Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC
|
|
- Barrie Ray
- 6 years ago
- Views:
Transcription
1 Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a Rendered to: Trinity ERD Columbia, SC WFCi Project # & Testing Completed on: April 19, 2011 and November 7, 2011 Report Issued: November 29, 2011 TL-180
2 TABLE OF CONTENTS INTRODUCTION... 3 TEST APPARATUS AND PROCEDURE... 4 SAMPLE DESCRIPTION... 5 FIGURE 1. PHOTOGRAPHS OF IUT AND 3-TAB SHINGLES... 5 TEST RESULTS... 6 CONCLUSION... 7 SIGNATURE... 7 APPENDIX A: ERD COC RECORD... 8 Western Fire Center, Inc. Page 2 of 8
3 INTRODUCTION Testing was performed on a roof system comprised of Class A asphalt 3-tab Shingles, one layer of PrimeSource Grip-Rite ShingleLayment synthetic underlayment over ½ plywood base deck in accordance with ASTM E108-07a. Testing was performed under the auspices of Trinity ERD. ASTM E a Class A Intermittent Flame Tests (2) and Class A Burning Brand Tests (4) were conducted for on their client s synthetic underlayment covered with 3-tab asphalt shingles (conforming to ASTM D3018) under WFCi Project No in April, Additional Class A E108 testing was performed on two Spread of Flame decks on November 7, The test material was sampled from the client s manufacturing facility by Brendan Smith of Trinity ERD in accordance with ICC-ES AC85 on 10/20/2010. Western Fire Center, Inc. Page 3 of 8
4 TEST APPARATUS AND PROCEDURE The essential elements of the ASTM E108 Fire Test Apparatus include a test roof deck mounted on an adjustable pitch steel frame, a gas burner or wood brand ignition source, a wind tunnel duct, and variable speed blowers to provide a controlled air flow across the test specimen. Airflow is measured at three locations across the test deck midway up the slope of the deck at its center and two outside edges. The measurements were made using a calibrated OMEGA- FLO, Model No. HH-30, vane anemometer manufactured by Omega Engineering, Inc. The airflow is adjusted and maintained at 12 ± 0.5 mph (5.36 ± 0.2 m/s) throughout the duration of the test. The Class A Spread of Flame Fire Test utilizes a luminous gas flame applied to the deck at a temperature of 1400 ± 50 F (760 ± 28 C) as measured by a type K 14 gauge thermocouple located 1" above the surface and 1/2" toward the test flame from the lower edge of the first board of a noncombustible calibration deck. The flame covers 3 ft. of the width of the bottom portion of the deck and extends in a triangular pattern with flames extending upward a distance of 4 1/3' from the lower edge of the deck prior to any contribution (if any) from the deck. The flame is applied for 10 minutes for the Class A test, during which time the test sample is observed for the distance to which flaming of the material has spread, production of flaming or glowing brands, and displacement of portions of the test sample. The flame attached to the deck was monitored for length of travel along the deck over the duration of the test. The Class A Intermittent Flame Fire Test requires the same flame as used in the Spread of Flame test to be applied for 15 cycles of 2 minutes on and 2 minutes off. During the above applications of the test flame, the test sample is observed for the distance to which flaming of the material has spread, production of flaming or glowing brands, and displacement of portions of the test sample. The primary characteristic monitored is the through penetration of the roofing system resulting in sustained flaming of the underside. For the Class A Burning Brand Fire Test, a Class A brand is ignited in a gas burner flame by presenting each surface to the flame in the following manner and sequence for a total of 5 minutes: Each 12 by 12 inch face for 30 seconds Each 2 1/4 by 12 inch face for 45 seconds Each 12 by 12 inch face again for 30 seconds After the brand is ignited, it is placed in a vulnerable location near the lower center of the deck with the 12 mile per hour wind passing over it. The test is continued until the brand is totally consumed and until all evidence of flame, glow, and smoke has disappeared from both the exposed surface of the material being tested and the underside of the test deck, or until failure occurs. One Class A brand is placed on each deck subjected to this test. Western Fire Center, Inc. Page 4 of 8
5 SAMPLE DESCRIPTION The base decks were constructed using nominal 2 X 4 D.fir wood joists (9-10% MC) and 1/2 plywood. The moisture content of the plywood was 4%. The moisture content of the plywood sheathing was determined using the ASTM D4442 oven dry method, and the moisture content of the studs was measured using the D4444 electrical resistance method. The Item Under Test (IUT), PrimeSource Grip-Rite ShingleLayment synthetic underlayment, was sampled at the manufacturer s facility by Trinity ERD personnel (Brendan Smith see the Trinity ERD chain of custody record provided in Appendix A) on November 3, UL-labeled 3-tab asphalt shingles (conforming to ASTM D3018; nominally 190 lbs/100 square ft) were used for this evaluation. The shingles were applied with a nominal 5-5/8 exposure over the candidate underlayment in accordance with the manufacturer s installation instructions. The underlayment and roof covering was applied by the Trinity ERD representative, Jeremy DeWitt. Figure 1. Photographs of IUT and 3-tab shingles Western Fire Center, Inc. Page 5 of 8
6 TEST RESULTS Calibration Date 4/18/11 Air velocity (average) 5.26 ± 0.06 m/s Laboratory air temperature 59 F Calibration Date 4/19/11 Air velocity (average) 5.27 ± 0.03 m/s Average flame temperature 758 C Gas flow rate (natural gas) 14.5 SCFM Laboratory air temperature 56 F Calibration Date 11/7/11 Air velocity (average) 5.3 ± 0.03 m/s Average flame temperature 765 C Gas flow rate (natural gas) SCFM Laboratory air temperature 54 F Two Class A intermittent flame (IF) tests and four Class A burning brand (BB) tests were conducted on April 18 and 19, All tests were performed at a slope of 5 per horizontal foot. The ambient laboratory temperature at the time of testing was above 50 degrees F. Testing was performed by Wayne Beres of WFCi, with Jeremy DeWitt of Trinity ERD in attendance on April 18. Test No. Test No. Smoke Class A Burning Brand Tests Glow Flame Duration of Test Result (Pass/ Fail) 1 03:00 None None 45:00 Pass 2 02:50 25:00, None 38:00 Pass out 37: :19 None None 45:00 Pass 4 03:00 None None 45:00 Pass Smoke Class A Intermittent Flame Tests Dripping Glow Flame Duration of Test Result (Pass/ Fail) 5 02:00 26:00 None None 75:00 Pass 6 02:00 26:00 None None 80:00 Pass Western Fire Center, Inc. Page 6 of 8
7 At no time during these IF and BB tests were any flying flaming brands of the roof covering material produced or did exposure of the roof deck occur. At no time did portions of the roof deck fall away in the form of particles that continued to glow after reaching the floor. Tests were terminated upon cessation of all signs of combustion. Two Class A Spread of Flame tests) tests were conducted on November 7, 2011 under WFCi Project No Both tests were performed at a slope of 5 per horizontal foot. The ambient laboratory temperature at the time of testing was above 55 degrees F. Testing was performed by Wayne Beres of WFCi. Class A Spread of Flame Tests Test No. Ignition Maximum Flame Extension Time to Maximum Flame Extension (mm:ss) Duration of Test Result (Pass/ Fail) 1 02:53 2ft, 6in 09:30 10:00 Pass 6 02:00 2ft, 9in 10:00 10:00 Pass At no time during these SOF tests were any flying flaming brands of the roof covering material produced or did exposure of the roof deck occur. At no time did portions of the roof deck fall away in the form of particles that continued to glow after reaching the floor. CONCLUSION The item under test, PrimeSource Grip-Rite ShingleLayment synthetic underlayment, tested as described in this report with Class A rated 3-Tab asphalt shingles, is considered to have met the Class A requirements of ASTM E108 when tested over a ½ plywood base deck. SIGNATURE Prepared and Approved by, Howard Stacy Director, Commercial Testing Services WESTERN FIRE CENTER AUTHORIZES THE CLIENT NAMED HEREIN TO REPRODUCE THIS REPORT ONLY IF REPRODUCED IN ITS ENTIRETY The test specimen identification is as provided by the client and WFCi accepts no responsibilities for any inaccuracies therein. WFCi did not select the specimen and has not verified the composition, manufacturing techniques or quality assurance procedures. Western Fire Center, Inc. Page 7 of 8
8 Trinity ERD PrimeSource Grip Rite/ASTM E108 APPENDIX A: ERD COC RECORD Western Fire Center, Inc. Page 8 of 8
1.0 INTRODUCTION 2.0 CLASSIFICATION CRITERIA
1.0 INTRODUCTION This report presents the results of an investigation of the external fire resistance characteristics of the VELUX FCM Deck Mounted Skylight roof covering system in general accordance with
More informationPERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio
PERFORMANCE TEST REPORT Report No.: F6398.01-121-24 Test Date: March 9 th & 10th, 2016 Rendered to: Metal Building Manufacturers Association Cleveland, Ohio ASSEMBLIES: Metal Roof Panels and Clay Roof
More informationPRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona
Architectural Testing PRODUCT PERFORMANCE TEST REPORT Report No.: D7226.01-121-24 Test Date: May 29, 2014 Rendered to: Natural Light Energy Systems Phoenix, Arizona PRODUCT TYPE: Tubular Daylight Device
More informationResearch-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly
Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly ASTM E119-98: Standard Test Methods for Fire Tests of Building Construction and Materials* *Research-scale horizontal
More informationREPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015
REPORT NUMBER: 101960325MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015 EVALUATION CENTER Intertek Testing Services NA Inc. 8431 Murphy Drive Middleton, WI 53562 TEST REPORT
More informationHeat and Smoke Release of a Ceiling-Installed Speaker
WFCi Project #12051 Heat and Smoke Release of a Ceiling-Installed Speaker Indicative testing conducted in accordance with the test methodology described in UL 2043, Fire test for heat and visible smoke
More informationREPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:
Page 1 of 10 TEST REPORT REPORT NUMBER: 102317918SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Road Elmendorf, TX 78112
More informationBURNING BRAND PERFORMANCE TEST REPORT. Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR (Acrylic Dome) VELUX SUN TUNNEL
BURNING BRAND PERFORMANCE TEST REPORT Rendered to: VELUX AMERICA, INC. SERIES/MODEL: TGF/TGR 022 0000 (Acrylic Dome) VELUX SUN TUNNEL ACCESSORY PRODUCTS: Tubular Skylight with ZTA 022 000090 9" Turrets
More informationFire Performance of Translucent Systems
Fire Performance of Translucent Systems ASTM E-108 Burning Brand Test on Quadwall Class A Approved Light Transmitting Plastics Fire Test Performance Meets Building Code Requirements: Self-Ignition ASTM
More informationTEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota
Architectural Testing TEST REPORT Report No.: D7913.05-121-24 Rendered to: 3M COMPANY St. Paul, Minnesota PRODUCT TYPE: Window Film SERIES/MODEL: 3M Scotchshield Ultra 800 TEST METHOD: ASTM E 84-11a, Standard
More informationTEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria
TEST REPORT Report No.: E6736.01-121-24 Test Date: May 6, 2015 Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria PRODUCT TYPE: Max Exterior F-Quality SERIES/MODEL: Décor. 0085 TEST METHOD:
More informationPERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome
PERFORMANCE TEST REPORT Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome Report No: D3964.01-106-31 Report Date: 06/19/14 Test Record Retention Date: 06/03/18 130 Derry Court York, PA
More informationFUNDERMAX GMBH FIRE TEST REPORT
FUNDERMAX GMBH FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON 19 MM MAX COMPACT REPORT NUMBER I0002.02-121-24 TEST DATE 01/29/18 ISSUE DATE 02/16/18 RECORD RETENTION END DATE 01/29/22 PAGES 10 DOCUMENT
More informationEffect of Rack Mounted Photovoltaic Modules on the Fire Classification Rating of Roofing Assemblies
Effect of Rack Mounted Photovoltaic Modules on the Fire Classification Rating of Roofing Assemblies Project Number: 08CA39594, 09CA40917 File Number: IN15911, R26475 Date: September 30, 2009 Revised February
More informationTech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5
INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5 5 Tech Notes TESTING PROTOCOL Fire Retardant Gel Coats Issue Date: 4/22/2010 Document ID: TN-TS-05A 2010 Interplastic Corporation Testing Protocol
More informationMaterials Testing by Gregory Havel
Materials Testing by Gregory Havel July 24, 2017 One of the most common tests cited in the technical bulletins on building materials is ASTM E84 Standard Method of Test of Surface Burning Characteristics
More informationSIGMADEK, LTD. FIRE TEST REPORT
SIGMADEK, LTD. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON ALUMINUM EXTRUSION DECK BOARD C/W PORCELAIN TILE INSERT REPORT NUMBER H5331.01-121-24 TEST DATE 09/13/17 ISSUE DATE 10/03/17 RECORD RETENTION
More informationIntertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008
Intertek I 0:: o D.. W 0:: I en w I REPORT NUMBER: 3161466SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: EVALUATION CENTER Intertek Testing Services NA Inc. 16015 Shady Falls Rd. Elmendorf,
More informationWe Identify and S.T.O.P. Your Noise Problems
ASTM E-84 TESTING FOR MANUFACTURER, RENDERED TO: Acoustical Surfaces Inc. 123 Columbia Court North, Suite 201 Chaska, MN 55318 Noise S.T.O.P. Fabrisorb Acoustical Wall Panels TESTED: OCTOBER 3, 2002 October
More informationThe Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
Retardants Inc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 21 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-8-913-9385 e-mail: info@fireretardantsinc.com
More informationPublic Comment No. 2-NFPA [ Section No ]
Page 1 of 13 Public Comment No. 2-NFPA 703-2013 [ Section No. 2.3.1 ] 2.3.1 ASTM Publications. ASTM International, P.O. Box C700, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. ASTM D 2898, Standard
More informationTitle: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: Indicative fire test WF Report
More informationTEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1
REPORT NUMBER: 101145164COQ-005 ORIGINAL ISSUE DATE: April 25, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO udecor Inc.
More informationFABRITRAK SYSTEMS, INC. FIRE TEST REPORT
FABRITRAK SYSTEMS, INC. FIRE TEST REPORT SCOPE OF WORK ASTM E84 TESTING ON POLYESTER INFILL REPORT NUMBER H5200.01-121-24 TEST DATE 08/31/17 ISSUE DATE 09/20/17 RECORD RETENTION END DATE 08/31/21 PAGES
More informationTechnical Training International Textiles Training September 2018 Ellen Roaldi Instructor
Technical Training International Textiles Training September 2018 Ellen Roaldi Instructor www.astm.org ASTM D1230 Flammability of Apparel Textiles Scope: This test method covers the evaluation of the flammability
More informationRENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy
REPORT NUMBER: 100900037COQ-002 ORIGINAL ISSUE DATE: October 10, 2012 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, BC V3K 7C1 RENDERED TO Laminam S.P.A.
More informationRENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3
REPORT NUMBER: 101207560COQ-001b ORIGINAL ISSUE DATE: June 12, 2013 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Vipco Industries
More informationPERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate
PERFORMANCE TEST REPORT Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate Report No: C7626.1-16-31 Report Date: 5/8/13 Test Record Retention Date: 5/8/17 PERFORMANCE TEST REPORT
More informationCertificate of Compliance
Certificate of Compliance This certificate is issued for the following: KS103SSF, KS103MSF, AND KS110CTF PANELS AS CLASS 1 INTERIOR WALL AND CEILING PANELS FOR INSTALLATION WITH NO HEIGHT RESTRICTION Prepared
More informationPERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product
PERFORMANCE TEST REPORT Rendered to: EVERBLOCK SYSTEMS, LLC PRODUCT: Modular Block Product Report No.: G1320.01-106-31 Report Date: 08/04/16 Test Record Retention Date: 07/29/20 130 Derry Court York, PA
More informationFIRE TESTING OF LOW SLOPE ROOF ASSEMBLIES AN INTERNATIONAL REVIEW
FIRE TESTING OF LOW SLOPE ROOF ASSEMBLIES AN INTERNATIONAL REVIEW Birgitte Messerschmidt Rockwool International A/S Denmark & John Scott Roxul Inc. Canada ABSTRACT Knowing the fire behaviour of roofs is
More informationRetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318
EST. 1860 RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318 952-448-7377 FAX:952-448-2613 Fire Retardant HOT LINE 1-800-913-9385 e-mail: info@fireretardantsinc.com
More informationASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"
UNCONTROLLED ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB" A Report To: Ciucevich 7200 Vermilion Ct. Wake Forest, NC 27587 USA Phone: (919) 570-291 E-mail:
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 153420 Date: 28 th April 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 153420 BS 476: Part
More informationTRANSLUCENT FIRE RATED SYSTEMS
28662 N. Ballard Drive Lake Forest, IL 60045 PHONE (800) 759-6985 FAX (847) 816-0425 TRANSLUCENT FIRE RATED SYSTEMS Committed to Fire Safety QUADWALL CLASS A IS SHOWN IN ACTUAL ASTM E-108 TESTS. ASTM E-108
More informationFire-resistance test on fire collars protecting a plasterboard wall penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire-resistance test on fire collars protecting a plasterboard wall penetrated by services Test Report Author: Peter Gordon Report number: FSP 1960 Date: 5 February 2019 Client:
More informationContact person Date Reference Page Richard Johansson P (2) Fire Research
issued by an Accredited Testing Laboratory Contact person Richard Johansson 215-8-13 5P4413 1 (2) Fire Research +46 1 516 56 75 richard.johansson@sp.se 12 ISO/IEC 1725 Sklejka-Pisz Paged S.A Ul. kwiatowa
More informationBS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited
BS 476: Part 3: 2004 External Fire Exposure Roof Test WF Report Number: 158117 Date: 13 th October 2006 Test Sponsor: Tapco Europe Limited 0249 Page 2 of 9 Warringtonfire Test Report No 158117 BS 476:
More informationOPERATING AND MAINTENANCE MANUAL
OPERATING AND MAINTENANCE MANUAL NVPOM-0104 TABLE OF CONTENTS Section Page 1 SPECIFICATIONS...1 1.1 Nova Plus Specifications...1-1 1.2 Warranty...1-2 2 GENERAL BURNER DESCRIPTION...2 2.1 Burner...2-1 2.2
More informationSOUTHWEST RESEARCH INSTITUTE
SOUTHWEST RESEARCH INSTITUTE 6220 CULEBRA ROAD 78238-5166 P.O. DRAWER 28510 78228-0510 SAN ANTONIO, TEXAS, USA (210) 684-5111 WWW.SWRI.ORG CHEMISTRY AND CHEMICAL ENGINEERING DIVISION FIRE TECHNOLOGY DEPARTMENT
More informationTEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Phone: (800) Fax: (800)
TEST REPORT ON CENTRAL STATES MANUFACTURING, INC. S CENTRAL-SNAP PANELS (24 GA., 1.75" HIGH, 16" WIDE PANEL) AT 5' 0" 3' 9" PANEL SPANS IN ACCORDANCE WITH ASTM E1646-95(2011) & E1680-11 TESTED FOR: Central
More informationFIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS
FIRE-RESISTANCE TEST ON DOWNLIGHT COVERS INSTALLED IN PLASTERBOARD CEILINGS Report number FSP 1290A CSIRO job number LP46ASP3085 Date of issue 30 NOVEMBER 2007 Client EFFICIENCY MATRIX PTY LTD and YOUNGEN
More informationFIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES
FIRE-RESISTANCE TEST ON FIRE COLLARS PROTECTING A PLASTERBOARD WALL PENETRATED BY SERVICES Report number FSP 1360 CSIRO job number SP3241 Date of issue 31 JULY 2009 Client SNAP FIRE SYSTEMS PTY LTD. Commercial-in-confidence
More informationTest Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13
Test Report No. AJHG1501000530FB Date: FEB.17, 2015 Page 1 of 13 ZHEJIANG TERASUN AIR DUCT CO., LTD MAREN VILLAGE, CHONGREN INDUSTRIAL ZONE, CHONGREN TOWN, SHENGZHOU CITY, ZHEJIANG PROVINCE, CHINA The
More informationRENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5
REPORT NUMBER: 3189147COQ-002 ORIGINAL ISSUE DATE: September 30, 2009 TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd. 1500 Brigantine Drive Coquitlam, B.C. V3K 7C1 RENDERED TO Radial Engineering
More information1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c
1.0 INTRODUCTION This report presents the results of a fire performance evaluation in accordance with the 2011 Edition of National Fire Protection Association (NFPA) Standard 265, Standard Methods of Fire
More informationUL 94 Flammability Ratings: Introduction
UL 94 Flammability Ratings: Introduction UL intends this standard to serve as a preliminary indication of a plastics acceptability for use as part of a device or appliance with respect to its flammability.
More informationEnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.
by NEENAH EnviroScape Mural pre-pasted printable wallcovering material EnviroScape Mural is a PVC free wall, window or hard surface scaping product that is pre-pasted with a water activated adhesive backing
More informationAbrasion Resistance of Fluoropolymer and polyester Coatings
Abrasion Resistance of Fluoropolymer and polyester Coatings British Standards British Standard 476 refers to fire tests on building materials and structures. The parts of this standard that are of most
More informationT-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh
PRODUCT SPECIFICATIONS GAS UNIT HEATERS / DUCT FURNACES TU T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ Bulletin No. 20402 November 207 Supersedes November 206
More informationTest Report No. AJD Date: JUN.09, 2013 Page 1 of 6
Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s)
More informationPERFORMANCE EVALUATION TEST REPORT. Rendered to: GREENFIELD MANUFACTURING COMPANY. PRODUCT: Hanger Screws
PERFORMANCE EVALUATION TEST REPORT Rendered to: GREENFIELD MANUFACTURING COMPANY PRODUCT: Hanger Screws Report No: Report Date: 01/12/11 Expiration Date: 12/28/14 Product: Hanger Screws PERFORMANCE EVALUATION
More informationASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet
UNCONTROLLED ELECTRONIC COPY ASTM D 635-14 Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet A Report To: Brett Martin Ltd. 24 Roughfort Road Mallusk, Co. Antrim United
More informationCLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009
P.O. Box 554 2665 ZN Bleiswijk Brandpuntlaan Zuid 16 2665 NZ Bleiswijk The Netherlands +31 88 3473 723 nederland@efectis.com CLASSIFICATION CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE
More informationLABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY
STAFF USE ONLY Thurston County Resource Stewardship 2000 Lakeridge Dr. S.W. Olympia, WA 98502 (360)786-5490 / (360)754-2939 (Fax) TDD Line (360) 754-2933 Email: permit@co.thurston.wa.us www.co.thurston.wa.us/permitting
More informationTitle: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves.
Title: Fire resistance test utilising the general principles of BS 476: Part 20: 1987 on four specimens of Uninsulated Air Valves Report No: 172158 Prepared for: Lindab Ventilation AB SE 26982 Båstad Järnvägsgatan
More informationResolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.
Public Input No. 1-NFPA 557-2012 [ New Section after 1.5.3 ] 1.6 Approved Qualifications The design shall be prepared by a person with qualifications acceptable to the AHJ. The term designer is used in
More informationCAN/ULC-S109 Flame Resistance of "Argo" Fabric
CAN/ULC-S109 Flame Resistance of "Argo" Fabric A Report To: Design/Craft Fabric Corporation 2230 Ridge Drive Glenview, IL 60025 USA Phone: Email: (847) 904-7000 x128 mboynton@design-craft.com Submitted
More informationASTM E 662 Rate of Smoke Generation of OXIFREE TM198"
ELECTRONIC COPY ASTM E 662 Rate of Smoke Generation of OXIFREE TM198" A Report To: Oxifree Global LLC 22955 State Highway 249, Suite 6 Tomball, TX 77375 USA Phone: (281) 251-7171 E-mail: ed.hall@oxifree.com
More information#5 Proposed Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-1011-R1 (RB/MB) John D. Nicholas Representing Background Relevant to AC179 18 Years in the Building
More informationGUARDIAN FIRE TESTING LABORATORIES, INC.
GUARDIAN FIRE TESTING LABORATORIES INC. Testing & Listing Field Labeling Page 1 of 5 Engineering & Product Certification Services Factory Inspections Guardian Fire Testing Laboratories, Inc. Phone: 716
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationBURNERS/ FLARES. VAREC BIOGAS 244W Series WASTE GAS BURNER & IGNITION SYSTEM
BURNERS/ FLARES VAREC BIOGAS 4W Series WASTE GAS BURNER & IGNITION SYSTEM The Varec Biogas 4W Series Waste Gas Burner is a highly reliable flare and ignition system ideal for use in burning excess biogas.
More informationStandard Laboratory Test Practice For Measurement Of Surface Appearance Change Of Textile Floor Covering As A Result Of The Vacuuming Process
CRI TM 114-110901 Standard Laboratory Practice for Carpet Surface Appearance Change Due To Vacuuming P.O. Box 2048 Dalton Georgia 30722-2048 706.278.3176 carpet-rug.org Standard Laboratory Test Practice
More informationFood Service Technology Center
Food Service Technology Center IR Energy Habanero HAB-M50 Gas Patio Heater Test Report Application of ASTM Standard Test Method FF2644-07 September 2014 Prepared by: Elan Frantz Trey Young Fisher-Nickel,
More informationASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS
ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS SPANK 9901101 REPORT NO. 75157 Septemer 11, 00 Prepared For: Pollack 150 Varick Street New York, NY 10013 F-316-A 555 76TH STREET S.W., GRAND RAPIDS.
More informationSubmittal Data Performance Data Electrical Data
ERMS Series Submittal Data Submittal Data Unit Designation: Job name: Architect: Engineer: Contractor: Performance Data Revision: 07/01/11 Cooling Capacity: EER: Heating Capacity: COP: Ambient Air Temp:
More informationCHAPTER 5: EXHAUST SYSTEMS
MOTORS, FANS AND FILTERS 503.1 General. Motors and fans shall be sized to provide the required air movement. Motors in areas that contain flammable vapors or dusts shall be of a type approved for such
More informationGASEOUS HYDROGEN SYSTEMS
CHAPTER 7 GASEOUS HYDROGEN SYSTEMS SECTION 701 GENERAL 701.1 Scope. The installation of gaseous hydrogen systems shall comply with this chapter and Chapters 30 and 35 of the Fire Compressed gases shall
More informationRooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options
2016 NFPA Conference & Expo Rooftop Photovoltaic (PV) Systems Examining the Risks and Researching the Options Presented by: Joel Sipe Senior Managing Engineer Exponent Inc. Outline Project Background Fire
More informationDetermination of Fire Exposure Heat Flux in Cable Fire Tests
Determination of Fire Exposure Heat Flux in Cable Fire Tests PRAVNRAY D. GANDH Underwriters Laborator~es nc 333 Pfingsten Rd. Northbrook, L 60062, USA LOREN CAUDLL and JAMES HOOVER Du Pont, Chestnut Run
More information3rd International Conference Polymers in Mining", University of Lancaster, United Kingdom (The Plastics and Rubber Institute), September 26-27, 1989
3rd International Conference Polymers in Mining", University of Lancaster, United Kingdom (The Plastics and Rubber Institute), September 26-27, 1989 FIRE HAZARD EVALUATION OF MINE CONVEYOR BELTS BY: Harry
More informationCAN/ULC-S109 Flame Resistance of "Xanadu" Material
CAN/ULC-S109 Flame Resistance of "Xanadu" Material A Report To: Design/Craft Fabric Corporation 2230 Ridge Dr. Glenview, IL 60025 USA Phone: (847) 904-7000 E-mail: mboynton@design-craft.com Attention:
More informationFire resistance test on fire collars protecting a concrete slab penetrated by services
INFRASTRUCTURE TECHNOLOGIES Fire resistance test on fire collars protecting a concrete slab penetrated by services Test Report Author: Mario Lara Report number: FSP 1601a Date: 11 April 2014 (This report
More informationSP METHOD 5320 Issue No: Test method for fire detection systems installed in engine compartments of heavy vehicles
SP METHOD 5320 Test method for fire detection systems installed in engine compartments of heavy vehicles Page 1(17) Copyright This test method is copyrighted by SP. Neither a printed nor electronic copy
More informationContents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...
Contents Page No Page 1 of 14... 1 1 Introduction... 3 2 Specimen verification... 3 3 Description of supporting constructions... 3 4 Description of specimen... 3 4.1 Air transfer grille blocks... 3 5 Test
More informationFire Test Methods ASTM NFPA UL ISO IEC
Fire Test Methods ASTM NFPA UL ISO IEC D2859 (Standard Test Method for Ignition Characteristics of Finished Textile Floor Covering Materials) E84 (Standard Test Method for Surface Burning Characteristics
More informationCAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"
ELECTRONIC DRAFT COPY CAN/ULC-S12 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel" A Report To: ABET Corporation 5 Paxman Road, Unit 1 Toronto, Ontario M9C 1B7
More informationIn Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa
In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by Norman Alvares & Harry Hasegawa First Paragraph of E-691 Tests performed on presumably identical materials in presumably
More informationASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009
ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC #100-3191-1 TESTED: MARCH 27, 2009 April 2, 2009 Client: Attention: Cole Motorsports/CM Racing Products
More informationSUBMITTAL SCHEDULE & DATA
SUBMITTAL SCHEDULE & DATA Gas- and Oil-Fired Unit Heaters, Infrared Heaters, and Indoor Duct Furnaces Job Name: Date: 10/31/2016 Location: Engineer: Submitted by: Jeff Musto Architect: Contractor: Model
More informationCOMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ. Steady-State Efficiency - up to 81% Input - 30,000 to 75,000 Btuh
GAS UNIT HEATERS / DUCT FURNACES LF24 COMPACT UNIT HEATERS Low Profile - Horizontal - 60 HZ PRODUCT SPECIFICATIONS Bulletin 2008 July 206 Supersedes October 20 Steady-State Efficiency - up to 8% Input
More informationBy Authority Of THE UNITED STATES OF AMERICA Legally Binding Document
By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has
More informationThis document is a preview generated by EVS
TECHNICAL REPORT RAPPORT TECHNIQUE TECHNISCHER BERICHT CLC/TR 50670 December 2016 ICS 13.220.50; 27.160; 91.060.20 English Version External fire exposure to roofs in combination with photovoltaic (PV)
More informationFurenflex RWV Advanced Liner
Furenflex RWV Advanced Liner To BS EN 1443:2003 Report 55942/1 Carried out for Kompozitor Ltd. By Dave Butler 08 June 2012 Furenflex RWV Advanced Liner To BS EN 1443:2003 Carried out for: Kompozitor Ltd.
More informationClassification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:
Classification of reaction to fire performance in accordance with EN 13501-1: 2007 +A1: 2009 on Superfoil SFNC Prepared for: Boulder Developments Ltd Black Horse Farm Main Street Norwell Nottinghamshire
More informationCAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"
UNCONTROLLED ELECTRONIC COPY CAN/ULC-S12 Surface Burning Characteristics of "ezobord 9 mm (Green)" A Report To: ivekter Inc. 1625 Drew Rd. Mississauga, Ontario L5S 1J5 Phone: 416-665-3571 Attention: E-mail:
More informationCAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"
ELECTRONIC DRAFT COPY CAN/ULC-S12.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate" A Report To: Polygal Plastics Industries, Ltd. Ramat Hashofet 19238 Israel Phone: 972-4-9596271 Email:
More informationUp on the Roof Fire Prevention BY David Laks, P. Eng., CFPS, ARM, RRC
Up on the Roof Fire Prevention BY David Laks, P. Eng., CFPS, ARM, RRC Every year there are a significant number of roof fires resulting from installation, neglected maintenance, or housekeeping. This article
More information25 th November Title:
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Fire Resistance Performance
More informationGUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS
12 December 1996 Ref. T4/4.01 GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS 1 The Maritime Safety
More informationTEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Telephone: (800) Fax: (800)
TEST REPORT ON CENTRAL STATES MANUFACTURING, INC. S R-LOC PANELS (26 GA., 80 KSI, 36" WIDE) AT 5' 0" 3' 9" PANEL SPANS IN ACCORDANCE WITH ASTM E1646-95(2011) & E1680-11 TESTED FOR: Central States Manufacturing,
More information+ = FIRE LABORATORY INTRODUCTION. APPLUS+ LGAI - Our company history. High Technology Knowledge. Customer Confidence. Branding
INTRODUCTION APPLUS+ LGAI - Our company history As a brief resume of our history LGAI - Laboratori General d'assaigs i Investigacions (whose commercial name was LGAI Technological Center) was fully owned
More informationShown in Colonial Slate
C e r t a i nte e d D e s i g n e r S h i n g l e s Shown in Colonial Slate Shown in Weathered Wood You know it, when you see it. It s not just a roof. It s a CertainTeed roof. Quality. Durability. Style.
More informationSouthern California Gas Company Customer Programs Department
Appliance Test Report SCGAT140220A Revision 0 Issued Date: March 2014 Duke 613Q-G1V Gas Convection Oven Performance Test Per ASTM F1496-13 Southern California Gas Company Customer Programs Department Food
More informationUPHOLSTERED FURNITURE AND MATTRESSES IN NEW AND EXISTING BUILDINGS
Page 20 ABOUT CODE CORNER CCFS would like to remind you to check with your local Authority Having Jurisdiction (AHJ) for questions and opinions concerning your local Fire and Building Codes. The information
More informationUltrasonic Clamp-On Flow Meter Testing
Ultrasonic Clamp-On Meter Testing Carried out for Micronics Ltd By Colin Judd Ultrasonic Clamp-On Meter Testing Carried out for: Micronics Ltd Unit B4 Business Centre Davies Way Loudwater High Wycombe
More informationAd-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0 1925 655116 F : +44 (0) 1925 655419 E : warrington@exova.com W: www.exova.com Ad-hoc IEC 60331-2 x Ad-hoc investigation
More informationNEW NEW. CertainTeed. Designer Shingles. Warranties. Shown in Max Def Weathered Wood
CertainTeed NEW NEW Lifetime Lifetime Limited Limited Warranties Warranties Designer Shingles Shown in Max Def Weathered Wood takes roofing to a higher level Shown in Max Def Weathered Wood SO MUCH DEPENDS
More informationDraft for Comment Please comments to Part A(i)
Draft for Comment Please email comments to info@plcouncil.com.au Part A(i) PRODUCT SPECIFICATION OF PHOTOLUMINESCENT EXIT SIGNS (v2.1) SECTION 1 - PRINCIPLES 1.1 Scope This standard sets out the product
More information