PHILADELPHIA REGIONAL PORT AUTHORITY VOLUME 2 SPECIFICATIONS FOR VEHICLE PROCESSING FACILITY NAVAL BUSINESS CENTER PHILADELPHIA PA.

Size: px
Start display at page:

Download "PHILADELPHIA REGIONAL PORT AUTHORITY VOLUME 2 SPECIFICATIONS FOR VEHICLE PROCESSING FACILITY NAVAL BUSINESS CENTER PHILADELPHIA PA."

Transcription

1 PHILADELPHIA REGIONAL PORT AUTHORITY VOLUME 2 SPECIFICATIONS FOR VEHICLE PROCESSING FACILITY NAVAL BUSINESS CENTER PHILADELPHIA PA Prepared By STV Incorporated 205 West Welsh Drive Douglassville, PA STV Project No FINAL BRIDGING DOCUMENT SUBMISSION February 23, 2018

2

3 TABLE OF CONTENTS VOLUME 1 Section Title Bid Form for Vehicle Processing Facility DIVISION 01 GENERAL REQUIREMENTS Summary Statement of Work B Alternates Submittal Procedures Design after Award Environmental Procedures Quality Requirements Temporary Facilities and Controls Product Requirements Execution Construction Waste Management and Disposal Closeout Procedures DIVISION 03 CONCRETE B Cast-In-Place Concrete DIVISION 05 METALS Structural Steel Framing Steel Decking Pipe and Tube Railings DIVISION 06 WOOD, PLASTICS, AND COMPOSITES Rough Carpentry Plastic-Laminate-Clad Architectural Cabinets Plastic Paneling DIVISION 07 THERMAL AND MOISTURE PROTECTION Thermal Insulation Firestopping Joint Sealants Interior Expansion Joint Cover Assemblies DIVISION 08 OPENINGS Metal Doors and Frames Aluminum-Framed Storefronts TABLE OF CONTENTS TOC - i

4 TABLE OF CONTENTS Continued Section Title DIVISION 08 OPENINGS Continued Translucent Panel Assemblies Door Hardware Glazing Fixed Louvers DIVISION 09 FINISHES Gypsum Board Ceramic Tile Acoustical Tile Ceilings Resilient Base and Accessories Resilient Tile Flooring Tile Carpet Painting DIVISION 10 SPECIALTIES Toilet Compartments Wall and Door Protection Toilet and Bath Accessories Fire Protection Specialties Metal Lockers DIVISION 11 EQUIPMENT Loading Dock Seals and Shelters Stationary Loading Dock Equipment DIVISION 12 FURNISHINGS Solid Surfacing Countertops DIVISION 13 SPECIAL CONSTRUCTION B Metal Building Systems DIVISION 21 FIRE SUPPRESSION Sleeves and Sleeve Seals for Fire-Suppression Piping Escutcheons for Fire-Suppression Piping General-Duty Valves for Fire Protection Piping Hangers and Supports for Fire Suppression Piping and Equipment TABLE OF CONTENTS TOC - ii

5 TABLE OF CONTENTS Continued Section Title DIVISION 21 FIRE SUPPRESSION Continued Vibration Controls for Fire-Suppression Piping and Equipment Identification for Fire-Suppression Piping and Equipment Facility Fire-Suppression Water-Service Piping Fire Department Connections Wet-Pipe Sprinkler Systems Electric-Drive, Centrifugal Fire Pumps Pressure-Maintenance Pumps DIVISION 22 PLUMBING Common Motor Requirements for Plumbing Equipment Expansion Fittings and Loops for Plumbing Piping Sleeves and Sleeve Seals for Plumbing Piping Escutcheons for Plumbing Piping Meters and Gages for Plumbing Piping Ball Valves for Plumbing Piping Check Valves for Plumbing Piping Gate Valves for Plumbing Piping Hangers and Supports for Plumbing Piping and Equipment Vibration Controls for Plumbing Piping and Equipment Identification for Plumbing Piping and Equipment Plumbing Piping Insulation Domestic Water Piping Domestic Water Piping Specialties Domestic-Water Pumps Natural Gas Pressure Boosters Sanitary Waste and Vent Piping Sanitary Waste Piping Specialties Sanitary Drains Sump Pumps General-Service Compressed-Air Piping General-Service Packaged Air Compressors and Receivers Electric, Domestic-Water Heaters Fuel-Fired, Domestic-Water Heaters Commercial Water Closets Commercial Urinals Commercial Lavatories Commercial Sinks Emergency Plumbing Fixtures Pressure Water Coolers TABLE OF CONTENTS TOC - iii

6 TABLE OF CONTENTS Continued Section Title DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) Common Motor Requirements for HVAC Equipment Sleeves and Sleeve Seals for HVAC Piping Vibration Controls for HVAC Identification for HVAC Piping and Equipment Testing, Adjusting, and Balancing for HVAC Duct Insulation HVAC Piping Insulation Vehicle Wash Equipment Paint Spray Booth Electric Vehicle Charging Station Tire Changer and Wheel Balancer Asymmetrical Two-Post Lift Compact Vertical Baler Direct Digital Control (DDC) System for HVAC Control Dampers Gas Instruments Temperature Instruments Facility Natural-Gas Piping Facility Aboveground Gasoline Storage Tank and Dispensing System Hydronic Piping Hydronic Piping Specialties Refrigerant Piping Water Treatment for Closed-Loop Hydronic Systems Metal Ducts Air Duct Accessories Flexible Ducts HVAC Power Ventilators Air Curtains Overhead Vehicle Tailpipe Exhaust Removal Systems Air Diffusers Registers and Grilles Condensing Boilers Low-Intensity, Gas-Fired, Radiant Heaters Packaged Compressor and Condenser Units Indoor, Basic Air-Handling Units Heating and Ventilation Units Energy Recovery Unit Dedicated Outdoor-Air Units Split-System Air Conditioners Cabinet Unit Heaters Radiant-Heating Hydronic Piping Prep Environment Booth TABLE OF CONTENTS TOC - iv

7 TABLE OF CONTENTS Continued VOLUME 2 Section Title DIVISION 26 ELECTRICAL B Low-Voltage Electrical Power Conductors and Cables Grounding and Bonding for Electrical Systems Hangers and Supports for Electrical Systems Raceways and Boxes for Electrical Systems Sleeves and Sleeve Seals for Electrical Raceways and Cabling B Identification for Electrical Systems Short Circuit Studies Arc-Flash Hazard Analysis Commissioning of Electrical Systems Lighting Control Devices B Low-Voltage Distribution Transformers Switchboards B Panelboards Wiring Devices Enclosed Switches and Circuit Breakers Manual and Magnetic Motor Controllers Controllers for Fire-Pump Drivers Gaseous Emergency Engine Generators Transfer Switches Lightning Protection for Structures LED Interior Lighting Emergency and Exit Lighting B LED Exterior Lighting DIVISION 27 COMMUNICATIONS Grounding and Bonding Communications Systems Pathways for Communications Systems Cable Trays for Communications Systems Sleeves and Sleeve Seals for Communications Pathways and Cabling Identification for Communications Systems Communications Equipment Room Fittings Communications Racks, Frames, and Enclosures Communications Optical Fiber Backbone Cabling Communications Copper Horizontal Cabling Public Address Systems TABLE OF CONTENTS TOC - v

8 TABLE OF CONTENTS Continued Section Title DIVISION 28 ELECTRONIC SAFETY AND SECURITY Access Control Software and Database Management Access Control Hardware Devices Video Surveillance Addressable Fire-Alarm Systems Attachments Scoring Committee Matrix for Technical Submission Bid Form for Vehicle Processing Facility Note: Sections with Suffix B applies to the Building Portion of the Project. In the Civil Package Specs, Sections with a Suffix C pertaining only to Site Work. TABLE OF CONTENTS TOC - vi I:\Projects\ \ _0001\70_Specifications\0002\Table of Contents.docx

9 SECTION B - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 1.1 SUMMARY A. Section Includes: 1. Copper building wire rated 600 V or less. 2. Metal-clad cable, Type MC, rated 600 V or less. 3. Connectors, splices, and terminations rated 600 V and less. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. B. Product Schedule: Indicate type, use, location, and termination locations. 1.3 INFORMATIONAL SUBMITTALS A. Field quality-control reports. PART 2 - PRODUCTS 2.1 COPPER BUILDING WIRE A. Description: Flexible, insulated and uninsulated, drawn copper current-carrying conductor with an overall insulation layer or jacket, or both, rated 600 V or less. B. Standards: 1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use. 2. RoHS compliant. 3. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide." C. Conductors: Copper, complying with ASTM B 3 for bare annealed copper and with ASTM B 8 for stranded conductors. D. Conductor Insulation: 1. Type THHN and Type THWN-2: Comply with UL Type THW and Type THW-2: Comply with NEMA WC-70/ICEA S and UL Type XHHW-2: Comply with UL 44. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES B - 1

10 2.2 METAL-CLAD CABLE, TYPE MC A. Description: A factory assembly of one or more current-carrying insulated conductors in an overall metallic sheath. B. Standards: 1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use. 2. Comply with UL RoHS compliant. 4. Conductor and Cable Marking: Comply with wire and cable marking according to UL's "Wire and Cable Marking and Application Guide." C. Circuits: 1. Single circuit. 2. Power-Limited Fire-Alarm Circuits: Comply with UL D. Conductors: Copper, complying with ASTM B 3 for bare annealed copper and with ASTM B 8 for stranded conductors. E. Ground Conductor: Insulated. F. Conductor Insulation: 1. Type TFN/THHN/THWN-2: Comply with UL Type XHHW-2: Comply with UL 44. G. Armor: Steel, interlocked. H. Jacket: PVC applied over armor. 2.3 CONNECTORS AND SPLICES A. Description: Factory-fabricated connectors, splices, and lugs of size, ampacity rating, material, type, and class for application and service indicated; listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and use. B. Jacketed Cable Connectors: For steel and aluminum jacketed cables, zinc die-cast with set screws, designed to connect conductors specified in this Section. C. Lugs: One piece, seamless, designed to terminate conductors specified in this Section. 1. Material: Copper. 2. Type: Two hole with standard barrels. 3. Termination: Compression. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES B - 2

11 PART 3 - EXECUTION 3.1 CONDUCTOR MATERIAL APPLICATIONS A. Feeders: Copper; solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger. B. Branch Circuits: Copper. Solid for No. 10 AWG and smaller; stranded for No. 8 AWG and larger. C. Power-Limited Fire Alarm and Control: Solid for No. 12 AWG and smaller. 3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING METHODS A. Service Entrance: Type XHHW-2, single conductors in raceway. B. Exposed Feeders: Type THHN/THWN-2, single conductors in raceway. C. Feeders Concealed in Ceilings, Walls, Partitions, and Crawlspaces: Type THHN/THWN-2, single conductors in raceway. D. Feeders Concealed in Concrete, below Slabs-on-Grade, and Underground: Type XHHW-2, single conductors in raceway. E. Exposed Branch Circuits, Including in Crawlspaces: Type THHN/THWN-2, single conductors in raceway. F. Branch Circuits Concealed in Ceilings, Walls, and Partitions: Type THHN/THWN-2, single conductors in raceway and metal-clad cable, Type MC. G. Branch Circuits Concealed in Concrete, below Slabs-on-Grade, and Underground: Type XHHW- 2, single conductors in raceway. 3.3 INSTALLATION OF CONDUCTORS AND CABLES A. Conceal cables in finished walls, ceilings, and floors unless otherwise indicated. B. Complete raceway installation between conductor and cable termination points according to Section "Raceways and Boxes for Electrical Systems" prior to pulling conductors and cables. C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values. D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway. E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible. LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES B - 3

12 F. Support cables according to Section "Hangers and Supports for Electrical Systems." 3.4 CONNECTIONS A. Tighten electrical connectors and terminals according to manufacturer's published torquetightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A-486B. B. Make splices, terminations, and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors. 1. Use oxide inhibitor in each splice, termination, and tap for aluminum conductors. C. Wiring at Outlets: Install conductor at each outlet, with at least 6 inches of slack. 3.5 IDENTIFICATION A. Identify and color-code conductors and cables according to Section B "Identification for Electrical Systems." B. Identify each spare conductor at each end with identity number and location of other end of conductor, and identify as spare conductor. 3.6 SLEEVE AND SLEEVE-SEAL INSTALLATION FOR ELECTRICAL PENETRATIONS A. Install sleeves and sleeve seals at penetrations of exterior floor and wall assemblies. Comply with requirements in Section "Sleeves and Sleeve Seals for Electrical Raceways and Cabling." 3.7 FIRESTOPPING A. Apply firestopping to electrical penetrations of fire-rated floor and wall assemblies to restore original fire-resistance rating of assembly according to Section "Firestopping." END OF SECTION B LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES B - 4 I:\Projects\ \ _0001\70_Specifications\0002\ B.docx

13 SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section includes grounding and bonding systems and equipment. B. Section includes grounding and bonding systems and equipment, plus the following special applications: 1. Underground distribution grounding. 2. Foundation steel electrodes. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. 1.3 INFORMATIONAL SUBMITTALS A. Coordination Drawings: Plans showing dimensioned as-built locations of grounding features specified in "Field Quality Control" Article. B. Qualification Data: For testing agency and testing agency's field supervisor. C. Field quality-control reports. 1.4 CLOSEOUT SUBMITTALS A. Operation and maintenance data. 1. Plans showing as-built, dimensioned locations of grounding features specified in "Field Quality Control" Article, including the following: a. Test wells. b. Ground rods. c. Ground rings. d. Grounding arrangements and connections for separately derived systems. 2. Instructions for periodic testing and inspection of grounding features at test wells based on NETA MTS. a. Tests shall determine if ground-resistance or impedance values remain within specified maximums, and instructions shall recommend corrective action if values do not. b. Include recommended testing intervals. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

14 1.5 QUALITY ASSURANCE A. Testing Agency Qualifications: Certified by NETA. PART 2 - PRODUCTS 2.1 SYSTEM DESCRIPTION A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. Comply with UL 467 for grounding and bonding materials and equipment. 2.2 CONDUCTORS A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction. B. Bare Copper Conductors: 1. Solid Conductors: ASTM B Stranded Conductors: ASTM B Tinned Conductors: ASTM B Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch in diameter. 5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor. 6. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches wide and 1/16 inch thick. C. Grounding Bus: Predrilled rectangular bars of annealed copper, 1/4 by 4 inches in cross section, with 9/32-inch holes spaced 1-1/8 inches apart. Stand-off insulators for mounting shall comply with UL 891 for use in switchboards, 600 V and shall be Lexan or PVC, impulse tested at 5000 V. 2.3 CONNECTORS A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected. B. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions. C. Bus-Bar Connectors: Compression type, copper or copper alloy, with two wire terminals. D. Beam Clamps: Mechanical type, terminal, ground wire access from four directions, with dual, tin-plated or silicon bronze bolts. E. Cable-to-Cable Connectors: Compression type, copper or copper alloy. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

15 F. Cable Tray Ground Clamp: Mechanical type, zinc-plated malleable iron. G. Conduit Hubs: Mechanical type, terminal with threaded hub. H. Ground Rod Clamps: Mechanical type, copper or copper alloy, terminal with hex head bolt. I. Lay-in Lug Connector: Mechanical type, copper rated for direct burial terminal with set screw. J. Service Post Connectors: Mechanical type, bronze alloy terminal, in short- and long-stud lengths, capable of single and double conductor connections. K. Signal Reference Grid Clamp: Mechanical type, stamped-steel terminal with hex head screw. L. Straps: Solid copper, copper lugs. Rated for 600 A. M. Tower Ground Clamps: Mechanical type, copper or copper alloy, terminal two-piece clamp. N. U-Bolt Clamps: Mechanical type, copper or copper alloy, terminal listed for direct burial. O. Water Pipe Clamps: 1. Mechanical type, two pieces with zinc-plated bolts. a. Material: Die-cast zinc alloy. b. Listed for direct burial. 2. U-bolt type with malleable-iron clamp and copper ground connector rated for direct burial. 2.4 GROUNDING ELECTRODES A. Ground Rods: Copper-clad steel; 3/4 inch by 10 feet. B. Ground Plates: 1/4 inch thick, hot-dip galvanized. PART 3 - EXECUTION 3.1 APPLICATIONS A. Conductors: Install solid conductor for No. 10 AWG and smaller, and stranded conductors for No.8 AWG and larger unless otherwise indicated. B. Underground Grounding Conductors: Install bare tinned-copper conductor, No. 2/0 AWG minimum. 1. Bury at least 24 inches below grade. C. Grounding Bus: Install in electrical equipment rooms, in rooms housing service equipment, and elsewhere as indicated. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

16 1. Install bus horizontally, on insulated spacers 2 inches minimum from wall, 6 inches above finished floor unless otherwise indicated. 2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, and down; connect to horizontal bus. D. Conductor Terminations and Connections: 1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors. 2. Underground Connections: Welded connectors except at test wells and as otherwise indicated. 3. Connections to Ground Rods at Test Wells: Bolted connectors. 4. Connections to Structural Steel: Welded connectors. 3.2 GROUNDING AT THE SERVICE A. Equipment grounding conductors and grounding electrode conductors shall be connected to the ground bus. Install a main bonding jumper between the neutral and ground buses. 3.3 GROUNDING SEPARATELY DERIVED SYSTEMS A. Generator: Install grounding electrode(s) at the generator location. The electrode shall be connected to the equipment grounding conductor and to the frame of the generator. 3.4 GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS A. Comply with IEEE C2 grounding requirements. B. Pad-Mounted Transformers and Switches: Install two ground rods and ground ring around the pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground cable and grounding electrodes. Install tinnedcopper conductor not less than No. 2 AWG for ground ring and for taps to equipment grounding terminals. Bury ground ring not less than 6 inches from the foundation. 3.5 EQUIPMENT GROUNDING A. Install insulated equipment grounding conductors with all feeders and branch circuits. B. Install insulated equipment grounding conductors with the following items, in addition to those required by NFPA 70: 1. Feeders and branch circuits. 2. Lighting circuits. 3. Receptacle circuits. 4. Single-phase motor and appliance branch circuits. 5. Three-phase motor and appliance branch circuits. 6. Flexible raceway runs. 7. Armored and metal-clad cable runs. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

17 8. Busway Supply Circuits: Install insulated equipment grounding conductor from grounding bus in the switchgear, switchboard, or distribution panel to equipment grounding bar terminal on busway. C. Air-Duct Equipment Circuits: Install insulated equipment grounding conductor to duct-mounted electrical devices operating at 120 V and more, including air cleaners, heaters, dampers, humidifiers, and other duct electrical equipment. Bond conductor to each unit and to air duct and connected metallic piping. D. Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate insulated equipment grounding conductor to each electric water heater and heat-tracing cable. Bond conductor to heater units, piping, connected equipment, and components. 3.6 INSTALLATION A. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage. B. Ground Rods: Drive rods until tops are 2 inches below finished floor or final grade unless otherwise indicated. 1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any. C. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit. 1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts. 2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports: Install bonding so vibration is not transmitted to rigidly mounted equipment. 3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp. D. Grounding and Bonding for Piping: 1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes; use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end. 2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector. 3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve. GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS

18 3.7 FIELD QUALITY CONTROL A. Perform tests and inspections. B. Tests and Inspections: 1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements. 2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions. 3. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal, at ground test wells, and at individual ground rods. Make tests at ground rods before any conductors are connected. a. Measure ground resistance no fewer than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance. b. Perform tests by fall-of-potential method according to IEEE Prepare dimensioned Drawings locating each test well, ground rod and ground-rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results. C. Grounding system will be considered defective if it does not pass tests and inspections. D. Prepare test and inspection reports. E. Report measured ground resistances that exceed the following values: 1. Power and Lighting Equipment or System with Capacity of 500 kva and Less: 10 ohms. 2. Power and Lighting Equipment or System with Capacity of 500 to 1000 kva: 5 ohms. 3. Power and Lighting Equipment or System with Capacity More Than 1000 kva: 3 ohms. 4. Switchboards and Pad-Mounted Equipment: 5 ohms. 5. Manhole Grounds: 10 ohms. F. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground resistance. END OF SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS I:\Projects\ \ _0001\70_Specifications\0002\ docx

19 SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Steel slotted support systems. 2. Conduit and cable support devices. 3. Support for conductors in vertical conduit. 4. Structural steel for fabricated supports and restraints. 5. Mounting, anchoring, and attachment components, including powder-actuated fasteners, mechanical expansion anchors, concrete inserts, clamps, through bolts, toggle bolts, and hanger rods. 6. Fabricated metal equipment support assemblies. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: For fabrication and installation details for electrical hangers and support systems. 1. Hangers. Include product data for components. 2. Slotted support systems. 3. Equipment supports. 4. Vibration Isolation Base Details: Detail fabrication including anchorages and attachments to structure and to supported equipment. Include adjustable motor bases, rails, and frames for equipment mounting. C. Delegated-Design Submittal: For hangers and supports for electrical systems. 1. Include design calculations and details of hangers. 2. Include design calculations for seismic restraints. 1.3 INFORMATIONAL SUBMITTALS A. Coordination Drawings: Reflected ceiling plan(s) and other details, drawn to scale, and coordinated with each other, using input from installers of the items involved. B. Seismic Qualification Data: Certificates, for hangers and supports for electrical equipment and systems, accessories, and components, from manufacturer. C. Welding certificates. HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

20 1.4 QUALITY ASSURANCE A. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M. B. Welding Qualifications: Qualify procedures and personnel according to the following: 1. AWS D1.1/D1.1M. PART 2 - PRODUCTS 2.1 PERFORMANCE REQUIREMENTS A. Delegated Design: Engage a qualified professional engineer, as defined in Section "Quality Requirements," to design hanger and support system. B. Surface-Burning Characteristics: Comply with ASTM E 84; testing by a qualified testing agency. Identify products with appropriate markings of applicable testing agency. 1. Flame Rating: Class Self-extinguishing according to ASTM D SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS A. Steel Slotted Support Systems: Preformed steel channels and angles with minimum 13/32-inch diameter holes at a maximum of 8 inches o.c. in at least one surface. 1. Standard: Comply with MFMA-4 factory-fabricated components for field assembly. 2. Material for Channel, Fittings, and Accessories: Galvanized steel. 3. Channel Width: Selected for applicable load criteria. 4. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to MFMA Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA Painted Coatings: Manufacturer's standard painted coating applied according to MFMA Protect finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping. B. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported. C. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for nonarmored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported. Body shall be made of malleable iron. D. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M steel plates, shapes, and bars; black and galvanized. HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

21 E. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their supports to building surfaces include the following: 1. Powder-Actuated Fasteners: Threaded-steel stud, for use in hardened portland cement concrete, steel, or wood, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used. 2. Mechanical-Expansion Anchors: Insert-wedge-type, zinc-coated steel, for use in hardened portland cement concrete, with tension, shear, and pullout capacities appropriate for supported loads and building materials where used. 3. Concrete Inserts: Steel or malleable-iron, slotted support system units are similar to MSS Type 18 units and comply with MFMA-4 or MSS SP Clamps for Attachment to Steel Structural Elements: MSS SP-58 units are suitable for attached structural element. 5. Through Bolts: Structural type, hex head, and high strength. Comply with ASTM A Toggle Bolts: Stainless-steel springhead type. 7. Hanger Rods: Threaded steel. 2.3 FABRICATED METAL EQUIPMENT SUPPORT ASSEMBLIES A. Description: Welded or bolted structural-steel shapes, shop or field fabricated to fit dimensions of supported equipment. PART 3 - EXECUTION 3.1 APPLICATION A. Comply with the following standards for application and installation requirements of hangers and supports, except where requirements on Drawings or in this Section are stricter: 1. NECA NECA NECA NECA NECA 111. B. Comply with requirements in Section "Firestopping" for firestopping materials and installation for penetrations through fire-rated walls, ceilings, and assemblies. C. Comply with requirements for raceways and boxes specified in Section "Raceways and Boxes for Electrical Systems." D. Maximum Support Spacing and Minimum Hanger Rod Size for Raceways: Space supports for EMT, IMC, and RMC as scheduled in NECA 1, where its Table 1 lists maximum spacings that are less than those stated in NFPA 70. Minimum rod size shall be 1/4 inch in diameter. E. Multiple Raceways or Cables: Install trapeze-type supports fabricated with steel slotted support system, sized so capacity can be increased by at least 20 percent in future without exceeding specified design load limits. HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS

22 1. Secure raceways and cables to these supports with two-bolt conduit clamps. F. Spring-steel clamps designed for supporting single conduits without bolts may be used for 1-1/2- inch and smaller raceways serving branch circuits and communication systems above suspended ceilings, and for fastening raceways to trapeze supports. 3.2 SUPPORT INSTALLATION A. Comply with NECA 1 and NECA 101 for installation requirements except as specified in this article. B. Raceway Support Methods: In addition to methods described in NECA 1, EMT, IMC, and RMC may be supported by openings through structure members, according to NFPA 70. C. Strength of Support Assemblies: Where not indicated, select sizes of components so strength will be adequate to carry present and future static loads within specified loading limits. Minimum static design load used for strength determination shall be weight of supported components plus 200 lb. D. Mounting and Anchorage of Surface-Mounted Equipment and Components: Anchor and fasten electrical items and their supports to building structural elements by the following methods unless otherwise indicated by code: 1. To Wood: Fasten with lag screws or through bolts. 2. To New Concrete: Bolt to concrete inserts. 3. To Masonry: Approved toggle-type bolts on hollow masonry units and expansion anchor fasteners on solid masonry units. 4. To Steel: Welded threaded studs complying with AWS D1.1/D1.1M, with lock washers and nuts. 5. To Light Steel: Sheet metal screws. 6. Items Mounted on Hollow Walls and Nonstructural Building Surfaces: Mount cabinets, panelboards, disconnect switches, control enclosures, pull and junction boxes, transformers, and other devices on slotted-channel racks attached to substrate by means that comply with seismic-restraint strength and anchorage requirements. E. Drill holes for expansion anchors in concrete at locations and to depths that avoid the need for reinforcing bars. 3.3 INSTALLATION OF FABRICATED METAL SUPPORTS A. Cut, fit, and place miscellaneous metal supports accurately in location, alignment, and elevation to support and anchor electrical materials and equipment. B. Field Welding: Comply with AWS D1.1/D1.1M. END OF SECTION HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS I:\Projects\ \ _0001\70_Specifications\0002\ docx

23 SECTION RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Metal conduits and fittings. 2. Nonmetallic conduits and fittings. 3. Metal wireways and auxiliary gutters. 4. Nonmetal wireways and auxiliary gutters. 5. Surface raceways. 6. Boxes, enclosures, and cabinets. 7. Handholes and boxes for exterior underground cabling. 1.2 ACTION SUBMITTALS A. Product Data: For each type of product. B. Shop Drawings: For custom enclosures and cabinets. Include plans, elevations, sections, and attachment details. 1.3 INFORMATIONAL SUBMITTALS A. Coordination Drawings: Conduit routing plans, drawn to scale, on which the following items are shown and coordinated with each other, using input from installers of items involved: 1. Structural members in paths of conduit groups with common supports. 2. HVAC and plumbing items and architectural features in paths of conduit groups with common supports. B. Seismic Qualification Data: Certificates, for enclosures, cabinets, and conduit racks and their mounting provisions, including those for internal components, from manufacturer. PART 2 - PRODUCTS 2.1 METAL CONDUITS AND FITTINGS A. Metal Conduit: 1. Listing and Labeling: Metal conduits, tubing, and fittings shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2. GRC: Comply with ANSI C80.1 and UL 6. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

24 3. ARC: Comply with ANSI C80.5 and UL 6A. 4. IMC: Comply with ANSI C80.6 and UL PVC-Coated Steel Conduit: PVC-coated rigid steel conduit. a. Comply with NEMA RN 1. b. Coating Thickness: inch, minimum. 6. EMT: Comply with ANSI C80.3 and UL FMC: Comply with UL 1; zinc-coated steel. 8. LFMC: Flexible steel conduit with PVC jacket and complying with UL 360. B. Metal Fittings: Comply with NEMA FB 1 and UL 514B. 1. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2. Fittings, General: Listed and labeled for type of conduit, location, and use. 3. Conduit Fittings for Hazardous (Classified) Locations: Comply with UL 1203 and NFPA Fittings for EMT: a. Material: Steel. b. Type: Compression. 5. Expansion Fittings: PVC or steel to match conduit type, complying with UL 651, rated for environmental conditions where installed, and including flexible external bonding jumper. 6. Coating for Fittings for PVC-Coated Conduit: Minimum thickness of inch, with overlapping sleeves protecting threaded joints. C. Joint Compound for IMC, GRC, or ARC: Approved, as defined in NFPA 70, by authorities having jurisdiction for use in conduit assemblies, and compounded for use to lubricate and protect threaded conduit joints from corrosion and to enhance their conductivity. 2.2 NONMETALLIC CONDUITS AND FITTINGS A. Listing and Labeling: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 1. ENT: Comply with NEMA TC 13 and UL RNC: Type EPC-40-PVC, complying with NEMA TC 2 and UL 651 unless otherwise indicated. 3. LFNC: Comply with UL B. Nonmetallic Fittings: 1. Fittings, General: Listed and labeled for type of conduit, location, and use. 2. Fittings for ENT and RNC: Comply with NEMA TC 3; match to conduit or tubing type and material. 3. Fittings for LFNC: Comply with UL 514B. 4. Solvents and Adhesives: As recommended by conduit manufacturer. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

25 2.3 METAL WIREWAYS AND AUXILIARY GUTTERS A. Description: Sheet metal, complying with UL 870 and NEMA 250, Type 1 or Type 3R unless otherwise indicated, and sized according to NFPA Metal wireways installed outdoors shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. Fittings and Accessories: Include covers, couplings, offsets, elbows, expansion joints, adapters, hold-down straps, end caps, and other fittings to match and mate with wireways as required for complete system. 2.4 SURFACE RACEWAYS A. Listing and Labeling: Surface raceways and tele-power poles shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. Surface Metal Raceways: Galvanized steel with snap-on covers complying with UL 5. C. Tele-Power Poles: 1. Material: Galvanized steel with ivory baked-enamel finish. 2. Fittings and Accessories: Dividers, end caps, covers, cutouts, wiring harnesses, devices, mounting materials, and other fittings shall match and mate with tele-power pole as required for complete system. 2.5 BOXES, ENCLOSURES, AND CABINETS A. General Requirements for Boxes, Enclosures, and Cabinets: Boxes, enclosures, and cabinets installed in wet locations shall be listed for use in wet locations. B. Sheet Metal Outlet and Device Boxes: Comply with NEMA OS 1 and UL 514A. C. Cast-Metal Outlet and Device Boxes: Comply with NEMA FB 1, ferrous alloy, Type FD, with gasketed cover. D. Nonmetallic Outlet and Device Boxes: Comply with NEMA OS 2 and UL 514C. E. Metal Floor Boxes: 1. Material: Cast metal or sheet metal. 2. Type: Fully adjustable. 3. Shape: Rectangular. 4. Listing and Labeling: Metal floor boxes shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. F. Luminaire Outlet Boxes: Nonadjustable, designed for attachment of luminaire weighing 50 lb. Outlet boxes designed for attachment of luminaires weighing more than 50 lb shall be listed and marked for the maximum allowable weight. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

26 G. Small Sheet Metal Pull and Junction Boxes: NEMA OS 1. H. Cast-Metal Access, Pull, and Junction Boxes: Comply with NEMA FB 1 and UL 1773, galvanized, cast iron with gasketed cover. I. Box extensions used to accommodate new building finishes shall be of same material as recessed box. J. Device Box Dimensions: 4 inches square by 2-1/8 inches deep. K. Gangable boxes are prohibited. L. Hinged-Cover Enclosures: Comply with UL 50 and NEMA 250, Type 1 or Type 3R with continuous-hinge cover with flush latch unless otherwise indicated. 1. Metal Enclosures: Steel, finished inside and out with manufacturer's standard enamel. 2. Interior Panels: Steel; all sides finished with manufacturer's standard enamel. M. Cabinets: 1. NEMA 250, Type 1 or Type 3R galvanized-steel box with removable interior panel and removable front, finished inside and out with manufacturer's standard enamel. 2. Hinged door in front cover with flush latch and concealed hinge. 3. Key latch to match panelboards. 4. Metal barriers to separate wiring of different systems and voltage. 5. Accessory feet where required for freestanding equipment. 6. Nonmetallic cabinets shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. 2.6 HANDHOLES AND BOXES FOR EXTERIOR UNDERGROUND WIRING A. General Requirements for Handholes and Boxes: 1. Boxes and handholes for use in underground systems shall be designed and identified as defined in NFPA 70, for intended location and application. 2. Boxes installed in wet areas shall be listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application. B. Polymer-Concrete Handholes and Boxes with Polymer-Concrete Cover: Molded of sand and aggregate, bound together with polymer resin, and reinforced with steel, fiberglass, or a combination of the two. 1. Standard: Comply with SCTE Configuration: Designed for flush burial with closed bottom unless otherwise indicated. 3. Cover: Weatherproof, secured by tamper-resistant locking devices and having structural load rating consistent with enclosure and handhole location. 4. Cover Finish: Nonskid finish shall have a minimum coefficient of friction of Cover Legend: Molded lettering, "ELECTRIC." 6. Conduit Entrance Provisions: Conduit-terminating fittings shall mate with entering ducts for secure, fixed installation in enclosure wall. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

27 PART 3 - EXECUTION 3.1 RACEWAY APPLICATION A. Outdoors: Apply raceway products as specified below unless otherwise indicated: 1. Exposed Conduit: GRC. 2. Concealed Conduit, Aboveground: GRC or IMC, EMT. 3. Underground Conduit: RNC, Type EPC-40-PVC, concrete encased. 4. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): LFMC. 5. Boxes and Enclosures, Aboveground: NEMA 250, Type 3R. B. Indoors: Apply raceway products as specified below unless otherwise indicated. 1. Exposed, Not Subject to Physical Damage: EMT. 2. Exposed, Not Subject to Severe Physical Damage: EMT. 3. Exposed and Subject to Severe Physical Damage: GRC. Raceway locations include the following: a. Loading dock. b. Corridors used for traffic of mechanized carts, forklifts, and pallet-handling units. c. Mechanical rooms. d. Body Shop Below 12. e. Car Wash Below 12. f. PIO Below Concealed in Ceilings and Interior Walls and Partitions: EMT. 5. Connection to Vibrating Equipment (Including Transformers and Hydraulic, Pneumatic, Electric Solenoid, or Motor-Driven Equipment): FMC, except use LFMC in damp or wet locations. 6. Damp or Wet Locations: GRC. 7. Boxes and Enclosures: NEMA 250, Type 1, except use NEMA 250, Type 3R stainless steel in damp or wet locations. C. Minimum Raceway Size: 3/4-inch trade size. D. Raceway Fittings: Compatible with raceways and suitable for use and location. 1. Rigid and Intermediate Steel Conduit: Use threaded rigid steel conduit fittings unless otherwise indicated. Comply with NEMA FB PVC Externally Coated, Rigid Steel Conduits: Use only fittings listed for use with this type of conduit. Patch and seal all joints, nicks, and scrapes in PVC coating after installing conduits and fittings. Use sealant recommended by fitting manufacturer and apply in thickness and number of coats recommended by manufacturer. 3. EMT: Use compression, steel fittings. Comply with NEMA FB Flexible Conduit: Use only fittings listed for use with flexible conduit. Comply with NEMA FB E. Do not install aluminum conduits, boxes, or fittings in contact with concrete or earth. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

28 F. Install surface raceways only where indicated on Drawings. G. Do not install nonmetallic conduit where ambient temperature exceeds 120 deg F. 3.2 INSTALLATION A. Comply with requirements in Section "Hangers and Supports for Electrical Systems" for hangers and supports. B. Comply with NECA 1 and NECA 101 for installation requirements except where requirements on Drawings or in this article are stricter. Comply with NECA 102 for aluminum conduits. Comply with NFPA 70 limitations for types of raceways allowed in specific occupancies and number of floors. C. Do not install raceways or electrical items on any "explosion-relief" walls or rotating equipment. D. Do not fasten conduits onto the bottom side of a metal deck roof. E. Keep raceways at least 6 inches away from parallel runs of flues and steam or hot-water pipes. Install horizontal raceway runs above water and steam piping. F. Comply with requirements in Section "Hangers and Supports for Electrical Systems" for hangers and supports. G. Arrange stub-ups so curved portions of bends are not visible above finished slab. H. Install no more than the equivalent of three 90-degree bends in any conduit run except for control wiring conduits, for which fewer bends are allowed. Support within 12 inches of changes in direction. I. Make bends in raceway using large-radius preformed ells. Field bending shall be according to NFPA 70 minimum radii requirements. Use only equipment specifically designed for material and size involved. J. Conceal conduit and EMT within finished walls, ceilings, and floors unless otherwise indicated. Install conduits parallel or perpendicular to building lines. K. Support conduit within 12 inches of enclosures to which attached. L. Raceways Embedded in Slabs: 1. Run conduit larger than 1-inch trade size, parallel or at right angles to main reinforcement. Where at right angles to reinforcement, place conduit close to slab support. Secure raceways to reinforcement at maximum 10-foot intervals. 2. Arrange raceways to cross building expansion joints at right angles with expansion fittings. 3. Arrange raceways to keep a minimum of 2 inches of concrete cover in all directions. 4. Do not embed threadless fittings in concrete unless specifically approved by Architect for each specific location. 5. Change to GRC before rising above floor. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

29 M. Stub-ups to Above Recessed Ceilings: 1. Use EMT, IMC, or RMC for raceways. 2. Use a conduit bushing or insulated fitting to terminate stub-ups not terminated in hubs or in an enclosure. N. Threaded Conduit Joints, Exposed to Wet, Damp, Corrosive, or Outdoor Conditions: Apply listed compound to threads of raceway and fittings before making up joints. Follow compound manufacturer's written instructions. O. Coat field-cut threads on PVC-coated raceway with a corrosion-preventing conductive compound prior to assembly. P. Raceway Terminations at Locations Subject to Moisture or Vibration: Use insulating bushings to protect conductors including conductors smaller than No. 4 AWG. Q. Terminate threaded conduits into threaded hubs or with locknuts on inside and outside of boxes or cabinets. Install bushings on conduits up to 1-1/4-inch trade size and insulated throat metal bushings on 1-1/2-inch trade size and larger conduits terminated with locknuts. Install insulated throat metal grounding bushings on service conduits. R. Install pull wires in empty raceways. Use polypropylene or monofilament plastic line with not less than 200-lb tensile strength. Leave at least 12 inches of slack at each end of pull wire. Cap underground raceways designated as spare above grade alongside raceways in use. S. Surface Raceways: 1. Install surface raceway with a minimum 2-inch radius control at bend points. 2. Secure surface raceway with screws or other anchor-type devices at intervals not exceeding 48 inches and with no less than two supports per straight raceway section. Support surface raceway according to manufacturer's written instructions. Tape and glue are not acceptable support methods. T. Install raceway sealing fittings at accessible locations according to NFPA 70 and fill them with listed sealing compound. For concealed raceways, install each fitting in a flush steel box with a blank cover plate having a finish similar to that of adjacent plates or surfaces. U. Install devices to seal raceway interiors at accessible locations. Locate seals so no fittings or boxes are between the seal and the following changes of environments. Seal the interior of all raceways at the following points: 1. Where conduits pass from warm to cold locations, such as boundaries of refrigerated spaces. 2. Where an underground service raceway enters a building or structure. 3. Conduit extending from interior to exterior of building. 4. Conduit extending into pressurized duct and equipment. 5. Conduit extending into pressurized zones that are automatically controlled to maintain different pressure set points. RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017 SECTION 26 0519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES SECTION 260519- LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1- GENERAL 1.1 SUMMARY Section Includes: 1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations

More information

On-Call General Contractor Specifications University of Maryland College Park June 2013

On-Call General Contractor Specifications University of Maryland College Park June 2013 SECTION 260500 - COMMON WORK RESULTS FOR ELECTRICAL PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION ELECTRICAL GENERAL PROVISIONS

SECTION ELECTRICAL GENERAL PROVISIONS PART 1 GENERAL 1.01 SECTION INCLUDES A. General provisions for Electrical Systems B. Wire and cable for 600 volts and less. C. Wiring connectors. D. Electrical tape. E. Heat shrink tubing. F. Wire pulling

More information

A. Product Data: For each type of product.

A. Product Data: For each type of product. SECTION 260519- LOW-VOLT AGE ELECTRICAL POWER CONDUCTORS AND CABLES PART 1- GENERAL 1.1 SUMMARY Section Includes: I. Copper building wire rated 600 V or less. 2. Aluminum building wire rated 600 V or less.

More information

DIVISION 16 ELECTRICAL

DIVISION 16 ELECTRICAL DIVISION 16 ELECTRICAL Saratoga Springs / standards / 02-2004 Page - 0 ELECTRICAL SECTION 16060 GROUNDING AND BONDING PART 1 GENERAL 1.01 SECTION INCLUDES A. Grounding electrodes and conductors, equipment

More information

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW) SECTION 26 05 21 PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, and connection of the low voltage power and lighting wiring. 1.2 RELATED WORK A. Excavation and backfill

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 260500 - BASIC ELECTRICAL MATERIALS AND METHODS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

DOCUMENT TABLE OF CONTENTS

DOCUMENT TABLE OF CONTENTS DOCUMENT 00003 June 16, 2005 TABLE OF CONTENTS DOCUMENT NO. INTRODUCTORY INFORMATION DOCUMENT 00003 TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS SECTION 01011 SECTION 01025 SSP21.1-1 SECTION 01026

More information

Weld County Maintenance Facility Natural Gas Vehicle Ungrades

Weld County Maintenance Facility Natural Gas Vehicle Ungrades DIVISION 26 - ELECTRICAL 260500 COMMON WORK RESULTS FOR ELECTRICAL 260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 260529 HANGERS AND SUPPORTS

More information

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less.

1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated 600 V and less. Copyright 2010 AlA MasterSpec Full Length 09/10 SECTION 260519- LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES PART I-GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wires and cables rated 600

More information

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015

Permit Fairview Municipal Building 55 Anderson Ave. Fairview NJ Issue December 31, 2015 SECTION 26 05 00 - BASIC ELECTRICAL MATERIALS AND METHODS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp.

Springpoint Architects, pc SECTION Childcare Center Architect s Project No TABLE OF CONTENTS Monroe County Comm. Sch. Corp. Volume 1 Bidding Requirements, Contract Forms, Conditions of the Contract, Division 1, Architectural and Site Specifications 000107 Certification Page 000110 Table of Contents DIV00 PROCUREMENT AND CONTRACTING

More information

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods 1. BASIC ELECTRICAL MATERIALS 1. All conduit and raceway must be 3/4" or larger. Exposed raceway in finished areas shall be in 700 or larger wiremold. Exception: runs to individual devices 10 or less,

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION SECTION 237433, PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION SECTION 16055 - OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL a. SUMMARY 1. This Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective

More information

16055 OVERCURRENT PROTECTIVE DEVICE COORDINATION

16055 OVERCURRENT PROTECTIVE DEVICE COORDINATION 16055 OVERCURRENT PROTECTIVE DEVICE COORDINATION PART 1 - GENERAL 1. SUMMARY This Section includes computer-based, fault-current and overcurrent protective device coordination studies. Protective devices

More information

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating.

SECTION DUCTWORK. A. Section Painting: Weld priming, weather resistant, paint or coating. SECTION 15890 DUCTWORK PART 1 - GENERAL 1.1 SECTION INCLUDES A. Metal ductwork. B. Duct cleaning. 1.2 RELATED SECTIONS A. Section 09900 - Painting: Weld priming, weather resistant, paint or coating. B.

More information

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS PART 0 A/E INSTRUCTIONS 0.01 Design Requirements A. Pumping system design 1. A primary-secondary pumping system is preferred. Redundant pipes are required for chillers and boilers. 2. Select pumps to operate

More information

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35

SECTION 2 NEC REFERENCES SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1. CHAPTER 1 GENERAL Introduction...35 SECTION 1 LOW-VOLTAGE AND POWER- LIMITED SYSTEMS...1 Overview of Low-Voltage and Power-Limited Systems...3 Chapter 4 Equipment for General Use...3 Chapter 5 Special Occupancies...3 Chapter 6 Special Equipment...4

More information

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint.

B. Galvanized-Steel-Sheet Sleeves: inch minimum thickness; round tube closed with welded longitudinal joint. (816) 373-4878 U1208-01/FAI29-029 (573) 751-2624 SECTION 2 105 17 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the

More information

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the

More information

Security System Renovation Western Reception Diagnostic and Correctional Center, St. Joseph, MO

Security System Renovation Western Reception Diagnostic and Correctional Center, St. Joseph, MO SECTION 26 0500 - COMMON WORK RESULTS FOR ELECTRICAL, COMMUNICATIONS AND ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.I RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings. DIVISION 21 21 05 00 COMMON WORK RESULTS FOR FIRE SUPPRESSION PART 1 GENERAL 1.1 SECTION INCLUDES A. Pipe, fittings, sleeves, escutcheons, seals, and connections for sprinkler systems. 1.2 RELATED REQUIREMENTS

More information

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR September 2012, rev. 00 26 0553 Identification for Electrical Systems PART 1. GENERAL 1.01 Summary A. Section Includes: 1.02 Submittals 1. Identification for raceways. 2. Identification of power and control

More information

Request for Proposals Steel Passenger Boarding Bridge Lt. Paul Baer Terminal Fort Wayne International Airport

Request for Proposals Steel Passenger Boarding Bridge Lt. Paul Baer Terminal Fort Wayne International Airport Addendum #1 111 W. Berry St. Suite 200 Fort Wayne, IN 46802 P: 260.424.7200 F: 260.424.7301 hochassoc.com November 7, 2014 Request for Proposals Steel Passenger Boarding Bridge Lt. Paul Baer Terminal Fort

More information

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL

APPENDIX - L INTERNATIONAL RESIDENTIAL CODE ELECTRICAL This Appendix (2000 IRC Appendix-L) is produced, copyrighted, and maintained by the National Fire Protection Association Association, all rights reserved. Use of this Appendix is pursuant to license with

More information

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No SECTION 213113 - ELECTRIC-DRIVE, CENTRIFUGAL FIRE PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number: SECTION 233423 - HVAC POWER VENTILATORS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Provisions of the Contract and of the Contract Documents apply to this Section. 1.2 PERFORMANCE REQUIREMENTS A. Operating

More information

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod

A. Connected to the equipment ground B. Bonded to the box C. Connected to nearest water pipe D. Connected to a ground rod Journeyman and Master Common Exam 2 1 The grounding terminal of a grounding-type receptacle installed in a metal box shall be? A. Connected to the equipment ground B. Bonded to the box C. Connected to

More information

PART GENERAL 1.01 SECTION INCLUDES

PART GENERAL 1.01 SECTION INCLUDES Specification Number: 26 24 16.06 Product Name: Emergency Lighting Control NQ Circuit Panelboards: 240 Vac, 48 Vdc Maximum SECTION 26 24 16.06 Emergency Lighting Control NQ Circuit Panelboards: 240 Vac,

More information

DIVISION 16. ElECTRICAl

DIVISION 16. ElECTRICAl DIVISION 16 ElECTRICAl SECTION 16030 ELECTRICAL POWER SYSTEM STUDIES PART 1 -GENERAL 1.01 SUMMARY A. Section Includes: 1. Short circuit study, protective device evaluation study, protective device coordination

More information

Chapter 1 General... 5

Chapter 1 General... 5 About This Textbook...xi About the National Electrical Code...xv About the Authors and Illustrator...xix About the Team...xxi Article 90 Introduction to the National Electrical Code... 1 90.1 Purpose of

More information

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS

SPECIFICATION DELETED SECTION CENTRIFUGAL HVAC FANS SECTION 23 34 16 CENTRIFUGAL HVAC FANS PART 1 - GENERAL 1.01 RELATED DOCUMENT A. Drawings and general provisions of the contract, including General and Special Conditions and Division 01 Specification

More information

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. SECTION 262416 - PANELBOARDS PART 1 - GENERAL 1.1 SUMMARY A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards. 1.2 PERFORMANCE REQUIREMENTS A. Seismic Performance:

More information

SECTION CONDUCTORS AND CABLES

SECTION CONDUCTORS AND CABLES SECTION 260519- CONDUCTORS AND CABLES PART 1 -GENERAL 1.1 SUMMARY This Section includes the following: 1. Building wires and cables rated 600 V and less. 2. Connectors, splices, and terminations rated

More information

occurs and be cause for termination of the contract.

occurs and be cause for termination of the contract. 1.02 SUBMITTALS occurs and be cause for termination of the contract. CITY OF MIAMI CAPITAL IMPROVEMENTS PROGRAM A. Manufacturer s Data: 1. Complete list of materials to be furnished under this section.

More information

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Construction Standards Page Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Construction Standards Page 233423-1 Copyright 2009 by The American Institute of Architects (AIA) Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA Modified

More information

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals. SECTION 23 21 23 - HYDRONIC PUMPS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

SPRINKLERS TABLE OF CONTENTS

SPRINKLERS TABLE OF CONTENTS SPRINKLERS TABLE OF CONTENTS SECTION 21 13 13 WET PIPE SPRINKLER SYSTEMS SECTION 211313 - WET PIPE SPRINKLER SYSTEMS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,

More information

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM SECTION 21 10 00 PART 1 - GENERAL 1.1 CODES A. Work shall conform to NFPA 13 Sprinkler Systems, 2002 Edition and NFPA 24 Outside Protection, 2002 Edition. NFPA 14 Standpipe Systems, 2000 Edition and International

More information

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION SECTION 21 1301- FIRE-SUPPRESSION SYSTEMS PART 1 - GENERAL 1.1 SUMMARY: A. This Section includes fire-suppression piping and equipment for the following building systems: 1. Wet-pipe, fire-suppression

More information

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers. SECTION 22 10 00 PLUMBING PIPING AND PUMPS PART 1 - GENERAL 1.1 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design.

More information

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers.

1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load centers. September 2012, rev. 00 26 2416 Panelboards PART 1. GENERAL 1.01 Summary A. Section includes: 1.02 Definitions 1. Distribution panelboards. 2. Lighting and appliance branch-circuit panelboards. 3. Load

More information

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS SECTION 26 05 53 (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Electrical identification materials and devices required to comply with ANSI C2, NFPA

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified Change Approver Initials 8/1/17 Updated section on Manufacturers 3 1. 6/15/16 Updated division section from 16120 to 26 05 00, - mgl44

More information

REFRIGERANT PIPING

REFRIGERANT PIPING SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 Building Services Piping. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS PART 1 GENERAL 1.01 SECTION INCLUDES A. Pipe and Pipe Fittings. B. Air compressor. C. Air receiver and accessories. D. Aftercooler. E. Refrigerated air dryer. F. Pressure reducing station. 1.02 RELATED

More information

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI Hydraulic Institute Standards. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 28 ELEC. SAFETY & SECURITY SECTION CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY SECTION 280513 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Coaxial cabling. 2. RS-232 cabling. 3. RS-485 cabling. 4. Low-voltage control

More information

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri

ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1. The Curators of the University of Missouri ADDENDUM #3 DATE: August 8, 2018 Page 1 of 1 TO CONTRACT DOCUMENTS ENTITLED: PROJECT MANUAL FOR: Women s and Children s Hospital New Water Service Main PROJECT NUMBER: CP172631 ADVERTISEMENT DATE: July

More information

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No. SECTION 22 63 13 GAS PIPING FOR LABORATORY AND HEALTHCARE FACILITIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION DRY-PIPE SPRINKLER SYSTEMS

SECTION DRY-PIPE SPRINKLER SYSTEMS Ul611-0l SECTION 211316- DRY-PIPE SPRINKLER SYSTEMS PARTl-GENERAL 1.1 RELATED DOCUMENTS Drawings and general provisions of the Contract, including General and Supplementary Conditions, and Division 1 Specification

More information

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN DIVISION 21 - FIRE SUPPRESSION (REFER TO SECTION 23 05 00 FOR BASIC FIRE SUPPRESSION REQUIREMENTS) 21 05 00 Common Work Results for Fire Suppression 21 13 13 Wet-Pipe Sprinkler Systems END OF SECTION FIRE

More information

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS

RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS RESIDENTIAL ELECTRICAL INSPECTIONS CHECKLISTS Key Questions for Residential Inspections 1. What wiring methods will be used, and are the wiring methods suitable for the conditions? 2. Will multiwire branch

More information

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM SECTION 21 0000 AUTOMATIC FIRE SPRINKLER SYSTEM PART 1 GENERAL 1.1 QUALITY ASSURANCE A. Codes and Standards: 1. FBC (Florida Building Code 2015) 2. FBC (Florida Fire Code 2015) 3. NFPA #13R (Standard for

More information

Union County Vocational - Technical Schools Scotch Plains, New Jersey

Union County Vocational - Technical Schools Scotch Plains, New Jersey SECTION 22 40 00 - PLUMBING FIXTURES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Faucets for lavatories, bathtubs, bathtub/showers, showers and sinks. 2. Flushometers. 3. Toilet

More information

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS

Building Division 201 SE 3 rd STREET (Second Floor) OCALA, FL Phone: (352) BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS BUILDING CODE GUIDELINES FOR ELECTRICAL INSPECTIONS Building Code compliance is the obligation of design professionals and/or contractors. Plan Review and Inspection Guidelines are intended to be used

More information

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work. Buchtel/Perkins Community Learning Center GPD -2007271.15 OSFC Project # 55-7110-9029425 Phase 3 CLC Package Bidding Documents July 1, 2010 SECTION 15513 CONDENSING BOILERS PART I- GENERAL 1.1 RELATED

More information

Ratio Architects, Inc. Section Refrigerant Piping

Ratio Architects, Inc. Section Refrigerant Piping SECTION 232300 - REFRIGERANT PIPING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Refrigerant pipes and fittings. 2. Refrigerant piping valves and specialties. 3. Refrigerants. 1.2 ACTION SUBMITTALS

More information

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5

TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION WATER BASED FIRE PROTECTION SYSTEMS... 5 DOC Cremer Heating and Hot Water Plant Project Number: M 1411-04 TABLE OF CONTENTS DIVISION 21- FIRE SUPPRESSION PAGES SECTION 21 30 00- WATER BASED FIRE PROTECTION SYSTEMS... 5 SECTION 22 40 00 -PLUMBING

More information

Section SEALS PAGE DIVISION 16 ~SEALS PAGE ~ 1 PROJECT. Wild Potato Buffet Cherokee Casino Catoosa, OK ENGINEER OF RECORD

Section SEALS PAGE DIVISION 16 ~SEALS PAGE ~ 1 PROJECT. Wild Potato Buffet Cherokee Casino Catoosa, OK ENGINEER OF RECORD SEALS PAGE Section 0001 07 PROJECT Wild Potato Buffet Cherokee Casino Catoosa, OK ENGINEER OF RECORD The following Consultant has provided professional services to the Architect for the referenced project

More information

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This section outlines the requirements for the nitrogen-generating sprinkler corrosion inhibiting system. The work

More information

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components. Page 238126-1 SECTION 238126 - This Section includes requirements for the LEED Rating System. However, equipment specified in this Section may not qualify for LEED Rating System prerequisites and credits.

More information

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties:

MASTERSPEC TECHNICAL SPECIFICATIONS DIVISION 22 PLUMBING. A. This Section includes the following sanitary drainage piping specialties: SECTION 221319 - SANITARY WASTE PIPING SPECIALTIES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following sanitary drainage piping specialties: 1. Backwater valves. 2. Cleanouts. 3. Floor

More information

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19

TABLE OF CONTENTS CHAPTER 2 WIRING AND PROTECTION CHAPTER 1 GENERAL RULES... 19 TABLE OF CONTENTS About This Textbook...xi How to Use the National Electrical Code... 1 Article 90 Introduction to the National Electrical Code... 7 90.1 Purpose of the NEC... 7 90.2 Scope of the NEC...

More information

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS SECTION 22 34 00 (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS System shall provide a complete hot water return throughout the entire system with balancing (flow control) valves not less than 10 feet from

More information

Element D Services Electrical

Element D Services Electrical PART 1 - GENERAL 1.01 OVERVIEW A. This Section includes design standards and requirements for electrical service and distribution. This is a design standard and is not intended to be used as a Specification.

More information

SECTION DOMESTIC WATER PUMPS

SECTION DOMESTIC WATER PUMPS SECTION 22 11 23 DOMESTIC WATER PUMPS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the following all-bronze and bronze-fitted centrifugal pumps for domestic cold- and hot-water circulation: 1. Close-coupled,

More information

Design Standards Manual

Design Standards Manual Design Standards Manual Table of Contents: Part III (Divisions 1-32) Section No. Title Revision DIVISION 1: GENERAL REQUIREMENTS 01524 Construction Waste Management 05/07 01815 HVAC Commissioning Requirements

More information

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements. FIRE PROTECTION GENERAL INFORMATION 1.1 Refer to Section 230000 for General Mechanical Requirements. 1.2 Refer to Section 230529 for Hangers and Supports. 1.3 Refer to Section 230553 for Pipe and Equipment

More information

5. Identification products.

5. Identification products. Essex County College - West Essex Campus Addition And Renovations dib # 54292 / 11-14 [SECTION 260523- CONTROL-VOLTAGE ELECTRICAL POWER CABLES PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems. SECTION 26 0553 PART 1 GENERAL 1.1 SECTION INCLUDES A. Electrical identification requirements. B. Identification nameplates and labels. C. Wire and cable markers. D. Voltage markers. E. Underground warning

More information

SECTION DUCTWORK

SECTION DUCTWORK PART 1 GENERAL 1.1 REFERENCES SECTION 23 31 00 DUCTWORK A. ASHRAE - Handbook, Duct Design B. ASHRAE - Handbook, Duct Construction C. ASTM A90/A90M - Standard Test Method for Weight (Mass) of Coating on

More information

E I Delmar Cobble MINOR ELECTRICAL DEMOLITION

E I Delmar Cobble MINOR ELECTRICAL DEMOLITION PART1 GENERAL 1.01 SECTION INCLUDES A. Electrical demolition. 1.02 RELATED REQUIREMENTS SECTION 26 0501 MINOR ELECTRICAL DEMOLITION A. Section 01 7000- Execution and Closeout Requirements: Additional requirements

More information

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION SPLIT-SYSTEM AIR-CONDITIONERS SECTION 23 81 26 SPLIT-SYSTEM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

More information

SECTION STEAM CONDENSATE PUMPS

SECTION STEAM CONDENSATE PUMPS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 23 22 23 STEAM CONDENSATE PUMPS SPEC WRITER NOTES: 1. Delete between // ---- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University. 15500 - FIRE PROTECTION PART I DESIGN GUIDELINES A. General 1. Vertical fire pumps shall not be used at the University. 2. coupling piping shall be permitted for sprinkler and standpipe systems only. B.

More information

Section Electical General Provision

Section Electical General Provision Section 26 05 00 Electical General Provision 26 05 00-1 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Except as modified in this Section, General Conditions, Supplementary Conditions, applicable provisions

More information

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1. SECTION 236426 - ROTARY-SCREW WATER CHILLERS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, water cooled or air cooled as scheduled, electric-motor-driven, rotary-screw water chillers

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 237413 - PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 - GENERAL 1.1 SUMMARY A. This Section includes packaged, outdoor, central-station air-handling units (rooftop units) with the

More information

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES PART 1 GENERAL A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section. 1.01 SECTION INCLUDES A. Lighting and appliance panelboards 1.02 RELATED SECTIONS A. 16475,

More information

SECTION PLUMBING EQUIPMENT

SECTION PLUMBING EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Water heaters B. Packaged water heating systems C. Water storage tanks D. Water softeners E. Pumps F. Circulators 1.2 REFERENCES SECTION 22 30 00 PLUMBING EQUIPMENT

More information

SECTION FAN COIL UNITS

SECTION FAN COIL UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork. SECTION 15855 AIR HANDLING UNITS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15885 - Air Filtration Equipment. 3. 15890 - Ductwork. 1.02 REFERENCES A. Air Moving

More information

SECTION (15833) - HVAC POWER VENTILATORS

SECTION (15833) - HVAC POWER VENTILATORS PART 1 GENERAL 1.01 SUMMARY SECTION 23 34 23 (15833) - HVAC POWER VENTILATORS A. Section Includes: 1. Centrifugal Roof Ventilators. 2. Up-blast Roof Exhaust Fans (Kitchen Hood Exhaust). 3. Ceiling-Mounted

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 13 13 WET-PIPE SPRINKLER SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories. Page 238219-1 SECTION 238219 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

PROJECT MANUAL FOR THE DESIGN AND INSTALLATION OF EMPLOYEE ALARM SYSTEM LOCATED AT

PROJECT MANUAL FOR THE DESIGN AND INSTALLATION OF EMPLOYEE ALARM SYSTEM LOCATED AT PROJECT MANUAL FOR THE DESIGN AND INSTALLATION OF EMPLOYEE ALARM SYSTEM LOCATED AT ALEXANDRIA RENEW WATER RESOURCE RECOVERY FACILITY 1500 EISENHOWER AVENUE ALEXANDRIA, VIRGINIA 22314 FOR JOHNSON CONTROLS

More information

DIVISION 10 SPECIALTIES

DIVISION 10 SPECIALTIES DIVISION 10 SPECIALTIES 11/11 SECTION 10 21 13.16 PLASTIC LAMINATE TOILET COMPARTMENTS PART 1 - GENERAL 1.01 SECTION INCLUDES Plastic laminate toilet compartments, urinal screens, head rail braced. 1.02

More information

MEDIUM, LOW AND CONTROL VOLTAGE CABLES

MEDIUM, LOW AND CONTROL VOLTAGE CABLES Related Sections U-M Design Guideline Sections: 260800 - Electrical Acceptance Tests Products Medium Voltage Primary Cables Primary power distribution cable shall be single conductor stranded copper, with

More information

SECTION WET-PIPE SPRINKLER SYSTEMS

SECTION WET-PIPE SPRINKLER SYSTEMS SECTION 21 1300 S PART 1 -GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SECTION AIR HANDLING UNIT

SECTION AIR HANDLING UNIT SECTION 15800 - AIR HANDLING UNIT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Basic Requirements: Provisions of Section 15010, BASIC MECHANICAL REQUIREMENTS, and Section 15030, ELECTRICAL REQUIREMENTS FOR

More information

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK

2016 CDM Smith All Rights Reserved July 2016 SECTION FIBER OPTIC DATA NETWORK PART 1 GENERAL 1.01 SCOPE OF WORK SECTION 27 12 23 FIBER OPTIC DATA NETWORK A. Furnish, install, terminate, and test all fiber optic equipment and cabling necessary for a complete and functional data highway

More information