIRED 5.0 LIGHTING IN GIS SUBSTATION 5.1 ILLUMINATION LEVEL REQUIRED 200 LUX DesignBasis_44LK5100_Rev0.doc Page 12 of 40

13 RECEIVING GIS 5.2 TYPE OF LIGHTING FITTING Medium Bay / ** 5.3 TYPE OF LAMPS HPMV 6.0 CABLE TRENCHES TYPE COVER RCC RCC 7.0 CABLE TRAYS WITHIN TRENCH TYPE REQUIRED / NOT REQUIRED GI LADDER TYPE NOTES : 1) PROTECTION RELAY PANELS FOR GIS SHALL BE KEPT TOUCHING WITH WALL AND BACK ACCESS SHALL NOT BE AVAILABLE FOR MAINTENANCE PURPOSE. VENDOR TO ENSURE THAT MAINTENANCE SHALL BE POSSIBLE FROM FRONT SIDE OF THE PANEL. * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING DesignBasis_44LK5100_Rev0.doc Page 13 of 40

14 STANDBY / CAPTIVE POWER GENERATION 1.0 GENERATION VOLTAGE 415V 2.0 PRIME MOVER TYPE EMERGENCY DG SET 3.0 TYPE OF STARTING AMF 4.0 NO. OF SETS 1 NO. 5.0 MODE OF OPERATION 5.1 INDEPENDENT REQUIRED 5.2 SYNCHRONIZED NA 6.0 PARALLELING WITH GRID NA 7.0 NEUTRAL EARTHING SOLID 8.0 SERVICE 8.1 UNDER MAINS FAILURE ONLY CHANGE OVER SCHEME REQUIRED 8.2 POWER CUT NA 8.3 CONTINUOUS NA NOTES : 1) COMMON EMERGENCY DG SET SHALL BE PROVIDED FOR PROVIDING EMERGENCY LIGHTING IN MAIN SUBSTATION, CONTROL ROOM, DHT, HGU, SULPHUR RECOVERY BLOCK AND OSBL AREAS. EEMERGENCY DG SHALL SUPPLY POWER TO EMERGENCY PCC. SWITCH FUSE FEEDERS SHALL BE PROVIDED IN EMERGENCY PCC FOR GIVING SUPPLY TO EMERGENCY BUS OF MAIN LIGHTING DISTRIBUTION BOARDS. 2) * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 14 of 40

15 HT SWITCHGEAR (INDOOR) 1.0 TYPE OF CIRCUIT BREAKER BASED ON QUENCHING MEDIUM (VACUUM, SF6, OIL, AIR) kv NOT APPLICABLE kv Vacuum 2.0 BUS BAR 6.6 KV, 50 HZ, TP (SINGLE BUSBAR SYSTEM) 2.1 MATERIAL/NOS. Copper (6.6 kv, TP, Single Busbar System) 2.2 INSULATION SUCH AS CAST RESIN Raychem sleeving required with shrouds at joints. 2.3 FAULT LEVEL AND DURATION kv NOT APPLICABLE kv 450 MVA for 3 sec. 3.0 PROTECTIVE RELAYS 3.1 INCOMING FEEDER 3.2 BUS COUPLER 3.3 OUTGOING FEEDERS As defined in Engineering TRANSFORMER FEEDER Design Guidelines Document No TIE FEEDER 44LK /E.02/0002/A MOTOR FEEDERS CAPACITOR FEEDER 4.0 METERING 4.1 INCOMING FEEDER 4.2 BUS COUPLER 4.3 OUTGOING FEEDERS As defined in Engineering TRANSFORMER FEEDER Design Guidelines Document No TIE FEEDER 44LK /E.02/0002/A MOTOR FEEDERS CAPACITOR FEEDER 5.0 TYPE OF CABLE TERMINATION Heat Shrinkable (Raychem make) 6.0 PROVISION FOR EXTENSION Required / Not Required DesignBasis_44LK5100_Rev0.doc Page 15 of 40

16 HT SWITCHGEAR (INDOOR) 7.0 EXECUTION Draw out 8.0 SWITCHGEARS FOR MOTOR CONTROL FEEDERS Circuit breaker 9.0 AUTO CHANGEOVER SCHEME Required / Not Required 10.0 PROVISION OF REMOTE ALARM / ANNUNCIATOR PANEL FOR HT SWITCHGEAR 11.0 RELAYS SHALL BE COMMUNICABLE TYPE AND SHALL COMMUNICATE WITH DCS / ECS / MMI. Required / Not Required YES / NO (USING IEC PROTOCOL) NOTE: 1) * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 16 of 40

17 MAIN / DISTRIBUTION TRANSFORMER 1.0 SELECTION OF TRANSFORMERS 1.1 SPARE CAPACITY TO BE CONSIDERED 20% 1.2 STANDBY TRANSFORMERS 100% 1.3 NORMAL LOADING OF EACH TRANSFORMER 40% of the capacity 1.4 TYPE OF COOLING ONAN / ONAF 2.0 VOLTAGE RATIO AT NO LOAD 110 / 6.9 kv, 6.6 / kv 3.0 TAP CHANGER MAIN TRAFO DISTRIB: TRAFO 3.1 OFF CIRCUIT For Distribution transformer (6.6 / kv) 3.2 ON LOAD For Power transformer (110 / 6.9 kv) 4.0 RANGE OF TAP CHANGING +/- 7.5 % in steps of 2.5% For Distribution transformer +/- 10% in steps of 1.25% For Power transformer 5.0 PRIMARY AND SECONDARY TERMINAL ARRANGEMENT 5.1 OVERHEAD CONDUCTOR Not Applicable 5.2 CABLE PRIMARY: GIS Duct on Primary side of 110 / 6.9 kv & Cables on Primary side of 6.6 / kv transformers SECONDARY: Cable for 110 / 6.9 kv transformers & 6.6 / kv transformers rated below 1.6 MVA 5.3 BUS DUCT For secondary of 6.6 / kv transformers (1.6MVA and above) 6.0 NEUTRAL EARTH ARRANGEMENT For 110 / 6.9 kv transformer through NGR For 6.6 / kv transformer Solidly Grounded. 7.0 VECTOR GROUP Dyn TAP CHANGER-INCREASE/DECREASE CONTROL MAIN TRAFO Local tap changer control panel / RTCC DISTRIB: TRAFO Local tap changer wheel NOTES : 1) DISTRIBUTION TRANSFORMERS SHALL BE EITHER OIL FILLED OR DRY TYPE TRANSFORMERS. 2) DISTRIBUTION TRANSFORMERS SHALL BE OF MINIMUM 2.5 MVA RATING. DesignBasis_44LK5100_Rev0.doc Page 17 of 40

18 POWER CONTROL CENTRE (PCC & PMCC) 1.0 TYPE OF CIRCUIT BREAKER 1.1 DRAWOUT / NON DRAWOUT Draw Out. 1.2 TPN / 4 POLE TPN 2.0 BUS BAR 415 V, TPN, 50 HZ, 50 KA FOR 1 SEC 2.1 MATERIAL. Copper 2.2 PVC SLEEVING Required / Not Required 2.3 BUS BAR SUPPORT Epoxy Resin / SMC / FRP 3.0 CONSTRUCTION FORM 3 B Construction 3.1 COMPARTMETALISED / NON COMPARMENTALISED Compartmentalized 3.2 OUTGOING FEEDERS Draw out / Non Draw out 3.3 BUS BAR LOCATION Top (Including Neutral Busbar) See Note PAD LOCKING FOR OUTGOING FEEDERS Required / Not Required 3.5 SIZE OF INSTRUMENTS Minimum 96 x 96 Sq. mm for analogue instruments 3.6 ENCLOSURE a) MATERIAL (SHEET STEEL, CAST IRON) CRCA Sheet Steel b) PROTECTION CLASS Min. IP EQUIPMENT SELECTION 4.1 RATING UPTO WHICH SWITCH DISCONNECTOR FUSE TO BE USED 4.2 RATINGS ABOVE WHICH ACB TO BE USED As specified in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A4. For feeders rated above 400 A and for motors rated above 55 kw. 5.0 PROTECTIVE RELAYS 5.1 INCOMING FEEDERS 5.2 BUS COUPLER 5.3 POWER FEEDERS As specified in Engineering Design 5.4 FEEDER TO MCC Guidelines Doc. No.: 5.5 FEEDER TO MLDB 44LK /E.02/0002/A4 5.6 FEEDER TO CAPACITOR BOARD (Discreet Numerical relays shall be 5.7 FEEDER TO MOTORS provided instead of releases for all 5.8 THERMISTOR RELAY/ COMPREHENSIVE MPR FOR MOTORS 75KW & ABOVE ACBs) DesignBasis_44LK5100_Rev0.doc Page 18 of 40

19 POWER CONTROL CENTRE (PCC & PMCC) 6.0 METERING 6.1 INCOMING FEEDERS 6.2 BUS COUPLER 6.3 POWER FEEDERS As specified in Engineering Design 6.4 FEEDER TO MCC Guidelines Doc. No.: 6.5 FEEDER TO MPDB 44LK /E.02/0002/A4 6.6 FEEDER TO CAPACITOR BOARD 6.7 FEEDER TO MOTOR 7.0 INDICATING LAMPS 7.1 INCOMERS As specified in Engineering Design 7.2 POWER FEEDERS Guidelines Doc. No.: 7.3 MOTOR FEEDERS 44LK /E.02/0002/A4 8.0 CURRENT TRANSFORMER SECONDARY 8.1 PROTECTION 1 A 8.2 METERING 1 A 9.0 POTENTIAL TRANSFORMER SECONDARY 110 V / 3 A.C 1 Phase 10.0 NO. OF FRONTS Single front for PCCs & PMCCs V MOTORS RATED ABOVE 55 KW & UPTO 160 KW 12.0 AUTOCHANGEOVER FACILITY AND SYNCHRO CHECK FACILITY SHALL BE PROVIDED. To be controlled from PCC / PMCC through ACB (Refer in Doc. No. 44LK /E.02/0002/A4). YES / NO 13.0 RELAYS SHALL BE COMMUNICABLE TYPE. YES 14.0 PROTOCOL OF COMMUNICATION FOR THE RELAYS. IEC NOTES : 1) FOR MOTOR FEEDERS ABOVE 55 KW NUMERICAL MOTOR PROTECTION RELAY WITH INBUILT CARD FOR ACCEPTING THERMISTOR INPUT SHALL BE PROVIDED. 2) IN CASE OF PCC / PMCC ALL OUTGOING FEEDERS SHALL BE MINIMUM 800A ACBS. 3) ANALOG AMMETERS ARE NOT REQUIRED FOR ALL PCC OUTGOING FEEDERS. 4) EARTH FAULT PROTECTION SHALL BE PROVIDED FOR ALL MOTOR FEEDERS. 5) THE VERTICAL NEUTRAL DROPPERS SHOULD BE AVAILABLE FOR ALL THE VERTICAL SECTIONS. DesignBasis_44LK5100_Rev0.doc Page 19 of 40

20 MOTOR CONTROL CENTRE (MCC) 1.0 TYPE Double Front 2.0 EXECUTION Draw out / Fixed 3.0 BUSBARS 415 V, TPN, 50 HZ, 50 KA FOR 1 SEC 3.1 MATERIAL Copper 3.2 PVC SLEEVING. Required / Not Required 3.3 BUS BAR SUPPORT Cast Resin / SMC / FRP 4.0 SEPARATE MARSHALLING CABINET Required / Not Required 5.0 LOCATION OF MAIN BUS BARS (TOP / BOTTOM) TOP (Including Neutral Busbar) See Note TYPE OF MOTOR STARTER a) DOL STARTER As specified in Engineering Design b) STAR / DELTA STARTER Guidelines Doc. No. 44LK /E.02/0002/A4 (Star Delta Starter not required) c) ANY OTHER TYPE Soft Starter. 7.0 MAXIMUM NO. OF FEEDERS PER PANEL TYPE OF ASSISTED STARTERS FOR MOTORS As specified in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A4 9.0 INCOMING FEEDERS 9.1 CIRCUIT BREAKER / SWITCH / SWITCHFUSE As specified in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A4 9.2 METERS (AMMETER, VOLTMETER, KWH, PF). 9.3 NOS. AND AMMETERS, SIZE 9.4 PROTECTION 10.0 OUTGOING FEEDERS 10.1 MOTOR FEEDERS CONTROL DEVICES ON COMPARTMENT DOOR Stop Push Button, BMR RESET PB, Ammeter, L/R Selector Switch INDICATION ON COMPARTMENT DOOR (ON / OFF / TRIP). ON / OFF / TRIP AMMETER ON MOTOR FEEDERS Required on all motor feeders DesignBasis_44LK5100_Rev0.doc Page 20 of 40

21 MOTOR CONTROL CENTRE (MCC) NO. & AMMETER SIZE ON MOTOR FEEDERS 1 No. / 72 X 72 Sq. mm Ammeter Selector Switch (ASS) for motors rated 37 kw and above CURRENT TRANSFORMER SECONDARY FOR METER & RELAYS CONTROL SUPPLY For Meter: 1 A For Relays: 1 A 240 V A.C 1 Phase SPARE FEEDERS 25% Spare feeders with min. one No. of each rating and type in each switchboard PAD LOCKING FOR ISOLATOR/MCCB/MPCB IN OFF POSITION. Required 10.2 SWITCHFUSE FEEDERS METERS NA 10.3 CONTROL TRANSFORMER FEEDER a) COMMON CONTROL TRANSFORMER FOR ENTIRE MCC b) WORKING & STANDBY CONTROL TRANSFORMER WITH CHANGE OVER SWITCH. c) CONTROL TRANSFORMER FOR EACH MOTOR FEEDER. No YES No FOUR POLE SWITCH / AUX. SWITCH IN ALL MOTOR FEEDERS FOR ISOLATING CONTROL SUPPLY Auxiliary switch with fuse and link 11.0 ELCB FOR EACH FEEDER Required 12.0 OTHER ACCESSORIES 12.1 CONTROL SUPPLY BUS BARS Wire Bus / Solid Bus 12.2 SPACE HEATER SUPPLY BUS BARS. Wire bus / Solid Bus 12.3 SPACE HEATER FOR MCC REQUIRED / NOT REQUIRED 13.0 ENCLOSURE: a) MATERIAL CRCA Sheet Steel / Cast Iron b) PROTECTION CLASS Minimum IP AUTOCHANGEOVER FACILITY AND SYNCHRO CHECK FACILITY SHALL BE PROVIDED. NOT REQUIRED IN MCC 15.0 RELAYS SHALL BE COMMUNICABLE TYPE YES DesignBasis_44LK5100_Rev0.doc Page 21 of 40

22 MOTOR CONTROL CENTRE (MCC) 16.0 PROTOCOL OF COMMUNICATION FOR THE RELAYS IEC MOTOR FEEDERS SHALL BE COMMUNICABLE TYPE NO 18.0 PROTOCOL OF COMMUNICATION FOR THE MOTOR FEEDERS NOT APPLICABLE NOTE : 1) SELECTOR SWITCH SHALL BE PROVIDED FOR TRIPPING & CLOSING OF BREAKERS DURING LOAD TRANSFER IN CASE OF MCCs. 2) FOR MOTORS <= 55 KW (WHICH ARE HAVING DOL STARTER) THE CONTROL SUPPLY FOR MOTOR FEEDERS SHALL BE 110V DC, WHEREVER THE LENGTH OF CABLES ARE MORE THAN 500 MTRS. 3) IN CASE OF MCC SWITCH FUSE UNITS SHALL BE USED FOR RATINGS UP TO 400A AND ACBS SHALL BE USED FOR RATING ABOVE 400A. 4) THE VERTICAL NEUTRAL DROPPERS SHOULD BE AVAILABLE FOR ALL THE VERTICAL SECTIONS. * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 22 of 40

23 H.T MOTORS 1.0 RATED VOLTAGE 6.6. KV 2.0 VOLTAGE AND FREQUENCY VARIATION ± 10 %V, ± 5 %Hz 3.0 COMBINED VOLTAGE AND FREQUENCY VARIATION ± 10 % 4.0 CLASS OF INSULATION & TEMP. RISE Class F with Temp. Rise limited to Class B 5.0 ENCLOSURE PROTECTION CLASS IPW TYPE OF ENCLOSURE As per Area Classification 7.0 TYPE OF COOLING (TEFC / CACA / CACW / TETV) TEFC / CACA As per Manufacturers Standard 8.0 TEMPERATURE DETECTORS FOR WINDING (RTD) Simplex / Duplex (2 nos per phase) 9.0 a) TEMPERATURE DETECTORS FOR BEARING b) DIAL TYPE LOCAL TEMP. INDICATOR FOR BEARINGS FAULT WITHSTAND CAPACITY FOR MAIN TERMINAL BOX Simplex / Duplex (1 each for DE & NDE bearing) Required 0.25 sec NEUTRAL TERMINAL BOX Required / Not Required 12.0 TYPE OF CABLE TERMINATION AT MOTOR END Heat Shrinkable (Phase Segregated) 13.0 NO. OF COLD STARTS PER HOUR 3 Nos. (min) / hour, Equally Spaced 14.0 NO. OF HOT STARTS PER HOUR 2 Nos. (min) / hour, Equally Spaced 15.0 SPECIAL WINDING TREATMENT Suitable for corrosive atmosphere with Epoxy Gel treatment on winding overhang 16.0 SEPARATE TERMINAL BOX FOR a) SPACE HEATER Required / Not Required b) RTD Required / Not Required 17.0 AUXILIARY NAME PLATE Required (SS) NOTES : 1) SAFE STALLING TIME OF MOTOR SHALL BE MINIMUM 2.5 SECS MORE THAN THE STARTING TIME OF MOTOR AT 80% VOLTAGE. 2) HT MOTORS IN HAZARDOUS AREAS SHALL BE EITHER WITH Ex d OR Ex p ENCLOSURE ONLY, IRRESPECTIVE OF ZONE CLASSIFICATION OF ZONE 1 OR ZONE 2. DesignBasis_44LK5100_Rev0.doc Page 23 of 40

24 LT MOTORS 1.0 RATED VOLTAGE 415 V 2.0 VOLTAGE AND FREQUENCY VARIATION ± 10 % V, ± 5 % Hz 3.0 COMBINED VOLTAGE AND FREQUENCY VARIATION ± 10 % 4.0 CLASS OF INSULATION & TEMP. RISE Class F with Temperature Rise Limited to Class B. 5.0 ENCLOSURE PROTECTION CLASS IPW 55 (Minimum) 6.0 TYPE OF ENCLOSURE As per Area Classification 7.0 TYPE OF COOLING (TEFC / SPDP) TEFC 8.0 TEMPERATURE DETECTORS FOR WINDING Thermistors for motors rated 75 kw and above and For all VSD driven motors. 9.0 TEMPERATURE DETECTORS FOR BEARING Not Required 10.0 NO. OF COLD STARTS PER HOUR 4 (Minimum) 11.0 NO. OF HOT STARTS PER HOUR 3 (Minimum) 12.0 WHETHER ENERGY EFFICIENT MOTORS REQUIRED? 13.0 ENERGY EFFICIENCY CLASS AS PER IS (2004) YES / NO EFF SPECIAL WINDING TREATMENT Suitable for corrosive atmosphere with epoxy gel treatment on winding overhang. NOTES : 1) MOTORS OF RATING 55 KW AND ABOVE SHALL BE PROVIDED WITH SPACE HEATERS. 2) SAFE STALLING TIME OF MOTOR SHALL BE MINIMUM 2.5 SEC MORE THAN THE STARTING TIME OF MOTOR AT 80% VOLTAGE. 3) MOTORS DRIVEN BY VSD SHALL BE INVERTER GRADE AND SHALL BE SUITABLY DERATED TO TAKE CARE OF REDUCED COOLING AT LOWER SPEEDS. 4) MOTOR TERMINAL BOX SHALL BE SUITABLE FOR TERMINATING THE ACTUAL NO. OF CABLES. 5) FOR PACKAGE UNIT MOTORS THE TERMINAL BOX SHALL BE FREELY ACCESSIBLE. * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 24 of 40

25 CABLES & ACCESSORIES 1.0 HIGH TENSION 1.1 VOLTAGE GRADE 6.6 kv (UE) 1.2 EARTHED / UNEARTHED SYSTEM As per clause no. 1.1 above. 1.3 ARMOURED / UNARMOURED Armoured 1.4 CONDUCTOR MATERIAL Aluminum / Copper (Based on Fault Withstand Capacity) 1.5 CONDUCTOR SCREENING Semi conducting compound 1.6 TYPE OF OUTER SHEATHING Extruded FRLS PVC Outer sheath. 1.7 FAULT LEVEL WITHSTAND TIME a) FEEDER WITHOUT INST. TRIPPING DEVICE. 1 sec. b) FEEDER WITH INST. TRIPPING DEVICE sec. 1.8 INSULATING MATERIAL XLPE 1.9 INSULATION SCREENING With semi conducting compound and with non-magnetic material (Cu foil) for multicore cables TYPE OF CABLE TERMINATION (RAYCHEM / M- SEAL / PUSH ON / BITUMEN COMPOUND) Raychem heat shrinkable type 1.11 ANY SPECIAL REQUIREMENT None 1.12 TYPE & MATERIAL OF CABLE LUGS Tinned Copper / Aluminium 1.13 MAXIMUM / MINIMUM SIZE TO BE USED As specified in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A4 2.0 LOW TENSION 2.1 VOLTAGE GRADE. 650 / 1100 V 2.2 CONDUCTOR MATERIAL Up to 16 Sq.mm Cu. Above 16 Sq.mm Al /CU - See Note 1 below 2.2 INSULATING MATERIAL XLPE 2.3 TYPE OF INNER SHEATH (EXTRUDED / TAPE) EXTRUDED 2.4 ARMOURED / UNARMOURED ARMOURED 2.5 TYPE OF OUTER SHEATH (PVC / HRPVC / FRLS) FRLS 2.6 TYPE AND MATERIAL OF CABLE LUGS Tinned cu for cu cables / Al for Al cables 2.7 TYPE OF CABLE GLANDS a) MATERIAL Nickel Plated Brass b) INDOOR PANEL Double compression type c) MOTORS IN FIELD Double compression type d) PUSH BUTTON & CONTROL PANELS IN FIELD Double compression type DesignBasis_44LK5100_Rev0.doc Page 25 of 40

26 CABLES & ACCESSORIES e) EQUIPMENT IN ZONE - 2 AREAS Ex (e)-double compression type f) EQUIPMENT IN ZONE - 1 AREAS Ex (d)-double compression type 2.8 MAXIMUM/MINIMUM SIZE TO BE USED As specified in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A ANY SPECIAL REQUIREMENT ---- NOTES : 1)If the length of the cable involved is high and if the number & size of the cable with Al conductor needed to limit voltage drop is high and is difficult to be terminated in the motor terminal box, then copper conductor cables which will result in lesser number/size of cable shall be provided. Providing junction box (JB) near to the motor end to terminate multiple cable from switchgear and providing lesser number/size of cable from JB to motor is not acceptable for motors <110 kw. Ex d Junction boxes may be provided for LT motors >= 110 kw 2) Bimetallic washers to be used for Copper Aluminium connections DesignBasis_44LK5100_Rev0.doc Page 26 of 40

27 DISTRIBUTION BOARDS (MLDB, ASB, LP, SLP, PP) A) MAIN DISTRIBUTION BOARD (MLDB, ASB) 1.0 DESIGN (COMPARTMENTALISED/FLOOR MOUNTING/DRAWOUT/FIXED TYPE) Project Title : DHT Compartmentalized / Floor mounting / Wall mounting / Fixed type 2.0 BUS BAR 415 V, TPN, 50 HZ, 50 KA FOR 1 SEC 2.1 MATERIAL Copper 2.2 INSULATING SLEEVING (HEAT SHRINKABLE PVC Required SLEEVING) 2.3 LOCATION Top (including Neutral busbar) 3.0 INCOMING FEEDERS 3.1 TYPE OF COMPONENT (FUSE SWITCH / MCCB) Switch fuse unit up to 400A rating and ACB above 400A rating MLDB, ASB 3.2 METERING Digital Enercon kwh Meter and Analogue voltmeter 4.0 OUTGOING FEEDERS 4.1 TYPE OF COMPONENT (FUSE SWITCH /MCCB/MCB) Switch Fuse Unit - MLDB, ASB 4.2 ENCLOSURE a) MATERIAL CRCA sheet steel b) TYPE & PROTECTION CLASS FOR INDOOR INSTALLATION FOR OUTDOOR INSTALLATION IP 52 Minimum Cast Al for outdoor duty IP 55 Minimum B) SUB-DISTRIBUTION BOARD (LP, SLP, PP) 1.0 BUS BAR 415 V, 50 HZ, TPN 1.1 MATERIAL Copper 2.0 INCOMING FEEDER 2.1 TYPE OF COMPONENT (FUSE SWITCH /MCCB/MCB) MCB (10kA) LP, SLP, PP 3.0 OUTGOING FEEDER 3.1 COMPONENT (FUSE SWITCH /MCB/ELMCB) SPN MCB with ELCB - LP, PP DesignBasis_44LK5100_Rev0.doc Page 27 of 40

28 DISTRIBUTION BOARDS (MLDB, ASB, LP, SLP, PP) Project Title : DHT 4.0 ELCB REQUIREMENT For outgoing feeders NOTES : 1) SWITCH FUSE UNITS SHALL BE PROVIDED IN AUXILIARY SWITCH BOARD (ASB) FOR GIVING SUPPLY TO WELDING RECEPTACLES. 2) IN CASE OF ASB / MLDB SWITCH FUSE UNITS SHALL BE USED FOR RATINGS UP TO 400A AND ACBS SHALL BE USED FOR RATING ABOVE 400A. * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 28 of 40

29 CONTROL STATIONS 1.0 MATERIAL OF ENCLOSURE Sheet steel / Cast iron / Cast Al. / FRP 2.0 PROTECTION CLASS OF ENCLOSURE IP PROVISION OF AMMETERS FOR DRIVES Required for all motors rated 15 kw and above and all Emergency & Critical Drives 4.0 REQUIREMENT OF SEPARATE / INTEGRAL CANOPY CANOPY OF FRP 5.0 STOP PUSH BUTTON TYPE MUSHROOM HEAD WITH STAYPUT FEATURE (PRESS TO LOCK AND TURN TO UNLOCK), LOCKABLE PROTECTIVE COVER TO PREVENT ACCIDENTAL ACTIVATION OF PB. 6.0 START PUSH BUTTON TYPE SHROUDED TYPE 7.0 LOCAL/ REMOTE SS (WITH MAKE BEFORE BREAK CONTACTS) REQUIRED 8.0 PAD LOCKING REQUIREMENT REQUIRED FOR STOP PB NOTES: * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 29 of 40

30 LIGHT FITTINGS 1.0 TYPES OF LAMP (GLS / FLUORESCENT / HPMV / HPSV) a) FOR PROCESS AREAS HPMV b) FOR OUTDOOR AREAS HPMV (For Safe Areas) c) FOR ROAD & SECURITY HPMV HPMV (For Hazardous Area) d) FOR GODOWN / WAREHOUSE ETC Not Applicable e) SUBSTATION / CONTROL ROOM Fluorescent f) ADMINISTRATION & OTHER NON PLANT BUILDINGS Fluorescent 2.0 PERCENTAGE OF LIGHT FITTINGS ON EMERGENCY SUPPLY. 3.0 LIGHT FITTINGS ON DC / UPS SUPPLY FOR CRITICAL AREAS 4.0 TYPE OF AUTOMATIC CONTROL OF LIGHTING- OUTDOOR LIGHTING 15% As specified in Engineering Design Guidelines Doc. No. 44LK /E.02/0002/A4 Control is through existing Centralized Lighting scheme / Photocell / Timer 5.0 TYPE OF FITTINGS IN HAZARDOUS AREA ZONE - I ZONE -II Ex (d) Ex (d) 6.0 PROVISION FOR LOOPING Junction box in Light fitting for looping 7.0 WIRING OF LIGHT FITTING, CONDUIT / CABLE (SPECIFY AREA WISE) Outdoor Areas with Armoured Copper cable stranded Cu Buildings with false ceiling: - Concealed conduit wiring below false ceiling PVC Conduits - Surface conduit wiring above false ceiling. PVC Conduits 8.0 ILLUMINATION LEVEL As specified in Engineering Design Guidelines Doc.No. 44LK /E.02/0002/A4 NOTES: * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 30 of 40

31 BATTERY & BATTERY CHARGER 1.0 BATTERY 1.1 TYPE Ni-Cd 1.2 VOLTAGE 110 V DC for Switchgear DC Control Supply & 220 V DC for Critical DC Lighting Supply 1.3 BACK UP TIME OF BATTERY 2 Hours (for Switchgear DC Control Supply) 1 Hour (Critical DC Lighting Supply) 2.0 BATTERY CHARGER 2.1 TYPE (DIODE WITH AUTO TRANSFORMER / THYRISTOR) 2.2 FLOAT CHARGING CUM BOOST CHARGER / FLOAT & BOOST CHARGER SEPARATELY Thyristor Float cum Boost Charger 2.3 REDUNDANCY OF BATTERY & CHARGER Charger : 100% redundant (for Switchgear DC Control Supply) : Single (for Critical DC Ltg Supply) Battery : One (1) Battery Bank for Switchgear DC Control Supply and One (1) Battery Bank for Critical DC Lighting Supply NOTES: * - INFORMATION TO BE FURNISHED BY CLIENT DesignBasis_44LK5100_Rev0.doc Page 31 of 40

32 CAPACITOR 1.0 FINAL POWER FACTOR REQUIRED 0.95 (*) 2.0 TYPE OF PF CONTROL a) GROUP CONTROL AT HT b) GROUP CONTROL AT LT (PCC / MCC) c) INDIVIDUAL CONTROL WITH MOTOR 6.6 kv Switchgear NA NA 3.0 TYPE OF CONTROL MANUAL 4.0 TYPE OF DI - ELECTRIC APP **. NOTE : 1) DELETED. * - INFORMATION TO BE FURNISHED BY CLIENT ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 32 of 40

33 PUBLIC ADDRESS SYSTEM 1.0 REQUIREMENTS (GENERAL PAGING / CONFERENCE BETWEEN VARIOUS STATIONS / POINT TO POINT COMMUNICATION) Refer Doc. No. 44LK /E.02/0002/A4 2.0 NO. OF STATIONS REQUIRED FOR ** 2.1 FOR OPERATION OF THE PLANT SECURITY Yes 2.2 INTEGRATION WITH TELEPHONE SYSTEM Required 2.3 INTEGRATION WITH FIRE ALARM SYSTEM Required 3.0 HOOK UP WITH EXISTING PA SYSTEM NOT REQUIRED NOTES : 1) PA SYSTEM SWITCHING PANEL SHALL BE LOCATED IN NEW CONTROL ROOM. * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 33 of 40

34 TELEPHONE SYSTEM 1.0 FUNCTIONAL REQUIREMENTS (BRIEF DESCRIPTION OF PLANT REQUIRED) 2.0 NO. OF HAND SETS Refer Doc. No. 44LK /E.02/0002/A4 As per scope requirement 3.0 FURTHER EXPANSION TO BE CONSIDERED YES 4.0 NO. OF P& T LINES TO BE INTERCONNECTED As per scope requirement 5.0 HOOK UP WITH PA & FA SYSTEM REQUIRED 6.0 HOOK UP WITH EXISTING TELEPHONE SYSTEM REQUIRED NOTES : 1) NEW EPABX (IF PROVIDED) SHALL BE INTEGRATED WITH EXISTING EPABX. NEW EPABX (IF PROVIDED) SHALL BE LOCATED IN NEW CONTROL ROOM. * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 34 of 40

35 ELECTRICAL INSTALLATION 1.0 MODE OF CABLE LAYING (TRENCH / BURIED / OVER HEAD TRAYS) 2.0 TYPE OF CABLE TRAY AND ACCESSORIES (PRE- FABRICATED / FABRICATED AT SITE WITH STRUCTURAL STEEL) Sand filled cable trench / Buried / Overhead tray Pre-fabricated ladder type. 3.0 MATERIAL OF PRE-FABRICATED TRAYS FRP / GI (Refer Note 1) 4.0 CABLE CLAMPING ARRANGEMENT (CLAMPS MADE OF STEEL / AL / NYLON ROPES) Clamps made of Aluminum 5.0 CABLE TAG (ALUMINIUM / S.S) SS 6.0 CABLE MARKER FOR UNDERGROUND CABLE / MATERIAL Wherever Applicable. (Shall be provided 15 Mtrs apart) SS 7.0 SECURITY LIGHTING WITH STRUCTURAL TOWERS Shall be provided Wherever Applicable. 8.0 TYPE OF STREET LIGHT POLE REQUIRED 12 / 10 meters high swaged tubular as per IS 2713 Aluminium Poles 9.0 SOCKET OUTLETS - INDUSTRIAL / FLP TYPE FLP socket outlets in DHT, HGU & Sulphur recovery block areas. IND / FLP socket outlets in OSBL areas. a) FOR WELDING (RATINGS & AREAS TO BE COVERED) 63 A, 415 V TPN + E As per area classification. b) FOR PORTABLE ELECTRICAL EQUIPMENT S 20 A, 240 V, SPN + E c) FOR FANS & OTHER EQUIPMENT S IN NON- PLANT AREAS d) FOR HAZARDOUS AREAS A, 240 V, SPN + E 20 A, 240 V, DP + E, Ex (d) type 20 A, 240 V, DP + E, Ex (e) type (As Applicable) NOTES : 1) CABLE TRAYS INSIDE SUBSTATION BUILDINGS SHALL BE PREFABRICATED GI AND CABLE TRAYS OUTSIDE SUBSTATION BUILDINGS SHALL BE PREFABRICATED FRP. 2) 200A, 415V, TPN+E SOCKET OUTLETS SHALL BE PROVIDED FOR MAINTENANCE ACTIVITIES DURING SHUTDOWN. 3) 24V AC SOCKET OUTLETS SHALL BE PROVIDED AT EACH ELEVATION OF PROCESS BLDG. * - INFORMATION TO BE FURNISHED BY CLIENT. DesignBasis_44LK5100_Rev0.doc Page 35 of 40

36 EARTHING 1.0 EARTH PIT TYPE & MATERIAL 100 mm Dia G.I Pipe for Neutral & Body Earthing of Transformer & Generators. Plate Electrode for GIS 2.0 EARTHING MATERIAL G.I Pipe: for other plant areas 3.0 TYPE OF EARTHING CONDUCTOR FOR EQUIPMENT S 3.1 EARTHING MAIN GRID 3.2 SWITCH YARD EQUIPMENT G.I Strip a) TRANSFORMER NEUTRAL Not Applicable b) EQUIPMENT Not Applicable c) LIGHTNING ARRESTOR Not Applicable d) STRUCTURE Not Applicable 3.3 SUBSTATION EQUIPMENT a) EQUIPMENT (PCC / MCC / HT SWGR. ETC.) G.I Strip b) TRANSFORMER NEUTRAL G.I Strip 3.4 PLANT EQUIPMENT a) MOTORS & LCS Unarmoured insulated aluminium cables of appropriate sizes (For cable sizes Refer Dwg.No. 44LK /E.01/0054/A3). Cables shall be Green in colour. b) STATIC EARTHING G.I Strip c) LIGHTING FITTINGS By 3 rd core of 3C x 4 YWY Lighting 4.0 LIGHTNING PROTECTION 4.1 AIR TERMINAL MATERIAL Copper Cable. & G.I of standard wire gauge 4.2 DOWN CONDUCTOR G.I Strip (32 X 6 mm) 4.3 EARTH PIT 1 No. per down conductor 4.4 LIGHTNING PROTECTION FOR TANK FARM AREA (Refer Dwg.No. 44LK /E.01/0054/A3) DesignBasis_44LK5100_Rev0.doc Page 36 of 40

37 STATIC UNINTERRUPTABLE POWER SUPPLY UNITS (UPS) 1.0 TYPE IGBT / Transistorized 2.0 REDUNDANCY / TYPE OF REDUNDANCY 100 % Dual Static parallel redundant 3.0 BACKUP TIME REQUIRED 30 Minutes 4.0 INPUT SUPPLY VOLTAGE 415 V, TPN, 50Hz 5.0 OUTPUT SUPPLY VOLTAGE 110 V SPN for Instrumentation loads 6.0 TYPE OF BATTERIES Ni-Cd 415 V TPN for Critical Load (If any) 7.0 BATTERY EXECUTION Single bank up to 600 Ah / Parallel bank above 600 Ah (2 nos Battery banks for Parallel Redundant UPS) 8.0 STABILISER IN BYPASS LINE Static Voltage Regulator 9.0 BYPASS TRANSFER CONTROL Auto / Manual through Static Switch (Manual for maintenance Bypass) 10.0 VDU WITH PC/PRINTER ETC. Required / Not Required 11.0 COMMUNICATION PORT Required NOTES: * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 37 of 40

38 FIRE ALARM SYSTEM 1.0 TYPE OF FIRE ALARM SYSTEM Digital addressable 2.0 FIRE ALARM PANEL Microprocessor based digital addressable 3.0 TYPE OF DETECTORS Beam detectors, Smoke detectors, Heat detectors as per application (Multi detection) 4.0 PROVISION OF MANUAL CALL POINTS Required 5.0 HOOK UP WITH PA & TELEPHONE SYSTEM REQUIRED 6.0 HOOK UP WITH EXISTING FA SYSTEM NA 7.0 HOOK UP WITH HVAC SYSTEM REQUIRED NOTES : 1) MAIN FIRE ALARM PANEL SHALL BE KEPT IN NEW CONTROL ROOM WHICH SHALL BE HOOKED UP WITH EXISTING FIRE ALARM PANEL IN FIRE STATION. 2) MAIN FIRE ALARM PANEL SHALL BE COMMON FOR MAIN SUBSTATION, DHT, HGU, SULPHUR RECOVERY, NEW CONTROL ROOM & OSBL AREAS. 3) LCD DISPLAY SHALL BE PROVIDED IN FIRE STATION. * - INFORMATION TO BE FURNISHED BY CLIENT. ** - SHALL BE DECIDED DURING DETAIL ENGINEERING. DesignBasis_44LK5100_Rev0.doc Page 38 of 40

39 VARIABLE SPEED DRIVE 1.0 VOLTAGE RATING OF VFD & MOTORS HAVING RATING ABOVE 160kW 1.1 REDUNDANCY IN TRANSFORMER FOR 415V / 660V VFD 415V NOT REQUIRED 2.0 RECTIFIER CONFIGURATION MINIMUM 12 PULSE 3.0 LOCATION OF VSD SEPARATE PANEL 4.0 INPUT ISOLATION TRANSFORMER REQUIRED 4.0 OUTPUT CHOKE REQUIRED / NOT REQUIRED 5.0 PROTOCOL COMMNUNICATION NOT REQUIRED 5.1 IF REQUIRED 6.0 VSD BYPASS BYPASS REQUIRED FOR MOTORS UP TO 55 KW. 7.0 REQUIREMENTS FOR CONTROL & MONITORING ON 7.1 VSD 7.2 LOP REFER NOTE 1 & 2 BELOW. 7.3 DCS / SCADA ON / OFF CONTROL FROM DCS AND RUNNING INDICATION TO DCS. 8.0 PROVISION OF SEPARATE THERMISTOR RELAY REQUIRED 9.0 CLIENT SPECIFIC REQUIREMENTS NOTES : 1) DOL BYPASS SHALL BE PROVIDED FOR VSDs OF RATING UP TO 55 KW. IN THESE VSDs VSD/DOL SELECTOR SWITCH SHALL BE PROVIDED ON THE VSD PANEL ITSELF. THE SCHEME OF THESE VSDs IS AS GIVEN IN ATTACHED ANNEXURE-I. LOCAL CONTROL STATION IN ABOVE MENTIONED VSDs SHALL INCLUDE START AND STOP PB, SPEED RAISE / LOWER PB, DIGITAL AMMETER AND DIGITAL SPEED INDICATOR. SOFTWARE LOCAL/REMOTE SELECTOR SWITCH SHALL BE PROVIDED IN DCS. 2) VSDs WITHOUT BYPASS LCS SHALL BE PROVIDED WITH START AND STOP PB, SPEED RAISE / LOWER PB, DIGITAL AMMETER AND DIGITAL SPEED INDICATOR. SOFTWARE LOCAL/REMOTE SELECTOR SWITCH SHALL BE PROVIDED IN DCS. 3) DELETED 4) IN CASE OF VSDs WITHOUT BYPASS ACB (ACB WITHOUT RELEASES) / SWITCH SHALL BE PROVIDED ON THE INCOMING SIDE. 5) FOR CRITICAL MOTORS (LIKE ID/FD FAN MOTORS) SOFT STARTER SHALL BE PROVIDED ON BYPASS SIDE TO VSD. DesignBasis_44LK5100_Rev0.doc Page 39 of 40

40 ANNEXURE-I (SCHEME FOR VSDs UP TO 55 KW RATING) From MCC SWITCH VFD PANEL I/P Contactor VSD DOL Bypass Contactor + Overload Relay O/P Contactor To Motor DesignBasis_44LK5100_Rev0.doc Page 40 of 40

MANUFACTURER OF LT PANELS

MANUFACTURER OF LT PANELS MANUFACTURER OF LT PANELS POWER CONTROL CENTRE PANEL(PCC): Power Control Centre is used for distribution & control of various power source used in industry. Normally PCC is installed near power source.

More information

1 NOS. 25mm x 4 mm thick with PVC sleeving e) 1Set, RYB, indicating lamps & CT

1 NOS. 25mm x 4 mm thick with PVC sleeving e) 1Set, RYB, indicating lamps & CT A MAIN PANEL/DB 1 Supply and Installation of main LT panel, floor mounted, front operated dead back, totally enclosed vermin proof, indoor, non drawout, cubicle type power dist. panel fabricated out of

More information

DC POWER DISTRIBUTION BOARD

DC POWER DISTRIBUTION BOARD DC POWER DISTRIBUTION BOARD February 2016 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata 700091.

More information

TAITA TAVETA UNIVERSITY P.O.BOX , VOI, KENYA Tel: TENDER NO: TTU/T/01A/

TAITA TAVETA UNIVERSITY P.O.BOX , VOI, KENYA   Tel: TENDER NO: TTU/T/01A/ TAITA TAVETA UNIVERSITY P.O.BOX 635-80300, VOI, KENYA EMAIL: procurement@ttu.ac.ke; Tel: 020 8150257 TENDER NO: TTU/T/01A/2017-2018 CONSTRUCTION OF PROPOSED ADMINISTRATION BLOCK- TAITA TAVETA UNIVERSITY

More information

KATALOGE. Trading of Electrical Switchgear, Lightings, Machineries & Construction Materials. Jamar Trading Co. W.L.L.

KATALOGE. Trading of Electrical Switchgear, Lightings, Machineries & Construction Materials. Jamar Trading Co. W.L.L. KATALOGE Trading of Electrical Switchgear, Lightings, Machineries & Construction Materials Jamar Trading Co. W.L.L. ACB & MCCB Main Panels We assemble Power Distribution Panels for local and export market.

More information

Requirements for Electrical Installations

Requirements for Electrical Installations BRITISH STANDARD BS 7671:2018 Corrigendum (December 2018) Requirements for Electrical Installations IET Wiring Regulations Eighteenth Edition The Institution of Engineering and Technology and BSI NO COPYING

More information

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD.

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. (A Wholly Owned Subsidiary of SBI) CIRCLE OFFICE: 4TH FLOOR, SBI LOCAL HEAD OFFICE III/1-PANDIT J N MARG, KHARAVELA NAGAR BHUBANESWAR, ODISHA-751001 Part-II PRICE

More information

Item/clause/Page no. Description as per tender. To be read as

Item/clause/Page no. Description as per tender. To be read as Date- 02.11.2012 Amendment-2 Work - Tender for SITC of HT/LT substation equipments installation and allied electrical works for lecture theatre complex, FCI campus, University of Allahabad, Allahabad.

More information

ADVANCE ELECTRICAL MEP CONTRACTING TRADING SERVICES

ADVANCE ELECTRICAL MEP CONTRACTING TRADING SERVICES ADVANCE ELECTRICAL MEP CONTRACTING TRADING SERVICES ABOUT US Quality products, exceptional service and quick delivery of a diverse product line are the foundation of our company. By leveraging the portfolio

More information

PROFILE. industrial services rental trading

PROFILE. industrial services rental trading PROFILE industrial services rental trading Introduction Power Corp General Trading & Contracting Company W.L.L. is incorporated by technocrats having vast experience in Engineering and Construction field

More information

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input

Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input Float Battery Chargers Unfiltered SCR and Filtered SCRF Series Single Phase Input / Three Phase Input April 2006 SCR-SCRF Utility & General Industry Switchgear Alarm Systems Engine Starting Railroad Emergency

More information

BOQ FOR FIRE HYDRANT & FIRE ALARM SYSTEM AT T.I.E

BOQ FOR FIRE HYDRANT & FIRE ALARM SYSTEM AT T.I.E A 1 2 4 PUMP HOUSE: BOQ FOR FIRE HYDRANT & FIRE ALARM SYSTEM AT T.I.E Supply, erection,testing & commissioning of Single stage, end suction / back pull-out type motor driven Jockey Pump of capacity 10.8

More information

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input SCR/SCRF SERIES FLOAT BATTERY CHARGERS Industry s First Choice for Time-Tested Proven Reliability Single-Phase Input Three-Phase Input Applications for: Utility & General Industry Switchgear Engine starting

More information

Reliable solutions for electrified railway systems

Reliable solutions for electrified railway systems Reliable solutions for electrified railway systems 1 2 3 Insulation Enhancement System Insulation Enhancement System 1. Raychem MVLC: (Medium Voltage Line Cover) Provides insulation for catenary, droppers

More information

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 12/23/16 Rev 9 UltraLITE Model ELU General Specification 4.2 KW to 5 KW UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW 1.0 General General Specification This specification describes

More information

TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS

TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GETCO/ENGG/TS/

More information

Annexure - 1. Detectors: Fire Alarm Control Panel :

Annexure - 1. Detectors: Fire Alarm Control Panel : Item 1. Supply Part This Specification includes Supply, Warranty, Installation, Testing and Commissioning and integration of the Fire Alarm System mainly consisting of the Fire Alarm Control Panel (FACP),

More information

Electrical Design Guidelines Table of Contents

Electrical Design Guidelines Table of Contents C: Compliant Rev. 3 Dated June 13 11 NC: Non-Compliant NA: Not Applicable Page1 16.1 General 16.2 Single Line Diagrams 16.3 Electric Motor Equipment and Controls 16.4 Lighting 16.5 Emergency Lighting 16.6

More information

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion

Table-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34

More information

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI FIRE PROTECTION 1 G.I.PIPES Supplying, installing, testing and commissioning of G.I Pipes confirming to IS 3589 Pt - I Heavy grade with painting, suitable type of supports, anchor fasteners, bolts nuts

More information

+91-8071806510 Neminath Electricals http://www.neminathelectricals.in/ We are one of the leading manufacturers, suppliers and traders of a wide range of optimum quality Outdoor & Industrial LED Lighting

More information

B. Section Transfer Switches: Automatic transfer switch.

B. Section Transfer Switches: Automatic transfer switch. SECTION 263213 - ENGINE GENERATORS PART 1 GENERAL 1.1 SECTION INCLUDES A. Packaged engine generator set. B. Exhaust silencer and fittings. C. Remote control panel. D. Battery and charger. E. Weatherproof

More information

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase

Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase Model LTN-3R Outdoor Rated Uninterruptible Power System Single Phase General Specification 550 VA/Watts 1300 VA/Watts 1.0 GENERAL This specification defines the electrical and mechanical characteristics

More information

soaring high. scoring high. Trading Co. LLC

soaring high. scoring high. Trading Co. LLC soaring high. scoring high. Trading Co. LLC SWITCHING GEARS TO GREATER SUCCESS Skyway tells a tale of electric growth that began in 1992. Coming a long way in its core business of electrical panel boards

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION

38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION 38-SDMS-04 REV. 0 SPECIFICATION FOR ANNUNCIATOR SYSTEMS FOR PRIMARY DISTRIBUTION SUBSTATION This specification is property of SEC and subject to change or modification without any notice. TABLE OF CONTENTS

More information

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS

TRANSMISSION ENGINEERING STANDARDS SUBSTATIONS This standard was reviewed and approved by key managers with final approval by an officer of Oncor Electric Delivery on. 1.0 SCOPE 1.1 This guide applies to the interconnection of a Customer with the Company

More information

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority. Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code

More information

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts Figure 1Document: SPEC-112 Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts construction requirements of UL approved Class H (180 C) insulation system. Transformers

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Assessor: Karardi, Shibpur, Narsingdi Narsingdi Dhaka Bangladesh Emkay Enterprises The Alliance for Bangladesh Worker Safety Page 1/15 10 Apr 2016 Introduction

More information

FLOAT BATTERY CHARGERS

FLOAT BATTERY CHARGERS FLOAT BATTERY CHARGERS UNFILTERED SCR SERIES FILTERED SCRF SERIES SINGLE PHASE INPUT THREE PHASE INPUT Applications for: UTILITY & GENERAL INDUSTRY Switchgear Engine Starting Emergency Lighting Alarm Systems

More information

LAWSON FINAL DISTRIBUTION PRODUCTS RANGE

LAWSON FINAL DISTRIBUTION PRODUCTS RANGE FINAL DISTRIBUTION PRODUCTS RANGE ISO 14001:2004 Certified ISO 9001:2008 Certified FUSES INDIA LTD Lawson Fuses India Ltd is a wholly owned subsidiary of Lawson Fuses Ltd,a long established UK company

More information

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket

More information

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input

SCR/SCRF SERIES. Industry s First Choice for Time-Tested Proven Reliability FLOAT BATTERY CHARGERS. Single-Phase Input SCR/SCRF SERIES FLOAT BATTERY CHARGERS Industry s First Choice for Time-Tested Proven Reliability Single-Phase Input Three-Phase Input Applications for: Utility & General Industry Switchgear Engine starting

More information

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018 SECTION 26 2913 - ENCLOSED CONTROLLERS GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7

Contents. Preface. Chapter 2 Faults, types and effects The development of simple distribution systems Faults-types and their effects 7 Practical Power System Protection for Engineers and Technicians Contents Preface ix Chapter 1 Need for protection 1 1.1 Need for protective apparatus 1 1.2 Basic requirements of protection 2 1.3 Basic

More information

IEEE Transformer Committee PC Distribution Transformer Monitoring - User

IEEE Transformer Committee PC Distribution Transformer Monitoring - User IEEE Transformer Committee PC57.167 Distribution Transformer Monitoring - User Mark Scarborough Electrical Engineering Consultant DuPont January 9, 2019 Transformer Types in DuPont Control power Dry-type

More information

User Information Sheet 008 : 2010

User Information Sheet 008 : 2010 User Information Sheet 008 : 2010 Formerly UIS008, July 2009 ELECTRICAL INSTALLATIONS ASSOCIATED WITH BULK LPG INSTALLATIONS 1. Introduction This Information Sheet describes some of the principles and

More information

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL SECTION 16400 AUTOMATIC TRANSFER SWITCHES 1.01 RELATED DOCUMENTS PART 1 - GENERAL A. Drawings and general provisions of Contract, including General Conditions and Division 1 Specification sections, apply

More information

CENTRAL BOARD OF SECONDARY EDUCATION SHIKSHA KENDRA, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI

CENTRAL BOARD OF SECONDARY EDUCATION SHIKSHA KENDRA, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI CENTRAL BOARD OF SECONDARY EDUCATION SHIKSHA KENDRA, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI 110092 NOTICE INVITING TENDER CBSE invites sealed Item rate tender from eligible contractors who are registered

More information

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls Specification General The Powerex Laboratory Scroll Enclosed Air Compressor System is designed to provide clean, dry air for

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Assessor: 5th floor, Ehasan Tower, 227/B, Hafez Nagar, Bakalia, Chittagong. Uttaron 22 Jul 2014 The Alliance for Bangladesh Worker Safety Page 1/19 Factory

More information

RELIABLE SOLUTIONS FOR ELECTRIFIED RAILWAY SYSTEMS

RELIABLE SOLUTIONS FOR ELECTRIFIED RAILWAY SYSTEMS Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Human photo. Can be environmental/ documentaty style or portrait of engineer. industry photo.

More information

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS

38-SDMS-03 SPECIFICATIONS FOR LV DIGITAL PANEL METERS SPECIFICATIONS FOR LV DIGITAL PANEL METERS This specification is property of SEC and subject to change or modification without any notice CONTENTS Clause Page 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE

More information

2 X 1996 Wartsila 18V mw Each 50hz HFO Generator Sets

2 X 1996 Wartsila 18V mw Each 50hz HFO Generator Sets 2 X 1996 Wartsila 18V26 5.125mw Each 50hz HFO Generator Sets The responsibility for any and all additional charges is the purchasers. 2 x WARTSILA 5 MW Power plant 2 Units of Wartsila 18V26 @ 5 MW each,

More information

COMPANY PROFILE Electrical & Instrumentation Contractor

COMPANY PROFILE Electrical & Instrumentation Contractor COMPANY PROFILE Electrical & Instrumentation Contractor Engineering I Supply I Installation I Testing I Commissioning Maintenance I Fabrication I Ship Repairing ABOUT US The year was 2003, where there

More information

POINT OBSTRUCTION CONTROLLER POC TOUCHSCREEN CONTROLLERS

POINT OBSTRUCTION CONTROLLER POC TOUCHSCREEN CONTROLLERS POINT OBSTRUCTION CONTROLLER Compliances: FAA Advisory Circular 70/7460-1L ICAO Annex 14, Volume I, Chapter 6 The controller provides the control and monitoring functions for an LED red obstruction lighting

More information

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems

elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 5/25/16 rev 6 elite Model ELN General Specification 550 W to 1.5 KW elite Model ELN Centralized Emergency Lighting Inverter Systems 550 W to 1.5 KW Systems 1.0 General General Specification This specification

More information

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT

EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT EQUIVALENT INITIAL ELECTRICAL SAFETY ASSESSMENT Hatimara Road, Barenda, Kashimpur, Gazipur, Gazipur Dhaka The Alliance for Worker Safety Page 1/18 Introduction to the Report The following report contains

More information

VACUUM CONTACTOR TYPE SVC-T 32. 7,2 kv A MANUAL FOR MOUNTING, OPERATION AND MAINTENANCE

VACUUM CONTACTOR TYPE SVC-T 32. 7,2 kv A MANUAL FOR MOUNTING, OPERATION AND MAINTENANCE VACUUM CONTACTOR TYPE SVC-T 32 7,2 kv - 400 A MANUAL FOR MOUNTING, OPERATION AND MAINTENANCE CONTENTS PAGE 1. Introduction...2 1.1 Acceptance inspection on delivery...2 2. General...2 3. Standards and

More information

Group THE ALI MIRZA GROUP OF COMPANIES CIVILCO OTHER GROUP COMPANIES

Group THE ALI MIRZA GROUP OF COMPANIES CIVILCO OTHER GROUP COMPANIES Group THE ALI MIRZA GROUP OF COMPANIES Ali Mirza Group, established in 1974, is a leading business group, incorporated. in the Sultanate of Oman with branches in Dubai. It functions in core infrastructure

More information

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION

INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION INITIAL ELECTRICAL SAFETY ASSESSMENT - EXPANSION Yunusco (BD) Ltd(Formerly Shore To Shore Textiles Ltd.) Plot# 224-233, Adamjee EPZ, Shiddirgonj, Narayangonj Siddirgonj The Alliance for Bangladesh Worker

More information

SECTION 1.02 DETAILED SCOPE OF WORK

SECTION 1.02 DETAILED SCOPE OF WORK SECTION 1.02 DETAILED SCOPE OF WORK 1.02.1 General 1.02.1.1 Introduction... 3 1.02.1.2 General description of the works... 4 1.02.1.3 Design criteria... 5 1.02.2 Public Health Services 1.02.2.1 Mains cold

More information

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES Part One General 1.01 Scope A. It is the intent of this specification to provide a medium voltage automatic transfer system. B. All components, testing and services specified and required for a complete

More information

UEE30811 Q-Tracker Work Tasks

UEE30811 Q-Tracker Work Tasks UEE30811 Q-Tracker Work Tasks UEENEEC020B Participate in electrical work and competency development activities Q-Tracker requirements: 40 hours of practical training. 1. Comply with electrical industry/enterprise

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Port of Portland Conveying Equipment Guidelines

Port of Portland Conveying Equipment Guidelines Role: Consultant for the Port Design Guidelines Port of Portland Conveying Equipment Guidelines ELEVATOR, ESCALATOR, AND MOVING WALK DESIGN OVERVIEW The Division 14 specification sections include appropriate

More information

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT

MODULAR TRACTION SUBSTATIONS CITY ELECTRIC TRANSPORT CITY ELECTRIC TRANSPORT 2 MODULAR TRACTION SUBSTATION Modular traction substation produced by PrJSC Pluton is an integrated solution for reliable power supply of electric transport catenary. Modular traction

More information

GENERAL SPECIFICATION ELECTRICAL

GENERAL SPECIFICATION ELECTRICAL GENERAL SPECIFICATION ELECTRICAL GS ELE 331 Tape trace heating 00 10/04 First issue Rev. Date Notes Contents 1. Scope...3 2. Reference documents...3 3. Environmental Conditions...4 4. Technical Requirements...5

More information

EDS SUBSTATION ELECTRICAL SERVICES

EDS SUBSTATION ELECTRICAL SERVICES Document Number: EDS 07-1119 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 07-1119 SUBSTATION ELECTRICAL SERVICES EPN, LPN, SPN This standard specifies the electrical services requirements including

More information

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA PART 1 - GENERAL 1.1 Background SECTION 26 00 10- ELECTRICAL DESIGN CRITERIA A. Brown University maintains it own campus electrical distribution system which serves the majority of the buildings and facilities

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. FLUORESCENT STRIP LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. WALL BRACKET FLUORESCENT

More information

Please refer to the drawing and notes for each particular plan view. Site Plan S1-1 Site Drawing. Electrical E1-1 Main Electrical Drawing

Please refer to the drawing and notes for each particular plan view. Site Plan S1-1 Site Drawing. Electrical E1-1 Main Electrical Drawing The property that I discuss is an actual property that I helped to build. My position was as the Facility/Project Manager while the building was under construction. I worked very closely with the Senior

More information

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection Technical Bulletin Arc Fault Monitor 4 Zones, 8 Sensors Features Four independent arc fault tripping zones 1 or 2 arc fault sensors per zone allowing up to 8 arc fault sensors per module Trip indication

More information

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED. x x x x x x OS LIGHTING S FLUORESCENT LIGHT FIXTURE, SEE LIGHT FIXTURE SCHEDULE FOR SIZE AND MOUNTING. CAPITAL LETTER DENOTES TYPE, LOWER CASE LETTER DENOTES SWITCH LEG. FLUORESCENT STRIP LIGHT FIXTURE,

More information

DESIGN GUIDELINES. THERMAL building SOLUTIONS

DESIGN GUIDELINES. THERMAL building SOLUTIONS DESIGN GUIDELINES XL-Trace LSZH Self-Regulating Heating Cables for Pipe Freeze Protection Systems THERMAL building SOLUTIONS WWW.PENTAIRTHERMAL.COM Pipe Freeze protection system overview SBS Control Panel

More information

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods 1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,

More information

ENGINE GENERATORS AND ACCESSORIES

ENGINE GENERATORS AND ACCESSORIES ENGINE GENERATORS AND ACCESSORIES GENERAL INFORMATION 1.1 This section applies to engine generators and accessories. DESIGN REQUIREMENTS 2.1 The Engineer of Record will consult with the University s Engineering

More information

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES 2.07 ELECTRICAL GENERAL DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES - 2.07 It is expected that the electrical design professional will conform to accepted good engineering design practices.

More information

Independent, accredited testing station Member laboratory of STL and LOVAG

Independent, accredited testing station Member laboratory of STL and LOVAG Independent, accredited testing station Member laboratory of STL and LOVAG TYPE TEST REPORT NO. 3096.2081034.859 GSAB Elektrotechnik GmbH Lindenstraße 23 99718 Greußen GERMANY GSAB Elektrotechnik GmbH

More information

PUMP CONTROL CENTER (PCC)

PUMP CONTROL CENTER (PCC) PART 1 SUMMARY A. In accordance with the plans and specifications, the Contractor shall provide and install a complete pre-fabricated, pre-tested ArcSafe Pump Control Center including all required equipment,

More information

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES

STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES STATEWIDE CAREER/TECHNICAL EDUCATION COURSE ARTICULATION REVIEW MINUTES Articulation Agreement Identifier: ELT 118 (2005-1) Identifier is the postsecondary course prefix followed by Plan-of-Instruction

More information

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED

FUEL OIL DAY TANKS. SST Level Controller: UL 508 LISTED FUEL OIL DAY TANKS SST Series - Engineering Submittal SST Series - Advanced Line Day Tanks Construction: UL 142 aboveground steel tank all seam welded, square, atmospheric tank of heavy gauge steel with

More information

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module FIRE ALARM CONTROL EQUIPMENT Addendum October 2006 Instructions for new style EN54-4 Power supply unit module MXLK-05 Issue 2.0 June 2007 INSTALLATION Safety Suppliers of articles for use at work are required

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM ANNEXUREIII D: FIRE PROTECTION SYSTEM SECTION ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, Installation, testing and commissioning of Analogue Addressable Fire Alarm Control panel with battery backup

More information

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual ITC 2000 HEATING CONTROL CABINET Installation & Operation Manual VTI, Incorporated 24 McMillan Way Newark, DE 19713 Phone (302) 738 0500 FAX (302) 738 6594 Revision Level 0.03 Manual No. 90003314 June,

More information

Page 1 of General

Page 1 of General Page 1 of 8 16.1 General 1. This section covers items common to sections of CSI s Master Format - Division 16. 2. Dalhousie University is certified by IBEW for new construction and all electrical contractors

More information

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7 SCR Battery Charger Product Specifications Description The is RIC Electronics premiere SCR battery charger/rectifier. The provides power to critical DC loads through a wide range of outputs and is engineered

More information

TECHNICAL SPECIFICATION FOR. 11 kv 25 KA INDOOR SWITCHGEAR INTEGRATED WITH ASSOCIATED CONTROL AND RELAY PANELS AND CONTROL DESK FOR REMOTE OPERATION

TECHNICAL SPECIFICATION FOR. 11 kv 25 KA INDOOR SWITCHGEAR INTEGRATED WITH ASSOCIATED CONTROL AND RELAY PANELS AND CONTROL DESK FOR REMOTE OPERATION TECHNICAL SPECIFICATION FOR 11 kv 25 KA INDOOR SWITCHGEAR INTEGRATED WITH ASSOCIATED CONTROL AND RELAY PANELS AND CONTROL DESK FOR REMOTE OPERATION FOR VARIOUS 33/11 KV SUBSTATIONS ( SPECIFICATION NO.DIST/MM/05/2006

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

Proposed Development at Likoni Road, Nairobi for NTSA - Electrical Installations Bills of Quantities. DESCRIPTION QTY UNIT RATE AMOUNT KSh. 28 No.

Proposed Development at Likoni Road, Nairobi for NTSA - Electrical Installations Bills of Quantities. DESCRIPTION QTY UNIT RATE AMOUNT KSh. 28 No. BILL 1 GROUND FLOOR Supply, Deliver, Install, Set to Work and Commission the Following: 1.01 Lighting point completely wired in 3x1.5mm² single core PVC insulated copper cables drawn in 20mm diameter HG

More information

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR)

INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) INITIAL ELECTRICAL ASSESSMENT REPORT (EAR) Factory Address: 687, Al-Haj Nurl Amin Sowdagar Lane CDA, R/A, Road No 20, South Agrabad Chittagong Chittagong Bangladesh 03 Apr 2014 The Alliance for Bangladesh

More information

Taking Over-cum-A/T Document For Redeployed NSN BTS Sites

Taking Over-cum-A/T Document For Redeployed NSN BTS Sites Taking Over-cum-A/T Document For Redeployed NSN BTS Sites Circle SSA BTS Site Name BTS Site ID Site Land marks Type of Site BSC SACFA ID Date NSN Rep. Name Ericsson Rep. Name Haryana Redeployed Sharing

More information

SCHEDULE OF RATES SHEET PRELIMINARIES

SCHEDULE OF RATES SHEET PRELIMINARIES Page : 1 PRELIMINARIES 1 CONTAINER BUDGET ALLOWANCE 1,100.00 1,100.00 1 SUPERVISION 3,900.00 3,900.00 1 ACCOMMODATION 5,390.00 5,390.00 1 TRAVEL ALLOWANCE 7,800.00 7,800.00 Sub- 18,190.00 18,190.00 Page

More information

AQ 100 Series. Arc Flash Protection System

AQ 100 Series. Arc Flash Protection System AQ 100 Series Arc Flash Protection System THE CONSEQUENCES OF AN ARC FAULT IN HIGH VOLTAGE SWITCHGEAR THE CONSEQUENCES OF AN ARC FAULT IN OIL-FILLED SWITCHGEAR Arc Phenomena Arc Phenomena Arc fault - facts

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

+91-8048761905 Volt-On Engineering http://www.volt-on.in/ Our organization engaged in manufacturing, supplying, exporting and providing services of a Automation Products and Panels in South India. These

More information

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems SECTION 26 05 54 IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Labels. 3. Wire markers. 4. Conduit markers. 5. Permanent Marking. 6. Underground

More information

NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies

NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies Version:- 2.0 Date of Issue:- May 2015 Page 1 of 17 NPS/003/030 Technical Specification for Transformer and Switchgear Cable Boxes and their associated Bushing Assemblies 1. Purpose The purpose of this

More information

Ho-Chunk Gaming THUNDERBIRD ENGINEERING, INC. MILWAUKEE: (414) MADISON: (608)

Ho-Chunk Gaming THUNDERBIRD ENGINEERING, INC. MILWAUKEE: (414) MADISON: (608) Ho-Chunk Gaming POWER SYMBOLS X ELECTRICAL PANEL - REFER TO DRAWINGS FOR WIDTH AND PANEL SCHEDULES PANEL NAMING: XXP-#X: DENOTES PANEL FUNCTION: L = LIGHTING P = GENERAL POWER E = EMERGENCY S = OPTIONAL

More information

Products and Portfolio 01 Relay Panels Control Panels Special Panels

Products and Portfolio 01 Relay Panels Control Panels Special Panels Contents Products and Portfolio 01 Relay Panels Control Panels Special Panels Standard Features 11 Manufacturing Facilities 12 Processes and Activities 13 Quality Control and Assurance 15 SCADA System

More information

NPS/003/025 Technical Specification for Fault Throwers

NPS/003/025 Technical Specification for Fault Throwers Version:- 1.0 Date of Issue:- September 2015 Page 1 of 74 NPS/003/025 Technical Specification for Fault Throwers 1. Purpose This document is the technical specification for Fault Throwers for use on the

More information

Factory Equipment Testing of Single Lift Substation

Factory Equipment Testing of Single Lift Substation Factory Equipment Testing of Single Lift Substation Presented by: Kurt Vosburg & Ronak Goswami IEEE CED Houston Chapter November 17-18, 2015 Objective This technical presentation will discuss various aspects

More information

ELECTRICAL INSTALLER THEORY EXAMINATION. 14 November 2015 QUESTION AND ANSWER BOOKLET

ELECTRICAL INSTALLER THEORY EXAMINATION. 14 November 2015 QUESTION AND ANSWER BOOKLET Candidate Code No. EIN 11 For Board Use Only Result Date Int Result Date Int ELECTRICAL INSTALLER THEORY EXAMINATION 14 November 2015 QUESTION AND ANSWER BOOKLET Time Allowed: Three hours INSTRUCTIONS

More information

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear

This is a preview - click here to buy the full publication. High-voltage switchgear and controlgear IEC/PAS 62271-109 Edition 1.0 2002-07 High-voltage switchgear and controlgear Part 109: Alternating-current series capacitor by-pass switches PUBLICLY AVAILABLE SPECIFICATION INTERNATIONAL ELECTROTECHNICAL

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SECTION POWER SUPPLIES AND DISTRIBUTION

SECTION POWER SUPPLIES AND DISTRIBUTION SECTION 17460 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for Power Supplies and Power Distribution for Station communications. 1.02 REFERENCE STANDARDS A. American National Standards

More information

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY

NATIONAL ELECTRICAL CODE (NEC) & NFPA 70E ARC FLASH ELECTRICAL SAFETY A new twist on the National Electrical Code - a practical application workshop. If you sign up in this class, prepare to work! Day 1: Fundamentals of OSHA requirements for performing electrical work -

More information