1 FIRE PROTECTION 1 G.I.PIPES Supplying, installing, testing and commissioning of G.I Pipes confirming to IS 3589 Pt - I Heavy grade with painting, suitable type of supports, anchor fasteners, bolts nuts (Galvanised), clamps, "U" bolte, malleable specials such as Reducers,Tees, elbows, flanges. Including cutting, Welding, fixing in / on walls, ceiling by using suitable supports etc, as per drawings. The quoted rate shall also include for chasing / chipping walls, making bore holes in walls / floor and making them good with filler material and finished in cement morter etc. a. 150mm nominal dia Rmts b. 100mm nominal dia Rmts c. 80mm nominal dia Rmts WRAPPING & COATING Supplying, installing, testing and commissioning of 4mm thick pypekote for Sq.mtrs underground pipes. Signature of Bidder 1 of 11 EPI
2 3 EXTRENAL HYDRANT Supplying, installing, testing and commissioning of yard hydrant comprising of the following, Single headed hydrant valve as per IS 5290, made of gunmetal with 63 mm dia instantaneous outlet of 80 mm dia fanged inelt,blank caps, chain and hand wheels etc. No INTERNAL HYDRANT Supplying, erecting and commissioning of Landing Hydrants comprising of the following in the Fire duct; Single headed hydrant valve as per IS 5290, made of gunmetal with 63 mm dia Hose reel drum of swinging type with 19mm dia Rubber braided hose of 36M. length with Gate valve ( upstream) and Shut off nozzle, complete. 5 BUTTERFLY VALVES Supplying, Installing, testing and commissioning CI butterfly valves ( PN 16) slim seal standard lever operated type confirming to IS Standard with required flanges, nuts, bolts etc. complete. No 6.00 No a. 150mm nominal dia No 8.00 b. 100mm nominal dia No 6.00 Signature of Bidder 2 of 11 EPI
3 c. 80mm nominal dia No AIRRELEASE VALVE Supplying and fixing approved make 25mm dia. Automatic air release valve 6 CIVIL WORKS Exacavation up to 1.0 mts. in depth, for laying pipes upto 150mm dia. Including forming bottom surface to required level, refilling the trenches with selected excavated earth around th pipe in layers of 150mm thick, watering, consolidating. Quoted price inclusive of disposing off / Carting away the surplus earth out side the site to a dump yard acceptable local bodies or as directed by the site engineer with a lead of 300 mts. etc. complete. No 6.00 a. Excavation in all kinds of soil Rmts Hard Rock:Upto 300 mm Normal soil. 300 b. mm to Below 1.5 mtr Hard rock 7 RCC HUME PIPE Supply and installation of RCC hume pipes of 300 mm dia & NP 2 Class with collars for road / below floor crossing of Fire water pipes. The rate shall includes excavation, PCC ( 1:4:8 100 mm thick)bed and ends shall be closed with Brick masonry work as directed by site engineer Mtrs Mtrs Signature of Bidder 3 of 11 EPI
4 8 VALVE CHAMBERS Supply & Construction of valve chamber with 230 mm Brick masonry wall with best quality TM bricks & CM 1:4,on a PCC 1:4;8 bed of 100 mm thick The wall shall be plastered internally smooth in CM 1:3, water proofing as required and externally rough plastered with sponge finish, including curing. The chamber shall be provided with M.S. 6 / 8 mm thick plate fabricated top cover in leaves with neccessory hinges and locking arrangement. The size of the chamber shall be 1200mm x 1200mm x1500mm in depth. No PCC PEDESTALS Supply and construction of PCC (1:2:4) pedastals / supports for Under ground / above ground pipes. Quoted rate shall inclusive of excavation ( if required ), chipping / chasing, shuttering, plastering ( if required) etc. complete. Cum 9.00 Note: The proposed Fire System shall be integrated seamless with the Fire Alarm system proposed for Package I,II,III,IV & V Signature of Bidder 4 of 11 EPI
5 10 ADDRESSABLEFIRE ALALRM PANEL Supply, Erection, Testing and Commissioning of 1Microprocessor based addressable fire alarm control panel with built in loop cards. FACP shall have capacity to look upto minimum of 198 devices per loop i.e.99 detectors & 99 modules, further shall be designed with 25% spare capacity towards future expansion FACP shall have 2 x 40 character LCD alphanumeric display with backlight, fully (100%) programmable disablement. Test, sounder fault, delayed mode, relays disabled, earth fault, system/cpu fault, sounder disabled. Alarm silenced, supply fault, power etc. It shall be provided with required capacity of maintainable free sealed acid batteries to provide 48 hours ( Including 30 mins in alarm condition) of indications with a maximum of 200 software zones. Signature of Bidder 5 of 11 EPI
6 FACP Loop shall have built- in networking feature i.e. to form networking on LAN using TCP/IP converter Interface. It shall also have built -in feature of automatic telephone dialer( 4 telephone/mobile nos.) with facility to pass pre- recorded message of up to 20 sec. System shall be designed as per the technical specification and shall comply to EN 54/IS 2189/UL Standards. a. Five loop with one card Analog addressable fire alarm networking control panel with built in one loop card, with built in 10 TCP/IP Converter module & Auto-tel dialer No 1.00 b. panel with Two loop card Analog addressable fire alarm networking control panel with built in two loop cards, with built in TCP/IP Converter module & Auto-tel dialer No RS 485 Network Communication Module No RS 232 Network Communication Module No 1.00 Signature of Bidder 6 of 11 EPI
7 13 ADDRESSABLE PHOTOELECTRIC SMOKE DETECTOR Supply, Erection, Testing Commissioning of Addressable Photoelectric smoke detector with multiple sensitivity( adjustable at site) levels, programmable for timed automatic sensitivity selection with base, Junction box and other accessories as required and Detectors shall be UL listed, No ADDRESSABLE HEAT DETECTOR Supply, Erection,Testing and Commissioning of Addressable combination of fixed temperature/ rate of rise heat detector of Grade I(20 second time instant) with LED indicator, mounting base and accessories etc., complete. No Signature of Bidder 7 of 11 EPI
8 15 ADDRESSABLE BEAM DETECTOR Supply, Erection,Testing and Commissioning of Analogue Addressable BEAM selector along with the required mounting accessories. It shall be operating on light obscuration principle utilizing Infra red optical beam with combined transmitter and receiver unit on one side and reflector on the other side. It shall be loop powered further shall sit on the same loop with other addressable devices(conventional detector with module shall be rejected).it shall comply to EN54/IS2189/ UL standards No ADDRESSABLE ELECTRONIC HOOTER Supply, Erection,Testing, Commissioning of Electronic Hooter giving output of 65db maximum or 5 db above any noise tends to exist. The hooter shall be of wall mounted type. The rate shall include for mounting accessories, etc., complete. As per IS No Signature of Bidder 8 of 11 EPI
9 17 ADDRESSABLE MANUAL CALL POINT Supply, Erection,Testing and Commissioning of Addressable manual call station with necessary break glass hammer with chain and push button. The manual call station shall be of wall mounted with necessary mounting and fixing arrangement and etc., complete. As per IS No CABLES Supplying, laying, testing and commissioning of 1100V grade FIRE RESISTANCE LOW SMOKE multicore, round type, insulated, sheathed, flexible copper conductor control cables with Including necessary end terminations with copper lugs, junction box, crimping identification tags at each end etc.,) 2 core x 1.5 Sq.mm Copper Un armoured cable Rmt CONDUIT Supply and laying of 20 SWG MS conduit painted with 2 coats of primer and two coats of red enamel paint, embedded in slab/run on wall/wall chases/on false ceiling etc., with pull wires and necessary conduit accessories. Rmt Signature of Bidder 9 of 11 EPI
10 20 CONTROL MODULE Analogue Control module for integrated to master panel(if required) shall be capable of providing provision for zone panel 21 FAULT ISOLATOR MODULE Analogue Addressable Fault isolator module capable of monitoring shorted loop circuit and automatically restore communications when shorted conditions are corrected No 4.00 No DRY CHEMICAL POWDER TYPE - 5KG TYPE Dry chemical powder type fire extinguisher of 5 Kgs. Capacity, with initial filling in brand new cylinder with powder coated finish, fitted with Gun metal union, high pressure CO2 gas cartridge, discharge hose, wall mounting bracket etc. complete, confirming to IS:2171. No CARBON DIOXIDE TYPE - 4.5KG Carbon-di- oxide type fire extinguisher of 4.5 kgs. Capacity, CO2 gas filled in brand 24 MECHANICAL FOAM TYPE - 9 LTRS Mechanical foam type fire extinguisher of 9 Ltrs. Capacity, with initial filling in brand 23 FIXED CO2 SUPRESSION 45 kgs manually operated fixed CO2 Supression system with about 36 meter hose with about extension type applicator complete set confirming to IS standard. No No No 3.00 Signature of Bidder 10 of 11 EPI
11 24 50 LTRS WATER MIST Water Mist of 50 Litres trolley with 6 litres, 300 bars steel cylinder having 5 Mtrs hose length. No FIRE BUCKET - 9 LTRS 25.1 Fire buckets round bottom type enamel painted, white inside & Red out side and No Fire bucket stand fabricated by MS angles to install 2 Nos. of buckets. No 2.00 GRAND TOTAL Signature of Bidder 11 of 11 EPI
PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM
ANNEXUREIII D: FIRE PROTECTION SYSTEM SECTION ADDRESSABLE FIRE DETECTION AND ALARM SYSTEM Supply, Installation, testing and commissioning of Analogue Addressable Fire Alarm Control panel with battery backup
More informationSUPPLY,INSTALLATION,TESTING AND COMMISSIONING OF SPRINKLER SYSTEM AND FIRE ALARM SYSTEM FOR AIR INDIA LIMITED AT SHAMSHABAD, HYDERABAD.
i 1 a SPRINKLER SYSTEM M S Pipes confirming to IS 1239 Pt - I Heavy grade with painting, suitable type of supports malleable srewed specials such as M S Reducers,Tees, elbows, flanges. Including cutting,
More informationBOQ FOR FIRE HYDRANT & FIRE ALARM SYSTEM AT T.I.E
A 1 2 4 PUMP HOUSE: BOQ FOR FIRE HYDRANT & FIRE ALARM SYSTEM AT T.I.E Supply, erection,testing & commissioning of Single stage, end suction / back pull-out type motor driven Jockey Pump of capacity 10.8
More informationENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) PRICED BILL OF QUANTITIES
NAME OF PROJECT : CONSTRUCTION OF SUPER SPECIALITY HOSPITAL FOR GOVT. RAJAJI MEDICAL COLLEGE, MADURAI, TAMIL NADU - FIRE PROTECTION & FIRE ALARM SYSTEM. NIT NO. SRO/MKT/TH/290 dated 03.07.2014 Item no.
More informationGAS FLOODING SYSTEM FOR CIFF AT BASEMENT
CONSTRUCTION OF BUILDINGS FOR LABORATORIES AND ASSOCIATED FACILITIES INSTEM BANGALORE SCHEDULE OF QUANTITIES FOR (EQUIPMENT ROOM 3 & 4) Sl.No. Description Unit Quantity Rate (in INR) in figure HFC-227ea
More informationTENDER NOTICE. Kolhapur Zilla Sahakari Dudh Utpadak Sangh Ltd. B-1, M.I.D.C., Gokul Shirgaon, Tal. Karveer, Dist. Kolhapur
TENDER NOTICE Sealed Tender offers are invited for supply, installation & commissioning of Fire Hydrant System at our Gokul Dairy Project Complex at Gokul Shirgaon Kolhapur. Only contractors having valid
More informationAnnexure - 1. Detectors: Fire Alarm Control Panel :
Item 1. Supply Part This Specification includes Supply, Warranty, Installation, Testing and Commissioning and integration of the Fire Alarm System mainly consisting of the Fire Alarm Control Panel (FACP),
More informationRequest for quotation (RFQ) for goods/services
Request for quotation (RFQ) for goods/services Firefighting equipment s and alarm system for UNICEF Warehouse Khartoum - Soba RFQ No: SDPC/89588/SERVICES/RFQ-135 Request for quotation (RFQ) for (Firefighting
More informationTECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATION FOR FIRE DETECTION & ALARM SYSTEM INCLUDING FIRE EXTINGUISHERS GETCO/ENGG/TS/
More informationFollowing are the systems proposed as per NBC & Local Fire Authority:
1. OBJECTIVES AND STRATEGIES OF THE FIRE PROTECTION DESIGN This report describes the design parameters, system requirements of fire protection system for mixed occupancy (Assembly + Business) building
More information1 NOS. 25mm x 4 mm thick with PVC sleeving e) 1Set, RYB, indicating lamps & CT
A MAIN PANEL/DB 1 Supply and Installation of main LT panel, floor mounted, front operated dead back, totally enclosed vermin proof, indoor, non drawout, cubicle type power dist. panel fabricated out of
More informationCLIENT DOCUMENT VOLUME I
CLIENT DOCUMENT VOLUME I A. TECHNICAL SPECIFICATION FOR FIRE PROTECTION WORKS B. CLIENT CONDITION FOR RETENTION MONEY Signature of Bidder with seal Page 1 of 28 EPI TECHNICAL SPECIFICATIONS FOR FIRE PROTECTION
More informationHEAD OFFICE, SECURITY DEPARTMENT
BANK OF INDIA HEAD OFFICE, SECURITY DEPARTMENT RATE TO BE QUOTED BY THE VENDOR Sr. no. Description Make Model Unit Rate Tax Total Amount I BURGLAR ALARM SYSTEM A Burglar/Intruder Alarm System.B Control
More informationTRIMAX ASIA ENGINEERING & CONSTRUCTION (PG U )
TRIMAX ASIA ENGINEERING & CONSTRUCTION (PG0176866-U ) FIRE PROTECTION EQUIPMENTS PARTS CATALOGUE TRIMAX ASIA ENGINEERING & CONSTRUCTION No. 24, Jalan Pantai, 12000 Butterworth, Penang, Malaysia. Fax: +6
More informationDRY POWDER FIRE EXTINGUISHER (Stored Pressure) ABC TYPE - PORTABLE
DRY POWDER FIRE EXTINGUISHER (Stored Pressure) ABC TYPE - PORTABLE Capacity: 1,, 5, 10 Kgs UFS dry powder type extinguishers are designed for protection of light and ordinary hazards. Suitable for A, B,
More informationPROFESSIONAL SUPPLIER
PROFESSIONAL SUPPLIER FOR FIRE-FIGHTING EQUIPMENT IRON MAN INDUSTRY LIMITED Sprinkler Small orifice, standard and quick response, spray sprinkler Designed for use in light hazard occupancies Requires less
More informationHRS035-MS-022-RD 22 (559mm) 19mm x 30m 310mm Fixed Manual. HRS037-GI-019-RD 19 (483mm) 19mm x 36m 350mm Swing Manual
FIRE HOSE REEL CertIFIeD to Bs en 671-1: 1995 Certification No: Ps005704 BRITISH STANDARDS INSTITUTION APPROVAL FIRE HOSE REELS CERTIFIED TO BS EN 671 LICENCE NO. KM 51857 Certified Product AUSTRALIAN
More informationWalk in Steam Curing Chamber for Concrete Application. Detailed Working Specifications
Detailed Working Specifications The Chamber with extremely high fabrication standard, high quality of finish, which matches the performance with emphasis on reliability and economy of use. The use of the
More informationInstallation, Operating and Maintenance Manual
STATUS ZONES CONTROLS FIRE FAULT DISABLED FIRE 1 2 3 4 5 6 7 8 TEST FAULT DISABLED 1 5 BUZZER SILENCE RESET 1 2 TEST 2 6 LAMP TEST 3 SUPPLY 3 7 SYSTEM FAULT 4 8 SOUNDERS ACTIVATE/ SILENCE 4 FAULTS INSTRUCTIONS
More informationThe supplier and installer of the system should be approved by the local civil defence authority.
ANALOGUE ADDRESSABLE FIRE ALARM SYSTEM 1. Scope of Work The contractor shall supply, install, test and commission a modern Analogue Addressable Fire Detection and Alarm System of an approved manufacturer
More informationTECHNICAL AND USER REQUIREMENTS FOR PERSONAL ALERT SAFETY SYSTEMS
Centrum Naukowo Badawcze Ochrony PrzeciwpoŜarowej (Scientific and Research Centre for Fire Protection) Nadwiślańska 213, 05-420 Józefów, Poland Telephone (+48) 22 789 11 11 Fax.: (+48) 22 769 33 45 e-mail:
More informationTECHNICAL AND USER REQUIREMENTS FOR FIRE-FIGHTING PRESSURE HOSES FOR FIRE-FIGHTING PUMPS
Centrum Naukowo Badawcze Ochrony PrzeciwpoŜarowej (Scientific and Research Centre for Fire Protection) Nadwiślańska 213, 05-420 Józefów, Poland Telephone (+48) 22 789 11 11 Fax.: (+48) 22 769 33 45 e-mail:
More informationConsultant Specification AGILE Wireless Fire Detection System
Contents Scope of Work... 2 The EN54 Part 2 & 4 Fire System... 2 Standards... 2 Wireless Intelligent Photoelectric Smoke Detector Specification... 4 Wireless Intelligent Thermal Heat Detector Specification...
More informationTR CASSETTE AC 1 NOS TR CASSETTE AC 1 NOS. Rate in words : TR HIGH WALL (3 star rated) 2 NOS.
BILL OF QUANTITIES FOR AIR CONDITIONING WORKS S.N. DESCRIPTION QTY UNIT VENTILATION & AIR CONDITIONING A HIGH SIDE WORKS (SUPPLY OF EQUIPMENTS) 1 DX TYPE SPLIT AIR-CONDITIONERS: Supply of Aircooled Split
More informationZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL
ZXe INTELLIGENT MULTI PROTOCOL FIRE ALARM CONTROL PANEL PRODUCT Specification FEATURES Designed To Meet The Requirements Of EN54 Expandable From 1 To 5 Loops As Standard A Variety Of Networking Options
More informationfour Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1
four Vigilon Compact Analogue Addressable Fire Detection & Alarm System 4/1 ANALOGUE FIRE DETECTION VIGILON COMPACT FEATURES & BENEFITS four Keep it Simple All Vigilon devices connect onto the same 2
More informationSPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION
1. GENERAL SPECIFICATION 1.1 The contractor shall provide an Intelligent AlarmLine Linear Heat Detection System to perform the following functionality: A. Fire Alarm, Supervisory and Trouble-Event Initiation
More informationIntelligent Addressable Fire Alarm System
Intelligent Addressable Fire Alarm System Company Profile The Company established in 2003, is manufacturing security system devices with the brand name DEKON Security Technologies for the exclusivity of
More informationPNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel
PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel INSTALLATION, OPERATION AND MAINTENANCE MANUAL Version: CN-PM-1000.VER1.1-12/2012 EN54 INFORMATION In accordance with EN 54-2 clause 13.7, the maximum
More informationNAME OF WORK - IIM AHMEDABAD - LIBRARY BOQ OF ELV WORKS Item #
NAME OF WORK - IIM AHMEDABAD - LIBRARY BOQ OF ELV WORKS Description Unit Qty Rate 1 INFORMATION & COMMUNICATIONS TECHNOLOGY (DATA) 1.1 Supply & laying of 25 mm dia. Open/conceal manner medium gauge rigid
More informationTABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2
Division 28 ELECTRONIC SAFETY AND SECURITY TABLE OF CONTENTS 28 0000 GENERAL... 2 A. DEFINITIONS...2 28 3111 DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2 A. DESIGN REQUIREMENTS...2 B. CONSTRUCTION REQUIREMENTS...2
More informationSystem 800 Addressable Fire Detection & Alarm System
SECTION 5: page 1 Section 5: System 800 Addressable Fire Detection & Alarm System SECTION 5: page 3 10 reasons to specify 800 1 Plug and Play A user friendly panel not requiring special software tools
More informationCENTRAL BOARD OF SECONDARY EDUCATION SHIKSHA KENDRA, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI
CENTRAL BOARD OF SECONDARY EDUCATION SHIKSHA KENDRA, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI 110092 NOTICE INVITING TENDER CBSE invites sealed Item rate tender from eligible contractors who are registered
More information1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.
FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment
More informationSmoke Detector Activation of any smoke detector shall start the alarm verification mode.
Description: The purpose of the section is to provide the UMCP Design Standards for the design and implementation of Fire Alarm Systems at the UMCP campus. Related Sections: TBD Effective Date: July 10,
More informationCODESEC FIRE ALARM SYSTEMS. security technologies
CODESEC FIRE ALARM SYSTEMS security technologies AA402 ADRESSABLE FIRE ALARM CONTROL PANEL AA402 Electronic Addressable Intelligent Fire Alarm Control Panel Onboard one loop, 250 nodes per loop, Metal
More informationSupply & Installation of Fire Protection System at STPI- Nashik. Tender No. STPI/P/PUR/07/14-15 Date Signature of Bidder
Software Technology Parks of India - Pune (An Autonomous Society under Govt. of India, Ministry of Communications & Information Technology, Department of Electronics and Information Technology), Plot no.p-1,
More informationDesign and Supply of Fire Equipments. External Fire Fighting Systems.
Design and Supply of Fire Equipments External Fire Fighting Systems INTRODUCTION Sheyas fire Services is one of the progressive firms in the field of Fire Fighting Equipment s and Consulting Services,
More informationPROJECT: NITESH PALO Bangalore FIRE SAFETY MEASURES
PROJECT: NITESH PALO ALTO @ Bangalore FIRE SAFETY MEASURES System Description 1 Firewater pumping system 2 Wet riser system and hose reel system. 3 Automatic sprinkler system 4 Yard hydrant system 5 Pressurization
More informationSmoke and Fire Curtains
Smoke and Fire Curtains NFPA UL Datasheet firecurtaintech.com SMOKE AND FIRE CURTAINS Fire Curtain Technologies distributes a wide range of fire and smoke protective curtains to protect every type of building
More informationTender document for Supply/ Installation of New Fire extinguishers & Refilling TENDER NOTICE
Relationship beyond banking Zonal Office, Bhopal Zone Bank of India Bhawan Jail Road, Arera Hills BHOPAL - 462011, MP. Phone. 0755-2764698 zo.bhopal@bankofindia.co.in ZOBDSDSGNFE TENDER2013-14 Dated 05.11.2013
More informationSBI INFRA MANAGEMENT SOLUTIONS PVT.LTD. HEAD OFFICE-GROUND FLOOR RAHEJA CHAMBERS, FREE PRESS JOURNAL MARG, NARIMAN POINT, MUMBAI-21
SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD. HEAD OFFICE-GROUND FLOOR RAHEJA CHAMBERS, FREE PRESS JOURNAL MARG, NARIMAN POINT, MUMBAI-21 PART B : PRICE BID TENDER FOR: PROPOSED AIR CONDITION WORKS OF SHIFTING
More informationBasic Fire Alarm SystemTraining. Arman Alnasar
Basic Fire Alarm SystemTraining Arman Alnasar Agenda Introduction to Esser 10 min Product Overview 5 min Control Panels 30 min Detectors 20 min Field Devices Alarm Devices 20min 10 min Management & Interface
More informationADR Analog Addressable Fire Alarm Control Panel. Technical Manual. Control Panels. 3000En. En pdf
Control Panels Analog Addressable Fire Alarm Control Panel Technical Manual TELEFIRE FIRE & GAS DETECTORS LTD PO Box 7036 Petach Tikva 49250 Israel Tel: 972 3 970 0400 Fax: 972 3 921 1816 email: Web: info@telefire.co.il
More informationIGD.CO.UK
APPLICATION DATA SHEET S p e c i f i c a t i o n 2 SO22 WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700+ D e t e c t o r Website: C o n t r o l P a n e l - Wall mounting or 19 Rack
More informationFIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.
15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.
More informationTable-1: Clarifications and modification in tender specifications based on Pre-bid meeting discussion
Table-1: Clarifications and modification in tender s based on Pre-bid meeting discussion Sr. Ref Page. 1 4 Clause Site Preparation and Partitions walls 2 11 SLD 3 18 Batteries 4 18 Batteries 5 32 to 34
More informationPROJECT: IIT MADRAS RESEARCH PARK-CHENNAI, TECHNICAL SPECIFICATION FOR FIRE ALARM SYSTEM TENDER
PROJECT: IIT MADRAS RESEARCH PARK-CHENNAI, TECHNICAL SPECIFICATION FOR FIRE ALARM SYSTEM TENDER INDEX S NO DESCRIPTION 1 Introduction 2 Standards & Regulations 3 Fire Detection System 1.0 INTRODUCTION
More informationMODUL-R FIRE ALARM CONTROL PANELS. MR-2900/MR-2920 Addressable Fire Alarm Control Panels MEA. Features. Description
MODUL-R FIRE ALARM CONTROL PANELS MR-2900/MR-2920 Addressable Fire Alarm Control Panels Description MR-2900 Fire Alarm Control Panel The MR-2900 fire alarm system control unit is the heart of a sophisticated
More informationSBI INFRA MANAGEMENT SOLUTIONS PVT. LTD.
SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD. (A Wholly Owned Subsidiary of SBI) CIRCLE OFFICE: 4TH FLOOR, SBI LOCAL HEAD OFFICE III/1-PANDIT J N MARG, KHARAVELA NAGAR BHUBANESWAR, ODISHA-751001 Part-II PRICE
More informationFIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS
VALOUR COMMUNITY CENTRE FIRE ALARM SYSTEM Section 28 00 00 GYMNASIUM ADDITION & RENOVATION Page 1 of 3 28 00 00 FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS 1.2 SCOPE 1. The specification covering the General
More informationANNEXURE-III BUILDING MANAGEMENT SYSTEM (BMS) BMS Total ANNEXURE-III. SL DESCRIPTION OF ITEM UNIT QTY Rate in figures Rate in words AMOUNT
PRICE BID Name of the Project : Supply, Installation, Testing and Commissioning of BMS, PA, CCTV, AVS, Access Control System for Construction of Partially completed Building at Centre for Development of
More informationDATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D
DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION Fike s CyberCat 254 (P/N 10-066) is a state-of-the-art true intelligent digital peer-to-peer modular fire alarm control system.
More informationAPPLICATION DATA SHEET
APPLICATION DATA SHEET S p e c i f i c a t i o n WWW.-..UK Control Systems Transmitters Sensors Accessories TOCSIN 700 D e t e c t o r C o n t r o l P a n e l Wall mounting 24V DC or 110/230vAC operation
More informationA. Section Common Motor Requirements for HVAC Equipment: Fan motors.
SECTION 233516 - ENGINE EXHAUST SYSTEMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Exhaust fans. B. Ductwork and duct fittings. C. Inlet fittings. D. Accessories. E. Carbon monoxide detectors. 1.2 RELATED
More informationConventional Releasing Control Panel
s Data Sheet Fire Safety Products Conventional Releasing Control Panel Pre-Action Deluge Agent-Releasing Fire System Model TXR-320 Remote configurable Up to two (2) hazard areas Operable with the following:
More informationFMR Installation Instructions. Addressable Fire System Controller
FMR-7033 EN Installation Instructions Addressable Fire System Controller EN 2 FMR-7033 Installation Instructions Contents Contents Contents...2 1.0 Introduction...3 2.0 Description...3 3.0 Device Mounting...3
More informationFIRE EXTINGUISHERS. Chapter 2. - Co2 Fire Extinguisher - Dry Foam Fire Extinguisher - Foam Fire Extinguisher - Portable Foam Applicator
FIRE EXTINGUISHERS Chapter 2 - Co2 Fire Extinguisher - Dry Foam Fire Extinguisher - Foam Fire Extinguisher - Portable Foam Applicator CO2 FIRE EXTINGUISHER - Dielectric test at 35000 V at 1mtr distance.
More informationID50series. intelligent fire alarm panels
ID50series intelligent fire alarm panels features LPCB approved to EN54 parts 2 and 4 One loop capacity (99 sensors and 99 modules) 16 fire zones, 16 non fire zones Supports NOTIFIER advanced range of
More informationPWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R
Region Project Page 1 PART 1 - GENERAL 1.1 REFERENCES.1 CAN/ULC-S524-2006, Standard for the Installation of Fire Alarm Systems..2 CAN/ULC-S525-2007, Audible Signal Device for Fire Alarm Systems..3 CAN/ULC-S526-2007,
More informationAddressable Fire Alarm Control Panel
PRODUCT SPECIFICATION XR2400F Addressable FACP Addressable Fire Alarm Control Panel Description The DMP XR2400F Addressable Fire Alarm Control Panel is an expandable Fire Alarm Control with built-in DACT
More informationAlgo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS)
Algo-Tec 6300 INTERACTIVE DIGITAL ADDRESSABLE FIRE CONTROL SYSTEM (1-4 LOOPS) INSTALLATION MANUAL Protec Fire Detection PLC, Protec House, Churchill Way, Nelson, Lancashire, BB9 6RT. Telephone: +44 (0)
More informationCalling for Quotations
Calling for Quotations 01012012 AMC FOR FIRE HYDRANT SYSTEM Frequency : Half-Yearly Once QUOTATION FOR AMC FOR FIRE HYDRANT SYSTEM Sl. No Item Descriptio n Qty U.O.M Unit Rate Amo unt 1 Servicing of Jockey
More informationINDIAN INSTITUTE OF TECHNOLOGY KANPUR
INDIAN INSTITUTE OF TECHNOLOGY KANPUR Tender tice. 119/IWD/ED/644 SCHEDULE OF QUANTITY Name of work: Electrical work for: Part-A: Rewinding, overhauling and repairing of ceiling fan and exhaust fan installed
More informationUEE30811 Q-Tracker Work Tasks
UEE30811 Q-Tracker Work Tasks UEENEEC020B Participate in electrical work and competency development activities Q-Tracker requirements: 40 hours of practical training. 1. Comply with electrical industry/enterprise
More informationFIREBETA EXTINGUISHING CONTROL PANEL (ECP)
F I R E D E T E C T I O N A N D C O N T R O L FIREBETA EXTINGUISHING CONTROL PANEL (ECP) Three versions: 2 areas of detection and 1 area extinguishing 4 areas of detection and 1 area extinguishing 4 areas
More informationLaserFOCUS VLF-250 Engineering Specification
Vision Fire & Security LaserFOCUS VLF-250 Engineering Specification May 2004 Part Number 20296 LaserFOCUS VESDA 2 VESDA LaserFOCUS Contents Scope...4 Description...4 General...4 Approvals...4 Codes, Standards
More informationCONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3
CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3 2.1 Electrical Specifications... 3 2.2 Communication Loop Parameters... 3 2.3 Dimensions...
More informationEnclosure 4- RISK ASSESSMENT
Enclosure 4- RISK ASSESSMENT RISK ASSESSMENT Risk is a potential that a chosen action or activity will lead to a loss of human or property. Risk assessment is a step for Risk Management. Risk assessment
More informationCHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM
CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION Fike s Cheetah Xi (P/N 10-068) is a state-of-the-art true intelligent digital peer-topeer modular suppression control system. It is ideal for
More informationMulti-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.
Fire Sentry Corporation (FSC) 593 Apollo Street Tel.: 714-671-1100 Brea, California 92821 Fax: 714-671-5821 Multi-Spectral, Digital, Infrared Electro-Optical FSC Model No. s FS10-R and FS10-A Unitized,
More informationWhy choose Fireray? Why use a Beam Smoke Detector? Product Range.
Range Brochure Why use a? Beam smoke detectors are the wide area smoke detection technology of choice, offering both excellent detection and value for money. With a high area of coverage per unit (as high
More informationThe EN54 Part 2 & 4 Fire System
Scope of work: To design, supply, install and commission an Analogue Addressable Fire Alarm Control System in accordance with the details specified herein and in accordance with supplied drawings The EN54
More informationSECTION FIRE ALARM SYSTEMS
SECTION 28 3100 PART 1 -GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this
More informationFire detection and alarm
Fire detection and alarm Aesthetic Install all cabling and cable containment neatly and unobtrusively, meeting the highest electrical industry installation standards. Neatly lay and securely fix cables.
More informationCHECKFIRE 210 Detection and Actuation System
DATA SHEET CHECKFIRE 210 Detection and Actuation System Features Supervised power, detection, release, and communication circuits Display module with LED system status indicators Adjustable mounting bracket
More informationZXSe Range Data Sheet
ZXSe Range Data Sheet Analogue addressable fire alarm control panel Product Overview The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and
More informationSECTION FIRE ALARM SYSTEMS
SECTION 16721 FIRE ALARM SYSTEMS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. The general provisions of the contract including General and Special Conditions and General Requirements shall apply to all work
More informationThe system is expanded via the RCC network with each RCC capable of passing information to and from up to 31 detection or output devices.
FireCell Radio Hub Fully addressable Wireless activation Third party approved (EN54) 2-way radio communication Loop powered Diagnostics port Range in excess of 150 metres Overview The model FCX-500-001
More information+91-8048763768 Cease Fire & Electrical Services http://www.ceasefireengineers.com/ We are the supplier, trader and service provider of fire alarm equipment, fire suppression system, fire detection system,
More informationIntelligent addressable fire alarm control panel
Intelligent addressable fire alarm control panel Input current consumption: Panel rating: Batteries: Networking and Interfaces Panel to panel communication: Number of panels: Interface port: System capacity
More informationZM2 OPERATING AND MAINTENANCE INSTRUCTIONS
ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status
More informationAND ARCHITECT SPECIFICATIONS
PXL Conventional Zone Fire Alarm Control Panel ENGINEER AND ARCHITECT SPECIFICATIONS 12 Zone System Expandable to 32 10 Amp Base Power Supply Multiple Power Supplies Available - Local or Remote 4 Notification
More informationSECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.
SECTION 15481 COMPRESSED AIR SYSTEM PART 1 - GENERAL 1.1 SECTION INCLUDES A. Pipe and pipe fittings, including valves, unions and couplings. B. Air compressor. C. After cooler. D. Refrigerated air dryer.
More informationStudent Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.
SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:
More informationCerberus TM PRO Fire Safety System A comprehensive fire-protection system
s Data Sheet Fire Safety & Security Products Cerberus TM PRO Fire Safety System A comprehensive fire-protection system Standard 50-point, 252-point and 504-point-capacity systems Remote viewing for the
More informationZX1e ZX2e ZX5e. Document No Issue 01 user manual
ZX1e ZX2e ZX5e Document No. 996-130 Issue 01 user manual MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Table of Contents 1 INTRODUCTION... 4 1.1 NOTICE... 4 1.2 WARNINGS AND CAUTIONS... 4 1.3 NATIONAL
More informationZSC100 Gas Detection and Alarm System Controller
ZSC100 Gas Detection and Alarm System Controller User Guide 1- Introduction... 3 1.1- General description... 3 1.2- Cautions and warnings... 3 2- Control panel... 4 2.1 Control panel overview... 4 2.2
More informationARCHITECTURAL SPECIFICATIONS
1 G4.1 Entrance System Page 1 of 6, August 2017 DIVISION 10 - SPECIALTIES SECTION 10450 PEDESTRIAN CONTROL DEVICES Specifier Note: Coordinate and edit articles and paragraphs below to suit project requirements.
More informationDifferent types of Fire Alarm System
Different types of Fire Alarm System Conventional Fire System Generally comes with Zones. Each zone can have max 20 detectors. Addressable Fire Alarm System This comes in loops. Different manufacturer
More informationORION Mini-Rep INSTALLATION MANUAL
ORION Mini-Rep INSTALLATION MANUAL Orion Mini-Rep - INSTALLATION MANUAL - REVISION 1.0-04/007 The Orion Mini-Rep will provide remote control and system display status from multiple locations to an Orion
More informationSECTION FIRE ALARM SYSTEM PART 1 GENERAL
SECTION 16720 - FIRE ALARM SYSTEM PART 1 GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and
More informationSPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL
SECTION 1 - GENERAL CONDITIONS I. SCOPE: This specification outlines the requirements for a Fike Micromist Water Mist Fire Suppression System with automatic detection and control. The work described in
More informationThe most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation
The most user friendly Contents Section 1 Overview of System 1.1 Kit Contents 1.2 Tools Required 1.3 System Features Security Alarm System L S 4 0 0 Section 2 Planning your Installation 2.1 Location of
More information.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.
Fitness Facility Addition Page 1 1.1 CODES AND STANDARDS.1 Do complete installation in accordance with the latest edition of the CSA C22.1 as amended by the latest editions of the National Building Code
More informationZXSe Range. Fire Safety. Analogue addressable fire alarm control panel KEY FEATURES. Panel Features
Fire Safety ZXSe Range Analogue addressable fire alarm control panel The ZXSe range of analogue addressable fire alarm control panels have been designed and constructed around proven and reliable microprocessor
More informationHakki Pilke Raven spare parts manual
1 ENGLISH Hakki Pilke Raven spare parts manual Valimotie 1, FI-85800 Haapajärvi, FINLAND Tel. +358 8 772 7300, Fax +358 8 772 732 info@maaselankone.fi, www.maaselankone.fi 2 Table of contents 1 Upper section
More informationSECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS
PART 1 GENERAL 1.1 SECTION INCLUDES A. Fire alarm and smoke detection systems 1.2 REFERENCES A. NFPA 72 B. NFPA 101 1.3 REGULATORY REQUIREMENTS A. System: UL listed B. Conform to requirements of NFPA 101
More informationEZT Series Integra Med Touch Area Alarm & Zone Valve Box with EZ Backfeed
Submittal Data Sheet Features The Powerex Med Touch area alarm zone valve panel digitally displays gas pressure (1 psi increments) and provides alarm conditions as required by the latest edition of NFPA
More informationPre-Pack INTEGRATED PRE-ACTION SYSTEM
Pre-Pack INTEGRATED PRE-ACTION SYSTEM HD FIRE PROTECT TECHNICAL DATA MODEL Pre-Pack SIZE DELUGE VALVE MODEL RISER CHECK VALVE MODEL WATER MOTOR GONG BELL MAXIMUM WORKING PRESSURE SYSTEM END CONNECTION
More information