Automation, Functional Safety. Assessment of the Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT Rockwell Automation, USA

Size: px
Start display at page:

Download "Automation, Functional Safety. Assessment of the Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT Rockwell Automation, USA"

Transcription

1 Automation, Functional Safety Assessment of the Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT, USA Report-No.: 968/EZ /12 Date: Report-No.: 968/EZ /12 Page 1 of 24

2 Assessment of the Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT, USA Report-No.: 968/EZ /12 Date: Pages: 24 Test object: Customer/Manufacturer: Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT 1 Allen-Bradley Drive Mayfield Heights, OH United States of America Order-No./Date: dated Test Institute: TÜV Rheinland Industrie Service GmbH Automation, Software and Information Technology (ASI) Am Grauen Stein Köln Germany TÜV-Offer-No./Date: 968/326/10 dated TÜV-Order-No./Date: dated Inspectors: Test location: Dipl.-Ing. Matthias Haynl see Test Institute Test duration: November February 2012 The test results are exclusively related to the test samples. This report must not be copied in an abridged version without the written permission of the Test Institute. Report-No.: 968/EZ /12 Page 2 of 24

3 Table of contents Page 1. Scope 4 2. Applicable standards 4 3. Test object description Safety related aspects Test samples Inspected documents Presented test reports and certificates 7 4. Performance of tests and results General Test steps Inspection to the requirements of IEC and EN Inspection of the documentation for completeness and correctness Assessment of the management of functional safety Assessment of measures to avoid failures during the different phases of the life cycle Assessment of measures to control failures during operation Hardware design inspection Software design inspection Calculation of the safety related parameters Assessment regarding the EN ISO : AC: Application specific considerations Requirements according to EN 13611: A2: Requirements according to EN 14459: Requirements according to NFPA 72: Requirements according to NFPA 79: Requirements according to NFPA 85: Requirements according to NFPA 86: Review of EMC Information to electrical safety Review of the climatic and mechanical tests Additional aspects Programming and configuration tools Communication requirements Summary 24 Report-No.: 968/EZ /12 Page 3 of 24

4 1. Scope The following report presents the results of the Point Guard Analog Input Safety Modules 1734-IE4S and 1734-IE4SXT type approval for safety related applications. The 1734-IE4S and 1734-IE4SXT have been subject to an assessment in accordance with IEC Safety Integrity Level 3 (SIL 3) and EN ISO Performance Level e (PL e) and Category 4 (Cat 4). This test report contains the essential safety engineering aspects, that were assessed during the inspection and identifies the various test steps, that were performed to provide evidence, that the test object complies with the safety-relevant requirements of the product specification and the relevant standards. 2. Applicable standards /N 1/ IEC 61508, parts 1-7:2010 Part 1-7: Functional safety of E/E/PES safety-related system /N 2/ EN ISO : AC:2009 Safety of machinery - Safety related parts of control systems Part1: General principles design /N 3/ EN 62061:2005 Functional safety of safety-related electrical, electronic and programmable electronic control systems /N 4/ IEC :2007 Programmable controllers Part2: Equipment requirements and tests /N 5/ IEC :2008 Electrical equipment for measurement, control and laboratory use - EMC requirements - Part 3-1: Immunity requirements for safety-related systems and for equipment intended to perform safety related functions (functional safety) - General industrial applications /N 6/ EN :2005/A1:2008 Safety of machinery - Electrical equipment of machines Part 2: General requirements /N 7/ EN 14459:2008 Control functions in electronic systems for gas burners and gas burning appliances /N 8/ EN 13611: A2:2011 Safety and control devices for gas burners and gas burning appliances General requirements /N 9/ NFPA 72:2010 National Fire Protection Association, Alarm and signalling systems /N 10/ NFPA 79:2012 National Fire Protection Association, Electrical Standard for Industrial Machinery Report-No.: 968/EZ /12 Page 4 of 24

5 /N 11/ NFPA 85:2011 National Fire Protection Association, Boiler and Combustion Systems Harzards Code /N 12/ NFPA 86:2011 National Fire Protection Association, Oven and Furnaces 3. Test object description The Point Guard I/O Safety Modules 1734-IE4S and 1734-IE4SXT (see Table 1) are utilized in the POINT I/O platform and can communicate safety messages via network adapters connect to EtherNet/IP or DeviceNet networks (see Table 2). A list of common applications and compatible partners is specified /U 16/. The 1734-IE4S and 1734-IE4SXT are industrial 24VDC analog safety modules with four analog safety-input ports and the related sensor power output ports. The four analog inputs are configurable as inputs set to current mode, set to voltage mode or set to tachometer mode. Single mode of operation (one sensor is connected to the 1734-IE4S or 1734-IE4SXT, see Figure 1) and dual mode of operation (two sensors are connected to the 1734-IE4S or 1734-IE4SXT, see Figure 2) are slso supported. Figure 1: Single mode of operation Figure 2: Dual mode of operation The 1734-IE4S and 1734-IE4SXT can be configured through software using either the Network configuration tool (RSNetWorx) or the GuardLogix programming tool (RSLogix 5000). Report-No.: 968/EZ /12 Page 5 of 24

6 3.1. Safety related aspects The 1oo2 architecture is the basic architecture of the modules and therefore the hardware fault tolerance (HFT) of one was assigned. To achieve the targeted safety integrity level the safety related parameters have to be: Safe Failure (SFF) 90 % (see /N 1/, part 2, table 3) Average Probability of a dangerous Failure on Demand (PFD) < 10-3 (see /N 1/, part 1, table 2) Probability of a dangerous Failure per Hour (PFH) < /h (see /N 1/, part 1, table 3) The safety function is to measure analog process variables, such as temperature, pressure, flow rate, etc. The analog input point can be configured in seven modes (±10V, ±5V, 0 5V, 0 10V, 4 20 ma, 0 20 ma, Tachometer) Test samples The necessary tests of the 1734-IE4S and 1734-IE4SXT were carried out at the Rockwell facilities in Milwaukee and Cleveland. Additionally Rockwell provided a test system to the Test Institute. It was used to verify partly the tests carried out at Rockwell and to incorporate additional tests. Catalogue Number Description Series F/W Rev IE4S Point Guard I/O Safety Modules A IE4SXT Point Guard I/O Safety Modules A 1.1 Table 1: Point Guard Analog Input Safety Modules Catalogue Number Description Series F/W Rev PDN DeviceNet Adapter B none 1734-AENT EtherNet/IP Adapter A 3.1 Table 2: Point Guard I/O Network Adapter (suitable for safety loops up to SIL 3) The test samples were stored at the Test Institute Inspected documents Testing was mainly based on the following documents: /U 1/ Functional Requirement Specification No rev 01.3, dated /U 2/ Point Guard I/O Safety Modules SRS, rev. 0.b, dated /U 3/ Safety Concept 1734-IE4S, No rev 00.0, dated /U 4/ High Level Design Document No , rev 00.03, dated /U 5/ Hardware Detailed Design Specification No , rev 00.01, dated /U 6/ Schematic - No (ver. 02), dated Report-No.: 968/EZ /12 Page 6 of 24

7 /U 7/ High Level Firmware Design Document No , rev 01.a, dated /U 8/ Project Plan / Safety Plan No , rev 00.03, dated /U 9/ Functional Safety Management Verification and Validation Documentation No , rev 00.b, dated /U 10/ PointGuard Analog Input Embedded Software Documentation (compiled html help file), dated /U 11/ Embedded C++ Coding Standard, No. ER#X 7014, rev. 1.6 /U 12/ FMEA Point Guard Analog Input Module, No , rev. 0.4 /U 13/ Fault Insertion Analysis ( Hardware ) of Point Guard Analog I/O, dated /U 14/ Calculation of the safety relevant parameters, dated /U 15/ QTP for Point Guard Analog IO, 1734-IE4S, 1734-IE4SXT, No , rev 2.0, dated /U 16/ Installation & User Manual (Catalog Numbers 1734-IB8S, 1734-OB8S, IE4S), Publication 1734-UM013E-EN-P - Preliminary Presented test reports and certificates The following tests and test reports were performed by other accredited test labs. /U 17/ Report-No.: 968/EZ /10, dated TÜV Rheinland Industrie Service GmbH /U 18/ EMC Test Report No , , , 96460, /U 19/ Technical Report 1734-IE4S Environmental Test (Shock and Vibration), Record Id# /U 20/ Technical Report 1734-IE4S Environmental Test (Temperature and Humidity), Record Id# /U 21/ ODVA DeviceNet Safety Composite Test, ODVA File Number ODVA Inc. /U 22/ ISO9001:2008 certificate, CERT USA-RvA Rev. 1 valid until Det Norske Veritas Certification, Inc. Report-No.: 968/EZ /12 Page 7 of 24

8 4. Performance of tests and results 4.1. General The measuring and test equipment, which has been used by the TÜV Rheinland Group in the tests described in the following, is subject to regular inspection and calibration. Only devices with valid calibration have been used. The devices used in the various tests are recorded in the inspector s documentation. All considerations concerning uncertainty of the measurements, so far applicable, are stated in the inspector s documentation, too. In cases where tests have been executed in an external test lab or in the test lab of the manufacturer and where the results of these tests have been used within the here documented approval, this has occurred after a positive assessment of the external test lab and the achieved test results in detail according to the Quality Management procedure QMA Test steps The functional safety assessment of the 1734-IE4S and 1734-IE4SXT was performed by the concept and the main assessment. The steps outlined below were performed as part of the concept assessment. Review of SRS and FRS according to IEC Review of measures for avoiding systematic failures as part of the hardware and software development Evaluation of measures for detection of random failures during operation Review of the verification and validation plan Assessment of the requirements for the management of functional safety on project/product level Based on the concept assessment (details are documented under /U 17/) the main assessment was performed with the steps listed below. Review of the documentation as part of the development life cycle Judgement of the FMEA at component level regarding the relevant failure mode requirements for SIL 3 (IEC 61508) and Pl e / Cat. 4 (EN ISO ) Review of the safety relevant parameter calculations (PFD/PFH, SFF) with regard to SIL 3 Performance and verification of functional tests and fault insertion tests Assessment of the relevant requirements driven by the application standards (e.g. NFPA) Review of the submitted test reports (EMC, Environmental) 4.3. Inspection to the requirements of IEC and EN Inspection of the documentation for completeness and correctness The documents /U 1/, /U 2/ and /U 3/ were presented by the customer as the actual specification and safety concept. These documents were checked for completeness, consistency and correctness according to the requirements of /N 1/. The presented documents are found to meet the requirements of the test basis with regard to completeness, consistency and correctness. Report-No.: 968/EZ /12 Page 8 of 24

9 Assessment of the management of functional safety The assessment was carried out by inspection of the specified management and technical activities/procedures as part of the development cycle to achieve the required functional safety as well as the consideration of the responsibilities (persons, departments and organizations) for the development cycle. The reviewed policy and strategy (RA TQCS) detailed mandatory requirements (e.g. verification and validation activities, management and communication policies, safety plan) and was classified as sufficient according to /N1/. The overall functional safety assessment was done by the Test Institute, whereby the required minimum level of independence was achieved Assessment of measures to avoid failures during the different phases of the life cycle Techniques and measures to control and avoid systematic failures during the different phases of the lifecycle were inspected in accordance to /N 1/. The following techniques and measures were subjected to evaluation: Project management according to ISO 9001:2008 (see /U 22/) Documentation and review activities controlled by RA TQCS Policy (e.g. development cycle procedures, design validation procedures) Structured design in hardware and software (see /U 4/) Controlled firmware development process and using of programming guidelines (C++) to achieve consistent firmware and documentation EMC and environmental tests with increased levels for safety related products Consistent and comprehensible installation and user documentation (see /U 16/) The inspected techniques and measures described in /U 9/ (section 1.2 and 1.3) to control and avoid systematic failures during the different phases of the lifecycle are sufficient according to the requirements of SIL 3 to /N 1/. The verification and validation plan /U 9/ deals with all individual phases of the lifecycle of the product Assessment of measures to control failures during operation The measures to control failures during operation were evaluated regarding to the requirements of IEC , Annex A. The implemented measures are described in /U 12/ (section 7.4) and were analyzed concerning the required diagnostic coverage under the subjected fault model. The following essential measures to control failures during operation were confirmed: Over- and under voltage monitoring with safe shut off Combination of temporal and logical monitoring of program sequences (Execution Sequence Diagnostic, I/O Heartbeat Watchdog Test, Timer Diagnostics) Background stack monitoring Report-No.: 968/EZ /12 Page 9 of 24

10 32 bit CRC algorithm for the invariable memory ranges (start up and run-time background diagnostic) RAM Galpat data diagnostic as part of the run-time background diagnostic Safety Protocol Cross Compare Input with automatic checks Information redundancy (channel discrepancy diagnostic) in order to detect soft errors The implementation of the measures to control failures during operation were proven by functional tests documented in /U 15/ fault insertion tests documented in /U 13/ and the analysis of the corresponding software sources. The above results have shown, that the measures to control failures during operation (random and systematic) are in accordance to the requirements of SIL 3 to /N 1/ Hardware design inspection The hardware design was inspected by performing the Hardware-FMEA under consideration of representative hardware faults at component level. The Hardware-FMEA is documented in /U 12/ and based on the schematic drawn up in /U 6/. The assessment was carried out regarding the diagnostic coverage and the fault model required by /N 1/ for SIL 3 and under consideration of the hardware architecture (see 3.1). The function- and fault insertion tests were performed in co-ordination with Rockwell. The Hardware-FMEA at component level has shown, that the implemented measures to detect failures during operation are adequate for the considered fault model. The performed function- and fault insertion tests have shown no dangerous failure in relation to the fault model required by /N 1/. The results of the fault insertion tests are documented in /U 13/ Software design inspection The software assessment was done by: Review of the architecture and the basic safety strategy for the embedded software Assessment of the software design at architectural level and review of the implemented measures to detect failures during operation (e.g. RAM test Galpat) at code line level Checking programming guidelines used for the software Verification of Software Tests (functional testing, white-box testing, statistical testing, code coverage) Review of the tool qualification in reference to the T1-T3 classes for tools The architecture of the software is characterized by a clearly structured design. No obvious deviations from the firmware architecture described in /U 7/ were identified during the review of the software sources documented in /U 10/. No obvious deviations from the stipulations of the specifications /U 7/ were identified in the course of checking the software design /U 10/. The implemented measures to detect failures during operation were inspected at code line level and were judged to be sufficient regarding the SIL 3 requirement. Report-No.: 968/EZ /12 Page 10 of 24

11 The inspection of the software based on the coding guideline /U 11/ as well as the review of the performed static code analysis (PC-Lint) has revealed no functional safety related issues. The functional tests documented in the manufacturer's test plan /U 15/ were judged to be sufficient. The combination of functional testing, white-box testing and statistical testing provides evidence that each software module satisfies its associated specification. The review of the software version V 1.1 (1734-IE4S and 1734-IE4SXT) shows that the requirements of SIL 3 of the IEC regarding the software life cycle are fulfilled. The tools utilized for the design and development are listed under /U 9/ (see section 1.4) and have been classified in reference to the T1-T3 classes of IEC The assessment of the tools was done by different measures and techniques (e.g. defect history analysis, compiler validation review, release review, etc.) The above results have shown that the measures to avoid systematic failures during the software design and development are in accordance to the requirements of SIL 3 to /N 1/ Calculation of the safety related parameters The calculation of the safety relevant parameters was performed by manufacturer and is documented under /U 14/. The following values were calculated by the manufacturer, reviewed and accepted by the Test Institute: Catalogue Number PFH [h -1 ] PFD av (T=10y) SFF 1734-IE4S 5,5 E-11 2,4 E-6 98,9% 1734-IE4SXT 5,5 E-11 2,4 E-6 98,9% Table 3: Safety related parameters in reference to /N 1/, single mode operation (Figure 1) Catalogue Number PFH [h -1 ] PFD av (T=10y) SFF 1734-IE4S 3,8 E-11 1,6 E-6 98,9% 1734-IE4SXT 3,8 E-11 1,6 E-6 98,9% Table 4: Safety related parameters in reference to /N 1/, dual mode operation (Figure 2) The calculation of the safety relevant parameters has shown, that the requirements of SIL 3 to /N 1/ are fulfilled. The review of the components failure rates, resulting from a third party data base, correlates with the SN and was accepted by the Test Institute Assessment regarding the EN ISO : AC:2009 The 1734-IE4S and 1734-IE4SXT were inspected regarding the requirements for Performance Level e (PL e) and category 4 (cat. 4) to /N 2/. Report-No.: 968/EZ /12 Page 11 of 24

12 All single failures will be detected by appropriate diagnostic measures. The effectiveness of these diagnostics were assessed during the assessment in reference to /N 1/. For components which are not covered by diagnostics the failure accumulation up to 2 failure in combination were considered. The resulted effects of the failure accumulation have shown no loss of the safety function. The safety structure, diagnostics and the detection of failures complies to the requirements of Performance Level e (PL e) and category 4 (cat. 4) in reference to /N 2/. Catalogue Number MTTF d DC avg Cat. PL 1734-IE4S 100 years High 4 e 1734-IE4SXT 100 years High 4 e Table 5: Safety related classification in reference to /N 2/ 4.5. Application specific considerations Requirements according to EN 13611: A2:2011 The EN 13611: A2:2011 specifies methods for classification and assessment of control devices designed to operate gas burners and gas burning appliances, particularly regarding their fault behaviour and preventative measures. The 1734-IE4S and 1734-IE4SXT have been assessed to the applicable class C requirements of EN 13611: A2:2011. Clause Requirements Result 6.6 Functional safety requirements see clause Requirements for control devices Failure avoidance and failure control Fulfilling the requirements of IEC (SIL 3), EN ISO (PL e, Cat. 4) is sufficient Reset device Requirement on system level architecture by the end user Documentation Fulfilling the requirements of IEC (SIL 3), EN ISO (PL e, Cat. 4) is sufficient Class A Class C was applied Class B Class C was applied Class C Fulfilling the requirements of IEC (SIL 3), EN ISO (PL e, Cat. 4) is sufficient. Report-No.: 968/EZ /12 Page 12 of 24

13 Clause Requirements Result Circuit and construction requirements Fulfilling the requirements of IEC (SIL 3), EN ISO (PL e, Cat. 4) is sufficient. For details see also /U 12/ and /U 13/. 7 Functional requirements Environmental requirements are fulfilled in reference to /N 4/. For details see EMC requirements Increased EMC levels have been used in reference to /N 5/. For details see Marking requirements Passed The 1734-IE4S and 1734-IE4SXT are fulfilling the requirements of IEC (SIL 3) and EN ISO (PL e, Cat. 4) and can be used as a class C control device in reference to annex J and K of EN 13611: A2:2011. The user shall comply with all other requirements from /N 8/ including requirements that have an effect on the safety configuration of the 1734-IE4S and 1734-IE4SXT Requirements according to EN 14459:2008 The EN 14459:2008 specifies methods for classification and assessment of function blocks designed to operate gas burners and gas burning appliances, particularly regarding their fault behaviour and preventative measures. The 1734-IE4S and 1734-IE4SXT have been assessed to the applicable requirements of EN 14459:2008 by using the RSLogix 5000 programming software. Clause Requirements Result EN 13611:2007 shall apply See applicable results under section of this test report Assessment for control functions in gas appliances Potential hazards arising from the use of gas appliances are among others covered by means of control functions. Informative Fault tolerating time is determined by the ability of the appliance to tolerate a fault for a certain time Fault modes on the appliance level shall be considered for assessing a certain control function. If not defined by the appliance standard, fault modes that are specific for the appliance with relation to the control function, shall be declared by the manufacturer, based on a clear description. Requirement on application level by the end user. DC fault model of /N 1/ are applied to the modules. 7 Performance EN 13611:2007 shall apply See applicable results under section of this test report Combined apparatus and Multifunctional systems Requirement on system level architecture by the end user. Report-No.: 968/EZ /12 Page 13 of 24

14 Clause Requirements Result 7.13 Data exchange Systems or apparatus with control functions may be connected to separate, independent apparatus or systems (which may themselves contain control functions or provide other information). Any data exchange between these systems or apparatus shall be taken into consideration regarding safety. Requirement on system level architecture by the end user Regarding safety relevance and influence, message types for data exchange in a control function or functions shall be defined according to as: - safety related; - non-safety related. Separation of safety and non-safety functions is supported and shall be considered on architecture on application level Communication of safety related data Transmission Safety related data shall be transmitted authentically concerning: - quantity of data (i.e. all data expected to and from respective addresses); - quality of data (i.e. in a correct and precise manner); - appropriate transmission time. Data variation or corrupted data shall not lead to an unsafe state Access to data exchange All types of access to a safety related data exchange system shall be clearly restricted. Safety related operating data, configuration parameters and/or software modules may be transmitted to control functions via communication, providing adequate hardware/software measures are taken to ensure that no unwanted access to the control function is possible. The CIP safety communication layer is SIL 3 certified (see /U 21/). Not applicable Requirement on system level architecture by the end user. 8-9 EN 13611:2007 shall apply See applicable results under section of this test report. Table 6 Applicable requirements of EN14459:2008 The review of the 1734-IE4S and 1734-IE4SXT in reference to the requirements of Table 7 has shown no deviations. The user shall comply with all other requirements from /N 7/ including requirements that have an effect on the safety configuration of the 1734-IE4S and 1734-IE4SXT Requirements according to NFPA 72:2010 The NFPA72:2010 from the National Fire Protection Association contains the requirements for fire alarm and signalling systems. In the following table the relevant general and specific requirements are listed. These requirements are applied to the 1734-IE4S and 1734-IE4SXT. Report-No.: 968/EZ /12 Page 14 of 24

15 Clause Requirements Result 10 System Fundamentals 10.5 Power supplies Installation requirements applies to the end user Unless configured in compliance with , at least two independent and reliable power supplies shall be provided, one primary and one secondary Monitoring the integrity of the power supplies shall be in accordance with Installation requirements applies to the end user. See paragraph Performance and limitation Voltage, Temperature, and Humidity Variation. Equipment Passed shall be designed so that it is capable of performing its intended functions under the following conditions: (1)* At 85 percent and at 110 percent of the nameplate primary (main) and secondary (standby) input voltage(s) (1) IEC :2007 (2) At ambient temperatures of 0 C (32 F) and 49 C (120 F) (3) At a relative humidity of 85 percent and an ambient temperature of 30 C (86 F) (2) IEC :2007 DIN EN , test Nb (3) IEC :2007 DIN EN , test Db, variant Protection of Fire Alarm Systems Installation requirements applies to the end user Annunciation and annunciation zoning Installation requirements applies to the end user Monitoring integrity Unless otherwise permitted or required by through , all means of interconnecting equipment, devices, and appliances and wiring connections shall be monitored for the integrity of the interconnecting conductors or equivalent path so that the occurrence of a single open or a single ground fault condition in the installation conductors or other signalling channels is automatically indicated within 200 seconds Unless otherwise permitted or required by through , all means of interconnecting equipment, devices, and appliances and wiring connections shall be monitored for the integrity of the interconnecting conductors or equivalent path so that the restoration to normal of a single open or a single ground fault condition in the installation conductors or other signaling channels is automatically indicated within 200 seconds. Single open or a single ground fault are detected within 200sec. Restoration to normal is processed within 200sec after clearing the fault condition Monitoring Integrity of Power Supplies Unless otherwise permitted or required by and , all primary and secondary power supplies shall be monitored for the presence of voltage at the point of connection to the system. All power domains are monitored. Report-No.: 968/EZ /12 Page 15 of 24

16 Clause Requirements Result Failure of either supply shall result in a trouble signal in accordance with Section Installation requirements, applies to the end user Documentation The provided documentation shall include the current revisions of all fire alarm software and the revisions of software of any systems with which the fire alarm software interfaces The revisions of fire alarm software, and the revisions of the software in the systems with which the fire alarm software interfaces, shall be verified for compatibility in accordance with the requirements of Application and firmware can be clearly identified by using RSLogix 5000 programming software. See following paragraph Initiating devices Not applicable 23 Protected Premises Fire Alarm Systems Passed (applicable sections) Software and Firmware control * Software and firmware within the fire alarm control system that interfaces to other required software or firmware shall be functionally compatible * The compatible software or firmware versions shall be documented at the initial acceptance test and at any reacceptance tests * All software and firmware shall be protected from unauthorized changes. Requirement on system level architecture by the end user. Requirement on system level architecture by the end user All changes shall be tested in accordance with Testing requirements applies to the end user. 23.6* Performance of signalling line circuits (SLC) The assignment of class designations to signalling line Informative circuits shall be based on their performance capabilities under abnormal (fault) conditions in accordance with the requirements for Class A, Class B, or Class X pathways specified in Chapter 12 and the requirements of through An open, short circuit, or ground fault shall result in the annunciation of a trouble signal Class B pathways shall maintain alarm capability during the application of a single ground fault Class A and Class X pathways shall maintain alarm capability during the application of a single ground fault, and also during the combination of a single open and a single ground fault Where digital communications are used, inability to send or receive digital signals over a signalling line circuit shall be indicated by a trouble signal. Table 7: Applicable requirements of NFPA72:2010 Requirement on system level architecture by the end user. Requirement on system level architecture by the end user. Requirement on system level architecture by the end user. Report-No.: 968/EZ /12 Page 16 of 24

17 The review of the 1734-IE4S and 1734-IE4SXT in reference to the requirements of Table 7 has shown no deviations. The user shall comply with all other requirements from /N 9/ including requirements that have an effect on the safety configuration of the 1734-IE4S and 1734-IE4SXT Requirements according to NFPA 79:2012 The NFPA79:2012 from the National Fire Protection Association contains the electrical requirements for industrial machinery. In the following table the relevant general and specific requirements are listed. These requirements are applied to the 1734-IE4S and 1734-IE4SXT. Clause Requirements Result 4.4 Physical environmental and operation conditions (covering EMC, climatic and mechanical requirements) See sections 4.6 and 4.8 of the report. 6 Protection against electrical shock See section 4.7 of the report Control Systems Incorporating Software and Firmware See following paragraphs Based Controllers , and Software modification Software verification Use in safety related functions Control systems incorporating software and firmware based controllers performing safety-related functions shall conform to all of the following: (1) In the event of any single failure perform as follows: (a) Not lead to the loos of the safety function(s) (b) Lead to the shutdown of the system in a safe state (c) Prevent subsequent operation until the component failure has been corrected (d) Prevent unintended start-up of equipment upon correction of the failure (2) Provide protection equivalent to that of control systems incorporating hardwired / hardware components. (3) Be designed in conformance with an approved standard that provides requirements for such systems Table 8: Applicable requirements of NFPA79:2012 See section of the report. The review of the 1734-IE4S and 1734-IE4SXT in reference to the requirements of Table 8 has shown no deviations. The user shall comply with all other requirements from /N 10/ including requirements that have an effect on the safety configuration of the 1734-IE4S and 1734-IE4SXT. Report-No.: 968/EZ /12 Page 17 of 24

18 Requirements according to NFPA 85:2011 The NFPA85:2011 from the National Fire Protection Association contains the requirements for boiler and combustion systems. In the following table the relevant general and specific requirements are listed. These requirements are applied to the 1734-IE4S and 1734-IE4SXT. Clause Requirement Results 85 1 Chapter 1 Administration Requirement on system level for the end user Referenced Publications Informative 85 3 Definitions Informative 85 4 Fundamentals of Boiler Combustion Systems Informative Manufacturer, Design and Engineering Requirement on system level for the end user Installation Requirement on system level for the end user Coordination of Design, Construction and Operation Requirement on system level for the end user Maintenance, Inspection, Training and Safety Requirement on system level for the end user Basic Operating Requirements Requirement on system level for the end user Structural Design Requirement on system level for the end user Functional Requirements for Fuel-Burning Systems Requirement on system level for the end user Multiple Boilers Requirement on system level for the end user Gasenous Vent Systems Requirement on system level for the end user Fuel System Venting Requirement on system level for the end user Burner Management System Logic As a minimum, the requirements of through shall be included in the design to ensure that a logic system for burner management meets the intent of these standards. See following paragraphs ( through ) Report-No.: 968/EZ /12 Page 18 of 24

19 Clause Requirement Results The logic system for burner management shall be designed specifically so that single failure in that system does not prevent an appropriate shutdown. The burner management system interlock and alarm functions shall be initiated by one or more of the following: One or more switches or transmitters that are dedicated to the burner management system. One or both signals from two transmitters exceeding a preset value. The median signal from three transmitters exceeding the preset value. When signals from multiple switches or transmitters are provided to initiate interlock or alarm functions, those signals shall be monitored in comparison to each other by divergence or other fault diagnostic alarms. When signals from multiple switches or transmitters are provided to initiate interlock or alarm functions, the provided signals shall be generated by individual sensing devices connected to separate process taps. Alarms shall be generated to indicate equipment malfunction, hazardous conditions, and misoperation. The burner management system designer shall evaluate the failure modes of components, and as a minimum the following failures shall be evaluated: 1. Interruptions, excursions, dips, recoveries, transients and partial losses of power 2. Memory corruption and losses 3. Information transfer corruption and losses 4. Inputs and Outputs (fail-on, fail-off) 5. Signals that are unreadable or not being read 6. Failure to address errors 7. Processor faults 8. Relay coil failure 9. Relay contact failure (fail-on, fail-off) 10. Timer failure All single failures will be detected by appropriate diagnostic measures. Shutdown has to be considered at the overall system level. Requirement on application and system Not applicable Requirement on application and system Requirement on application and system Requirement on application and system See sections 4.3 and 4.4 of this test report. Report-No.: 968/EZ /12 Page 19 of 24

20 Clause Requirement Results The design of the logic system for burner management shall include and accommodate the following requirements: 1. Diagnostic shall be included in the design to monitor processor logic function. 2. Logic system failure shall not preclude proper operator intervention. 3. Logic shall be protected from unauthorized changes. 4. Logic shall not be changed while the associated equipment is in operation. 5. System response time (through-put) shall be short to prevent negative effects on the application. 6. Protection from the effects of noise shall prevent false operation. 7. No single component failure within the logic system shall prevent a mandatory master fuel trip. 8. The operation shall be provided with a dedicated manual switch(es) that shall actuate the master fuel trip relay independent and directly 9. At least one manual switch ref in (8) shall be identified and located remotely where it can be reached in case of emergency 10. The logic system shall be monitored for failure. 11. Failure of the logic system shall required a fuel trip for all equipment supervised by the failed logic system. 12. Logic shall be maintained either in nonvolatile storage or in other memory that retains information on the loss of system power. Requirements for Independence Momentary Closing of Fuel Values. Circuit Devices. No momentary contact or automatic resetting device, control, or switch that can cause chattering or cycling of the safety shutoff valves shall be installed in the wiring between the load side (terminal) of the primary or programming control and the main or ignition fuel valves. Documentation. Documentation shall be provided to the owner and operator, indicating that all safety devices and logic meet the requirements of the application. Passed (1) is inherent to section 4.3 and 4.4 of this test report. (2) to have to be considered at the system level. (12) Logic remains maintained after loss of power. Note: Remaining items have to be considered by the end user at the application level. Not applicable Not applicable Not applicable Logic sequences have to be implemented by the end user at the application level. Passed See safety manual /U 16/ Flame Monitoring and Tripping System. Not applicable Report-No.: 968/EZ /12 Page 20 of 24

21 Clause Requirement Results Combustion Control System Not applicable Power-Supplies. Precautions shall be taken to ensure the availability of a failure-free power-supply (electric or pneumatic) to all control and safety devices. Not applicable Requirement on application and system Operating Information Not applicable Selective Catalytic Reduction Not applicable 85 5 Single Burner Boilers Not applicable 85 6 Multiple Burner Boilers Not applicable 85 7 Atmospheric Fluidized Bed Boilers Not applicable 85 8 Heat Recovery Steam Generators and Other Combustion Turbine Exhaust Systems Not applicable 85 9 Pulverized Fuel Systems Not applicable Stokers Not applicable Table 9: Applicable requirements of NFPA85:2011 The review of the 1734-IE4S and 1734-IE4SXT in reference to the requirements of Table 9 has shown no deviations. The user shall comply with all other requirements from /N 11/ including requirements that have an effect on the safety configuration of the 1734-IE4S and 1734-IE4SXT Requirements according to NFPA 86:2011 The NFPA 86:2011 from the National Fire Protection Association contains the requirements for oven and furnaces. In the following table the relevant general and specific requirements are listed. These requirements are applied to the 1734-IE4S and 1734-IE4SXT. Clause Requirement Compliance description 86 1 Administration Informative 86 2 Referenced Publications Informative 86 3 Definitions Informative 86 4 General Report-No.: 968/EZ /12 Page 21 of 24

22 Clause Requirement Compliance description 86 5 Location and Construction 86 6 Furnace Heating Systems 86 7 Commissioning, Operation, Maintenance, Inspection and Testing 86 8 Safety Equipment and Application Safety Device Requirements Informative All Safety devices shall meet one of the following See paragraph 8.4 criteria: (3) Be programmable controllers applied in accordance with Section Logic Systems Informative General Informative Hardwired Logic Systems Not hardwired Programmable Logic Controller Systems (E) The PLC shall detect the following conditions: (1) Failure to execute any program or task containing safety logic (2) Failure to communicate with any safety input or output (3) Changes in software set point of safety functions (4) Failure of outputs related to safety functions (5) Failure of timing related to safety functions (F) A safety shutdown shall occur within 3 seconds of detecting any condition listed failures in (E) Hardware (A) Memory that retains information on loss of system power shall be provided by software (B) The PLC shall have a minimum mean-timebetween failures (MTBF) rating of 250,000 hours (D) Output checking shall be provided for PLC outputs controlling fuel safety shutoff valves and oxygen safety shutoff valves. Software (A) Access to the PLC and its logic shall be restricted to authorized personnel. (B) The following power supplies shall be monitored: (1) Power supplies used to power PLC inputs and outputs that control furnace safety functions See sections 4.3 and 4.4 of this test report. Requirement on application and system (A ) Logic remains maintained after loss of power. MTBF 250,000 hours Not applicable, analog inputs only. Password for safety application See sections 4.3 and 4.4 of this test report. Report-No.: 968/EZ /12 Page 22 of 24

23 Clause Requirement Compliance description (C) When any power supply required by (B) (1) fails, the dedicated PLC output required in (G) shall be deactivated. (E) Software shall be documented as follows (1) Labeled to identify elements or group of elements containing safety software (2) Labeled to describe the function of each element containing safety software Safety PLCs (A) Where used for combustion safety service, safety programmable logic controllers shall have the following characteristics: (1) The processor and the input and output (I/O) shall be listed for control reliable service with an SIL rating of at least 2. (2) Access to PLCs dedicated to safety functions shall be restricted. (3) Nonsafety functions, where implemented, shall be independently accessible from safety functions. (4) All safety function sensors and final elements shall be independent of operating sensors and final elements. Table 10 Applicable requirements of NFPA86:2011 Analog inputs only. If a power failure is occurs the analog inputs stops the communication. Application and firmware can be clearly identified by using RSLogix 5000 programming software. Passed See sections 4.3 and 4.4 of this test report. The review of the 1734-IE4S and 1734-IE4SXT in reference to the requirements of Table 10 has shown no deviations. The user shall comply with all other requirements from /N 12/ including requirements that have an effect on the safety configuration of the 1734-IE4S and 1734-IE4SXT Review of EMC The EMC tests were performed at the Environmental Evaluation Laboratory of Rockwell Automation. The product certification lab is audited for compliance to ISO 17025, and is an independent department. The review of the test results documented in /U 18/ has shown, that the product requirements according to /N 4/ and /N 5/ are fulfilled Information to electrical safety The 1734-IE4S and 1734-IE4SXT are connected to 24VDC powered by the DeviceNet or additional external 24VDC power supplies. All outputs (e.g. sensor supply) are internally fused and operating to a nominal voltage of 24VDC. A power supply that will be used for 1734-IE4S and 1734-IE4SXT in safety application shall fulfil the requirements according to EN or similar standards. Power supplies shall fulfil the requirements for Protective Extra-low-Voltage (PELV) or Safety Extra Low Voltage (SELV). No voltage greater then 24VDC is generated by the device. Report-No.: 968/EZ /12 Page 23 of 24

24 4.8. Review of the climatic and mechanical tests The climatic and mechanical tests for the 1734-IE4S and 1734-IE4SXT were performed by the Environmental Evaluation Laboratory of. The product certification lab is audited for compliance to ISO 17025, and is an independent department. The review of the test results documented in /U 19/ and /U 20/ has shown no obviously derivations regarding the climatic and mechanical test requirements stipulated by /N 4/ Additional aspects Programming and configuration tools For the 1734-IE4S and 1734-IE4SXT the following parts of software will be used: RSLogix 5000 programming software. RSNetworks Network configuration. Both parts of software are not safety relevant. The special requirements for the PC-based software used for safety related configuration tasks are clearly described in the /U 16/ and have to be observed Communication requirements The 1734-IE4S and 1734-IE4SXT shall be connected to the DeviceNet or EtherNet/IP network and proceed information with other compatible partners by using the CIP safety communication. The CIP safety communication layer is SIL 3 certified. The test results documented in /U 22/ have shown no derivations regarding the compliance to the DeviceNet Safety protocol. 5. Summary During the assessment no infringement of the functional and safety related requirements outlined in the applied standards could be found. Observance have to be given to the installation instructions /U 16/ released by. On the basis of the above assessment the 1734-IE4S and 1734-IE4SXT, specified under chapter 3.2, can be used in SIL 3 (IEC 61508), SIL CL 3 (EN62061) and Pl e / Cat. 4 (EN ISO ) applications. The resistance against the environmental conditions (climatic, mechanic, EMC) fulfils the requirements of /N 4/ and /N 5/. Cologne, Report released after review: TIS/ASI/Kst. 968 hay-nie Date: The inspector Dipl.-Ing. Matthias Haynl Dipl.-Ing. Heinz Gall Report-No.: 968/EZ /12 Page 24 of 24

Automation, Software und Informationstechnologie

Automation, Software und Informationstechnologie Automation, Software und Informationstechnologie Report on the type approval of the Adjustable Frequency AC Drives PowerFlex 753 and 755 of Rockwell Automation Inc. Bericht-Nr.: 968/EZ 334.00/08 Datum:

More information

Why AC800M High Integrity is used in Burner Management System Applications?

Why AC800M High Integrity is used in Burner Management System Applications? Why AC800M High Integrity is used in Burner Management System Applications? Prepared by: Luis Duran Product Marketing Manager Safety Systems ABB Process Automation/Control Technologies TÜV Functional Safety

More information

Certification Report of the ST3000 Pressure Transmitter

Certification Report of the ST3000 Pressure Transmitter Certification Report of the ST3000 Pressure Transmitter Revision No.: 1.0 Date: Report Number: Product: Customer: Order Number: Authority: Responsible: 2006-Dec-12 SAS-128/2006T ST3000 Pressure Transmitter

More information

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Certification Report of the ST 3000 Pressure Transmitter with HART 6 Certification Report of the ST 3000 Pressure Transmitter with HART 6 Revision No.: 2.4 Date: Report Number: 2010-Mar-18 SAS-190/2006T Product: ST 3000 Pressure Transmitter with HART 6 Customer: Order Number:

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Detcon FP-700 Combustible Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: DC 06/08-04 Report No.: DC 06/08-04 R001 Version V1, Revision

More information

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions

SITRANS. Temperature transmitter Functional safety for SITRANS TW. Introduction. General safety instructions 2. Device-specific safety instructions Introduction 1 General safety instructions 2 SITRANS Temperature transmitter Device-specific safety instructions 3 Appendix List of Abbreviations/Acronyms A B Product Information Supplement to Operating

More information

Test reports for the determination of B 10d values for emergency stop switches of families 800F, 800H, 800T and D7 of Rockwell Automation

Test reports for the determination of B 10d values for emergency stop switches of families 800F, 800H, 800T and D7 of Rockwell Automation Report about the inspection of test reports for the determination of B 10d values for emergency stop switches of families, 800H, 800T and of Rockwell Automation Report-No.: 968/EL 660.01/10 Date: 2010-06-08

More information

Measurement of Safety Integrity of E/E/PES according to IEC61508

Measurement of Safety Integrity of E/E/PES according to IEC61508 Measurement of Safety Integrity of E/E/PES according to IEC61508 Mr. Chen Zhenkang TUV Rheinland Singapore 18. May. 2018 Singapore World Metrology Day 2018 1 Agenda 1. TÜV Rheinland: a Certification Body

More information

Proservo NMS5- / NMS7-

Proservo NMS5- / NMS7- Functional Safety Manual Proservo NMS5- / NMS7- Tank gauge for Liquid level measurement with 4 to 20mA Output or with Alarm Relay Contact Output Application Operating minimum (e.g. dry run protection),

More information

Safety in the process industry

Safety in the process industry Products Solutions Services Safety in the process industry Simply reliable Table of contents Endress+Hauser: At home in the process safety Smart devices and concepts for hazardous areas Introduction to

More information

Burner Management and Combustion Control. Copyright 2014 Rockwell Automation, Inc. All Rights Reserved.

Burner Management and Combustion Control. Copyright 2014 Rockwell Automation, Inc. All Rights Reserved. Burner Management and Combustion Control Rev 5058-CO900E Industrial Combustion Team Overview Background and Industry Experience RA s IC&PG Team Expertise 3 Extensive experience working with Factory Mutual

More information

100 & 120 Series Pressure and Temperature Switches Safety Manual

100 & 120 Series Pressure and Temperature Switches Safety Manual 100 & 120 Series Pressure and Temperature Switches Safety Manual MECH-SM-01 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

FUNCTIONAL SAFETY CERTIFICATE

FUNCTIONAL SAFETY CERTIFICATE FUNCTIONAL SAFETY CERTIFICATE This is to certify that the X5000 & S5000 Fixed Gas Detector Range MSA The Safety Company manufactured by General Monitors 1000 Cranberry Woods Drive 26776 Simpatica Cir Cranberry

More information

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA

Failure Modes, Effects and Diagnostic Analysis. Rosemount Inc. Chanhassen, Minnesota USA Failure Modes, Effects and Diagnostic Analysis Project: 2088 Pressure Transmitter Customer: Rosemount Inc. Chanhassen, Minnesota USA Contract No.: ROS 06/10-18 Report No.: ROS 06/10-18 R001 Version V1,

More information

Options for Developing a Compliant PLC-based BMS

Options for Developing a Compliant PLC-based BMS Options for Developing a Compliant PLC-based BMS Jack Boone aesolutions Greenville, South Carolina, United States of America ABSTRACT Facilities are focusing on improving the reliability of their burner

More information

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300

FMEDA Report. Failure Modes, Effects and Diagnostic Analysis. KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300 Failure Modes, Effects and Diagnostic Analysis Device Designation: KFD0-CS-Ex*.54* and KFD0-CS-Ex*.56* Project: X7300 Pepperl+Fuchs GmbH Mannheim Germany Mannheim norm sheet 1 of 16 Released EDM checkout

More information

Functional Safety Manual June pointek CLS500/LC500

Functional Safety Manual June pointek CLS500/LC500 Functional Safety Manual June 2009 pointek CLS500/LC500 Introduction 1 Level Switch Pointek CLS500 SITRANS LC500 SIL Safety Manual Supplement to device manual General safety instructions 2 Device-specific

More information

IEC Functional Safety Assessment

IEC Functional Safety Assessment IEC 61508 Functional Safety Assessment Project: Detcon IR-700 Combustible Hydrocarbon Gas Sensor Customer: Detcon The Woodlands, TX USA Contract No.: Q13/06-003 Report No.: DC 13-06-003 R002 Version V1,

More information

Operating Guide Safe Torque Off

Operating Guide Safe Torque Off ENGINEERING TOMORROW Operating Guide Safe Torque Off VLT Frequency Converters vlt-drives.danfoss.com Contents Operating Guide Contents 1 Introduction 2 1.1 Purpose of the Manual 2 1.2 Additional Resources

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Type 95IR/95UV/95DS Flame Scanners Customer: FIREYE Derry, New Hampshire USA Contract No.: FIR 04/08-21 Report No.: FIR 04/08-21 R002 Version V1,

More information

United Electric Controls One Series Safety Transmitter Safety Manual

United Electric Controls One Series Safety Transmitter Safety Manual United Electric Controls One Series Safety Transmitter Safety Manual OneST-SM-02 1 INTRODUCTION This Safety Manual provides information necessary to design, install, verify and maintain a Safety Instrumented

More information

Overview of Emerging Safety Standards Machinery Sector By Phill Carroll Business Development Manager Topics Historical Situation Introduction of New Standards Terminology Safety Integrity identification

More information

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions. 11/16/12 TerraView First Revision No. 15-NFPA 720-2012 [ Global Input ] Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

More information

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No

User s Manual. YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters. Manual Change No User s Manual YTA110, YTA310, YTA320, and YTA710 Temperature Transmitters Manual Change No. 16-045 Please use this manual change for the manuals listed below. 1. Applicable manuals, revised item, revised

More information

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH

FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH FUNCTIONAL SAFETY OF ELECTRICAL INSTALLATIONS IN INDUSTRIAL PLANTS BY OTTO WALCH Troublefree and safe operation of industrial systems is of great importance, not only for the safety of the systems and

More information

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System

White Paper. Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System White Paper Project: Integrated Safety for a Single BMS Evaluation Based on Siemens Simatic PCS7 System Version 1, Revision 2, August 4, 2016 Jim Jenkins, William Goble The document was prepared using

More information

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL SAFETY MANUAL PointWatch Eclipse Infrared Hydrocarbon Gas Detector SIL 2 Certified Model PIRECL Safety Certified Model PIRECL PointWatch Eclipse IR Gas Detector This manual addresses the specific requirements

More information

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators

SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators SIL Safety Guide Series MS Single-Acting Spring-Return Hydraulic Linear Actuators Rev 0, November 17 2015 Page 1 of 9 Table of Contents 1 INTRODUCTION 3 1.1 Terms and abbreviations 3 1.2 Acronyms 4 1.3

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Fireye Flame Sensor Module CE Flameswitch, model MBCE-110/230FR Company: Fireye Derry, NH USA Contract Number: Q09/10-26 Report No.: FIR 09/10-26

More information

New Developments in the IEC61511 Edition 2

New Developments in the IEC61511 Edition 2 New Developments in the IEC61511 Edition 2 Presented by Dr Issam Mukhtar PhD(Eng.) TÜV FS Expert (IDNo.:117/06) 6 th May 2013 2010 Invensys. All Rights Reserved. The names, logos, and taglines identifying

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: ST3000 pressure transmitter Customer: Honeywell International Inc. Fort Washington, Pennsylvania USA Contract No.: HON 06/05-18 Report No.: HON 06/05-18

More information

The agri-motive safety performance integrity level Or how do you call it?

The agri-motive safety performance integrity level Or how do you call it? TÜV Rheinland InterTraffic GmbH Safety in Transportation 4 The agri-motive safety performance integrity level Or how do you call it? Dipl.-Ing. Sebastian Gräfling, TÜV Rheinland InterTraffic GmbH Contents

More information

DIRECTIVE NO: D-B

DIRECTIVE NO: D-B DIRECTIVE NO: D-B6 100604 1 LOW PRESSURE THERMAL FLUID PLANT AUTOMATED CONTROL SYSTEMS Date of Issue: June 4, 2010 General Details This directive is being issued to owners, licensed contractors, consulting

More information

Integrated but separate

Integrated but separate End users of older automation systems essentially had to invest in two separate systems: a basic process control system and a separate safety instrumented system. Nowadays, suppliers differ in their opinions

More information

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS)

SAFETY MANUAL. Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) SAFETY MANUAL Electrochemical Gas Detector GT3000 Series Includes Transmitter (GTX) with H 2 S or O 2 Sensor Module (GTS) Sensor Module (GTS) Transmitter (GTX) Detector (GT3000) SAFETY CERTIFIED GT3000

More information

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition

Functional safety according to IEC / IEC Important user information. Major changes in IEC nd Edition International Symposium in China Functional Safety in Industrial Applications 18 19 October 2011, Shanghai - China Functional safety according to IEC 61508 / IEC 61511 Important user information Major

More information

Safety Speed Monitoring

Safety Speed Monitoring Monitoring Considerations about sensors in applications for safety speed monitoring Marketing Documentation - November 2013 MV - Rev. 1.0 MOSAIC MV and SENSORS Encoder Proximity MV Module Safety Level

More information

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd.

Process Safety - Market Requirements. V.P.Raman Mott MacDonald Pvt. Ltd. Process Safety - Market Requirements V.P.Raman Mott MacDonald Pvt. Ltd. Objective of Process Safety Protect personnel Protect the environment Protect the plant equipment / production. Multiple Layers

More information

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd Abstract Session Four Functional safety: the next edition of IEC 61511 Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd The functional safety standard IEC 61511 provides a framework for managing

More information

Digital EPIC 2 Safety manual

Digital EPIC 2 Safety manual Safety manual Before installation these instructions must be fully read and understood Table of contents Safety manual... 1 1. Introduction... 1 1.1 Terms and abbreviations... 2 1.2 Acronyms... 2 1.3 Product

More information

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017

Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 Functional Safety of Machinery Presented by Greg Richards Manufacturing in America 02/22-23/2017 AGENDA Definition of Safety? Machinery Safety Standards Comparison of ISO 13849-1 and IEC 62061 Safety-related

More information

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update

Technical Paper. Functional Safety Update IEC Edition 2 Standards Update Technical Paper Functional Safety Update IEC 61511 Edition 2 Standards Update Functional Safety Update Table of Contents 1.0 Introduction 2.0 IEC 61511-1 changes 3.0 IEC 61511-2 changes 4.0 IEC 61511-3

More information

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR

SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR SAFETY MANUAL SIL 2 Certified Model FP-700 Combustible Hydrocarbon Gas Sensor Version 2.0 1 SAFETY CERTIFIED MODEL FP-700 COMBUSTIBLE GAS DETECTOR This manual addresses the specific requirements and recommendations

More information

Failure Modes, Effects and Diagnostic Analysis

Failure Modes, Effects and Diagnostic Analysis Failure Modes, Effects and Diagnostic Analysis Project: Oldham OLCT 200 Transmitter Company: Industrial Scientific Corporation Oakdale, PA USA Contract Number: Q11/05-009 Report No.: IS 10/10-010 R001

More information

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service

Functional Safety of Machinery: EN ISO Stewart Robinson. Overview of the presentation. References. TÜV SÜD Product Service Functional Safety of Machinery: EN ISO 13849-1 Stewart Robinson Overview of the presentation Defining Safety Functions Avoidance of Systematic Failures Defining Performance Levels Required Verifying Performance

More information

Functional Safety: the Next Edition of IEC 61511

Functional Safety: the Next Edition of IEC 61511 HazAus2015/1507 Functional Safety: the Next Edition of IEC 61511 Mirek Generowicz Engineering Manager I&E Systems Pty Ltd Level 2, 445 Hay Street Perth WA 6000 Abstract The functional safety standard IEC

More information

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification LMV52 Control Product Description February 3, 2017 The LMV52 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft burners.

More information

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content 8 Appendix 8.1 Wiring examples...4 8.2 Start configuration...4 8.3 Sensor configuration...4 8.4 Actuator configuration...5 Operating instructions.............pages 1 to 6 Original 9 EU Declaration of conformity

More information

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2 Architectural & Engineering Specifications Control Panel 1.0 GENERAL... 2 1.1 SCOPE OF WORK... 2 1.1.1 Introduction... 2 1.2 GENERAL CONDITIONS... 2 1.2.1 After-Sales Support... 2 1.2.2 Quality assurance...

More information

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark

Failure Modes, Effects and Diagnostic Analysis. PR electronics A/S Rønde Denmark Failure Modes, Effects and Diagnostic Analysis Project: 9203 Solenoid / Alarm Driver Customer: PR electronics A/S Rønde Denmark Contract No.: PR electronics 06/03-19 Report No.: PR electronics 06/03-19

More information

SECTION Fluorescent Dissolved Oxygen Measuring System

SECTION Fluorescent Dissolved Oxygen Measuring System SECTION 40 75 43 Fluorescent Dissolved Oxygen Measuring System PART 1 General 1.01 SUMMARY A. Requirements for a high-performance, digital fluorescence sensor for measurement of dissolved oxygen in liquid.

More information

Report to the Certificate

Report to the Certificate Report to the Certificate XEF 15 SIL 0039 rev.1 Monitoring System, TDSP Manufacturer: CEMB S.p.A. Via Risorgimento n.9 23826 Mandello del Lario (Lc) Italy Report No.: 22CEM-TECH-15-03 Revision 2.0 of January,

More information

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany

FMEDA and Proven-in-use Assessment. Pepperl+Fuchs GmbH Mannheim Germany FMEDA and Proven-in-use Assessment Project: Transmitter Supply Isolators KF**-CRG-*** Customer: Pepperl+Fuchs GmbH Mannheim Germany Contract No.: P+F 02/11-01 Report No.: P+F 02/11-01 R012 Version V2,

More information

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland

Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options. TÜVRheinland Scully Intellitrol Safety Manual Overfill Prevention Control Unit with Ground Verification & Vehicle Identification Options TÜVRheinland Functional Safety Type Approved FS IEC 61508 Certified SIL 2 / SIL

More information

Functional Safety Manual Oil Leak Detector NAR300 System

Functional Safety Manual Oil Leak Detector NAR300 System SD01357G/08/EN/01.14 71255416 Products Solutions Services Functional Safety Manual Oil Leak Detector NAR300 System Application This system is designed to be installed in a pit, dike, plant, or sump pit

More information

SAFETY RELAY APPLICATION

SAFETY RELAY APPLICATION SAFETY RELAY APPLICATION Application manual for YRB-4EML-31S safety relay Designation: Revision: Order No.: SAFETY RELAY APPLICATION 02 / 13.07.2016 605-000-728 This manual is valid for: YRB-4EML-31S from

More information

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters

Safety Manual. XNX TM Universal Transmitter. Table of Contents SIL 2 Certificates Overview Safety Parameters XNX TM Universal Transmitter Safety Manual Table of Contents SIL 2 Certificates Overview Safety Parameters Fault Diagnostic Time Interval Proof Test Proof Testing Procedure Table of Contents 1 SIL 2 Certificate...3

More information

Safety Function: Single-beam Area Access Control (AAC)

Safety Function: Single-beam Area Access Control (AAC) Application Technique Safety Function: Single-beam Area Access Control (AAC) Products: Guardmaster Dual-input Safety Relay, Single-beam Area Access Control Sensors with E-stop Safety Rating: CAT. 4, PLe

More information

Operating Guide Safe Torque Off

Operating Guide Safe Torque Off ENGINEERING TOMORROW Operating Guide Safe Torque Off VLT Frequency Converters vlt-drives.danfoss.com Contents Operating Guide Contents 1 Introduction 2 1.1 Purpose of the Manual 2 1.2 Additional Resources

More information

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual

HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual HAWK Measurement Systems Pty. Ltd. Centurion CGR Series Safety Manual Document No. SIL0008 Version 1.7 17/04/2018 1. Revision History: Revision Author Reviewed Approved Update Details Date 0.1 Klaus Lorentschitsch

More information

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document 1 About this document Operating instructions... pages 1 to 6 Translation of the original operating instructions 1.1 Function This operating instructions manual provides all the information you need for

More information

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511

Safety Integrity Verification and Validation of a High Integrity Pressure Protection System to IEC 61511 TÜV Rheinland International Symposium in China Functional Safety in Industrial Applications October 18 19, 2011 in Shanghai China Safety Integrity Verification and Validation of a High Integrity Pressure

More information

SIPART. Electropneumatic positioner Functional safety for SIPART PS2. Introduction. General safety instructions 2. Device-specific safety instructions

SIPART. Electropneumatic positioner Functional safety for SIPART PS2. Introduction. General safety instructions 2. Device-specific safety instructions Introduction 1 General safety instructions 2 SIPART Electropneumatic positioner Device-specific safety instructions 3 Appendix List of Abbreviations/Acronyms A B Product Information Supplement to the manuals

More information

Technical Report Proven In Use SITRANS P500

Technical Report Proven In Use SITRANS P500 Technical Report Proven In Use SITRANS P500, Industry Sector, Industry Automation Division, Sensors and Communication, PD PA PI R&D PM CRT Oestliche Rheinbrueckenstr. 50 76187 Karlsruhe, Germany Number:

More information

NFPA 72 Code Changes vs 2013

NFPA 72 Code Changes vs 2013 NFPA 72 Code Changes - 2010 vs 2013 AFAA-NE Westborough, MA February 7, 2018 Richard Roux NFPA 72 National Fire Alarm and Signaling Code Overview and 2013 Changes NFPA 72 1993 Edition Aug 20, 1993 1996

More information

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy

Introduction. Additional information. Additional instructions for IEC compliant devices. Measurement made easy ABB MEASUREMENT & ANALYTICS SIL-SAFETY MANUAL TTH300, TTF300 Temperature transmitter Additional instructions for IEC 61508 compliant devices Measurement made easy TTH300 TTF300 Introduction TTH300, TTF300

More information

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications

SAFETY MANUAL. Intelligent Sensors for H 2 S Gas Applications SAFETY MANUAL Intelligent Sensors for H 2 S Gas Applications The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent specifically

More information

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM SECTION 283111 - DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SensaGuard TM Integrated Latch Installation Instructions

SensaGuard TM Integrated Latch Installation Instructions TM Integrated Latch Installation Instructions Certifications IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE Note: Refer to Technical Specifications for Certification information and ratings. 2 TM Installation

More information

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry

Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry Assessment of the Safety Integrity of Electrical Protection Systems in the Petrochemical Industry 1. Introduction Author: Colin Easton ProSalus Limited ~ Independent Safety Consultants Within the United

More information

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure

Safety Manual. XNXTM Universal Transmitter. Fault Diagnostic Time Interval Proof Test Proof Testing Procedure XNXTM Universal Transmitter Safety Manual Table of Contents SIL 2 Certificates Overview Safety Parameters Fault Diagnostic Time Interval Proof Test Proof Testing Procedure Revision 2 Table of Contents

More information

Functional Safety: What It Is, Why It s Important And How to Comply

Functional Safety: What It Is, Why It s Important And How to Comply Functional Safety: What It Is, Why It s Important And How to Comply November 11, 2010 Copyright 1995-2010 Underwriters Laboratories Inc. All rights reserved. No portion of this material may be reprinted

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61508-2 First edition 2000-05 BASIC SAFETY PUBLICATION Functional safety of electrical/electronic/ programmable electronic safety-related systems Part 2: Requirements for electrical/electronic/

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61800-5-2 First edition 2007-07 Adjustable speed electrical power drive systems Part 5-2: Safety requirements Functional Commission Electrotechnique Internationale International

More information

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB 2CMT2016-005511 rev

More information

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017

67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017 Canadian Society for Chemical Engineering (CSChE) 67 th Canadian Chemical Engineering Conference EDMONTON, AB OCTOBER 22-25, 2017 MONDAY, 23 OCTOBER, 2017 Guillermo Pacanins, P. Eng., FS Senior Expert

More information

Operating Manual MS220KA and MSR220KA

Operating Manual MS220KA and MSR220KA Temperature Relays and MINIKA, Mains Monitoring, Digital Panel meters MINIPAN, Switching Relays and Controls Operating Manual MS220KA and MSR220KA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße

More information

Datasheet: K-22 LO Sensor

Datasheet: K-22 LO Sensor Datasheet: K-22 LO Sensor The K- 22 LO is a CO2 sensor module designed to be built- in into stationary ventilation equipment, such as window vent or duct exhaust actuators, serving as a linear transmitter

More information

Rules for Classification and Construction Additional Rules and Guidelines

Rules for Classification and Construction Additional Rules and Guidelines VI Rules for Classification and Construction Additional Rules and Guidelines 7 Guidelines for the Performance of Type Approvals 7 Test Requirements for Statical Converters with Semi-Conductors Edition

More information

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015

Rosemount Functional Safety Manual. Manual Supplement , Rev AF March 2015 Rosemount 2120 Functional Safety Manual Manual Supplement Manual Supplement Contents Contents 1Section 1: Introduction 1.1 Scope and purpose of the safety manual.................................. 1 1.2

More information

Procedure for the Approval of New Fire Detection and Alarm Technologies

Procedure for the Approval of New Fire Detection and Alarm Technologies VdS Guidelines for Automatic Fire Detection and Fire Alarm Systems VdS 3469en Procedure for the Approval of New Fire Detection and Alarm Technologies VdS 3469en : 2016-01 (01) Publisher and publishing

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD IEC 61784-3 INTERNATIONAL STANDARD Edition 1.0 2007-12 Industrial communication networks Profiles Part 3: Functional safety fieldbuses General rules and profile definitions INTERNATIONAL ELECTROTECHNICAL

More information

PPA Michaël GROSSI - FSCE PR electronics

PPA Michaël GROSSI - FSCE PR electronics Functional Safety Component selection according to IEC61511 Title 2 Presentation Michaël GROSSI: Ex / SIL Product manager @ Degree in Instrumentation & Measurement More than 10 years experience in Functional

More information

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal

Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with ma output signal Safety Manual SD 159P/00/en Pressure Transmitter cerabar S PMC 731/631 cerabar S PMP 731/635 with 4...20 ma output signal Functional safety manual Application Pressure measurements (e.g. limit pressure

More information

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification SCC Inc. LMV51 Control Product Description February 7, 2017 The LMV51 is a microprocessor-based burner management system with matching system components for the control and supervision of forced draft

More information

Is your current safety system compliant to today's safety standard?

Is your current safety system compliant to today's safety standard? Is your current safety system compliant to today's safety standard? Abstract It is estimated that about 66% of the Programmable Electronic Systems (PES) running in the process industry were installed before

More information

Industrial Grade Gas Detection Detecting The Difference

Industrial Grade Gas Detection Detecting The Difference detcon inc. Industrial Grade Gas Detection Detecting The Difference PO Box 8067 The Woodlands, TX 77387 888-367-4286 (toll free) 713-559-9200 281-292-2860 (fax) sales@detcon.com Catalog #CB-0409 www.detcon.com

More information

Siemens Process Automation End-user Summit- 2011

Siemens Process Automation End-user Summit- 2011 Siemens Process Automation End-user Summit- 2011 Experience. Technology. Community SIMATIC PCS 7 Process Safety Jean-Luc Gummersbach I IA AS PA PRM1 Global market trend in Process Safety Process Safety

More information

ADIPEC 2013 Technical Conference Manuscript

ADIPEC 2013 Technical Conference Manuscript ADIPEC 2013 Technical Conference Manuscript Name: Heidi Fuglum Company: ABB AS Job title: Deployment Manager Address: Ole Deviksvei, Oslo, Norway Phone number: +47 91 36 98 70 Email: Heidi.Fuglum@no.abb.com

More information

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017

STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT Revision 4 September 2017 STT850 and STT750 SmartLine Temperature Transmitter HART Communications Options Safety Manual 34-TT-25-05 Revision 4 September 2017 Honeywell Process Solutions Copyrights, Notices and Trademarks Copyright

More information

CERTIFICATION BULLETIN

CERTIFICATION BULLETIN File: ULC Subject C100 ULC-G.5.2 CCF7 S500F/SC2 October 28, 2014 CERTIFICATION BULLETIN 2014-07 Second Edition ULC/ORD-C100-13 Smoke Control System Equipment To: Members of the ULC Advisory Committee Members

More information

Operating Manual MS220DA

Operating Manual MS220DA ZIEHL industrie elektronik GmbH + Co KG Daimlerstraße 13, D 74523 Schwäbisch Hall + 49 791 504-0, info@ziehl.de, www.ziehl.de Temperature Relays and MINIKA Mains Monitoring Digital Panel Meters MINIPAN

More information

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors

SAFETY MANUAL. FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors SAFETY MANUAL FL4000H and FL4000 Multi-Spectral Infrared Flame Detectors The information and technical data disclosed in this document may be used and disseminated only for the purposes and to the extent

More information

STEAMPAK Series BurnerPAK BMS Burner Management Systems

STEAMPAK Series BurnerPAK BMS Burner Management Systems BurnerPAK BMS Burner Management Systems Sequence of operation, ignition and control of burners Meets NFPA 85 safety standard MFT alarming with manual reset, first-out indication Optional enhanced alarming

More information

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal

Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with ma output signal Safety Manual SD 158P/00/en Differential Pressure Transmitter deltabar S PMD 230/235 deltabar S FMD 230/630/633 with 4...20 ma output signal Functional safety manual Application Overspill protection or

More information

New requirements for IEC best practice compliance

New requirements for IEC best practice compliance New requirements for IEC 61511 best practice compliance Proof testing and a SIL study may no longer be enough by Sven Grone Schneider Electric Safety Services Practice Leader Executive summary Since its

More information

CONTENTS AUTOMATIC TRANSFER SWITCHES

CONTENTS AUTOMATIC TRANSFER SWITCHES CONTENTS AUTOMATIC TRANSFER SWITCHES PART 1 GENERAL 1.1 Related Documents 1.2 Summary 1.3 References 1.4 Quality Assurance 1.5 Submittals 1.6 Delivery, Storage and Handling 1.7 Instructions And Training

More information

Report Nr

Report Nr Report Nr. 07207334856 Applicant: Fluid Components Ltd. 1755 La Costa Meadows Drive San Marcos, CA 92069 USA Device under test: FLT 93 - Sensor System Testing body: TÜV NORD CERT GmbH Safety Related Services

More information

Shipboard incinerators with capacities up to 4000 kw

Shipboard incinerators with capacities up to 4000 kw STANDARD FOR CERTIFICATION No. 2.9 Approval Programmes Type Approval Programmes for Marine Equipment Directive (MED) No. 431.90 - MED A.1/2.7 Shipboard incinerators with capacities up to 4000 kw JANUARY

More information

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

SAFETY MANUAL. Multispectrum IR Flame Detector X3301 SAFETY MANUAL Multispectrum IR Flame Detector X3301 SAFETY-CERTIFIED MODEL X3301 MULTISPECTRUM INFRARED DETECTOR This manual addresses the specific requirements and recommendations applicable to the proper

More information