FIRE DOORS RHUL REQUIREMENTS

Size: px
Start display at page:

Download "FIRE DOORS RHUL REQUIREMENTS"

Transcription

1 Fire Safety Technical Guide FIRE DOORS RHUL REQUIREMENTS This guide draws together the general requirements of a range of published standards and reference documents and is to be used in addition to any other requirements from the Local Fire or Building Control Authority/Approved Inspector. Its purpose is to ensure that the College operates a consistent approach to fire safety. Where any doubt exists as to the action to be taken, or advice or assistance is required, contact should be made with the College Fire Safety Officer. 1 FIRE DOORS (FUNCTION AND STANDARDS) 1.1 Function Fire doors are required to perform two main functions; a) To maintain any compartmentation of a building, which has been introduced to limit the size and spread of fire in order to control the perceived risk (this will include areas of high fire risk such as Plant Rooms, Kitchens, Service Ducts, Workshops etc); b) To allow access to protected escape routes, both vertically and horizontally, without any loss of fire resistance, and limit smoke movement in the structure forming these routes, (this will include Protected Corridors, Staircases, Lobbies, Shafts, Dead-end escape areas etc) In addition, all doors to sleeping accommodation will be Fire Doors. 1.2 Standards and Guidance Reference documents Reference is made here to BS Code of Practice for Fire Door Assemblies, which makes recommendations regarding the significant parameters governing the design and use of fire door and frame sets. The rating for a fire door is derived from its performance when tested in accordance with BS (or BS EN ) and is judged by the time it takes to fail for both integrity and insulation. However, regulatory guidance will only refer to a door s performance for 1

2 integrity, hence the designation FD30 for a door able to resist failure for 30 minutes. A fire strategy might require a door to also meet the criteria for insulation, in which case the designation will be FD30/30. Certain doors are also required to restrict the spread of ambient (cold) smoke and will be identified by the suffix S, having been tested in accordance with BS (or BS EN ). The guidance on where a fire door will be required and what rating it should have is given in: a) Approved Document B (often simply known as ADB) of the Building Regulations or; b) BS Code of practice for fire safety in the design, management and use of buildings - where a risk-based approach is adopted; or c) BS Application of fire safety engineering principles to the design of buildings for fire engineered strategies Design standards and documentation The following paragraph, taken from BS8214, forms an essential part of the process of project management for new buildings or extensions to existing buildings. It should also be followed when an alteration or addition is made to an existing building, which involves the installation of a new fire door. The building designer should ensure that all fire doors to be used are of a design that has been tested or assessed for the required fire resistance period, and that documentary evidence exists to that effect. Where the elements of a fire door are to be obtained from different sources, the building designer should ensure that the elements to be used are compatible and are able to provide the required fire resistance period, and that documentary evidence exists to that effect. Before proceeding with contractual commitments it should be established that evidence of performance exists which meets with the approval of the enforcing authority. Project Managers must be aware that the provision of the correct documentary evidence plays a vital role in supporting the Fire Risk Assessment of a building, as the College must be able to produce such evidence when requested by the Fire Authority. Any person, who is required to install a fire door (with or without frame), must produce documentary evidence to support the rating and performance of that door and/or frame Installation Doors and Frames The failure of doors under fire conditions usually occurs either at the gap between the door and the frame, or at one or more of the points where building hardware is fixed (particularly at the hinges or lock positions) or, in the case of glazed doors, at the line of the junction between the glazed area and the rest of the door. For this and other reasons, it is particularly important to ensure that doors installed on site conform, in dimensions and workmanship, to the manufacturer s specification for the appropriate fire resistance test report/assessment. 2

3 Doors should be hung to give an equal gap across the head and down both jambs. A typical gap to achieve good fire performance is between 2 mm and 4 mm. Certain smoke seals might require a larger gap in order to operate without causing significant frictional increases, but the gap should remain within tested tolerances. The selection and installation of door frames is as important as the door itself. Ideally the two should be matched and supplied as a complete unit, as the fire resistance of one may depend on the design features of the other. In order to maintain the fire resistance of a fire-resisting wall or partition, and the frame of a door assembly, the joint between the two elements should be adequately sealed. Tables 2 and 3 of BS provide recommendations on tolerances and infilling of this joint. Doors should be hung to ensure a good fit to the frame when closed and the junction between door assembly and surrounding structure should be adequately sealed. Care needs to be taken when adding smoke seals as these can inhibit the complete closing of the door if not fitted correctly. HINGES Unless otherwise specified by the Manufacturer, a Fire Door will be hung on a minimum of THREE metal hinges with a melting point of not less than 800 C 2 FIRE DOORS (GENERAL) 2.1 Direction of escape Any door forming part of an escape route should open in the direction of escape travel. This is an absolute requirement if the number of people expected to use it exceeds 60. If that door is also a Fire Door, it should be rebated into a frame and have the required intumescent and smoke seals. It should not be a double swing door unless it is a mid-corridor smoke check door, which may be double-swing but must be fitted with smoke seals. 2.2 Intumescent Materials and Smoke Seals Door edges are the part of a door-set most susceptible to penetration by heat and smoke because the pressure of a developing fire drives hot gases between the door and frame, leading to loss of integrity. This used to be countered by the use of a large (25mm) doorstop, but this relied heavily on a very close fit between the door and frame. The modern solution is to use a strip of intumescent material, set into either the door edges or the frame opposite the edges. At around 100 C this will expand to fill the gap between the door and the frame, thus maintaining its integrity. Several points must be considered in their use: If a door has achieved a rating when tested with intumescent materials, then it must be supplied complete with them There are several different types, so the correct type, as specified by the manufacturer of the door-set, must be used. Different types are not interchangeable. 3

4 They may be fitted either in the door frame or the door edges. They must be applied to both vertical edges and the top; they are not required along the bottom edge Where a door is also required to have smoke seals the best solution is to use a combined strip. The Brush type is preferred to the rubber blade type as experience has shown that they are longer lasting. At no time are these strips to be overpainted as this causes them to harden and lose their ability to perform When fitting strips and seals they must not be altered in shape or size, as this will reduce their effectiveness On doors up to FD30 rating it is acceptable to interrupt the strip for hinges or latches On doors over FD30 rating, where double strips are required, one may be interrupted but the other must be continuous When these strips are used, it is no longer necessary to provide an oversized doorstop. A standard 12mm planted stop is acceptable Concealed Intumescent - Several manufacturers offer door assemblies in which pressureforming intumescent material is concealed behind the timber lipping of the door leaf. In such cases, the manufacturer s documentation must be provided and no attempt is to be made to plane the edges of these doors or route them to apply further seals. If smoke seals are also required, they must be fitted to the door frame. 2.3 Self-Closing Devices Fire doors can only operate correctly if they are fully closed at the time of fire. It is, therefore, normally necessary for them to be fitted with a self-closing device. A Fire door, except to a cupboard or service duct (both of which are normally kept locked shut), should be fitted with a self-closing device (other than rising-butt hinges) that should: a) be of a type that cannot readily be disconnected or immobilized and does not embody a mechanical hold-open facility unless it automatically releases the door in a fire situation; and b) override any latches fitted to the door or, in the absence of a suitable latch or other positive device for holding the door shut in its frame, be of a type that, when tested in accordance with BS or BS or BS EN , is shown to be able to hold the door closed in the frame for a sufficient period of time for the closing role to be taken over by a thermally activated sealing device (e.g. an intumescent seal), or throughout the full period of exposure if such seals are not incorporated; and c) conform to BS EN The strength and control of the closing device should be compatible with the size of the door, and any other factors, such as resistance from latches and air pressure, heavy traffic use, abusive treatment, use by disabled persons. Perko style closers are not normally acceptable (RHUL Fire Safety Officer must be consulted if no other option is practicable) 4

5 2.4 Air Transfer Grilles Where a fire door is required to be fitted with an air transfer grille, it should only be fitted with one that is capable of sealing both by thermal initiation and by interface with smoke sensors either directly or via a fire alarm panel. Mechanical fire-resisting air transfer grilles are closed by the activation of a thermal release mechanism usually preset to operate between 70 C and 74 C. The majority of fire doors now require smoke control and consequently any fire-resisting air transfer grille fitted should also be able to seal automatically when activated by interface with smoke sensors or a fire alarm panel. The installation of air transfer grilles should only be undertaken when full fitting instructions and relevant wiring diagrams are available, and should only be undertaken by competent persons. In the case of electrically interactive air transfer grilles, the installer should liaise with the persons responsible for the fire alarm panel or building management system. All air transfer grilles should be installed in accordance with the manufacturer s installation and commissioning instructions. 2.5 Hardware Building hardware falls into two categories: essential and non-essential. The selection of building hardware is vital to the performance of fire-resisting doors and it should be selected and fitted with care in accordance with the manufacturer s instructions. Essential hardware Items vital to the fire resisting performance of the door, which would include Hinges/Pivots, a Latch and a Self-Closing Device. Non-essential hardware Items not vital for fire-resistance but might be vital for means of escape or general fire performance, including Handles, Automatic Release Mechanisms, and Push Bars. All door furniture should be fitted in such a way as to ensure that the fire-resisting properties of the doorset are not compromised. It is recommended in most instances that building hardware be bedded in intumescent mastic or pre-shaped intumescent pads to restrict heat transfer to the door edge via the metal products. Interruption of intumescent seals at the positions of building hardware should be avoided where possible. Locks and Latches Any door forming part of an escape route should open in the direction of escape travel. This is an absolute requirement if the number of people expected to use it exceeds 60. It should be easily and readily openable without the need for a key or other separate device. If a Security Risk Assessment has recommended that the door be locked, then that lock must be easily overcome by a single action lever type handle or other opening device. If the door 5

6 is fitted with an Electromagnetic type locking device it must comply with the requirements of BS :2007, the significant elements of which require that: a) the lock defaults to the open position in the event of any power failure or short circuit b) the lock opens on actuation of the fire alarm system c) the lock is provided with a manual override (green box break glass) adjacent to the door. Disability Considerations Locking devices associated with Thumb turns should be avoided. It should be possible to operate all door-opening furniture one-handed, without the need to grasp or twist. Care should be taken in the selection of security and fire exit fittings, such as short lever turn buttons, bolts, latches or locks, with the aim of making them manageable for all users. Wherever possible, door opening furniture used in conjunction with locks and latches should have a lever action. Knobs with a spherical, circular or similar design, as well as small symmetrical turn buttons, are difficult to use by people with limited dexterity, arthritis or a weak grip. 2.6 Glazing Vision Panels In general, a vision panel should be provided in any door in an escape route, circulation route, corridor, stair enclosure, lobby etc. and in any double-swing door. Additionally, a vision panel should be provided in: a) a door to an Inner Room, where fire detection is not provided in the Access Room b) in doors to laboratories, kitchens and similar areas where hazardous items are regularly carried through the doors Where a vision panel is provided to comply with Disability Access requirements, Approved Document Part M of the Building Regulations must be consulted. Where the need for privacy or technical reasons is paramount, a vision panel may be omitted, provided a suitable fire risk assessment is carried out Fire-resisting glazing Fire-resisting glazing is categorised in two performance criteria as tested in accordance with BS or BS EN : Integrity is able to resist the passage of fire, heat and smoke by remaining intact for a specified period Insulation is able (in addition to the integrity performance) to resist the transfer of heat through the glass so that the non-fire side remains cool. 6

7 Restrictions apply to the use of non-insulating fire-resisting glazed elements because of the risks that they pose from their relative inability to afford adequate protection against transmitted heat. In this respect there are four possible hazards to consider, even if the integrity of the glazed element as a flame and smoke barrier is maintained. These are: Direct exposure to potentially high levels of radiant heat with the risk of burns to exposed skin; Convective heating of the atmosphere in the escape way; Smouldering smoke generation (before ignition) from floor coverings, fixtures and fittings in the corridor; Secondary ignition and flaming of fixtures and fittings in the escape way. The limitations on the use of Non-insulating glazing are shown in BS9999 (table 29) and ADB. Glazing able to provide insulation properties may be used without any restrictions. There are many products on the market which go by a variety of trade names. Those which provide Integrity only are: Pyrostem; Pyroshield; Firelite; Keralite; Vertroflam; Pyroswiss; Pyrocet; Pyrosec; Tempaflam; Fireswiss; Pyroguard; Pyrobelite; Pyrodur; Contraflam; Pyran. (other products may be available) Those which provide both Integrity and Insulation are: Pyrobel; Pyrostop; System Glass; Pyranova; Pyraflam. (other products may be available) All fire-resisting glass should be marked, as a minimum, with an identifiable name or trademark, or other mark, capable of unambiguous identification to the manufacturer or supplier. For example, this could be a product name (as above), manufacturer s name or code. Safety Glass glazing that is marked BS6206:1981 or BS6262 is not fire-resisting glazing and the College Fire Safety Officer will require this to be replaced where appropriate. The College will also require documentary evidence detailing the performance of the glazing as it has been used in situ (and not a general certificate of performance for the product). Glazed apertures can potentially be the weakest part of any fire door if glazed incorrectly. For this reason, factory-glazed doors should be used wherever practicable, rather than glazing on site. Some integrity-only glasses, most notably modified toughened glasses, are sensitive with regard to edge cover and bead profile, and should always be installed in accordance with the manufacturer s instructions. Insulating glasses are more tolerant of glazing methods, but the bead fixings are critical and again the advice of the manufacturer should be sought and followed. Only complete tested glazing systems should be used. These should identify the glass product type and thickness, glazing seals, beads and fixings. Components within a glazing system should not be interchanged without relevant test evidence. 7

8 Due allowance should be made for expansion between glass edge and aperture. It is important, therefore, that apertures are cut accurately as recommended by the manufacturer. To meet the requirements of some independent certification schemes, the cutting of apertures for glass on site, is not permitted. Any cut-outs made to a door are likely to invalidate its certification. 2.7 Signage All Fire Doors MUST be provided with signs in accordance with BS ISO 7010:2011. These will be a minimum of 100mm x 100mm and preferably in rigid plastic, but maybe produced in other materials appropriate to the surface or the building design. Sign Description Positioned at eye level, on both sides of each fire door fitted with a selfclosing device. Positioned at eye level on the outer face of a fire door to a cupboard, store, plant room, riser etc, which does not have a self-closing device. Positioned at eye level on the visible face of a fire door which is fitted with a self-closer, but is held open by a device which releases the door on activation of the fire alarm. This is to prevent the door from being obstructed and unable to close. 3 KEY TO TERMINOLOGY AND ABBREVIATIONS Key Description Key Description FD30 A Fire Door with 30 minutes Integrity and Insulation properties (also shown as FD30/30) and complete with Intumescent Strips. FD60 Intumescent strips. (s) FRG30/60 VP Smoke Seals (use brush type, as these wear better than rubber blade type) often combined with the intumescent strips. Fire Resisting Glazing (30 or 60 minutes standard) Vision Panel required (if within a Fire Door, then must be FRG30/60 as above) SC FD30(s) SC & VP PB A Fire Door with 60 minutes Integrity and Insulation properties (also shown as FD60/60) and complete with Self-Closing Device complying with BS EN 1154: Door Closers Fire Door 30/30 with Intumescent Strips and Smoke Seals (usually combined), a Self- Closing Device and a Vision Panel. Push Bar/Panic Bar Emergency opening device complying with BS EN

9 General view of a Fire-resisting door and associated furniture (taken from the DCLG Guide to Fire Risk Assessment in Educational Premises) Alan Oakes Fire Safety Officer 01/05/2012 Version 1 9

IDD 033C - Fire door sets

IDD 033C - Fire door sets IDD 033C - Fire door sets Why are fire door sets important? Fire doors are one of the most important features of a building s fire precautions and have two key functions: To protect escape routes from

More information

FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS

FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS Fire Safety Technical Note FIRE DOORS - GENERAL UCL OVERVIEW AND REQUIREMENTS Fire Door Provision In UCL Buildings - what you need to know: Mandatory - all doors on main traffic and circulation routes,

More information

Regulatory Reform (Fire Safety) Order 2005

Regulatory Reform (Fire Safety) Order 2005 Regulatory Reform (Fire Safety) Order 2005 This document has been prepared by ASDMA (Architectural & Specialist Door Manufacturers Association) to provide for guidance for Responsible Persons in respect

More information

GENERAL FIRE SAFETY TERMS & DEFINITIONS

GENERAL FIRE SAFETY TERMS & DEFINITIONS UCL Fire Technical Note - TN006 Fire Safety Technical Guide GENERAL FIRE SAFETY TERMS & DEFINITIONS Reference: BS4422-2005 Fire Safety Vocabulary - for further information and definitions BS EN ISO 13943-2000:

More information

Specification, installation & maintenance of fire doors: Technical Note 2

Specification, installation & maintenance of fire doors: Technical Note 2 Specification, installation & maintenance of fire doors: Technical Note 2 March 2016 You & Your Care \\raptor\user data\users\kbyard www.bdct.nhs.uk Karen Byard: Fire Officer Tel: 07946 413 331 Karen.byard@bdct.nhs.uk

More information

A Guide to the Selection of Smoke Seals for Doorsets. Information Sheet No. 5. Intumescent Fire Seals Association

A Guide to the Selection of Smoke Seals for Doorsets. Information Sheet No. 5. Intumescent Fire Seals Association Information Sheet No. 5 Intumescent Fire Seals Association A Guide to the Selection of Smoke Seals for Doorsets THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Introduction 1 Purpose of smoke seals

More information

Managing Fire Safety in your building: Fire Doors Inspections. Part of the KCC Architectural Group

Managing Fire Safety in your building: Fire Doors Inspections. Part of the KCC Architectural Group Managing Fire Safety in your building: Fire Doors Inspections Part of the KCC Architectural Group 2 Fire Door Inspections 3 The unavoidable truth Fire doors are a crucial part of any public, commercial

More information

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house

Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house Schedule of works required for Fire Protection in a 2 Storey semi-detached/terraced house THIS DOES NOT COVER 3 STOREY PROPERTIES you must consult with the Private Sector Housing Team on any 3 storey property.

More information

Guide to Fire and Escape Doors: Part 1 - What are they? Produced by the Guild of Architectural Ironmongers Sponsored by Abloy UK

Guide to Fire and Escape Doors: Part 1 - What are they?  Produced by the Guild of Architectural Ironmongers Sponsored by Abloy UK Guide to Fire and Escape Doors: Part 1 - What are they? Produced by the Guild of Architectural Ironmongers Sponsored by Abloy UK www.gai.org.uk Introduction This will be a brief overview of the subject,

More information

1.4 Provide and fix the following ironmongery.

1.4 Provide and fix the following ironmongery. Schedule of works required for Fire Protection in a first & second floor purpose built masionette above shops where the exit door is at first floor level. THIS DOES NOT COVER NORMAL 3 STOREY PROPERTIES

More information

Practice Guidee No.1. of the

Practice Guidee No.1. of the Intumescent Fire Seals Association Good Practice Guide No. 1 The Fire Risk Assessors Good Practice Guidee No.1 Guidance to risk assessors in respect of the use of intumescent door sealss THE HOME OF REACTIVE

More information

Guide to the use of Smoke Seals in Doorsets

Guide to the use of Smoke Seals in Doorsets Information Sheet No. 3 Intumescent Fire Seals Association Guide to the use of Smoke Seals in Doorsets THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Effect of Smoke 1 The Role of the Doorstop 1

More information

Fire Door Maintenance Guide.

Fire Door Maintenance Guide. Fire Door Maintenance Guide http://www.c-sgroup.co.uk/products/acrovyn-impact-resistant-doors/ Introduction Fire Doors are a critical safety feature of any building in which people work or visit, as they

More information

Maintenance. Why Maintain Fire Doors? Regulations

Maintenance. Why Maintain Fire Doors? Regulations Introduction Fire doors are commonly overlooked as an essential part of a commercial or public building maintenance regime. However, fire doors help sub-divide a building into compartments, slowing down

More information

fire doors the burning issues From specification to maintenance the life cycle of a fire door explained guide

fire doors the burning issues From specification to maintenance the life cycle of a fire door explained guide fire doors the burning issues From specification to maintenance the life cycle of a fire door explained guide Passive Fire Protection Passive fire protection products are built into the fabric of a building,

More information

FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES

FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES FIRE SAFETY MANAGEMENT PROTOCOL FIRE DOORS & FIRE DOOR ASSEMBLIES This is a new procedural document, please read in full. Did you print this document yourself? The Trust discourages the retention of hard

More information

Fire Doors Technical Guidance

Fire Doors Technical Guidance Fire Doors Technical Guidance Introduction Buildings are compartmented to delay the spread of fire from one area to another. The compartments are usually linked by doors to allow for passage of traffic

More information

Fire Protection. Intumescent fire and smoke seals for door assemblies

Fire Protection. Intumescent fire and smoke seals for door assemblies Fire Protection Intumescent fire and smoke seals for door assemblies Intumescent Seals Fire Protection Quality you can trust Exitex offer a wide range of fully tested intumescent strips, glazing seals

More information

Fire Risk Assessment

Fire Risk Assessment Fire Risk Assessment Maritime Studios Pendennis Rise Falmouth TR11 4FB Carried out by: Date: October 2015 Review Date: October 2016 Les Carter CMIOSH Health & Safety Consultant Mobile 07831 636751, Email

More information

30 Minute Firedoor. 30 minute firedoor

30 Minute Firedoor. 30 minute firedoor 30 minute firedoor 30 Minute Firedoor Rockdoor design and manufacture bespoke 30 minute accredited Firedoors in a pre-hung fire door set, helping house builders, local authorities and contractors to meet

More information

Fire doors guidance. Provided by

Fire doors guidance. Provided by Fire doors guidance Provided by Contents 1. Scope... 3 2. Introduction... 3 3. Where you could find a fire door... 4 4. Doors not required to be fire doors... 5 5. Which way should a fire door open?...

More information

CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS

CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS CHAPTER 5 - STRUCTURAL FIRE PRECAUTIONS 5.1 General In the previous chapter, the importance of protecting escape routes from penetration by smoke and fire was discussed, so as to ensure they can be safely

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT HORSEFAIR HOUSE FIRE RISK ASSESSMENT HORSEFAIR HOUSE BUILDING SUMMARY The building is utilised for the teaching of Science and contains Laboratories and Chemical storage. 1. Identification of the hazards 1.1 Identification

More information

THE INSTITUTE OF HEALTHCARE ENGINEERING AND ESTATE MANAGEMENT FIRE SAFETY TECHNICAL PLATFORM (FSTP) LIBRARY OF TECHNICAL GUIDANCE. No 2.

THE INSTITUTE OF HEALTHCARE ENGINEERING AND ESTATE MANAGEMENT FIRE SAFETY TECHNICAL PLATFORM (FSTP) LIBRARY OF TECHNICAL GUIDANCE. No 2. THE INSTITUTE OF HEALTHCARE ENGINEERING AND ESTATE MANAGEMENT FIRE SAFETY TECHNICAL PLATFORM (FSTP) LIBRARY OF TECHNICAL GUIDANCE No 2. FIRE DOOR PPM Introduction The FSTP has at its core, to act as the

More information

FP-PGN-14 Part of NTW(O)41 Fire Policy

FP-PGN-14 Part of NTW(O)41 Fire Policy Fire Policy Practice Guidance Note Fire Evacuation in Trust Owned and Occupied Premises V02 Date Issued Issue 1 Aug 2017 Planned Review Aug - 2020 Responsible Officer Head of Estates & Facilities (NTW

More information

Panic and Emergency Exit Devices

Panic and Emergency Exit Devices Panic and Emergency Exit Devices BS EN 1125: 2008 & BS EN 179: 2008 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Panic and Emergency Exit Devices BS EN 1125: 2008 & BS EN 179: 2008 dhf

More information

Unit 2 Fire Safety (Zone 1)

Unit 2 Fire Safety (Zone 1) IFE Level 3 Diploma in Fire Safety and Fire Science Unit 2 Fire Safety (Zone 1) Examiner Report March 2018 Introduction 42% of candidates attained a Pass. Half of the candidates that attained a Pass secured

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY) BUILDING SUMMARY The building was constructed in Victorian times and is constructed of brick with knapped flint in fill on some outer walls. The building

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NEW BUILDINGS FIRE RISK ASSESSMENT NEW BUILDINGS BUILDING SUMMARY The building is utilised for classroom teaching for Modern Languages. 1. Identification of the hazards 1.1 Identification of sources of fuel. Timber

More information

Cl/SfB (32.5) Ro8 (K2) Fire Resistant Glazing Systems

Cl/SfB (32.5) Ro8 (K2) Fire Resistant Glazing Systems Cl/SfB (32.5) Ro8 (K2) Fire Resistant Glazing Systems protecting against smoke and fire Fire and smoke protection measures are essential, lifesaving precautions in a building. What s more, they protect

More information

BWF-Certifire Fire Doors and Doorsets. Best Practice Guide

BWF-Certifire Fire Doors and Doorsets. Best Practice Guide BWF-Certifire Fire Doors and Doorsets Best Practice Guide 1 BWF-Certifire BWF-Certifire: The leading authority on fire door safety A fire door is a vital safety device engineered to save lives and property.

More information

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan

Fire Risk Assessment. Index. Part 1 Introduction Part 2 The Fire Risk Assessment Part 3 The Management Action Plan Fire Risk Assessment Worksafe Solutions Consultancy Ltd 67 Flitwick Road Maulden Bedfordshire, MK45 2BJ Tel: 01525 406787 email enquiries@worksafesoultions.co.uk Index Part 1 Introduction Part 2 The Fire

More information

Fire Enforcement Report

Fire Enforcement Report AGENDA ITEM 4.4 Fire Enforcement Report Executive Lead: Director of Planning Author: Senior Fire Safety Adviser, Capital Planning & Estate Management Contact Details for further information: Frank Barrett,

More information

Fire precautions in dwellings

Fire precautions in dwellings NORWICH City Council Fire precautions in dwellings Private sector housing Providing homes building communities Version 2 Published by Norwich City Council June 2010 Contents Page Introduction 1 2 Types

More information

Life Safety and Fire Resistant Glazing Systems

Life Safety and Fire Resistant Glazing Systems Life Safety and Fire Resistant Glazing Systems Kevin Hulin CEO, Mann McGowan Group Agenda GGF Introduction GGF and The Fire Resistant Glazing Group (FRGG) Fire Testing, Reports, Assessments and 3rd Party

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

Code of Practice: Hardware for Fire and Escape Doors. Issue No.2 June 2006 THE GUILD OF ARCHITECTURAL IRONMONGERS

Code of Practice: Hardware for Fire and Escape Doors. Issue No.2 June 2006 THE GUILD OF ARCHITECTURAL IRONMONGERS Code of Practice: Hardware for Fire and Escape Doors Issue No.2 June 2006 THE GUILD OF ARCHITECTURAL IRONMONGERS Index Page Foreword 1 Section 1...Introduction 1.0 General 3 1.1 Scope 3 1.2 Terminology

More information

Passive Fire Protection Guidance. Niall Rowan Technical Officer Association for Specialist Fire Protection

Passive Fire Protection Guidance. Niall Rowan Technical Officer Association for Specialist Fire Protection Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking

More information

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT SPORTS CENTRE FIRE RISK ASSESSMENT SPORTS CENTRE BUILDING SUMMARY The building is used as a Sports Centre and contains a large sports hall with changing rooms, an office for staff and a fitness area. 1. Identification

More information

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection

Passive Fire Protection Guidance for the Fire Risk Assessor. Niall Rowan Technical Officer Association for Specialist Fire Protection Passive Fire Protection Guidance for the Fire Risk Assessor Niall Rowan Technical Officer Association for Specialist Fire Protection ASFP has just completed a guide on what to look for when undertaking

More information

Introduction of MSBC Secure India Pvt Ltd. Manufacturer & Installer of Fire Resistance Timber Doorsets

Introduction of MSBC Secure India Pvt Ltd. Manufacturer & Installer of Fire Resistance Timber Doorsets Introduction of MSBC Secure India Pvt Ltd Manufacturer & Installer of Fire Resistance Timber Doorsets Introduction MSBC Secure India Pvt Ltd MSBC Secure is a pioneer in the Door industry having vast knowledge

More information

Loss Prevention Standards

Loss Prevention Standards Introduction Fire compartmentation is an essential part of an effective fire safety design of a building. The primary objective of fire compartmentation or passive fire protection is to prevent a building

More information

About the Instructor & Presenter:

About the Instructor & Presenter: About the Instructor & Presenter: Paul G. Baillargeon, AHC, FDAI Vice President, Technical Consulting Door Security & Safety Foundation A noted veteran in the door and hardware industry, Mr. Baillargeon

More information

Best practice guide. Door coordinator devices to BS EN in association with. Association of Building Hardware Manufacturers

Best practice guide. Door coordinator devices to BS EN in association with. Association of Building Hardware Manufacturers CI/SfB (32) Xt7 June 2003 Association of Building Hardware Manufacturers Best practice guide Door coordinator devices to BS EN 1158 in association with BRITISH HARDWARE FEDERATION Extracts from BS EN 1158:

More information

Loss Prevention Standard

Loss Prevention Standard Loss Prevention Standard LPS 1056: Issue 6.2 Requirements for the LPCB approval and listing of fire doorsets, lift landing doors and shutters This Loss Prevention Standard is the property of BRE Global

More information

London Borough of Hammersmith & Fulham

London Borough of Hammersmith & Fulham Assessment Details: Property Assessed Flora Gardens 186-197, FLORA GARDENS, LONDON Assessment Date 19/12/2017 Assessment Valid Until 04/12/2020 Assessor Details Mark Richards LBHF Fire Risk Assessor QA

More information

CEN/TC 33 - Doors, windows, shutters, building hardware and curtain walling. EN 107:1980 Methods of testing windows - Mechanical test 89/106/EEC

CEN/TC 33 - Doors, windows, shutters, building hardware and curtain walling. EN 107:1980 Methods of testing windows - Mechanical test 89/106/EEC C/TC 33 - Doors, windows, shutters, building hardware and curtain walling Standard reference Title Directive 107:1980 Methods of testing windows - Mechanical test 129:1984 130:1984 179:2008 477:1995 478:1995

More information

FIRE DOOR SAFETY. Important information for leaseholders about fire doors in your property. September 2017 Version 1

FIRE DOOR SAFETY. Important information for leaseholders about fire doors in your property. September 2017 Version 1 FIRE DOOR SAFETY Important information for leaseholders about fire doors in your property. September 2017 Version 1 It s important that everybody knows their role in keeping themselves and others safe

More information

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Mandatory Fire Safety Instruction UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES Principal Contractor fire safety considerations in shared occupancy project or refurbishments

More information

Fire doors are a lifeline. When properly fitted and properly cared for they give vital minutes for people to safely escape from fire and smoke.

Fire doors are a lifeline. When properly fitted and properly cared for they give vital minutes for people to safely escape from fire and smoke. Fire Doors: A Guide About This Guide Fire doors are a lifeline. When properly fitted and properly cared for they give vital minutes for people to safely escape from fire and smoke. It s critical then that

More information

Paper presented at the International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, Japan, April 6 7, 2003

Paper presented at the International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, Japan, April 6 7, 2003 Paper presented at the International Symposium on Protection of Cultural Heritage Buildings from Fire, Kyoto, Japan, April 6 7, 2003 UPGRADING THE FIRE RESISTANCE OF FLOORS AND DOORS IN HERITAGE BUILDINGS

More information

The Association for Specialist Fire Protection

The Association for Specialist Fire Protection The Association for Specialist Fire Protection Door hardware Maintenance and replacement Jacky Sinclair Technical Consultant Guild of Architectural Ironmongers Pioneering fire protection through innovation

More information

THE HOME OF REACTIVE PROTECTION SYSTEMS

THE HOME OF REACTIVE PROTECTION SYSTEMS THE HOME OF REACTIVE PROTECTION SYSTEMS CONTENTS Page Introduction 1 Role of air transfer grilles 1 Definitions and functions 1 Fire performance requirements 2 Varieties of air transfer grilles 3 Recommended

More information

Fire Risk Assessment 2017

Fire Risk Assessment 2017 Fire Risk Assessment 2017 Westmorland House Windermere School Author Paul Brownless Date 11 April 2017 Revised Revised by 04/12/2017 Richard Hennah Reference FRA_WSWH_11042017 1 AUTHOR CLIENT Paul Brownless

More information

BWF-Certifire Fire Doors and Doorsets. Best Practice Guide

BWF-Certifire Fire Doors and Doorsets. Best Practice Guide BWF-Certifire Fire Doors and Doorsets Best Practice Guide 1 BWF-Certifire BWF-Certifire: The leading authority on fire door safety A fire door is a vital safety device engineered to save lives and property.

More information

Hands On Training for Fire Door Products and Fire Door Assemblies

Hands On Training for Fire Door Products and Fire Door Assemblies 2017 NFPA Conference & Expo Hands On Training for Fire Door Products and Fire Door Assemblies Presented by: Paul M. Goldense, FDAI Goldense Building Products, Inc. Jeffery S. Batick, FDAI Allegion Why

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK ISO/IEC 17065:2012 to provide product conformity 20 Park Street Princes Risborough Buckinghamshire HP27 9AH Contact: Ian Woodhouse Tel: +44

More information

A GUIDE FOR SELECTING FLAT ENTRANCE DOORSETS. A publication for housing associations, landlords, building owners and local authorities in England

A GUIDE FOR SELECTING FLAT ENTRANCE DOORSETS. A publication for housing associations, landlords, building owners and local authorities in England A GUIDE FOR SELECTING FLAT ENTRANCE DOORSETS A publication for housing associations, landlords, building owners and local authorities in England www.dfhonline.org.uk www.securedbydesign.com www.fia.uk.com

More information

IS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0)

IS-ORANGE Envirograf. Orange Book. Ventilation. T +44 (0) F +44 (0) IS-ORANGE-01-15 Orange Book Ventilation Envirograf Innovators - Developers - Manufacturers Passive Fire Prevention Products T +44 (0) 1304 842 555 F +44 (0) 1304 842 666 sales@envirograf.com www.envirograf.com

More information

Code of Practice: Hardware for Fire and Escape Doors

Code of Practice: Hardware for Fire and Escape Doors Code of Practice: Hardware for Fire and Escape Doors Issue No.3 July 2009 This page is intentionally left blank Index Section 1 Section 2 Section 3 Section 4 Page Foreword 1 Introduction 1.0 General 3

More information

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /) Fire resistance (A copy of this is available on www.routledge.com/books/details/ 9780415809696/).1 Fire resistance The overall aim of fire safety precautions is to ensure that: all corridor doors shall

More information

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31.

Title: The Air Leakage Performance of Timber Doorsets fitted with NOR710 Smoke Seals in Accordance with BS 476: Part 31, Section 31. Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The Air Leakage Performance of

More information

Fire and Smoke Door Inspections Qualified Training 02/03/17

Fire and Smoke Door Inspections Qualified Training 02/03/17 Fire and Smoke Door Inspections Qualified Training 02/03/17 Basis of Requirements NFPA 101 requires annual fire and smoke door inspections (Section 18/19.2.2.2.1) Sections 18/19.2.2.1 require compliance

More information

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring.

1970s building housing main school reception and support offices. Well managed buildings with no significant risk of a fire occurring. Record of significant findings Risk assessment for : Assessment undertaken by : 71a The Close Nigel Billing CMIOSH Date: 21/3/17 Overview of Premises: 1970s building housing main school reception and support

More information

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY

FIRE RISK ASSESSMENT NOT KNOWN 15/10/ SOMERTON COURT BROADMOSS DRIVE SIMON ROFFEY UPRN Date of inspection Address 1 (flat numbers) Address 2 (street) Address 3 (area) Fire Risk Assessor Checked by Approved by Postcode Does the building have common areas? Was access available to the

More information

Design of Fire safety in Multi Occupancy Residential Accommodation

Design of Fire safety in Multi Occupancy Residential Accommodation Design of Fire safety in Multi Occupancy Residential Accommodation Myth vs Reality Myth. Fire is bright Reality. It isn t. Flames are bright Outside fires have bright flames because of the availability

More information

Developing a Healthcare Facility Fire Door Inspection Program

Developing a Healthcare Facility Fire Door Inspection Program Developing a Healthcare Facility Fire Door Inspection Program WELCOME Moderator: Richard Schieferdecker support.webinato.com Audio QUESTIONS How To Ask a Question: 1 POLLING There will be occasional interactive

More information

Product. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals

Product. Regulations. Agrément Certificate No 92/2841 Third issue* Designated by Government to issue European Technical Approvals Lorient Polyproducts Ltd Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 e-mail: admin@lorientuk.com website: www.lorientgroup.com CI/SfB (32.5)

More information

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications Smoke shafts - an overview Scope of this guide Smoke shaft is the common term for

More information

Best practice guide. Electrically powered hold-open devices to BS EN in association with. Association of Building Hardware Manufacturers

Best practice guide. Electrically powered hold-open devices to BS EN in association with. Association of Building Hardware Manufacturers CI/SfB (32) Xt7 June 2003 Association of Building Hardware Manufacturers Best practice guide Electrically powered hold-open devices to BS EN 1155 in association with BRITISH HARDWARE FEDERATION Extracts

More information

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK Exova (UK) Limited trading as Warrington Certification Issue No: 033 Issue date: 06 November 2017 to provide product conformity Holmesfield

More information

The Association for Specialist Fire Protection

The Association for Specialist Fire Protection The Association for Specialist Fire Protection The Role of Fire Doors, Frames and Fire Seals, Door Hardware Maintenance and Replacement John Fletcher Technical Consultant British Woodworking Federation

More information

Agrément Certificate 92/2841 website: Product Sheet 1

Agrément Certificate   92/2841 website:   Product Sheet 1 Lorient Polyproducts Ltd Endeavour House Fairfax Road Heathfield Industrial Estate Newton Abbot Devon TQ12 6UD Tel: 01626 834252 Fax: 01626 833166 Page 1 of 1 Agrément Certificate e-mail: mktg@lorientuk.com

More information

Following a near miss (after a fire or where evidence suggests that a fire could have occurred).

Following a near miss (after a fire or where evidence suggests that a fire could have occurred). Contents: This is your Fire Risk Assessment Revision of this risk assessment Scope of assessment and methodology Executive Summary Risk Rating Assessment Overview The Responsible Person/Duty Holder Persons

More information

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted

Fire Risk Assessment. ABC Car Workshop. Prepared for. Redacted Fire Risk Assessment Prepared for ABC Car Workshop Assessor: (Assessor s Name) Date of Assessment: 24/07/17 Date of Next Assessment Review: Upon occupation Introduction and Scope This Fire Risk Assessment

More information

Meeting the requirements of the Equality Act & Fire regulations. Which Door Control?

Meeting the requirements of the Equality Act & Fire regulations. Which Door Control? Meeting the requirements of the Equality Act & Fire regulations Which Door Control? Introduction There are two main considerations in specifying door controls: Does it meet the requirements of the Equality

More information

Fire Protection. Fire-resistant glasses. Pilkington Pyrostop. Pilkington Pyrodur

Fire Protection. Fire-resistant glasses. Pilkington Pyrostop. Pilkington Pyrodur Fire Protection Fire-resistant glasses Pilkington Pyrostop Pilkington Pyrodur Protection and Fire Safety Save lives Limit fire damage to property and valuables Protect the building s structure Provide

More information

Fire Risk Assessment 2016

Fire Risk Assessment 2016 Fire Risk Assessment 2016 Elleray Campus Windermere School Author Paul Brownless Date 07 December 2016 Reviewed Reviewer 20 November 2017 Richard Hennah Reference FRA_EC_07122016 1 AUTHOR CLIENT Paul Brownless

More information

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points.

Well managed building mean risk is normal. Fire action notices should be displayed by all alarm break glass call points. Record of significant findings Risk assessment for : Assessment undertaken by : Horsefair House Nigel Billing CMIOSH Date: 28/3/17 Overview of Premises: 2 buildings on 3 stories in an L shaped configuration,

More information

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006)

MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) MAINTENANCE OF ESSENTIAL SAFETY MEASURES EXPLAINED (Building Regulations 2006) 1. INTRODUCTION 1.1 Essential Safety Measures Defined Essential Safety Measures (previously called essential services) are

More information

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

First Aspen Federal Regulation Set: K LSC 2000 Health Existing First Aspen Federal Regulation Set: K 01.01 LSC 2000 Health Existing K 0000 Title CFR Type INITIAL COMMENTS Memo K 0011 If the building has a common wall with a nonconforming building, the common wall

More information

Dear Customer. Section Old F8 February 2014 Amendments to F8. Replace with new title page and document history pages 1 2B

Dear Customer. Section Old F8 February 2014 Amendments to F8. Replace with new title page and document history pages 1 2B Dear Customer Please find enclosed Amendment 3, effective 14 February 2014, to the Acceptable Solution and Verification Method for Clause F8 Signs of the New Zealand Building Code. THe previous amendment

More information

Best Practice BS 3621: 2007 BS 8621: 2007 BS 10621: 2007 dhf

Best Practice BS 3621: 2007 BS 8621: 2007 BS 10621: 2007 dhf Thief Resistant Lock Assemblies Thief resistant lock assemblies - Key egress BS 3621: 2007 Thief resistant lock assemblies - Keyless egress BS 8621: 2007 Thief resistant dual mode lock assemblies BS 10621:

More information

Guidance Note FIA Application Guidance on BS :2015

Guidance Note FIA Application Guidance on BS :2015 Guidance Note FIA Application Guidance on BS 7273-4:2015 FIA Application Guidance on BS 7273-4:2015 1. INTRODUCTION... 3 2. OVERVIEW... 3 2.1. WHAT IS A DOOR RELEASE MECHANISM?...3 2.2. WHY INSTALL DOOR

More information

Independent Living Scheme Fire Risk Assessment. General needs residential sleeping accommodation

Independent Living Scheme Fire Risk Assessment. General needs residential sleeping accommodation Sutton House 1 Forster Street Radford ttingham NG67 3DQ At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire

More information

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to

best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to best practice guide Pedestrian doorsets Fire resisting and/or smoke control characteristics - to BS EN 16034: 2014 Permission to reproduce extracts from BS EN 16034 : 2014 is granted by BSI. DHF BEST PRACTICE

More information

Dear Customer. Please find attached the January 2017 amendments to C/AS3 Acceptable Solution for Buildings. Innovation and Employment.

Dear Customer. Please find attached the January 2017 amendments to C/AS3 Acceptable Solution for Buildings. Innovation and Employment. Dear Customer Please find attached the January 2017 amendments to C/AS3 Acceptable Solution for Buildings Where Care or Detention is Provided (Risk Group SI), published by the Ministry of Business, Innovation

More information

Controlled Door Closing Devices

Controlled Door Closing Devices Controlled Door Closing Devices to BS EN 1154: 1997 + A1:2003 www.dhfonline.org.uk 01 dhf Best Practice dhf Best Practice : Controlled Door Closing Devices to BS EN 1154: 1997 + A1:2003 dhf Best Practice

More information

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT

AFEC FIRE ENGINEERING TEMPLATE FOR CLIENTS INTERNALLY COMPLETED RISK ASSESMENT AFEC FIRE & RISK ENGINEERING SPECIALISTS would like to share an in house Risk Assessment Template we have developed for in house use to assist Facilities Managers and Environmental Health and Safety Staff

More information

Updated to. include Declaration of Performance Certificates WHICH DOOR CONTROL? Meeting the requirements of the Equality Act & Fire regulations

Updated to. include Declaration of Performance Certificates WHICH DOOR CONTROL? Meeting the requirements of the Equality Act & Fire regulations Updated to include Declaration of Performance Certificates WHICH DOOR CONTROL? Meeting the requirements of the Equality Act & Fire regulations WHICH DORMA DOOR CONTROL? INTRODUCTION There are two main

More information

Cylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55. Follower (mm) 8 Latch Bolt

Cylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55. Follower (mm) 8 Latch Bolt Product ID: KL.1902 Name: Cylinder Mortice Dead lock Lockcase(mm) A=87 Backset (mm) B=55 Centres C=N/A Follower (mm) 8 Latch Bolt N/A Mechanism Euro- Profile Forend Finish SSS Rebates available (mm) KL.1902A

More information

Independent Living Scheme Fire Risk Assessment. Independent Living Sheltered residential accommodation

Independent Living Scheme Fire Risk Assessment. Independent Living Sheltered residential accommodation Keverne Close Wendover Drive Aspley ttingham NG8 5EF At ttingham City Homes we want our residents to be assured that their homes are safe. We willingly accept our duty to comply with our statutory fire

More information

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper

TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Damper September 2010 TransShield ACS TransShield ACS Fully Automated Intumescent Fire and Sliding Plate Smoke Features and Design Guide Slimline non-vision intumescent fire and smoke damper with unique sliding

More information

Welcome to the. Firestop Seminar. Hilti Technical and Engineering Support

Welcome to the. Firestop Seminar.  Hilti Technical and Engineering Support Welcome to the Firestop Seminar www.hilti.co.uk/technical Hilti Technical and Engineering Support 1 Agenda 1. Passive Fire Protection a) The Importance of Firestop b) What are the Regulations c) Test Criteria

More information

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL

STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL 14SH200001022 STEEL DUCT - FIRE RATED CLADDING INSTALLATION MANUAL DUCTLINER GS - VENTILATION, SMOKE OUTLET AND KITCHEN EXTRACT DUCT SYSTEMS Tested under BS 476: Part 24: 1987 Fire tests building materials

More information

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT

REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT OVERALL COLOUR ACTION CODE RISK AMBER STATUTORY INSTRUMENT 2005:1541 REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT Address of Premises: Thuurock CCG, Civic Offices New Road Grays Responsible

More information

High Security Locking. Product Catalogue

High Security Locking. Product Catalogue High Security Locking Product Catalogue An ASSA ABLOY Group company 2 Adams Rite Europe Limited About the company Adams Rite was formed in 1946 in Los Angeles, California and over the years we have created

More information

SELF PRESERVATION SOCIETY By Jim Creak

SELF PRESERVATION SOCIETY By Jim Creak SELF PRESERVATION SOCIETY By Editor of the Means of Escape Magazine and Chairman of The Health & Safety Signs Association. w w w. m e a n s - of- e s c a p e. c o m Agenda Regulatory Reform Fire Safety

More information

Fire Risk Assessment Guide

Fire Risk Assessment Guide Fire Risk Assessment Guide Thank you for your interest in the Fire Risk Assessment for your block. All of our blocks have had a recent Fire Risk Assessment in line with regulatory requirements and we are

More information

fire risk assessment For use by landlords of small premises Premises Address

fire risk assessment For use by landlords of small premises Premises Address fire risk assessment For use by landlords of small premises Premises Address FIRE RISK ASSESSMENT for use by landlords of small premises Person having control of the premises: Name of landlord (if different):

More information